This document is an addendum for the Career Connect Campus - Technology Bid Package, issued by the Kalamazoo Regional Educational Service Agency. The addendum clarifies and changes specifications for the project, including revisions to the Alternates Form, schedule updates, and responses to RFIs. The project requires a single prime contractor to provide a full technology package, including AV, security, and other systems. The bid due date has been extended to January 16, 2024. No partial bids will be accepted, and there are no union or prevailing wage requirements for the project. Performance and payment bonds are required. The addendum provides detailed responses to contractor questions on topics such as cable counts, speaker zones, access control, and camera specifications. Additionally, the addendum includes revised drawings and an updated Alternates Form that changes the base bid and alternate for larger display sizes in conference rooms.

The contract will be awarded to a single prime contractor responsible for the full technology package. Pricing should include performance and payment bonds. The project is funded by the Kalamazoo Regional Educational Service Agency, and no set-asides or incumbents are specified. The addendum provides clarifications and changes to address contractor questions and concerns regarding the project requirements and specifications.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM NO. 4

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\Addendum 4\2024.01.18 Addendum 4.docx

PROJECT: Career Connect Campus - Technology Bid Package

CLIENT: Kalamazoo Regional Educational Service Agency

ISSUE DATE: 1/18/2024

The following clarifications and changes shall be included in the Plans and Specifications for the above referenced project, as prepared by Wightman & Associates, Inc. dated November 29, 2023. This Addendum shall be deemed a part of the Contract Documents, and to the extent that the provisions of the other Contract Documents are in conflict herewith, this Addendum shall control.

SPECIFICATIONS:

1. Revised Section 00 43 23 Alternates Form, 1.4 A. Schedule of Alternates, Alternate No. 1.

a. Reversed the base bid and alternate to be consistent with the drawings. Base bid is 98” monitor and alternate is 110”.

b. Removed Large Conference Room 210 from the alternate, consistent with the drawings.

2. Revised Section 00 43 23 Alternates Form, 1.5 A. Submission of Bid Supplement date to 2024.

DRAWINGS:

1. Disregard the reference in Addendum 2 of sheets E2.1C, E3.1C, and E7.17 being included in the addendum. They were not included; they are bulletin drawings for the electrical contractor that is under contract.

ATTACHMENTS:

1. RFIs to date.

The bidder hereby acknowledges receipt of this Addendum and shall include a signed copy with their bid.

Company Date

Signature Title

Print or Type Name

Kalamazoo Regional Educational Service Agency Wightman Career Connect Campus - Technology Bid Package 11/29/2023 Project No. 214175 Addendum 4

ALTERNATES FORM 00 43 23 - 1

DOCUMENT 00 43 23 - ALTERNATES FORM

1.1 BID INFORMATION

A. Bidder: ___________________________________________________________.

B. Project Name: Career Connect Campus – Technology Bid Package

C. Project Location: 3500 Vanrick Drive, Kalamazoo, MI 49001

D. Owner: Kalamazoo Regional Educational Service Agency

E. Architect: Wightman & Associates, Inc.

F. Architect Project Number: 214175

1.2 BID FORM SUPPLEMENT

A. This form is required to be attached to the Bid Form.

1.3 DESCRIPTION

A. The undersigned Bidder proposes the amount below be added to or deducted from the Base Bid if particular alternates are accepted by Owner. Amounts listed for each alternate include costs of related coordination, modification, or adjustment.

B. If the alternate does not affect the Contract Sum, the Bidder shall indicate "NO

CHANGE."

C. If the alternate does not affect the Work of this Contract, the Bidder shall indicate "NOT

APPLICABLE."

D. The Bidder shall be responsible for determining from the Contract Documents the affects of each alternate on the Contract Time and the Contract Sum.

E. Owner reserves the right to accept or reject any alternate, in any order, and to award or amend the Contract accordingly within [60] days of the Notice of Award unless otherwise indicated in the Contract Documents.

F. Acceptance or non-acceptance of any alternates by the Owner shall have no affect on the Contract Time unless the "Schedule of Alternates" Article below provides a formatted space for the adjustment of the Contract Time.

Kalamazoo Regional Educational Service Agency Wightman Career Connect Campus - Technology Bid Package 11/29/2023 Project No. 214175 Addendum 4

ALTERNATES FORM 00 43 23 - 2

1.4 SCHEDULE OF ALTERNATES

A. Alternate No. 1: Provide an alternate cost to revise the 98” (AV-FPD-98) monitor to a 110” monitor (AV-FPD-110) where shown in the large Conference Room F210, and Medium Conference Room F110.

1. ADD____ DEDUCT____ NO CHANGE____ NOT APPLICABLE____.

2. ________________________________________________Dollars

B. Alternate No. 2: Provide an alternate cost to replace the DirectView LED in the Commons CR110 to a video wall using a monitor array equal to diagonal size of 217”.

1. ADD____ DEDUCT____ NO CHANGE____ NOT APPLICABLE____.

2. ________________________________________________Dollars

1.5 SUBMISSION OF BID SUPPLEMENT

A. Respectfully submitted this ____ day of ____________, 2024.

B. Submitted By:________________________________________________ (Name of bidding firm or corporation)

C. Authorized Signature:__________________________________________ (Handwritten signature)

D. Signed By:__________________________________________________ (Type or print name)

E. Title:_______________________________________________________ (Owner/Partner/President/Vice President)

END OF DOCUMENT 00 43 23

PROJECT: Career Connect Campus - Technology Bid Package

CLIENT: Kalamazoo Regional Educational Service Agency

Date Question Answer

12/5/2023

Will the owner accept bids from contractors that can provide only partial scope, i.e. AV, security?

No. There is to be one Prime Contractor to which specialty contractors can provide a bid.

12/5/2023 Where can contractors find a list of Prime

Contractors?

A plan holders list may be found at gowightman.com. You may also reach out to

Builder's Exchange.

12/5/2023 Is there a union requirement for this project?

No.

12/5/2023 Is there a prevailing wage requirement for this project?

No.

12/5/2023 With the holiday and tight schedule, it may be challenging to get the bonds.

Security can be in the form of a bid bond, bank check, or cashier check by the prime bidder.

12/5/2023 Is there an opportunity to entertain an extension in the schedule?

The bid due date has been extended as noted in the Addendum 1 Advertisement to Bidders and

Preliminary Schedule.

12/5/2023 Are performance and payments bonds required for this project?

Yes, see the Advertisement to Bidders, AIA 101

Standard form of Agreement between Owner and

Contractor and AIA 201 General Conditions. This amount is to be included in your your Base Bid, item 1.2A on Bid

Form Specification Section 00 41 13. Item has been added in Addendum 1 to the Bid Form for contractors to indicate the P&P bonds amount that is included in the base bid.

12/22/2023

Drawing T3.10 Technology Riser show a

Functional Diagram for a Vet Clinic E100.

Where is the Vet Clinic on the plans?

The Vet Clinic is located second floor Area E.

See T2.1E for the AV device layout, column line

17/G Waiting Area, and T1.1E for network infrastructure and security layout.

12/22/2023

Drawing T7.3 Information Outlet Schedule chart shows camera and wall phone both get

2 faceplate ports. Is this correct?

Provide 2-port faceplate for the camera as listed in the Information Outlet Schedule. Wallphone shall be a 1-port stainless steel faceplace with mounting lugs.

12/22/2023

Where on the drawing does it state how many data cables are required for any of the locations? How many cables are required for

WAPS, Cameras, Data locations? Drawing

T.01 only shows configurations.

Refer to T7.3 Information Outlet Schedule. The jacks listed reference the # of cables per faceplate. Clocks and intercom require 1-data cable as indicated in Addendum 2.

12/22/2023 Do clocks need a data cable?

Clocks and intercom require 1-data cable.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx

Date Question Answer

12/22/2023 Are there any locations not mentioned in the preceeding four questions that need cables?

Refer to T7.3 Information Outlet Schedule. The jacks listed reference the # of cables per faceplate, and Section 27 11 00 for patch cable requirements.

1/3/2024

Should the jack schedule in the lower left correspond to the number of cables pulled to that location?

Yes, jack schedule has been revised in

Addendum 2.

1/3/2024

Camera locations listed as "C1" get one cable and jack according to the schedule, yet previous RFI response indicates 2 cables are required. Which is it? Example: Stairway near column 13/N on T1.1E shows two camera locations with a CM number which correlates to one drop per the chart.

2-cables per Addendum 2.

1/3/2024 There are camera locations that shown on

T2.1E that do not show on T1.1E.

T2.1E is an AV drawing showing AV cameras.

T1.1E shows Security cameras.

1/3/2024

Comparing the AV prints which show camera locations, some are not shown on the technology prints. Please confirm locations.

The AV prints show AV device locations while the technology prints show network device, paging, and security device locations.

1/3/2024

There are references to "CM-4" that by the chart only get one cable which differs from a previous RFI answer which states a 2-port faceplate is required for cameras. Is it to be a two-port faceplate and one cable?

Summary is, how many cables are to be at each camera?

Security cameras (CM-#) shall receive 2-cables and 2-port faceplace. This will be updated in

Addendum 2.

1/3/2024 There are three types of speakers listed.

How many of each type in each zone?

Speaker locations and zones have been identified in the T1 series drainwgs. The contractor shall verify count in technology drawings.

1/3/2024 How many overall speaker zones?

A total of 48 zones. Public/Common (and back of house) spaces, administative spaces, and each instructional space shall be zoned separately.

Revision issued in Addendum 2

1/3/2024

Speakers indicate supervision is required yet, Bogen control equipment and amps are not capable of this. IP/POE speakers would be necessary. Please advise.

Revision issued in Addendum 2. Non-supervised is acceptable.

1/3/2024 How many speaker/locations are to have talkback capability?

Revision issued in Addendum 2. Talk back speakers are not required.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx

1/3/2024 Is there a functional diagram for paging? Included in Addendum 2.

1/3/2024 Given the number of questions, will the bid due date be extended?

Bid due date has been extended to January 16, 2024. Same time and location.

1/3/2024 Will a camera system other than Aviligon be accepted?

No substitutions allowed for this system as indicated on the equipment schedule. Bidders are encouraged to if unable to provide Avigilon, to partner with a subcontractor that can.

1/9/2024

The equipment schedule does not include a definition for the symbol AV-HDMIDA, as shown in the C100 Comp Systems drawing

(T3.11, fig. 2). It has been assumed that this is an Extron DA4 HD 4K Plus. Please confirm.

The Basis of Design is based on an Atlona RON-

444: 4K HDR 4-Output HDMI Distribution

Amplifier. The Extron DA4 HD 4K Plus is an acceptable alternate.

1/9/2024

The description for AV equipment item AV-

MP2-REC includes a generic call-out for a

Countryman, but does not specify a type or model. It is assumed that this is intended to refer to a headset type mic. Therefore, we have included the H6 series headset. Please confirm that this is acceptable.

The E6 or H6 are acceptable.

1/9/2024

The Addendum 2 dialog indicates that three electrical (E series) drawings have been revised. The E series drawings have not been provided with this package, and do not appear to be part of the scope of this bid.

Should these drawings and revisions be included?

Remove the E series drawings for Addendum 2.

This will be issued as a separate Bulletin package.

1/9/2024

In the Commons (T3.5, fig. 3), the wallplate indicted as AV-AV2 appears to be intended to be the AT-OME-SW21-TX-WPC model previously specified here. Please confirm or indicate other intentions.

The AT-OME-SW21-TX-WPC is correct.

1/9/2024

T2.1E shows two Lobby displays, a 65” and a

TSD 65”, which are not shown in signal flow diagrams. Please indicate what these will be connected to and what other devices are associated with them.

The 2 lobby displays are stand alone displays and will be used for digital signage. No additional AV connectivity is required.

1/9/2024

Please confirm that the BGR-25SA-27 is what is intended as the equipment rack in the

Culinary Labs

BGR-25SA-27 could be used. With front locking door.

1/10/2024

Are we to bid 12-strand single mode fiber, 24-strand single mode or multi-mode. Specs call for 12-strand single mode. Drawing T3.4 calls for 24-strand single-mode and multi-mode.

Drawings and specs appear to be consistent.

There are keynotes 7, 8, and 9 on T3.4 that reference cable types to specific locations. A/E recommends contractor confirm they are looking at Tech Addendum #2 drawings dated

01/05/2024.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx

1/10/2024 Do bids need to be mailed or can they be emailed?

State of MI rdoes NOT allow electronic bid submissions for school projects. Hard copies are required.

1/11/2024

Motorola (security manufacturer) indicated

Motorola Open Path access control is a hosted solution. Motorola ACM is an on-premise access control solution. Motorola has indicated the on-premise should be provided rather than was is specified in the contract documents. Please confirm.

Provide an On-Prem Access Control Soultion.

Revise to Motorola ACM.

1/12/2024 May we have a copy of the reflected ceiling plans for reference?

Yes. Included in Addendum 3. Note that what is depicted as 2x2 ceiling tile is perforated and in many cases metal except in toilet and storage rooms. Camera and WAP mounting elevations have been coordination with these conditions.

1/12/2024 May we have a copy of the door hardware schedule so we know what is being installed?

Yes. Included in Addendum 3.

1/12/2024 Where in the documents are the WAP and switch manf/models listed?

The WAP model is located in the Information

Outlet schedule. The swicthes are on the rack elevations, issued in Addendum 2.

1/12/2024 Where in the documents are UPS model/manfacturer?

UPSs are by owner and not to be included in contractor's bid.

1/17/2024

Does contractor need to be certified in

Panduit or just experienced and knowledgable, given contractor having 20 years experience.

The contractor needs to be certified by the manufacturer per the specifications and shall be in place at a inimum of 1 year.

1/17/2024

Cloud and local server requirements specified for security/surveillance is more than what hospitals and schools require. We see that only at government level and is very costly. Are both required?

Local Server for Security/Surveillance is required.

1/17/2024

The specified clock – Atlas IP-SDH – requires GlobalControlKom®, InformaCast®, or Revolution Notification, which would not be within the scope of this current bid package.

Please confirm that that is being provided by others.

Replace the Atlas IP-SDH with Primex 163-

PE150R. The C1 locations are POE digital clock locations, and does not include a speaker.

1/17/2024

The BenQ displays specified for the 86 inch and 98 inch size displays are available with either 3 year or 5 year warranties. Please indicated which version is preferred.

Provide 5 year warranty.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx

1/17/2024

The original Alternates Form doesn’t appear to match the alternates as currently called out on the drawings. The originally provided form has Alternate #1 as changing 110” displays in

F110 & F210 down to 98” displays. The current drawings (per T2.1F) ask for an alternate to change 98” displays in F110 up to 110” displays. Will a new Alternates Form be issued? Please confirm what is currently expected as alternates.

A new alternates form is included in Addendum 4.

The smaller displays are base bid. The alternate is for the larger displays.

1/17/2024

The current AV equipment schedule indicates the 98 inch display model as an interactive touch display and the 110 inch display model as a non-interactive display. Alternate #1 involves swapping between these models.

Please confirm that it is understood that one is interactive and not the other.

This is correct.

1/17/2024

The speaker model called out for PA-S1-W is an indoor speaker while it appears that it is being used in outdoor locations. Please indicate if there is an outdoor model preferred, perhaps Atlas SM42T?

Use Atlas SM42T for outdoor locations.

1/17/2024

The signal flows for Labs E205, E206 &

Agriculture E111 & E112 show connections for hearing Assistance, but Beacons are not indicated for those rooms on the floor plans.

Should those rooms have hearing assistance? Should those rooms have

Beacons?

ALS for Labs E205, E206 & Agriculture E111 &

E112 rooms should be included along with beacons.

1/17/2024

Switches and WAPs were added in an addendum. Is the awarded contractor to install the fire wall and configure?

All switches and WAPs shall be purchased and installed by the contractor. All equipment shall be turned over to owner for programming prior to install.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx

With the access control system being changed to Avigilon ACM, there are two PoE controllers available. They are the LP1501 &

MR62e. The LP1501 is a single-door controller (Not 2-door as listed in the Spec) and has no additional inputs for bringing in additional monitored points. This board is limited to a single-door application. The

MR62e can provide two full doors of access with additional inputs and outputs for additional monitored points. This is close to the Open Path controller originally spec’d.

These boards require a network controller to function. The LP1502 can support up to 64

MR62e boards. With the size of this project, it will require a minimum of (3) LP1502 controllers and an enclosure to house the boards and power supply. Which PoE controller is to be bid? It could be a a combination of the two based on the requirements to bring in monitored points or additional full access doors. (Specification sheets are attached)

Provide a 2-door controller as specified.

1/17/2024

Portions of the access control spec look like it was not written for PoE boards as it calls out for power supplies, relay boards, and separate terminal blocks for all connections before landing them on the boards. This is not typical for these boards. If this is a requirement larger enclosures and additional components are necessary. If not, a smaller enclosure can be used and eliminating the terminal blocks, power supplies, and relay boards.

The Specification lists the power supplies, relay boards, and terminal blocks for all connections in the event the project will require the traditional architecture for connectivity. It is not required to be provided if not required as part of the install.

The contratcor shall use it for reference only.

1/17/2024

I believe KRESA already has an access control server they use for all the ACM systems in the district. Are we to provide only provide 16-packs of reader license that will be loaded onto the existing server?

Provide a new server for the ACM system.

1/17/2024

Who is to provide the roof penetrations for

DAS and entrance cables, (T6.1, 4) and the

2" and 4" sleeves for data cable between floors as well as conduit needs in hard ceilings and 15A 120v power recepts for the

4 DAS?

Electrical contractor will provide roof penetrations, sleeves, conduit above hard ceilings and power recepts.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx

Access control tech drawings differ from the hardware schedule provided for reference in

Addendum 3. i.e. T1.2A door from

Collaboration CR201A to Outdoor Terrace

D101C has a card reader on only the interior while the hardware schedule has it on both sides, similar to the door between the

Outdoor Terrace and Admin Open Office

A201H that also accesses the Outdoor

Terrace. Are we to follow the door hardware schedule or the T-series sheets. SImilarly, sheet T1.2B, the door between Instructional

Studios B201 and B202 shows no card readers while the door schedule has one on each side.

This will be reviewed and updated. For bidding purposes and In the event of a discrepancy, follow the T-series sheets and specifications.

1/17/2024

Avigilon has discontinued the H4A model shown on T7.1 camera types. Please confirm CM-3 should be 15C-H5A-3MH-270 to reflect the new model, same function.

Similarly, VS-CM-6 would be 20C-H5A-4MH-

360.

The provided part #s are acceptable. Replace CM-

3, and CM-6 with updated part #, 1/17/2024

VS-CM-2 description states "2-Channel" but the model number is a 3-head. Confirm this should be 10C-H5DH to be both dual head and new model number.

Use a 3-channel camera to provide a 180 deg view.

1/17/2024 Are VS-CM-2 and VS-CM-7 the same function?

No. The CM-2 is a (3-channel) 180 deg camera while the CM-7 is a dual head camera per the equipment list.

1/17/2024

VS-CM-2 calls out "Peanut Shaped".

Avigilon does not make a peanut shape. Axis does. Please confirm what is desired.

The CM-2 is a 180 (3-channel) camera per responses above. This will be updated in the description.

P:\Kalamazoo\214175 KRESA Career & Technical Edu Campus\G) CA\G10 Bid Docs\Technology Bid Package\_RFI Log draft.xlsx