2025.05.14 - Permit Issue Set - ODF Astoria District.pdf
PDF 9 MB Posted
- Attached to
- Roofing and siding Rehabilitation
- Solicitation number
- S-62900-00011088
- Issued by
- Clatsop County, Oregon
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
N
PROJECT INFORMATION:
ADDRESS:
Oregon Department of Forestry Astoria District 92219 Highway 202, Astoria, OR 97103 PO Box 950 Astoria, OR 97103
LEGAL DESCRIPTION:
Township 8N, Range 9W, Section 27, Tax Lot 2000, Clatsop County,
32.70 Acres
PERMIT No.:
TBD
PROJECT SUMMARY:
This Design Contract Document package is for Permit Issue purposes and are for project construction. Refer to sheets A0.00, A1.00 Architectural Site Plan, and to the Project Manual Summary of Work section for full project scope, basis of design, and description.
PROJECT DESIGN / ASSEMBLY GROUPS:
A0.00 COVER SHEET, GENERAL NOTES, ABBREVIATIONS &
SYMBOLS, CODE REVIEW, AND PROJECT DESCRIPTION
A0.10 SHEET SEQUENCE AND DETAIL INDEX
A1.00 SITE PLAN AND ROOF PLAN SHEETS
A2.00 REFERENCE BUILDING ELEVATIONS PHOTOS
A3.00 WALL DETAILS
A4.00 WALL OPENING DETAILS
A5.00 ROOF DETAILS
Building H: Chemical Storage Warehouse - North Elevation View Aerial View - Looking North
05.14.2025 - PERMIT ISSUE SET
Oregon Department of Forestry - Astoria District Building
Roof and Siding Rehabilitation Project (PO-62900-00046358)
PROJECT
LOCATION
EXISTING USE AND OCCUPANCY:
1. Zoning: LR (Land Reserve)
2. Zoning Overlay: n/a
3. Occupancy Groups: B, S, U
4. Construction Type: Type VB
5. County Seat: Clatsop (Unincorporated)
6. Tax Account: 60164 & 27465 (Included for Coordination)
7. Tax Map: 80927 0002000 (Included for Coordination)
SITE AREAS AND BUILDING HEIGHTS:
1. Site Area: 32.68 AC. (Unchanged)
2. Number of Buildings: 7 (Unchanged)
3. Total Site Building Area: 16,925 SF (Existing) (Unchanged)
4. Number of Stories: Varies (Existing) (Unchanged)
5. Existing Building Heights: (Existing) (Unchanged)
APPLICABLE PROJECT CODES:
1. BUILDING CODES IN EFFECT AT TIME OF REHABILITATION PROJECT:
· STATE OF OREGON 2022 OREGON STRUCTURAL SPECIALTY CODE
(O.S.S.C.) AMENDMENTS (BASED ON 2021 IBC)
· 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)
· 2022 OREGON MECHANICAL SPECIALTY CODE (BASED ON THE 2021 IMC
& INTERNATIONAL FUEL GAS CODE (IFGC)
· 2021 PORTLAND FIRE CODE AND THE 2019 OREGON FIRE CODE
· 2021 OREGON ELECTRICAL SPECIALTY CODE (BASED ON THE 2020 NFPA
70 - NATIONAL ELECTRICAL CODE)
· 2021 OREGON PLUMBING SPECIALTY CODE (BASED ON THE 2021
UNIFORM PLUMBING CODE)
REHABILITATION:
1. IT IS THE OWNER'S INTENT TO PERFORM THE REHABILITATION WITHIN THE
LIMITS WORK AREA WHILE THE BUILDINGS ARE OCCUPIED.
2. IT IS THE OWNER'S INTENT TO PERFORM A REHABILITATION OF IDENTIFIED
EXTERIOR CLADDING, WINDOWS, DOORS, AND ROOF AREAS AS
DESIGNATED FOR EACH EXISTING BUILDING AS ONE SINGLE PHASE OF
WORK. CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR
SCHEDULE, PHASING, AND WORK.
3. BUILDING REHABILITATION MAY NOT OCCUR IN NUMERICAL ORDER AS
RELATED TO SITE LAYOUT OR BUILDING DESIGNATION.
4. REFER TO THE SITE PLAN AND PROJECT MANUAL FOR NOTES, ASSUMED
LIMITS OF WORK, AND FULL SUMMARY OF WORK.
PROJECT CODE ANALYSIS: PROJECT DESCRIPTION:
1. THE OREGON DEPARTMENT OF FORESTRY ASTORIA DISTRICT CAMPUS IN
ASTORIA OREGON IS A COMPOUND OF SEVEN (7) FACILITY OPERATIONS
BUILDINGS. BUILDINGS WITHIN THE COMPOUND HAVE VARIED YEARS OF
DEVELOPMENT WITH LIMITED DOCUMENTATION RELATING TO ORIGINAL
DESIGN AND CONSTRUCTION. BUILDING ENCLOSURE WORK FOR THIS
PROJECT ARE PRIMARILY DESIGNATED FOR THE MAIN OFFICE BUILDING
HOWEVER EACH BUILDING SHALL RECEIVE IDENTIFIED WORK AS PART OF
THE PROPOSED SCOPE.
2. BUILDING A: MAIN OFFICE - ELEVATIONS ARE SIMILAR IN ASSEMBLY
CONFIGURATIONS, AND ARE PREDOMINANTLY VARIED BY FLOOR LEVEL
ACCESS, SIDING MATERIALS, AND ROOF CONFIGURATION. OF NOTE THE
OFFICE BUILDING UNDERWENT AN EXPANSION AROUND THE YEAR 1997
WHICH INCLUDED A FIRE-RATED AREA SEPARATION WALL BETWEEN THE
ORIGINAL OFFICE BUILDING AND THE NEW OFFICE ADDITION. BUILDING
COMPONENTS ARE A COMBINATION OF HARDBOARD "MASONITE"
COMPOSITE LAP SIDING WITH METAL CORNER CLOSURE PIECES ON THE
ORIGINAL STRUCTURE AND FIBER CEMENT PLANK LAP SIDING AND TRIM
ON THE ADDITION. TRIM VARIES WITH BOTH FIBER CEMENT AND WOOD
FENESTRATION TRIM MEMBERS. THE BUILDING ROOF AREAS ARE PITCHED
ROOF AND GABLE CONFIGURATIONS WITH OVERHANGS AND ARE CLAD IN
COMPOSITION ASPHALT SHINGLE ROOFING.
2.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSIST OF REMOVAL, DISPOSAL, AND REPLACEMENT ALL EXISTING
SIDING AND TRIM ALONG EACH BUILDING ELEVATION AND INCLUDE
CONCEALED WRB AND FLASHINGS. REMOVAL, DISPOSAL, AND
REPLACEMENT OF ALL EXISTING WINDOW UNITS. REMOVAL AND
REINSTALLATION OF ALL EXISTING SWING DOOR UNITS. REMOVAL,
DISPOSAL, AND REPLACEMENT OF ALL EXISTING ROOF CLADDINGS
INCLUDING UNDERLAYMENT AND FLASHINGS. EXISTING GUTTERS AND
DOWNSPOUTS TO BE REMOVED AND REINSTALLED.
3. BUILDING B AND C: MECHANIC'S SHOP - ELEVATIONS ARE SIMILAR IN
ASSEMBLY COMPONENTS AND CONSIST OF FIBER CEMENT PLANK LAP
CLADDING AND TRIM, FLANGED VINYL WINDOWS, METAL CLAD SWING
DOORS, AND COMPOSITION ASPHALT SHINGLE ROOFING ASSEMBLIES
WITH METAL FLASHINGS.
3.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSISTS TARGETED REPAIR WORK TO THE EXISTING ROOF
ASSEMBLY AND MAY INCLUDE REMOVAL AND REPLACEMENT OF
EXISTING ASPHALT SHINGLE ROOFING AND FLASHING COMPONENTS.
4. BUILDING D: PUMPER SHED - ELEVATIONS ARE SIMILAR IN ASSEMBLY
COMPONENTS AND CONSIST OF A COMBINATION OF T1-11 PLYWOOD
SIDING AND FIBER CEMENT PLANK LAP CLADDING, (1) FLANGED ALUMINUM
AND (1) VINYL WINDOW ASSEMBLY, TRANSLUCENT FIBERGLASS AND
METAL ROLL UP DOOR ASSEMBLIES, AND COMPOSITION ASPHALT SHINGLE
ROOFING ASSEMBLIES WITH METAL FLASHINGS.
4.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSIST OF REMOVAL, DISPOSAL, AND REPLACEMENT OF ALL ROOF
CLADDINGS INCLUDING UNDERLAYMENT, FLASHINGS, GUTTERS AND
DOWNSPOUTS.
5. BUILDING E: OLD PRESERVATION BUILDING - ELEVATIONS ARE SIMILAR IN
ASSEMBLY COMPONENTS AND CONSIST OF FIBER CEMENT SIDING, LIMITED
PROTECTED AREAS OF T1-11, CEDAR TRIMS AND MOUNTING BLOCKS,
PANEL CLAD WOOD DOORS, METAL ROLL UP DOOR, AND COMPOSITION
ASPHALT SHINGLE ROOFING ASSEMBLIES WITH METAL FLASHINGS.
5.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSISTS TARGETED REPAIR WORK TO THE EXISTING ROOF
ASSEMBLY AND MAY INCLUDE REMOVAL AND REPLACEMENT OF
EXISTING ASPHALT SHINGLE ROOFING AND FLASHING COMPONENTS..
GENERAL NOTES: GENERAL NOTES, CONT.:
1. READ DESIGN DOCUMENTS (DRAWINGS) IN CONJUNCTION WITH THE
PROJECT MANUAL (PRODUCT SPECIFICATIONS).
2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON SITE.
3. DRAWINGS OF ELEVATIONS AND SITE PLANS OF THE PROJECT ARE
REPRODUCED FROM BASE DRAWINGS PREPARED BY ORIGINAL
ARCHITECT. BRING DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND
ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE
BUILDING ENVELOPE CONSULTANT AND REQUEST A REVIEW.
4. EXECUTION OF THE CONTRACT BY THE CONTRACTOR IS A
REPRESENTATION THAT THE CONTRACTOR HAS VISITED THE SITE,
BECOME GENERALLY FAMILIAR WITH THE LOCAL CONDITIONS UNDER
WHICH THE WORK IS TO BE PERFORMED AND CORRELATED PERSONAL
OBSERVATIONS WITH REQUIREMENTS OF THE CONTRACT DOCUMENTS.
5. ALL WORK TO BE PERFORMED UNDER THIS SCOPE OF REPAIRS (WORK)
SHALL BE CONDUCTED IN FULL COMPLIANCE WITH ALL APPLICABLE
LOCAL, STATE, AND FEDERAL LAWS AND REGULATIONS. IT IS THE
CONTRACTOR'S DUTY TO BE FAMILIAR WITH ALL SUCH APPLICABLE
LOCAL, STATE, AND FEDERAL LAWS AND REGULATIONS. FURTHERMORE,
THE CONTRACTOR SHALL ENSURE THAT ALL ACTIVITIES PERFORMED BY
THE CONTRACTOR'S PERSONAL EMPLOYEES, SUBCONTRACTORS, AND
SUPPLIERS COMPLY WITH THESE LAWS AND REGULATIONS DURING THE
CONSTRUCTION PROCESS.
6. CONTRACT DRAWINGS ARE COMPLIMENTARY, AND WHAT IS REQUIRED
BY ANY ONE SHALL BE BINDING AS IF REQUIRED BY ALL. BEFORE
STARTING EACH PORTION OF THE WORK, CAREFULLY STUDY AND
COMPARE THE VARIOUS DRAWINGS AND OTHER CONTRACT DOCUMENTS
RELATIVE T0 THAT PORTION OF THE WORK, AS WELL AS INFORMATION
FURNISHED BY OWNER. TAKE FIELD MEASUREMENTS OF ANY EXISTING
CONDITIONS RELATED TO THAT PORTION OF THE WORK AND OBSERVE
CONDITIONS AT THE SITE AFFECTING IT. THESE OBLIGATIONS ARE FOR
THE PURPOSE OF FACILITATING CONSTRUCTION BY THE CONTRACTOR
AND NOT FOR THE PURPOSE OF DISCOVERING ERRORS, OMISSIONS, OR
INCONSISTENCIES IN THE CONTRACT DOCUMENTS; HOWEVER, REPORT
ERRORS, OMISSIONS, OR INCONSISTENCIES DISCOVERED BY THE
CONTRACTOR PROMPTLY TO THE CONSULTANT AS A REQUEST FOR
INTERPRETATION IN THE FORM PROVIDED IN THE PROJECT MANUAL.
7. REPORT DISCREPANCIES IN CONTRACT DOCUMENTS TO FORENSIC FOR
CLARIFICATION PRIOR TO COMMENCING WORK.
8. IMMEDIATELY NOTIFY BUILDING ENVELOPE CONSULTANT UPON
DISCOVERY OF ADDITIONAL UNFORESEEN DAMAGE TO EXISTING
CONSTRUCTION SCHEDULED TO REMAIN AND THAT IS OUTSIDE THE
CONTRACT. REQUEST A REVIEW. DO NOT COMMENCE RELATED WORK
TO NEARBY WORK WITHOUT CONSULTANT APPROVAL.
9. TRADE CONTRACTORS ARE RESPONSIBLE FOR THE LAYOUT OF THEIR
OWN WORK, AND TO SEE THAT ITS WORK COMES TOGETHER WITH THAT
OF OTHERS. REPORT DISCREPANCIES ON DRAWINGS TO BUILDING
ENVELOPE CONSULTANT FOR DECISIONS.
10. TRADE CONTRACTORS MUST ASSURE THEMSELVES THAT THEY HAVE
THE LATEST DRAWINGS ISSUED FOR CONSTRUCTION, SPECIFICATIONS,
MANUFACTURERS' INSTALLATION INSTRUCTIONS AND REFERENCE
STANDARDS IN THE CONTRACTOR'S OFFICE.
11. DURING REMEDIATION WORK, THE CONTRACTOR IS TO VERIFY AND
MAINTAIN RATED WALL ASSEMBLIES AT ALL EXISTING WALL LOCATIONS.
OVERSIGHT IS REQUIRED BY A LICENSED STRUCTURAL ENGINEER TO
PROVIDE FRAMING AND SHEATHING CONDITIONS ASSESSMENT
INCLUDING RATED WALLS WHERE REPAIR WORK IS IDENTIFIED DURING
ACTUAL WORK ON THE PROJECT. THE CONTRACTOR IS TO PROVIDE
AREA SPECIFIC ENGINEERED DRAWINGS SHOWING EXTENT, DETAILS,
AND CALCULATIONS TO THE AUTHORITY HAVING JURISDICTION FOR
REVIEW AND APPROVAL PRIOR TO REMEDIATION WORK.
CONCEALED BARRIER INSTALLATION:
1. CLEAN AND PREPARE SURFACES PRIOR TO INSTALLATION OF ALL
MEMBRANES IN ACCORDANCE TO PRODUCT MANUFACTURERS'
RECOMMENDATIONS AND AS DIRECTED BY BUILDING ENCLOSURE
CONSULTANT.
2. CONTRACTOR TO PROVIDE ISOMETRIC FLEXIBLE SADDLE
FLASHINGS AT MULTI-PLANE WALL, WALL OPENING, ROOF
TRANSITION, AND DECK TRANSITION AREAS AS OCCURS AND AS
DETAILED PER DESIGN DOCUMENTS.
MEMBRANE INSTALLATION:
1. SEAL WEATHER-RESISTIVE BARRIER AT ALL LAPS AND
TERMINATIONS TO CREATE AIR BARRIER. NOT ALL SEALANT
LOCATIONS ARE ILLUSTRATED.
2. PROVIDE FURRING STRIPS/RAIN SCREEN BEHIND ALL EXTERIOR
CLADDING AND TRIM IN ACCORDANCE WITH THE DRAWINGS,
SPECIFICATIONS, AND MANUFACTURER'S WRITTEN
INSTRUCTIONS.
METAL FLASHING:
1. PROVIDE AND INSTALL METAL HEAD FLASHING WITH FOLDED,
UPTURNED END DAMS OVER WINDOW, DOOR, AND SLIDING
GLASS DOORS TRIM. CONTRACTOR TO FIELD VERIFY THAT METAL
HEAD FLASHING DOES NOT INTERFERE WITH OPERATION OF THE
FENESTRATION.
2. FORM 100% OF THROUGH-WALL AND HEAD FLASHINGS WITH A
SLOPED HORIZONTAL SURFACE CONFORMING TO THE
FOLLOWING CRITERIA:
· ENSURE A 5% SLOPE AT GREATER THAN OR EQUAL TO A
1-1/2" WIDE HORIZONTAL SURFACE
· ENSURE A 10% SLOPE AT LESS THAN A 1-1/2" WIDE
HORIZONTAL SURFACE
3. CONTRACTOR TO PROVIDE 3-DIMENSIONAL METAL SADDLE
FLASHINGS AT MULTI-PLANE SUBSTRATE INTERSECTIONS, ROOF
TRANSITIONS, WALLS TRANSITIONS, DECK TRANSITIONS, AND AT
OTHER SIMILAR LOCATIONS AS OCCURS AND AS DETAILED PER
DESIGN DOCUMENTS.
EXTERIOR OPENINGS AND PENETRATIONS:
1. ALL SCHEDULES AND QUANTITIES OF WINDOWS, DOORS, VENT
PENETRATIONS, AND EXTERIOR FIXTURES, SUCH AS LIGHT
FIXTURES, CONVENIENCE RECEPTACLES, EXHAUST VENTS, PIPE
PENETRATIONS, HOSE BIBBS, ELECTRICAL OR METERS, ETC.,
THAT HAVE BEEN PROVIDED IN THE DOCUMENTS ARE
APPROXIMATE AND MUST BE VERIFIED BY THE CONTRACTOR ON
SITE. CONTRACTOR SHALL PERFORM OWN QUANTITY SURVEY
AND VERIFIED QUANTITIES OF ALL ITEMS INDICATED IN THE
DRAWINGS.
2. SEAL EXTERIOR WALL PENETRATIONS FOR AIR BARRIER
CONTINUITY WITH SCHEDULED MINIMALLY EXPANDING FOAM
INSULATION.
3. FORM EXTERIOR PERIMETER DYNAMIC SEALANT JOINTS, 1/2"
WIDE TYPICAL, WITH CONTINUOUS CLOSED CELL BACKER ROD
U.O.N., ENSURE BACKER ROD DIAMETER EXCEEDS JOINT WIDTH
BY 25% AND MAINTAIN A JOINT WIDTH-TO-DEPTH RATIO OF 2:1.
GENERAL NOTES, CONT.:
DRAWING TERMS:
1. DEMOLISH: (DEMO) TO COMPLETELY REMOVE AND LEGALLY
DISPOSE OF OFF-SITE IN A MANNER COMPLIANT WITH FEDERAL,
STATE, AND LOCAL PROTOCOLS.
2. SCHEDULED (ITEM): COMPONENTS CALLED OUT AS SCHEDULED
SHALL REMAIN IN PLACE, BE REMOVED AND REINSTALLED, BE
REMOVED AND REPLACED, BE INSTALLED AS A NEW
COMPONENT, OR REPLACED IF DAMAGED IS DISCOVERED.
REFER TO PROJECT MANUAL FOR CONDITION, ASSEMBLIES, AND
RELATED MATERIALS.
3. PROTECT (ITEM): A TERM USED ON DRAWINGS TO INDICATE AN
ITEM REQUIRES PROTECTION FROM THE WORK.
4. REMOVE (ITEM): A TERM USED ON DRAWINGS TO INDICATE A
SPECIFIC ITEM TO BE DETACHED FROM EXISTING CONSTRUCTION
AND LEGALLY DISPOSED OF OFF-SITE, UNLESS INDICATED
OTHERWISE TO BE REMOVED, SALVAGED, AND REINSTALLED.
5. REMOVE AND REINSTALL (ITEM): A TERM USED ON DRAWINGS TO
INDICATE A SPECIFIC ITEM TO BE DETACHED FROM EXISTING
CONSTRUCTION, PREPARED FOR REUSE, AND REINSTALLED
BACK IN ITS EXISTING LOCATION.
6. RELOCATE (ITEM): A TERM USED IN DRAWINGS TO INDICATE AN
EXISTING ITEM THAT HAS BEEN REMOVED, AND TO BE
REINSTALLED IN A NEW LOCATION
7. SALVAGE (ITEM): CAREFULLY DETACH FROM EXISTING
CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE READY FOR
REUSE. INCLUDE FASTENERS OR BRACKETS NEEDED FOR
REATTACHMENT IN ORIGINAL LOCATION OR ELSEWHERE.
8. EXISTING TO REMAIN (ITEM): A TERM USED ON DRAWINGS TO
INDICATE EXISTING ITEMS OF CONSTRUCTION THAT ARE NOT BE
REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE
REMOVED, SALVAGED, OR REMOVED AND REINSTALLED.
EXISTING TO REMAIN IS INDICATED BY GRAPHIC LINETYPE
SYMBOL.
9. PHASE: A PORTION OF THE WORK TO BE COMPLETED DURING A
SET PERIOD OF TIME, AS DEFINED IN THE PROJECT
SPECIFICATIONS.
10. REFER TO SPECIFICATIONS SUMMARY OF WORK, GENERAL
DESCRIPTION OF WORK, FOR SCOPE OF REPAIR ASSEMBLIES.
ALUM. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
BLDG. BUILDING
BOT BOTTOM
COL. COLUMN
CONC. CONCRETE
CONT. CONTINUOUS
CONST. CONSTRUCTION
C/W COMPLETE WITH
DIA. DIAMETER
DEFS DIRECT-APPLIED
FINISH SYSTEM
DIM. DIMENSION
DWG DRAWING
DS DOWNSPOUT
E. EAST
EA. EACH
ELEV. ELEVATION
ELEC. ELECTRICAL
EIFS EXTERIOR INSULATION &
FINISH SYSTEM
EQ. EQUAL
EQUIP. EQUIPMENT
EXIST. EXISTING
EXT. EXTERIOR
FC FIBER CEMENT
FIN. FINISH
ABBREVIATIONS:
F.O.S. FACE OF STUD
FLR. FLOOR
FRTW FIRE-RETARDANT
TREATED WOOD
FURR FURRING OR FURRED
GA GAUGE
GALV. GALVANIZED
GWB GYPSUM WALL BOARD
GYP. GYPSUM
HORIZ. HORIZONTAL
INT. INTERIOR
INSUL. INSULATION
MAX MAXIMUM
MEMB. MEMBRANE
MTL METAL
MIN. MINIMUM
MISC. MISCELLANEOUS
N. NORTH
N.I.C. NOT IN CONTRACT
(NOT IN SCOPE)
NTS NOT TO SCALE
O.C. ON CENTER
PLY PLYWOOD
P.T. PRESSURE TREATED (POST-TENSIONED
WHEN USED WITH CONCRETE)
R RADIUS
REF. REFERENCE
REINF REINFORCED
REQ'D REQUIRED
RD ROOF DRAIN
S. SOUTH
SAM SELF ADHESIVE
MEMBRANE (FLASHING)
SECT. SECTION
SIM. SIMILAR
SPEC SPECIFICATION
S.S. STAINLESS STEEL
STRUCT. STRUCTURAL
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TEMP TEMPERATURE
T.O.W. TOP OF WALL
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
VERT. VERTICAL
V.I.F. VERIFY IN FIELD
W. WEST
W/ WITH
W/O WITHOUT
WRB WEATHER-RESISTIVE
BARRIER
GYPSUM SHEATHING / GYPSUM WALLBOARD
BATT INSULATION
DETAIL HATCH PATTERN LEGEND:
TYPICAL LINE WEIGHT OF 'NEW' BUILDING ENVELOPE
COMPONENTS - WALLS, WINDOWS, DOORS, ETC.
SAM - SELF APPLIED MEMBRANE FLEXIBLE FLASHING,
OR MANUFACTURED FLASHING PANELS AS NOTED
WRB - WEATHER RESISTIVE BARRIER
MISC. COMPONENTS - DRAINAGE MAT, REINFORCING
MESH, BUG SCREEN, FASTENERS, SCREWS, NAILS
EXISTING ROOF UNDERLAYMENT, OTHER EXISTING
COMPONENTS
METAL FLASHING
SEALANT / ADHESIVE LAYER
LINETYPE LEGEND:
FIBER CEMENT CLADDING / CEMENT
BOARD / TILE ADHESIVE
CONCRETE
DECK COATING REINFORCEMENT MESH
DRAINAGE MAT
ACRYLIC REINFORCED CEMENTITIOUS DECK
COATING SYSTEM
POLYURETHANE DECK COATING / CONCRETE
DAMP-PROOFING
RIGID INSULATION / FOAM
STEEL / METAL
SCHEDULED WRB
SCHEDULED SAM
METAL FLASHING, COPING, AND SADDLES
APPLIED DECK COATING SYSTEM
SCHEDULED SEALANT
ISOMETRIC DETAIL HATCH PATTERN LEGEND:
TYPICAL LINE WEIGHT OF EXISTING BUILDING
ENVELOPE COMPONENTS
DYNAMIC SEALANT JOINT: SEALANT APPLIED OVER
CLOSED CELL BACKER ROD (2:1 RATIO)
CONTINUOUS SEALANT BEAD
PLYWOOD SHEATHING
PROJECT TEAM:
Buildings D, E, F, & G - Easterly View
PROJECT PARAMETERS:
1. UNLESS ACCOMPANIED BY DOCUMENTATION STAMPED BY A LICENSED
PROFESSIONAL, THE WORK DESCRIBED WITHIN THESE CONTRACT
DOCUMENTS SHALL NOT INCLUDE THE FOLLOWING CRITERIA (REFER TO
ORS 671.030d):
· THE STRUCTURAL PART OF THE BUILDING, INCLUDING BUT NOT
LIMITED TO THE FOUNDATION WALLS, FLOORS, ROOF, FOOTINGS,
BEARING PARTITIONS, BEAMS, COLUMNS AND JOISTS, IS NOT
INVOLVED;
· THE BUILDING CODE CLASSIFICATION BY USE OR OCCUPANCY OF
THE BUILDING IS NOT CHANGED; AND
· THE BUILDING CODE CLASSIFICATION BY TYPE OF CONSTRUCTION
OF THE BUILDING IS NOT CHANGED.
2. NON-STRUCTURAL WORK DESCRIBED WITHIN THESE CONTRACT
DOCUMENTS SHALL FALL UNDER EXCEPTIONS: 2 OF OSSC 107.1IN THAT
PLANS, SPECIFICATIONS, CALCULATIONS, DIAGRAMS AND OTHER DATA
PREPARED AND DESIGNED BY AN ENGINEER OR ARCHITECT LICENSED
BY THE STATE TO PRACTICE AS SUCH ARE NOT REQUIRED FOR THE
FOLLOWING WORK:
· 2.3 ALTERATIONS OR REPAIRS THAT DO NOT INVOLVE THE
STRUCTURAL PARTS OF THE BUILDING.
3. IT IS RECOGNIZED THAT THERE MAY BE SEPARATE TRADE PERMITS
RELATED TO PLUMBING OR UTILITY EXTENSIONS AND/OR MINOR
RECONFIGURATIONS OF EXTERIOR VENTILATION AND ELECTRICAL
PENETRATIONS RELATED TO THIS REHABILITATION PROJECT. IT IS
UNLIKELY THAT MECHANICAL AND/OR FIRE LIFE SAFETY SYSTEMS
INCLUDING ALARMS OR FIRE SPRINKLER SYSTEMS WILL BE AFFECTED.
CLIENT:
Oregon Department of Forestry 2600 State Street Salem, OR 97310 Contact: Joseph Pfau Phone: 503.507.1527 email: joseph.j.pfau@odf.oregon.gov
BUILDING ENVELOPE CONSULTANT:
Forensic Building Consultants 12901 SE 97th Ave., Suite 310 Clackamas, OR 97015 Phone: 503.772.1114 Contact: Jordon Wyatt, Project Manager email: jordon@forensicbuilding.com
Michael Green, Technical Design Manager email: michaelg@forensicbuilding.com
AUTHORITY HAVING JURISDICTION:
Clatsop County Building Permits 800 Exchange St., Ste. 100 Astoria, OR 97103 Building and Inspections: 503.338.3697 email:BuildingDivision@clatsopcounty.gov https://www.clatsopcounty.gov/building
Building D: Tanker/Engine Garage/Workshop - South Elevation View Building A: Main Office Building - East Elevation View
CONTRACTOR:
92219 OR-202 Astoria, OR 97103
STRUCTURAL ENGINEER
PROJECT BASIS OF DESIGN
1. PROJECT BASE BID SCOPE OF REPAIR WORK COMPONENTS TO INCLUDE
THE FOLLOWING AREAS OF WORK:
· REMOVE AND DISPOSE OF HARDBOARD AND FIBER CEMENT
WALL CLADDING COMPONENTS
· REMOVE AND DISPOSE OF VINYL WINDOW ASSEMBLIES
· REMOVE AND STORE SWING DOOR ASSEMBLIES
· REMOVE AND DISPOSE OF ASPHALT SHINGLE ROOFING
· REMOVE AND DISPOSE OF METAL PARAPET COPING
· REMOVE AND DISPOSE OF EXPOSED PORTIONS OF EXISTING
MASONRY BRICK CHIMNEY, BOILER VENT STACK, AND
ASSOCIATED FLASHING COMPONENTS
2. SCHEDULED PROJECT COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO:
· WOOD FRAMING AND FURRING MEMBERS
· BATT, FOAM, AND CELLULOSE INSULATION (TO MATCH
EXISTING)
· PLYWOOD AND GYPSUM WALLBOARD SHEATHING
· CODE COMPLIANT WEATHER-RESISTIVE BARRIER (WRB)
AND FLEXIBLE SAM FLASHING
· FIBER CEMENT PLANK LAP CLADDING, TRIM MEMBERS, AND
MOUNTING BLOCKS
· FLANGED VINYL WINDOWS
· ALUMINUM GUTTERS AND DOWNSPOUTS
· METAL PARAPET COPING, TRANSITION FLASHING, AND
THREE-DIMENSIONAL METAL SADDLE FLASHINGS
· SCHEDULED SEALANTS
· EXTERIOR PAINTING
PROJECT DESCRIPTION CONT.:
6. BUILDING F: REFORESTATION WAREHOUSE - ELEVATIONS ARE SIMILAR IN
ASSEMBLY COMPONENTS AND CONSIST OF FIBER CEMENT SIDING,
CEDAR TRIMS AND MOUNTING BLOCKS, (1) METAL ROLL UP DOOR, AND
COMPOSITION ASPHALT SHINGLE ROOFING ASSEMBLIES WITH METAL
FLASHINGS.
6.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSISTS TARGETED REPAIR WORK TO THE EXISTING ROOF
ASSEMBLY AND MAY INCLUDE REMOVAL AND REPLACEMENT OF
EXISTING ASPHALT SHINGLE ROOFING AND FLASHING
COMPONENTS.
7. BUILDING G: PROTECTION WAREHOUSE/OFFICE - ELEVATIONS ARE
SIMILAR IN ASSEMBLY COMPONENTS AND CONSIST OF A COMBINATION
OF T1-11 PLYWOOD SIDING AND FIBER CEMENT PLANK LAP CLADDING, (1)
FLANGED ALUMINUM WINDOW ASSEMBLY, METAL ROLL UP DOOR
ASSEMBLIES, PANEL CLAD SWING DOOR UNITS, AND COMPOSITION
ASPHALT SHINGLE ROOFING ASSEMBLIES WITH METAL FLASHINGS.
7.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSISTS TARGETED REPAIR WORK TO THE EXISTING ROOF
ASSEMBLY AND MAY INCLUDE REMOVAL AND REPLACEMENT OF
EXISTING ASPHALT SHINGLE ROOFING AND FLASHING
COMPONENTS.
8. BUILDING H: CHEMICAL STORAGE WAREHOUSE - ELEVATIONS ARE
SIMILAR IN ASSEMBLY COMPONENTS AND CONSIST OF A COMBINATION
OF T1-11 PLYWOOD SIDING, FIBER CEMENT PLANK LAP CLADDING, AND
TRANSLUCENT FIBERGLASS PANELS, (2) FLANGED ALUMINUM WINDOW
ASSEMBLY, (2) METAL ROLL UP DOOR ASSEMBLIES, (2) PANEL CLAD
SWING DOOR UNITS, AND COMPOSITION ASPHALT SHINGLE ROOFING
ASSEMBLIES WITH METAL FLASHINGS.
8.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL
CONSIST OF REMOVAL, DISPOSAL, AND REPLACEMENT OF ALL ROOF
CLADDINGS INCLUDING UNDERLAYMENT, FLASHINGS, GUTTERS AND
DOWNSPOUTS.
A0.00
COVER SHEET
CODE ANALYSIS
PROJECT DESCRIPTION
05.14.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2025 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-062
Permit Issue Set
O re go n
D ep ar tm en t o f F or es try
A st or ia
D is tri ct
B ui ld in g
- R oo f a nd S id in g R eh ab ili ta tio n
(P O
-6
-0
8)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
O
R -2
A st or ia , O
R
NEW ISSUE REVISED ISSUE ISSUED W/NO CHANGES NOT ISSUED AS PART OF S.O.W.*
DE
TA
IL
N O.
SH
EE
T N
O.
SHEET SEQUENCE AND DETAIL INDEX Pe rm it I ss ue S et:
.14 .20
GENERAL
A0.00 COVER SHEET, GENERAL NOTES, PROJECT AND CODE ANALYSIS
A0.10 SHEET SEQUENCE AND DETAIL INDEX
A1.00 PLAN SHEETS
1 A1.00 SITE PLAN
1 A1.10 BUILDING 'A' ROOF PLAN
2 A1.10 BUILDING 'B' AND 'C' ROOF PLAN
1 A1.11 BUILDING 'D' ROOF PLAN
2 A1.11 BUILDING 'E' ROOF PLAN
3 A1.11 BUILDING 'F' ROOF PLAN
1 A1.12 BUILDING 'G' ROOF PLAN
2 A1.12 BUILDING 'H' ROOF PLAN
A2.00 REFERENCE ELEVATIONS
1 A2.01 BUILDING 'A' MAIN OFFICE PARTIAL FRONT ELEVATION
2 A2.01 BUILDING 'A' MAIN OFFICE PARTIAL FRONT ELEVATION
3 A2.01 BUILDING 'A' MAIN OFFICE ENLARGED CONDITIONS
4 A2.01 BUILDING 'A' MAIN OFFICE SIDE ELEVATION
1 A2.02 BUILDING 'A' MAIN OFFICE PARTIAL REAR ELEVATION
2 A2.02 BUILDING 'A' MAIN OFFICE PARTIAL REAR ELEVATION
3 A2.02 BUILDING 'A' MAIN OFFICE ENLARGED CONDITIONS
4 A2.02 BUILDING 'A' MAIN OFFICE SIDE ELEVATION
1 A2.03 BUILDING 'D' TANKER/ENGINE GARAGE AND WORKSHOP FRONT ELEVATION
2 A2.03 BUILDING 'D' TANKER/ENGINE GARAGE AND WORKSHOP SIDE ELEVATION
3 A2.03 BUILDING 'D' TANKER/ENGINE GARAGE AND WORKSHOP REAR ELEVATION
4 A2.03 BUILDING 'D' TANKER/ENGINE GARAGE AND WORKSHOP SIDE ELEVATION
1 A2.04 BUILDING 'H' CHEMICAL STORAGE WAREHOUSE FRONT ELEVATION
2 A2.04 BUILDING 'H' CHEMICAL STORAGE WAREHOUSE SIDE ELEVATION
3 A2.04 BUILDING 'H' CHEMICAL STORAGE WAREHOUSE REAR ELEVATION
4 A2.04 BUILDING 'H' CHEMICAL STORAGE WAREHOUSE SIDE ELEVATION
3.00 WALL DETAILS
1 A3.01 TYPICAL THRU-WALL FLASHING PROFILE AND LAP ISOMETRIC DETAILS
2 A3.01 TYPICAL FIBER CEMENT PLANK LAP CLADDING WALL ASSEMBLY LAP
AND FASTENING DETAIL
3 A3.01 TYPICAL CLADDING FASTENER INSTALLATION
4 A3.01 TYPICAL SEALANT JOINT CONFIGURATION AND APPLICATION
5 A3.01 BASE OF WALL ASSEMBLY WITH FIBER CEMENT PLANK LAP
CLADDING - ISOMETRIC DETAIL
6 A3.01 TYPICAL MOUNTING BLOCK AND SEALANT INSTALLATION AT FIBER
CEMENT PLANK LAP CLADDING AND TRIM
7 A3.01 OUTSIDE CORNER JOINT CONDITION WITH FIBER CEMENT CLADDING
OVER RAINSCREEN CAVITY
8 A3.01 INSIDE CORNER JOINT CONDITION WITH FIBER CEMENT CLADDING
OVER RAINSCREEN CAVITY
9 A3.01 BASE OF WALL CLADDING TERMINATION FLASHING AT EXPOSED
CONCRETE STEM WALL
1 A3.02 GRADE BASE OF WALL FLASHING WITH CLEARANCE AT FIBER
CEMENT PLANK LAP CLADDING OVER RAINSCREEN CAVITY
2 A3.02 DOWNSPOUT CLEANOUT ASSEMBLY AT GRADE WITH FIBER CEMENT
PLANK LAP CLADDING
3 A3.02 BASE OF WALL FLASHING WITH KERF CUT CONCRETE SLAB AND
FIBER CEMENT CLADDING OVER RAINSCREEN CAVITY
4 A3.02 SAME PLANE TRIM WITH BRACKETED DOWNSPOUT AT FIBER CEMENT
CLADDING AND TRIM - PLAN VIEW
5 A3.02 VERTICAL TRANSITION JOINT AT FIBER CEMENT CLADDING TO
EXPOSED CONCRETE - PLAN VIEW
6 A3.02 INSIDE CORNER TRANSITION JOINT AT FIBER CEMENT CLADDING TO
EXPOSED CONCRETE - PLAN VIEW
7 A3.02 PERPENDICULAR RATED PARTITION WALL TRANSITION WITH FIBER
CEMENT CLADDING
8 A3.02 RATED PARTITION WALL END CAP DETAIL WITH FIBER CEMENT
CLADDING, TRIM, AND SEALANT
1 A3.03 SOFFIT TRANSITION DETAIL AT FIBER CEMENT PLANK LAP CLADDING
2 A3.03 SOFFIT TO WALL CORNER TRANSITION - ISOMETRIC SEQUENCE
5 A3.03 EXHAUST VENT PENETRATION WITH MOUNTING BLOCK AT FIBER
CEMENT PLANK LAP CLADDING
6 A3.03 TYPICAL MOUNTING BLOCK INSTALLATION AT FIBER CEMENT PLANK
LAP CLADDING - ISOMETRIC SEQUENCE
8 A3.03 SOFFIT TO EXTERIOR WALL TRANSITION DETAIL AT FIBER CEMENT
PLANK LAP CLADDING
1 A3.04 SURFACE MOUNTED ELECTRICAL BOX AT FIBER CEMENT PLANK LAP
CLADDING OVER RAINSCREEN CAVITY
2 A3.04 RECESSED FIXTURE / J-BOX WITH MOUNTING BLOCK AT FIBER
CEMENT CLADDING OVER RAINSCREEN CAVITY
3 A3.04 HOSE BIBB / PIPE PENETRATION WITH MOUNTING CLOCK AT FIBER
CEMENT CLADDING OVER RAINSCREEN CAVITY
4 A3.04 WIDE MOUNTING BLOCK INSTALL WITH FIBER CEMENT PLANK LAP CLADDING
5 A3.04 UTILITY MOUNTING BLOCK WITH PROPER DATA CABLE PENETRATION
WITH FIBER CEMENT PLANK LAP CLADDING
SHEET SEQUENCE AND DETAIL INDEX
DE
TA
IL
N
O.
SH
EE
T N
O.
SHEET SEQUENCE AND DETAIL INDEX Pe rm it I ss ue S et:
.14 .20
IS
SU
E
DA
TE
5.00 ROOF DETAILS
1 A5.01 TYPICAL ROOF FLASHING - ISOMETRIC DETAILS
2 A5.01 ROOF EAVE OVERHANG DETAIL AT TOP OF WALL
3 A5.01 ROOF GABLE/RAKE FASCIA DETAIL AT TOP OF WALL
4 A5.01 BLDG D AND H ROOF GABLE/RAKE FASCIA DETAIL WITH WIND DAM
FLASHING AT TOP OF EXISTING WALL
5 A5.01 ROOF TO WALL STEP FLASHING INTEGRATION AT FIBER CEMENT
PLANK LAP CLADDING
6 A5.01 BUILDING A METER CLOSET/BUILDING E & F ROOF TO WALL APRON
FLASHING INTEGRATION
7 A5.01 TYPICAL VALLEY CONDITION WITH UNDERLAYMENT AND METAL
VALLEY FLASHING
8 A5.01 CONTINUOUS RIDGE VENT COMPONENT PENETRATION AT PITCHED
ROOF CONDITION
1 A5.02 UNVENTED RIDGE SHINGLE CONDITION AT PITCHED ROOF
ASSEMBLY WITH COMPOSITION ASPHALT SHINGLE ROOFING
2 A5.02 DEAD VALLEY CRICKET TO RATED SEPARATION WALL WITH FIBER
CEMENT PLANK LAP CLADDING
3 A5.02 STATIC ROOF VENT ASSEMBLY AT KITCHEN/BATH EXHAUST DUCT
5 A5.02 BOILER HEAT VENT EXHAUST STACK PENETRATION AT PITCHED
COMPOSITION ASPHALT SHINGLE ROOF ASSEMBLY
6 A5.02 BOILER HEAT VENT EXHAUST STACK PENETRATION AT PITCHED
ROOF CONDITION - ISOMETRIC SEQUENCE
1 A5.03 TYPICAL THRU-ROOF PIPE PENETRATION AT PITCHED ROOF
ASSEMBLY WITH COMPOSITION ASPHALT SHINGLE ROOFING
2 A5.03 BUILDING E & F ACTIVE ROOF VENT AT PITCHED ROOF ASSEMBLY
WITH COMPOSITION ASPHALT SHINGLE ROOFING
3 A5.03 ROOF RIDGE TO WALL FLASHING TRANSITION - ISOMETRIC
SEQUENCE
5 A5.03 ROOF TO WALL PERPENDICULAR TRANSITION - ISOMETRIC SEQUENCE
7 A5.03 METER CLOSET ROOF TO WALL SHED ROOF TRANSITION - ISOMETRIC
SEQUENCE
1 A5.04 ROOF TO RATED PARTITION WALL CRICKET WITH END WALL
DIVERTER FLASHING - ISOMETRIC SEQUENCE
5 A5.04 ROOF SADDLE TRANSITION AT RIDGE TO PITCHED ROOF CONDITION -
ISOMETRIC DETAIL
6 A5.04 BUILDING F ROOF SADDLE TRANSITION CONDITION AT GABLE TO
PITCHED ROOF CONDITION ISOMETRIC DETAIL
7 A5.04 ANTENNA GUY WIRE CONNECTION HARDWARE AT PITCHED ROOF
ATTACHMENT
DE
TA
IL
N
O.
SH
EE
T N
O.
SHEET SEQUENCE AND DETAIL INDEX Pe rm it I ss ue S et:
.14 .20
IS
SU
E
DA
TE
3.00 WALL DETAILS CONT.
6 A3.04 NON-PENETRATING MOUNTING BLOCK WITH FIBER CEMENT PLANK
LAP CLADDING
7 A3.04 LOUVERED VENT HEAD AND SILL FLASHING WITH FIBER CEMENT
PLANK LAP CLADDING
1 A3.05 RECESSED METER BASE HEAD WITH FIBER CEMENT PLANK LAP CLADDING
3 A3.05 METER BASE CONDUIT FLASHING WITH FIBER CEMENT PLANK LAP
CLADDING - PLAN VIEW
4 A3.05 METER BASE GANGED CONDUIT FLASHING WITH FIBER CEMENT
PLANK LAP CLADDING - PLAN VIEW
5 A3.05 UTILITY PANEL INSTALLATION - ISOMETRIC SEQUENCE
7 A3.05 GANGED UTILITY PENETRATION FLASHING WITH MOUNTING BLOCK
WITH FIBER CEMENT PLANK LAP CLADDING
8 A3.05 WALL INTEGRATION OF ENTRY FLASHING WITH FIBER CEMENT PLANK
LAP CLADDING - ISOMETRIC DETAIL
1 A3.06 RATED PARAPET PARTITION WALL AT ROOF WITH CAP FLASHING AND
FIBER CEMENT PLANK LAP CLADDING
2 A3.06 BUILDING A GABLE END ANTENNA / METEOROLOGICAL EQUIPMENT
MOUNT WITH ATTACHMENT AT FASCIA TRIM
3 A3.06 BUILDING D CCTV POST ATTACHMENT BRACKET CONDITION AT
EXISTING T1-11 CLADDING
5 A3.06 TOP OF WALL AT EAVE OVERHANG WITH FIBER CEMENT PLANK LAP
CLADDING
5 A3.06 TOP OF WALL TO GABLE/RAKE FASCIA WITH FIBER CEMENT PLANK
LAP CLADDING
1 A3.07 SADDLE FLASHING INTEGRATION DETAIL AT PERPENDICULAR
FOUNDATION TRANSITION - ISOMETRIC SEQUENCE
A4.00 WALL OPENING DETAILS
1 A4.00 WINDOW TYPE, WALL OPENING SCHEDULE
2 A4.00 WINDOW TYPES
1 A4.01 TYPICAL WINDOW FLASHING - INSTALLATION LOCATIONS
2 A4.01 REPLACEMENT WINDOW HEAD DETAIL - CONCEALED COMPONENT -
INSTALL CONDITION
3 A4.01 REPLACEMENT WINDOW HEAD DETAIL WITH TRIM AND CLADDING
COMPONENTS OVER RAINSCREEN CAVITY
4 A4.01 WINDOW HEAD CLADDING JOINT WITH SCHEDULED FIBER CEMENT
PLANK LAP CLADDING - ISOMETRIC DETAIL
5 A4.01 REPLACEMENT WINDOW HEAD DETAIL AT CONCRETE FOUNDATION
WALL OPEING - INSTALL CONDITION
6 A4.01 REPLACEMENT WINDOW JAMB DETAIL - CONCEALED COMPONENTS -
INSTALL CONDITION
7 A4.01 REPLACEMENT WINDOW JAMB DETAIL WITH FIBER CEMENT TRIM AND
CLADDING COMPONENTS OVER RAINSCREEN CAVITY
8 A4.01 REPLACEMENT WINDOW JAMB - INSIDE CORNER WITH FIBER CEMENT
TRIM AND CLADDING COMPONENTS - INSTALL CONDITION
1 A4.02 REPLACEMENT WINDOW JAMB DETAIL AT CONCRETE FOUNDATION
WALL OPENING - INSTALL CONDITION
2 A4.02 REPLACEMENT WINDOW SILL - CONCEALED COMPONENTS - INSTALL
CONDITION
3 A4.02 REPLACEMENT WINDOW SILL DETAIL WITH TRIM AND CLADDING
COMPONENTS OVER RAINSCREEN CAVITY
4 A4.02 REPLACEMENT WINDOW SILL DETAIL WITH FLANGE AT CONCRETE
FOUNDATION STEM WALL
5 A4.02 REPLACEMENT WINDOW SILL DETAIL AT CONCRETE FOUNDATION
WALL OPENING - INSTALL CONDTION
1 A4.03 SWING DOOR HEAD DETAIL - TRIM AND CLADDING
2 A4.03 SWING DOOR JAMB DETAIL - TRIM AND CLADDING
3 A4.03 SWING DOOR CORNER JAMB DETAIL - TRIM AND CALDDING
4 A4.03 ENTRY SWING DOOR SILL AT NEAR FLUSH CONCRETE WALKWAY SLAB
1 A4.04 TYPICAL VINYL WINDOW INSTALL - ISOMETRIC SEQUENCE
1 A4.05 TSWING DOOR INSTALL AT CONCRETE SLAB - ISOMETRIC SEQUENCE
DE
TA
IL
N
O.
SH
EE
T N
O.
SHEET SEQUENCE AND DETAIL INDEX IS
SU
E
DA
TE
IS
SU
E
DA
TE
A0.01
SHEET SEQUENCE
AND DETAIL INDEX
05.14.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2025 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-062
Permit Issue Set
O re go n
D ep ar tm en t o f F or es try
A st or ia
D is tri ct
B ui ld in g
- R oo f a nd S id in g R eh ab ili ta tio n
(P O
-6
-0
8)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
O
R -2
A st or ia , O
R
N
1 SITE PLAN
1" = 100'-0" Oregon Department of Forestry - Astoria District mhg
GENERAL SITE NOTES:
1. CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS TO BETTER UNDERSTAND THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS, ELEVATIONS AND CONDITIONS PRIOR TO BEGINNING ANY WORK AND NOTIFY FORENSIC OF ANY DISCREPANCIES. DO NOT SCALE DRAWINGS.
2. SITE PLAN ARE CREATED USING INFORMATION REPRODUCED FROM BASE DRAWINGS ACQUIRED FROM PUBLIC RECORD, AND/OR PREPARED BY ORIGINAL/PREVIOUS ARCHITECT, DESIGNER, AND/OR CONSULTANT. BRING ANY DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE BUILDING
ENCLOSURE CONSULTANT AND REQUEST A REVIEW.
3. BUILDINGS OR AREAS DESIGNATED AS NOT IN CONTRACT (N.I.C.) ARE OUTSIDE OF THE LIMITS AND SCOPE OF THE PROPOSED WORK. N.I.C. BUILDINGS MAY BE ANCILLARY OR NOT BE DIRECTLY ASSOCIATED WITH THE PROJECT PROPERTY AT ALL. N.I.C. DESIGNATED BUILDINGS AND AREAS ARE INCLUDED FOR SITUATIONAL REFERENCE TO THE
BOUNDARIES OF THE PROJECT ONLY.
4. UNLESS OTHERWISE INDICATED ON THESE DRAWINGS OR IN THE PROJECT MANUAL AS BEING N.I.C. OR EXISTING, ALL ITEMS, MATERIALS, ETC. AND INSTALLATION OF THE SAME ARE PART OF THE CONTRACT DEFINED BY THESE DRAWINGS
AND SPECIFICATIONS.
5. THE CONTRACTOR IS TO VERIFY AND MAINTAIN, OR REPLACE EXISTING ASSEMBLIES AS NECESSARY TO MEET RATED WALL REQUIREMENTS. OVERSIGHT REQUIRED BY A LICENSED STRUCTURAL ENGINEER TO BE PROVIDED FOR FRAMING AND SHEATHING INCLUDING RATED WALL ASSEMBLIES WHERE REPAIR WORK IS IDENTIFIED DURING CONSTRUCTION.
PROVIDE ENGINEERED DRAWINGS SHOWING EXTENT, DETAILS, AND CALCULATIONS TO THE AUTHORITY HAVING
JURISDICTION FOR REVIEW AND APPROVAL PRIOR TO REMEDIATION.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND EXECUTION OF ALL PERMITS, LICENSES, INSPECTIONS AND TESTING AS REQUIRED BY THE CONTRACT DOCUMENTS OR ANY GOVERNMENT AGENCY.
7. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOBSITE CONDITIONS. COMPLY WITH SAFETY REGULATIONS AND RESTRICTIONS AS REQUIRED FOR WORKER AND PEDESTRIAN PROTECTION DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT. PROVIDE PROTECTION AS REQUIRED TO PREVENT ANY DAMAGE TO EXISTING CONSTRUCTION WITHIN AND ADJACENT TO THE JOBSITE. WHERE DAMAGE OCCURS, REPAIR OR REPLACE DAMAGED AREA AND/OR MATERIAL AS REQUIRED TO THE OWNER'S APPROVAL AT NO ADDITIONAL COST. THESE
REQUIREMENTS SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL HOURS.
8. SHOULD ANY CONCRETE REQUIRE PATCHING ADJACENT TO IN SCOPE BUILDINGS, IT SHALL BE OF THE SAME SECTION
AND DRAINAGE PROFILE AS THE ADJACENT PAVED AREAS.
SITE AREAS AND INFORMATION:
1. Total Site Area: 32.68 AC. (1,423,540.8 SF)
2. County Seat: Clatsop
3. Zoning: LR (Land Reserve)
4. Map Tax Lot: 80927 0002000
SITE LEGEND:
APPROXIMATE AREAS OF EXISTING 'MAJOR' SITE TREES.
SITE KEY NOTES:
EXISTING GRAVEL PROPERTY ACCESS/DRIVE/APRON/PARKING AREA: (NOT IN SCOPE)
EXISTING CONCRETE DRIVES, ASPHALT PAVING, APRONS, WALKWAYS, AND FLATWORK AREAS: NOT IN PROJECT SCOPE.
ALTERATION OF EXISTING UNIMPROVED/LANDSCAPED AREAS, VEGETATION, AND SITE TREES ARE NOT WITHIN THE SCOPE
OF THE PROPOSED REHABILITATION PROJECT.
APPROXIMATE LOCATION OF SEASONAL CREEK AND HIGHWAY RUNOFF.
THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL BE CONSIDERED 'LIKE FOR LIKE' IN GENERAL APPEARANCE AND INCLUDE WORK TO CLADDING, ROOFING, AND FENESTRATIONS AS DESIGNATED ON SHEET A0.00.
ADJACENT
PARCEL
(N.I.C.)
WALLUSKI LOOP
'10
0'
90'
80'
80'
698.0'
94.4'90.0'
9.
5'
227.8'
2.
2'
0.
.0
5.
4'
57.0'
209.8'
210.3'
9.7
660.0' 270.0'
253.4' N27°27'00"W
720.0'
O
R HIG
HW
AY 202
O R
H
IG
H
W A
Y
125.0' BPA TRANSMISSION LINE EASEMENT
± 100'-0"
ADJACENT
PARCEL
(N.I.C.)
ADJACENT
PARCEL
(N.I.C.)
ADJACENT
PARCEL
(N.I.C.)
ADJACENT
PARCEL
(N.I.C.)
ADJACENT
PARCEL
(N.I.C.)
ADJACENT
PARCEL
(N.I.C.)
BUILDING LEGEND:
MAIN OFFICE BUILDING
MECHANIC'S SHOP
PUMPER SHED
OLD PRESERVATION BUILDING
REFORESTATION WAREHOUSE/OFFICE BUILDING
PROTECTION WAREHOUSE/OFFICE BUILDING
CHEMICAL STORAGE WAREHOUSE BUILDING
A
A
B
B
D
E
F
H
G
F E
G
D
C
H
ADJACENT
PARCEL
(N.I.C.)
C
A1.00
SITE PLAN
05.14.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2025 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-062
Permit Issue Set
O re go n
D ep ar tm en t o f F or es try
A st or ia
D is tri ct
B ui ld in g
- R oo f a nd S id in g R eh ab ili ta tio n
(P O
-6
-0
8)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
O
R -2
A st or ia , O
R
2 BUILDING 'B' AND 'C' ROOF PLAN
1/8" = 1'-0" mhg
ROOF PLAN KEYNOTES:
ROOF PLAN NOTES:
1. COORDINATE ROOF DEMOLITION WITH SCHEDULED WORK AT ADJACENT EXTERIOR WALL CLADDING
INTEGRATION WORK PER THE DESIGN DOCUMENTS AND ACCOMPANYING PROJECT MANUAL. PERFORM
SELECTIVE AND LIMITED DEMOLITION OF EXISTING WALL ASSEMBLIES AS REQUIRED.
2. VERIFY CLEARANCE REQUIREMENTS AND MATCH ASSEMBLY OF EXISTING FIRE RATED WALLS AND ROOF
SYSTEMS WHERE REPAIRED DURING THE COURSE OF REQUIRED WORK.
3. REPLACE EXTERIOR PLYWOOD AND GYPSUM WALLBOARD SHEATHING AS NECESSARY TO PERFORM REQUIRED WORK AND AS NECESSARY TO CHASE DAMAGE TO EXTINCTION. PATCH, REPAIR, AND MATCH
PLANE OF EXISTING ADJACENT SURFACES.
4. PLANS HAVE BEEN CREATED USING INFORMATION REPRODUCED FROM INFORMATION ACQUIRED FROM PUBLIC RECORD, THIRD PARTY DATA SETS, AND/OR PREPARED BY ORIGINAL/PREVIOUS ARCHITECT, DESIGNER, AND/OR CONSULTANT. PLANS ARE FOR REFERENCE TO EXISTING CONDITIONS, WALL LOCATIONS, AND FENESTRATIONS ONLY. BRING ANY DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE BUILDING ENCLOSURE CONSULTANT AND
REQUEST A REVIEW.
5. CONTRACTOR TO VERIFY VENTILATION OF EXISTING BUILDING ATTIC AREA FOR VENTILATION REQUIREMENTS.
INSTALL ADDITIONAL INTAKE AT EAVE AND UPPER ROOF EXHAUST LOCATIONS AS REQUIRED.
6. CONTRACTOR SHALL MAKE REQUIRED REPAIRS TO EXISTING RATED DRAFT STOP ASSEMBLIES TO ENSURE
CONTINUOUS FIRE RATING FOR EACH EXISTING ATTIC AREA.
ROOF PLAN LEGEND:
REMOVE AND DISPOSE OF 100% OF EXISTING COMPOSITION ASPHALT SHINGLE
ROOFING, UNDERLAYMENT, STATIC VENTS, EXHAUST VENTS, AND ASSOCIATED ROOF
AND FLASHING COMPONENTS. INSTALL SCHEDULED COMPOSITION ASPHALT SHINGLE
ROOFING, UNDERLAYMENT, AND ASSOCIATED COMPONENTS PER DESIGN DOCUMENT
ROOF DETAILS AND PROJECT MANUAL.
INSTALL SCHEDULED ROOF GUTTERS AT ROOF EAVE LOCATIONS WITH DOWNSPOUTS
AND CLEANOUT LOCATED TO TIE INTO EXISTING SITE STORM SEWER LOCATIONS.
REFER TO DESIGN DOCUMENT PACKAGE AND PROJECT MANUAL.
STATIC STEMMED ROOF VENT ASSEMBLY, CONTRACTOR TO ACCOUNT FOR TIGHT-LINING
100% OF BUILDINGS BATH AND KITCHEN LOCATIONS AS OCCURS, REFER TO DETAIL 3/A5.02
PLUMBING VENT STACK ASSEMBLY, REFER TO DETAIL 1/A5.03
SCHEDULED CONTINUOUS RIDGE VENT, REFER TO DETAIL 8/A5.01
APPROXIMATE LOCATION OF STEMMED STATIC ROOF VENT PENETRATION.
EXISTING ROOF SLOPE TO REMAIN.
APPROXIMATE LOCATION OF BOILER EXHAUST STACK PENETRATION.
APPROXIMATE LOCATION OF PLUMBING STACK VENT PENETRATION.
APPROXIMATE LOCATION OF CONTINUOUS RIDGE EXHAUST VENT.
BOILER VENT STACK ASSEMBLY, REFER TO DETAIL 5/A5.02
1 BUILDING 'A' ROOF PLAN
1/8" = 1'-0" mhg
N
N
APPROXIMATE LOCATION OF TURBINE VENT PENETRATION.
A5.01 TYP.
A5.01 TYP. 1
A3.03
A5.01 TYP.
A5.01 TYP.
A3.03
A5.01TYP.
A3.06 8
A5.01TYP.
A5.02
A5.03
A5.01TYP.
A5.01 TYP.
A5.01 SIM.
A5.--SIM.
A5.01SIM.
A5.01 SIM.
A5.01TYP.
A5.01TYP.
A5.01TYP.
SIM.
2 TYP.
1 TYP.
1 TYP.
2 TYP.
1 TYP.2 TYP.
2TYP.
1TYP.
TYP.
ANTENNA POLE ASSEMBLY AND 3-POINT GUY-WIRE ATTACHMENT, REFER TO VENT PIPE
PENETRATION DETAIL 1/A5.03 FOR SIMILAR ROOF INTEGRATION AND TO DETAIL 7/A5.04.
TYP.
A5.02
A5.02
A5.021
A5.02
A3.04
SIM.
A5.04 TYP.3
A5.02TYP.
A5.02
A5.02
4'-0" 4'-0"
A5.02 1
A5.02
A5.01 BELOW
A5.04
A5.04SIM.
A5.04TYP.
TARGETED ROOF REHABILITATION AND REPAIRS AT IDENTIFIED LOCATIONS TO BE DETAILED IN SIMILAR FASHION TO CONDITIONS FOR THE FULL ROOFING REPLACEMENT OCCURRING AT BUILDING 'A'. REFER
TO DESIGN PACKAGE FOR RELATED DETAILS AND CORRELATING CONDITIONS.
SIM.
A5.02
SIM. AS
NEEDED
DS APPROXIMATE LOCATION OF EXISTING DOWNSPOUT, CLEANOUT, AND STORM
SEWER TIE-IN OR DAYLIGHT TO GRADE.
DS DSDSDSDS
DSDS
DS
DS
DS DS
DS
DS DS
DS
DSDSDS
DS
DS DS
DS DS
A5.03
SIM. AS
NEEDED
A1.10
TYPE 1 & 2
ROOF PLANS
05.14.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2025 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-062
Permit Issue Set
O re go n
D ep ar tm en t o f F or es try
A st or ia
D is tri ct
B ui ld in g
- R oo f a nd S id in g R eh ab ili ta tio n
(P O
-6
-0
8)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
O
R -2
A st or ia , O
R
1 BUILDING 'D' ROOF PLAN
mhg
2 BUILDING 'E' ROOF PLAN
1/8" = 1'-0" ORIENTATION VARIES
mhg
3 BUILDING 'F' ROOF PLAN
1/8" = 1'-0" mhg
N
N N
A5.01
TYP.
A5.01
SIM.
A5.01 SIM.
A5.01SIM.
A5.01 8
A5.01TYP.
A5.01
BELOW
A5.--
ROOF PLAN KEYNOTES:
ROOF PLAN NOTES:
1. COORDINATE ROOF DEMOLITION WITH SCHEDULED WORK AT ADJACENT EXTERIOR WALL CLADDING
INTEGRATION WORK PER THE DESIGN DOCUMENTS AND ACCOMPANYING PROJECT MANUAL. PERFORM
SELECTIVE AND LIMITED DEMOLITION OF EXISTING WALL ASSEMBLIES AS REQUIRED.
2. VERIFY CLEARANCE REQUIREMENTS AND MATCH ASSEMBLY OF EXISTING FIRE RATED WALLS AND ROOF
SYSTEMS WHERE REPAIRED DURING THE COURSE OF REQUIRED WORK.
3. REPLACE EXTERIOR PLYWOOD AND GYPSUM WALLBOARD SHEATHING AS NECESSARY TO PERFORM REQUIRED WORK AND AS NECESSARY TO CHASE DAMAGE TO EXTINCTION. PATCH, REPAIR, AND MATCH
PLANE OF EXISTING ADJACENT SURFACES.
4. PLANS HAVE BEEN CREATED USING INFORMATION REPRODUCED FROM INFORMATION ACQUIRED FROM PUBLIC RECORD, THIRD PARTY DATA SETS, AND/OR PREPARED BY ORIGINAL/PREVIOUS ARCHITECT, DESIGNER, AND/OR CONSULTANT. PLANS ARE FOR REFERENCE TO EXISTING CONDITIONS, WALL LOCATIONS, AND FENESTRATIONS ONLY. BRING ANY DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE BUILDING ENCLOSURE CONSULTANT AND
REQUEST A REVIEW.
5. CONTRACTOR TO VERIFY VENTILATION OF EXISTING BUILDING ATTIC AREA FOR VENTILATION REQUIREMENTS.
INSTALL ADDITIONAL INTAKE AT EAVE AND UPPER ROOF EXHAUST LOCATIONS AS REQUIRED.
6. CONTRACTOR SHALL MAKE REQUIRED REPAIRS TO EXISTING RATED DRAFT STOP ASSEMBLIES TO ENSURE
CONTINUOUS FIRE RATING FOR EACH EXISTING ATTIC AREA.
ROOF PLAN LEGEND:
REMOVE AND DISPOSE OF 100% OF EXISTING COMPOSITION ASPHALT SHINGLE
ROOFING, UNDERLAYMENT, STATIC VENTS, EXHAUST VENTS, AND ASSOCIATED ROOF
AND FLASHING COMPONENTS. INSTALL SCHEDULED COMPOSITION ASPHALT SHINGLE
ROOFING, UNDERLAYMENT, AND ASSOCIATED COMPONENTS PER DESIGN DOCUMENT
ROOF DETAILS AND PROJECT MANUAL.
INSTALL SCHEDULED ROOF GUTTERS AT ROOF EAVE LOCATIONS WITH DOWNSPOUTS
AND CLEANOUT LOCATED TO TIE INTO EXISTING SITE STORM SEWER LOCATIONS.
REFER TO DESIGN DOCUMENT PACKAGE AND PROJECT MANUAL.
STATIC STEMMED ROOF VENT ASSEMBLY, CONTRACTOR TO ACCOUNT FOR TIGHT-LINING
100% OF BUILDINGS BATH AND KITCHEN LOCATIONS AS OCCURS, REFER TO DETAIL 3/A5.02.
PLUMBING VENT STACK ASSEMBLY, REFER TO DETAIL 1/A5.03.
SCHEDULED CONTINUOUS RIDGE VENT, REFER TO DETAIL 8/A5.01.
APPROXIMATE LOCATION OF STEMMED STATIC ROOF VENT PENETRATION.
EXISTING ROOF SLOPE TO REMAIN.
APPROXIMATE LOCATION OF BOILER EXHAUST STACK PENETRATION.
APPROXIMATE LOCATION OF PLUMBING STACK VENT PENETRATION.
APPROXIMATE LOCATION OF TURBINE VENT PENETRATION.
2 TYP.
1 TYP.
2 TYP.1 TYP.
TARGETED ROOF REHABILITATION AND REPAIRS AT IDENTIFIED LOCATIONS TO BE DETAILED IN SIMILAR FASHION TO CONDITIONS FOR THE FULL ROOFING REPLACEMENT OCCURRING AT BUILDING 'A'. REFER
TO DESIGN PACKAGE FOR RELATED DETAILS AND CORRELATING CONDITIONS.
TARGETED ROOF REHABILITATION AND REPAIRS AT IDENTIFIED LOCATIONS TO BE DETAILED IN SIMILAR FASHION TO CONDITIONS FOR THE FULL ROOFING REPLACEMENT OCCURRING AT BUILDING 'A'. REFER
TO DESIGN PACKAGE FOR RELATED DETAILS AND CORRELATING CONDITIONS.
A5.03
TYP. AS
NEEDED
NOT USED
NOT USED
8 CCTV POST ATTACHMENT BRACKET CONDITION, REFER TO DETAIL 3/A3.06.
A5.03 SIM.
TYP.
A5.04
TYP. AS
NEEDED 2
A5.03
TYP. AS
NEEDED
APPROXIMATE LOCATION OF CONTINUOUS RIDGE EXHAUST VENT.
DS APPROXIMATE LOCATION OF EXISTING DOWNSPOUT, CLEANOUT, AND STORM
SEWER TIE-IN OR DAYLIGHT TO GRADE.
DS
DS
DS DS DS
DS
DS
DS
DS
DS DS
DS DS
DS
DS DS
DS
A1.11
TYPE 3 & 4
ROOF PLANS
05.14.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2025 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-062
Permit Issue Set
O re go n
D ep ar tm en t o f F or es try
A st or ia
D is tri ct
B ui ld in g
- R oo f a nd S id in g R eh ab ili ta tio n
(P O
-6
-0
8)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
O
R -2
A st or ia , O
R
1 BUILDING 'G' ROOF PLAN
mhg
1 BUILDING 'H' ROOF PLAN
1/8" = 1'-0" mhg
N N
A5.01
TYP.
A501TYP.
-4
A5.01 TYP.
A5.01TYP
ROOF PLAN KEYNOTES:
ROOF PLAN NOTES:
1. COORDINATE ROOF DEMOLITION WITH SCHEDULED WORK AT ADJACENT EXTERIOR WALL CLADDING
INTEGRATION WORK PER THE DESIGN DOCUMENTS AND ACCOMPANYING PROJECT MANUAL. PERFORM
SELECTIVE AND LIMITED DEMOLITION OF EXISTING WALL ASSEMBLIES AS REQUIRED.
2. VERIFY CLEARANCE REQUIREMENTS AND MATCH ASSEMBLY OF EXISTING FIRE RATED WALLS AND ROOF
SYSTEMS WHERE REPAIRED DURING THE COURSE OF REQUIRED WORK.
3. REPLACE EXTERIOR PLYWOOD AND GYPSUM WALLBOARD SHEATHING AS NECESSARY TO PERFORM REQUIRED WORK AND AS NECESSARY TO CHASE DAMAGE TO EXTINCTION. PATCH, REPAIR, AND MATCH
PLANE OF EXISTING ADJACENT SURFACES.
4. PLANS HAVE BEEN CREATED USING INFORMATION REPRODUCED FROM INFORMATION ACQUIRED FROM PUBLIC RECORD, THIRD PARTY DATA SETS, AND/OR PREPARED BY ORIGINAL/PREVIOUS ARCHITECT, DESIGNER, AND/OR CONSULTANT. PLANS ARE FOR REFERENCE TO EXISTING CONDITIONS, WALL LOCATIONS, AND FENESTRATIONS ONLY. BRING ANY DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE BUILDING ENCLOSURE CONSULTANT AND
REQUEST A REVIEW.
5. CONTRACTOR TO VERIFY VENTILATION OF EXISTING BUILDING ATTIC AREA FOR VENTILATION REQUIREMENTS.
INSTALL ADDITIONAL INTAKE AT EAVE AND UPPER ROOF EXHAUST LOCATIONS AS REQUIRED.
6. CONTRACTOR SHALL MAKE REQUIRED REPAIRS TO EXISTING RATED DRAFT STOP ASSEMBLIES TO ENSURE
CONTINUOUS FIRE RATING FOR EACH EXISTING ATTIC AREA.
ROOF PLAN LEGEND:
APPROXIMATE LOCATION OF STEMMED STATIC ROOF VENT PENETRATION.
EXISTING ROOF SLOPE TO REMAIN.
APPROXIMATE LOCATION OF BOILER EXHAUST STACK PENETRATION.
APPROXIMATE LOCATION OF PLUMBING STACK VENT PENETRATION.
APPROXIMATE LOCATION OF TURBINE VENT PENETRATION.
2 TYP.
1 TYP.
2TYP.
1TYP.
A5.02
A5.01
TARGETED ROOF REHABILITATION AND REPAIRS AT IDENTIFIED LOCATIONS TO BE DETAILED IN SIMILAR FASHION TO CONDITIONS FOR THE FULL ROOFING REPLACEMENT OCCURRING AT BUILDING 'A'. REFER
TO DESIGN PACKAGE FOR RELATED DETAILS AND CORRELATING CONDITIONS.
4'- 0"
A5.02
SIM. AS
NEEDED
ANTENNA POLE ASSEMBLY AND 3-POINT GUY-WIRE ATTACHMENT, REFER TO VENT PIPE
PENETRATION DETAIL 1/A5.03 FOR SIMILAR ROOF INTEGRATION AND TO DETAIL 7/A5.04.
NOT USED
APPROXIMATE LOCATION OF CONTINUOUS RIDGE EXHAUST VENT.
DS APPROXIMATE LOCATION OF EXISTING DOWNSPOUT, CLEANOUT, AND STORM
SEWER TIE-IN OR DAYLIGHT TO GRADE.
DS
DS
DS
DS
DS
DS DS
DS
REMOVE AND DISPOSE OF 100% OF EXISTING COMPOSITION ASPHALT SHINGLE
ROOFING, UNDERLAYMENT, STATIC VENTS, EXHAUST VENTS, AND ASSOCIATED ROOF
AND FLASHING COMPONENTS. INSTALL SCHEDULED COMPOSITION ASPHALT SHINGLE
ROOFING, UNDERLAYMENT, AND ASSOCIATED COMPONENTS PER DESIGN DOCUMENT
ROOF DETAILS AND PROJECT MANUAL.
INSTALL SCHEDULED ROOF GUTTERS AT ROOF EAVE LOCATIONS WITH DOWNSPOUTS
AND CLEANOUT LOCATED TO TIE INTO EXISTING SITE STORM SEWER LOCATIONS.
REFER TO DESIGN DOCUMENT PACKAGE AND PROJECT MANUAL.
STATIC STEMMED ROOF VENT ASSEMBLY, CONTRACTOR TO ACCOUNT FOR TIGHT-LINING
100% OF BUILDINGS BATH AND KITCHEN LOCATIONS AS OCCURS, REFER TO DETAIL 3/A5.02.
PLUMBING VENT STACK ASSEMBLY, REFER TO DETAIL 1/A5.03.
SCHEDULED CONTINUOUS RIDGE VENT, REFER TO DETAIL 8/A5.01.
A1.12
TYPE 5
ROOF PLAN
05.14.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2025 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-062
Permit Issue Set
O re go n
D ep ar tm en t o f F or es try
A st or ia
D is tri ct
B ui ld in g
- R oo f a nd S id in g R eh ab ili ta tio n
(P O
-6
-0
8)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
O
R -2
A st or ia , O
R
EXISTING CONCRETE FOUNDATION WALLS TO REMAIN, REFER TO BASE OF WALL DETAILS FOR INTEGRATION
OF WRB AND FLASHING PROVISIONS.
EXISTING VINYL WINDOW UNIT, INCLUDING ADJACENT TRIM AND CONCEALED COMPONENTS TO BE REMOVED AND LEGALLY DISPOSED OF. INSTALL SCHEDULED REPLACEMENT FLANGED VINYL WINDOW UNIT, INCLUDING RELATED SAM PRE AND POST WRAP FLASHING, METAL HEAD FLASHING, AND RELATED CONCEALED COMPONENTS, TYPICAL. INSTALL SCHEDULED DYNAMIC SEALANT JOINTS AND FIBER CEMENT TRIM ALONG 100% OF WINDOW PERIMETERS. REFER TO WALL OPENING DETAILS AND PROJECT MANUAL.
ELEVATION KEYNOTES:
EXISTING EXTERIOR SIDING AND TRIM TO BE REMOVED AND LEGALLY DISPOSED OF. INSTALL SCHEDULED REPLACEMENT FIBER CEMENT PLANK LAP CLADDING AND TRIM INSTALLED OVER PRESSURE TREATED FURRING STRIPS WITH INSECT SCREENS AT HORIZONTAL TERMINATIONS, REFER TO WALL DETAILS AND
PROJECT MANUAL.
REMOVE, LEGALLY DISPOSE OF, AND REPLACE 100% OF EXISTING GUTTER AND DOWNSPOUT ASSEMBLIES
AT EXISTING LOCATIONS, REFER TO PROJECT DESIGN DOCUMENTS AND PROJECT MANUAL.
EXISTING ENTRY SWING DOOR UNITS, INCLUDING ADJACENT TRIM AND CONCEALED COMPONENTS TO BE REMOVED, SAFELY STORED, AND REINSTALLED. REINSTALL DOOR UNITS WITH RELATED SAM PRE AND POST WRAP FLASHING, METAL HEAD AND SILL PAN FLASHING, AND RELATED CONCEALED COMPONENTS, TYPICAL.
INSTALL SCHEDULED DYNAMIC SEALANT JOINTS AND FIBER CEMENT TRIM ALONG DOOR HEAD AND JAMB
PERIMETERS. REFER TO DOOR SCHEDULE, WALL OPENING DETAILS, AND PROJECT MANUAL.
IDENTIFIED LOCATION OF EXISTING UTILITY SERVICE CONNECTIONS. REFER TO WALL DETAILS.
1 BUILDING 'A' MAIN OFFICE PARTIAL FRONT ELEVATION
N.T.S. ORIENTED FACING EAST
mhg
4 BUILDING 'A' MAIN OFFICE SIDE ELEVATION
N.T.S. ORIENTED FACING SOUTH / SOUTHEAST
mhg
2 BUILDING 'A' MAIN OFFICE PARTIAL FRONT ELEVATION
N.T.S. ORIENTED FACING EAST
mhg
3 BUILDING 'A' MAIN OFFICE ENLARGED CONDITIONS
N.T.S.
mhg
REMOVE AND DISPOSE OF 100% OF EXISTING COMPOSITION ASPHALT SHINGLE ROOFING, UNDERLAYMENT, STATIC VENTS, EXHAUST VENTS, AND ASSOCIATED ROOF AND FLASHING COMPONENTS. INSTALL SCHEDULED COMPOSITION ASPHALT SHINGLE ROOFING, UNDERLAYMENT, AND ASSOCIATED COMPONENTS
PER DESIGN DOCUMENT ROOF DETAILS AND PROJECT MANUAL.
STATIC STEMMED ROOF VENT ASSEMBLY, CONTRACTOR TO ACCOUNT FOR TIGHT-LINING 100% OF
BUILDINGS BATH AND KITCHEN LOCATIONS AS OCCURS, REFER TO DETAIL 3/A5.02
PLUMBING VENT STACK ASSEMBLY, REFER TO DETAIL 1/A5.03.
ELEVATION NOTES:
1. PHOTO ELEVATIONS ARE INCLUDED FOR REFERENCE TO EXISTING CONDITIONS ONLY. CONTRACTOR SHALL
FIELD VERIFY ALL CONDITIONS PRIOR TO NOTICE TO PROCEED FROM OWNER, PRODUCT OR MATERIALS TAKE-OFFS, PRODUCT OR MATERIALS PROCUREMENT, OR FABRICATOR SHOP-DRAWING PRODUCTIONS.
2. COORDINATE DEMOLITION WITH EXTERIOR CLADDING, WINDOW AND ROOF REPLACEMENT PER THE DESIGN DOCUMENTS. PERFORM SELECTIVE AND LIMITED DEMOLITION OF EXISTING EXTERIOR SHEATHING AS REQUIRED.
3. VERIFY CLEARANCE REQUIREMENTS AND MATCH ASSEMBLY OF EXISTING FIRE RATED WALLS AND ROOF
SYSTEMS WHERE…