20260730_GPS_BH_Fire Alarm Upgrades_CDs.pdf

PDF 2 MB Posted

Attached to
Fire Alarm Upgrades
Solicitation number
RFP GRPS 270000000035 1
Issued by
Macomb County, Michigan

About this file

This is a set of construction documents for fire alarm upgrades at Baldwin Heights Elementary School operated by Greenville Public Schools in Greenville, Michigan. The project involves the complete replacement of the existing fire alarm system with a new voice-capable, addressable fire alarm system that provides both manual and automatic alarm initiation capabilities. The scope of work includes removal of all existing fire alarm control panels, devices, cabling, and associated accessories from three building units (Unit A, Unit B, and Unit C), followed by installation of new fire alarm components including smoke detectors, heat detectors, duct detectors, door hold-open devices, manual pull stations, notification appliances (strobes and speakers), and a new fire alarm control panel. The construction documents are dated July 30, 2026, and were prepared by Kingscott Associates Inc. (Portage, Michigan) as the architect, with Ignyte Design (Grand Rapids, Michigan) serving as the MEP engineer and Fritz Wahlfield Construction (Comstock Park, Michigan) as the construction manager.

The electrical construction documents establish specific technical requirements for the fire alarm system installation, including conduit sizing (minimum 1/2" trade size), wiring specifications (THHN-2 copper indoors and THWN-2 copper outdoors), mounting heights for various devices, and compliance with the Michigan Electrical Code and NFPA 72 standards. All work must be performed in accordance with applicable building codes and includes provisions for shop drawings, equipment labeling with lamacoid labels, and coordination with existing building systems such as the kitchen hood fire suppression system. The project requires the contractor to procure all necessary building permits and inspections, provide a dedicated 120-volt circuit with lockout-type circuit breaker for the control panel, and ensure proper grounding and surge protection throughout the system installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NO. NAME

GENERAL

G0.1 TITLE SHEET

ELECTRICAL

E000 ELECTRICAL SYMBOLS AND GENERAL NOTES

ED110A FIRST FLOOR ELECTRICAL DEMOLITION PLAN - UNIT A

ED110B FIRST FLOOR ELECTRICAL DEMOLITION PLAN - UNIT B

ED110C FIRST FLOOR ELECTRICAL DEMOLITION PLAN - UNIT C

E110 OVERALL FIRST FLOOR POWER PLAN

E110A FIRST FLOOR POWER PLAN UNIT A

E110B FIRST FLOOR POWER PLAN UNIT B

E110C FIRST FLOOR POWER PLAN UNIT C

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB NO.

SHEET TITLE

SHEET NO.

ISSUANCES DATE

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

N D

C

O P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

E S

A

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

W

IT

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | DETROIT

/3

/2

:2

:1

P

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /G

P S

B a ld w in

H e ig h ts

A rc h r2

.r v t

3197.04A0

TITLE SHEET

G0.1

W

O ak

S tre et

G re en vi lle , M

I 4

G re e n vi lle P u b lic S ch o o ls

B a ld w in H e ig h ts

Fi re A la rm

U p g ra d e s -B

P

Greenville Public Schools

Baldwin Heights - Fire Alarm Upgrades - BP02

SHEET INDEX:

CONSTRUCTION DOCUMENTS

JULY 30, 2026

CLIENT:

GREENVILLE PUBLIC SCHOOLS

1414 CHASE STREET

GREENVILLE, MI 48838

P. (616) 754-3686

ARCHITECT:

KINGSCOTT ASSOCIATES INC.

950 TRADE CENTRE WAY, SUITE 130

PORTAGE, MI 49002

P. (800) 632-7815

CONSTRUCTION MANAGER:

DIRECTORY

FRITZ WAHLFIELD CONSTRUCTION

4455 WESTSHIRE DR

COMSTOCK PARK, MI 49321

P. (616) 784-5833

MEP ENGINEER

IGNYTE DESIGN

38 COMMERCE AVENUE SW

SUITE 450

GRAND RAPIDS, MI 49503

P. (616) 550-5411

CONSTRUCTION DOCUMENTS 07.30.2026

ELECTRICAL ABBREVIATION LIST

ABBREVIATION DESCRIPTION

A

AF

AFCI

A.F.F.

AIC

AL

AR

AT

ATS

AUX

BKR

BPS

C

CB

CKT

CT

DEMO

DIM

DISC

DP

DS

DWG

EBU

EC

ELEC

EM/ EMERG

EMT

EO

EPO

EWC

EXIST

EXT

FA

FLA

FLR

FOH

FSEC

FU

G/GRD/EG

GFCI

GFP

HOA

HP

HV

HZ

IG

JB

KV

KVA

KW

KWH

LA

LP

LDP

AMPERES

AMPERES FRAME (BREAKER RATING)

ARC FAULT CIRCUIT INTERRUPTER

ABOVE FINISH FLOOR

AMPS INTERRUPTING CAPACITY

AUDIENCE LEFT

AUDIENCE RIGHT

AMPERS TRIP (BREAKER SETTING)

AUTOMATIC TRANSFER SWITCH

AUXILIARY

BREAKER

BOLTED PRESSURE SWITCH

CONDUIT

CIRCUIT BREAKER

CIRCUIT

CURRENT TRANSFORMER

DEMOLITION

DIMENSION

DISCONNECT

DISTRIBUTION PANEL

DOWNSTAGE

DRAWING

EMERGENCY BATTERY UNIT

ELECTRICAL CONTRACTOR

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

ELECTRICALY OPERATED

EMERGENCY POWER OFF

ELECTRIC WATER COOLER

EXISTING

EXTERIOR

FIRE ALARM

FULL LOAD AMPS

FLOOR

FRONT OF HOUSE

FOOD SERVICE EQUIPMENT

FUSE

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

HAND-OFF-AUTO

HORSEPOWER

HIGH VOLTAGE

HERTZ

ISOLATED GROUND

JUNCTION BOX

KILOVOLT

KILOVOLT - AMPERES

KILOWATT

KILOWATT - HOURS

LIGHTING ARRESTOR

LIGHTING PANEL

LIGHTING DISTRIBUTION PANEL

MAX

MCB

MCC

MDP

MECH

MIN

MISC.

MLO

MTD

MTG

MTR

N

NC

NEC

NF

NIC

NL

NO

NTS

OC

OFCI

OFOI

P

PB

PH

PT

PDP

RECEPT.

RCP

RDP

RP

RSC

SCHED

SW

SWBD

SWGR

TB

TELECOM

TR

TTP

TYP

UNO

US

V

W

WG

WP

XFMR

XP

(E)

(R)

MAXIMUM

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MECHANICAL

MINIMUM

MISCELLANEOUS

MAIN LUGS ONLY

MOUNTED

MOUNTING

MOTOR

NEUTRAL

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NON-FUSIBLE

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

ON CENTER

OWNER FURNISHED,

CONTRACTOR INSTALLED

OWNER FURNISHED,

OWNER INSTALLED

POLE

PUSHBUTTON STATION

PHASE

POTENTIAL TRANSFORMER

POWER DISTRIBUTION PANEL

RECEPTACLE

RECEPTACLE

RECEPTACLE DISTRIBUTION PANEL

RECEPTACLE PANEL

RIGID STEEL CONDUIT

SCHEDULE

SWITCH

SWITCHBOARD

SWITCHGEAR

TERMINAL BOX

TELECOMMUNICATIONS

TAMPER RESISTANT

TELEPHONE TERMINAL BACKBOARD

TYPICAL

UNLESS OTHERWISE NOTED

UPSTAGE

VOLTS

WIRE OR WATTS

WIRE GUARD

WEATHERPROOF

TRANSFORMER

EXPLOSION PROOF

EXISTING

RELOCATED

ELECTRICAL SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE - ARCHITECTURAL TROFFER

EMERGENCY LIGHTING FIXTURE

LIGHTING FIXTURE - PENDANT

WALL MOUNTED LIGHTING FIXTURE

LIGHTING FIXTURE

LIGHTING TRACK OR ROPE LIGHT

TRACK LIGHTING FIXTURE

EMERGENCY LIGHTING UNIT

POLE MOUNTED LIGHTING FIXTURE

POLE MOUNTED LIGHTING FIXTURE - POST TOP

BOLLARD LIGHTING FIXTURE

EXIT LIGHTING FIXTURE WITH DIRECTIONAL

ARROWS (SHADED AREA INDICATES FACE)

EXIT LIGHTING FIXTURE WITH DIRECTIONAL

ARROWS (SHADED AREA INDICATES FACE)

EXIT LIGHTING FIXTURE - WALL MOUNTED

SINGLE POLE TOGGLE SWITCH

TWO POLE TOGGLE SWITCH

3 WAY TOGGLE SWITCH

4 WAY TOGGLE SWITCH

KEY OPERATED SWITCH

DIMMER SWITCH

PILOT SWITCH

OCCUPANCY SENSOR DEVICE - CEILING

SIMPLEX / DUPLEX RECEPTACLE

SIMPLEX / DUPLEX RECEPTACLE CONTROLLED BY

AUTOMATIC CONTROL DEVICE / SYSTEM

QUAD RECEPTACLE

ABOVE COUNTER DUPLEX RECEPTACLE (SIMILAR FOR

TAMPER RESISTANT, QUADS, EMERGENCY AND GFI

RECEPTACLES)

DUPLEX RECEPTACLE-GROUND FAULT CIRCUIT

INTERRUPTER

DUPLEX EMERGENCY RECEPTACLE

CEILING MOUNTED

DUPLEX RECEPTACLE

SPECIAL RECEPTACLE - REFER TO ELECTRICAL

STANDARD SCHEDULES

MULTI-OUTLET RACEWAY - LEGRAND AL3300 OR EQUAL

POKE-THROUGH ASSEMBLY - LEGRAND

EVOLUTION SERIES OR EQUAL

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

CONTROL PANEL

VARIABLE FREQUENCY DRIVE

MOTOR

MANUAL CONTROLLER

MAGNETIC CONTROLLER

COMBINATION MAGNETIC CONTROLLER

NON-FUSIBLE DISCONNECT SWITCH

FUSIBLE DISCONNECT SWITCH

ENCLOSED CIRCUIT BREAKER

PUSH BUTTON STATION

AUTOMATIC DOOR CONTROLLER

AUTOMATIC DOOR PUSH PAD OPERATOR

GROUND ROD

GROUND CONNECTION

CONDUIT SLEEVE WITH BUSHINGS; LENGTH AS REQUIRED

"X" INDICATES CONDUIT SIZE

CONDUIT STUB - UP/DOWN, 2" CONDUIT UNLESS

NOTED OTHERWISE.

EMPTY BOX FOR FUTURE

TELECOMMUNICATION OUTLET

EMPTY BOX FOR FUTURE TELECOMMUNICATION

OUTLET MOUNTED 4" ABOVE COUNTERTOP

EMPTY BOX FOR FUTURE CEILING MOUNTED

TELECOMMUNICATION OUTLET

TELECOMMUNICATION OUTLET

"X" INDICATES TYPE

SPEAKER

SPEAKER - WALL MOUNTED

MICROPHONE

VOLUME CONTROL

SIGNALING BELL

SINGLE FACE CLOCK - CEILING MOUNTED

SINGLE FACE CLOCK - WALL MOUNTED

DOUBLE FACE CLOCK - CEILING MOUNTED

DOUBLE FACE CLOCK - WALL MOUNTED

P

PT

FB

CP

VFD

CB

DP

PP

X

X

S

S

MIC

VC

B

USB RECEPTACLE

GENERATOR TRANSFER DEVICEGTD

REMOTE GENERATOR ANNUNCIATOR PANELRGP

AUTOMATIC TRANSFER SWITCHATS

SWITCHBOARD

BRANCH CIRCUIT PANEL BOARD - 208/120V

TRANSFORMER

DISTRIBUTION PANEL - 208/120V

SECURITY CAMERA

MOTION DETECTOR

SECURITY KEY SWITCH

DOOR CONTACT

KEY PAD

CARD READER

CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER

MANUALLY/ OPERATED

SWITCH

AUTOMATIC OR MANUAL TRANSFER

SWITCH

FUSE

TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

LIGHTNING ARRESTOR

PANELBOARD

"X" INDICATES PANELBOARD NAME

GROUND

SECURITY KEY INTERLOCK

ENGINE GENERATOR

UTILITY METER

AMMETER

VOLTMETER

AMMETER SWITCH

VOLTMETER SWITCH

SURGE PROTECTIVE DEVICE

TIME DELAY RELAY

THERMAL OVERLOAD RELAY

NORMALLY OPEN CONTACTS

NORMALLY CLOSED CONTACTS

N.O. PUSH BUTTON SINGLE CIRCUIT

N.C. PUSH BUTTON SINGLE CIRCUIT

GROUND BUS

MD

K

DC

KP

CR

X

K

G

M

A

V

AS

VS

SPD

TDR

GB

DURESS PUSH BUTTON STATION

DELAYED EGRESS

DB

DE

REQUEST TO EXIT STATIONREX

MANUAL FIRE ALARM PULL STATION

SMOKE DETECTOR

REMOTE TEST STATION (FOR DUCT DETECTOR)

FIRE ALARM BELL

NOTIFICATION APPLIANCE - WALL MOUNT SPEAKER/STROBE

TAMPER SWITCH

FLOW SWITCH

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

F

SD

RT

F

F

TS

FS

FACP

FAA

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANELNAC

R

E F

E R

T O

E L

E C

T R

IC

L

T

A N

D A

R D

S C

H E

D U

L E

S

DIMMER OCCUPANCY SENSOR SWITCH

LOW VOLTAGE DIMMER SWITCH

POWER POLE - WIREMOLD TYPE

F NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER/STROBE

LIGHTING CONTROL DEVICE - REFER TO LIGHTING

CONTROL SCHEDULE

LC

K

D

OS

LV

GFI

USB

CLG

FLOOR BOX ASSEMBLY - LEGRAND

EVOLUTION SERIES OR EQUAL

TOUCH SCREEN SWITCHTS

OS

OCCUPANCY SENSOR DEVICE - WALLOS

PC PHOTOCELL DEVICE - REFER TO ZONES SHOWN ON

PLANS

EQ

EQUIPMENT CONNECTION - REFER TO ELECTRICAL

FEEDER AND PANEL SCHEDULE FOR BREAKER AND

CONDUCTOR SIZE/QUANTITY

J JUNCTION BOX

EMERGENCY POWER OFF BUTTON

V NOTIFICATION APPLIANCE - CEILING MOUNT STROBE

NOTIFICATION APPLIANCE - WALL MOUNT STROBEV

BRANCH CIRCUIT PANEL BOARD - 480/277V

DISTRIBUTION PANEL - 480/277V

CARBON MONOXIDE DETECTORCO

HEAT DETECTORHD

BEAM DETECTORBD

DUCT DETECTORDD

COMBINATION SMOKE DETECTOR - SMOKE/CARBON MONOXIDESD

S/C

SPRINKLER VALVE MONITOR SWITCHOSY

SMOKE DAMPERSD

MAGNETIC DOOR HOLDERDH

S NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER

NOTIFICATION APPLIANCE - WALL MOUNT SPEAKERS

FIRE ALARM BATTERY CABINETBATT

EXIT FIXTURE-BACK

MOUNTED BOTTOM OF EXIT

SIGN TO BE 4" ABOVE TOP OF

DOOR FRAME

EXIT

EXIT

1' -6

EXIT

A/C SUPPLY

DIFFUSER

90" MAX (IBC)

4' -0

5"

8' -6

EXIT-CEILING MOUNTED

EXIT-FIXTURE END

MOUNTED

NFPA 72 AUDIBLE APPLIANCE 6" MIN

BELOW FINISHED CEILING

EMERGENCY

BATTERY

FIXTURE

ABOVE FINISHED FLOOR

AUDIBLE 80" MIN (IBC)

CEILING HEIGHTS LESS THEN 86" VISUAL

LENS MOUNTING HEIGHT WILL BE WITHIN 6"

OF THE CEILING

FINISHED CEILING

AUDIO/VISUAL &

VISUAL ONLY

DEVICES

SYNCHRONIZE MORE THAN

TWO APPLIANCES IN ANY

FIELD OF VIEW

MANUAL PULL STATION

AUDIBLE

ONLY

'-8

DOOR WIDTH LESS THEN 3'-0"

(MODIFY FOR DIFFERENT

DOOR WIDTHS)

FINISHED FLOOR

O R

A P

P R

O V

E D

F R

O M

A H

J

M

IN

B

O V

E F

IN

IS

H E

D F

L O

O R

CEILING MOUNTED SMOKE/HEAT

DETECTOR

3'-0" MIN 4"

NOTES:

1. INSTALL ELECTRICAL DEVICES AT MOUNTING HEIGHTS NOTED ABOVE UNLESS OTHERWISE NOTED ON PLANS. COORDINATE WITH ALL OTHER DISCIPLINES PRIOR TO INSTALL.

2. VISUAL MOUNTING APPLIANCE MOUNTING HEIGHT IN SLEEPING ROOMS:

A. MINIMUM DISTANCE IN SLEEPING ROOMS IS 24" FROM CEILING TO THE TOP OF LENS FOR 110cd STROBES WITHIN 16' OF PILLOW

B. 177cd STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING, THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER

7' -6

(M

IN

(M

A X

1' -0

"4"

M A

X

DO NOT INSTALL HEAT DETECTOR IN

SHADED AREA

WALL MOUNTED

SMOKE/HEAT

DETECTOR

MAGNETIC

DOOR

HOLDER

FINISHED WALL

SWITCHBANK

AUTOMATIC DOOR OPERATOR PUSH

BUTTON

RECEPTACLE, DATA JACK OR

TELEPHONE JACK

3'-0"

5' MAX TO EXIT DOOR

4' -0

4"

7' -6

ELECTRICAL DEVICE TYPICAL MOUNTING HEIGHTS

6' -6

BRANCH CIRCUIT PANELBOARDS

DISCONNECT SWITCH

5' -0

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :3

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

ELECTRICAL SYMBOLS AND

GENERAL NOTES

E000

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

NOTE: SOME SYMBOLS AND ABBREVIATIONS SHOWN

MAY NOT APPLY TO THIS PROJECT.

GENERAL ELECTRICAL NOTES

1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.

2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.

3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY FUNCTIONAL ELECTRICAL SERVICE.

4. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.

5. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.

6. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:

A. CONDUIT.

B. CONDUCTORS.

C. WIRING DEVICES INCLUDING COVERPLATES.

D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.

E. PANELBOARDS. AND SWITCHBOARDS

F. TRANSFORMERS.

G. SURGE PROTECTION DEVICES

H. POWER METERS.

I. INTERIOR LIGHT FIXTURES.

J. EXTERIOR LIGHT FIXTURES INCLUDING SITE POLES.

K. LIGHTING CONTROL SYSTEM AND DEVICES.

L. FIRE ALARM SYSTEM.

7. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.

8. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.

9. PROVIDE LAMACOID LABELS FOR:

A. PANELBOARDS AND SWITCHBOARDS.

B. TRANSFORMERS.

C. DISCONNECT SWITCHES.

D. VARIABLE FREQUENCY DRIVES.

E. LIGHTING CONTROL PANELS. LABEL SHALL INDICATE ROOMS CONTROLLED.

10. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.

11. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:

A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.

B. OUTDOORS: RIGID GALVANIZED STEEL.

C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.

D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.

12. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.

13. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.

14. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS.

15. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING.

16. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.

17. EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-EMERGNECY CIRCUITS.

18. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUITS OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR VOLTAGE DROP.

19. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.

20. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.

21. PANELBOARDS SHALL BE FULLY RATED, SERIES RATED PANELS ARE NOT ACCEPTABLE. HAVE HINGED SWING DOOR-IN-DOOR. LOAD CENTERS ARE NOT ACCEPTABLE. SQUARE D NQOD OR EQUAL FOR

208/120V BRANCH PANELBOARDS. SQUARE D NF OR EQUAL FOR 480/277V PANELBOARDS. PROVIDE TYPED PANELBOARD CIRCUIT LABEL CARDS. UPDATE ALL EXISTING LABEL CARDS AS REQUIRED.

22. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.

23. ALL FLOOR MOUNTED EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PAD.

24. RECEPTACLES SHALL BE TAMPER-RESISTANT EXTRA HEAVY DUTY GRADE, 20AMP MINIMUM. WHITE IN COLOR UNLESS NOTED OTHERWISE.

25. ALL DEVICE COVERS SHALL MATCH DEVICE COLOR UNLESS STAINLESS STEEL COVERS ARE SPECIFIED.

26. WEATHERPROOF RECEPTACLE COVERS SHALL BE METAL, WHILE-IN-USE TYPE.

27. SWITCHES SHALL BE HEAVY DUTY GRADE, 20 AMP, QUIET TYPE, WHITE UNLESS NOTED OTHERWISE.

28. LIGHTING CONTROL DEVICES SHALL BE MANUFACTURED BY N-LIGHT, UNLESS NOTED OTHERWISE.

29. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013 WITH MICHIGAN AMENDMENTS.

30. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED.

INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL

INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND

LOCAL CODES.

CONSTRUCTION DOCUMENTS 7/30/2026

V

V

V

V

V

V

V

V

VV

V

V

V

F F

F

F

V

V V

FF

SD

SD

DH DH

SD

SD

D

HD

H

V

2 2

2 2 2 2

2 2

UNIT

AUNIT

B

UNIT A

UNIT B

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :3

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN - UNIT A

ED110A

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

ELECTRICAL DEMOLITION KEYED NOTES

1 REMOVE EXISTING FIRE ALARM CONTROL PANEL AND ALL

ASSOCIATED CABLING AND ACCESSORIES. FULL BUILDING FIRE

ALARM SYSTEM TO BE REPLACED IN NEW CONSTRUCTION.

2 REMOVE EXISTING FIRE ALARM DEVICE AND ASSOCIATED CABLING

BACK TO SOURCE. FULL BUILDING FIRE ALARM SYSTEM TO BE

REPLACED IN NEW CONSTRUCTION. PROVIDE STAINLESS STEEL

COVER PLATE OVER EXISTING JUNCTION BOX WHERE DEVICE IS

REMOVED AND NOTE REPLACED IN SAME LOCATION.

CONSTRUCTION DOCUMENTS 7/30/2026

8' 16'4'0

1/8" = 1'-0"ED110A

1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN - UNIT A

DN

F

F

V

F

V

V

V

V V V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

F

SD

SD

D

HD

H

V

V

V

V

V

V

F F

F

F

F

SD SD

DD

DD

DH

DH

F F

F

F

F

2 2 2

2 2

2 2 2 2

AHU-42

UNIT

AUNIT

B

UNIT A

UNIT B

U N

IT

C

U N

IT

B

U N

IT

C

U N

IT

B

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :3

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN - UNIT B

ED110B

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

ELECTRICAL DEMOLITION KEYED NOTES

1 REMOVE EXISTING FIRE ALARM CONTROL PANEL AND ALL

ASSOCIATED CABLING AND ACCESSORIES. FULL BUILDING FIRE

ALARM SYSTEM TO BE REPLACED IN NEW CONSTRUCTION.

2 REMOVE EXISTING FIRE ALARM DEVICE AND ASSOCIATED CABLING

BACK TO SOURCE. FULL BUILDING FIRE ALARM SYSTEM TO BE

REPLACED IN NEW CONSTRUCTION. PROVIDE STAINLESS STEEL

COVER PLATE OVER EXISTING JUNCTION BOX WHERE DEVICE IS

REMOVED AND NOTE REPLACED IN SAME LOCATION.

CONSTRUCTION DOCUMENTS 7/30/2026

8' 16'4'0

1/8" = 1'-0"ED110B

1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN - UNIT B

DN

F F

F A

C P

SD

D D

D D

D D

D D

D D

D D

V

F F

F

F

F

F

F

V

V

V

F

V V

V V

V

V

VV

F F

V

F F

SD

SD

DHDH

F F

D H

D H

F

F F

F F F

F

F F

V

V

F

F

V

V

F F

J

AHU-2

AHU-1

AHU-3

2 2 2 2 2

2 2

2 2

2 2

2 2

2 2

IN MEZZANINE

ABOVE

IN MEZZANINE

ABOVE

IN MEZZANINE

ABOVE

U N

IT

C

U N

IT

B

U N

IT

C

U N

IT

B

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :3

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN - UNIT C

ED110C

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

ELECTRICAL DEMOLITION KEYED NOTES

1 REMOVE EXISTING FIRE ALARM CONTROL PANEL AND ALL

ASSOCIATED CABLING AND ACCESSORIES. FULL BUILDING FIRE

ALARM SYSTEM TO BE REPLACED IN NEW CONSTRUCTION.

2 REMOVE EXISTING FIRE ALARM DEVICE AND ASSOCIATED CABLING

BACK TO SOURCE. FULL BUILDING FIRE ALARM SYSTEM TO BE

REPLACED IN NEW CONSTRUCTION. PROVIDE STAINLESS STEEL

COVER PLATE OVER EXISTING JUNCTION BOX WHERE DEVICE IS

REMOVED AND NOTE REPLACED IN SAME LOCATION.

CONSTRUCTION DOCUMENTS 7/30/2026

8' 16'4'0

1/8" = 1'-0"ED110C

1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN - UNIT C

DN

DN

J

UNIT

AUNIT

B

U N

IT

C

UNIT A

UNIT B

U N

IT

B

U N

IT

C

U N

IT

B

FIRE ALARM CONTROL

PANEL LOCATION

FACP

FIRE ALARM

CONTROL PANEL

F

WP

BUILDING EXTERIOR AT

F.D. CONNECTION

FFVV

S

HORN STROBESSTROBES

SPEAKERS

TO ADDITIONAL

DEVICES

DD

RT

RESET/TEST

STATION

TO ADDITIONAL

DEVICES

SD SD HD

DUCT ELEV SMOKE HEAT

DETECTORS

AT ELEVATOR LANDING(S). COORDINATE

WITH ELEVATOR MANUFACTURER

SD DH F

TO ADDITIONAL

DEVICES SMOKE

DAMPERS

DOOR

HOLDS

PULL

STATIONS

MISCELLANEOUS

SPECIAL CONNECTIONS

FAA

REMOTE

ANNUNCIATOR

(2) DEDICATED PHONE LINES TO

BUILDING PHONE SYSTEM

DEDICATED 120V CIRCUIT; PROVIDE

CIRCUIT BREAKER LOCKOUT

BUILDING

EQUIPMENT

GROUND

IAM

OSY

WF

WATER FLOW

SWITCH

TAMPER

SWITCH

INDIVIDUAL

ADDRESSABLE MODULE

TO ADDITIONAL

DEVICES

ZAM

FS

FIRE

SHUTTER

ZONE ADAPTOR

MODULE

TO ADDITIONAL

DEVICES

BUIDLING LIGHTING

CONTROL SYSTEM

LCS

SD SD

R

5'-0" MAX 15'-0" MAX

FIRE ALARM RELAY FOR SMOKE DAMPER

CONTROL

(REFER TO MECHANICAL PLANS FOR

DAMPER LOCATIONS)

CENTERLINE OF CORRIDOR

DOORS WITH JAMB 24" OR LESS TO CEILING

SHALL HAVE SMOKE DETECTOR WITHIN 5'-0" ON

ONE SIDE OF DOORS AND WITHIN 15'-0" ON OTHER

SIDE

NOTE:

SMOKE DETECTORS TO BE INSTALLED ON ALL FIRE RATED

DOORS (REFER TO ARCHITECTURAL PLANS) AND ALL OTHER

REQUIRED DOORS IN ACCORDANCE WITH NFPA 72

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :3

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

OVERALL FIRST FLOOR

POWER PLAN

E110

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

CONSTRUCTION DOCUMENTS 7/30/2026

0 16' 32'8'

1/16" = 1'-0"E110

1 OVERALL FIRST FLOOR POWER PLAN

1/8" = 1'-0"E110

2 FIRE ALARM SYSTEM RISER DIAGRAM

1/8" = 1'-0"E110

3 CROSS CORRIDOR SMOKE DETECTOR/DAMPER DOOR INTERFACE DETAIL

FF

F F

F F

FF

F

F

F

FF

F

F

V

V F

FF

SD SD

SD

SD SD

SD

F

SD

SD

SD

SD SD

SDSD

SD SD

SD

SD

SD

SD

SD

D H

D H

DH DHSD

F

SD

F

SD

V V

S

SD

F

SD

S

SD

F

SD

V

V

SDSD

1 1

S/C

S/C S/C

S/C

S/C S/C

S/C

S/C

S/C

S/C S/C

S/CS/C

S/C S/C

S/C

S/C

S/C

S/C

S/C

S/C

S/CS/C

S/C

S/C

S/C

S/C

UNIT

AUNIT

B

UNIT A

UNIT B

AREA OF EXPOSED

STRUCTURE

S/C S/C

1 2 31 2 3

1 2 31 2 3

1 2 1 2

3'-0" 3'-0"

4 4

HIGH POINT OF SLOPED

ROOF DECK ABOVE

10 10

10 10

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :4

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

FIRST FLOOR POWER PLAN

UNIT A

E110A

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

8' 16'4'0 1/8" = 1'-0"E110A

1 FIRST FLOOR POWER PLAN - UNIT A

CONSTRUCTION DOCUMENTS 7/30/2026

ELECTRICAL POWER KEYED NOTES

1 PENDANT MOUNT NEW FIRE ALARM DEVICE(S) FROM STRUCTURE

ABOVE. PAINT CONDUIT AND BOX(ES) TO MATCH COLOR OF

STRUCTURE ABOVE.

2 PENDANT MOUNT NEW FIRE ALARM DEVICE(S) WITHIN 12" OF CEILING

DECK ABOVE.

3 PROVIDE SMOKE DETECTION WITHIN 36" HORIZONTALLY FROM PEAK

OF SLOPED ROOF DECK ABOVE.

4 PROVIDE NEW MAGNETIC DOOR HOLD OPEN IN PLACE OF

DEMOLISHED FIRE ALARM DEVICE. TIE DOOR HOLD OPEN TO FIRE

ALARM SYSTEM TO RELEASE DOOR UPON ACTIVATION OF SMOKE

DETECTION.

5 PROVIDE NEW DUCT DETECTOR(S) IN PLACE OF EXISTING. PROVIDE

ALL REQUIRED WIRING AND PROGRAMMING TO PROPERLY SHUT

DOWN MECHANICAL UNIT UPON DETECTION OF SMOKE.

6 INSTALL NEW FIRE ALARM SYSTEM CONTROL PANEL IN PLACE OF

DEMOLISHED EQUIPMENT. NEW FIRE ALARM SYSTEM SHALL BE

VOICE CAPABLE ADDRESSABLE AND PROVIDE MANUAL AND

AUTOMATIC ALARM INITIATION. PROVIDE DEDICATED 120V CIRCUIT

WITH LOCKOUT TYPE CIRCUIT BREAKER.

7 PROVIDE PROTECTIVE WIREGUARD OVER FIRE ALARM DEVICE.

COORDINATE FINAL GUARD SELECTION WITH OWNER.

8 MOUNT FIRE ALARM DEVICE AT TOP OF STAIRS IN MEZZANINE ABOVE.

9 CONNECT EXISTING KITCHEN HOOD FIRE SUPPRESSION SYSTEM TO

NEW BUILDING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED WIRING

AND PROGRAMMING TO MONITOR KITCHEN HOOD FIRE SUPPRESSION.

10 ALTERNATE #1: PROVIDE SEPARATE COST TO INCLUDE SMOKE

DETECTION IN SPACE NOT CURRENTLY LICENSED FOR EARLY

CHILDHOOD.

F

F

F F

F

F F F F

F

F F F

V

V F

F

F

F F

F

F

F

F

F

F

SD

SD SD SD SD SD

SD

SD SD

DH

DH

SD

SD

SD

SD

SD

F

F

SD

F

SD

SD

SD

SD

SDSD

SD SD SD

SD SD

SD

SD

SD

S S F F F

F

F

F

F

SD

F

D H

D H

S

SD

F

SD

V

V

V V

F

DD

DD

S/C

S/C

S/CS/CS/CS/C

S/C

S/C

S/C

S/C

S/C

S/C

S/C

S/CS/C

S/C

S/C

S/C

S/C

S/CS/C

S/C S/C S/C

S/C S/C

S/CS/C

S/C

S/C

S/C

S/C

AHU-4

UNIT

AUNIT

B

UNIT A

UNIT B

U N

IT

C

U N

IT

B

U N

IT

C

U N

IT

B

4 4

10 10 10 10 10

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :4

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

FIRST FLOOR POWER PLAN

UNIT B

E110B

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

ELECTRICAL POWER KEYED NOTES

1 PENDANT MOUNT NEW FIRE ALARM DEVICE(S) FROM STRUCTURE

ABOVE. PAINT CONDUIT AND BOX(ES) TO MATCH COLOR OF

STRUCTURE ABOVE.

2 PENDANT MOUNT NEW FIRE ALARM DEVICE(S) WITHIN 12" OF CEILING

DECK ABOVE.

3 PROVIDE SMOKE DETECTION WITHIN 36" HORIZONTALLY FROM PEAK

OF SLOPED ROOF DECK ABOVE.

4 PROVIDE NEW MAGNETIC DOOR HOLD OPEN IN PLACE OF

DEMOLISHED FIRE ALARM DEVICE. TIE DOOR HOLD OPEN TO FIRE

ALARM SYSTEM TO RELEASE DOOR UPON ACTIVATION OF SMOKE

DETECTION.

5 PROVIDE NEW DUCT DETECTOR(S) IN PLACE OF EXISTING. PROVIDE

ALL REQUIRED WIRING AND PROGRAMMING TO PROPERLY SHUT

DOWN MECHANICAL UNIT UPON DETECTION OF SMOKE.

8' 16'4'0 1/8" = 1'-0"E110B

1 FIRST FLOOR POWER PLAN - UNIT B

CONSTRUCTION DOCUMENTS 7/30/2026

ELECTRICAL POWER KEYED NOTES

6 INSTALL NEW FIRE ALARM SYSTEM CONTROL PANEL IN PLACE OF

DEMOLISHED EQUIPMENT. NEW FIRE ALARM SYSTEM SHALL BE

VOICE CAPABLE ADDRESSABLE AND PROVIDE MANUAL AND

AUTOMATIC ALARM INITIATION. PROVIDE DEDICATED 120V CIRCUIT

WITH LOCKOUT TYPE CIRCUIT BREAKER.

7 PROVIDE PROTECTIVE WIREGUARD OVER FIRE ALARM DEVICE.

COORDINATE FINAL GUARD SELECTION WITH OWNER.

8 MOUNT FIRE ALARM DEVICE AT TOP OF STAIRS IN MEZZANINE ABOVE.

9 CONNECT EXISTING KITCHEN HOOD FIRE SUPPRESSION SYSTEM TO

NEW BUILDING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED WIRING

AND PROGRAMMING TO MONITOR KITCHEN HOOD FIRE SUPPRESSION.

10 ALTERNATE #1: PROVIDE SEPARATE COST TO INCLUDE SMOKE

DN

DN

F

F F F F F F

F

F

F F S S F S S F

F

F

V V

F

F

S

F

F F

F

F F

F

F

F

F

F

F

F

F

F

F

F

SD SD SD SD SD SD

SD

SD

SD

SD

SD

SD

DHDH

DH

DH

DH

DH

D H

D H

SD

SD SD

SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD SD

SD SD

SD

SD

SD

SD

F F

F A

C P

F

V

F SD F SD

V

SD SD SD SD SD

SD

F

F

F F

F

V

F SD

V

F

F

F

F

SD

F

D D

D D

D D

D D

D D

D D

F

F

J

S/C S/C S/C S/C S/C S/C

S/C

S/C

S/C

S/C

S/C

S/C

S/C

S/C, WG S/C, WG

S/C S/C

S/C

S/C

S/C S/C

S/C

S/C

S/C

S/C

S/C

S/C

S/C

S/C, WG S/C, WG

S/C, WG S/C, WG

S/C

S/C

S/C

S/C

S/C S/C

S/C S/C S/C S/C S/C

S/C

S/C

S/C

WG

WG

AHU-2

AHU-1

IN MEZZANINE

ABOVE

IN MEZZANINE

ABOVE

AHU-3

IN MEZZANINE

ABOVE

U N

IT

C

U N

IT

B

U N

IT

C

U N

IT

B

4 4

4 4

1 2 7 1 2 7

1 2 7 1 2 7

1 2 7 1 2 7

WG

WG

10 10 10 1010

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB

SHEET TITLE

SHEET NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | ROYAL OAK

/3

/2

:4 :4

A

M

A u to d e s k D o c s

/G P

S

S in k in g F u n d

B a ld w in

H e ig h ts

E le m e n ta ry /X

K

G A

B

A L D

W

IN

H E

IG

H

T S

E L E

M E

N T

A R

Y .r v t

26.XX

FIRST FLOOR POWER PLAN

UNIT C

E110C

W

O a k S t, G re e n vi lle

M I

G R

E E

N V

IL

L E

P U

B L

IC

S

C H

O O

L S

B A

L D

W

IN

H E

IG

H

T S

E L

E M

E N

T A

R Y

F

IR

E A

L A

R M

8' 16'4'0 1/8" = 1'-0"E110C

1 FIRST FLOOR POWER PLAN - UNIT C

CONSTRUCTION DOCUMENTS 7/30/2026

ELECTRICAL POWER KEYED NOTES

1 PENDANT MOUNT NEW FIRE ALARM DEVICE(S) FROM STRUCTURE

ABOVE. PAINT CONDUIT AND BOX(ES) TO MATCH COLOR OF

STRUCTURE ABOVE.

2 PENDANT MOUNT NEW FIRE ALARM DEVICE(S) WITHIN 12" OF CEILING

DECK ABOVE.

3 PROVIDE SMOKE DETECTION WITHIN 36" HORIZONTALLY FROM PEAK

OF SLOPED ROOF DECK ABOVE.

4 PROVIDE NEW MAGNETIC DOOR HOLD OPEN IN PLACE OF

DEMOLISHED FIRE ALARM DEVICE. TIE DOOR HOLD OPEN TO FIRE

ALARM SYSTEM TO RELEASE DOOR UPON ACTIVATION OF SMOKE

DETECTION.

5 PROVIDE NEW DUCT DETECTOR(S) IN PLACE OF EXISTING. PROVIDE

ALL REQUIRED WIRING AND PROGRAMMING TO PROPERLY SHUT

DOWN MECHANICAL UNIT UPON DETECTION OF SMOKE.

ELECTRICAL POWER KEYED NOTES

6 INSTALL NEW FIRE ALARM SYSTEM CONTROL PANEL IN PLACE OF

DEMOLISHED EQUIPMENT. NEW FIRE ALARM SYSTEM SHALL BE

VOICE CAPABLE ADDRESSABLE AND PROVIDE MANUAL AND

AUTOMATIC ALARM INITIATION. PROVIDE DEDICATED 120V CIRCUIT

WITH LOCKOUT TYPE CIRCUIT BREAKER.

7 PROVIDE PROTECTIVE WIREGUARD OVER FIRE ALARM DEVICE.

COORDINATE FINAL GUARD SELECTION WITH OWNER.

8 MOUNT FIRE ALARM DEVICE AT TOP OF STAIRS IN MEZZANINE ABOVE.

9 CONNECT EXISTING KITCHEN HOOD FIRE SUPPRESSION SYSTEM TO

NEW BUILDING FIRE ALARM SYSTEM. PROVIDE ALL REQUIRED WIRING

AND PROGRAMMING TO MONITOR KITCHEN HOOD FIRE SUPPRESSION.

10 ALTERNATE #1: PROVIDE SEPARATE COST TO INCLUDE SMOKE

Sheets
G0.1 - TITLE SHEET

File details come from the government source that posted it. Updated .