206.22 - Mech ADDENDUM-1 23-11-01.pdf

PDF 1 MB Posted

Attached to
Midwest City Library Chiller Replacement
Solicitation number
24-041-02
Issued by
Oklahoma County, Mill Creek Town, Oklahoma

About this file

This document is an Addendum for the Midwest City Library Chiller Replacement project in Oklahoma, specifically detailing mechanical equipment schedules for the HVAC system replacement. The documentation provides comprehensive technical specifications for multiple system components, including a 130-ton air-cooled scroll chiller (CH-1), two chilled water pumps (CHP-1 & 2), an air separator (ADS-1), a glycol make-up unit (GF-1), and a hydronic expansion tank (ET-1). The chiller is specified as a Trane CGAM 130 model with specific performance requirements, including a 15.93 NPLV efficiency rating, 460/3 voltage electrical specifications, and operational parameters for ambient temperatures up to 105°F.

The technical specifications include detailed requirements for each component, such as providing hail guards, a BACnet interface, a 30% polypropylene glycol solution, connection to an existing building automation system, and specific electrical and operational characteristics. Additional notes outline installation requirements like shaft grounding rings, epoxy base grouting, valve replacements, expansion tank modifications, and removal of existing chilled water pump infrastructure. The project appears to be a comprehensive mechanical system upgrade focused on improving the library's HVAC performance and efficiency through targeted equipment replacement and system integration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M2.0

MECHANICAL

DEMOLITION PLAN

Expiration:

Issue Date:

Drawn by:

Checked by:

6/30/2024 10/26/2023

SHEET TITLE

SHEET No.

M et ro po lit an

L ib ra ry

S ys te m

M id w es t C ity

B ra nc h

- C hi lle r R ep la ce m en t

CA No: CA2192 Project No: 206.22

N . M er ce de s

D riv e Su ite

N or m an , O

K

(4

) 4

-2

2, F ax (4

) 4

-2

WRW

WTA

KEYPLAN

ACI Project No. CA2192 Expires: 6/30/2024

110 N. Mercedes Dr., Suite 100 Norman, Ok 73069-6578

Ph.(405)447-2282, Fax(405)447-2284

206.22

DEMOLITION NOTES:

/0 1/

AD

D

EN

D

U M

M3.0

PARTIAL PIPING

PLAN

Expiration:

Issue Date:

Drawn by:

Checked by:

6/30/2024 10/26/2023

SHEET TITLE

SHEET No.

M et ro po lit an

L ib ra ry

S ys te m

M id w es t C ity

B ra nc h

- C hi lle r R ep la ce m

N . M er ce de s

D riv e Su ite

N or m an , O

K

(4

) 4

-2

2, F ax (4

) 4

-2

WRW

WTA

KEYPLAN

ACI Project No. CA2192 Expires: 6/30/2024

110 N. Mercedes Dr., Suite 100 Norman, Ok 73069-6578

Ph.(405)447-2282, Fax(405)447-2284

206.22

SCOPE OF WORK KEYED NOTES:

/0 1/

AD

D

EN

D

U M

M4.0

MECHANICAL

SCHEDULES &

DETAILS

Expiration:

Issue Date:

Drawn by:

Checked by:

6/30/2024 10/26/2023

SHEET TITLE

SHEET No.

M et ro po lit an

L ib ra ry

S ys te m

M id w es t C ity

B ra nc h

- C hi lle r R ep la ce m

N . M er ce de s

D riv e Su ite

N or m an , O

K

(4

) 4

-2

2, F ax (4

) 4

-2

WRW

WTA

ACI Project No. CA2192 Expires: 6/30/2024 110 N. Mercedes Dr., Suite 100

Norman, Ok 73069-6578 Ph.(405)447-2282, Fax(405)447-2284

206.22

SIDE VIEW TRAPEZE HANGER FOR UP TO 1000

LB. [453KG] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE

43 - SEE SPECIFICATIONS

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" [200mm] MIN.)

BAND

1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE

1/2" [15mm] DIA.

HANGER RODS WITH

36" [900mm] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (90 PSI

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

[mm]

FT.

[mm]

FT.

[mm]

[2 5m m

1" M

AX

NOTES:

SEE SPECIFER FOR DETAILED

HANGER REQUIREMENTS

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (90 PSI

MIN. DENSITY) UNDER

INSULATION SHIELD

NOTE:

4" CONCRETE

PAD IS EXTG

Chiller Schedule

MARK

CH-1

Notes

TYPE

AIR COOLED SCROLL

PROVIDE HAIL GUARDS.

PROVIDE LOW AMBIENT.

SINGLE POINT POWER.

PROVIDE BACNET INTERFACE.

PROVIDE 30% POLYPROPYLENE GLYCOL SOLUTION.

CONNECT TO EXISTING BAS SYSTEM.

PROVIDE A 300A, FUSED DISCONNECT FOR THE CHILLER.

NOMINAL

TONS

NPLV

15.93

IPLV

16.53

EFFICIENCY

EER

8.604

SOUND

POWER

95% Dba

EVAPORATOR

EWT

LWT

GPM

PD (FT)

17.5

AMBIENT

F

ELECTRICAL DATA

VOLTAGE

460/3

MCA

MOP

OPERATING

WEIGHT

7,900

MANUFACTURER

MODEL

TRANE

CGAM 130

HVAC Pump Schedule - Alt.#1

MARK

CHP-1 & 2

NOTES;

TYPE

END

SUCTION

1. PROVIDE SHAFT GROUNDING RINGS ON MOTOR.

2. PROVIDE EXPOXY BASE GROUT ON BASE MOUNTED PUMPS.

3. SELECTION WITH 30" PROPYLENE GLYCOL.

4. PROVIDE NEW VALVES AND MISC TRIM. REPLACE WITH A 2" PIPE SPOOL AND INSULATE PROPERLY.

5. REPLACE EXISTING EXPANSION TANK AND AIR SEPARATOR.

6. CONNECT TO BAS SYSTEM AND PROGRAM TO ALTERNATE PUMPS.

7. REMOVE CHILLED WATER PUMP AND TRIM IN EAST MECH. ROOM SERVING AHU-2.

8. PROVIDE A 20A, FUSED DISCONNECT FOR BOTH PUMPS.

SERVICE

CHILLED

WATER

GPM

DESIGN

HEAD

FEET

HP

7.5

RPM

VOLTAGE

460/3/60

PUMP

EFFICIENCY

77%

PUMP

WEIGHT

LBS

MANUFACTURER

MODEL

TACO

2509D

REMARKS

PROVIDE VFD; MOUNT ON

WALL BY PUMP

Air Separator Schedule - Alt.#1

MARK

ADS-1

NOTES:

1.

2.

MAX FLOW

(GPM)

PROVIDE MODEL WITH REMOVABLE LOWER HEAD.

PROVIDE AUTOMATIC AIR VENT.

STRAINER

STAINLESS

MAX P.D.

(PSI)

MANUFACTURER/

MODEL

SPIRO THERM / VDN600

WEIGHT

(LBS)

NOTES

1,2

Glycol Make Up Unit Schedule - Alt.#1

MARK

GF-1

NOTES:

CAPACITY

(GPM@psi

10 at 30

1. SYSTEM SHALL BE A PACKAGED AUTOMATIC GLYCOL SOLUTION MAKE UP UNIT WITH DIAPHRAGM EXPANSION TANK, LOW WATER CUTOFF, PRESSURE SWITCH/STARTER, Y-STRAINER ON DISCHARGE, 0-60 PSI PRESSURE GAUGE AND MODEL 3DX-1 VALVE.

TANK

SIZE

GALLON

TANK

DIMENSIONS

58"H x 30"

CONN

SIZE

3/4"NPT

PRESSURE

RANGE

3 to 30

PSI

PUMP DATA

MODEL

RPM

HP

1/2

SIZE

1x1 1/4x6

UNIT

ELECTRICAL

115V/1PH/60

MANUFACTURER

MODEL

BELL & GOSSETT

GMU-30

FLUID

PROPYLENE

GLYCOL

MAX

WEIGHT

650LBS

REMARKS

PROVIDE 3/4" MAKE UP WATER LINE AND

NON THREADED WALL HYDRANT TO FILL TANK.

Hydronic Tank Schedule - Alt.#1

MARK

ET-1

SERVICE

CHILLED WATER

EXPANSION TANK

VOLUME

(GAL)

ACCEPTANCE

(GAL)

MAX

TEMP (F)

TOTAL SYSTEM

VOLUME

GALLONS

MIN

TEMP (F)

MAX

(psi)

PRE-CHARGE

(psi)

FLUID

70% WATER

30% PROP. GLYCOL

WEIGHT

LBS

MANUFACTURER

MODEL

BELL & GOSSETT

B-85

REMARKS

VERTICAL BLADDER

ASME RATED

/0 1/

AD

D

EN

D

U M