2022200045_A2_Addendum 4.pdf
PDF 861 KB Posted
- Solicitation number
- S-KE0010-00006478
- Issued by
- Lane County, Oregon
About this file
This document is Addendum No. 4 to Invitation to Bid (ITB) 2022200045 for Kitchen Improvements at the Whiteaker Head Start Facility located in Eugene, Oregon. The solicitation, issued by the City of Eugene in partnership with Lane County, has been updated with revised drawings for the Site Plans and Elevation/Section Details. The work involves modifications to walls, foundation, and exterior, as well as the construction of a new walk-in cooler/freezer. All other specifications, terms, and conditions remain unchanged.
The project is funded through a Community Development Block Grant from the City of Eugene. The successful bidder will be expected to coordinate with the City and Head Start to facilitate the project, with the intent that work will commence as soon as reasonably possible.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: May 16, 2023 To: All Potential Bidders From: Noel Dietz, Purchasing Analyst Subject: Invitation to Bid 2022200045 Kitchen Improvements at Whiteaker Head Start Facility
ADDENDUM NO. 4
The solicitation referenced above is updated & amended as follows.
The following revised drawings for Attachment A, Plans are attached:
07 A-2 Site Plans Floor Plan 07 A-3 Elevation Section Details
All other specifications, terms and conditions remain unchanged.
8'2' 4'0'
1/4" = 1'-0"1 FLOOR PLAN
NEW STAINLESS STEEL COUNTER -
2' X 10' W/ (1) SHELF BELOW
NEW EXHAUST FAN AT CEILING -
GREENHECK CSP-A700-VG
580 CFM, 0.3" ESP
CONTRACTOR TO VERIFY IF EXISITNG
DUCTWORK IS SUITABLE FOR REUSE AND
REPLACE AS NECESSARY.
WALK-IN
FREEZER
WALK-IN
COOLER
(E) GREASE INTERCEPTOR TO REMAIN
RBA #:
SET ISSUE
P.I.C:
PM / PA:
DATE
REV. DATE
REVISIONS TO THIS SHEET
PROJECT TRACKING
John Rowell Lorri Nelson
STAMP
Owner
Project Name
Project Address
Whiteaker Walk-in Cooler / Freezer
21 N. Grand St.
Euegen, OR
BID / PERMIT SET 2023-05-04
X
SH
EE
T
A-2
SITE PLANS
FLOOR PLAN
16'4' 8'0'
1/8" = 1'-0"2 EXISTING COURTYARD PLAN
EXISTING GREASE INTERCEPTOR
16'4' 8'0'
1/8" = 1'-0"3 NEW COURTYARD PLAN
245 SF
(E) PERVIOUS SURFACE
1,105 SF
(E) IMPERVIOUS SURFACE -
ASPHALT TO BE REMOVED
(E) AREA DRAIN TO REMAIN
691 SF
PERVIOUS SURFACE
4" MIN. THICKNESS OF PLAYGROUND CHIPS -
TOP OF CHIPS TO BE LEVEL WITH TOP OF ADJACENT PAVED
SURFACES
163 SF
IMPERVIOUS SURFACE - BUILDING
465 SF
IMPERVIOUS SURFACE - NEW CONCRETE SLAB ON GRADE
KITCHEN
STORAGE
WALK-IN
(DS) DOWNSPOUT FROM COVERED WALKWAY -
REROUTE UNDERGROUND LINE TO EXISTING AREA
DRAIN
(E) 4" UNDERGROUND STORMWATER LINE TO BE
REMOVED
NEW 4" UNDERGROUND STORMWATER LINE
KITCHEN
STORAGE
EXISTING COVERED WALKWAY
TOP OF SLAB ELEVATION TO MATCH EXISTING AT ALL
EDGES - SLOPE TO (E) AREA DRAIN MIN. 2%
SLOPE
2% MAX,
TYP.
SLOPE
SL
O
PE
'-0
A-3
CUT NEW OPENING IN WALL FOR DOOR -
SEE DETAILS
A-3
A-3
PHOTO -
EXISTING
WALL
2" 13'-6"
A-3
A-3
A-3
(E) 8" CMU WALL WITH BRICK VENEER
WALK-IN COOLER / FREEZER -
MODULAR UNIT
3' -4
1'
-6
3' -0
" 3' -1
WH
5' -4
2' -0
1' -6
A-3
(E) 4" UNDERGROUND STORMWATER LINE -
REPLACE WITH NEW 4" LINE - CONNECT TO
DOWNSPOUTS - INCLUDE CLEANOUT, TYP.
(E) 6" UNDERGROUND STORMWATER LINE TO REMAIN
WOOD FENCE AND GATES
MECH. UNITS
EXISTING GREASE INTERCEPTOR TO REMAIN
1/2" = 1'-0"4 EQUIPMENT ENCLOSURE
3' -6
1/
2" 2'
-9
/2
3"
1/
2"
ADJUST-A-GATE STEEL FRAME KIT (BLACK)
EAST ELEVATION NORTH ELEVATION
PLAN
SIMPSON POST
BASE Model
#FPBB44 (BLACK)
SLOPED SLAB EDGE AT COOLER/FREEZER
EXPANSION JOINT
4" CONC. SLAB ON GRADE W/ 4"
3/4- COMPACTED BASE
MECH. UNITS FOR COOLER/FREEZER
4X4 FENCE POST, TYP.
ALL WOOD TO BE TK CEDAR W/ PPG
PROLUX LOG & SIDING FINISH -
CEDAR COLOR
1" X 5 1/2" BOARDS
LATCH AND PADLOCK ON INSIDE OF GATES
2X4 NAILER BOARD
TALL HEAVY DUTY
CANE BOLT
(INSIDE GATES)
4X4 FENCE POST
BLACK METAL
POST CAP
SL
O
PE
PAIR OF GATES
4' -0
3" TY
P.
8'-6"
3" 8'-0" 3"
ADD-01
ADD-01 2023-05-04
ADD-01
ADD-01
ADD-01
3"
A-2
ADD-01
1 1/2"
1" X 5 1/2" BOARDS
ADD-02
(E) WATER HEATER PRESSURE RELIEF ROUTES THROUGH
LOWER (E) OPENING. CONTRACTOR TO COORDINATE WITH
ARCHITECT AND OWNER FOR PREFERRED NEW DAYLIGHT
LOCATION.
(E) COMBUSTION AIR OUTLET. RECONFIGURE ROUTING AS
NEEDED BASED ON NEW WATER HEATER LOCATION IF IT
MOVES. REUSE (E) ROOF PENETRATION.
(E) COMBUSTION AIR INLET TO (E) OPENING IN
WALL. RETOUTE INLET THROUGH ROOF.
MAINTAIN 3' SEPARATION FROM COMBUSTION
AIR OUTLET.
ADD-02
ADD-02 2023-05-16
1/4" = 1'-0"1 EXTERIOR ELEVATION
1/4" = 1'-0"4 SECTION
(E) EXHAUST AIR SIDEWALL
OUTLET HOOD TO REMAIN
A-3
11'-9"
9' -0
4" 7'
-4
1' -0
"4"
3'-4"5'-4"3'-1"
4'-8"3'-0"4'-1"
RBA #:
SET ISSUE
P.I.C:
PM / PA:
DATE
REV. DATE
REVISIONS TO THIS SHEET
PROJECT TRACKING
John Rowell Lorri Nelson
STAMP
Owner
Project Name
Project Address
Whiteaker Walk-in Cooler / Freezer
21 N. Grand St.
Euegen, OR
BID / PERMIT SET 2023-05-04
X
SH
EE
T
A-3
ELEVATION
SECTION
DETAILS
STORAGE WALK-IN
A-3
A-3
A-3
COOLER FREEZER
A-3
NEW WALK-IN MODULAR
7 FOUNDATION DETAIL
2 PHOTO - (E) CONDITIONS
1/4" - 1'-0"3 INTERIOR ELEVATION
10 1" = 1'-0"8 1" = 1'-0"1" = 1'-0"
6 OPENING DETAILS
1" = 1'-0"9
1" = 1'-0"
FOUNDATION DETAILFOUNDATION DETAILFOUNDATION DETAIL
1'-0"8"
4" 6"
4"
13'-6"
WALK-IN MODULAR
4" EXPANSION JOINT
1"
SEALANT PER MFR. REQUIREMENTS
1"
4" CONC. WEAR SLAB
2X6 BLOCKOUT @ DOOR - VERIFY
WIDTH W/ MODULAR MFR -
INSTALL CABLE ASSEMBLY &
GROUT SOLID
INSULATION
4" CONC. SLAB
COOLER FREEZER
8"
CONC. SLAB
2X6 TREATED WD.
6"10"
4"
UNDISTURBED SOIL
4" CONC. SLAB ON GRADE W/ 4"
COMPACTED SUBBASE
VAPOR BARRIER
(VERIFY W/
FREEZER/COOLER
MFR.)
2X TREATED WD
WALL PANEL & FLASHING BY
WALK-IN INSTALLERMULTI PIECE ALUM.
THRESHOLD ANCHOR TO
CMU / CONC. - FILL BELOW
VAPOR BARRIER
WALL PANEL & FLASHING
BY WALK-IN INSTALLER
WALL PANEL & FLASHING BY WALK-IN MFR.
1'-0" 8"
8" 4"
EXISTING FOUNDATION
WALL & FOOTING - VERIFY
SIZE & LOCATION - NOTIFY
ARCHITECT OF ANY
DISCREPANCIES PRIOR TO
COMMENCEMENT OF WORK
1'-0"8"
VAPOR BARRIER
4" 8"
CONC. SLAB
WALL PANEL & FLASHING BY
WALK-IN INSTALLER
5'-4" X 7'-4" CUT OPENING IN WALL
(E) VENT / OPENING IN WALL
(E) CMU WALL W/ BRICK VENEER @ EXTERIORWD. TRIM OVER CMU
(E) VENT / OPENING IN WALL
STEEL ANGLE / PLATE -
SEE DETAIL
A-3
FILL (E) VENT / OPENING IN
WALL W/ SPRAY FOAM
INSULATION
WALL PANEL & DOOR BY
WALK-IN MFR
3/8" PLATE W/ 1/2"X6" TITEN HDS
@ 24" O.C. MAX. (ANCHORS MUST
BE INSTALLED INTO GROUTED
CMU COARSE)
(NO SPECIAL INSPECTION
REQUIRED)
FLASHING - BY WALK-IN MFR
3/8"
6"X8"X3/8" STEEL ANGLE
1/2" THRU BOLT @ 24" O.C.
6"X4"X3/8" STEEL ANGLE
(EXTEND MIN. 24" PAST EACH
SIDE OF OPENING W/ (2) 1/2"X6"
TITEN HDS)
FACE OF CMU OPENING
BEYOND
NON-STRUCTURAL WOOD
FRAMING @ OPENING
(E) CMU BOND BEAM & BRICK
VENEER
EXPANSION JOINT COVER - SEE 5/A-3
FREEZER / COOLER WALL
PANEL
3/8" PLATE W/ 1/2"X6" TITEN HDS
@ 24" O.C. MAX. (ANCHORS MUST
BE INSTALLED INTO GROUTED
CMU COARSE)
HEAD
JAMB
REPLACE DOWNSPOUT AND
STORMWATER LINE TO AREA
DRAIN
(E) OPENING IN WALL
5'-4"
NEW OPENING
IN WALL
5 EXPANSION JOINT COVER
3" = 1'-0"
NOTE:
1. SLAB REINFORCING TO BE #4 @
18" EACH WAY - LAP 18" WITH
EDGE REINFORCING, TYP.
2. TYPICAL REINFORCING COVER
TO GRADE SHALL BE 3"
3. OTHER REINFORCING COVER
MIN. 2"
4. CENTER REINFORCING IN SLAB
24"X7" #4 BARS @ 18" OC
#4 @ 24" OC - (2) #4
LONGITUDINAL BARS
17"X6" #4 BARS @ 18" OC
(2) #4
LONGITUDINAL
BARS
24"X7" #4 BARS @ 18" OC
24"X9" BARS @ 18" OC
9' -6
VI
F
8' -6
AF
F
8' -6
8' -0
A-3
GROUT CELLS SOLID BELOW
THRESHOLD
NON-STRUCTURAL WOOD
FRAMING @ OPENING
SHIM, BACKER ROD &
SEALANT
12"
FIELD VERIFY
NOTE:
3RD PARTY SPECIAL INSPECTION REQUIRED FOR
INSTALLATION OF BOLTS AND STEEL ANGLE. SPECIAL
INSPECTOR SHALL VERIFY EXISTING CMU BOND BEAM IS
GROUTED IN PLACE AND BOLTS ARE SNUG.
(E) CMU BOND BEAM & BRICK
VENEER
2"
FACTORY APPLIED SILICONE
FACE
1/ 8"
2"
FIELD APPLIED SILICONE LAYER
PRE-COMPRESSED
IMPREGNATED OPEN CELL
FOAM
EXPANSION JOINT COVER BY
CS CONSTRUCTION SPECIALTIES OR EQUAL
WALL OF MODULAR WALK-IN
UNIT
2X TREATED WD
WRAP VAPOR BARRIER UNDER
WALL PANEL PER MFR.
REQUIREMENTS
SEALANT PER MFR.
REQUIREMENTS
1"
FELT PAPER
NOTE:
1. OVERLAP LAYERS OF VAPOR
BARRIER BELOW INSULATION A
MINIMUM OF 3" AND SEAL
SEAMS.
2. INSTALL LAYERS OF INSULATION
- SECOND LAYER TO BE
PERPENDICULAR TO THE FIRST
LAYER SO THAT SEAMS ARE NOT
CONTINUOUS VERTICALLY, AND
SO ON WITH EACH LAYER.
ADD-02
(E) EXHAUST FAN TO REMAIN
ADD-02 2023-05-16
AutoCAD SHX Text
| 2022200045_A2_Addendum 4_Draft |
| 07_A-2_SITE PLANS-FLOOR PLAN_R_ |
| 07_A-3_ELEVATION-SECTION-DETAILS_R |