206.22 - Mech ADDENDUM-1 23-11-01.pdf
PDF 1 MB Posted
- Attached to
- Midwest City Library Chiller Replacement
- Solicitation number
- 24-041-02
- Issued by
- Oklahoma County, Mill Creek Town, Oklahoma
About this file
This document is an Addendum for the Midwest City Library Chiller Replacement project in Oklahoma, specifically detailing mechanical equipment schedules for the HVAC system replacement. The documentation provides comprehensive technical specifications for multiple system components, including a 130-ton air-cooled scroll chiller (CH-1), two chilled water pumps (CHP-1 & 2), an air separator (ADS-1), a glycol make-up unit (GF-1), and a hydronic expansion tank (ET-1). The chiller is specified as a Trane CGAM 130 model with specific performance requirements, including a 15.93 NPLV efficiency rating, 460/3 voltage electrical specifications, and operational parameters for ambient temperatures up to 105°F.
The technical specifications include detailed requirements for each component, such as providing hail guards, a BACnet interface, a 30% polypropylene glycol solution, connection to an existing building automation system, and specific electrical and operational characteristics. Additional notes outline installation requirements like shaft grounding rings, epoxy base grouting, valve replacements, expansion tank modifications, and removal of existing chilled water pump infrastructure. The project appears to be a comprehensive mechanical system upgrade focused on improving the library's HVAC performance and efficiency through targeted equipment replacement and system integration.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M2.0
MECHANICAL
DEMOLITION PLAN
Expiration:
Issue Date:
Drawn by:
Checked by:
6/30/2024 10/26/2023
SHEET TITLE
SHEET No.
M et ro po lit an
L ib ra ry
S ys te m
M id w es t C ity
B ra nc h
- C hi lle r R ep la ce m en t
CA No: CA2192 Project No: 206.22
N . M er ce de s
D riv e Su ite
N or m an , O
K
(4
) 4
-2
2, F ax (4
) 4
-2
WRW
WTA
KEYPLAN
ACI Project No. CA2192 Expires: 6/30/2024
110 N. Mercedes Dr., Suite 100 Norman, Ok 73069-6578
Ph.(405)447-2282, Fax(405)447-2284
206.22
DEMOLITION NOTES:
/0 1/
AD
D
EN
D
U M
M3.0
PARTIAL PIPING
PLAN
Expiration:
Issue Date:
Drawn by:
Checked by:
6/30/2024 10/26/2023
SHEET TITLE
SHEET No.
M et ro po lit an
L ib ra ry
S ys te m
M id w es t C ity
B ra nc h
- C hi lle r R ep la ce m
N . M er ce de s
D riv e Su ite
N or m an , O
K
(4
) 4
-2
2, F ax (4
) 4
-2
WRW
WTA
KEYPLAN
ACI Project No. CA2192 Expires: 6/30/2024
110 N. Mercedes Dr., Suite 100 Norman, Ok 73069-6578
Ph.(405)447-2282, Fax(405)447-2284
206.22
SCOPE OF WORK KEYED NOTES:
/0 1/
AD
D
EN
D
U M
M4.0
MECHANICAL
SCHEDULES &
DETAILS
Expiration:
Issue Date:
Drawn by:
Checked by:
6/30/2024 10/26/2023
SHEET TITLE
SHEET No.
M et ro po lit an
L ib ra ry
S ys te m
M id w es t C ity
B ra nc h
- C hi lle r R ep la ce m
N . M er ce de s
D riv e Su ite
N or m an , O
K
(4
) 4
-2
2, F ax (4
) 4
-2
WRW
WTA
ACI Project No. CA2192 Expires: 6/30/2024 110 N. Mercedes Dr., Suite 100
Norman, Ok 73069-6578 Ph.(405)447-2282, Fax(405)447-2284
206.22
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (90 PSI
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[2 5m m
1" M
AX
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (90 PSI
MIN. DENSITY) UNDER
INSULATION SHIELD
NOTE:
4" CONCRETE
PAD IS EXTG
Chiller Schedule
MARK
CH-1
Notes
TYPE
AIR COOLED SCROLL
PROVIDE HAIL GUARDS.
PROVIDE LOW AMBIENT.
SINGLE POINT POWER.
PROVIDE BACNET INTERFACE.
PROVIDE 30% POLYPROPYLENE GLYCOL SOLUTION.
CONNECT TO EXISTING BAS SYSTEM.
PROVIDE A 300A, FUSED DISCONNECT FOR THE CHILLER.
NOMINAL
TONS
NPLV
15.93
IPLV
16.53
EFFICIENCY
EER
8.604
SOUND
POWER
95% Dba
EVAPORATOR
EWT
LWT
GPM
PD (FT)
17.5
AMBIENT
F
ELECTRICAL DATA
VOLTAGE
460/3
MCA
MOP
OPERATING
WEIGHT
7,900
MANUFACTURER
MODEL
TRANE
CGAM 130
HVAC Pump Schedule - Alt.#1
MARK
CHP-1 & 2
NOTES;
TYPE
END
SUCTION
1. PROVIDE SHAFT GROUNDING RINGS ON MOTOR.
2. PROVIDE EXPOXY BASE GROUT ON BASE MOUNTED PUMPS.
3. SELECTION WITH 30" PROPYLENE GLYCOL.
4. PROVIDE NEW VALVES AND MISC TRIM. REPLACE WITH A 2" PIPE SPOOL AND INSULATE PROPERLY.
5. REPLACE EXISTING EXPANSION TANK AND AIR SEPARATOR.
6. CONNECT TO BAS SYSTEM AND PROGRAM TO ALTERNATE PUMPS.
7. REMOVE CHILLED WATER PUMP AND TRIM IN EAST MECH. ROOM SERVING AHU-2.
8. PROVIDE A 20A, FUSED DISCONNECT FOR BOTH PUMPS.
SERVICE
CHILLED
WATER
GPM
DESIGN
HEAD
FEET
HP
7.5
RPM
VOLTAGE
460/3/60
PUMP
EFFICIENCY
77%
PUMP
WEIGHT
LBS
MANUFACTURER
MODEL
TACO
2509D
REMARKS
PROVIDE VFD; MOUNT ON
WALL BY PUMP
Air Separator Schedule - Alt.#1
MARK
ADS-1
NOTES:
1.
2.
MAX FLOW
(GPM)
PROVIDE MODEL WITH REMOVABLE LOWER HEAD.
PROVIDE AUTOMATIC AIR VENT.
STRAINER
STAINLESS
MAX P.D.
(PSI)
MANUFACTURER/
MODEL
SPIRO THERM / VDN600
WEIGHT
(LBS)
NOTES
1,2
Glycol Make Up Unit Schedule - Alt.#1
MARK
GF-1
NOTES:
CAPACITY
(GPM@psi
10 at 30
1. SYSTEM SHALL BE A PACKAGED AUTOMATIC GLYCOL SOLUTION MAKE UP UNIT WITH DIAPHRAGM EXPANSION TANK, LOW WATER CUTOFF, PRESSURE SWITCH/STARTER, Y-STRAINER ON DISCHARGE, 0-60 PSI PRESSURE GAUGE AND MODEL 3DX-1 VALVE.
TANK
SIZE
GALLON
TANK
DIMENSIONS
58"H x 30"
CONN
SIZE
3/4"NPT
PRESSURE
RANGE
3 to 30
PSI
PUMP DATA
MODEL
RPM
HP
1/2
SIZE
1x1 1/4x6
UNIT
ELECTRICAL
115V/1PH/60
MANUFACTURER
MODEL
BELL & GOSSETT
GMU-30
FLUID
PROPYLENE
GLYCOL
MAX
WEIGHT
650LBS
REMARKS
PROVIDE 3/4" MAKE UP WATER LINE AND
NON THREADED WALL HYDRANT TO FILL TANK.
Hydronic Tank Schedule - Alt.#1
MARK
ET-1
SERVICE
CHILLED WATER
EXPANSION TANK
VOLUME
(GAL)
ACCEPTANCE
(GAL)
MAX
TEMP (F)
TOTAL SYSTEM
VOLUME
GALLONS
MIN
TEMP (F)
MAX
(psi)
PRE-CHARGE
(psi)
FLUID
70% WATER
30% PROP. GLYCOL
WEIGHT
LBS
MANUFACTURER
MODEL
BELL & GOSSETT
B-85
REMARKS
VERTICAL BLADDER
ASME RATED
/0 1/
AD
D
EN
D
U M