2025-0214 NMNH Baird Bid Set - SPECS (VOL2).pdf

PDF 17 MB Posted

Attached to
Smithsonian institution's National Museum of Natural History Renovate Baird Auditorium
Solicitation number
33330225RT0010018
Issued by

About this file

This document is a volume of technical specifications for the Smithsonian Institution's National Museum of Natural History Baird Auditorium renovation project, specifically Volume 2 covering Divisions 10-28. The comprehensive renovation encompasses a complete restoration of the historic auditorium, including infrastructure upgrades, mechanical/electrical/plumbing systems modernization, accessibility improvements, and preservation of historic architectural elements like the Guastavino tile ceiling.

Key project details include a 730-calendar day construction period with a budget exceeding $10 million, targeting LEED Gold certification. Subcontracting goals are set at 40% for small businesses, with at least 7% allocated to Service-Disabled Veteran-owned small businesses. The project involves upgrading theater systems, replacing floor slabs, installing fire sprinklers, updating audio/visual and lighting equipment, refurbishing seating, improving acoustics, installing display cases, and rehabilitating adjacent spaces. The Davis-Bacon Wage Determination DC20250002 applies, and the proposal due date is May 23, 2025, at 3:00 PM EST, with questions due by April 25, 2025.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATIONS

VOLUME 2 OF 2 (DIVISION 10 - DIVISION 28)

2200109

Renovate Baird Auditorium

National Museum of Natural History (NMNH)

January 31, 2025February 14, 2025

2/26/25

February 14, 2025 Smithsonian Facilities Project No. 2200109

SmithGroup Project No. 14572

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 1

TABLE OF CONTENTS

COVER SHEET

TABLE OF CONTENTS

NOTE: SECTIONS INDICATED WITH “ ** ”ARE WRITTEN AND PROVIDED BY

SMITHGROUP CONSULTANTS.

VOLUME 1

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

SECTION 00 0101 - PROJECT TITLE PAGE

SECTION 00 0107 - SEALS PAGE

SECTION 00 3119 - EXISTING CONDITION INFORMATION

SECTION 00 3126 - EXISTING HAZARDOUS MATERIAL INFORMATION

SECTION 00 3126.01 - HAZARDOUS MATERIALS INSPECTION REPORT (SI)

DIVISION 01 - GENERAL REQUIREMENTS

SECTION 01 0000 - SUPPLEMENTARY CONDITIONS FOR CONSTRUCTION (SI)

SECTION 01 1000 – SUMMARY

SECTION 01 3100 – PROJECT MANAGEMENT AND COORDINATION (SI)

SECTION 01 3200 – CONSTRUCTION PROGRESS DOCUMENTATION (SI)

SECTION 01 3250 – BIM REQUIREMENTS (SI)

SECTION 01 3573 – DELEGATED DESIGN REQUIREMENTS AND PROCEDURES

SECTION 01 3591 - HISTORIC TREATMENT PROCEDURES

SECTION 01 4000 – QUALITY REQUIREMENTS (SI)

SECTION 01 7300 - EXECUTION

SECTION 01 7419 - CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL

SECTION 01 7419.13 – WASTE MANAGEMENT FORMS

SECTION 01 7823 - OPERATION AND MAINTENANCE DATA (SI)

SECTION 01 8113.15 - SUSTAINABLE DESIGN REQUIREMENTS - LEED V4 BD+C

SECTION 01 9113 - COMMISSIONING

DIVISION 02 - EXISTING CONDITIONS

SECTION 02 4119 - SELECTIVE STRUCTURE DEMOLITION

SECTION 02 4296 - HISTORIC REMOVAL AND DISMANTLING

SECTION 02 8200 - ASBESTOS ABATEMENT**

SECTION 02 8300 - WORK ACTIVITIES IMPACTING LEAD-CONTAINING MATERIALS**

DIVISION 03 - CONCRETE

SECTION 03 3000 - CAST-IN-PLACE CONCRETE**

SECTION 03 5416 - HYDRAULIC CEMENT UNDERLAYMENT

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 2

DIVISION 04 - MASONRY

SECTION 04 0110 - MASONRY CLEANING**

SECTION 04 0140.91 - STONE MASONRY RESTORATION**

SECTION 04 0180.93 - GUASTAVINO TILEWORK RESTORATION**

SECTION 04 0513 - RESTORATION MORTARS AND GROUTS**

SECTION 04 0513.91 - MASONRY POINTING**

SECTION 04 2000 – MASONRY **

DIVISION 05 - METALS

SECTION 05 0170.91 – DECORATIVE METAL RESTORATION**

SECTION 05 0371 – HISTORIC DECORATIVE METAL CLEANING

SECTION 05 1200 – STRUCTURAL STEEL FRAMING**

SECTION 05 3100 – STEEL DECKING**

SECTION 05 5000 - METAL FABRICATIONS

SECTION 05 5213 - PIPE AND TUBE RAILINGS

SECTION 05 7300 - DECORATIVE METAL RAILINGS

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY

SECTION 06 1600 - SHEATHING

SECTION 06 4023 - INTERIOR ARCHITECTURAL WOODWORK

SECTION 06 4113 - WOOD-VENEER-FACED ARCHITECTURAL CABINETS

SECTION 06 4216 - FLUSH WOOD PANELING

SECTION 06 6116 – SOLID SURFACING FABRICATIONS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

SECTION 07 2100 – THERMAL INSULATION

SECTION 07 5900 - ROOF CUTTING, PATCHING AND REPAIR

SECTION 07 8100 – SPRAYED FIRE-RESISTANT MATERIAL

SECTION 07 8413 - PENETRATION FIRESTOPPING

SECTION 07 8443 - JOINT FIRESTOPPING

SECTION 07 9200 - JOINT SEALANTS

SECTION 07 9219 - ACOUSTICAL JOINT SEALANTS

DIVISION 08 - OPENINGS

SECTION 08 0314 – HISTORIC TREATMENT OF WOOD DOORS

SECTION 08 1113 - HOLLOW METAL DOORS AND FRAMES

SECTION 08 1416 - FLUSH WOOD DOORS

SECTION 08 1433 - STILE AND RAIL WOOD DOORS

SECTION 08 3113 - ACCESS DOORS AND FRAMES

SECTION 08 3123 – FLOOR DOORS

SECTION 08 5113 – ALUMINUM WINDOWS

SECTION 08 7100 - DOOR HARDWARE**

SECTION 08 8000 - GLAZING

SECTION 08 9119 – FIXED LOUVERS

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 3

DIVISION 09 - FINISHES

SECTION 09 0120.91 – PLASTER RESTORATION**

SECTION 09 0169.91 - TERRAZZO RESTORATION**

SECTION 09 2116.23 - GYPSUM BOARD SHAFT WALL ASSEMBLIES

SECTION 09 2216 - NON-STRUCTURAL METAL FRAMING

SECTION 09 2300 - GYPSUM PLASTERING

SECTION 09 2313 – ACOUSTICAL PLASTERING

SECTION 09 2713 - GLASS-FIBER-REINFORCED GYPSUM FABRICATIONS

SECTION 09 2900 - GYPSUM BOARD

SECTION 09 3013 - CERAMIC TILING

SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS

SECTION 09 6466 - WOOD ATHLETIC FLOORING

SECTION 09 6536 - STATIC-CONTROL RESILIENT FLOORING

SECTION 09 6623 – RESINOUS MATRIX TERRAZO FLOORING

SECTION 09 6813 – TILE CARPETING

SECTION 09 6816 - SHEET CARPETING

SECTION 09 8129 – SPRAYED ACOUSTIC INSULATION

SECTION 09 8433 – SOUND-ABSORBING WALL UNITS

SECTION 09 9123 - INTERIOR PAINTING

SECTION 09 9300 - STAINING AND TRANSPARENT FINISHING

SECTION 09 9600 – HIGH-PERFORMANCE COATINGS

VOLUME 2

DIVISION 10 - SPECIALTIES

SECTION 10 1200 - DISPLAY CASES

SECTION 10 2600 - WALL AND DOOR PROTECTION

SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES

SECTION 10 4400 - FIRE EXTINGUISHERS, CABINETS, AND ACCESSORIES (SI)

DIVISION 11 - EQUIPMENT

SECTION 11 2400 – SUSPENDED MAINTENANCE AND FALL PROTECTION EQUIPMENT

SECTION 11 3300 - RETRACTABLE STAIRS

SECTION 11 6112 – ADJUSTABLE ACOUSTICS**

SECTION 11 6191 – THEATRICAL LIGHTING INSTRUMENTS AND ACCESSORIES**

DIVISION 12 - FURNISHINGS

SECTION 12 2413 - ROLLER WINDOW SHADES

SECTION 12 3661.16 - SOLID SURFACING COUNTERTOPS

SECTION 12 6715 – RENOVATION OF UPHOLSTERED AUDITORIUM SEATING**

DIVISION 14 - CONVEYING EQUIPMENT

SECTION 14 4216 - WHEELCHAIR LIFT

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 4

DIVISION 21 - FIRE SUPPRESSION

SECTION 21 1313 - WET-PIPE SPRINKLER SYSTEMS

DIVISION 22 - PLUMBING

SECTION 22 0516 - EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING

SECTION 22 0517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

SECTION 22 0518 - ESCUTCHEONS FOR PLUMBING PIPING

SECTION 22 0523.12 - BALL VALVES FOR PLUMBING PIPING

SECTION 22 0529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION 22 0553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION 22 0719 - PLUMBING PIPING INSULATION

SECTION 22 1116 - DOMESTIC WATER PIPING

SECTION 22 1119 - DOMESTIC WATER PIPING SPECIALTIES

SECTION 22 1316 - SANITARY WASTE AND VENT PIPING

SECTION 22 1319 - SANITARY WASTE PIPING SPECIALTIES

SECTION 22 1319.13 - SANITARY DRAINS

SECTION 22 4213.13 - COMMERCIAL WATER CLOSETS

SECTION 22 4216.13 - COMMERCIAL LAVATORIES AND SINKS

SECTION 22 4216.16 – COMMERCIAL SINKS

SECTION 22 4716 - PRESSURE WATER COOLERS

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 5

DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)

SECTION 23 0513 – COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

SECTION 23 0516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION 23 0517 - SLEEVES AND SLEEVE SEALS FOR HVAC PIPING

SECTION 23 0518 - ESCUTCHEONS FOR HVAC PIPING

SECTION 23 0519 - METERS AND GAUGES FOR HVAC PIPING

SECTION 23 0523.12 - BALL VALVES FOR HVAC PIPING

SECTION 23 0523.13 - BUTTERFLY VALVES FOR HVAC PIPING

SECTION 23 0523.14 - CHECK VALVES FOR HVAC PIPING

SECTION 23 0529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 23 0548.13 - VIBRATION CONTROLS FOR HVAC

SECTION 23 0553 - IDENTIFICATION FOR HVAC, PIPING AND EQUIPMENT

SECTION 23 0593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC

SECTION 23 0713 - DUCT INSULATION

SECTION 23 0719 - HVAC PIPING INSULATION

SECTION 23 0800 - COMMISSIONING OF HVAC

SECTION 23 2113 - HYDRONIC PIPING

SECTION 23 2116 - HYDRONIC PIPING SPECIALTIES

SECTION 23 2123 - HYDRONIC PUMPS

SECTION 23 3113 - METAL DUCTS

SECTION 23 3300 - AIR DUCT ACCESSORIES

SECTION 23 3346 - FLEXIBLE DUCTS

SECTION 23 3400 - HVAC FANS

SECTION 23 3600 - AIR TERMINAL UNITS

SECTION 23 3713 - DIFFUSERS, REGISTERS, AND GRILLES

SECTION 23 7313.19 – INDOOR, CUSTOM AIR HANDLING UNITS

SECTION 23 8219 - FAN COIL UNITS

SECTION 23 8236 – FINNED-TUBE RADIATION HEATERS

DIVISION 25 – INTEGRATED AUTOMATION

SECTION 25 0900 – INSTRUMENTATION AND CONTROLS FOR HVAC (SI)

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 6

DIVISION 26 - ELECTRICAL

SECTION 26 0400 – COMMON WORK RESULTS FOR ELECTRICAL

SECTION 26 0519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION 26 0523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES

SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION 26 0529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION 26 0533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

SECTION 26 0544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND

CABLING

SECTION 26 0553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION 26 0573 - POWER SYSTEM STUDIES

SECTION 26 0800 - COMMISSIONING ELECTRICAL SYSTEMS

SECTION 26 0913 – ELECTRICAL POWER MONITORING AND CONTROL

SECTION 26 0923 - LIGHTING CONTROL DEVICES

SECTION 26 0933 - CENTRAL DIMMING CONTROLS

SECTION 26 0936 - MODULAR DIMMING CONTROLS

SECTION 26 0943 - NETWORK LIGHTING CONTROLS

SECTION 26 2416 - PANELBOARDS

SECTION 26 2726 - WIRING DEVICES

SECTION 26 2813 - FUSES

SECTION 26 2816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION 26 2913.03 – MANUAL AND MAGNETIC MOTOR CONTROLLERS

SECTION 26 2923 - VARIABLE-FREQUENCY MOTOR CONTROLLERS

SECTION 26 4313 – SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER

CIRCUITS

SECTION 26 5100 - INTERIOR LIGHTING

SECTION 26 6111 – THEATRICAL LIGHTING POWER AND CONTROLS**

SECTION 26 6115 – LIGHTING CONTROLS SYSTEM INTEGRATOR**

SECTION 26 6120 – COMPANY SWITCHES**

DIVISION 27 - COMMUNICATIONS

SECTION 27 0500 - COMMON WORK RESULTS FOR COMMUNICATIONS**

SECTION 27 0526 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS**

SECTION 27 0528 - PATHWAYS FOR COMMUNICATIONS SYSTEMS**

SECTION 27 0553 - IDENTIFICATION FOR COMMUNICATIONS SYSTEMS**

SECTION 27 1100 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS**

SECTION 27 1500 - COMMUNICATIONS HORIZONTAL CABLING**

SECTION 27 1700 - TESTING OF STRUCTURED CABLING SYSTEMS**

SECTION 27 4116.61 – PERFORMANCE SOUND, VIDEO, AND COMMUNICATIONS

SYSTEMS AND EQUIPMENT**

SECTION 27 4116.62 – APPENDIX A – AV EQUIPMENT LIST**

Smithsonian Institution - Renovate Baird Auditorium

Table of Contents

Bid Set

TOC - 7

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

SECTION 28 0500.10 - COMMON WORK RESULTS FOR ELECTRONIC SECURITY**

SECTION 28 0507.10 – POWER SOURCES FOR ELECTRONIC SECURITY**

SECTION 28 0531.10 – COMMUNICATIONS EQUIPMENT FOR ELECTRONIC SECURITY**

SECTION 28 0800.10 - COMMISSIONING OF ELECTRONIC SECURITY**

SECTION 28 1000 - ACCESS CONTROL**

SECTION 28 1515 - ELECTRIFIED LOCKING DEVICES AND ACCESSORIES**

SECTION 28 2000 – VIDEO**

SECTION 28 3100 - INTRUSION DETECTION **

SECTION 28 3111 – ADDRESSABLE FIRE ALARM SYSTEM

APPENDIX

LEED V4 IDC CHECKLIST

SmithGroup Project No. 14572.000

Smithsonian Institution - Renovate Baird Auditorium

PROJECT TITLE PAGE

Bid Set

00 0101 - 1

DOCUMENT 000101 - PROJECT TITLE PAGE

1.1 PROJECT MANUAL VOLUME 2 OF 2

A. NMNH Renovate Baird Auditorium.

Smithsonian Institution - Facilities.

Washington, D.C.

B. Owner Project No. SF 2200109.

C. Architect Project No. 14572.000.

D. SmithGroup.

1700 New York Avenue NW - Suite 100.

Washington, DC 20006.

Phone: 202-842-2100.

Website: smithgroup.com.

E. Issued: February 14, 2025.

F. Copyright 2025 SmithGroup. All rights reserved.

END OF DOCUMENT

SmithGroup Project No. 14572.000

Smithsonian Institution - Renovate Baird Auditorium

SEALS PAGE

Bid Set 00 0107 - 1

DOCUMENT 000107 - SEALS PAGE

Architect SmithGroup, Inc.

Washington, DC James W. Shepherd, AIA

Structural Engineer Silman Washington, DC Christopher K. Ruiz, PE

Fire Protection Engineer SmithGroup, Inc.

Kyle J. Lehman, PE

Mechanical Engineer SmithGroup, Inc.

Ionel Petrus, PE

Electrical Engineer

Kenz Meliani, PE

Plumbing Engineer

Ionel Petrus, PE

END OF DOCUMENT

Smithsonian Institution - Renovate Baird Auditorium

DISPLAY CASES

Bid Set

10 1200 - 1

SECTION 10 1200 - DISPLAY CASES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Custom fabricated Display cases.

1.2 PREINSTALLATION MEETINGS

A. Preinstallation Conference: Conduct conference at Project site.

1.3 REFERENCES

A. 2022 NMAI Conservation Approved Materials.

B. ACI WIKI.

1.4 ACTION SUBMITTALS

A. Refer to Section 01 0000 Supplementary Conditions for Construction for submittal requirements.

B. Product Data: For each type of product.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for display cases. Include furnished specialties and accessories.

2. Include electrical characteristics for illuminated display cases

3. Cut sheets of light fixtures.

4. Oddy Test results for all materials used in construction of display case interior environment.

C. Sustainable Design Submittals:

1. Laboratory Test Reports: For adhesives, indicating compliance with requirements for low-emitting materials.

2. Laboratory Test Reports: For composite wood products, indicating compliance with requirements for low-emitting materials.

D. Shop Drawings: For display cases .

1. Include plans, elevations, sections, and attachment details.

2. Show location of seams and joints in tackboard panels.

3. Include sections of typical trim members.

4. Include diagrams for wiring illuminated display cases and access for changing fixtures.

5. Include diagrams and details for security of all casework both locking hardware and wired/wireless security devices.

6. Include details of desiccant chambers including access and details regarding airflow.

7. Hardware details.

Smithsonian Institution - Renovate Baird Auditorium

DISPLAY CASES

Bid Set

10 1200 - 2

E. Samples: For each exposed product and for each color and texture specified; not less than 8-1/2 by 11 inches (215 by 280 mm) for panels and 6 inches (150 mm) long for trim with factory finish.

1. Finish metal samples for each type of exposed metal and hardware.

2. Glass for doors.

1.5 CLOSEOUT SUBMITTALS

A. Maintenance Data: For display cases to include in maintenance manuals.

1.6 QUALITY ASSURANCE

A. Provide the following:

1. Product Test Reports: For tests performed by a qualified testing agency.

2. Oddy Test results for all materials used in construction of display case interior environment.

1.7 FIELD CONDITIONS

A. Environmental Limitations: Do not deliver or install display cases for indoor installations until spaces are enclosed and weather tight, wet-work in spaces is complete and dry, work above ceilings is complete, and temporary HVAC system operates and maintains ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.

PART 2 - PRODUCTS

2.1 SOURCE LIMITATIONS

A. Obtain display cases from single source from single manufacturer.

2.2 PERFORMANCE REQUIREMENTS

A. Electrical Components: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Construct custom-fabricated display cases to the following environmental requirements:

1. Temperature (T): 66-74 degrees F (Winter and Summer extremes, not fluctuations).

2. Relative Humidity (RH): 37%-53% (Winter and Summer extremes, not fluctuations).

3. Air Exchange Rate (AER): 0.3 – 1.0/day.

2.3 DISPLAY CASES

A. Manufacturers: Subject to compliance with requirements, provide products by the following:

1. Case[werks].

2. Goppion.

3. Guenschel.

B. Display Case: Custom-fabricated display case; lighted, with finished interior, passive micro-climate control system, and operable, locking, glazed, hinged doors at front.

1. Display Case Cabinet: Extruded aluminum.

2. Face Frame:

http://www.specagent.com/LookUp/?ulid=592&mf=&src=wd

Smithsonian Institution - Renovate Baird Auditorium

DISPLAY CASES

Bid Set

10 1200 - 3

a. Aluminum.

3. Aluminum Finish: Manufacturer's standard powder coated finish.

a. Color: As selected by COTR from manufacturer's full range.

4. Desiccant Chamber: Passive micro-climate control to allow for air exchange with the primary case volume (above the deck) at recommended AER, but be vapor sealed from the uncontrolled environment under the deck.

a. The size of chambers shall be compatible with the with the air volume of the case to include enough single layer, high performance gel to maintain RH requirements.

b. Construct of inert materials such as powder-coated aluminum, Dibond or acrylic.

C. Glazed Hinged Doors: Anti-reflective, low iron, clear-white laminated safety glass .

1. Thickness: Not less than 6 mm thick.

2. Number of Doors: As indicated on Drawings.

D. Back Panel: Dibond or Plexiglas (polymethyl methacrylate).

E. Cam lock: Length and cam required to suit construction.

F. Seals and Gasketing: As required to maintain performance requirements.

1. Use only platinum-cured silicone rubbers (dimethyl silicone), cellular silicone sponge

(poly-dimethyl siloxane; PDMS) and ethylene vinyl acetate closed-cell elastomeric

(EVA) seals.

2. Ethylene propylene diene monomer (EPDM) is acceptable only if approved by COTR.

G. Illumination System: Concealed top-lighting LED system separated from the case interior.

Include lamps and internal wiring with single concealed electrical connection to the building system. Coordinate electrical characteristics with power supply provided.

H. Size: As indicated on Drawings.

2.4 MATERIALS

A. Only materials listed as PASS in 2022 NMAI Conservation Approved Materials as or approved for use by the Smithsonian Institution and the National Museum of Natural History in the construction of display cases are acceptable.

B. Any material test data older than Five (5) years shall be retested at the contractor’s expense and results submitted to the Smithsonian Institution and National Museum of Natural History for final approval for use.

C. Extruded-Aluminum Bars and Shapes: ASTM B221 (ASTM B221M), Alloy 6063.

D. Aluminum Tubing: ASTM B429/B429M, Alloy 6063.

E. Glazing: Clear-White, Laminated, UV protecting, safety glass.

F. Adhesives and Sealants: Use only adhesives and sealants that have been vetted and PASS contemporary Oddy Testing and are listed for use in display case interiors in 2022 NMAI

Conservation Approved Materials and approved by conservation consultation.

Smithsonian Institution - Renovate Baird Auditorium

DISPLAY CASES

Bid Set

10 1200 - 4

2.5 FABRICATION

A. Fabricate display cases to requirements indicated for dimensions, design, and thickness and finish of materials.

B. Use metals and shapes of thickness and reinforcing required to produce flat surfaces, and to impart strength for size, design, and application indicated.

C. Fabricate cabinets and door frames with reinforced corners, mitered to a hairline fit, with no exposed fasteners.

2.6 GENERAL FINISH REQUIREMENTS

A. Comply with NAAMM/NOMMA 500 for recommendations for applying and designating finishes.

B. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

C. Appearance of Finished Work: Noticeable variations in same piece are unacceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved

Samples and are assembled or installed to minimize contrast.

2.7 ALUMINUM FINISHES

A. Powder-Coat Finish: AAMA 2603, except with a minimum dry film thickness of 1.5 mils (0.04 mm). Comply with coating manufacturer's written instructions for cleaning, conversion coating, and applying and baking finish.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine walls, with Installer present, for compliance with requirements for installation tolerances, surface conditions of wall, and other conditions affecting performance of the Work.

B. Examine roughing-in for electrical power systems to verify actual locations of connections before installation of illuminated units.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Prepare recesses for display cases as required by type and size of unit.

3.3 INSTALLATION

A. General: Install units in locations and at mounting heights indicated on Drawings, or if not indicated, at heights indicated below. Keep perimeter lines and case decks straight, level and plumb. Provide grounds, clips, backing materials, adhesives, brackets, anchors, trim, and accessories necessary for complete installation.

Smithsonian Institution - Renovate Baird Auditorium

DISPLAY CASES

Bid Set

10 1200 - 5

B. Use adhesives, structural or sealing, in a manner to minimize quantity applied while ensuring structural and sealing integrity. Neatly clean excessive adhesives and sealants from all surfaces.

C. Install all materials in a manner that all fabrication and construction materials are able to appropriately cure. Leave assembled cases opened until curing has completed based on manufacturer’s recommendations for full curing time and after inspection by COTR.

D. Comply with requirements specified elsewhere for connecting illuminated display cases.

3.4 ADJUSTING AND CLEANING

A. Adjust doors to lock and operate smoothly without warp or bind and so contact points meet accurately. Lubricate operating hardware as recommended in writing by manufacturer.

B. Touch up factory-applied finishes to restore damaged areas.

END OF SECTION

SECTION 10 2600 - WALL AND DOOR PROTECTION

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Corner guards.

B. Related Requirements:

1. Section 08 7100 "Door Hardware" for metal armor, kick, mop, and push plates.

1.2 ACTION SUBMITTALS

A. Refer to Sectin 01 0000 Supplementary Conditions for Construction for sumittal requirements.

B. Product Data: Include construction details, material descriptions, impact strength , fire-test-response characteristics, dimensions of individual components and profiles, and finishes for each impact-resistant wall protection unit.

C. Sustainable Design Submittals:

1. Product Data: For adhesives, indicating VOC content.

2. Laboratory Test Reports: For adhesives, indicating compliance with requirements for low-emitting materials.

3. Laboratory Test Reports: For composite wood products, indicating compliance with requirements for low-emitting materials.

D. Shop Drawings: For each impact-resistant wall protection unit showing locations and extent.

Include sections, details, and attachments to other work.

E. Samples for Initial Selection: For each type of impact-resistant wall protection unit indicated.

F. Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below.

1. Corner Guards: 12 inches (300 mm) long. Include examples of joinery, corners, and field splices.

1.3 CLOSEOUT SUBMITTALS

A. Maintenance Data: For each impact-resistant wall protection unit to include in maintenance manuals.

1. Include recommended methods and frequency of maintenance for maintaining optimum condition of plastic covers under anticipated traffic and use conditions. Include precautions against using cleaning materials and methods that may be detrimental to plastic finishes and performance.

1.4 QUALITY ASSURANCE

A. Vendor Qualifications: A vendor that is certified for chain of custody by an FSC-accredited certification body.

Smithsonian Institution - Renovate Baird Auditorium

WALL AND DOOR PROTECTION

Bid Set 10 2600 - 1

B. Installer Qualifications: An employer of workers trained and approved by manufacturer.

C. Source Limitations: Obtain impact-resistant wall protection units from single source from single manufacturer.

D. Product Options: Drawings indicate size, profiles, and dimensional requirements of impact-resistant wall protection units and are based on the specific system indicated. Refer to Section 01 4000 "Quality Requirements."

1. Do not modify intended aesthetic effects, as judged solely by Architect, except with

Architect's approval. If modifications are proposed, submit comprehensive explanatory data to Architect for review.

E. Surface-Burning Characteristics: Provide impact-resistant, plastic wall protection units with surface-burning characteristics as determined by testing identical products per ASTM E 84, NFPA 255, or UL 723 by UL or another qualified testing agency.

F. Regulatory Requirements: Comply with applicable provisions in the U.S. Architectural & Transportation Barriers Compliance Board's ADA-ABA Accessibility Guidelines and

ICC/ANSI A117.1.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Store impact-resistant wall protection units in original undamaged packages and containers inside well-ventilated area protected from weather, moisture, soiling, extreme temperatures, and humidity.

1. Maintain room temperature within storage area at not less than 70 deg F (21 deg C) during the period plastic materials are stored.

2. Store plastic wall protection components for a minimum of 72 hours, or until plastic material attains a minimum room temperature of 70 deg F (21 deg C).

a. Store corner-guard covers in a vertical position.

b. Store covers in a horizontal position.

1.6 PROJECT CONDITIONS

A. Environmental Limitations: Do not deliver or install impact-resistant wall protection units until building is enclosed and weatherproof, wet work is complete and dry, and HVAC system is operating and maintaining temperature at 70 deg F (21 deg C) for not less than 72 hours before beginning installation and for the remainder of the construction period.

1.7 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of impact-resistant wall protection units that fail in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, the following:

a. Structural failures.

b. Deterioration of plastic and other materials beyond normal use.

2. Warranty Period: Five years from date of Substantial Completion.

Smithsonian Institution - Renovate Baird Auditorium

WALL AND DOOR PROTECTION

10 2600 - 2

PART 2 - PRODUCTS

2.1 MATERIALS

A. Aluminum Extrusions: Alloy and temper recommended by manufacturer for type of use and finish indicated, but with not less than strength and durability properties specified in ASTM B 221 (ASTM B 221M) for Alloy 6063-T5.

B. Stainless-Steel Sheet: ASTM A 240/A 240M.

C. Brass: ASTM B 249/B 249M for extruded shapes and ASTM B 36/B 36 M for sheet.

D. Fasteners: Aluminum, nonmagnetic stainless-steel, or other noncorrosive metal screws, bolts, and other fasteners compatible with items being fastened. Use security-type fasteners where exposed to view.

E. Adhesive: As recommended by protection product manufacturer.

1. Verify adhesives have a VOC content of 70 g/L or less.

2. Verify adhesive complies with the testing and product requirements of the California

Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."

2.2 CORNER GUARDS

A. Surface-Mounted, Metal Corner Guards : Fabricated from one-piece, formed or extruded metal with formed edges; with 90- or 135-degree turn to match wall condition.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. American Floor Products Co., Inc.

b. Arden Architectural Specialties, Inc.

c. Balco, Inc.

d. Boston Retail Products.

e. Construction Specialties, Inc.

f. IPC Door and Wall Protection Systems; Division of InPro Corporation.

g. Korogard Wall Protection Systems; a division of RJF International Corporation.

h. Pawling Corporation.

i. Tepromark International, Inc.

j. WallGuard.com.

2. Material: Stainless steel, Type 304 .

a. Thickness: Minimum 0.0500 inch (1.3 mm).

b. Finish: Directional satin, No. 4.

3. Material: Extruded aluminum, minimum 0.0625 inch (1.6 mm) thick, with clear anodic finish.

4. Material: Brass sheet, minimum 0.0500 inch (1.3 mm) thick, with buffed, smooth specular finish.

5. Wing Size: Nominal 1-1/2 by 1-1/2 inches (38 by 38 mm).

6. Corner Radius: 1/8 inch (3 mm).

7. Mounting: Adhesive.

Smithsonian Institution - Renovate Baird Auditorium

WALL AND DOOR PROTECTION

10 2600 - 3

2.3 FABRICATION

A. Assemble components in factory to greatest extent possible to minimize field assembly.

Disassemble only as necessary for shipping and handling.

B. Fabricate components with tight seams and joints with exposed edges rolled. Provide surfaces free of wrinkles, chips, dents, uneven coloration, and other imperfections. Fabricate members and fittings to produce flush, smooth, and rigid hairline joints.

2.4 METAL FINISHES

A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

1. Remove tool and die marks and stretch lines, or blend into finish.

2. Grind and polish surfaces to produce uniform finish, free of cross scratches.

3. Run grain of directional finishes with long dimension of each piece.

4. When polishing is completed, passivate and rinse surfaces. Remove embedded foreign matter and leave surfaces chemically clean.

B. Protect finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and wall areas, with Installer present, for compliance with requirements for installation tolerances, fire rating, and other conditions affecting performance of work.

B. Examine walls to which impact-resistant wall protection will be attached for blocking, grounds, and other solid backing that have been installed in the locations required for secure attachment of support fasteners.

1. For impact-resistant wall protection units attached with adhesive or foam tape, verify compatibility with and suitability of substrates, including compatibility with existing finishes or primers.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Complete finishing operations, including painting, before installing impact-resistant wall protection system components.

B. Before installation, clean substrate to remove dust, debris, and loose particles.

3.3 INSTALLATION

A. General: Install impact-resistant wall protection units level, plumb, and true to line without distortions. Do not use materials with chips, cracks, voids, stains, or other defects that might be visible in the finished Work.

Smithsonian Institution - Renovate Baird Auditorium

WALL AND DOOR PROTECTION

10 2600 - 4

3.4 CLEANING

A. Immediately after completion of installation, clean plastic covers and accessories using a standard, ammonia-based, household cleaning agent.

B. Remove excess adhesive using methods and materials recommended in writing by manufacturer.

END OF SECTION

Smithsonian Institution - Renovate Baird Auditorium

WALL AND DOOR PROTECTION

10 2600 - 5

SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Public-use washroom accessories.

2. Hand dryers.

3. Underlavatory guards.

B. Related Requirements:

1. Section 09 3013 "Ceramic Tiling" for ceramic toilet and bath accessories.

1.2 COORDINATION

A. Coordinate accessory locations with other work to prevent interference with clearances required for access by people with disabilities, and for proper installation, adjustment, operation, cleaning, and servicing of accessories.

B. Deliver inserts and anchoring devices set into concrete or masonry as required to prevent delaying the Work.

1.3 ACTION SUBMITTALS

A. Refer to Section 01 0000 Supplementary Conditions for Construction for submittal requirements.

B. Product Data: For each type of product.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes.

2. Include anchoring and mounting requirements, including requirements for cutouts in other work and substrate preparation.

3. Include electrical characteristics lighted mirrors.

C. Samples: For each exposed product and for each finish specified, full size.

1. Approved full-size Samples will be returned and may be used in the Work.

D. Product Schedule: Indicating types, quantities, sizes, and installation locations by room of each accessory required.

1. Identify locations using room designations indicated.

2. Identify accessories using designations indicated.

1.4 CLOSEOUT SUBMITTALS

A. Maintenance Data: For accessories to include in maintenance manuals.

1.5 WARRANTY

A. Manufacturer's Special Warranty for Mirrors: Manufacturer agrees to repair or replace mirrors that fail in materials or workmanship within specified warranty period.

Smithsonian Institution - Renovate Baird Auditorium

TOILET, BATH, AND LAUNDRY ACCESSORIES

10 2800 - 1

1. Failures include, but are not limited to, visible silver spoilage defects.

2. Warranty Period: 15 years from date of Substantial Completion.

3.

B. Manufacturer's Special Warranty for Electric Lighted Mirrors: Manufacturer agrees to repair or replace mirrors that fail in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, visible silver spoilage defects.

Not all manufacturers offer a special mirror warranty. Verify available warranties and warranty periods.

2. Warranty Period: 10 years from date of Substantial Completion.

C. Manufacturer's Special Warranty for Hand Dryers: Manufacturer agrees to repair or replace hand dryers that fail in materials or workmanship within specified warranty period.

1. Warranty Period: 7 years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Structural Performance: Design accessories and fasteners to comply with the following requirements:

1. Grab Bars: Installed units are able to resist 250 lbf (1112 N) concentrated load applied in any direction and at any point.

2.2 PUBLIC-USE WASHROOM ACCESSORIES

A. Source Limitations: Obtain public-use washroom accessories from single source from single manufacturer.

B. Combination Toilet Tissue Dispenser TA-1:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. American Specialties, Inc. (ASI).

b. Bobrick Washroom Equipment, Inc.

c. Bradley Corporation.

2. Description: Combination unit with double-roll toilet tissue dispenser and the following:

a. Removable sanitary-napkin waste receptacle with self-closing, disposal-opening cover.

b. Seat-cover dispenser with minimum capacity of 500 single or half-fold seat covers.

3. Mounting: Surface mounted .

4. Toilet Tissue Dispenser Capacity: 4-1/2- or 5-inch- (114- or 127-mm-) iameter tissue rolls.

5. Toilet Tissue Dispenser Operation: Noncontrol delivery with theft-resistant spindles.

6. Material and Finish: Stainless steel, ASTM A480/A480M No. 4 finish (satin).

7. Lockset: Tumbler type.

C. Soap Dispenser TA-3:

Smithsonian Institution - Renovate Baird Auditorium

TOILET, BATH, AND LAUNDRY ACCESSORIES

Bid Set 10 2800 - 2 http://www.specagent.com/LookUp/?ulid=11610&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457218074&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218075&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218076&mf=04&src=wd

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. American Specialties, Inc. (ASI).

b. Bobrick Washroom Equipment, Inc.

c. Bradley Corporation.

2. Description: Designed for manual operation and dispensing soap in liquid or lotion form.

3. Mounting: Vertically oriented, surface mounted.

4. Capacity: 40 fl oz.

5. Materials: Stainless Steel.

6. Lockset: Tumbler type.

7. Refill Indicator: Window type.

D. Grab Bar TA-4, TA-5:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. American Specialties, Inc. (ASI).

b. Bobrick Washroom Equipment, Inc.

c. Bradley Corporation.

2. Mounting: Flanges with concealed fasteners.

3. Material: Stainless steel, 0.05 inch (1.3 mm) thick.

a. Finish: Smooth, ASTM A480/A480M No. 4 finish (satin) on ends and slip-resistant texture in grip area.

4. Outside Diameter: 1-1/2 inches (38 mm).

5. Configuration and Length: As indicated on Drawings.

E. Mirror Unit TA-6:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. American Specialties, Inc. (ASI).

b. Bobrick Washroom Equipment, Inc.

c. Bradley Corporation.

2. Frame: Stainless steel channel .

a. Corners: Welded and ground smooth.

3. Size: As indicated on Drawings.

4. Hangers: Manufacturer's standard rigid, tamper and theft resistant.

5.

F. Electric Lighted Mirror Unit TA-8

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Electric Mirror - Integrity Lighted Mirror.

2. Frame: Manufacturer's standard.

3. Size: As indicated on Drawings.

4. Mounting: mount chasis to wall studs; mounting holes provided..

5. Lighting:

a. CRI: 90+.

b. CCT: 3000K.

c. Replaceable LED's.

d. 50 initial lumens/inch .

e. Maximum 100 lumens/watt efficacy.

Smithsonian Institution - Renovate Baird Auditorium

TOILET, BATH, AND LAUNDRY ACCESSORIES

Bid Set 10 2800 - 3 http://www.specagent.com/LookUp/?ulid=11622&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457218133&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218134&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218135&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=11624&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457218149&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218150&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218151&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=11629&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457217983&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457217984&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457217985&mf=04&src=wd

f. Calculated L70 124,000-hour LED lifespan.

6. Coordinate installation with electrical for power for mirrors.

a. 120V-240V hardwire electrical connection, provide 36" whip; junction box not required.

b. Power requirements based on size.

G. Hook TA-7:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. American Specialties, Inc. (ASI).

b. Bobrick Washroom Equipment, Inc.

c. Bradley Corporation.

2. Description: Single-prong unit .

3. Mounting: Concealed .

4. Material and Finish: Stainless steel, ASTM A480/A480M No. 4 finish (satin) .

2.3 HAND DRYERS

A. Source Limitations: Obtain hand dryers from single source from single manufacturer.

B. Warm-Air Dryer TA-2:

1. Manufacturers: Subject to compliance with requirements, [provide products by the following] [provide products by one of the following] [available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following]:

a. American Specialties, Inc. (ASI).

b. Bobrick Washroom Equipment, Inc.

c. Bradley Corporation.

d. World Dryer Corporation.

2. Description: Standard-speed, warm-air hand dryer.

3. Mounting: Surface mounted.

a. Protrusion Limit: Installed unit protrudes maximum 4 inches (102 mm) from wall surface.

4. Operation: Infrared-sensor activated with timed power cut-off switch.

a. Automatic Shutoff: At 85 seconds.

5. Maximum Sound Level: 67 dB.

6. Cover Material and Finish: Stainless steel, ASTM A480/A480M No. 4 finish (satin).

7. Electrical Requirements: 110V-240V, 0.8-1.9 AMP, 50/60 Hz, 202-213 watts, cUL.us

Listed and CE marked..

2.4 UNDERLAVATORY GUARDS

A. Underlavatory Guard <Insert drawing designation>:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Buckaroos, Inc.

b. Plumberex Specialty Products, Inc.

c. Truebro by IPS Corporation.

Smithsonian Institution - Renovate Baird Auditorium

TOILET, BATH, AND LAUNDRY ACCESSORIES

Bid Set 10 2800 - 4 http://www.specagent.com/LookUp/?ulid=11630&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457217993&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457217994&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457217995&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=11846&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457218053&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218054&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218055&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218061&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=11662&mf=&src=wd http://www.specagent.com/LookUp/?uid=123457218391&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218389&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123457218390&mf=04&src=wd

2. Description: Insulating pipe covering for supply and drain piping assemblies that prevents direct contact with and burns from piping; allow service access without removing coverings.

3. Material and Finish: Antimicrobial, molded plastic, color as selected by COTR.

2.5 MATERIALS

A. Stainless Steel: ASTM A240/A240M or ASTM A666, Type 304, 0.031-inch- (0.8-mm-) minimum nominal thickness unless otherwise indicated.

B. Mirrors: ASTM C1503, Mirror Glazing Quality, clear-glass mirrors, nominal 6.0 mm thick.

2.6 FABRICATION

A. General: Fabricate units with tight seams and joints, and exposed edges rolled. Hang doors and access panels with full-length, continuous hinges. Equip units for concealed anchorage and with corrosion-resistant backing plates.

B. Keys: Provide universal keys for internal access to accessories for servicing and resupplying.

Provide minimum of six keys to Owner's representative.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install accessories in accordance with manufacturers' written instructions, using fasteners appropriate to substrate indicated and recommended by unit manufacturer. Install units level, plumb, and firmly anchored in locations and at heights indicated.

1. Remove temporary labels and protective coatings.

B. Grab Bars: Install to comply with specified structural-performance requirements.

C. Install electric lighted mirrors per manufacturer's writteninstructions and in compliance with all applicable electrical codes.

3.2 ADJUSTING AND CLEANING

A. Adjust accessories for unencumbered, smooth operation. Replace damaged or defective items.

B. Clean and polish exposed surfaces in accordance with manufacturer's written instructions.

END OF SECTION

Smithsonian Institution - Renovate Baird Auditorium

TOILET, BATH, AND LAUNDRY ACCESSORIES

10 2800 - 5

Smithsonian Institution - Renovate Baird Auditorium

FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

10 4400 - 1

SECTION 10 4400 -FIRE EXTINGUISHERS, CABINETS, AND ACCESSORIES

PART 1 - GENERAL

1.01 RELATED DOCUMENTS

A. Drawings and General Provision of Contract, including General and Special Conditions and

Division 1 Specification Section, apply to work of this Section.

1.02 SUMMARY

A. This Section includes the following:

1. Portable fire extinguishers

2. Cabinets for portable fire extinguishers

1.03 DEFINITIONS

A. COTR: Contracting Officer Technical Representative

B. FM: FM Global (Factory Mutual)

C. FPE: Fire Protection Engineer

D. Furnish: To supply the stated equipment or materials

E. Install: To set in position and connect or adjust for use

F. NFPA: National Fire Protection Association

G. NICET: National Institute for Certification in Engineering Technologies

H. OSHEM: Office of Safety Health and Environmental Management

I. Provide: To furnish and install the stated equipment or materials

J. UL: Underwriters Laboratories

1.04 SYSTEM DESCRIPTION

A. Portable fire extinguishers and cabinets for occupant use.

1.05 PERFORMANCE REQUIREMENTS

A. In accordance with NFPA 10.

B. Extinguishers installed throughout most occupancies shall have a minimum rating of

2A:10B:C

C. Provide clean agent, water mist, or CO2 portable fire extinguishers and one water extinguisher for class A fires in all IT specs. Dry chemical extinguishers shall not be permitted.

D. Exhibit display areas and ordinary collection storage spaces shall be provided with water mist type portable extinguishers. Dry chemical extinguishers shall not be permitted in these spaces.

E. Wet collection storage areas shall be provided with CO2 portable fire extinguishers.

F. Provide fire extinguishers throughout all buildings and spaced in accordance with NFPA

10.

10 4400 - 2

1.06 SUBMITTALS

A. A. Submit manufacturers brochure and product data for each type of fire extinguisher, complete with manufacturers’ warranty and inspection tag.

B. Submit data to illustrate cabinets and installation/mounting methods.

1.07 QUALITY ASSURANCE

A. American Disability Act (ADA)

1. ADA Accessibility Guidelines (ADAAG)

B. American Society for Testing and Materials (ASTM)

1. A1008/A1008M Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved

Formability

2. ASTM A167-Stainless and heat resisting chromium-nickel steel plate, sheet and strip

3. ASTM A336-Cold rolled carbon steel sheets, commercial quality

4. C1036 Standard Specification for Flat Glass

5. E814 Standard Test Method for Fire Tests of Through-Penetration Fire Stops

C. National Fire Protection Association (NFPA)

1. NFPA 10 Portable Fire Extinguishers

D. Fire Extinguishers: Listed and labeled by Underwriter’s Laboratory (UL) or Factory Mutual

(FM) for type, rating, and classification

1. UL 8 Standard for water based agent fire extinguishers

2. UL 154 Standard for carbon dioxide fire extinguishers

3. UL 626 Standard for water fire extinguishers

4. UL 2129 Standard for halocarbon clean agent fire extinguishers

1.08 DELIVERY, STORAGE, AND HANDLING

A. Do not deliver fire extinguishers or cabinets to site until rooms in which they are to be installed are ready to receive them.

B. Protect cabinets to avoid damage to finish.

1.09 COORDINATION

A. Coordinate installation with finished wall surfaces.

1.10 WARRANTY

A. Provide a warranty by the manufacturer against defects in manufacturing and materials.

PART 2 - PRODUCTS

2.01 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the work include, but are not limited to, the following:

10 4400 - 3

1. Ansul Inc.

2. J L Industries

3. Larsen’s Manufacturing Co.

4. Encon Safety Products

2.02 MATERIALS

A. Cold-Rolled Steel Sheet: Carbon steel, complying with ASTM A1008/A1008M, commercial quality, stretcher leveled, temper rolled.

2.03 PORTABLE FIRE EXTINGUISHERS

A. General: Provide fire extinguishers of type, size, and capacity for each cabinet and other locations indicated. See section 1.07 for requirements for specific spaces.

1. Product: A 10-lb, multi-purpose, UL listed, dry chemical fire extinguisher with rating based on spacing and hazard.

a. recessed type cabinets

B. Mounting Brackets: Manufacturer’s standard steel bracket, designed to secure extinguisher, of sizes required for types and capacities of fire extinguisher indicated, with plated or baked-enamel finish.

C. Fire extinguishers installed outside shall be located in approved weather-tight fire extinguisher cabinets.

2.04 FIRE EXTINGUISHER CABINETS

A. General: Unless specified otherwise on construction drawings, provide fire extinguisher cabinet of type, size, and rating as indicated below, or equivalent.

B. Cabinet Size: The minimum inside box dimensions shall be 24”H x 9½W x 6”D for SNL

Type I and Type III fire extinguishers, and 27”H x 12”W x 8”D for SNL Type II fire extinguishers.

C. Cabinet Construction: Provide manufacturer’s standard box, with trim, frame, door, and hardware to suit cabinet type, trim style, and door style indicated. Weld joints and grind smooth. Miter and weld perimeter door frames.

D. Fire-Rated Cabinets: Listed and labeled to meet requirements of ASTM E814 for fire-resistance rating of wall where it is installed. Construct fire-rated cabinets with double walls fabricated from 0.0478-inch (1.2-mm) thick, cold-rolled steel sheet lined with minimum 5/8-inch (16-mm) thick, fire-barrier material. Provide factory drilled mounting holes.

1. Cabinet Metal: Enameled-steel sheet.

2. Shelf: Same metal and finish as cabinet.

E. Cabinet Mounting: Suitable for the following:

1. Recessed: Cabinet box recessed in walls of sufficient depth to suit style of trim indicated.

F. Cabinet Trim Style: Fabricate cabinet trim in one piece with corners mitered, welded and ground smooth.

10 4400 - 4

G. Cabinet Trim Material: Steel sheet.

H. Door Material: Steel sheet.

I. Door Glazing: Clear Float Glass, ASTM C1036, Type 1, Class 1

J. Door Style: Vertical duo panel with frame.

K. Door Construction: Provide a minimum ½-inch (13 mm) thick door frames.

L. Door Hardware: Provide manufacturer’s standard door-operating hardware of proper type for cabinet type, trim style, and door material and style indicated. Provide recessed door pull and friction latch. Provide continuous-type hinge permitting door to open 180 degrees.

M. Cabinet and Door Finishes: Provide manufacturer’s standard baked-enamel paint for the exterior and interior of the cabinet and doors.

PART 3 - EXECUTION

3.01 EXAMINATION

A. Examine walls and partitions for suitable framing depth and blocking where recessed and semirecessed cabinets are to be installed. Verify that rough openings for cabinets are correctly sized and located.

B. Examine fire extinguishers for proper charging and tagging. Remove and replace damaged, defective, or undercharged units.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.02 INSTALLATION OF FIRE EXTINGUISHERS

A. Comply with manufacturer’s written instructions for installing fire extinguishers and mounting brackets.

B. Mounting Height: Install extinguishers at heights indicated below.

1. Install fire extinguishers mounted on hangers or brackets attached to a wall so that the top of the fire extinguisher is not more than 3½ ft. above the floor.

2. In no case shall the clearance between the bottom of the fire extinguisher and the floor be less than 4 inches.

C. Locations: Install extinguishers at locations indicated below.

1. Install fire extinguishers at locations specified on the drawings or as directed by the authority having jurisdiction.

2. Fire extinguishers shall be conspicuously located, along normal paths of travel, including exits from areas. Extinguishers shall not be obstructed or obscured from view.

D. Install portable fire extinguishers on the hanger or in the bracket supplied, or place in the fire extinguisher cabinets provided. Verify that the extinguisher operating instructions face outward.

3.03 INSTALLATION OF FIRE EXTINGUISHER CABINETS

A. Comply with manufacturer’s written instructions for installing fire extinguisher cabinets.

B. Mounting Height: Install fire extinguisher cabinets at the…