21152 Building 106 Drawings V1.pdf

PDF 13 MB Posted

Attached to
Renovations to Camp Dawson Building 106 Construction
Solicitation number
CRFQ-0603-ADJ2500000040-1
Issued by
Pleasants County, Kermit Town, West Virginia

About this file

These construction documents detail renovations to Building 106 at Camp Dawson, a West Virginia Army National Guard facility located in Kingwood, West Virginia. The project involves comprehensive renovations to a multi-unit billeting facility, with work scheduled to be completed by 05.30.2025. The renovation encompasses extensive upgrades including mechanical, electrical, plumbing, HVAC, and structural improvements across approximately 11,250 square feet of building space. The project will transform the existing building, which currently contains multiple billeting rooms, toilets, chases, mechanical spaces, and a classroom, into a modernized facility.

The project is being managed by ZMM Architects and Engineers, located in Charleston, West Virginia, with the West Virginia Army National Guard Construction and Facilities Maintenance Office serving as the owner. The documents include detailed architectural, mechanical, electrical, and plumbing plans covering demolition, site utilities, structural modifications, equipment replacements, and systems upgrades. Key improvements include installing new HVAC systems with split system units and dedicated outdoor air systems, upgrading electrical infrastructure with new panelboards and distribution systems, replacing plumbing fixtures and water heating systems, and implementing comprehensive fire protection measures. The documents suggest a thorough, systematic approach to modernizing the facility while maintaining its core military billeting function.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

c by ZMM, INC.

S I T E L O C A T I O N M A P

A R C H I T E C T A N D E N G I N E E R

O W N E R

B U I L D I N G I N F O R M A T I O ND R A W I N G I N D E X

U S E A N D O C C U P A N C Y C L A S S I F I C A T I O N

C O N S T R U C T I O N C L A S S I F I C A T I O N

B U I L D I N G A R E A

SHEET NO. SHEET NAME SHEET NO. SHEET NAMESHEET NO. SHEET NAME

PROFESSIONAL SEALS

West Virginia Army National Guard Construction and Facilities

Maintenance Office 1703 Coonskin Drive

Charleston, West Virginia 25311

222 Lee Street, West Charleston, West Virginia 25302

Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

ARCHITECTS

ENGINEERS

5/

/2

:4 3:

A

M C

:\U se rs \ja lle n\

D oc um en ts \2

_B ui ld in g

6_ A_

_j al le nA

FM

U Q

.rv t

05.30.2025

Renovations to

CAMP DAWSON -

BUILDING 106

Kingwood, West Virginia West Virginia Army National Guard

CO

NST

RUC

TIO

N D

OC

UM

ENT

S

Kingwood, West VirginiaPROJECT SITE

EXISTING RESIDENTIAL

TYPE IV : FULLY SPRINKLERED

TOTAL: 10,389 SF

GENERAL

G000 COVER SHEET

CIVIL

C400 SITE UTILITY PLAN

C470 SITE UTILITY DETAILS

C471 SITE UTILITY DETAILS

ARCHITECTURAL

A101 DEMOLITION PLAN

A111 DEMOLITION REFLECTED CEILING PLAN

A121 DEMOLITION ROOF PLAN

A131 FLOOR PLAN

A132 ENLARGED PLANS

A141 REFLECTED CEILING PLAN

A151 ROOF PLAN

A310 BUILDING ELEVATIONS

A311 BUILDING SECTIONS

A410 CASEWORK SECTIONS

A510 DOOR AND WINDOW ELEVATIONS AND SCHEDULES

A511 DETAILS

A512 ALTERNATE #1 DETAILS

FIRE PROTECTION

FP130 FIRE PROTECTION ZONING PLAN

FP131 FIRE PROTECTION PLAN

FP132 FIRE PROTECTION DETAILS AND NOTES

PLUMBING

P111 PLUMBING DEMOLITION PLANS

P131 DOMESTIC WATER AND GAS PLUMBING PLAN

P132 SANITARY SEWER AND STORM PLAN

P510 DETAILS

P511 DETAILS

P520 SCHEDULES, NOTES AND LEGEND

P530 SANITARY SEWER AND VENT RISER DIAGRAM

P531 SANITARY SEWER AND VENT RISER DIAGRAM

MECHANICAL

M000 HVAC SYMBOLS, LEGEND AND GENERAL NOTES

M111 HVAC DEMOLITION PLAN

M131 HVAC PLANS

M132 HVAC PIPING PLAN

M310 HVAC SECTIONS & VIEWS

M510 DETAILS

M520 SCHEDULES

M620 HVAC CONTROL DIAGRAMS

ELECTRICAL

E000 ELECTRICAL GENERAL NOTES AND SYMBOLS

E110 ELECTRICAL DEMOLITION PLAN

E131 LIGHTING PLAN

E151 POWER PLAN

E161 MECHANICAL POWER PLAN

E171 SYSTEMS PLAN

E540 LUMINAIRE FIXTURE SCHEDULE AND DETAILS

E550 PANELBOARD SCHEDULES

E551 PANELBOARD SCHEDULES

E552 PANELBOARD SCHEDULES

E553 PANELBOARD SCHEDULES

E554 PANELBOARD SCHEDULES

E580 ELECTRICAL DETAILS

OPEN-CUT 6"

HOT TAP BY

LOCAL UTILITY

(RENOVATION PROJECT)

CONNECT EXISTING MH

I.E 1242.97 COORD W/

LOCAL UTILITY

(SEE DETAIL)

C.O.

GAS SERVICE

EQUIPMENT

PER LOCAL

UTILITY

SWBD

REM/REPL CONC

TRANSFORMER PAD.

COORD SIZE WITH

EQUIPMENT SELECTIONS.

SEE DETAIL.

CAMP DAWSON BUILDING 106

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

G

AS

G

AS

G

AS

G

AS

W W W W W W W W

W

W

W

W

W

W

W

W

ELE

C.

EL

EC

EL

EC

EL

EC

ELEC.

ELEC.

ELEC.

ELEC.

W

W W

W W

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W W

W W

W W

W

GAS

GAS

GAS

GAS GAS GAS GAS GAS

GAS

GAS

GAS

GAS

GAS

OH

E

OH

E

OH

E

OHE

OHE

O H E

O H E

O H E

O H E

O H E

O H E

O H E

EL

EC

EL

EC

EL

EC

EL

EC

ELEC.

ELEC

ELEC

ELEC

ELEC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

ELEC. ELEC. ELEC. ELEC. ELEC. ELEC. ELEC.

ELEC.

ELEC. ELEC. ELEC. ELEC. ELEC. ELEC. ELEC.

EL

EC

ELE

C.

ELE

C.

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

ELEC.

ELEC.

ELEC.

ELEC.

ELEC.

ELEC. ELEC.

ELEC

ELEC

ELEC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

ELEC.

ELEC.

ELEC.

ELEC.

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

EL

EC

W W

W W

W W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

ELEC

ELEC

ELEC.

ELEC.

ELEC.

FFE = 1249.40

CONTRACTOR SHALL

COORDINATE ALL BUILDING

SERVICE CONNECTIONS WITH

PLUMBING, MECHANICAL,

AND ELECTRICAL PLANS.

SAW CUT

AND

REPLACE

SIDEWALK

(TYP)

OPEN CUT AND REPAIR

TO MATCH EXISTING

PAVEMENT STRUCTURE

SEE DETAIL.

3" P.E. GAS

SERVICE LINE

SEE DETAIL

T/C = 1246.90

MH

3" P.E. GAS

SERVICE LINE

SEE DETAIL

GAS SERVICE TAP

BY LOCAL UTILITY

T.B.

T.B.

ROOF OVERHANG

ROOF OVERHANG

SIDEWALK BELOW

SIDEWALK BELOW

6" SCH 40 PVC

SANITARY SEWER

@ 1.8%

3" DIP POTABLE WATER SERVICE

ROOF OVERHANG

SIDEWALK BELOW

ROOF OVERHANG

SIDEWALK BELOW

FIELD-VERIFY/

AVOID

CONFLICTS

MH

INV. 1244.50

INV. 1244.01

INV. 1243.46

SAW CUT AND

REPLACE SIDEWALK

SEE DETAIL.

EXISTING PAVEMENT

EXISTING PAVEMENT

EXISTING PAVEMENT

EXISTING PAVEMENT

INSTALL (4)

BOLLARDS AS

SHOWN. SEE

DETAIL.

W W W

FIELD-VERIFY EXISTING WATER

SERVICE. REMOVE AND DISPOSE

AS SHOWN.

T.B.3' COMPACTED

CRUSHER-RUN APRON.

TYPICAL ALL PADS

CONC. PAD. COORD SIZE

WITH EQUIPMENT

SELECTIONS

EXISTING PAVEMENT

THIS PAD REQUIRES

SIGNIFICANT GRADE

PREPARATION. 2%

MAXIMUM SLOPE.

GRADE TO DRAIN.

T.B.

REPLACE EXISTING PERIMETER SIDEWALK AROUND THE ENTIRE

PERIMETER OF THE BUILDING, APRROXIMATELY 547 LF. SEE DETAIL.

CONC. PAD. COORD SIZE

WITH EQUIPMENT

SELECTIONS

6" DIP WATER

SERVICE MAIN

(FIRE SERVICE)

SERVICE VALVE.

RIM FLUSH WITH

SIDEWALK.

OPEN-CUT 3"

HOT TAP AND VALVE

BY LOCAL UTILITY

SCREENING/ACCESS

PER SPECIFICATIONS.

TYPICAL ALL PADS.

05.30.2025

21152

C A

M P

D A

W

SO

N

B U

IL

D

IN

G

R en ov at io ns to

Ki ng w oo d, W es t V irg in ia W es t V irg in ia A rm y

N at io na l G ua rd

SITE UTILITY

PLAN

C400

JPM JPM

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

CHECKED

DATE

COMM. NO.

DRAWN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

c by ZMM, LLC

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

GENERAL UTILITY NOTES

1. CONTRACTOR IS RESPONSIBLE FOR LOCATION AND COORDINATION WITH BELOW AND ABOVE

GROUND UTILITIES.

2. CONTRACTOR IS RESPONSIBLE FOR TRENCHING, BACK FILLING, AND CUTTING AND PATCHING

OF PAVEMENT AND WALKS.

3. CONTRACTOR SHALL COORDINATE WORK WITH WVANG PRIOR TO BEGINNING WORK AND

SHALL FURNISH AND INSTALL ADDITIONAL ITEMS FOR TIE IN TO UTILITY LINES REQUIRED BY

WVANG AT NO ADDITIONAL COST TO THE OWNER.

4. LAWN AREAS DISTURBED DURING CONSTRUCTION SHALL BE REGRADED, SEEDED, AND

MULCHED TO ORIGINAL CONDITIONS, UNLESS OTHERWISE NOTED.

5. PAVED AREAS DISTURBED DURING CONSTRUCTION SHALL BE REPAIRED TO ORIGINAL

CONDITION, UNLESS OTHERWISE NOTED.

6. THIS PLAN IS SCHEMATIC IN NATURE AND DOES NOT SHOW EVERY COMPONENT NECESSARY

FOR COMPLETE, WORKMANLIKE CONSTRUCTION.

1. FEATURES SHOWN HAVE BEEN DRAWN FROM GOOGLE EARTH MAPPING, FIELD

MEASUREMENTS AND EXISTING DRAWINGS TITLED "TRAINING FACILITIES - PHASE 1 165

PERSON BARRACKS HEADQUARTERS BUILDING ADDITION" DATED 4/30/1987. NO GUARANTEE

THAT THE UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES IN THE AREA, EITHER IN

SERVICE OR ABANDONED. THE DRAWINGS FURTHER DO NOT WARRANT THAT THE UTILITIES

SHOWN ARE IN THE EXACT LOCATION INDICATED. PRIOR TO ANY EXCAVATION IT IS THE

RESPONSIBILITY OF THE CONTRACTOR TO PHYSICALLY LOCATE THE UNDERGROUND

UTILITIES.

GENERAL NOTES

402001020

SCALE: 1" = 20'-0" FEET

LEGEND

PROPOSED WATER LINE

PROPOSED SANITARY SEWER LINE

PROPOSED GAS LINE

THRUST BLOCKING

SANITARY CLEAN-OUT

EQUIPMENT SCREENING

T.B.

C.O.

AutoCAD SHX Text

DI

05.30.2025

21152

C A

M P

D A

W

SO

N

B U

IL

D

IN

G

R en ov at io ns to

Ki ng w oo d, W es t V irg in ia W es t V irg in ia A rm y

N at io na l G ua rd

SITE UTILITY

DETAILS

C470

BSM JPM

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

CHECKED

DATE

COMM. NO.

DRAWN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

c by ZMM, LLC.

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

SCALE: NOT TO SCALE

C470

SITE TRANSFORMER DETAIL

12" 8' - 0"

NOTES:

1. WHERE POSSIBLE, DO NOT PLACE CONDUIT UNDER THIS SECTION OF FOUNDATION.

2. REINFORCING: #4 BARS 12" C.C. BOTH WAYS.

3. WHEN INSTALLING CONDUIT, DISTURB GROUND IN FOUNDATION AREA AS LITTLE AS

POSSIBLE.

4. TOP OF FOUNDATINON TO BE SMOOTH AND LEVEL. FINAL GRADE SHALL SLOPE AWAY

FROM PAD.

5. CONCRETE SHALL BE 3500 PSI AT 28 DAYS AND 1:2:4 MIXTURE WITH 6 GAL. MAX. WATER

CONTENT PER SACK OF CEMENT.

6. 1-1/4" GALVANIZED RIDGID STEEL CONDUIT UNDER PAD FOR GROUND WIRE.

7. LOCATE CONDUITS UNDER PRIMARY AND SECONDARY BUSHINGS. COORDINATE WITH

TRANSFORMER MANUFACTURER FOR EXACT LOCATION OF BUSHINGS.

8. TRANSFORMER PAD REQUIRES A MINIMUM OF 3'-0" CLEARANCE AROUND EACH SIDE AND

BACK OF PAD. A 15'-0" CLEARANCE IS REQUIRED ON FRONT SIDE OF PAD.

9. TRANSFORMER PAD SHALL EXTEND 4" BEYOND TRANFORMER ENCLOSURE SELECTED.

10. PROVIDE 6" OF COMPACTED CLASS 1 STONE UNDER TRANSFORMER PAD.

SEE NOTE 6

18"

12" 30"

PRIMARY

30"

SECONDARY

18"

SEE NOTE 2

12"

ITEM DESCRIPTION

CONDUIT, PVC SCHEDULE 40

ADAPTER, CONDUIT, GALV. TO PVC (REQUIRED SIZE)

CONDUIT BUSHING (REQUIRED SIZE)

CONDUIT, 90-DEGREE BEND, RGSC (REQUIRED SIZE)

EXOTHERMIC WELD CONNECTION, TYPICAL.

3/4" X 10'-0" COPPER CLAD GROUND ROD IN TEST WELL. SEE DETAILS. TYPICAL OF 2.

CONDUCTOR, COPPER, #4/0 BARE

3/4" X 10'-0" COPPER CLAD GROUND ROD. TYPICAL OF 2.

FINISH GRADE

1 4 2

SEE POWER

RISER DETAIL

1" BEVEL 6

12" MIN.

60"

MIN.

2 3" 3

M

IN

8" 4"

3"

6"

1" 3'

8"

SE

E

N O

TE

VE

R

IF

Y

EX

IS

TI

N

G

IN

F

IE

LD

SEE NOTE 7

SEE NOTE 10

SEE NOTE 3

NOTE:

COORDINATE PAD DIMENSIONS WITH TRANSFORMER TO BE PROVIDED PRIOR

TO ANY CONSTRUCTION.

TYPICAL BOLLARD DETAIL

SCALE: N.T.S.

C470

A

48"

B

24"

PIPE

6"

SIZE

BOLLARD DETAILS

B

SET POST IN

CONCRETE

FINISHED GRADE

CONCRETE CAP

PAINT POST GREY

STEEL PIPE

2" WIDE, WHITE REFLECTIVE

TAPE

PAINT TOP 18" OF POST

SAFETY YELLOW

FILL POST WITH CONCRETE

6"

12"

27"

1"

A

6"

12" 3"

SCALE: NOT TO SCALE

C470

ELECTRICAL DUCT BANK DETAIL

12" WIDE FOIL BACKED

MARKING TAPE

BACKFILL USING SATIFACTORY

MATERIAL IN ACCORDANCE

WITH SPECIFICATIONS

CONCRETE ENCASEMENT FOR

CONDUIT PROTECTION

-3,000 PSI CONCRETE

-6" SLUMP

3"

3"

3"

" M

IN

3" SCH 40 PVC DUCTS, TYP.

12"

CONCRETE SIDEWALK DETAIL1

C470 N.T.S.

VARIES, SEE PLANS

3" TOOL BANDING ON

ALL EDGES

ROUGH BROOM TEXTURE / FINISH

PERPENDICULAR TO TRAFFIC FLOW

TYP. JOINT (CONTRACTOR TO

DELINEATE PER NOTE BELOW)

PLAN

4"

4"

SCORE JOINT

1" DEEP - 14" WIDE

8" RADIUS, TYP.

2" EXPANSION JOINT OR

SAWED SCORE JOINT

8" RADIUS, TYP.

2" EXPANSION JOINT

WITH SELF LEVELING SEALANT

RIGID STRUCTURE

CONCRETE

COMPACTED AGGREGATE

STONE BASE

COMPACTED SUBBASE

GROOVE AND EXPANSION JOINTS (TYPICAL) IN SIDEWALK

NOTES:

1. CONCRETE SHALL BE AIR-ENTRAINED WITH A

COMPRESSIVE STRENGTH OF 4500 PSI IN 28 DAYS.

2. A GROOVE JOINT 1" DEEP WITH 18" RADII SHALL BE

REQUIRED IN THE CONCRETE SIDEWALK AT A

SPACING EQUAL TO THE SIDEWALK WIDTH OR AS

SHOWN ON PLANS.

3. ONE SEALED 12" EXPANSION JOINT WILL BE

REQUIRED AT 20' INTERVALS (NOT TO EXCEED 30')

AND MATCHING EXPANSION / CONSTRUCTION

JOINT IN ADJACENT CURB.

4. A SEALED 12" EXPANSION JOINT WILL BE REQUIRED

WHERE THE SIDEWALK JOINS ANY RIGID

STRUCTURE. SIDEWALK AT DRIVEWAY ENTRANCES

TO BE 6" THICK.

5. MINIMUM WIDTH OF SIDEWALKS SHALL BE 5',

UNLESS OTHERWISE INDICATED.

6. SIDEWALK TO BE POURED TO END TO RADIUS AT

INTERSECTING STREETS.

7. CONCRETE FINISH TO BE ROUGH BROOM TEXTURE

/ FINISH PERPENDICULAR TO TRAFFIC.

8. TYPICAL JOINT LOCATIONS TO BE REFERENCED

PER LAYOUT PLAN, CONTRACTOR RESPONSIBLE

TO CONFORM TO ALL NOTED ITEMS ABOVE.

6X6 W2.9 X W2.9 WWF

OR FIBROUS REINFORCEMENT

NOTE:

COORDINATE WIRING WITH ELECTRICAL PLAN.

4" M

IN.

4" M

IN

" C

O

VE

R

1' -0

D"

12" MIN.

COMPACTED SOIL

BACKFILL

SAND BEDDING

MATERIAL

COMPACTED SUBGRADE

FINISHED GRADE

TRACING WIRE AND WARNING

TAPE 12" BELOW FINISHED

GRADE

PAVEMENT / SHOULDER

MATERIAL

NO SCALE:

C470

GAS LINE TRENCH DETAIL

1-5/8" DIAMETER STANDARD WEIGHT,

SCHEDULE 40, GALVANIZED STEEL PIPE

BOTTOM RAIL.

2" (50.8mm) GALVANIZED MESH, 0.192", (4.88mm) DIA. ZINC-COATED

(GALVANIZED) FABRIC

2-3/8" DIAMETER STANDARD WEIGHT,

SCHEDULE 40, GALVANIZED STEEL PIPE

LINE POST. (CORNER AND END POSTS

TO BE 4" DIAMETER SCHEDULE 40

GALVANIZED.)

1-5/8" DIAMETER STANDARD WEIGHT,

SCHEDULE 40, GALVANIZED STEEL PIPE

TOP RAIL.

POSTS 10' O.C.

MAX SPACING

CONCRETE FOOTING

CHAIN LINK FENCE DETAIL4

C470 NOT TO SCALE

3 - STRAND BARBWIRE (WHERE

INDICATED ON PLANS)

NOTES:

1. SEE SPECIFICATIONS FOR FENCE / GATE INFORMATION.

2. FENCE FABRIC, POSTS, RAILS, AND FITTINGS SHALL HAVE BLACK

VINYL COATING, (WHERE INDICATED ON PLANS).

3'-0"

3"-5" SMOOTH RIVER STONE

6" MIN.

COMPACTED SUBGRADE

SLOPE AWAY FROM BUILDING

FABRIC SEPARATION

CONCRETE WALK

SIDEWALK OFFSET FROM BUILDING DETAIL7

C470

GRAVEL SECTION BETWEEN HVAC PADS

BUILDING

3'-0"

COMPACTED SUBGRADE

CONCRETE WALK

SECTION AT HVAC PAD

BUILDING

4,500 PSI CONCRETE

#5 BARS @ 12" EW

PAD 8" ABOVE GRADE

2" EXPANSION JOINT

WITH SELF LEVELING SEALANT

2" EXPANSION JOINT

WITH SELF LEVELING SEALANT

NOTE:

COORDINATE PAD LOCATIONS AND WIDTH WITH MECHANICAL PLAN.

NOT TO SCALE

FINISHED GRADE

05.30.2025

21152

C A

M P

D A

W

SO

N

B U

IL

D

IN

G

R en ov at io ns to

Ki ng w oo d, W es t V irg in ia W es t V irg in ia A rm y

N at io na l G ua rd

SITE UTILITY

DETAILS

C471

BSM JPM

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

CHECKED

DATE

COMM. NO.

DRAWN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

c by ZMM, LLC.

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

FLEXIBLE GASKET CONNECTOR

10" MINIMUM FROM

MANHOLE JOINT

INFLUENT PIPE (PVC)

10" MINIMUM FROM

MANHOLE JOINT

2" MAX

1" MIN

EXISTING OR NEW PRECAST

CONCRETE MANHOLE

90° BEND IN CONCRETE OR BRICK

BENCH TO CROWN OF PIPE.

1" GROUT BETWEEN PVC PIPE AND

CONCRETE OR BRICK.

I.D. DROP PIPE

SET CHANNEL 2" BELOW CROWN

OF DISCHARGE SEWER PIPE

SLOPE CHANNEL AND PROVIDE SMOOTH

TRANSITION INTO CHANNEL FLOW

BENCH

1-1/2" WIDE, 11 GAUGE STAINLESS STEEL

ADJUSTABLE CLAMPING BRACKETS AT 4" MAX

SPACING (MIN. OF 2 PER PIPE JOINT)

ANCHORED WITH 3 8" S.S. EXPANSION BOLTS

PVC DROP PIPE SECTIONS. THE SAME

DIAMETER AS INFLUENT PIPE

COUPLING

FIBERGLASS DROP BOWL. INSTALL PER

MANUFACTURERS' REQUIREMENTS

CUT A "V" SHAPED NOTCH AT THE BOTTOM

OF INFLUENT PIPE

NOTES:

1. THIS DETAIL MAY BE USED FOR CONNECTIONS TO PRECAST MANHOLES ONLY.

2. ONLY ONE INSIDE DROP CONNECTION PER MANHOLE WILL BE ALLOWED, UNLESS OTHERWISE

INDICATED ON THE DRAWINGS.

3. THE DROP BOWL SHALL NOT EXTEND INTO THE AREA THAT IS DEFINED BY THE PROJECTION

OF THE MANHOLE ENTRANCE VERTICALLY DOWN TO THE MANHOLE BOTTOM. IF NECESSARY,

MANHOLE FRAME, COVER, CONE SECTION AND STEPS SHALL BE REMOVED AND PLACED TO

ALLOW FOR UNOBSTRUCTED ENTRY AND EXIT.

NO SCALE:

7 MANHOLE INSIDE DROP CONNECTION

C471NO SCALE:

C471

CLEANOUT DETAIL

ZURN ZN1400-HD (SEE SPEC FOR

CONCRETE WALK COVER REQUIREMENT)

2'-0"

8"

NOTES:

1. PIPE MUST NOT SUPPORT

INSPECTION FRAME AT ANY POINT.

2. CLEANOUT TO BE SAME SIZE AS

MAIN STORM LINE.

PIPE JOINTS AS REQUIRED

45° BEND

45° "Y" BRANCH OR BEND

D"

APPROVED BACKFILL

MECHANICALLY COMPACTED

IN 12" LIFTS

BEDDING MATERIAL #8 STONE TO

6" ABOVE PIPE

PIPE PER PLANS AND

SPECIFICATIONS

COMPACTED SUBGRADE

12"

MIN.

METALLIC LOCATING TAPE

LAY PIPE WITH PIPE SIZE

MARKINGS VISIBLE AT TOP

OF PIPE

PAVEMENT

FINISHED GRADE

NO SCALE:

C471

SANITARY TRENCH DETAIL

TEE INSTALLATION

CAP

DUC - LUG

8" DIA. ALL THREAD

ROD

FRICTION CLAMPCONC. COLLAR

90° BEND INSTALLATIONEND CAP RESTRAINT

THRUST BLOCK SCHEDULE

S.F. AREA AGAINST UNDISTURBED SOIL 150 PSI @ SOIL BEARING CAPACITY OF

1000 LBS/FT i.e. SOFT CLAY

PIPE SIZE TEE OR

DEAD END 90°45°22 1/2°11 1/4°

2"

6"

8"

12"

1. ALL PIPE AND FITTINGS SHALL BE WRAPPED WITH1. POLYETHYLENE SHEET TO PREVENT CONTACT WITH CONCRETE.

2. USE MECHANICAL JOINT FITTINGS WITH MEGA LUGS AT ALL LOCATIONS REQUIRING THRUST BLOCKING

3. THRUST BLOCKING BEARING SURFACES TO BE PLACED AGAINST UNDISTURBED EARTH (SEE THRUST BLOCK

SCHEDULE FOR SIZES)

NOTES:

11 1/4° - 45° BEND INSTALLATION

RETAINER GLAND TYPICAL

6 2 3 5 9

13 3 6 10 19

23 5 9 18 33

52 10 20 39 71

NO SCALE:

C471

TYPICAL THRUST BLOCK DETAIL

HORIZONTAL SLOT CUT IN VALVE BOX

APPROXIMATLEY 12" BELOW GRADE TO

ACCEPT COATED #12 THNN SOLID COPPER

TRACER WIRE. PULL ENOUGH WIRE

THROUGH SLOT TO ALLOW 4' OF ACCESS

ABOVE GRADE.

RESILIENT WEDGE TYPE GATE VALVE

PER AWWA C-515, UNLESS OTHERWISE

SHOWN ON DRAWINGS.

CONCRETE BEARING PAD TO

BE USED WITH PVC OR PE PIPE

BRICK OR AGGREGATE

FILL AS REQ'D.

ADJUSTABLE CAST IRON

VALVE BOX BASE

ADJUSTABLE

SHAFT

COMPACTED BACKFILL

TYPICAL AROUND

FOR BEDDING MATERIAL SEE

TRENCH BEDDING DETAIL 9

C340

3"

WATER MAIN

1. PROVIDE PLASTIC POST - TYPE VALVE LOCATOR AT EACH VALVE LOCATION.

2. ALL VALVES ON FIRE SERVICE MAINS REQUIRE TAMPER SWITCHES WITH

CONTROL CIRCUIT TO MAIN FIRE CONTROL PANEL.

NOTES:

TYPICAL VALVE BOX INSTALLATION

NO SCALE:

EXISTING OR PROPOSED

FINISHED GRADE C.I. VALVE BOX COVER

" M

IN

O R

A S

AP

PR

O

VE

D B

Y

EN

G

IN

EE

R

ADJUSTABLE

SHAFT

C471

DOMESTIC METER BOX DETAIL

C471

2" WATER METER

AND SETTER BY

CONTRACTOR

FLOW

FROM WATER MAIN

3" 2"

WATER DRUM BY

CONTRACTOR

4" M

IN

METALLIC CAUTION TAPE

PER SPECIFICATIONS

SAND BEDDING

MATERIAL

SAND BEDDING

MATERIAL

COMPACTED SUBGRADE

" M

IN

.1'

-0

COMPACTED BACKFILL

PER SPECIFICATIONS

12"

MIN.

PAVEMENT / SHOULDER

MATERIAL

NO SCALE:

C471

WATER LINE TRENCH DETAIL

NO SCALE:

3"x2" REDUCER

BY CONTRACTOR

3"2"

3"x2" REDUCER

BY CONTRACTOR

AutoCAD SHX Text

FINISHED GRADE

1 1 1 1 1 11 1 1 1 1 1 1 1 1

1 1 1 1

1 1 1 1 1 1 1 1 1 1 1 1 1

111111111111 1

11 11 11 11 1 11 11

2 2 2 2 2 22 2 2 2 2 2 2 2 2

2 2 2 2 2 2 2 2 2 2 2 2 2

99 9 9 9 9 99 9101010 1010101010

11 11 11 11 11 11 11 11 11

11 11 11 11

11 11 11 11 11 11 11 11 11 11 11 1111

15 15 15 15

15 15 15

16161616

15 15

16 16 16 16

17 17 17

1.

2.

3.

4.

5.

6.

ALL DEMOLITION WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL

APPLICABLE LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.

THE DEMOLITION PLANS ARE INTENDED TO REASONABLY REPRESENT EXISTING

CONDITIONS. ACTUAL CONDITIONS MAY DEVIATE FROM THAT SHOWN ON THE

DRAWINGS. THE CONTRACTOR SHALL VISIT THE JOBSITE AND VERIFY ACTUAL

CONDITIONS AND COORDINATE THE DEMOLITION WORK WITH THE NEW WORK SO

THAT DEMOLITION IS COMPLETE. FIELD VERIFY ALL DIMENSIONS SHOWN ON

DRAWINGS PRIOR TO CONSTRUCTION AND NOTIFY ARCHITECT OF ANY

DISCREPANCIES.

PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND SERVICES AND PERFORM ALL

OPERATIONS REQUIRED FOR COMPLETE INTERIOR DEMOLITION AND RELATED

WORK AS DESCRIBED AND SPECIFIED HEREIN, AND AS MAY BE REASONABLY

IMPLIED AS NECESSARY TO COMPLETE NEW CONSTRUCTION WORK.

THE CONTRACTOR SHALL BE AWARE THAT THE BUILDING WILL BE OCCUPIED AND

IN-USE DURING THE LENGTH OF THE CONTRACT. THE CONTRACTOR SHALL

CONDUCT THEIR OPERATIONS SO THAT THERE WILL BE MINIMUM INTERFERENCE

WITH THE CONTINUED OPERATIONS OF THE BUILDING AND STAFF. COORDINATE

TIMING AND HOURS OF DEMOLITION OPERATIONS WITH THE OWNER. MINIMIZE

NOISE FROM DEMOLITION OPERATIONS PARTICULARLY WHEN CONDUCTED

DURING REGULAR WORKING HOURS.

CONDUCT DEMOLITION OPERATIONS TO PREVENT INJURY TO PEOPLE AND

DAMAGE TO ADJACENT BUILDING AREAS. THE CONTRACTOR SHALL TAKE ALL

PRECAUTIONS TO ENSURE SAFE PASSAGE OF PEOPLE THROUGH AND AROUND

SELECTIVE DEMOLITION AREAS. MAINTAIN SAFE MEANS OF EGRESS FROM THE

BUILDING AT ALL TIMES.

THE CONTRACTOR IS RESPONSIBLE FOR INSURING THE STRUCTURAL STABILITY

OF THE EXISTING BUILDING IN THE AREAS INVOLVING NEW WORK OR FOR

PROTECTING THE EXISTING BUILDING FROM DAMAGE DURING THE COURSE OF

THE WORK. DO NOT ALTER THE STRUCTURAL INTEGRITY OF THE EXISTING

BUILDING OR ITS ASSEMBLIES UNLESS SPECIFICALLY DIRECTED TO BY THE

ARCHITECT.

GENERAL NOTES

7.

8.

9.

10.

11.

NO DEMOLITION SHALL OCCUR WHICH LEAVES THE BUILDINGS INTERIOR WITHOUT

WEATHER PROTECTION. ALL DEMOLITION AT EXTERIOR SURFACES SHALL BE

FOLLOWED IMMEDIATELY BY PROTECTIVE CONSTRUCTION. THE CONTRACTOR

SHALL PROVIDE AND INSTALL SECURE TEMPORARY PROTECTION IN ALL

OPENINGS.

EXISTING CONSTRUCTION TO REMAIN UNLESS OTHERWISE NOTED. THE

CONTRACTOR SHALL TAKE ALL POSSIBLE PRECAUTIONS AGAINST DAMAGE TO ALL

EXISTING CONSTRUCTION INTENDED TO REMAIN. TAKE CARE NOT TO ENCROACH

ON ADJACENT OCCUPIED AREAS OR AREAS NOT WITHIN THE SCOPE OF WORK.

ANY DAMAGE CAUSED BY THE CONTRACTOR'S DEMOLITION OPERATIONS SHALL

BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE COMPLETE SATISFACTION OF

THE ARCHITECT AND OWNER.

GENERAL CONTRACTOR SHALL MAINTAIN A SEPARATION BETWEEN AREAS WITHIN

THE SCOPE OF THE WORK AND AREAS OUTSIDE THE SCOPE OF THE WORK BY

PROVIDING A DUST BARRIER FOR PROTECTION OF EXISTING AREAS TO REMAIN AS

REQUIRED. USE ALL MEANS NECESSARY TO PREVENT THE SPREAD OF DUST TO

ADJACENT AREAS.

REMOVE FROM SITE ALL DEMOLISHED MATERIALS, DEBRIS AND RUBBISH ON A

DAILY BASIS. DO NOT ACCUMULATE DEBRIS ON THE FLOOR OR AT THE SITE.

DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF THE SITE

COMPLYING WITH ALL LOCAL HAULING AND DISPOSAL REQUIREMENTS. UPON

COMPLETION, CLEAN ALL AREAS IMPACTED BY THE DEMOLITION, INCLUDING, BUT

NOT LIMITED TO, ADJACENT OCCUPIED AREAS AND AREAS NOT WITHIN THE

SCOPE OF WORK.

REMOVAL AS DESCRIBED HEREIN SHALL BE ACCOMPLISHED WITHOUT STORING

ON THE FLOOR EXCESSIVE QUANTITIES OF ANY MATERIALS OR WASTE RESULTING

FROM THE REMOVAL OPERATIONS ON THE FLOOR.

12.

13.

14.

15.

16.

17.

18.

19.

CONTRACTOR TO REVIEW WITH ARCHITECT ALL ITEMS SCHEDULED TO BE

DEMOLISHED, SALVAGED AND RELOCATED. SAID ITEMS TO BE REMOVED

CAREFULLY, PROTECTED AND STORED PRIOR TO RELOCATION.

THE ARCHITECT HAS NO KNOWLEDGE OF AND SHALL NOT BE HELD LIABLE FOR

ANY ASBESTOS OR OTHER HAZARDOUS MATERIALS ON JOBSITE. IF THE

CONTRACTOR ENCOUNTERS WHAT APPEARS TO BE HAZARDOUS MATERIALS

DURING CONSTRUCTION, HE SHALL IMMEDIATELY ISOLATE THE AFFECTED AREAS

AND FOLLOW THE PROCEDURES OUTLINED IN THE PROJECT MANUAL FOR

RESOLUTION.

DEMO PLAN KEYED NOTES APPLY TO ITEMS TAGGED, AND REPETITIVE/TYPICAL

ITEMS & CONDITIONS WHICH MAY ONLY BE TAGGED AT ONE LOCATION AND NOT

AT EVERY OCCURRENCE.

REPAIR ALL AREAS DAMAGED DURING DEMOLITION TO MATCH ADJACENT

CONSTRUCTION.

PREPARE ALL AREAS REMAINING AFTER DEMOLITION TO RECEIVE NEW FINISH

AND/OR CONSTRUCTION.

REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

DEMOLITION.

PARGE ALL CMU DAMAGED DURING DEMOLITION IN AREAS TO REMAIN EXPOSED

TO MATCH ADJACENT CONSTRUCTION.

PATCH ALL HOLES IN WALLS, ROOFS, FLOOR SLABS, ETC. FROM DEMOLITION OF

EXISTING MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT TO MATCH

ADJACENT CONSTRUCTION.

c by ZMM, INC.

CHECKED

DATE

COMM. NO.

DRAWN

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

ARCHITECTS

ENGINEERS

5/

/2

:4 4:

A

M C

:\U se rs \ja lle n\

D oc um en ts \2

_B ui ld in g

6_ A_

_j al le nA

FM

U Q

.rv t

A101

21152

05.30.2025

DEMOLITION

PLAN

R en ov at io ns to C

A M

P D

A W

SO

N

B

U

IL

D

IN

G

W es t V irg in ia A rm y

N at io na l G ua rd Ki ng w oo d, W es t V irg in ia

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

NHS

JSA

ARK

1/8" = 1'-0"1 DEMOLITION PLAN

KEYED NOTES

1 REMOVE DOOR AND FRAME

2 REMOVE WINDOW SYSTEM - REMOVE SILL FLASHING AND INTERIOR SILL -

REMOVE CURTAINS AND ALL ASSOCIATED HARDWARE INCLUDING VERTICAL

WOOD TRIM BOARD

3 REMOVE WINDOW SYSTEM

4 REMOVE UTILITY SINK

5 REMOVE WASHER AND DRYER

7 REMOVE ENTIRE KITCHENETTE INCLUDING UPPER AND LOWER CABINETS,

COUNTERTOP, SINK, REFRIGERATOR, COOKTOP, BACKSPLASH, MICROWAVE, ETC.

8 REMOVE FULL HEIGHT OF PARTITION TO EXTENT SHOWN

9 REMOVE VANITY INCLUDING BASE CABINETS, COUNTERTOP, SINKS, WALL

MIRRORS, TOWEL RACKS, WALL-MOUNTED DISPENSERS, ETC.

10 REMOVE TOILET, BATHTUB, TUB SURROUND, TILE FLOORING, WALL BASE,

SHOWER CURTAIN/ROD, TOILET PAPER DISPENSER, AND ALL TOILET

ACCESSORIES

11 REMOVE FLOOR FINISH DOWN TO EXISTING CONCRETE SLAB AND WALL BASE

THROUGHOUT ENTIRE SPACE

12 REMOVE SOFFIT PANELS AND ALL ASSOCIATED ITEMS

13 REMOVE SUSPENDED ACOUSTICAL CEILING AND ALL ASSOCIATED ITEMS

14 REMOVE WALL AS REQUIRED TO ACCOMMODATE NEW OPENING

15 REMOVE DOWNSPOUT - ALTERNATE #1 - EXISTING DOWNSPOUT BOOT TO REMAIN

16 HATCHING INDICATES EXTENT OF CONCRETE SIDEWALK TO BE REMOVED

17 SIDEWALK DEMOLITION EXTENDS FOR FULL LENGTH OF SIDEWALK AND STOPS AT

ADJACENT PAVING

18 REMOVE GUTTER - ALTERNATE #1

19 SAND HATCHING INDICATES EXTENT OF ASPHALT SHINGLE ROOFING AND ANY

UNDERLAYMENTS TO BE REMOVED DOWN TO EXISTING SHEATHING - REMOVE

ALL PERIMETER TRIM AND FLASHINGS - ALTERNATE #1

20 REMOVE LOUVERS AND ANY SIDING ABOVE ROOF AND BELOW UPPER OVERHANG

21 REMOVE EXISTING CMU WALL TO EXTENT SHOWN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

A

TE

1.

2.

3.

4.

5.

6.

ALL DEMOLITION WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL

APPLICABLE LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.

THE DEMOLITION PLANS ARE INTENDED TO REASONABLY REPRESENT EXISTING

CONDITIONS. ACTUAL CONDITIONS MAY DEVIATE FROM THAT SHOWN ON THE

DRAWINGS. THE CONTRACTOR SHALL VISIT THE JOBSITE AND VERIFY ACTUAL

CONDITIONS AND COORDINATE THE DEMOLITION WORK WITH THE NEW WORK SO

THAT DEMOLITION IS COMPLETE. FIELD VERIFY ALL DIMENSIONS SHOWN ON

DRAWINGS PRIOR TO CONSTRUCTION AND NOTIFY ARCHITECT OF ANY

DISCREPANCIES.

PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND SERVICES AND PERFORM ALL

OPERATIONS REQUIRED FOR COMPLETE INTERIOR DEMOLITION AND RELATED

WORK AS DESCRIBED AND SPECIFIED HEREIN, AND AS MAY BE REASONABLY

IMPLIED AS NECESSARY TO COMPLETE NEW CONSTRUCTION WORK.

THE CONTRACTOR SHALL BE AWARE THAT THE BUILDING WILL BE OCCUPIED AND

IN-USE DURING THE LENGTH OF THE CONTRACT. THE CONTRACTOR SHALL

CONDUCT THEIR OPERATIONS SO THAT THERE WILL BE MINIMUM INTERFERENCE

WITH THE CONTINUED OPERATIONS OF THE BUILDING AND STAFF. COORDINATE

TIMING AND HOURS OF DEMOLITION OPERATIONS WITH THE OWNER. MINIMIZE

NOISE FROM DEMOLITION OPERATIONS PARTICULARLY WHEN CONDUCTED

DURING REGULAR WORKING HOURS.

CONDUCT DEMOLITION OPERATIONS TO PREVENT INJURY TO PEOPLE AND

DAMAGE TO ADJACENT BUILDING AREAS. THE CONTRACTOR SHALL TAKE ALL

PRECAUTIONS TO ENSURE SAFE PASSAGE OF PEOPLE THROUGH AND AROUND

SELECTIVE DEMOLITION AREAS. MAINTAIN SAFE MEANS OF EGRESS FROM THE

BUILDING AT ALL TIMES.

THE CONTRACTOR IS RESPONSIBLE FOR INSURING THE STRUCTURAL STABILITY

OF THE EXISTING BUILDING IN THE AREAS INVOLVING NEW WORK OR FOR

PROTECTING THE EXISTING BUILDING FROM DAMAGE DURING THE COURSE OF

THE WORK. DO NOT ALTER THE STRUCTURAL INTEGRITY OF THE EXISTING

BUILDING OR ITS ASSEMBLIES UNLESS SPECIFICALLY DIRECTED TO BY THE

ARCHITECT.

GENERAL NOTES

7.

8.

9.

10.

11.

NO DEMOLITION SHALL OCCUR WHICH LEAVES THE BUILDINGS INTERIOR WITHOUT

WEATHER PROTECTION. ALL DEMOLITION AT EXTERIOR SURFACES SHALL BE

FOLLOWED IMMEDIATELY BY PROTECTIVE CONSTRUCTION. THE CONTRACTOR

SHALL PROVIDE AND INSTALL SECURE TEMPORARY PROTECTION IN ALL

OPENINGS.

EXISTING CONSTRUCTION TO REMAIN UNLESS OTHERWISE NOTED. THE

CONTRACTOR SHALL TAKE ALL POSSIBLE PRECAUTIONS AGAINST DAMAGE TO ALL

EXISTING CONSTRUCTION INTENDED TO REMAIN. TAKE CARE NOT TO ENCROACH

ON ADJACENT OCCUPIED AREAS OR AREAS NOT WITHIN THE SCOPE OF WORK.

ANY DAMAGE CAUSED BY THE CONTRACTOR'S DEMOLITION OPERATIONS SHALL

BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE COMPLETE SATISFACTION OF

THE ARCHITECT AND OWNER.

GENERAL CONTRACTOR SHALL MAINTAIN A SEPARATION BETWEEN AREAS WITHIN

THE SCOPE OF THE WORK AND AREAS OUTSIDE THE SCOPE OF THE WORK BY

PROVIDING A DUST BARRIER FOR PROTECTION OF EXISTING AREAS TO REMAIN AS

REQUIRED. USE ALL MEANS NECESSARY TO PREVENT THE SPREAD OF DUST TO

ADJACENT AREAS.

REMOVE FROM SITE ALL DEMOLISHED MATERIALS, DEBRIS AND RUBBISH ON A

DAILY BASIS. DO NOT ACCUMULATE DEBRIS ON THE FLOOR OR AT THE SITE.

DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF THE SITE

COMPLYING WITH ALL LOCAL HAULING AND DISPOSAL REQUIREMENTS. UPON

COMPLETION, CLEAN ALL AREAS IMPACTED BY THE DEMOLITION, INCLUDING, BUT

NOT LIMITED TO, ADJACENT OCCUPIED AREAS AND AREAS NOT WITHIN THE

SCOPE OF WORK.

REMOVAL AS DESCRIBED HEREIN SHALL BE ACCOMPLISHED WITHOUT STORING

ON THE FLOOR EXCESSIVE QUANTITIES OF ANY MATERIALS OR WASTE RESULTING

FROM THE REMOVAL OPERATIONS ON THE FLOOR.

12.

13.

14.

15.

16.

17.

18.

19.

CONTRACTOR TO REVIEW WITH ARCHITECT ALL ITEMS SCHEDULED TO BE

DEMOLISHED, SALVAGED AND RELOCATED. SAID ITEMS TO BE REMOVED

CAREFULLY, PROTECTED AND STORED PRIOR TO RELOCATION.

THE ARCHITECT HAS NO KNOWLEDGE OF AND SHALL NOT BE HELD LIABLE FOR

ANY ASBESTOS OR OTHER HAZARDOUS MATERIALS ON JOBSITE. IF THE

CONTRACTOR ENCOUNTERS WHAT APPEARS TO BE HAZARDOUS MATERIALS

DURING CONSTRUCTION, HE SHALL IMMEDIATELY ISOLATE THE AFFECTED AREAS

AND FOLLOW THE PROCEDURES OUTLINED IN THE PROJECT MANUAL FOR

RESOLUTION.

DEMO PLAN KEYED NOTES APPLY TO ITEMS TAGGED, AND REPETITIVE/TYPICAL

ITEMS & CONDITIONS WHICH MAY ONLY BE TAGGED AT ONE LOCATION AND NOT

AT EVERY OCCURRENCE.

REPAIR ALL AREAS DAMAGED DURING DEMOLITION TO MATCH ADJACENT

CONSTRUCTION.

PREPARE ALL AREAS REMAINING AFTER DEMOLITION TO RECEIVE NEW FINISH

AND/OR CONSTRUCTION.

REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

DEMOLITION.

PARGE ALL CMU DAMAGED DURING DEMOLITION IN AREAS TO REMAIN EXPOSED

TO MATCH ADJACENT CONSTRUCTION.

PATCH ALL HOLES IN WALLS, ROOFS, FLOOR SLABS, ETC. FROM DEMOLITION OF

EXISTING MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT TO MATCH

ADJACENT CONSTRUCTION.

12 12 12

12 12 12

15 15 15 15 15 15 15 15

15 15 15 15 15 15 15 15

181818

18 18 18 c by ZMM, INC.

CHECKED

DATE

COMM. NO.

DRAWN

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

ARCHITECTS

ENGINEERS

5/

/2

:4 4:

A

M C

:\U se rs \ja lle n\

D oc um en ts \2

_B ui ld in g

6_ A_

_j al le nA

FM

U Q

.rv t

A111

21152

05.30.2025

DEMOLITION

REFLECTED

CEILING PLAN

R en ov at io ns to C

A M

P D

A W

SO

N

B

U

IL

D

IN

G

W es t V irg in ia A rm y

N at io na l G ua rd Ki ng w oo d, W es t V irg in ia

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

NHS

JSA

ARK

KEYED NOTES

1 REMOVE DOOR AND FRAME

2 REMOVE WINDOW SYSTEM - REMOVE SILL FLASHING AND INTERIOR SILL -

REMOVE CURTAINS AND ALL ASSOCIATED HARDWARE INCLUDING VERTICAL

WOOD TRIM BOARD

3 REMOVE WINDOW SYSTEM

4 REMOVE UTILITY SINK

5 REMOVE WASHER AND DRYER

7 REMOVE ENTIRE KITCHENETTE INCLUDING UPPER AND LOWER CABINETS,

COUNTERTOP, SINK, REFRIGERATOR, COOKTOP, BACKSPLASH, MICROWAVE, ETC.

8 REMOVE FULL HEIGHT OF PARTITION TO EXTENT SHOWN

9 REMOVE VANITY INCLUDING BASE CABINETS, COUNTERTOP, SINKS, WALL

MIRRORS, TOWEL RACKS, WALL-MOUNTED DISPENSERS, ETC.

10 REMOVE TOILET, BATHTUB, TUB SURROUND, TILE FLOORING, WALL BASE,

SHOWER CURTAIN/ROD, TOILET PAPER DISPENSER, AND ALL TOILET

ACCESSORIES

11 REMOVE FLOOR FINISH DOWN TO EXISTING CONCRETE SLAB AND WALL BASE

THROUGHOUT ENTIRE SPACE

12 REMOVE SOFFIT PANELS AND ALL ASSOCIATED ITEMS

13 REMOVE SUSPENDED ACOUSTICAL CEILING AND ALL ASSOCIATED ITEMS

14 REMOVE WALL AS REQUIRED TO ACCOMMODATE NEW OPENING

15 REMOVE DOWNSPOUT - ALTERNATE #1 - EXISTING DOWNSPOUT BOOT TO REMAIN

16 HATCHING INDICATES EXTENT OF CONCRETE SIDEWALK TO BE REMOVED

17 SIDEWALK DEMOLITION EXTENDS FOR FULL LENGTH OF SIDEWALK AND STOPS AT

ADJACENT PAVING

18 REMOVE GUTTER - ALTERNATE #1

19 SAND HATCHING INDICATES EXTENT OF ASPHALT SHINGLE ROOFING AND ANY

UNDERLAYMENTS TO BE REMOVED DOWN TO EXISTING SHEATHING - REMOVE

ALL PERIMETER TRIM AND FLASHINGS - ALTERNATE #1

20 REMOVE LOUVERS AND ANY SIDING ABOVE ROOF AND BELOW UPPER OVERHANG

21 REMOVE EXISTING CMU WALL TO EXTENT SHOWN

1/8" = 1'-0"1 DEMOLITION REFLECTED CEILING PLAN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

3.

4.

5.

6.

ALL DEMOLITION WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL

APPLICABLE LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.

THE DEMOLITION PLANS ARE INTENDED TO REASONABLY REPRESENT EXISTING

CONDITIONS. ACTUAL CONDITIONS MAY DEVIATE FROM THAT SHOWN ON THE

DRAWINGS. THE CONTRACTOR SHALL VISIT THE JOBSITE AND VERIFY ACTUAL

CONDITIONS AND COORDINATE THE DEMOLITION WORK WITH THE NEW WORK SO

THAT DEMOLITION IS COMPLETE. FIELD VERIFY ALL DIMENSIONS SHOWN ON

DRAWINGS PRIOR TO CONSTRUCTION AND NOTIFY ARCHITECT OF ANY

DISCREPANCIES.

PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND SERVICES AND PERFORM ALL

OPERATIONS REQUIRED FOR COMPLETE INTERIOR DEMOLITION AND RELATED

WORK AS DESCRIBED AND SPECIFIED HEREIN, AND AS MAY BE REASONABLY

IMPLIED AS NECESSARY TO COMPLETE NEW CONSTRUCTION WORK.

THE CONTRACTOR SHALL BE AWARE THAT THE BUILDING WILL BE OCCUPIED AND

IN-USE DURING THE LENGTH OF THE CONTRACT. THE CONTRACTOR SHALL

CONDUCT THEIR OPERATIONS SO THAT THERE WILL BE MINIMUM INTERFERENCE

WITH THE CONTINUED OPERATIONS OF THE BUILDING AND STAFF. COORDINATE

TIMING AND HOURS OF DEMOLITION OPERATIONS WITH THE OWNER. MINIMIZE

NOISE FROM DEMOLITION OPERATIONS PARTICULARLY WHEN CONDUCTED

DURING REGULAR WORKING HOURS.

CONDUCT DEMOLITION OPERATIONS TO PREVENT INJURY TO PEOPLE AND

DAMAGE TO ADJACENT BUILDING AREAS. THE CONTRACTOR SHALL TAKE ALL

PRECAUTIONS TO ENSURE SAFE PASSAGE OF PEOPLE THROUGH AND AROUND

SELECTIVE DEMOLITION AREAS. MAINTAIN SAFE MEANS OF EGRESS FROM THE

BUILDING AT ALL TIMES.

THE CONTRACTOR IS RESPONSIBLE FOR INSURING THE STRUCTURAL STABILITY

OF THE EXISTING BUILDING IN THE AREAS INVOLVING NEW WORK OR FOR

PROTECTING THE EXISTING BUILDING FROM DAMAGE DURING THE COURSE OF

THE WORK. DO NOT ALTER THE STRUCTURAL INTEGRITY OF THE EXISTING

BUILDING OR ITS ASSEMBLIES UNLESS SPECIFICALLY DIRECTED TO BY THE

ARCHITECT.

GENERAL NOTES

7.

8.

9.

10.

11.

NO DEMOLITION SHALL OCCUR WHICH LEAVES THE BUILDINGS INTERIOR WITHOUT

WEATHER PROTECTION. ALL DEMOLITION AT EXTERIOR SURFACES SHALL BE

FOLLOWED IMMEDIATELY BY PROTECTIVE CONSTRUCTION. THE CONTRACTOR

SHALL PROVIDE AND INSTALL SECURE TEMPORARY PROTECTION IN ALL

OPENINGS.

EXISTING CONSTRUCTION TO REMAIN UNLESS OTHERWISE NOTED. THE

CONTRACTOR SHALL TAKE ALL POSSIBLE PRECAUTIONS AGAINST DAMAGE TO ALL

EXISTING CONSTRUCTION INTENDED TO REMAIN. TAKE CARE NOT TO ENCROACH

ON ADJACENT OCCUPIED AREAS OR AREAS NOT WITHIN THE SCOPE OF WORK.

ANY DAMAGE CAUSED BY THE CONTRACTOR'S DEMOLITION OPERATIONS SHALL

BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE COMPLETE SATISFACTION OF

THE ARCHITECT AND OWNER.

GENERAL CONTRACTOR SHALL MAINTAIN A SEPARATION BETWEEN AREAS WITHIN

THE SCOPE OF THE WORK AND AREAS OUTSIDE THE SCOPE OF THE WORK BY

PROVIDING A DUST BARRIER FOR PROTECTION OF EXISTING AREAS TO REMAIN AS

REQUIRED. USE ALL MEANS NECESSARY TO PREVENT THE SPREAD OF DUST TO

ADJACENT AREAS.

REMOVE FROM SITE ALL DEMOLISHED MATERIALS, DEBRIS AND RUBBISH ON A

DAILY BASIS. DO NOT ACCUMULATE DEBRIS ON THE FLOOR OR AT THE SITE.

DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF THE SITE

COMPLYING WITH ALL LOCAL HAULING AND DISPOSAL REQUIREMENTS. UPON

COMPLETION, CLEAN ALL AREAS IMPACTED BY THE DEMOLITION, INCLUDING, BUT

NOT LIMITED TO, ADJACENT OCCUPIED AREAS AND AREAS NOT WITHIN THE

SCOPE OF WORK.

REMOVAL AS DESCRIBED HEREIN SHALL BE ACCOMPLISHED WITHOUT STORING

ON THE FLOOR EXCESSIVE QUANTITIES OF ANY MATERIALS OR WASTE RESULTING

FROM THE REMOVAL OPERATIONS ON THE FLOOR.

12.

13.

14.

15.

16.

17.

18.

19.

CONTRACTOR TO REVIEW WITH ARCHITECT ALL ITEMS SCHEDULED TO BE

DEMOLISHED, SALVAGED AND RELOCATED. SAID ITEMS TO BE REMOVED

CAREFULLY, PROTECTED AND STORED PRIOR TO RELOCATION.

THE ARCHITECT HAS NO KNOWLEDGE OF AND SHALL NOT BE HELD LIABLE FOR

ANY ASBESTOS OR OTHER HAZARDOUS MATERIALS ON JOBSITE. IF THE

CONTRACTOR ENCOUNTERS WHAT APPEARS TO BE HAZARDOUS MATERIALS

DURING CONSTRUCTION, HE SHALL IMMEDIATELY ISOLATE THE AFFECTED AREAS

AND FOLLOW THE PROCEDURES OUTLINED IN THE PROJECT MANUAL FOR

RESOLUTION.

DEMO PLAN KEYED NOTES APPLY TO ITEMS TAGGED, AND REPETITIVE/TYPICAL

ITEMS & CONDITIONS WHICH MAY ONLY BE TAGGED AT ONE LOCATION AND NOT

AT EVERY OCCURRENCE.

REPAIR ALL AREAS DAMAGED DURING DEMOLITION TO MATCH ADJACENT

CONSTRUCTION.

PREPARE ALL AREAS REMAINING AFTER DEMOLITION TO RECEIVE NEW FINISH

AND/OR CONSTRUCTION.

REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

DEMOLITION.

PARGE ALL CMU DAMAGED DURING DEMOLITION IN AREAS TO REMAIN EXPOSED

TO MATCH ADJACENT CONSTRUCTION.

PATCH ALL HOLES IN WALLS, ROOFS, FLOOR SLABS, ETC. FROM DEMOLITION OF

EXISTING MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT TO MATCH

ADJACENT CONSTRUCTION.

15 15 15 15 15 15 15 15

15 15 15 15 15 15 15 15

181818

18 18 18

19 19

19 19 19

202020 c by ZMM, INC.

CHECKED

DATE

COMM. NO.

DRAWN

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

ARCHITECTS

ENGINEERS

5/

/2

:4 4:

A

M C

:\U se rs \ja lle n\

D oc um en ts \2

_B ui ld in g

6_ A_

_j al le nA

FM

U Q

.rv t

A121

21152

05.30.2025

DEMOLITION

ROOF PLAN

R en ov at io ns to C

A M

P D

A W

SO

N

B

U

IL

D

IN

G

W es t V irg in ia A rm y

N at io na l G ua rd Ki ng w oo d, W es t V irg in ia

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

NHS

JSA

ARK

KEYED NOTES

1 REMOVE DOOR AND FRAME

2 REMOVE WINDOW SYSTEM - REMOVE SILL FLASHING AND INTERIOR SILL -

REMOVE CURTAINS AND ALL ASSOCIATED HARDWARE INCLUDING VERTICAL

WOOD TRIM BOARD

3 REMOVE WINDOW SYSTEM

4 REMOVE UTILITY SINK

5 REMOVE WASHER AND DRYER

7 REMOVE ENTIRE KITCHENETTE INCLUDING UPPER AND LOWER CABINETS,

COUNTERTOP, SINK, REFRIGERATOR, COOKTOP, BACKSPLASH, MICROWAVE, ETC.

8 REMOVE FULL HEIGHT OF PARTITION TO EXTENT SHOWN

9 REMOVE VANITY INCLUDING BASE CABINETS, COUNTERTOP, SINKS, WALL

MIRRORS, TOWEL RACKS, WALL-MOUNTED DISPENSERS, ETC.

10 REMOVE TOILET, BATHTUB, TUB SURROUND, TILE FLOORING, WALL BASE,

SHOWER CURTAIN/ROD, TOILET PAPER DISPENSER, AND ALL TOILET

ACCESSORIES

11 REMOVE FLOOR FINISH DOWN TO EXISTING CONCRETE SLAB AND WALL BASE

THROUGHOUT ENTIRE SPACE

12 REMOVE SOFFIT PANELS AND ALL ASSOCIATED ITEMS

13 REMOVE SUSPENDED ACOUSTICAL CEILING AND ALL ASSOCIATED ITEMS

14 REMOVE WALL AS REQUIRED TO ACCOMMODATE NEW OPENING

15 REMOVE DOWNSPOUT - ALTERNATE #1 - EXISTING DOWNSPOUT BOOT TO REMAIN

16 HATCHING INDICATES EXTENT OF CONCRETE SIDEWALK TO BE REMOVED

17 SIDEWALK DEMOLITION EXTENDS FOR FULL LENGTH OF SIDEWALK AND STOPS AT

ADJACENT PAVING

18 REMOVE GUTTER - ALTERNATE #1

19 SAND HATCHING INDICATES EXTENT OF ASPHALT SHINGLE ROOFING AND ANY

UNDERLAYMENTS TO BE REMOVED DOWN TO EXISTING SHEATHING - REMOVE

ALL PERIMETER TRIM AND FLASHINGS - ALTERNATE #1

20 REMOVE LOUVERS AND ANY SIDING ABOVE ROOF AND BELOW UPPER OVERHANG

21 REMOVE EXISTING CMU WALL TO EXTENT SHOWN

1/8" = 1'-0"1 DEMOLITION ROOF PLAN

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

3.

4.

5.

6.

7.

8.

9.

10.

11.

FURNITURE SHOWN IS NOT IN CONTRACT - SHOWN FOR OWNER CLARITY ONLY.

INTERIOR PARTITIONS ARE DIMENSIONED TO FACE OF WALL UNLESS NOTED

OTHERWISE.

THE HINGE SIDE OF INTERIOR DOOR FRAMES ARE LOCATED 2" FROM FACE OF

ADJACENT WALL (METAL STUD) AND 4" FROM FACE OF ADJACENT WALL (MASONRY)

UNLESS NOTED OTHERWISE.

PROVIDE FIRE-TREATED WOOD BLOCKING IN CAVITY OF METAL STUD PARTITIONS

FOR ALL WALL-MOUNTED ITEMS.

ALL WALLS AND GYPSUM CEILINGS TO BE PT-1 UNLESS OTHERWISE NOTED.

WHERE FLOOR MATERIAL CHANGES IN DOORWAYS, PLACE TRANSITION

UNDERNEATH DOOR LEAF.

ALL INTERIOR HM DOOR FRAMING SHALL BE PT-2 SEMIGLOSS.

WHERE CASEWORK ABUTS ADJOINING WALLS, PROVIDE 1" (MIN, V.I.F.) PLAM FILLER

PANEL BETWEEN CASEWORK AND WALL, TYP.

ALL GRILLES, VENTS, ELECTRICAL PANELS, ACCESS PANELS, ETC. TO MATCH

ADJACENT WALL COLOR UNLESS NOTED OTHERWISE.

ALL BULKHEADS AND SOFFITS TO BE PT-1 UNLESS OTHERWISE NOTED. ALL

CEILING SURFACES SHALL BE FINISHED ON ALL FACES UNLESS NOTED

OTHERWISE. REFER TO REFLECTED CEILINGS PLANS FOR ADDITIONAL

INFORMATION.

ALL RESTROOMS, KITCHEN, AND MECHANICAL/ELECTRICAL SPACES SHALL

RECEIVE AN EPOXY PAINT FINISH.

GENERAL NOTES

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

12 BILLETING

ROOM

CLASSROOM

MECH /

ELECT

ELECTRICAL

28a

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

LAUNDRY

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

BILLETING

ROOM

CHASE

CHASE

CHASE

1001 1005 1009 1013

1019 1023 1027 1031

1035 1039 1043 1047

1063 1067 1071 1075 1079

1085 1089 1093 1097

1103 1107 1111 1115

A310

A310

A310

A310

BILLETING

ROOM

1004 1008

1007 1011

1012 1015

1014 1037

1042 1046

1045 1049

1050 1054

1096 1100

11181114

11131109

11101106

11051080

10781074

10731069

10701066

10651032

10331030

10291025

10261022

A132

A132

A A A A A A A A A A A A A A

AAAAAAAAAAAAA

1 1

2 2 2 2 2 2 2 2

2 2 2 2 2 2 2 2

A

RR

14A

CHASE /

MECH

CHASE /

MECH

ENCLOSED

BREEZEWAY

37 MECH.

8' - 0"

A311

A311

A132

PARTITION TO RESIST THE PASSAGE OF SMOKE

PARTITION TYPE TAG

A EXTERIOR WINDOW TAG

KEYED NOTE

1 INTERIOR WINDOW TAG

LEGEND

1 HOUR FIRE RATED WALL ASSEMBLY

2 HOUR FIRE RATED WALL ASSEMBLY

DOOR TAG

A01 c by ZMM, INC.

CHECKED

DATE

COMM. NO.

DRAWN

222 Lee Street, West Charleston, West Virginia 25302 Phone: 304.342.0159 Fax: 304.345.8144 www.zmm.com

ARCHITECTS

ENGINEERS

5/

/2

:4 4:

A

M C

:\U se rs \ja lle n\

D oc um en ts \2

_B ui ld in g

6_ A_

_j al le nA

FM

U Q

.rv t

A131

21152

05.30.2025

FLOOR PLAN

R en ov at io ns to C

A M

P D

A W

SO

N

B

U

IL

D

IN

G

W es t V irg in ia A rm y

N at io na l G ua rd Ki ng w oo d, W es t V irg in ia

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

NHS

JSA

ARK

1/8" = 1'-0"1 FLOOR PLAN

ROOM FINISH SCHEDULE

ROOM # ROOM NAME FLOOR BASE WALLS REMARKS

01 BILLETING ROOM LVP-1 RB-1 PT-1

01a CLOSET LVP-1 RB-1 PT-1

01b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

01c CLOSET LVP-1 RB-1 PT-1

02 BILLETING ROOM LVP-1 RB-1 PT-1

02a CLOSET LVP-1 RB-1 PT-1

02b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

02c CLOSET LVP-1 RB-1 PT-1

03 BILLETING ROOM LVP-1 RB-1 PT-1

03a CLOSET LVP-1 RB-1 PT-1

03b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

03c CLOSET LVP-1 RB-1 PT-1

04 BILLETING ROOM LVP-1 RB-1 PT-1

04a CLOSET LVP-1 RB-1 PT-1

04b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

04c CLOSET LVP-1 RB-1 PT-1

05 BILLETING ROOM LVP-1 RB-1 PT-1

05a CLOSET LVP-1 RB-1 PT-1

05b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

05c CLOSET LVP-1 RB-1 PT-1

06 BILLETING ROOM LVP-1 RB-1 PT-1

06a CLOSET LVP-1 RB-1 PT-1

06b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

06c CLOSET LVP-1 RB-1 PT-1

07 BILLETING ROOM LVP-1 RB-1 PT-1

07a CLOSET LVP-1 RB-1 PT-1

07b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

07c CLOSET LVP-1 RB-1 PT-1

08 BILLETING ROOM LVP-1 RB-1 PT-1

08a CLOSET LVP-1 RB-1 PT-1

08b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

08c CLOSET LVP-1 RB-1 PT-1

09 BILLETING ROOM LVP-1 RB-1 PT-1

09a CLOSET LVP-1 RB-1 PT-1

09b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

09c CLOSET LVP-1 RB-1 PT-1

10 BILLETING ROOM LVP-1 RB-1 PT-1

10a CLOSET LVP-1 RB-1 PT-1

10b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

10c CLOSET LVP-1 RB-1 PT-1

11 BILLETING ROOM LVP-1 RB-1 PT-1

FINISH LEGEND

CODE TYPE MANUFACTURER / STYLE

STYLE NUMBER /

COLOR COMMENTS

ETR EXISTING TO REMAIN -- --

LVP-1 LUXURY VINYL PLANK 6X48 TARKETT / EVENT WOOD ATLANTIC WALNUT

PLAM-1 PLASTIC LAMINATE ABET LAMINATI 2906 / POLARIS BK

PT-1 PAINT - FIELD SHERWIN WILLIAMS SW9166 / DRIFT OF MIST

PT-2 PAINT - STEEL DOORS/FRAME SHERWIN WILLIAMS SW9168 / ELEPHANT EAR

RB-1 RUBBER WALL BASE TARKETT / JOHNSONITE WELSH CASTLE

SC-1 SEALED CONCRETE N/A NATURAL

SS-1 SOLID SURFACE FORMICA / EVERFORM 781 / LUNA CONCRETE

T-1 TILE - FLOOR 12X24 AMERICAN OLEAN / COLOR STORY FLOOR 0016 / MATTE SHADOW RUNNING BOND

INSTALLATION

T-2 TILE - WALL 4X12 AMERICAN OLEAN / COLOR STORY WALL 0014 / BALANCE VERTICAL STACK BOND

INSTALLATION

TB-1 TILE BASE - 3X12 BULLNOSE AMERICAN OLEAN / COLOR STORY FLOOR 0016 / MATTE SHADOW

ROOM FINISH SCHEDULE

ROOM # ROOM NAME FLOOR BASE WALLS REMARKS

11a CLOSET LVP-1 RB-1 PT-1

11b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

11c CLOSET LVP-1 RB-1 PT-1

12 BILLETING ROOM LVP-1 RB-1 PT-1

12a CLOSET LVP-1 RB-1 PT-1

12b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

12c CLOSET LVP-1 RB-1 PT-1

13 BILLETING ROOM LVP-1 RB-1 PT-1

13a CLOSET LVP-1 RB-1 PT-1

13b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

13c CLOSET LVP-1 RB-1 PT-1

14 CLASSROOM LVP-1 RB-1 PT-1

14A RR T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

14a CLOSET LVP-1 RB-1 PT-1

14b ADA TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

15 BILLETING ROOM LVP-1 RB-1 PT-1

15a CLOSET LVP-1 RB-1 PT-1

15b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

15c CLOSET LVP-1 RB-1 PT-1

16 BILLETING ROOM LVP-1 RB-1 PT-1

16a CLOSET LVP-1 RB-1 PT-1

16b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

16c CLOSET LVP-1 RB-1 PT-1

17 BILLETING ROOM LVP-1 RB-1 PT-1

17a CLOSET LVP-1 RB-1 PT-1

17b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

17c CLOSET LVP-1 RB-1 PT-1

18 BILLETING ROOM LVP-1 RB-1 PT-1

18a CLOSET LVP-1 RB-1 PT-1

18b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

18c CLOSET LVP-1 RB-1 PT-1

19 BILLETING ROOM LVP-1 RB-1 PT-1

19a CLOSET LVP-1 RB-1 PT-1

19b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

19c CLOSET LVP-1 RB-1 PT-1

20 BILLETING ROOM LVP-1 RB-1 PT-1

20a CLOSET LVP-1 RB-1 PT-1

20b Room T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

20c Room LVP-1 RB-1 PT-1

21 BILLETING ROOM LVP-1 RB-1 PT-1

ROOM FINISH SCHEDULE

ROOM # ROOM NAME FLOOR BASE WALLS REMARKS

21a CLOSET LVP-1 RB-1 PT-1

21b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

21c CLOSET LVP-1 RB-1 PT-1

22 BILLETING ROOM LVP-1 RB-1 PT-1

22a CLOSET LVP-1 RB-1 PT-1

22b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

22c CLOSET LVP-1 RB-1 PT-1

23 BILLETING ROOM LVP-1 RB-1 PT-1

23a CLOSET LVP-1 RB-1 PT-1

23b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

23c CLOSET LVP-1 RB-1 PT-1

24 BILLETING ROOM LVP-1 RB-1 PT-1

24a CLOSET LVP-1 RB-1 PT-1

24b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

24c CLOSET LVP-1 RB-1 PT-1

25 BILLETING ROOM LVP-1 RB-1 PT-1

25a CLOSET LVP-1 RB-1 PT-1

25b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

25c CLOSET LVP-1 RB-1 PT-1

26 BILLETING ROOM LVP-1 RB-1 PT-1

26a CLOSET LVP-1 RB-1 PT-1

26b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

26c CLOSET LVP-1 RB-1 PT-1

27 BILLETING ROOM LVP-1 RB-1 PT-1

27a CLOSET LVP-1 RB-1 PT-1

27b TOILET T-1 TB-1 T-2, PT-1 WALL TILE ON WET WALLS

ONLY. FLOOR TO CEILING.

27c CLOSET LVP-1 RB-1 PT-1

28 MECH / ELECT LVP-1 RB-1 PT-1

28a ELECTRICAL SC-1 RB-1 PT-1

29 LAUNDRY LVP-1 RB-1 PT-1

29a ELECTRICAL SC-1 RB-1 PT-1

30 MECHANICAL SC-1 RB-1 PT-1

31 CHASE ETR ETR ETR

32 CHASE / MECH SC-1 RB-1 PT-1

33 CHASE ETR ETR ETR

34 CHASE / MECH SC-1 RB-1 PT-1

35 CHASE ETR ETR ETR

36 HVAC SC-1 RB-1 PT-1

37 ENCLOSED

BREEZEWAY SC-1 RB-1 PT-1

38 ENCLOSED

BREEZEWAY SC-1 RB-1 PT-1

39 MECH. SC-1 RB-1 PT-1

KEYED NOTES

1 LINE OF CANOPY/BUILDING ABOVE

2 ALUMINUM DOWNSPOUT - ROUTE TO EXISTING DOWNSPOUT BOOT - CLEAN, PREP,

AND PAINT EXISTING DOWNSPOUT BOOT - ALTERNATE #1

3 FIRE EXTINGUISHER - SURFACE MOUNTED - NO PART OF THE EXTINGUISHER

SHALL EXTEND ABOVE 48" ABOVE FINISHED FLOOR - FIRE EXTINGUISHER N.I.C. -

CONTRACTOR TO PROVIDE BRACKET AND INSTALL

5 WASHING MACHINE - N.I.C.

6 DRYER - N.I.C.

7 PROVIDE BLOCKING IN STUD WALL FOR MOUNTING CASEWORK AND EQUIPMENT

8 INFILL OPENING WITH MASONRY TO MATCH EXISTING - TOOTH-IN MASONRY WITH

EXISTING

9 WALL MOUNTED TV - N.I.C. - CONTRACTOR TO PROVIDE BLOCKING IN WALL

10 CLOSET SHELF AND ROD - REFER TO MISCELLANEOUS DETAILS

11 CLOSET SHELVING - REFER TO MISCELLANEOUS DETAILS

12 ROLLER WINDOW SHADE

R

EV

IS

IO

N S

N O

D

ES

C

R

IP

TI

O

N D

BILLETING

ROOM

TOILET

01b

CLOSET

01c

2 2

2' - 0"

5'

- 0

2' - 2" 4"

4' - 6" 2' - 10"

FIELD VERIFY

�4' - 8" +/-1' - 4"

A132

LAY DIRECTION

LA

Y

DI

RE

CT

IO

N

4" CONCRETE CURB

SLOPE SHOWER

@ 1/2" PER FOOT

TOWARDS DRAIN

RR

14A

8'

- 0 ø 5 ' - 0

8' - 0"

8"

1 8

PLAN

BASE

5/8" GWB

EACH SIDE

FLOOR

STRUCTURE

1 3-5/8" MS - NON-RATED

HEAD

3-5/8" METAL

STUD

ACOUSTICAL

SEALANT, TYP.

EACH SIDE

ACOUSTICAL

SEALANT CONT.

ALONG BOTTOM OF

STUD TRACK

3 1/2" SOUND

ATTENUATION

BLANKET

ACOUSTICAL

SEALANT CONT.

ALONG TOP OF

STUD TRACK

ACOUSTICAL

SEALANT, TYP.

EACH SIDE

2 3-5/8" MS - NON-RATED

PLAN

BASE

5/8" GWB

ONE SIDE

FLOOR

STRUCTURE

HEAD

3 5/8" METAL

STUD

FACE OF

EXISTING

CONSTRUCTION

(IF APPLICABLE)

SEALANT

PLAN

BASE

5/8" GWB

ONE SIDE

FLOOR

STRUCTURE

3 2-1/2" MS - NON-RATED

HEAD

2 1/2" METAL

STUD

FACE OF

EXISTING

CONSTRUCTION

(IF APPLICABLE)

SEALANT

HEAD

PLAN

BASE

NOMINAL 8" CONCRETE

MASONRY UNIT

FLOOR

STRUCTURE

4 8" CMU - NON-RATED

CMU BOND BEAM, TYP.

7 5/8"

BRACE TO

STRUCTURE

W/ANGLES - SEE

STRUCTURAL FOR

DETAIL

SEALANT TYP.

EACH SIDE

COMPRESSIBLE

INSULATION

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

DO NOT SCALE DRAWINGS.

ALL FIRE-RATED PARTITIONS MUST BE CONSTRUCTED WITH THE EXACT

MATERIALS DESCRIBED IN THE U.L. FIRE TEST NUMBER INDICATED TO PROVIDE

SPECIFIED RATING.

METAL STUDS ARE TO BE SPACED AT 16" O.C. UNLESS OTHERWISE INDICATED.

OVERALL PARTITION WIDTHS INDICATED ON THE PLANS MUST BE MAINTAINED

G.C. SHALL ADJUST METAL STUD GAUGES AND SPACING AS NECESSARY SO AS

NOT TO EXCEED L/240 DESIGN CRITERIA.

WHERE GYPSUM BOARD ON NON-RATED PARTITIONS IS INDICATED TO EXTEND 6"

ABOVE THE ADJACENT CEILING, IT IS THE OPTION OF THE G.C. TO EXTEND THE

STUDS TO STRUCTURE OR TO BRACE STUDS TO STRUCTURE WITH METAL STUD

KICKERS AT 4'-0" O.C.

PROVIDE U.L. APPROVED PRODUCTS AND MATERIALS WHERE REQUIRED BY

RATING.

APPLY ACOUSTICAL SEALANT ALONG CENTERLINE OF STUD TRACKS TO ENTIRE

PERIMETER OF ALL PARTITIONS INDICATED.

PROVIDE FIRE RATED SEALANT TO BOTH SIDES OF ENTIRE PERIMETER OF FIRE

RATED PARTITIONS.

CONTRACTOR TO STAGGER ALL ELECTRICAL, COMMUNICATION, AND TELEPHONE

AND OTHER SIMILAR WALL BOXES AT MIN. OF 12" O.C. IN SOUND-RATED

PARTITIONS.

G.C. TO PROVIDE FIRE RATED PUTTY PADS ON ALL ELECTRICAL OUTLET BOXES

ON FIRE RATED WALLS.

PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM BOARD ON ALL WALLS AND

CEILINGS OF TOILET ROOMS, MECHANICAL ROOMS, LAUNDRY ROOMS, AND

JANITOR'S CLOSETS.

PROVIDE FIRE-TREATED WOOD BLOCKING OR 18 GAUGE SHEET METAL (WELDED

TO STUDS) WHERE SUPPORT FOR CABINETRY, MILLWORK, TOILET ACCESSORIES,

CLOSET SHELVING, WALL STOPS, ARTWORK, WALL BUMPERS/GUARDS, DRAPERY

CONNECTIONS, AND OTHER SIMILAR CONDITIONS EXIST.

THE U.L. NUMBERS INDICATED REFERENCE THE MOST RECENT FIRE RESISTANCE

DIRECTORY PUBLISHED BY UNDERWRITERS LABORATORIES INC.

ALL THROUGH-WALL PENETRATIONS OF FIRE RATED WALLS/PARTITIONS MUST BE

SEALED W/SEALANT APPROVED BY U.L. FOR PENETRATIONS IN APPLICABLE WALL.

20 GA. DEEP-LEG DEFLECTION TRACKS TO BE PROVIDED AT TOP RUNNERS OF

ALL METAL STUD PARTITIONS THAT EXTEND TO UNDERSIDE OF STRUCTURE.

ALL FIRE RATED PARTITIONS MUST BE IDENTIFIED W/PAINTED STENCILS ABOVE

CEILINGS.

WALLS THAT EXTEND "TO STRUCTURE" SHALL EXTEND TO UNDERSIDE OF

EXISTING ROOF FRAMING.

ALL DIMENSIONS ARE FROM FACE OF FINISHED WALL TO FACE OF FINISHED

WALL.

CONTRACTOR TO VERIFY ALL DIMENSIONS IN FIELD AND NOTIFY ARCHITECT OF

ANY DISCREPANCIES PRIOR TO PARTITION INSTALLATION.

CONTRACTOR TO COORDINATE PARTITION LAYOUT W/M.E.P. WORK AND NOTIFY

ARCHITECT OF ANY DISCREPANCIES PRIOR TO INSTALLATION OF

METAL/PLUMBING SLEEVES AT TIME OF CONCRETE PLACEMENT.

CONTRACTOR TO VERIFY SIZE AND LOCATION OF ALL EQUIPMENT.

COORDINATE LOCATIONS AND COLORS OF ALL LIFE SAFETY ITEMS AND

EQUIPMENT (I.E. FIRE ALARM PULL STATIONS, FIRE STROBES/SPEAKERS,

FIREMAN'S TELEPHONE JACKS, ETC.) WITH INTERIOR DESIGNER PRIOR TO

INSTALLATION.

COORDINATE LOCATIONS AND COLORS OF ALL MECHANICAL ITEMS AND

EQUIPMENT (I.E. THERMOSTATS, GRILLES, SLOT DIFFUSERS, ETC.) WITH INTERIOR

DESIGNER PRIOR TO INSTALLATION.

COORDINATE LOCATIONS, COLORS, AND FINISHES OF ALL ELECTRICAL ITEMS AND

EQUIPMENT (I.E. POWER OUTLETS, PHONE AND DATA OUTLETS, ETC.) WITH

INTERIOR DESIGNER PRIOR TO INSTALLATION.

PARTITION TYPE NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

FURNITURE SHOWN IS NOT IN CONTRACT - SHOWN FOR OWNER CLARITY ONLY.

INTERIOR PARTITIONS ARE DIMENSIONED TO FACE OF WALL UNLESS NOTED

OTHERWISE.

THE HINGE SIDE OF INTERIOR DOOR FRAMES ARE LOCATED 2" FROM FACE OF

ADJACENT WALL (METAL STUD) AND 4" FROM FACE OF ADJACENT WALL (MASONRY)

UNLESS NOTED OTHERWISE.

PROVIDE FIRE-TREATED WOOD BLOCKING IN CAVITY OF METAL STUD PARTITIONS

FOR ALL WALL-MOUNTED ITEMS.

ALL WALLS AND GYPSUM CEILINGS TO BE PT-1 UNLESS OTHERWISE NOTED.

WHERE FLOOR MATERIAL CHANGES IN DOORWAYS, PLACE TRANSITION

UNDERNEATH DOOR LEAF.

ALL INTERIOR HM DOOR FRAMING SHALL BE PT-2 SEMIGLOSS.

WHERE CASEWORK ABUTS ADJOINING WALLS, PROVIDE 1" (MIN, V.I.F.) PLAM FILLER

PANEL BETWEEN CASEWORK AND WALL, TYP.

ALL GRILLES, VENTS, ELECTRICAL PANELS, ACCESS PANELS, ETC. TO MATCH

ADJACENT WALL COLOR UNLESS NOTED OTHERWISE.

ALL BULKHEADS AND SOFFITS TO BE PT-1 UNLESS OTHERWISE NOTED. ALL

CEILING SURFACES SHALL BE FINISHED ON ALL FACES UNLESS NOTED

OTHERWISE. REFER TO REFLECTED CEILINGS PLANS FOR ADDITIONAL

INFORMATION.

ALL RESTROOMS, KITCHEN, AND MECHANICAL/ELECTRICAL SPACES SHALL

RECEIVE AN EPOXY PAINT FINISH.

GENERAL NOTES

PARTITION TO RESIST THE PASSAGE OF SMOKE

PARTITION TYPE TAG

A EXTERIOR WINDOW TAG

KEYED NOTE

1 INTERIOR WINDOW TAG

LEGEND

1 HOUR FIRE…