This document is a set of bid documents comprising architectural, structural, mechanical, plumbing, fire protection, and electrical construction drawings for a renovation project at the Louis A. Johnson VA Medical Center in Clarksburg, West Virginia.
The project (No. 540-18-020) involves renovating the pharmacy to achieve USP 800 Compliance. Work includes demolition and new construction on the partial basement and sixth floor, with associated roof modifications on the fourth floor. Key scope elements encompass new wall framing and partitions, mechanical systems including HVAC equipment and ductwork, plumbing systems including new piping and fixtures, fire protection sprinkler modifications, and electrical systems including lighting, power distribution, and control systems. The project requires coordination across multiple trades with infection control barriers (Level IV ICRA) to be installed prior to work commencement. Structural work involves steel framing for equipment support, concrete slab repairs, and foundation modifications. Mechanical systems include new air handling units, chilled water coils, heating coils, exhaust fans, and associated controls. Fire protection work includes sprinkler head relocation and new piping. Electrical work requires new panelboards, lighting fixtures, receptacles, and control systems. The drawings indicate the facility is fully sprinklered and the project must maintain fire-rated assemblies and life safety requirements throughout construction. Submittals, shop drawings, and coordination with the Contracting Officer's Representative are required prior to fabrication and installation of all components.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 540-18-020 Addendum No. 2 .pdf | ||
| 36C24526B0001 0008.docx | DOCX document | |
| 36C24526B0001 0007.docx | DOCX document | |
| 36C24526B0001 0006.docx | DOCX document | |
| 36C24526B0001 0005.docx | DOCX document | |
| Record of Attendance - 2nd Site Visit - 5-13-2026 Pharmacy USP 800.pdf | ||
| 36C24526B0001 0004.docx | DOCX document | |
| 540 05 401 As-Builts.pdf | ||
| 540-18-020 Addendum No. 1 .pdf | ||
| REVISED BID SCHEDULE.docx | DOCX document | |
| 540-18-020 Asbestos and Hazmat Testing Report.pdf | ||
| 36C24526B0001 0003.docx | DOCX document | |
| 36C24526B0001 0002.docx | DOCX document | |
| Record of Attendance - Site Visit- Pharmacy USP 800 Upgrade - 4-1-2026.pdf | ||
| 36C24526B0001 0001.docx | DOCX document | |
| SAM Wage Determination WV20260011 1-2-2026.pdf | ||
| Bid Doc Specs Vol 2.pdf | ||
| LIMITATIONS ON SUBCONTRACTING-CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION.pdf | ||
| Bid Doc Specs Vol 1.pdf | ||
| 36C24526B0001_1.docx | DOCX document | |
| PCRA USP800 - AD signed.pdf |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET INDEX
GI001
SHEET
NO. DRAWING TITLE
GENERAL
GI002
ARCHITECTURAL
SHEET
NO.
COVER SHEET
GENERAL NOTES, DETAILS, ABBREVIATIONS AND LEGENDS
PARTIAL BASEMENT PLANAE101
RENOVATE PHARMACY FOR USP COMPLIANCE
PROJECT NUMBER: 540-18-020
BID DOCUMENTS
LOUIS A. JOHNSON VA MEDICAL CENTER
CLARKSBURG, WV
PARTIAL BASEMENT DEMOLITION PLANAD101
LOCATION MAP
NOT TO SCALE
AREA MAP
NOT TO SCALE
PROJECT LOCATION PROJECT LOCATION
TRUE
NORTH
PLAN
NORTH
TRUE
NORTH
PLAN
NORTH
PARTIAL SIXTH FLOOR, REFLECTED CEILING AND ROOF DEMOLITION PLANAD102
PARTIAL BASEMENT DEMOLITION REFLECTED CEILING PLANAD111
PARTIAL SIXTH FLOOR, REFLECTED CEILING AND ROOF PLANAE102
PARTIAL BASEMENT REFLECTED CEILING PLANAE111
GI003 INFECTION CONTROL PLANS
ROOM FINISH SCHEDULE, PARTITION TYPES AND DETAILSAE601
DOOR SCHEDULE AND DETAILSAE611
ENLARGED FLOOR PLANS, EQUIPMENT AND SIGNAGE SCHEDULESAE401
INTERIOR ELEVATIONSAE451
PARTIAL FOURTH FLOOR DEMOLITION ROOF PLANAD121
PARTIAL FOURTH FLOOR ROOF PLANAE121
STRUCTURAL
STRUCTURAL NOTESS001
BASEMENT FOUNDATION PLANS101
ROOF AND FLOOR FRAMING PLANSS102
STEEL DETAILSS501
PLUMBING ABBREVIATIONS, LEGENDS, SCHEDULES & NOTESP-001
PLUMBING
PLUMBING PARTIAL UNDERGROUND PLAN - DEMOPD-100
PLUMBING PARTIAL BASEMENT FLOOR PLAN - DEMOPD-101
PLUMBING PARTIAL BASEMENT FLOOR PLAN - NEW WORKP-101
PLUMBING PARTIAL SIXTH FLOOR PLAN - NEW WORKP-102
PLUMBING DETAILSP-501
SEISMIC BRACING DETAILSP-502
MECHANICAL LEGEND, ABBREVIATIONS, AND NOTESM001
MECHANICAL
MECHANICAL NOTESM002
PARTIAL BASEMENT DUCT - DEMOLITION PLANMD101
PARTIAL BASEMENT PIPING - DEMOLITION PLANMD102
PARTIAL ROOF DUCT AND PIPING - DEMOLITION PLANMD103
PARTIAL SIXTH FLOOR AND ROOF DUCT AND PIPING - DEMOLITION PLANMD104
PARTIAL BASEMENT AND SIXTH FLOOR AIRFLOW AND PRESSURE PLAN - NEW WORK PLANM100
PARTIAL BASEMENT DUCTWORK - NEW WORK PLANM101
PARTIAL BASEMENT PIPING - NEW WORK PLANM102
PARTIAL ROOF DUCT AND PIPING - NEW WORK PLANM103
PARTIAL SIXTH FLOOR AND ROOF DUCT AND PIPING - NEW WORK PLANM104
ENLARGED, SECTION, AND ISOMETRIC MECHANICAL PLAN - NEW WORK PLANM401
HVAC DETAILSM501
M502 MECHANICAL PIPING DETAILS
M503
MECHANICAL SCHEDULESM601
VA STATION GENERAL CONTROL NOTES AND LEGENDM800
CONTROL SCHEMATIC, SEQUENCE OF CONTROL, AND CONTROL POINT - MECHANICALM801
CONTROL SCHEMATIC, SEQUENCE OF CONTROL, AND CONTROL POINT - MECHANICALM802
ELECTRICAL GENERAL NOTES AND ABBREVIATIONSE001
ELECTRICAL
ELECTRICAL LEGENDE002
ELECTRICAL PARTIAL BASEMENT PLANSEE101
ELECTRICAL PARTIAL SIXTH FLOOR, RCP AND ROOF PLANEE102
ELECTRICAL DETAILSEE501
ELECTRICAL SCHEDULESEE612
FIRE PROTECTION ABBREVIATIONS, LEGEND & NOTESFP-001
FIRE PROTECTION
FIRE PROTECTION PARTIAL SIXTH FLOOR PLAN - DEMO & NEW WORK
FP-101
FP-102
FIRE PROTECTION PARTIAL BASEMENT FLOOR PLAN - DEMOFD-101
FIRE PROTECTION SEISMIC BRACING DETAILSFP-501
FIRE PROTECTION PARTIAL BASEMENT FLOOR PLAN - NEW
ELECTRICAL PARTIAL BASEMENT DEMO PLANED101
ED102 ELECTRICAL PARTIAL SIXTH FLOOR, RCP, AND ROOF DEMO PLAN
LOW VOLTAGE PLANSEE103
MISCELLANEOUS DETAILSAE501
MECHANICAL DETAILS
PARTIAL BASEMENT AND SIXTH FLOOR LIFE SAFETY PLANSLS101
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
JH SJ/KB
540-18-020
03-13-2026REVISIONS:
A
B
C
D
E
F
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
COVER SHEET
GI001
sjeffries Snapshot
ARCHITECTURAL ABBREVIATIONSARCHITECTURAL LEGEND
GENERAL ARCHITECTURAL NOTES
GENERAL PROJECT NOTES
A
GA4
A301
A201
A401
ROOM
NAME
+ 0'-6"
F.E.C.
AIR CONDITIONING
ACOUSTICAL CEILING TILE
ABOVE FINISH FLOOR
ALUMINUM
BATT INSULATION
BOTTOM OF
CEMENTITIOUS BACKER BOARD
CEMENTITIOUS CRYSTALLINE WATERPROOFING
COLD-FORMED METAL FRAMING
CORNER GUARD
CENTERLINE
CONCRETE MASONRY UNIT
CASED OPENING
COMMUNICATION
CONCRETE
SEALED CONCRETE
CONTINUOUS
CONTRACTING OFFICER'S REPRESENTATIVE
CERAMIC TILE
CERAMIC TILE BASE
CARPET
DIAMETER
EXPANSION JOINT
ELECTRICAL
EPOXY FLOORING
EXPOSED STRUCTURE
ET CETERA
EXISTING
EXPOSED
FACTORY FINISH
FLOOR DRAIN
FIRE EXTINGUISHER CABINET
FIRE HOSE CABINET
FINISHED FLOOR
FINISH
FLOOR
FACE OF
FIELD VERIFY
FABRIC WALLCOVERING
GAGE
GRANITE
GYPSUM (WALL) BOARD
HANDICAPPED
HOLLOW METAL
HANDRAIL
HEATING VENTILATION AND AIR-CONDITIONING
MATERIAL
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
MASONRY OPENING
METAL
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
PLASTER
PLASTIC LAMINATE
PORCELAIN TILE
PAIR
PAINT
QUARRY TILE
RESILIENT BASE
REFRIGERATOR
REQUIRED
RESINOUS FLOORING
RESINOUS EPOXY WALL-CEILING
ROUGH OPENING
RUBBER FLOORING
RECESSED PAPER HOLDER
SEALED HIGH BUILD GLAZED COATING
SOLID CORE WOOD
SIMILAR
SPECIAL FACED
STAINLESS STEEL
STEEL
SUBSTRATE
SHEET VINYL
SOLID VINYL TILE
TELEPHONE
TOP OF
TYPICAL
UNLESS NOTED OTHERWISE
VINYL COMPOSITION TILE
VINYL WALL COVERING
WALL COVERING
WALL PROTECTION
WOOD
WELDED SEAM SHEET FLOORING
AC
AT
AFF
AL
BATT
BO
CBB
CCW
CFMF
CG
C
CMU
CO
COMM
CONC
SCONC
CONT
COR
CT
CTB
CP
DIA
EJ
ELEC
EPY
ES
ETC
EXIST
EXP
FAC FIN
FD
FEC
FHC
FF
FIN
FLR
FO
FV
FWC
GA
GRA
GYP BD/GWB
HC
HM
HR
HVAC
MATL
MAX
MECH
MFR
MIN
MO
MTL
NIC
NTS
OC
OH
PLS
PL
PT
PR
P
QT
RB
REF
REQ'D
RES
RES-W
RO
RF
RPH
SC
SCW
SIM
SP
SS
STL
SUBS
SV
SVT
TELE
TO
TYP
UNO
VCT
VWC
WC
WP
WD
WSF
L
FIRE EXTINGUISHER CABINET
ROOM NAME AND NUMBER
DOOR NUMBER
KEY NOTE
WINDOW TYPE
PARTITION TYPE
DETAIL CALLOUT
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
SECTION CALLOUT
VERTICAL ELEVATION
COLUMN CENTERLINE DESIGNATION
DEMOLITION KEY NOTE
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
INTERIOR ELEVATION CALLOUT
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
CARD READERCR
HIGH-PRESSURE LAMINATEHPL
LUXURY VINYL TILELVT
EDGE OF DECKEOD
DOWNSPOUTDS
CONTROL JOINTCJ
DRINKING FOUNTAINDF
FIRE RETARDANT TREATEDFRT
EXTERIOR INSULATION FINISHING SYSTEMEIFS
WATER RESISTANTWR
EQUALEQ
CARPET TILECPT
REFLECTED CEILING PLANRCP
SOLID SURFACE MATERIALSSM
X1045 EQUIPMENT AND ACCESSORY TAG
ALUMINUM COMPOSITE METAL PANELSACMP
A. DIMENSIONS, UNLESS OTHERWISE INDICATED, ARE TO:
• FACE OF EXISTING WALL SURFACE
• FACE OF MASONRY
• FACE OF WALL STUDS
• TOP OF SLAB
• TOP OF MASONRY
• ALIGN WALLS WITH EXISTING WHERE NOT OTHERWISE INDICATED.
B. COORDINATE WITH ALL DISCIPLINES DRAWINGS FOR ADDITIONAL REQUIREMENTS.
COORDINATE OPENINGS IN SLABS, ROOF, AND WALLS. WHERE NEW HOLES IN EXISTING
WALLS AND SLABS ARE CREATED FOR PENETRATIONS, COORDINATE SIZE AND LOCATION.
PATCH HOLES CAUSED BY THE REMOVAL OF EQUIPMENT, PIPING, CONDUIT, DUCT,
GRILLES, ETC. WITH MATERIALS MATCHING EXISTING SLAB OR WALL IN STRUCTURE,
MATERIAL, THICKNESS, ALIGNMENT, GRADES, AND QUALITY.
C. COORDINATE AND PROVIDE GALVANIZED METAL BACKER PLATE OR SOLID FIRE
RETARDANT TREATED WOOD BLOCKING FOR WALL-MOUNTED ITEMS. COORDINATE
LOCATIONS WITH COR FOR GOVERNMENT PROVIDED/CONTRACTOR INSTALLED
EQUIPMENT.
D. `PROVIDE' IS DEFINED AS PROVIDING MATERIALS, DELIVERY, STORAGE, HANDLING,
INSTALLATION, ADJUSTMENT, AND CLEANING FOR THE ITEM INDICATED.
E. SEAL PIPE PENETRATIONS THROUGH SLABS, MASONRY, SMOKE RATED PARTITIONS AND
FIRE-RATED PARTITIONS WITH THE APPROPRIATE FIRESTOP TO MAINTAIN THE RATING OF
THE WALL OR SLAB. SUBMIT CUT SHEETS AND SPECIFICATIONS TO THE COR FOR
APPROVAL PRIOR TO INSTALLATION. PROVIDE UL LISTED ASSEMBLIES.
F. SKIM COAT ALL DAMAGED EXISTING WALL SURFACES THAT REQUIRE PAINTING.
G. REMOVED MATERIALS WHICH ARE INDICATED TO BE TURNED OVER TO THE COR SHALL BE
DELIVERED BY THE CONTRACTOR TO A PLACE INDICATED BY THE COR .
H. REMOVE COMPLETELY ALL MATERIALS AS INDICATED ON THE DRAWINGS AND AS
REQUIRED FOR NEW CONSTRUCTION. EDGES AND FACES OF REMOVED AREAS SHALL BE
REPAIRED TO ACCEPT NEAT INSTALLATION OF NEW CONSTRUCTION OR FINISHES. WHERE
EXISTING MATERIALS ARE TO BE REPLACED (WALLS, INSULATION, FLOORING, ETC.)
EXISTING MATERIALS, ADHESIVES, ETC. SHALL BE REMOVED AND EXPOSED SURFACES
SHALL BE PREPARED AS INDICATED OR SPECIFIED PRIOR TO INSTALLATION OF
MATERIALS.
I. PREVENT DAMAGE TO MATERIALS AND FINISHES TO REMAIN. REPAIR DAMAGES FROM
CONSTRUCTION ACTIVITIES TO EXISTING ITEMS TO REMAIN, AT NO ADDITIONAL COST
WHERE SUCH EXPOSED MATERIALS OR FINISHES TO REMAIN ARE DAMAGED.
J. SEAL ALL PLATES, COVERS, DEVICES; AND GENERAL FLOOR, WALL AND CEILING
PENETRATIONS IN ALL SPACES, TYPICAL.
A. THE CONTRACTOR SHALL BE PREPARED TO STOP ANY WORK AND CLEAN UP THE WORK AREA
AS DIRECTED IN MEDICAL SITUATIONS REQUIRING SUCH ACTION.
B. THE CONTRACTOR SHALL NOT ORDER OR INSTALL ANY MATERIALS OR EQUIPMENT UNTIL
SUBMITTALS FOR SUCH HAVE BEEN APPROVED.
C. ALL TOOLS AND MATERIALS USED IN THIS PROJECT SHALL BE PROPERLY SECURED AT ALL
TIMES BY THE CONTRACTOR TO REDUCE THE POSSIBILITY OF ANY OF THESE TOOLS BEING A
HAZARD TO PATIENTS, VISITORS AND STAFF.
D. THE CONTRACTOR WILL BE RESPONSIBLE FOR ACQUIRING I.D. BADGES FOR EACH MEMBER OF
HIS WORK FORCE. VALID FORMS OF I.D. ARE REQUIRED TO RECEIVE BADGES. COORDINATE
WITH COR.
E. THE CONTRACTOR, AT HIS EXPENSE, WILL BE RESPONSIBLE FOR TRAINING EACH MEMBER OF
HIS WORK FORCE ON VA POLICIES FOR ON-SITE WORK BEFORE ANY MEMBER WILL BE
ALLOWED TO PERFORM WORK ON VA PREMISES.
F. ABSOLUTELY NO VA TOOLS, MATERIALS OR EQUIPMENT WILL BE LOANED OR GIVEN BY THE VA
TO ANY MEMBER OF THE CONTRACTOR'S WORK FORCE AT ANY TIME.
G. ANY SMOKE DETECTORS HAVING ANY POTENTIAL FOR EXPOSURE TO CONSTRUCTION SMOKE,
DUST AND DEBRIS SHALL BE SUITABLY PROTECTED TO PREVENT ACCIDENTAL ALARM DURING
CONSTRUCTION. ALL SUCH ACTION MUST BE FIRST COORDINATED AN CLEARED WITH THE COR
AND THE VA SAFETY OFFICER. ALL FUNCTIONAL FIRE ALARM DEVICES SHALL BE ACTIVE
WHENEVER THE CONTRACTOR'S FORCES ARE NOT PRESENT IN THE WORK AREA.
H. THE CONTRACTOR MUST PROVIDE WRITTEN FIRE SAFETY CHECKLIST AT THE END OF EVERY
WORK DAY TO THE COR CERTIFYING THAT ALL WORK AREAS HAVE BEEN SURVEYED AND
FOUND TO BE SECURE, SAFE AND FREE OF ANY FLAMMABLE LIQUIDS.
I. CONTRACTOR SHALL COORDINATE ONLY WITH THE COR AND CONTRACTING OFFICER.
J. SEE SPECIFICATIONS SECTIONS 01 00 00 AND 01 35 26 FOR INTERIM LIFE SAFETY MEASURES.
K. ALL FINISH COLORS TO BE SELECTED BY COR/ VA INTERIOR DESIGNER WHERE NOT
OTHERWISE INDICATED. CONTRACTOR SHALL SUBMIT COLORS FROM THE MANUFACTURER'S
FULL RANGE OF COLORS.
L. PROVIDE 24"X24" ACCESS PANELS IN HARD CEILINGS WHERE DUCTS AND DAMPERS OR OTHER
PIPES REQUIRE ACCESS AS REQUIRED. COORDINATE EXACT LOCATIONS WITH THE COR.
M. THE CONTRACTOR SHALL NOT OPERATE ANY EXISTING VA EQUIPMENT WITHOUT
AUTHORIZATION FROM VAMC ENGINEERING SERVICE UNLESS AN EMERGENCY SITUATION
OCCURS.
N. CONTRACTOR SHALL MAINTAIN ALL FIRE-RATED ASSEMBLIES WITHIN THE PROJECT AREA
DURING PERFORMANCE OF THE WORK.
O. CONTRACTOR SHALL PROVIDE AND MAINTAIN ALL REQUIRED EXIT LIGHTING AND SIGNAGE
REQUIRED FOR EGRESS WITHIN AND ADJACENT TO THE PROJECT AREA DURING
PERFORMANCE OF THE WORK.
P. INDICATED EXISTING CONDITIONS ARE BASED UPON LIMITED FIELD INVESTIGATION AND DID
NOT INCLUDE DESTRUCTIVE INVESTIGATION OR TESTING. CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS INCLUDING DIMENSIONS OF THE INSTALLED CONSTRUCTION PRIOR TO
COMMENCING WITH THE WORK. IF DISCREPANCIES ARE DISCOVERED, THE CONTRACTOR
SHALL NOTIFY THE COR FOR INTERPRETATION AND DIRECTION PRIOR TO PROCEEDING WITH
THE WORK.
Q. COORDINATE WORK WITH EQUIPMENT SUPPLIER/ INSTALLER CONTRACTED SEPARATELY WITH
THE GOVERNMENT.
CODE SUMMARY
1. VA DESIGN GUIDES – TECHNICAL INFORMATION LIBRARY
2. PG 18-3 VA DESIGN AND CONSTRUCTION PROCEDURES, TOPIC 1
3. 2018 NPFA 1 FIRE CODE
4. 2018 NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS
5. 2018 NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
6. 2018 NFPA 70 NATIONAL ELECTRIC CODE (NEC)
7. 2018 NFPA 72 NATIONAL FIRE ALARM SIGNALING CODE
8. 2018 NFPA 90A INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS
9. 2018 NFPA 90B INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING SYSTEMS
10. 2018 NFPA 101 LIFE SAFETY CODE (LSC)
11. 2018 NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION
12. 2018 INTERNATIONAL BUILDING CODE (IBC)
13. 2018 INTERNATIONAL PLUMBING CODE (IPC)
14. 2018 INTERNATIONAL MECHANICAL CODE (IMC) AND ASHRAE 90.1
15. 2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
16. ARCHITECTURAL BARRIES ACT ACCESSIBILITY STANDARDS (ABAAS)
17. VA BARRIER FREE DESIGN GUIDE (PG-18-13)
18. RESOURCE CONSERVATION AND RECOVERY ACT (RCRA) (42 U.S.C.6901, ET SEQ)
19. THE NATIONAL ENERGY CONSERVATION POLICY ACT
20. EXECUTIVE ORDER 131468 PF APRIL 21, 2000, GREENING THE GOVERNMENT THROUGH
LEADERSHIP IN ENVIRONMENTAL MANAGEMENT.
21. EXECUTIVE ORDER 13101 OF SEPTEMBER 14, 1998, GREENING THE GOVERNMENT THROUGH
WASTE PREVENTION, RECYCLING, AND FEDERAL ACQUISITION; AND EXECUTIVE ORDER 13123
OF JUNE 1999, GREENING THE GOVERNMENT THROUGH EFFICIENT ENERGY MANAGEMENT.
SIGNAGE TYPE1
ACCESSIBILITY REQUIREMENTS
FRONT APPROACHES
HINGE-SIDE APPROACHES
LATCH-SIDE APPROACHES
USE EITHER
OPTION 1 OR
OPTION 2
ALL DOOR ASSEMBLIES SHALL BE CONSTRUCTED TO MEET THE
INDICATED MINIMUM CLEARANCES AS APPLICABLE.
1'-0" IF DOOR HAS BOTH
A CLOSER AND A
LATCH
5' -0
1'-6"
3' -6
4'-6"
4' -0
O P
TI
O
N
5' -0
OPTION 1
3'-0"
O P
TI
O
N
4' -6
OPTION 2
3'-6"
2'-0"
4' -0
2'-0"
3' -6
4' -0
4' -6
W / C
LO
S
E R
4' -0
W / C
LO
S
E R
W /C
LO
S
E R
A N
D L
A
TC
H
ALL WORK SHALL COMPLY WITH FEDERAL ABA,
LOCAL, AND STATE ACCESSIBILITY CODES AND
REQUIREMENTS.
DOOR LOCATIONS
TYPICAL DETAILS
TYP DOOR LOCATION
SEE DOOR SCHEDULE
4"
TYP
TYPICAL SIGNAGE MOUNTING HEIGHTS
A A
5' -0
4' -9
EQ EQ
MOUNTING HEIGHTS
PROVIDE BLOCKING AT ALL WALL MOUNTED EQUIPMENT AND ACCESSORIES
3' -4
3' -8
CL
CL
FEC GARMENT
HOOK
TYPICAL SCRUB SINK
PAPER
TOWEL
DISPENSER
3' -5
3' -6
SOAP
DISPENSER
3' -6
APRON/GLOVE
RACK
2' -1
0"
TOILET
ROOM SHELF
ELECTRIC
HAND DRYER
3' -7
3' -6
PASS-THROUGH
CABINET
2' -1
0"
1'-6"
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
JH SJ/KB
540-18-020
03-13-2026REVISIONS:
A
B
C
D
E
F
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
GENERAL NOTES, DETAILS, ABBREVIATIONS
AND LEGENDS
GI002
UP
AF AE
AAABACAD
A8
A7
A7.9
15 16 17 18 19 20 21 22
L
J
F
TABLE TABLE TABLE
TABLE
T A
B L E
BIO SAFETY
CABINET
BIO SAFETY
CABINET
BIO
SAFETY
CABINET
REF
REF
AHU
OFFICE
B235
HSKP
B236
OFFICE
B235B
OFFICE
B235C
HAC
B216
B215A
TLT
B215B
OFFICE
B 308
TOI
B237
ELEC
B245
DATA
B247
BF111C
OFFICE
B239
MEDICAL
RECORDS
B218
BF111E
B214A OFFICE
B240
FILE ROOM
B218B
OFFICE
B 309
TOI
B238
STAIR J
B246
MECH
B242
OFFICE
B218APHAR ADMIN
B214
MECH
B241
STORAGE
B243
ANTEROOM
B215D
IV LAB
B215E
HAZ STOR
B215G
MECH
B215C
ONCOLOGY
B215F
STAIR K
B244
REF REF
C A
R
T DELIVERY
STAGING UNIT
FRZR
ORDERS
CLERK
WORKSTATION
ONCOLOGY
REF
PHARMACY
TECH STAT
PREPARATIONS
DAILY CART
BF111C
PHARMACY
CHIEF
STAT INPATIENT PHARMACY
B215E
17.
15.
18.
19.
CEF.
17.5
BED RM
BED RM
SUPPLY RM
LOCKER
OFFICE
WORK
AREA
ELEVATOR
P2
STAIR - C
TLT
645A
TLT
OFFICE
PIPE CHASE
601A
#ICRA BARRIER PLAN KEY NOTES:
PRIOR TO COMMENCING ANY WORK, CONTRACTOR TO INSTALL LEVEL
IV INFECTION CONTROL BARRIERS WITH ACCESS DOORS. ANY WORK
OUTSIDE OF BARRIERS WILL BE PERFORMED ON NIGHTS AND/OR
WEEKENDS (AS COORDINATED WITH COR). PROVIDE KEYPAD LOCKSET
AT ICRA BARRIER ENTRANCE DOORS.
ICRA BARRIER PLAN LEGEND
LEVEL IV INFECTION CONTROL
BARRIER AND ENTRANCE DOOR
ICRA BARRIER PLAN GENERAL NOTES:
A. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL BARRIER WALL CONSTRUCTION
AND INFECTION CONTROL MEASURES WITH COR AND PATIENT SAFETY/INFECTION CONTROL
REPRESENTATIVE. TEMPORARY IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS
ARE APPROXIMATE. CONTRACTOR SHALL PROVIDE MEASURED DRAWINGS TO COR AND
PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA PROTOCOLS AND
SCHEDULE IS APPROVED.
B. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED DURING NORMAL
BUSINESS HOURS. ANY INTERRUPTIONS MUST BE REQUESTED AHEAD OF TIME AND
APPROVED. SEE SPECIFICATION 013526 AND MEMO 001S-08-18 FOR PROCEDURES AND HOURS
OF OPERATION.
C. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES: A 24"X36" STICKY WALK OFF MAT
AND HAND SANITIZER AT EACH TEMPORARY DOOR LOCATION. MAT SHALL BE REPLACED OR
CLEANED AS NECESSARY.
D. PROVIDE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH TEMPORARY ICRA
ENTRANCE DOOR.
E. PROVIDE LEVEL IV ICRA BARRIERS AND ENTRANCE DOORS AS REQUIRED AND INDICATED ON
FLOOR PLANS. COORDINATE LOCATIONS WITH COR. BASIS OF DESIGN: STARC SYSTEMS.
CONTACT: MAX DANSKY; OFFICE : 207-844-2789; CELL: 978-502-9689; EMAIL:
MDANSKY@STARCSYSTEMS.COM.
F. CONTRACTOR SHALL MAINTAIN 4'-0" CLEAR WIDTH IN THE CORRIDOR FROM THE ICRA BARRIER
FOR CIRCULATION THROUGHOUT THE CONSTRUCTION.
G. PLANS PROVIDED ARE FOR GUIDANCE, CONTRACTOR TO PROVIDE SUBMITTAL PACKAGE
SHOWING ACTUAL LAYOUT AND CONSTRUCTION OF BARRIERS FOR REVIEW AND APPROVAL OF
COR.
TRUE
NORTH
PLAN
NORTH
BASEMENT KEY PLAN
N.T.S
PROJECT AREA
SIXTH FLOOR KEY PLAN
N.T.S
PROJECT AREA
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
JH SJ/KB
540-18-020
03-13-2026REVISIONS:
A
B
C
D
E
F
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
INFECTION CONTROL PLANS
GI003
1/8" = 1'-0"GI003
1 PARTIAL BASEMENT ICRA PLAN
1/8" = 1'-0"GI003
2 PARTIAL SIXTH FLOOR ICRA PLAN
0' 4' 8' 16' 24'
SCALE: 1/8" = 1' - 0"
DESIGN CODES:
1.1 BUILDING CODE: 2021 INTERNATIONAL BUILDING CODE AS AMENDED BY
A.VA H-18-8 SEISMIC DESIGN REQUIREMENTS
B.NATIONAL LOADING STANDARD: ASCE 7-16 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
C.STEEL: AISC 360-16 - SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS
DESIGN LOADS:
1.1 DESIGN LOADS ARE AS FOLLOWS:
A.ROOF:
1. DEAD LOADS:
a. PLATFORM & EXISTING ROOF: SELF WEIGHT OF MATERIALS
b. EQUIPMENT ON PLATFORM: SEE BELOW
2. LIVE LOADS:
a. PLATFORM: 60 PSF
b. EXISTING ROOF: 20 PSF
3. COLLATERAL LOADS:
a. PLATFORM & EXISTING ROOF: 10 PSF
4. RAIN LOADS:
a. N/A: NO ACCUMULATION
5. FLOOD LOADS:
a. N/A: NOT IN FLOOD HAZARD AREA
6. SNOW LOADS:
a.GROUND SNOW LOAD = 20 PSF
B.WIND LOADS:
1. DESIGN WIND SPEED = Vult 120 MPH
2. WIND EXPOSURE = B
3. RISK CATEGORY = IV
C.EARTHQUAKE LOADS:
1. OCCUPANCY CATEGORY = IV
2. SPECTRAL RESPONSE COEFFICIENT
a. Ss = 0.103 g
b. S1 = 0.051 9
3. SPECTRAL RESPONSE ACCELERATION
a. Sds = 0.110 g
b. Sd1 = 0.081 g
4. SEISMIC DESIGN CATEGORY = C
5. SITE CLASS = D
6. SEISMIC COEFFICIENTS FOR FANS:
a. COMPONENT AMPLIFICATION FACTOR (Ap) = 2.5
b. COMPONENT RESPONSE MODIFICATION FACTOR (Rp) = 6
c. ANALYSIS PROCEDURE = EQUIVALENT LATERAL FORCE PROCEDURE
d. MECHANICAL COMPONENT ANCHORAGE: Fp = 0.466 Wp
1.2 DEFLECTION CRITERIA: REFER TO TABLE 1604.3 FOR DEFLECTION LIMITS.
UNIT IDENTIFIER
L(IN) W(IN) H(IN)
MAX DIMENSIONS
MAX WEIGHT(LB)
EF-02A&B 49 22 132 844
117 57 156 3167EF-01A&B
GENERAL STRUCTURAL NOTES:
1.1 ELEVATIONS AS SHOWN ON THE STRUCTURAL DRAWINGS ARE ELEVATIONS RELATIVE TO THE FINISH EXISTING
FLOOR ELEVATION UNLESS NOTED OTHERWISE
1.2 WHERE A DETAIL, TYPICAL DETAIL, SECTION, TYPICAL SECTION OR NOTE IS SHOWN FOR ONE CONDITION, IT SHALL
APPLY FOR ALL SIMILAR OR LIKE CONDITIONS UNLESS OTHERWISE NOTED.
1.3 THE STRUCTURAL DESIGN OF THE STRUCTURE IS BASED ON THE FULL INTERACTION OF ALL ITS COMPONENT PARTS, WITH NO PROVISION MADE FOR CONDITIONS OCCURRING DURING CONSTRUCTION. THEREFORE, CONTRACTOR SHALL PROVIDE ADEQUATE BRACING AND TEMPORARY SHORING DURING CONSTRUCTION.
1.4 CONTRACTOR IS RESPONSIBLE FOR ALL JOB SITE SAFETY INCLUDING THE SAFE RIGGING, LIFTING AND SETTING OF
EQUIPMENT IN ACCORDANCE WITH APPLICABLE STANDARDS.
1.5 FURNISH AND INSTALL ALL NECESSARY ATTACHMENTS, ANCHORAGES AND ACCESSORIES TO PROVIDE A COMPLETE STRUCTURALLY SOUND STRUCTURE WITH A CONTINUOUS LOAD PATH. BRING ANY DISCONTINUITIES TO THE
ATTENTION OF THE STRUCTURAL ENGINEER IMMEDIATELY.
1.6 FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF FABRICATION OR CONSTRUCTION. BRING ANY DISCREPANCIES ALONG WITH DETAILED FIELD SKETCHES OF AS-BUILT CONDITIONS TO THE ATTENTION OF THE
STRUCTURAL ENGINEER IMMEDIATELY.
1.7 COORDINATE AND VERIFY ALL DIMENSIONS AND DETAILS WITH THE EXISTING, CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY OF
ANY DISCREPANCIES.
SHOP DRAWINGS
2.1 STRUCTURAL DRAWINGS INDICATE TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. SHOP DRAWINGS SHALL
DETAIL ALL CONDITIONS IN ACCORDANCE WITH SPECIFIED STANDARDS AND THE SPECIFIC REQUIREMENTS OF THIS
PROJECT AS INDICATED ON THE DRAWINGS.
2.2 CONTRACTOR SHALL PROVIDE A MINIMUM OF ONE HARD COPY AND LEGIBLE PDF FOR EACH STRUCTURAL
COMPONENT FOR REVIEW PRIOR TO FABRICATION.
2.3 PHOTOCOPY REPRODUCTIONS OF THE CONTRACT DOCUMENTS WILL BE REJECTED AND CONTRACTOR WILL BE
RESPONSIBLE FOR ANY ASSOCIATED DELAYS.
2.4 SUBMITTALS FOR VENDOR DESIGNED COMPONENTS SHALL BE ACCOMPANIED BY DRAWINGS AND CALCULATIONS SEALED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT. IN ADDITION, THESE SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDER THE DIRECT SUPERVISION OF THE STRUCTURAL
ENGINEER SEALING THIS WORK.
2.5 REVIEW OF SUBMITTALS INCLUDING SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THE SOLE RESPONSIBILITY FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF THOSE SUBMITTALS.
2.6 SUBMITTALS SHALL BE REVIEWED BY THE CONTRACTOR, PRIOR TO SUBMISSION FOR ENGINEER'S REVIEW, FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS AND AS-BUILT CONDITIONS. ANY DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS SHALL BE CLEARLY NOTED ALONG WITH REASONS FOR THE DEVIATION.
2.7 ALLOW A MINIMUM OF TWO CALENDAR WEEKS (14 DAYS) FROM RECEIPT OF SUBMITTALS AT THE ENGINEERS OFFICE FOR REVIEW. ALLOW TIME IN THE CONSTRUCTION SCHEDULE FOR SHIPPING AND PROCESSING TIME IN ADDITION TO
SUCH REVIEWS.
SPECIAL INSPECTIONS:
1.1 SPECIAL INSPECTIONS SHALL BE PERFORMED IN ACCORDANCE WITH CHAPTER 17 OF THE BUILDING CODE
REFERENCED ABOVE AND AS DEFINED IN THE SPECIFICATIONS.
EQUIPMENT NOTES:
1.1 EQUIPMENT COORDINATION
A.THE CONTRACTOR SHALL COORDINATE DIMENSIONAL AND UTILITY REQUIREMENTS OF ACTUAL EQUIPMENT
PURCHASED WITH PROVISIONS SHOWN ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING ANY CHANGES NECESSARY TO MAKE SUCH COORDINATION WITHOUT ADDITIONAL COST
TO THE GOVERNMENT.
1.2 EQUIPMENT ANCHORAGE
A.THE CONTRACTOR SHALL ENGINEER, FURNISH AND INSTALL NECESSARY ANCHORAGE AND VIBRATION ISOLATION
FOR ALL EQUIPMENT AND CURBS TO RESIST ALL LOADING INCLUDING BUT NOT LIMITED VIBRATORY, WIND AND
EARTHQUAKE LOADS AT NO ADDITIONAL COST TO THE GOVERNMENT.
B.THE CONTRACTOR SHALL PREPARE AND SUBMIT ANCHORAGE DETAILS AND SUPPORTING CALCULATIONS PREPARED AND SEALED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT FOR ALL MOUNTED EQUIPMENT, AND ASSOCIATED CURBS, FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND
INSTALLATION.
1.3 EQUIPMENT STRUCTURAL SUPPORT
A.THE STRUCTURAL DESIGN DEPICTED ON THESE DRAWINGS IS BASED ON THE EQUIPMENT DIMENSIONS AND
WEIGHTS OUTLINED ABOVE. IN THE EVENT THE CONTRACTOR SELECTS EQUIPMENT WITH WEIGHT GREATER THAN THAT DEPICTED IN THE TABLE SHOWN ON THIS SHEET, OR DIMENSIONS MORE THAN 10% GREATER OR LESS THAN THOSE DEPICTED IN THE TABLE SHOWN ON THIS SHEET, THE CONTRACTOR SHALL HAVE THE AFFECTED SUPPORTING STRUCTURE (NEW AND EXISTING) EVALUATED AND REINFORCED AS NECESSARY BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT, AND SUBMIT SEALED CALCULATIONS AND DRAWINGS FOR REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF FABRICATION. COSTS ASSOCIATED WITH ENGINEERING ANALYSIS, DESIGN AND CONSTRUCTION OF REPAIRS SHALL BE BORN BY THE CONTRACTOR AT NO ADDITIONAL
COST TO THE GOVERNMENT.
STRUCTURAL STEEL NOTES:
1.1 GENERAL
A.GENERAL REQUIREMENTS
1. DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE MANUAL OF
STEEL CONSTRUCTION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, INC.
B.SUBMITTALS
1. SHOP DRAWINGS: ERECTION AND FABRICATION DRAWINGS. SHOP DRAWINGS SHALL NOT CONTAIN
REPRODUCTIONS OF THE CONTRACT DRAWINGS. MEMBER SUBSTITUTION AND DEVIATIONS FROM THE CONTRACT DRAWINGS SHALL BE CLEARLY IDENTIFIED WITH AN EXPLANATION FOR THE PROPOSED DEVIATION.
C.DELIVERY, STORAGE AND HANDLING
1. PROTECT FROM CORROSION, DEFORMATION, AND OTHER TYPES OF DAMAGE. STORE ITEMS IN AN ENCLOSED
AREA FREE FROM CONTACT WITH SOIL AND WEATHER. REMOVE AND REPLACE DAMAGED ITEMS WITH NEW
ITEMS.
1.2 PRODUCTS
A.MATERIALS:
1. ALL WIDE FLANGE W'S & WT'S SHALL BE IN CONFORMANCE WITH ASTM A 992, LATEST ADOPTED EDITION, UNO.
2. ALL OTHER SHAPES, PLATES AND BARS SHALL BE IN CONFORMANCE WITH ASTM A 36, LATEST ADOPTED EDITION, UNO.
3. ALL SQUARE, RECTANGULAR AND ROUND TUBING SHALL BE IN CONFORMANCE WITH ASTM A 500, LATEST
ADOPTED EDITION, GRADE B.
4. ALL ROUND PIPE SHALL BE IN CONFORMANCE WITH ASTM A 53, LATEST ADOPTED EDITION, GRADE B.
5. BOLTS SHALL CONFORM TO F 1852 (A 325) TYPE 1 LOAD INDICATOR BOLTS, UNO.
6. THREADED RODS SHALL COMPLY WITH ASTM A 36, LATEST ADOPTED EDITION, UNO.
7. HARDENED STEEL WASHERS SHALL COMPLY WITH ASTM F 436.
8. HEAVY HEX NUTS SHALL COMPLY WITH ASTM A 563.
9. GROUT (WHERE SHOWN OR REQUIRED) SHALL BE NON-SHRINK, NON-METALLIC FACTORY PREMIXED GROUT
HAVING A COMPRESSIVE STRENGTH OF 6800PSI AT 28 DAYS.
B.FABRICATION
1. ALL NATURAL AND FABRICATED CAMBER SHALL BE INSTALLED UPWARD.
2. THE MINIMUM THICKNESS OF GUSSET AND FIN PLATES SHALL BE 3/8 IN.
3. BOLTED CONNECTIONS:
a. ALL OTHERS MAY BE CONSIDERED AS "BEARING" TYPE N.
b. THE MINIMUM NUMBER OF BOLTS IN STRUCTURAL STEEL CONNECTIONS SHALL BE AS FOLLOWS:
1) A MINIMUM OF TWO BOLTS PER CONNECTION SHALL BE USED, UNO.
C.FINISH (ROOF TOP EQUIPMENT SUPPORT)
1. SURFACE PREPARATION:
a. UNLESS NOTED OTHERWISE, SHOP CLEAN THE SURFACE OF ALL STRUCTURAL STEEL IN ACCORDANCE WITH
THE REQUIREMENTS OF SSPC-SP2
2. PRIMER:
a. UNLESS NOTED OTHERWISE SHOP PAINT WITH A MINIMUM OF 1.0 MILS OF THE FABRICATORS STANDARD RUST
INHIBITIVE PRIMER.
b. BLOCK OUT PRIMER AT THE FOLLOWING LOCATIONS:
1) STEEL AT SLIP CRITICAL CONNECTIONS.
2) STEEL TO BE EMBEDDED IN CONCRETE.
3) STEEL TO RECEIVE SPRAY-ON FIRE PROOFING.
4) STEEL TO RECEIVE GALVANIZED FINISH.
3. FINISH COATING:
a. HOT DIPPED GALVANIZED: ALL STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER SHALL BE HOT-
DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A153.
D.FINISH (ALL OTHER STEEL)
1. SURFACE PREPARATION:
a. UNLESS NOTED OTHERWISE, SHOP CLEAN THE SURFACE OF ALL STRUCTURAL STEEL IN ACCORDANCE WITH
THE REQUIREMENTS OF SSPC-SP2.
2. PRIMER:
a. UNLESS NOTED OTHERWISE SHOP PAINT WITH A MINIMUM OF 1.0 MILS OF THE RUST INHIBITIVE PRIMER.
3. FINISH COATING
a. PAINT AS DIRECTED BY THE ARCHITECT
b. STANDARD COLORS AS SELECTED BY THE GOVERNMENT
1.3 PART 3 EXECUTION
A.EXAMINATION
1. PRIOR TO STRUCTURAL STEEL ERECTION, ERECTOR SHALL INSPECT EXISTING CONSTRUCTION FOR CORRECT SIZE, LAYOUT AND ALIGNMENT. ANY INCONSISTENCIES DEEMED DETRIMENTAL TO THE ERECTION OF STEEL
SHALL BE REPORTED AND REPAIRED PRIOR TO INSTALLATION.
B. INSTALLATION
1. WELDED CONNECTIONS SHALL BE MADE WITH E70XX ELECTRODES IN ACCORDANCE WITH AWS D1.1, STRUCTURAL WELDING CODE BY THE AMERICAN WELDING SOCIETY, AND SHALL BE PERFORMED BY CERTIFIED
WELDERS. WELDER CERTIFICATION SHALL BE AVAILABLE ON SITE FOR INSPECTION.
C.FIELD QUALITY CONTROL
1. TOLERANCES
a. MAXIMUM VARIATION FROM PLUMB: 1/4" (6 MM) PER STORY, NON-CUMULATIVE.
b. MAXIMUM OFFSET FROM TRUE ALIGNMENT
2. WELDED CONNECTIONS:
a. ALL WELDS SHALL BE VISUALLY EXAMINED.
b. 15% OF ALL WELDS SHALL BE TESTED IN ACCORDANCE WITH THE FOLLOWING METHODS:
1) TESTED BY THE LIQUID PENETRANT METHOD IN ACCORDANCE WITH ASTM E 165 OR THE MAGNETIC PARTICLE
METHOD IN ACCORDANCE WITH ASTM E 709.
D.REPAIR
1. PROTECTIVE COATINGS DAMAGED DURING THE TRANSPORTATION, ERECTION AND FIELD WELDING PROCESSES
SHALL BE REPAIRED IN THE FIELD TO MATCH THE SHOP APPLIED COATING.
E.CLEANING AND PROTECTION
1. CLEAN AFTER INSTALLATION EXPOSED PREFINISHED ITEMS IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS.
2. PROTECT INSTALLED ITEMS FROM DAMAGE CAUSED BY SUBSEQUENT CONSTRUCTION.
POST-INSTALLED ANCHORS:
1.1 POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS.THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER-OF-RECORD PRIOR TO INSTALLING POST- INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REBAR. HOLES SHALL BE DRILLED AND CLEANED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER- OF-RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED & SEALED BY A REGISTERED PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERTINENT EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.
1.2 CONCRETE ANCHORS
A.ADHESIVE ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED IN
ACCORDANCE WITH ACI 318 APPENDIX D.
B.ALL POST INSTALLED ANCHORS THAT ARE NOT PROPERLY INSPECTED IN ACCORDANCE WITH THE APPROPRIATE
ICC ESR CODE REPORT SHALL BE CONSIDERED TO HAVE ZERO CAPACITY AND CORRECTED BY THE CONTRACTOR
AND INSPECTED DURING INSTALLATION AT NO COST TO THE GOVERNMENT.
C.ALL POST-INSTALLED ANCHORS SHALL BE DESIGNED, DETAILED, INSTALLED, AND INSPECTED WITH THE
APPROPRIATE ICC ESR CODE REPORT.
D.PRE-APPROVED ANCHOR MANUFACTURER
1. HILTI HY200 W/ HAS STD ROD IN ACCORDANCE WITH ICC ESR #3187
2. ADD HILTI KWIK BOLT TZ ANCHOR IN ACCORDANCE WITH ICC ESR #1917
EXISTING CONDITIONS
3.1 AS WITH ANY WORK AFFECTING EXISTING CONSTRUCTION, UNFORESEEN CONDITIONS ARE UNAVOIDABLE WITHOUT
DEMOLISHING OTHERWISE SERVICEABLE CONSTRUCTION, DISRUPTING OCCUPIED OPERATIONS AND INCURRING SIGNIFICANT COST FOR CLOSE UP EXAMINATION AND NON-DESTRUCTIVE TESTING DURING THE DESIGN STAGE.
3.2 WITH THE PASSAGE OF TIME SINCE THE CREATION OF AS-BUILT DRAWINGS AND/OR THE DESIGNERS SURVEY, BOTH CONCEALED AND VISIBLE CONDITIONS MAY HAVE CHANGED DUE TO ALTERATIONS, ADDITIONS, RENOVATIONS AND
DETERIORATION.
3.3 PRIOR TO THE COMMENCEMENT OF ANY WORK IN PREPARATION OF CONSTRUCTION RELATED ACTIVITIES, INCLUDING BUT NOT LIMITED TO SHOP DRAWING PREPARATION, ALL EMBEDDED AND CONCEALED ITEMS LIKELY TO BE ENCOUNTERED DURING CONSTRUCTION SHALL BE LOCATED AND MARKED ON THE SURFACE. THIS WORK SHALL BE ACCOMPLISHED BY DESTRUCTIVE AND/OR NON-DESTRUCTIVE MEANS WITHOUT IMPAIRING THE STRUCTURAL INTEGRITY OF THE ASSOCIATED MEMBERS. SHORING AS REQUIRED SHALL BE DESIGNED BY A PROFESSIONAL STRUCTURAL ENGINEER, LICENSED IN THE STATE OF THE PROJECT, AND FURNISHED AND INSTALLED AT NO
ADDITIONAL COST.
3.4 EXISTING CONDITIONS THAT INTERFERE OR OTHERWISE AFFECT THE DESIGN, CONSTRUCTION OR SERVICEABILITY OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER, INCLUDING PLAN AND SECTION SKETCHES PREPARED BY A LICENSED SURVEYOR, IMMEDIATELY FOR RESOLUTION. THE CONTRACTOR SHALL ALLOW TWO CALENDAR WEEKS IN THE SCHEDULE FOR DESIGN RESOLUTION OF THE INTERFERENCE AFTER ALL INFORMATION ABOUT THE INTERFERENCE, INCLUDING SIZE, LOCATION AND FUNCTION OF THE EMBEDMENT, HAS
BEEN RECEIVED BY THE STRUCTURAL ENGINEER.
DRAWING ABBREVIATIONS:
BOT BOTTOM
B/STL BOTTOM OF STEEL
CONN CONNECTION
CTD CONTINUED
DIAG DIAGONAL
EA EACH
EF EACH FACE
EL ELEVATION
EMBED EMBEDMENT
EOD EDGE OF DECK
EOS EDGE OF SLAB
HORIZ HORIZONTAL
LLH LONG LEG HORIZONTAL
LLO LONG LEG OUT
LLV LONG LEG VERTICAL
MAX. MAXIMUM
MIN. MINIMUM
OC ON CENTER
STD STANDARD
T&B TOP AND BOTTOM
T/STL TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
REINFORCED CONCRETE NOTES
1.1 CONCRETE DESIGN IS IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, ACI 318.
1.2 CONCRETE WORK SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH THE FIELD REFERENCE MANUAL: STANDARD
SPECIFICATIONS FOR STRUCTURAL CONCRETE ACI 301 WITH SELECTED ACI AND ASTM REFERENCES (SP-15 )
1.3 SUBMIT REINFORCING STEEL SHOP DRAWINGS AND RECEIVE APPROVAL PRIOR TO FABRICATION OF SAME.
1.4 ALL CONCRETE SHALL BE NORMAL WEIGHT (145PCF) AND HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH AS FOLLOWS UNLESS
NOTED OTHERWISE:
A. F'c = 4,000 PSI UNLESS NOTED OTHERWISE.
1.5 CONCRETE MIX DESIGN SUBMITTAL REQUIREMENTS:
A. FOR EACH UNIQUE MIX DESIGN/CODE PROPOSED, CLEARLY INDICATED WHICH COMPONENT THE MIX WILL BE USED FOR. (E.G.
FOOTING, EXTERIOR WALLS, INTERIOR WALLS, EXTERIOR SLAB ON GRADE, INTERIOR SLAB ON GRADE, ELEVATED SLAB, MASONRY
GROUT FILL, PAVING, ETC.)
B. CEMENT: AMOUNT PER CUBIC YARD AND SUPPLIER.
C. FLYASH: AMOUNT PER CUBIC YARD, SUPPLIER, A HISTORY OF SUCCESSFUL USE OF FLYASH CONCRETE IN SIMILAR APPLICATIONS.
D. AGGREGATE: AMOUNT PER CUBIC YARD, TYPE AND COMPOSITE GRADATION ANALYSIS INCLUDING BOTH COARSE AND FINE.
E. WATER: AMOUNT PER CUBIC YARD AND WATER/CEMENT RATIO.
F. ADMIXTURES: TYPE, AMOUNT PER CUBIC YARD, PRODUCT DATA INDICATING ASTM COMPLIANCE AND CHLORIDE ION CONTENT.
G. COMPRESSIVE TESTS OF PAST USAGE OF THE SUBMITTED MIX DESIGN INDICATING THE SAME MIX DESIGN CODE.
1.6 WHEN STRENGTH DATA FROM FIELD EXPERIENCE OR TRIAL MIXTURES ARE NOT AVAILABLE, CONCRETE MIX DESIGN SHALL COMPLY
WITH THE FOLLOWING:
A. 4000 PSI NORMAL WEIGHT CONCRETE SHALL BE BASED ON A MAXIMUM AGGREGATE SIZE OF 1 IN., MAXIMUM WATER/CEMENT
RATIO OF 0.5 FOR NON-AIR-ENTRAINED AND A MAXIMUM SLUMP OF 4 IN.
B. THE MAXIMUM SLUMPS SPECIFIED ABOVE SHALL NOT BE EXCEEDED PRIOR TO THE ADDITION OF WATER REDUCING ADMIXTURES
REGARDLESS OF THE EXISTENCE OF TEST DATA.
C. NORMAL WEIGHT AGGREGATE SHALL COMPLY WITH ASTM C 33.
D. AGGREGATE FOR FLATWORK SHALL BE WELL GRADED INCLUDING FINE, INTERMEDIATE AND COARSE AGGREGATE UNLESS
OTHERWISE SPECIFIED.
E. WHEN PERMITTED, THE WEIGHT OF CLASS C FLYASH SHALL NOT EXCEED 25% OF THE WEIGHT OF CEMENT PLUS POZZOLAN.
1.7 CONCRETE SLABS ON GRADE SHALL NOT BE LOADED UNTIL A MINIMUM CONCRETE STRENGTH OF 1800 PSI HAS BEEN ATTAINED AND THE CONCRETE IS AT LEAST THREE DAYS OLD. ALL OTHER CONCRETE MEMBERS SHALL NOT BE LOADED UNTIL THE SPECIFIED
CONCRETE DESIGN STRENGTH HAS BEEN ATTAINED.
1.8 CONCRETE SHALL BE TESTED IN ACCORDANCE WITH ACI 301 AND THE SPECIFICATIONS, WHEN PROVIDED, FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS. AT A MINIMUM, CONCRETE SPECIMENS SHALL BE TAKEN FOR EVERY 100 YARDS OR PORTION THEREOF FOR EACH MIX DESIGN PLACED IN A DAY. CONCRETE TEST REPORTS SHALL BE AVAILABLE ON SITE FOR INSPECTION.
1.9 C.J. ON THE SLAB AND FOUNDATION PLAN INDICATES A KEY-FORMED CONSTRUCTION JOINT OR SAW-CUT CONTROL JOINT IN THE CONCRETE SLAB-ON-GROUND. SAW-CUT CONTROL JOINTS SHALL BE INSTALLED WITHIN 12 HOURS OF SLAB PLACEMENT. CONTINUE REINFORCEMENT THROUGH JOINTS UNLESS NOTED OTHERWISE, IN WHICH CASE DO NOT CUT REINFORCING STEEL. UNLESS OTHERWISE NOTED CONSTRUCTION AND/OR CONTROL JOINTS SHALL BE SPACED NO FARTHER APART THAN 13-FT. O.C. IN EACH
DIRECTION CREATING PANELS WITH AN ASPECT RATIO NOT GREATER THAN 2:1.
1.10 ALL STEEL REINFORCEMENT SHALL CONFORM WITH THE FOLLOWING:
A. DEFORMED BARS SHALL CONFORM WITH ASTM A 615 GRADE 60.
B. DEFORMED BARS THAT WILL BE WELDED SHALL CONFORM TO ASTM A 706 GRADE 60. WELDING SHALL BE IN ACCORDANCE WITH
AWS D1.4 STRUCTURAL WELDING CODE.
C. WELDED WIRE REINFORCING (WWR) SHALL CONFORM WITH ASTM A 185, LATEST ADOPTED EDITION, 65 KSI YIELD AND SHALL BE
SUPPLIED IN FLAT SHEETS.
1. SLAB-ON-GROUND WWR SHALL BE SUPPORTED BY RECOVERABLE PLASTIC COATED CHAIRS WITH SAND BASE OR CONCRETE
BRICK 2" BELOW THE TOP OF SLAB @ 2’-0” O.C. MAXIMUM. THE USE OF CLAY BRICKS OR PULLING UP WWR DURING CONCRETE
PLACEMENT IS STRICTLY PROHIBITED. USE A MINIMUM OF 6 X 6 - W1.4 X W1.4.
2. WWR ABOVE FORMED SURFACES SHALL BE SUPPORTED BY PLASTIC COATED CHAIRS AT THE MID DEPTH BETWEEN THE
CONCRETE SURFACE AND TOP OF FORM OR FLOOR DECK FLUTE.
1.11 PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE. SPLICE ONLY AS SHOWN OR APPROVED. STAGGER SPLICES WHERE POSSIBLE. DOWELS SHALL MATCH SIZE AND SPACING OF THE SPECIFIED REINFORCEMENT AND SHALL BE LAPPED WITH TENSION SPLICES. UNLESS OTHERWISE NOTED, ALL REINFORCING SHALL BE CONTACT LAP SPLICED WITH A CLASS B SPLICE IN ACCORDANCE WITH ACI 318-05. FOR BARS WITH A MINIMUM COVER AND SPACING GREATER THAN 2.0DB AND 3.0DB (DB = BAR DIAMETER) RESPECTIVELY, THE MINIMUM SPLICE LENGTH, EXPRESSED IN BAR DIAMETERS, SHALL NOT BE LESS THAN SPECIFIED IN THE REBAR SPLICE SCHEDULE. SPLICE LENGTHS SHALL BE INCREASED BY A FACTOR OF 1.3 FOR TOP REINFORCEMENT AND WHEN LIGHTWEIGHT CONCRETE IS USED. LAP WELDED WIRE FABRIC (WWF) ONE SPACE PLUS 2 IN. ON ALL SIDES AT SPLICES.
1.12 ALL DOWELS AND TERMINATING BARS SHALL HAVE A STANDARD 90-DEG HOOK UNO.
1.13 ALL HORIZONTAL REINFORCING SHALL BE CONTINUOUS AROUND CORNERS, THROUGH CONTROL JOINTS, AND THROUGH
CONSTRUCTION JOINTS UNO.
1.14 CONCRETE COVER AT REINFORCEMENT:
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH -3 IN.
B. FORMED CONCRETE EXPOSED TO WEATHER OR EARTH:
1. (#5 AND SMALLER) -1½ ".
2. (#6 TO #18) -2".
3. ALL OTHER -1 ½".
C. FORMED CONCRETE NOT EXPOSED TO WEATHER OR EARTH:
1. SLABS, WALL, AND JOISTS:
a. # 11 BARS & SMALLER - 3/4".
b. # 14 & # 18 BARS - 1½ ".
2. BEAMS AND COLUMNS - 1½ IN.
3. GRADE BEAMS - 1½ ".
1.15 MINIMUM CONCRETE COVER FOR REINFORCEMENT
A. FOUNDATIONS:
1. BOTTOM & SIDES: 3 IN.
2. TOP: 3 IN.
B. SLABS: 2 IN.
C. WALLS: 2 IN.
1.16 CORNER EDGES OF CONCRETE TO BE LEFT EXPOSED TO VIEW SHALL HAVE A CHAMFER OR RADIUS OR AS INDICATED ON THE
DRAWINGS.
1.17 CHECK ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, EQUIPMENT, AND PROCESS DRAWINGS FOR
EMBEDDED ITEMS AND PENETRATIONS PRIOR TO CONCRETE PLACEMENT.
REINFORCED CONCRETE NOTES: (CTD)
1.18 ALL CONSTRUCTION JOINTS SHALL HAVE A ROUGH SURFACE AND BE CLEAN PRIOR TO SUBSEQUENT CONCRETE POUR.
1.19 NO HORIZONTAL CONSTRUCTION JOINTS WILL BE PERMITTED IN SLABS, WALLS, AND FOOTINGS UNO.
1.20 WHERE OPENINGS OCCUR IN SLABS, AND WALLS, PLACE THE REINFORCING THAT NORMALLY OCCURS IN LINE WITH THE
OPENING EQUALLY TO EITHER SIDE OF THE OPENING.
1.21 CONCRETE SHALL RECEIVE THE FOLLOWING FINISHES:
A. INTERIOR EXPOSED SLABS - STEEL TROWEL FINISH.
B. SLAB-ON-GROUND
1. SPECIFIED OVERALL VALUE: FF 35/FL 25
2. MINIMUM LOCAL VALUE: FF 24/FL 17
C. EXTERIOR SLABS - BROOM FINISH IN DIRECTION OF SLOPE.
D. ALL OTHER CONCRETE - STEEL TROWEL FINISH
1.22 ALL CONCRETE SHALL BE CONSOLIDATED BY VIBRATION SO THAT THE CONCRETE IS THOROUGHLY WORKED AROUND THE REINFORCEMENT, AROUND EMBEDDED ITEMS, AND INTO CORNERS OF FORMS, ELIMINATING ALL AIR OR STONE POCKETS
WHICH MAY CAUSE HONEYCOMBING, PITTING, OR PLANES OF WEAKNESS. IF VIBRATORS, OF ADEQUATE SIZE, ARE USED THEY SHALL BE INSERTED AND WITHDRAWN AT POINTS APPROXIMATELY 18 INCHES APART. AT EACH INSERTION, THE DURATION SHALL BE SUFFICIENT TO CONSOLIDATE THE CONCRETE BUT NOT SUFFICIENT TO CAUSE SEGREGATION
(GENERALLY ROM 5 TO 15 SECONDS).
1.23 MAINTAIN CONCRETE AFTER PLACEMENT WITH MINIMAL MOISTURE LOSS AT RELATIVELY CONSTANT TEMPERATURE FOR THE PERIOD NECESSARY FOR HYDRATION OF CEMENT AND HARDENING OF CONCRETE (NOT LESS THAN 7 DAYS). COMPLY WITH THE REQUIREMENTS OF ACI 308 - STANDARD PRACTICE FOR CURING CONCRETE; AMERICAN CONCRETE INSTITUTE.
A COMBINATION CURING AND SEALING COMPOUND SHALL BE APPLIED AFTER THE CONCRETE HAS BEEN FINISHED OR THE FORMS REMOVED. COMPOUND SHALL BE IN ACCORDANCE WITH ASTM C309, LATEST ADOPTED EDITION, TYPE I, CLASS B.
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
REVISIONS:
A
B
C
D
E
F
STRUCTURAL NOTES
S001
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
540-18-020
06-20-2025
BID DOCUMENTS
DCASLW
PLAN
NORTH
TRUE
NORTH
AF AE ACAD
A8
16 17 18 19 20 21
J
F
F1
REF
24' - 0"
REF
10' - 9 1/2"
REF
13' - 2 1/2"
REF
11' - 9 1/4"
REF
12' - 2 3/4"
REF
11' - 10 3/8"
REF
12' - 1 5/8"
REF
13' - 10 3/8"
REF
10' - 1 5/8"
R E
F
R E
F 2'
0"
R E
F
6'
8"
S501
S501
S501
S501
S501
S501
S501
S501
EXISTING FOOTING
TYP
EXISTING
CONCRETE
COLUMN TYP
EXISTING CONCRETE
WALL TYP
S101
NEW 5" SLAB ON
GROUND TO MATCH
EXISTING
3' - 3" 3' - 6"
9'
3/
4" 1'
1/ 4"
DENOTES HIDDEN EDGE OF FOOTING
DENOTES EDGE OF EXIST SLAB / FOOTING
NEW WALL PENETRATION
1. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD
VERIFY
2. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS.
3. DO NOT OVERCUT HOLES FOR NEW PENETRATIONS.
4. PROVIDE ROUNDED CORNERS AT ALL EDGES OF NEW PENTRATIONS.
5. DO NOT CUT OR DAMAGE EXISTING STRUCURE TO REMAIN DURING
DEMOLITION WORK.
PIPE INSTALLATION
AS REQUIRED FOR
M
ID
D E
P T
H
CLEAN AND ROUGHEN
EXISTING SURFACE APPLY
EPOXY BONDING AGENT PRIOR
TO PLACEMENT OF FRESH
CONCRETE IN ACCORDANCE
WITH MANUFACTURERS
RECOMMENDATIONS
DRILL HOLE INTO EXISTING SLAB 12 BAR
DIAMETERS DEEP BY ONE BAR DIAMETER + 1/4"
MAX IN DIAMETER INTO SLAB IN ACCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS CLASS B
SPLICE TYP
#4@14" E.W.
NEW SLAB TO MATCH EXISTING
SLAB THICKNESS, ALIGN
CONTROL JOINTS WITH
EXISTING JOINTS
EXISTING SLAB
MINIMUM 4" GRANULAR BASE.
COMPACTED TO 98% OF ITS STANDARD
PROCTOR MAXIMUM DRY DENSITY IN
ACCORDANCE WITH ASTM D698.
LAP AND TAPE 10 MIL
VAPOR BARRIER
NEW PIPE. REFER TO
PLUMBING FOR PIPE SIZE,
DEPTH AND BEDDING
REQUIREMENTS.
NOTES:
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. DO NOT INTERRUPT OR UNDERPIN EXISTING FOOTINGS OR
SLAB DURING PIPE DEMOLITION OR INSTALLATION
AE
A8
18 19
J
F
F1
3' - 3" 3' - 6"
9'
3/
4" 1'
1/ 4"
R E
F
R E
F
2'
0"
R E
F
6'
0"
REF
11' - 9 1/4"
REF
12' - 2 3/4"
DENOTES HIDDEN EDGE OF FOOTING
DENOTES EDGE OF EXIST SLAB / FOOTING
DENOTES AREA OF SLAB TO BE DEMOLISHED
1. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD
VERIFY
2. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS.
3. DO NOT OVERCUT HOLES FOR NEW PENETRATIONS.
4. PROVIDE ROUNDED CORNERS AT ALL EDGES OF NEW PENTRATIONS.
5. DO NOT CUT OR DAMAGE EXISTING STRUCURE TO REMAIN DURING
DEMOLITION WORK.
3/16" = 1'-0"S101
2 PARTIAL BASEMENT FOUNDATION PLAN
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
REVISIONS:
A
B
C
D
E
F
BASEMENT FOUNDATION PLAN
S101
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
540-18-020
06-20-2025
BID DOCUMENTS
DCASLW
BASEMENT FOUNDATION PLAN LEGEND BASEMENT FOUNDATION PLAN NOTES
3/4" = 1'-0"S101
3 TYPICAL SLAB REPAIR DETAIL
3/16" = 1'-0"S101
1 PARTIAL BASEMENT DEMOLITION PLAN
PARTIAL BASEMENT
DEMOLITION PLAN LEGEND
PARTIAL BASEMENT
DEMOLITION PLAN NOTES
PLAN
TRUE
NORTH
1. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
2. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY
3. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
4. COORDINATE ALL NEW AND EXISTING STEEL WITH ACTUAL EQUIPMENT
PROVIDED AND ALL ASSOCIATED DUCT WORK AND PIPING PRIOR TO
SUBMISSION OF SHOP DRAWINGS FOR REVIEW
5. ALL STEEL EXPOSED TO THE ELEMENTS SHALL BE HOT DIPPED
GALVANIZED.
6. DO NOT DAMAGE EXISTING STRUCTURAL MEMBERS, INCLUDING
REINFORCING, TO REMAIN DURING INSTALLATION OF ALL NEW WORK.
CONTRACTOR SHALL LOCATE EXISTING REINFORCING BY NON-
DESTRUCTIVE MEANS PRIOR TO SUBMISSION OF SHOP DRAWINGS FOR
REVIEW.
7. EQUIPMENT ATTACHMENT TO STRUCTURE SHALL BE BY THE EQUIPMENT
SUPPLIER.
8. TOP OF STEEL FOR NEW MECHANICAL FRAME IS 2'-0" ABOVE EXIST. ROOF
DENOTES HORIZONTAL BRACING
DENOTES NEW STEEL BEAM
DENOTES EXISTING CONCRETE COLUMN CAP BELOW
DENOTES EXIST SLAB EDGE
19 20 21 22
L
J
F
M
F1
REF
24' - 0"
REF
24' - 0"
REF
24' - 0"
R E
F
R E
F
R E
F
R E
F 2'
0"
HSS4X4X1/4
HSS4X4X1/4HSS4X4X1/4
HSS4X4X1/4
W8X10
W 8X
W 8X
W8X10
3' - 3" 4' - 5 1/4"
2'
0" 9'
4"
S501
EF-01A&B
EXISTING
CONCRETE
COLUMN TYP
EXISTING SLAB
DROP PANEL
TYP
EXISTING 9"
TWO-WAY FLAT
SLAB TYP
L3x3x3/8
HORIZONTAL
CROSS BRACING
CEF
17.5
B'
REF
8' - 6"
REF
17' - 8 1/2"
REF
7' - 0"
R E
F
R E
F
R E
F
7'
1/
2"
R E
F
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
W 8X
W 8X
W8X10
W8X10
S501
EF-02A&B
2' - 4 1/4" 7' - 7 1/8"
EXISTING
CONCRETE
BEAM TYP
EXISTING
CONCRETE
JOIST TYP
EXISTING
CONCRETE
COLUMN TYP
1'
/8
4'
1" 1'
5/ 8"
L3x3x3/8
HORIZONTAL
CROSS BRACING
HSS6x2x1/4 LSH
BELOW POSTS
CONNECTED TO
JOISTS BELOW.
SEE 9/S501
DENOTES NEW STEEL BEAM
DENOTES EXISTING CONCRETE JOIST / BEAM BELOW
DENOTES EXIST SLAB EDGE
1. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
2. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY
3. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
4. COORDINATE ALL NEW AND EXISTING STEEL WITH ACTUAL EQUIPMENT
PROVIDED AND ALL ASSOCIATED DUCT WORK AND PIPING PRIOR TO
SUBMISSION OF SHOP DRAWINGS FOR REVIEW
5. ALL STEEL EXPOSED TO THE ELEMENTS SHALL BE HOT DIPPED
GALVANIZED.
6. DO NOT DAMAGE EXISTING STRUCTURAL MEMBERS, INCLUDING
REINFORCING, TO REMAIN DURING INSTALLATION OF ALL NEW WORK.
CONTRACTOR SHALL LOCATE EXISTING REINFORCING BY NON-
DESTRUCTIVE MEANS PRIOR TO SUBMISSION OF SHOP DRAWINGS FOR
REVIEW.
7. EQUIPMENT ATTACHMENT TO STRUCTURE SHALL BE BY THE EQUIPMENT
SUPPLIER.
8. TOP OF STEEL FOR NEW MECHANICAL FRAME IS 2'-0" ABOVE EXIST. ROOF
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
REVISIONS:
A
B
C
D
E
F
ROOF AND FLOOR FRAMING PLANS
S102
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
540-18-020
06-20-2025
BID DOCUMENTS
DCASLW
3/16" = 1'-0"S102
1 ROOF FRAMING PLAN
FOURTH FLOOR FRAMING PLAN NOTESFOURTH FLOOR FRAMING PLAN LEGEND
3/16" = 1'-0"S102
2 FOURTH FLOOR FRAMING PLAN
Scale: 3/16"=1'-0"
2' 4' 8' 12'1'
Scale: 3/16"=1'-0"
2' 4' 8' 12'1'
ROOF FRAMING PLAN LEGENDROOF FRAMING PLAN NOTES
1 1/2"
6" 3"
STEEL COLUMN,
SEE PLAN
1/4
13/16'' DIA. HOLE
3/4" THICK BASE PLATE, U.N.O.
CL
CL
NOTES:
1. USE 1/2" DIA x 2 3/4" EMBED HILTI HY200 ADHESIVE ANCHORS, TYP. U.N.O.
2. DO NOT DAMAGE EXISTING BEAM REINFORCING DURING ANCHOR
INSTALLATION. LOCATE EXISTING REINFORCING THROUGH NON-DESTRUCTIVE
MEANS PRIOR TO SUBMISSION OF SHOP DRAWINGS FOR REVIEW.
1' - 4" CONCRETE BEAM BELOW
3" R 1/
2"
TYP
1/2" TYP
T O
N E
A R
E S
T
/4 k R
O U
N D
E D
U P bf
T O
N E
A R
E S
T
/4 k R
O U
N D
E D
U P
ROUND UP TO NEAREST 1/4"
(b /2 + 1/2") f
STEEL BEAM,
SEE PLAN
DOUBLE ANGLES
(5/16" THICKNESS
MIN.)
NOTE:
QTY OF FASTENERS TO BE
BASED ON THE BEAM SIZE PER TABLE
THIS DETAIL & STEEL NOTES
C BEAML
BEAM SIZE
W8
# OF 3/4" A325
BOLTS
3" MAX.
S P
A C
E S
M A
X
2'
0"
TOP OF
EXIST ROOF
EXIST ROOF
SLAB OR
BEAM SEE
PLAN
BEAM,
SEE PLAN
1/2"x6"x0'-6"
STEEL PLATE
3/16
TYP.
BASE PLATE
SEE DETAILS
ON S501 COLUMN,
SEE PLAN
3/16
TYP. T&B
3/8"x6"x0'-8" PLATE
D O
O R
O
P E
N
IN
G H
E
IG
H T
P
LU
S
DOOR / OPENING WIDTH PLUS 8"
EXISTING
CONCRETE
WALL
L4x4x1/4x0'-6"
LONG
HSS12x4x1/4 LSH
HSS12x4x1/4
HSS12x4x1/4
3/16
3 SIDES
3/4"x4"x1'-0"
PLATE TYP.
1/2" DIA. x 2 3/4"
EMBED ADHESIVE
ANCHOR AT 12" O.C.
AND 6" FROM ENDS
3/16
L4x4x1/4x0'-6" LONG
NOTE:
1. SHORING DESIGN AND INSTALLATION SHALL BE BY
THE CONTRACTOR AND SUBMITTED FOR REVIEW.
2. COORDINATE DOOR FRAME WITH BOLT HEADS
PRIOR TO SUBMISSION OF SHOP DRAWINGS FOR
REVIEW.
T/SLAB
T/ FTG
O P
E N
IN
G
H E
IG
H
T P
LU
S
EXISTING
CONCRETE
WALL
L4x4x1/4x0'-6"
LONG
HSS12x2x1/4 LSH
HSS12x4x1/4
HSS12x4x1/
3/16
3 SIDES
1/2" DIA. x 2 3/4"
EMBED ADHESIVE
ANCHOR AT 12" O.C.
AND 6" FROM ENDS
L4x4x1/4x0'-6"
LONG
NOTE:
1. SHORING DESIGN AND
INSTALLATION SHALL BE BY THE
CONTRACTOR AND SUBMITTED
FOR REVIEW.
PLUS 8"
OPENING WIDTH
1'
0"
3" M
IN
BOTTOM OF
EXISTING SLAB
MAX
4' - 0"
EXIST
CONCRETE
L4x4x3/8 LINTEL
BEARING
4"
BEARING
4"
EXISTING
BRICK
1 1/2"
3"
3"
STEEL COLUMN,
SEE PLAN
1/4
13/16'' DIA. HOLE
3/4" THICK BASE PLATE, U.N.O.
CL
CL
NOTES:
1. USE 1/2" DIA x 2 3/4" EMBED HILTI HY200 ADHESIVE ANCHORS, TYP. U.N.O.
2. DO NOT DAMAGE EXISTING BEAM REINFORCING DURING ANCHOR INSTALLATION. LOCATE
EXISTING REINFORCING THROUGH NON-DESTRUCTIVE MEANS PRIOR TO SUBMISSION OF SHOP
DRAWINGS FOR REVIEW.
10"
CONCRETE SLAB BELOW
1/
2"
STEEL COLUMN,
SEE PLAN
1/4
BEAM SEE PLAN
NOTES:
1. USE 1/2" DIA x 2 3/4" EMBED HILTI HY200 ADHESIVE ANCHORS, TYP. U.N.O.
2. PROVIDE 1" GROUT BETWEEN BOTTOM OF TUBE/ANGLES AND EXISTING SLAB.
3. DO NOT DAMAGE EXISTING BEAM REINFORCING DURING ANCHOR INSTALLATION. LOCATE EXISTING REINFORCING THROUGH
NON-DESTRUCTIVE MEANS PRIOR TO SUBMISSION OF SHOP DRAWINGS FOR REVIEW.
EXISTING CONCRETE JOIST
BELOW
L3x3x1/4x6" LONG TYP
CL
3/6
PLAN VIEW
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
512 MEANS STREET NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
REVISIONS:
A
B
C
D
E
F
STEEL DETAILS
S501
RENOVATE PHARMACY FOR USP 800
COMPLIANCE
CLARKSBURG, WEST VIRGINIA
540-18-020
06-20-2025
BID DOCUMENTS
DCASLW
1 1/2" = 1'-0"S501
1 TYPICAL BASE PLATE AT EXISTING BEAM
3" = 1'-0"S501
2 TYPICAL COPE DETAIL
3/4" = 1'-0"S501
TYPICAL BEAM TO BEAM
CONNECTION DETAIL (ALL BOLTED)
1" = 1'-0"S501
4 MECHANICAL UNIT FRAMING SECTION
1" = 1'-0"S501
ELEVATION AT NEW DOOR
OPENINGI N EXISTING CONCRETE WALL
1" = 1'-0"S501
ELEVATION AT NEW OPENING IN EXISTING
CONCRETE WALL
1/2" = 1'-0"S501
7 ELEVATION AT NEW OPENING
1 1/2" = 1'-0"S501
TYPICAL BASE PLATE AT
EXISTING CONCRETE SLAB
1 1/2" = 1'-0"S501
9 TYPICAL BASE PLATE AT EXISTING JOIST
C
6 6
15 6
B
A
A
A
A
A
A
A 6 A
A
C
K
IT
C H E N
O
FF
IC
E TL
T
S
TO
R E
B E D
R O O M
TL
T
P
IP
E
C H A S E
S O
IL
E D
U
TI
LI
TY
B .R M
TL
T
TL
T
B .R M
B .R M
TL
T
TL
T
B .R M
O .T R E C R E A
TI
O N A L
TH
E R A P Y
N H C U
M E D
D
IR
O
FF
TL
T
B R M
B .R M
TL
T
TL
T
B .R M P
IP
E
C H A S E
F.
C
LO
S
TA
IR
A
E
LE
V A
TO
R
P
CODE ANALYSIS
CODES, STANDARDS AND EXECUTIVE ORDERS
1. VA DESIGN GUIDES – TECHNICAL INFORMATION LIBRARY
2. PG 18-3 VA DESIGN AND CONSTRUCTION PROCEDURES, TOPIC 1
3. 2021 NPFA 1 FIRE CODE
4. 2018 NFPA 10 STANDARD…