2022200022_A2_Attachment A_Drawings_AMENDED_10-22-21pdf.pdf
PDF 11 MB Posted
- Solicitation number
- S-KE0010-00000996
- Issued by
- Lane County, Oregon
About this file
This document is the Attachment A - Drawings for ITB 2022200022 Airport Checked Baggage System Expansion, a contract opportunity issued by Lane County and the City of Eugene, Oregon. The project involves modifying existing checked baggage inspection areas and installing one new CT-80 DR+EDS to TC3 screening line. The work includes electrical, conveyor system installation, compliance testing, equipment training, general finishing, and other related services.
The contract is for a state and local government project within Lane County and the City of Eugene. No additional pricing terms, set asides, incumbents, funding requirements, or other salient information is provided in this attachment.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AEC PROJECT NUMBER
NOT ISSUED FOR
CONSTRUCTION
REVISIONS
/3
/2
:2
:5
P
M B
IM
/2
E
U G
C B
IS
E x p a n s io n T
C B
H S
/2
E
U G
C
B
IS
E x p a n s io n
T C
B
H S
A
R
.r v t
2241872012
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
ISSUED FOR BID
BNP Associates, Inc.
1999 Broadway, Suite 4250
Denver, Colorado 80202
BAGGAGE HANDLING
Copyright © 2021. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
© 2021 RS&H, INC
303-409-9700
4582 S Ulster St., Suite 1100 Denver, Colorado 80237-2603 www.rsandh.com
Oregon Registration No. 0871AF
EUGENE AIRPORT CBIS TC3 EXPANSION
NO. DESCRIPTION DATE
9/30/2021
As Amended per Addendum 1
A. THE WORK CAN BE DESCRIBED IN SUMMARY AS FOLLOWS:
THE MODIFICATION OF EXISTING CHECKED BAGGAGE INSPECTION AREAS TO ACCOMMODATE THE INSTALLATION OF ONE
(1) NEW CT-80 DR + EDS TO TC3 SCREENING LINE.
THERE WILL BE NO CHANGE IN USE CLASSIFICATION, OCCUPANCY, OR EGRESS DUE TO REVISIONS IN THIS PROJECT.
USE GROUP CLASSIFICATION: COVERED MALL (SECTION 402)
TYPE OF CONSTRUCTION: TYPE III-B (CHAPTER 6)
AREA LIMITATION: NOT LIMITED (SECTION 402.6)
HEIGHT LIMITATION: 3 STORIES (SECTION 402.6)
CODE ANALYSIS
APPLICABLE CODES
MINIMUM STANDARD CODES :
2019 OREGON STRUCTURAL SPECIALTY CODE (OSSC)
2019 OREGON MECHANICAL SPECIALTY CODE (OMSC)
2021 OREGON ELECTRICAL SPECIALTY CODE (OESC)
2021 OREGON PLUMBING SPECIALTY CODE (OPSC)
2021 OREGON ENERGY ENERGY EFFICIENCY SPECIALTY CODE (OEESC)
ADA: 2019 OSSC, CHAPTER 11: ACCESSIBILITY (ANSI A117.1)
OCCUPANCY CLASSIFICATION (IBC/LSC)
GROUP A2/ASSEMBLY: RESTAURANT
GROUP A3/ASSEMBLY: WAITING AREAS, CONFERENCE ROOMS, TABLE AND CHAIR SEATING
GROUP B/BUSINESS: OFFICE AREAS AND AIR TRAFFIC CONTROL TOWER (ATCT)
BUILDING DATA
TOTAL EXISTING GROSS BUILDING SQUARE FOOTAGE: 143,200 SF
LEVEL 1: 113,000 SF
LEVEL 2: 29,700 SF
NUMBER OF FLOORS: 2
HEIGHT OF BUILDING: 37'-8" OVERALL
SPRINKLERED: YES
CONSTRUCTION CLASSIFICATION (IBC)
PROJECT DESCRIPTION
AREA OF WORK
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
4582 S Ulster St., Suite 1100
Denver, CO 80237
303-409-9700
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /3
/2
:5
:3
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
A
R
.r vt
09/30/2021
GG
KS
2241872012
PROJECT
DEFINITIONS,
CODE INFO &
SHEET INDEX
G001
GG
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
SHEET INDEX
SHEET NUMBER SHEET NAME
N
PN
SCALE: 1" = 50'-0"
ARCHITECTURAL PROJECT DESCRIPTION
No. DESCRIPTION DATE
9/30/2021
B000 SYMBOLS, LEGENDS, ABBREVIATIONS & SHEET LIST
B001 CONVEYOR MANIFEST
B100 BHS - EXISTING LAYOUT
B101 COORDINATION LAYOUT
B200 BHS - PROPOSED LAYOUT
B400 BHS - SECTION VIEWS
B500 BHS - PROPOSED REMOVAL PATH
B501 BHS - TSA EGRESS PATH
B502 BHS - BAGGAGE INSPECTION STATION
B503 BHS - FAIL SAFE ZONE
B800 BHS - TYPICAL DETAILS
B801 BHS - TYPICAL DETAILS
B802 BHS - TYPICAL DETAILS
COVER SHEET
G001 PROJECT DEFINITIONS, CODE INFO & SHEET INDEX
G002 GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
E001 ELECTRICAL GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
EL111 FIRST FLOOR REFLECTED CEILING PLAN - AREA H
EP111 FIRST FLOOR ELECTRICAL POWER PLAN - AREA H
Grand total: 9.1
ARCHITECTURAL ABBREVIATIONS PLAN SYMBOLS
1-HOUR RATED WALL 2-HOUR RATED WALL
SMOKE RATED WALL
BATT INSULATION CONCRETE
EARTH EXPOSED & FINISHED WOOD TRIM
GYPSUM / PLASTER MASONRY - BRICK
PLYWOOD
RIGID INSULATION
STEEL
MATERIAL SYMBOLS
MASONRY - CONCRETE BLOCK
XX
View Name
SCALE:1/8" = 1'-0"
DOOR TAG
CALLOUT HEAD & REGION
A101
A1
SIM
BUILDING SECTION
KEYNOTE
BUILDING SECTION LEVEL HEAD
A1
A101
SIM
A1
A101
SIM
A1
A101
SIM
A1
A101
SIM
Name Elevation
ROOM TAG WALL TAG
XXX
DETAIL SECTION
WINDOW & STOREFRONT TAG
MATERIAL TAG
VIEW REFERENCE
REVISION TAG
NORTH ARROW
XX
A-101 A-101
ELEVATION - EXTERIOR ELEVATION - INTERIOR
WALL SECTION
CEILING TAG
GENERAL NOTES
1. ALL DIMENSIONS ARE IN FEET / INCHES UNLESS NOTED OTHERWISE.
2. THESE GENERAL NOTES ARE NOT INTENDED TO REPLACE SPECIFICATIONS - REFER TO SPECIFICATIONS FOR REQUIREMENTS IN ADDITION TO GENERAL NOTES.
3. THE TERMS RENOVATE AND REHABILITATE ARE USED INTERCHANGEABLY IN THESE DOCUMENTS.
4. ROOM AREAS AND PERIMETERS ARE APPROXIMATE AND FOR REFERENCE ONLY. VERIFY QUANTITIES AND DIMENSIONS IN FIELD.
5. NO DEVIATIONS FROM THESE CONTRACT DOCUMENTS SHALL BE MADE WITHOUT THE PRIOR WRITTEN APPROVAL OF THE ARCHITECT.
6. DO NOT SCALE DIMENSIONS FROM DRAWINGS - THE CONTRACTOR SHALL REQUEST NECESSARY DIMENSIONS NOT SHOWN ON THE DRAWINGS FROM THE ARCHITECT.
7. ALL DIMENSIONS ORIGINATE FROM EXISTING FACE OF WALLS & ARE TO FACE OF FRAMING AT NEW WORK OR CENTER OF DOORS, WINDOWS AND OPENINGS UNLESS NOTED OTHERWISE - ALL NON-DIMENSIONED DOOR LOCATIONS SHALL BE OFFSET 4" FROM THE ADJACENT WALL TO THE HINGE SIDE OF THE DOOR OPENING. ALL DOORS MUST BE INSTALLED TO MEET ALL APPLICABLE CODES, INCLUDING ADA.
8. DETAILS SHOWN ON DRAWINGS ARE TYPICAL FOR ALL SIMILAR CONDITIONS.
9. DRAWING NOTES AND SPECIFICATIONS ARE INSTRUCTIONS TO THE CONTRACTOR AND APPLY TO ALL THE WORK UNLESS MORE SPECIFIC INFORMATION IS SHOWN ELSEWHERE ON THE DRAWINGS OR WRITTEN IN THE SPECIFICATIONS - IN THE EVENT OF CONFLICTING INSTRUCTIONS, THE ARCHITECT SHALL DETERMINE WHAT CONTROLS THE CONTRACT DOCUMENTS ARE COMPLEMENTARY WHAT IS REQUIRED BY ONE SHALL BE REQUIRED BY
ALL.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR SCHEDULING AND COORDINATING THE WORK OF THE SUB-CONTRACTORS - THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH THE BUILDING OWNER, TENANT OR HIS REPRESENTATIVES THE DELIVERY AND INSTALLATION OF ITEMS BEING PROVIDED AND INSTALLED BY OTHERS.
11. ELECTRICAL WORK RELATED TO DEMOLITION AND NEW INSTALLATION OF COMPONENTS SHALL COMPLY WITH ALL APPLICABLE CODES.
12. ALL MATERIALS, FABRICATION AND INSTALLATION SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS AND SPECIFICATIONS FOR EACH DIVISION OF WORK.
13. CONSTRUCTION MUST COMPLY WITH APPLICABLE CODES AND ORDINANCES, LAWS AND SAFETY ORDERS AS DIRECTED BY LOCAL JURISDICTION.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR THE TIMELY ORDERING OF MATERIALS INCLUDED IN THESE CONTRACT DOCUMENTS - SOME ITEMS IN THESE DOCUMENTS MAY REQUIRE LONG LEAD TIMES OR SPECIAL COORDINATION. SUBSTITUTIONS WILL NOT BE ALLOWED FOR MATERIAL NOT ORDERED IN A TIMELY FASHION.
15. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS, (BOTH NEW AND EXISTING) REPORTING ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO ORDERING MATERIALS OR PROCEEDING WITH
ANY PHASE OF THE WORK.
16. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS PRIOR TO COMMENCING CONSTRUCTION - ALL DISCREPANCIES SHALL BE NOTED AND SENT TO THE ARCHITECT WITH ADEQUATE TIME TO REVIEW PRIOR TO STARTING
THAT PORTION OF THE WORK IN ORDER TO AVOID PROJECT DELAYS.
17. CONTRACTOR SHALL CLEAN, PATCH AND REPAIR ALL SURFACES DAMAGED BY DEMOLITION, ALTERATION OR INSTALLATION OF THE WORK.
18. CONTRACTOR SHALL PROVIDE ADDITIONAL FURRING (THE ENTIRE LENGTH OF THE WALL) TO FULLY CONCEAL ELECTRICAL OR IT ITEMS THAT PROJECT FROM THE FACE OF THE WALL OR PARTITION AND ARE NOT SPECIFICALLY
NOTED TO BE SURFACE MOUNTED.
19. CONTRACTOR TO PROVIDE PORTABLE FIRE EXTINGUISHERS IN ACCORDANCE WITH LOCAL JURISDICTION AND NFPA 10. MAXIMUM TRAVEL DISTANCE TO NEAREST FIRE EXTINGUISHER FROM ANY POINT IN THE BUILDING SHALL NOT EXCEED 75 FEET. EXISTING FIRE EXTINGUISHERS SHALL BE TESTED AND RE-USED IF FULLY OPERATIONAL. FIRE EXTINGUISHERS SHALL BE SIZED FOR NO LESS THAN ORDINARY HAZARD.
20. ALL REQUESTS FROM INFORMATION PROMPTED BY THE BUILDING OFFICIALS SHALL INCLUDE A COPY OF THE BUILDING OFFICIALS’ COMMENTS AND THE BUILDING INSPECTORS FIELD REPORT TO ENSURE AN ACCURATE AND
TIMELY RESPONSE.
21. CONTRACTOR AND SUBCONTRACTOR SHALL ALL BE LICENSED TO PERFORM THEIR REQUESTED DUTIES AS REQUIRED IN ACCORDANCE WITH LOCAL STANDARDS.
22. ALL EXISTING EQUIPMENT AND FINISHES THAT ARE SCHEDULED OR NOTED TO REMAIN WILL BE PROTECTED BY THE CONTRACTOR. PHOTOGRAPHS OF EXISTING CONDITIONS SHALL BE PROVIDED BY THE CONTRACTOR TO
DOCUMENT PRE-EXISTING DAMAGE & FINISH CONDITIONS.
23. THE CONTRACTOR SHALL COORDINATE ALL DEMO AND NEW WORK ACTIVITIES WITH THE AIRPORT PRIOR TO PROCEEDING. THE EXISTING TSA BAG SCREENING LINE, TC4 WILL REMAIN IN OPERATION DURING CONSTRUCTION WORK FOR THIS PROJECT, AND NEW CONSTRUCTION ACTIVITIES SHALL NOT IMPEDE CURRENT TSA OR AIRPORT OPERATIONS. COORDINATE ALL WORK ACTIVITIES WITH THE AIRPORT PRIOR TO THE COMMENCEMENT OF THE WORK TO MINIMIZE DISRUPTIONS TO TSA, AIRPORT OPERATIONS, AND TRAVELING PASSENGERS.
24. MOCK UPS (AS REQUIRED) SHALL BE CONSTRUCTED BY THE CONTRACTOR PRIOR TO BEGINNING DEMOLITION WORK.
25. DO NOT USE ESCALATORS OR STAIRS FOR MOVING EQUIPMENT AND OR MATERIALS UNLESS COORDINATED WITH AIRPORT FACILITIES/OPERATIONS. WHEN USING ELEVATOR, ELEVATOR WALL, SIDES AND CEILING MUST BE PROTECTED FROM DAMAGE, ALL DAMAGE IS THE RESPONSIBILITY OF GENERAL CONTRACTOR AND MUST BE CORRECTED PRIOR TO PROJECT COMPLETION.
26. THE CONTRACTOR IS TO PROTECT EXISTING FINISHES, AND MAKE REPAIRS TO THE EXISTING FINISHES AND FIRE PROOFING WHERE DAMAGED AS PART OF THE NEW WORK ASSOCIATED WITH THIS PROJECT.
27. WHERE MATERIALS ARE APPLIED TO, OR ARE IN DIRECT CONTACT WITH WORK INSTALLED BY ANOTHER SUBCONTRACTOR, COMMENCEMENT OF WORK IMPLIES ACCEPTANCE OF THE SUBSTRATE AS SUITABLE FOR THE
APPLICATION INTENDED.
A. ISOLATE DISSIMILAR METALS TO PREVENT GALVANIC CORROSION.
28. OPENINGS IN RATED WALL, FLOOR, CEILING AND ROOF ASSEMBLIES SHALL BE SEALED WITH PENETRATION SEALANT SYSTEMS MEETING OR EXCEEDING THE REQUIRED FIRE RESISTIVE RATINGS.
29. MAINTAIN THE FIRE RATING OF CONSTRUCTION AROUND CABINETS, PANELS, AND BOXES RECESSED IN FIRE RATED WALL, FLOOR, AND CEILING ASSEMBLIES.
30. PROVIDE CONTINUOUS PERIMETER FIRE SAFING BETWEEN FLOORS AND COORDINATE THE INSTALLATION WITH THE EXTERIOR WALL. FIRE RATING OF SAFING SHALL MATCH FIRE RATING OF FLOOR CONSTRUCTION.
31. FIELD MEASURE AND CONFIRM DIMENSIONS FOR OWNER PROVIDED EQUIPMENT AND FURNISHINGS.
32. PROVIDE STIFFENERS, BRACING, BACKING PLATES AND BLOCKING REQUIRED FOR SECURE INSTALLATION OF MISCELLANEOUS EQUIPMENT, AND SUSPENDED ELECTRICAL EQUIPMENT.
33. DO NOT OBSTRUCT ACCESS TO EXISTING EXITS, OR REDUCE THE WIDTH OF PUBLIC CORRIDORS.
34. PENETRATIONS IN THE EXTERIOR BUILDING WALL ARE NOT ALLOWED, INCLUDING THOSE REQUIRED FOR OUTLETS AND BLOCKING.
35. FINISH FLOOR ELEVATIONS ARE TO TOP OF CONCRETE UNLESS OTHERWISE NOTED.
36. GANG MULTIPLE SWITCHES TOGETHER INTO ONE BOX WITH A SINGLE COVER PLATE WHENEVER POSSIBLE. MULTIPLE SWITCHES, WHICH CANNOT BE GANGED TOGETHER IN THE SAME BOX, SHALL BE LOCATED CLOSE
TOGETHER AS POSSIBLE AND MOUNTED AT THE SAME HEIGHT.
37. WALL OUTLETS SHALL BE INSTALLED AT 18" AFF UNLESS OTHERWISE NOTED. INSTALL SWITCH PLATES AT 42" AFF UNLESS OTHERWISE NOTED.
38. DO NOT INSTALL OUTLET OR J-BOXES BACK-TO-BACK ON OPPOSITE SIDES OF THE WALL. BOXES MUST BE SEPARATED BY A STUD.
39. SPECIAL INSPECTION REQUIRED FOR POST-INSTALLED CONCRETE ANCHORS PER OSSC, SECTION 1705.1.1)
XXXX 12'-0" AFF
CEILING TYPE
CEILING HEIGHT
*NOTE - REFER TO PARTITION TYPE SHEET FOR INFO ON TAG
PT-1
A1 1A11
FURNITURE & EQUIPMENT TAG TOILET ACCESSORY TAG
1i 1i
TILE / CARPET
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
4582 S Ulster St., Suite 1100
Denver, CO 80237
303-409-9700
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /1
/2
:1
:3
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
A
R
.r vt
09/30/2021
GG
KS
2241872012
GENERAL NOTES,
ABBREVIATIONS
AND SYMBOLS
G002
GG
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
LB. POUND
LDG. LANDING
LONG. LONGITUDINAL
LRV. LOUVER
LT. LIGHT
LTG. LIGHTING
LVP LUXURY VINYL PLANK
LVT LUXURY VINYL TILE
M.O. MASONRY OPENING
MATL. MATERIAL
MAX. MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, & PLUMBING
MFGR. MANUFACTURER
MGR. MANAGER
MIN. MINIMUM
MOD MODIFIED
MSC. MISCELLANEOUS
MTL METAL
MUFID MULTI-USER FLIGHT INFORMATION DISPLAY
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
N/A NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NO. NUMBER
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
OFCI OWNER FUNISHED CONTRACTOR INSTALLED
OPG OPENING
OPP. OPPOSITE
OSHA OCCUPATIONAL SAFETY AND HEALTH ACT
OVHD OVERHEAD
P.LAM. PLASTIC LAMINATE
PBB PASSENGER BOARDING BRIDGE
PBB PASSENGER BOARDING BRIDGE
PDU POWER DISTRIBUTION UNIT
PLYWD. PLYWOOD
PNL. PANEL
PR. PAIR
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PRESSURE TREATED
PVC POLYVINYL CHLORIDE
Q.T. QUARRY TILE
R RADIUS
R.A.F. RAISED ACCESS FLOOR
R.A.G. RETURN AIR GRILLE
R.D. ROOF DRAIN
R.O. ROUGH OPENING
RB RUBBER BASE
RECEP. RECEPTION, RECEPTIONIST
REF. REINFORCING, REINFORCEMENT
REQ'D. REQUIRED
REV. REVISED, REVISION
S.F. SQUARE FEET
S.G.P. SEMI-GLOSS PAINT
S.S. SERVICE SINK
SC SEALED CONCRETE
SCHED. SCHEDULE
SCW. SOLID CORE WOOD
SECT. SECTION
SFRM SPRAYED FIRE RESISTIVE MATERIAL
SHT. SHEET
SHTS. SHEETS
SIM. SIMILAR
SPECS. SPECIFICATIONS
SQ. SQUARE
SQ. IN. SQUARE INCHES
STC SOUND TRANSMISSION CLASS
STD. STANDARD
STL. STEEL
STOR. STORAGE
STRUCT STRUCTURAL, STRUCTURE
SUSP. SUSPENDED
T&G TONGUE & GROOVE
T.O. STL. TOP OF STEEL
T.O.B. TOP OF BRICK, TOP OF BEAM
T.O.S. TOP OF STEEL, TOP OF SLAB
T.O.SH. TOP OF SHEATHING
T.O.W. TOP OF WALL
TEL. TELEPHONE
TG TEMPERED GLASS
TYP. TYPICAL
U.L. UNDERWRITERS LABORATORIES
U.O.N. UNLESS OTHERWISE NOTED
VB VAPOR BARRIER
VCT OR VT VINYL COMPOSITION TILE
VDC VIRTUAL DESIGN & CONSTRUCTION
VERT. VERTICAL
VR VIRTUAL REALITY
W.C. WATER CLOSET
W/ WITH
WCO WALL CLEANOUT
WD WOOD
WMP WIRE MESH PARTITION
WWF WELDED WIRE FABRIC
YD. YARD
Ø DIAMETER
& AND
@ AT
A.B. ANCHOR BOLT
A.F.S. ABOVE FLOOR SLAB
A.W.I. ARCHITECTURAL WOODWORK INSTITUTE
A/C AIR CONDITIONER
ACT ACOUSTICAL CEILING TILE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
ANOD. ANODIZED
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX. APPROXIMATE OR APPROXIMATELY
ARCH ARCHITECTURE, ARCHITECTURAL
AVG AVERAGE
B.H.M.I. BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION, INC.
B.O. BOTTOM OF
B.U.R. BUILT-UP ROOFING
BHS BAGGAGE HANDLING SYSTEM
BID BAGGAGE INFORMATION DISPLAY
BIM BUILDING INFORMATION MODELING
BLDG. BUILDING
BM. BEAM
C.J. CONTROL JOINT
CBIS CHECKED BAGGAGE INSPECTION STATION
CFMF COLD FORMED METAL FRAMING
CL CENTERLINE
CL O.T.S. CENTERLINE OF TENANT SEPARATION
CLG. CEILING
CLO. CLOSET
CLR. CLEAR
CMU CONCRETE MASONRY UNIT
COL. COLUMN
COLS. COLUMNS
CONC. CONCRETE
CONT. CONTINUOUS
D.S. DOWNSPOUT
DIA. DIAMETER
DR. DOOR
DTL. OR DET. DETAIL
DWG. DRAWING
E.F.S. EXTERIOR FACE OF SHEATHING
E.J. EXPANSION JOINT
E.O.S. EDGE OF SLAB
E.P. ELECTRICAL PANEL
E.R.D. EMERGENCY ROOF DRAIN
E.T.D. ESTIMATED TRAVEL DISTANCE
E.W.C. ELECTRIC WATER COOLER
EA. EACH
ELEC. ELECTRIC, ELECTRICAL
ELEV. ELEVATION
ENG. ENGINEER, ENGINEERING
EPDM ethylene propylene diene monomer
EQ. EQUAL
EQUIP. EQUIPMENT
EXIST. EXISTING
EXP. EXPANSION, EXPOSED
EXT. EXTERIOR
F.D. FIRE DAMPER, FLOOR DRAIN
F.F. FINISHED FLOOR
F.F.E. FINISHED FLOOR ELEVATION
F.O. FACE OF
F.O.B. FACE OF BRICK
F.O.P. FACE OF POST
F.V. FIELD VERIFY
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FID FLIGHT INFORMATION DISPLAY
FIN. FINISH, FINISHED
FLR. FLOOR
FRP FIBER REINFORCED PANEL
FT. FEET
FTG. FOOTING
G.P. GLOSSY PAINT
GA. GAUGE
GALV. GALVANIZED
GBF GYPSUM BOARD FURRING
GID GATE INFORMATION DISPLAY
GL. GLASS
GWB GYPSUM WALL BOARD
GYP. GYPSUM
HB HOSE BIB
HDW HARDWARE
HGT. OR HT. HEIGHT
HKS HOOKS
HM HOLLOW METAL
HORIZ. HORIZONTAL
HVAC HEATING VENTILATION & AIR CONDITIONING
I.D. INSIDE DIAMETER
i.e. THAT IS, SUCH AS
I.F.S. INTERIOR FACE OF STUD
IN. INCH, INCHES
INSUL. INSULATION
INT. INTERIOR
JAN. JANITOR
JST. JOIST
JT. JOINT
K.P. KICK PLATE
LAM. LAMINATE
LAV. LAVATORY
1. PROVIDE AND INSTALL A RAISED WORK PLATFORM SIMILAR TO WHAT WAS PREVIOUSLY INSTALLED AT THE ADJACENT TC5 LINE, SHOWN IN THE ATTACHED IMAGE ON THIS DRAWING. THIS SELF-SUPPORTED PLATFORM IS A FREE-STANDING UNIT WITH NO REQUIRED ATTACHMENTS TO ANY BUILDING ELEMENT. THE DESIGN INTENT IS TO PROVIDE A SAFE WALKWAY THAT IS FREE OF TRIPPING HAZARDS, SUCH AS CONDUIT OR CABLING FOR TSA PERSONNEL TO ACCESS THE
EDS, CT-80 DR+ MACHINE.
PROVIDE AND INSTALL ONE (1) EACH 97" X 24" GLOBAL INDUSTRIAL MODEL NO. WLOS597242. VERIFY FIELD DIMENSIONS AND COORDINATE WITH BHS EQUIPMENT AND ELECTRICAL COMPONENTS. A LINK TO THE BASIS OF DESIGN EQUIPMENT IS
BELOW.
HTTPS://WWW.GLOBALINDUSTRIAL.COM/P/97-X-24-ADJUSTABLE-HEIGHT-5-8-STEEL-WORK-PLATFORM
REFERENCE BHS DRAWING SHEET B501 FOR PLAN LOCATION
WORK NOTE:
No. DESCRIPTION DATE
WORK PLATFORM(S) INSTALLED AT
ADJACENT TC5 SCREENING LINE
9/30/2021
ELECTRICAL ABBREVIATIONS GENERAL NOTESELECTRICAL SYMBOLS
1. ALL ELECTRICAL WORK SHALL COMPLY WITH NATIONAL ELECTRICAL CODE, NFPA 70, THE NATIONAL FIRE CODES, THE AMERICANS WITH DISABILITIES ACT, AND OTHER BUILDING CODES AS APPLICABLE FOR THE SITE.
2. THE CONTRACTOR SHALL THOROUGHLY REVIEW THE PROJECT TO ENSURE THAT ALL WORK SHALL MEET OR EXCEED THE ABOVE REQUIREMENTS. ANY ALLEGED DISCREPANCIES SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION.
3. THE CONTRACTOR IS DIRECTED TO OBTAIN COPIES OF ALL RELATED PLANS, SPECIFICATIONS, SHOP DRAWINGS AND
ADDENDA TO COORDINATE THE RELATED WORK AND SCHEDULING.
4. THE ELECTRICAL SERVICE TO AND FOR EQUIPMENT IS BASED ON EQUIPMENT DESIGN DATA. THE ACTUAL VALUES MAY DIFFER DEPENDING UPON THE EQUIPMENT TO BE FURNISHED. ANY MODIFICATION TO THE ELECTRICAL INSTALLATION, BASED UPON ACTUAL EQUIPMENT SELECTION, SHALL RESULT IN NO ADDITIONAL COST TO THE OWNER.
5.
6. THE CONTRACTOR SHALL THOROUGHLY FAMILIARIZE HIMSELF/HERSELF WITH THE WORK TO BE PERFORMED BY OTHER TRADES AND THE PHYSICAL CHARACTERISTICS OF THE STRUCTURE IN ORDER TO SCHEDULE AND INSTALL EQUIPMENT AND TO MINIMIZE POSSIBLE INTERFERENCE. FAILURE TO PROPERLY COMMUNICATE AND SCHEDULE WORK WITH OTHER TRADES THAT RESULTS IN ADDITIONAL WORK AND MATERIAL, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE MODIFICATIONS REQUIRED TO RESOLVE THE CONFLICT SHALL BE DECIDED BY THE ENGINEER.
7. ALL PANELBOARDS MODIFIED AS A RESULT OF WORK PERFORMED SHALL BE FURNISHED AND INSTALLED WITH A TYPEWRITTEN SCHEDULE SHOWING CIRCUIT NUMBERS AND A COMPLETE DESCRIPTION OF EACH CIRCUIT, INCLUDING
OFFICIAL ROOM NUMBER.
8. ALL LIGHT SWITCHES AND DUPLEX RECEPTACLES SHALL BE RATED FOR 20 AMPERES AT 120/277 VOLTS AC. WIRING
DEVICES SHALL BE SPECIFICATION GRADE.
9. THE LUMINAIRE SCHEDULE IS FOR REFERENCE ONLY. MODEL NUMBERS LISTED MAY NOT INCLUDE ALL REQUIRED OPTIONS, HOWEVER, THESE OPTIONS SHALL BE FURNISH AND INSTALLED WITH THE LUMINAIRES. ALL SUBSTITUTIONS
ARE SUBJECT TO PRIOR APPROVAL AS EQUAL BY THE ENGINEER OF RECORD.
10. ALL EXIT LIGHTS, INCLUDING LIGHTS REQUIRING RELOCATION AS A RESULT OF THIS PROJECT, SHALL BE FURNISH AND INSTALLED WITH UNIVERSAL MOUNTING BRACKETS. THE CONTRACTOR SHALL VERIFY ALL DIRECTIONAL ARROWS WITH
ARCHITECTURAL EGRESS PLANS PRIOR TO ORDERING LUMINAIRES.
11. ALL RECESSED LUMINAIRES IN FIRE RATED CEILINGS SHALL BE TENTED TO COMPLY WITH THE APPLICABLE CEILING
RATING. THE CONTRACTOR SHALL VERIFY REQUIREMENTS.
12. ALL COMMUNICATIONS OUTLET BOXES SHALL BE MIN. 4" WIDE BY 4" HIGH BY 2 1/2" DEEP WITH SINGLE GANG MUD RING.
13. FURNISH AND INSTALL 1" C FROM COMMUNICATIONS OUTLET TO THE ACCESSIBLE CEILING SPACE, UON. CONTRACTOR SHALL FURNISH AND INSTALL CABLING AS REQUIRED. CABLE ROUTING WILL BE VIA CONDUIT (INACCESSIBLE SPACES) OR 'J' HOOKS AND CABLE TRAY SYSTEM (ACCESSIBLE SPACES) TO COMMUNICATION ROOM OR ROOM OF TERMINATION.
FURNISH AND INSTALL RACEWAY SYSTEM OVER THE INACCESSIBLE CEILING SPACE AS INDICATED ON PLANS.
COMMUNICATION CONDUITS ARE TO BE LONG RADIUS TYPE AND SHALL CONTAIN PULL STRINGS. FURNISH AND INSTALL
PLATES FOR ALL OUTLETS. CAT6 CABLES SHALL BE PLENUM RATED.
14. ALL SPECIAL PURPOSE OUTLETS SHALL BE FURNISHED AND INSTALLED TO MATCH EQUIPMENT TO BE SUPPLIED.
15. ALL CONDUITS SHALL INCLUDE A SEPARATE GREEN EQUIPMENT GROUNDING CONDUCTOR.
16. ANY EXISTING UTILITIES LOCATED IN THE AREA OF CONSTRUCTION THAT REQUIRE RELOCATION OR TIE-IN SHALL BE
COORDINATED WITH THE OWNER'S REPRESENTATIVE. PROVIDE 72 HOUR ADVANCE NOTICE.
17. ALL DISCONNECT SWITCHES SHALL BE THE HEAVY DUTY TYPE, FUSED DISCONNECTS SHALL HAVE LITTLEFUSE TIME DELAY, CLASS RK5 AND INDICATING CLASS RK5, OR AS REQUIRED PER EQUIPMENT MANUFACURER DATA SHEETS.
18. ALL EMPTY CONDUITS SHALL CONTAIN JET LINE #232 POLYOLEFIN 200 LB. TEST PULL STRING.
19. ALL WORK SHOWN ON THE ELECTRICAL PLANS SHALL BE PERFORMED BY THE CONTRACTOR, UON.
20. ALL EXIT FIXTURES SHALL BE CONNECTED TO THE BUILDING LIFE SAFETY PANEL AND/OR HAVE INTEGRAL EMERGENCY
BATTERY.
21. ALL SURGE PROTECTED OUTLETS SHALL BE EQUAL TO HUBBELL #5352.
22. EQUIPMENT INSTALLED WITHIN CONCEALED SPACES SHALL HAVE REASONABLE ACCESS PANELS FURNISH AND INSTALLED NEARBY FOR INSPECTION, TESTING, AND SERVICE CONSIDERATIONS. LOCATION OF ACCESS PANELS PER
APPROVAL OF ARCHITECT.
23. THE CONTRACTOR SHALL VERIFY CEILING TYPES AND INSTALLATION REQUIREMENTS PRIOR TO ORDERING LUMINAIRES.
24. WHERE CABLES OR CONDUITS ARE REQUIRED TO PASS THROUGH A FIRE RATED WALL, FLOOR, OR CEILING THEY SHALL BE SEALED WITH FIRESTOP. THE APPROVED FIRESTOP METHOD SHALL COMPLY WITH ARTICLES 300.21 OF NEC AND SHALL BE UL LISTED UNDER "THROUGH-PENETRATION FIRESTOP SYSTEM (XHEZ)" IN UL FIRE RESISTANCE DIRECTORY.
ALL UNSPRINKLERED FACILITES SHALL BE CONSIDERED TO HAVE INTERIOR CORRIDORS WITH FIRE RATED WALLS, UNO.
ANY PENETRATION THROUGH THESE WALLS AND OTHER FIRE RATED WALLS SHALL BE SEALED WITH FIRESTOP.
FURNISH AND INSTALL MINIMUM 1" EMT THROUGH WALL PENETRATIONS.
25. CONDUITS, WIREWAYS, AND CABLE TRAYS SHALL BE SUPPORTED FROM BUILDING STRUCTURE AND NOT FROM OTHER
PIPES, DUCTS, OR EXISTING RACKS, UON.
26. EXTERIOR BURIED CONDUIT RUNS SHALL BE MINIMUM 24" BELOW FINISHED GRADE. FURNISH AND INSTALL CAUTION TAPE 12" BELOW GRADE. FURNISH AND INSTALL (1) SPARE WITH EACH UNDERGROUND RUN. DUCTBANKS SHALL BE CONCRETE ENCASED WITH LOCATION PLAQUES PLACED EVERY 50' AND BEFORE AND AFTER EVERY TURN, UON.
SUBMIT SHOP DRAWINGS BEFORE DIGGING.
27. FURNISH AND INSTALL GROUND STRAP ACROSS ALL CABLE TRAY JOINTS. GROUND CABLE TRAY TO SERVICE GROUND
WITH #1/0 AWG BARE COPPER.
28. ALL CONDUIT BENDS FOR COMMUNICATIONS WIRING SHALL BE SMOOTH LONG RADIUS TYPE. "LB" TYPE FITTINGS SHALL
NOT BE USED FOR FOR COMMUNICATION RACEWAY.
29. DO NOT LOCATE ELECTRICAL OUTLETS AND DEVICES ON WALL PANEL JOINTS. FIELD VERIFY FOR WALL PANEL LAYOUT
AND PANEL JOINT LOCATIONS.
30. CONTRACTOR SHALL FURNISH AND INSTALL A SEPARATE NEUTRAL FOR EACH PHASE CONDUCTOR OF SINGLE POLE BRANCH CIRCUITS THAT SERVE HIGH HARMONIC LOADS, SUCH AS, BALLAST OR SWITCH MODE POWER SUPPLIES (I.E.
PERSONAL COMPUTERS AND SERVERS).
31. RACEWAYS INSTALLED IN OUTDOOR LOCATIONS SHALL BE HOT DIPPED GALVINIZED, AT MINIMUM, FOR CORROSION RESISTANCE. FOR HIGHLY CORROSIVE ENVIRONMENTS, SUCH AS COASTAL AREAS, ALUMINUM, STAINLESS STEEL, OR
PVC COATED RACEWAYS SHALL BE REQUIRED.
32. POWER CHANGE EXPENSES RESULTING FROM EQUIPMENT SUBSTITUTIONS THAT DIFFER FROM ITEMS CALLED FOR IN DRAWINGS OR SPECIFICATIONS SHALL BE BORNE BY THE CONTRACTOR OR THEIR SUB. THESE SHALL INCLUDE CHANGES IN VOLTAGE OR FULL LOAD AMPS RESULTING IN LARGER FEEDERS AND OR CIRCUIT BREAKERS.
33. COORDINATE FINAL ELECTRICAL DEVICE AND LUMINAIRE LOCATIONS WITH FINAL SPRINKLER HEAD LOCATIONS TO
COMPLY WITH NFPA REQUIREMENTS.
34. ALL EXISTING ELECTRICAL DEVICES THAT ARE NOT SHOWN ARE EXISTING TO REMAIN, UON.
35. COORDINATE DISCONNECT REQUIREMENTS WITH EQUIPMENT FOR THE SCOPE OF PROJECT. CONTRACTOR SHALL FURNISH AND INSTALL DISCONNECTS FOR THOSE DEVICES THAT DO NOT COME WITH FACTORY INSTALLED
DISCONNECTS.
36. BEFORE INITIATING ANY UNDERGROUND WORK, CONTRACTOR MUST LOCATE ALL UTILITIES.
37. INTERIOR FIRE ALARM CONDUCTORS SHALL BE INSTALLED IN RED EMT CONDUIT. EXTERIOR FIRE ALARM CONDUIT
SHALL BE RED RMC CONDUIT.
LIGHTING SYMBOLS
GENERAL NOTE: UPPER CASE LETTER INDICATES LUMINAIRE TYPE, SEE LUMINAIRE SCHEDULE. LOWER
CASE LETTER INDICATES SWITCH CIRCUIT.
POWER SYSTEMS
RECESSED LUMINAIRE WITH OUTLET
RECESSED EMERGENCY OR NIGHTLIGHT LUMINAIRE WITH OUTLET
RECESSED OR SURFACE STANDBY LUMINAIRE WITH OUTLET
SURFACE LUMINAIRE WITH OUTLET
SURFACE EMERGENCY OR NIGHTLIGHT LUMINAIRE WITH OUTLET
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
4582 S Ulster St., Suite 1100
Denver, CO 80237
303-409-9700
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /1
/2
:4
:4
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
E
R
.r vt
09/30/2021
CJB
2241872012
ELECTRICAL
GENERAL NOTES,
SYMBOLS, AND
ABBREVIATIONS
E001
TSK
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
SCCR SHORT CIRCUIT CURRENT RATING
SCHWP SECONDARY CHILLED WATER PUMP
SD SUB-DISTRIBUTION CABINET
SE SOUTH ENTRANCE
SEC SECURITY
SEGB SERVICE ENTRANCE GROUND BAR
SF SUPPLY FAN
SHWP SECONDARY HOT WATER PUMP
SIM SIMILAR
SLC SIGNAL LINE CIRCUIT
SN SOLID NEUTRAL
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE SINGLE THROW
SQ SQUARE
SS STAINLESS STEEL
SSF SIDE STREAM FILTER
ST SHUNT TRIP COIL
STC SECURITY TERMINAL CABINET
STR STARTER
STS STAINLESS STEEL
STS STATIC TRANSFER SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
T TRANSFORMER
TB TELEPHONE BACKBOARD
TE THERMAL ELEMENT
TEFC TOTALLY ENCLOSED FAN COOLED
TEL TELEPHONE
TGB TELECOMMUNICATIONS
GROUNDING BUS BAR
TMGB TELECOMMUNICATIONS MAIN
GROUNDING BUS BAR
TR TAMPER RESISTANT
TS TAMPER SWITCH
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UDS UTILITY DISTRIBUTION SYSTEM
UG UNDERGROUND
UGC UNDERGROUND COMMUNICATIONS
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UNSW UNSWITCHED
UON UNLESS OTHERWISE NOTED
UT UTILITY
UTR UP THROUGH ROOF
V VOLTS
VAV VARIABLE AIR VOLUME (HVAC)
VFD VARIABLE FREQUENCY DRIVE
VFI VACUUM FAULT INTERRUPTER
VT VOLTAGE TRANSFORMER
W WIRE
W WALL MOUNTED
W WATTS
W WEST
WP WEATHERPROOF
WR WEATHER-RESISTANT
Y WYE (CONNECTED)
Z ZONE
Z IMPEDANCE
FAPS FIRE ALARM POWER SUPPLY
FATC FIRE ALARM TERMINAL CABINET
FCU FAN COIL UNIT
FID FLIGHT INFORMATION DISPLAY
FLA FULL LOAD AMPS
FLR FLOOR
FO FIBER OPTIC
FPB FAN POWERED TERMINAL BOX
FPU FAN POWERED TERMINAL UNIT
FS FLOW SWITCH
FSPC FLUSH/FAUCET SENSOR POWER
CONVERTER
FTU FAN POWERED VAV TERMINAL UNIT
G GROUND
GC GENERAL CONTRACTOR
GDF GAS DUCT FURNACE
GF GROUND FAULT
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GFP GROUND FAULT PROTECTION
GID GATE INFORMATION DISPLAY
GPU GROUND POWER UNIT
GR GROUND ROD
GRC GALVANIZED RIGID CONDUIT
GUH GAS UNIT HEATER
GWH GAS WATER HEATER
HB HIGH BAY
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HP HORSE POWER
HVAC HEATING, VENTILATING & AIR
CONDITIONING
IC INTERCOM
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
ITC INTERCOM TERMINAL CABINET
J JUNCTION
JB JUNCTION BOX
KAIC (THOUSAND) AMPERE
INTERRUPTING CAPACITY
Kcmil THOUSANDS OF CIRCULAR MILS
KO KNOCK OUT
KVA KILOVOLT-AMPERES
KW KILOWATT
LBS LOAD BREAK SWITCH
LC LIGHTING CONTACTOR
LED LIGHT EMITTING DIODE
LSI LONG TIME, SHORT TIME,
INSTANTANEOUS
LSIG LONG TIME, SHORT TIME,
INSTANTANEOUS, GROUND FAULT
LT LIGHT
LTG LIGHTING
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MNS MASS NOTIFICATION SYSTEM
MTD MOUNTED
MTS MANUAL TRANSFER SWITCH
MUFID MULTI-USER FLIGHT INFORMATION
DISPLAY
N NEUTRAL
N NORTH
N/A NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CIRCUIT
NE NORTH ENTRANCE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOC
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NUMBER
NTS NOT TO SCALE
O.C. ON CENTER
OAE OR APPROVED EQUAL
OAHU OUTSIDE AIR HANDLING UNIT
OH OVERHEAD
OS OCCUPANCY SENSOR
P PHASE
PBB PASSENGER BOARDING BRIDGE
PBX PRIVATE BRANCH EXCHANGE
PCHWP PRIMARY CHILLED WATER PUMP
PIV POST INDICATOR VALVE
PNEU PNEUMATIC
PNL PANELBOARD
PNL PANEL
POE POWER OVER ETHERNET
PP POWER PANEL
PS PRESSURE SWITCH
PT POTENTIAL TRANSFORMER
PVC POLYVINYLCHLORIDE
RAF RETURN AIR FAN
RECP RECEPTACLE
REF REFRIGERATOR
RGS RIGID GALVANIZED STEEL
RM ROOM
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
S SOUTH
SCADA SUPERVISORY CONTROL AND DATA
ACQUISITION
A AMPERES
A/C AIR CONDITIONING
AC ABOVE COUNTER
AC AIR COMPRESSOR
ACCU AIR COOLED CONDENSER UNIT
ACT ACOUSTIC CEILING TILE
ACU AIR CONDITIONING UNIT
ADA AMERICANS WITH DISABILITIES ACT
ADAAG AMERICANS WITH DISABILITIES ACT
ACCESSIBILITY GUIDELINES
AF AMP FUSE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFD ADJUSTABLE FREQUENCY DRIVE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CURRENT
AIR AMPERE INTERUPTING RATING
AL ALUMINUM
AMP AMPERE
AMS ACCESS MANAGEMENT SYSTEM
AP ACCESS PANEL
APU AUXILIARY POWER UNIT
AT/FP ANTITERRORISM/FORCE
PROTECTION
ATR ALL THREADED ROD
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BCW BARE COPPER WIRE
BDCT BUILDING DESIGN AND
CONSTRUCTION TEAM
BFG BELOW FINISHED GRADE
BHS BAGGAGE HANDLING SYSTEM
BID BAGGAGE INFORMATION DISPLAY
BTS BEAM TRANSPORT SYSTEM
C CONDUIT
CAT6 CATEGORY 6 ETHERNET CABLE
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CC CRANE CONTROL
CCP CONCRETE CAMERA POLE
CCTV CLOSED CIRCUIT TELEVISION
CE COMMUNICATIONS ENCLOSURE
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CFL COMPACT FLUORESCENT
CH CHILLER
CKT CIRCUIT
CLP CONCRETE LIGHT POLE
CMH COMMUNICATIONS MANHOLE
CMU CONCRETE MASONRY UNIT
CNTRL CONTROLLER
CO CONDUIT ONLY
COMM COMMUNICATION
CONC CONCRETE
CP CONSOLIDATION POINT
CR CARD READER
CRU COMPUTER ROOM UNIT
CT COOLING TOWER
CT CURRENT TRANSFORMER
CTWP COOLING TOWER WATER PUMP
CU COPPER
CUB CENTRAL UTILITIES BUILDING
DACT DIGITAL ALARM COMMUNICATOR
TRANSMITTER
DAS DISTRIBUTED ANTENNA SYSTEM
DC DIRECT CURRENT
DCU DUCTLESS SPLIT AIR CONDITIONING
OUTDOOR UNIT
DDC DIRECT DIGITAL CONTROL PANEL
DH DOOR HOLDER
DHZ DAYLIGHT HARVESTING ZONE
DISC DISCONNECT
DTCO DOUBLE THROW CENTER OFF
DWG DRAWING
E EXISTING
E EAST
EC ELECTRICAL CONTRACTOR
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EL ELEVATION
EL EMERGENCY LIGHT
ELEC ELECTRIC/ELECTRICAL
EM EMERGENCY
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
EMH ELECTRICAL MANHOLE
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EOR ENGINEER OF RECORD
EPO EMERGENCY POWER-OFF
EQ EQUAL
ER EXISTING TO BE REMOVED
ERU ENERGY RECOVERY UNIT
ESS ENERGY SELECTION SYSTEM
ETSP ELECTRONIC TRAP SEAL PRIMER
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING TO REMAIN
EXR EXISTING TO BE RELOCATED
F/P FAX / PRINTER
FA FIRE ALARM
FAAA FIRE ALARM AUDIO AMPLIFIER
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAGA FIRE ALARM GRAPHIC
ANNUNCIATOR
FAIC FIRE ALARM INTERFACE CABINET
No. DESCRIPTION DATE
TSK
THE CONTRACTOR SHALL THOROUGHLY REVIEW THE PROJECT REQUIREMENTS TO ASSURE THAT ELECTRICAL SERVICE FOR ALL ITEMS AND/OR EQUIPMENT REQUIRING ELECTRICAL SERVICE IS INCLUDED. ANY ITEM AND/OR EQUIPMENT NOT FURNISH AND INSTALLED WITH ELECTRICAL SERVICE, REQUIRING ELECTRICAL SERVICE, SHALL BE
BROUGHT TO THE ENGINEER'S ATTENTION.
GENERAL NOTES
A. LUMINARE LOCATIONS ARE APPROXIMATE.
4N4N
5N5N
6N6N
7N7N
8N8N
9N9N
10N10N
11N11N
D
D
D.5
D.5
E
E
F
F
G
G
H
H
D.8
D.8
D.4
D.4
C
C
TSA SCREENING
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
4582 S Ulster St., Suite 1100
Denver, CO 80237
303-409-9700
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /1
/2
:4
:4
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
E
R
.r vt
09/30/2021
CJB
2241872012
FIRST FLOOR
REFLECTED
CEILING PLAN −
AREA H
EL111
TSK
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
N
PN
SCALE: 3/32" = 1'-0"
A1
FIRST FLOOR REFLECTED CEILING PLAN - AREA H
KEYNOTES
1 REPLACE EXISTING LUMINARES WITH LED LUMINAIRES.
No. DESCRIPTION DATE
TSK
GENERAL NOTES
A. MEZZANINE ELECTRICAL ROOM LOCATION IS LOCATED IN THE GENERAL AREA ABOVE THE NEW
INSTALLATION AREA. ELECTRICAL CONTRACTOR SHALL VERIFY LOCATION AND INSTALLATION
CONSIDERATIONS REQUIRED FOR SCOPE OF THIS INSTALLATION.
4N4N
5N5N
6N6N
7N7N
8N8N
9N9N
10N10N
11N11N
D
D
D.5
D.5
E
E
F
F
G
G
H
H
D.8
D.8
D.4
D.4
C
C
TSA SCREENING
1 2 3 4
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
4582 S Ulster St., Suite 1100
Denver, CO 80237
303-409-9700
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /1
/2
:4
:4
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
E
R
.r vt
09/30/2021
CJB
2241872012
FIRST FLOOR
ELECTRICAL
POWER PLAN −
AREA H
EP111
TSK
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
N
PN
SCALE: 3/32" = 1'-0"
A1
FIRST FLOOR ELECTRICAL POWER PLAN - AREA H
KEYNOTES
1 REMOVE CIRCUIT AND RACEWAY WHICH ARE IN PLACE FOR EXPLOSIVE DETECTION
SYSTEM (EDS) AND CHECKED BAGGAGE INSPECTION SYSTEM (CBIS) INSTALLATION.
2 FURNISH AND INSTALL NEW 30 AMP CIRCUIT INCLUDING RACEWAY, WIRING, 2-POLE 30
AMP 208VAC CIRCUIT BREAKER, AND ANY OTHER MATERIAL REQUIRED FROM PANEL
NPX-1 TO THE EDS AND CBIS.
3 PERFORM 30 DAY LOAD STUDY ON NPX-1
4 CONTRACTOR SHALL FURNISH AND INSTALL FIBER OPTIC CONNECTION FROM EXISTING
COMMUNICATIONS JUNCTION BOX LOCATED ON THE OPPOSITE WALL OF THE PROJECT
AREA FOR INSTALLATION OF EDS.
TSK
CHECK AND FIELD VERIFY ALL BHS RELATED DIMENSIONS ON THE JOB SITE
BEFORE PROCEEDING WITH WORK AND BE RESPONSIBLE FOR THEIR ACCURACY.
IF DISCREPANCIES ARE FOUND BETWEEN THE BHS DRAWINGS, SPECIFICATIONS
AND FIELD CONDITIONS, REPORT THEM TO THE OWNER.
THE FOLLOWING REQUIREMENTS, TOGETHER WITH THE PROJECT SPECIFICATIONS AND
BHS DRAWINGS SHALL APPLY.
FINISHED FLOOR ELEVATIONS PROVIDED FOR INFORMATION ONLY.
NO DIMENSIONS SHALL BE SCALED. DRAWING DIMENSIONS SHOWN SHALL BE
USED.
BHS CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING BHS RIGHT-OF-WAY ISSUES
AND REPORTING THEM TO THE OWNER.
ALL DIMENSIONS ARE FROM GRID TO OUTER EXTENT OF CONVEYOR SIDEGUARD,
UNLESS NOTED.
ALL OTHER TRADES SHALL MAINTAIN 3' CLEAR RIGHT-OF-WAY (UNLESS NOTED)
FROM TOP OF BELT TO NEAREST OBSTRUCTION. HANGING ANY EQUIPMENT
COMPONENTS (E.G. MECHANICAL, ELECTRICAL, PLUMBING, HVAC). FROM THE
CONVEYOR, CATWALK OR ASSOCIATED SUPPORTS IS NOT ACCEPTABLE.
ALL BHS RIGHTS-OF-WAY SHALL TAKE PRECEDENCE OVER ALL OTHER BUILDING
SERVICES (E.G. MECHANICAL, DUCT WORK AND PIPES, CONDUIT, FIRE
PROTECTION, PLUMBING).
SUPPLY SAFETY DEVICES PER CONTRACT SPECIFICATIONS.
1.
2.
3.
4.
5.
6.
7.
8.
STANDARD
CONVEYOR
TOP OF
BELT
C
LR
3'
R O
W
4'
CONV
3' - 6"
ROW
5' - 6"
MINIMUM 12" CLEARANCE
AROUND ALL BHS
ELEMENTS UNLESS
OTHERWISE NOTED
XXY-ZZ
NEW OR REWORKED CONVEYOR ID
SEQUENTIAL NUMBER OF
COMPONENTS IN TRAIN
SEQUENTIAL NUMBER OF
SUBSYSTEMS OF THIS TYPE
SUBSYSTEM DESCRIPTION
IDENTIFIER
SUBSYSTEM DESCRIPTION IDENTIFIERS
TC - TICKET COUNTER
SHEET NUMBER DESIGNATIONS
B2.10
SEQUENCE DRAWING #
WORK AREA
DISCIPLINE DESIGNATOR
45° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
45° SPIRAL POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
90° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
90° SPIRAL POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
INCLINE CONVEYOR
END ROLLER
QUEUE CONVEYOR
45° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
90° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
90° SPIRAL POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
END ROLLER
QUEUE CONVEYOR
45° SPIRAL POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
INCLINE CONVEYOR
BHS FLOW DIRECTION
TOP OF BELT ELEVATION
UNLESS NOTED
EXISTING BHS EQUIPMENT
DEMOLISHED BHS EQUIPMENT
NEW BHS EQUIPMENT
CONTROL PANEL
ITEM NUMBER
EXISTING EQUIPMENT
ITEM NUMBER
NEW EQUIPMENT
ITEM NUMBER
CONTROL EQUIPMENT
CONVEYOR CROSS SECTION
CONVEYOR WITH DRIVE
CROSS SECTION
XXY-ZZ
XXY-ZZ
XXY-ZZ
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
SYMBOLS,
LEGENDS,
ABBREVIATIONS
& SHEET LIST
B000
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
SHEET NO DESCRIPTION
B000 SYMBOLS, LEGENDS, ABBREVIATIONS & SHEET LIST
B001 CONVEYOR MANIFEST
B100 BHS - EXISTING LAYOUT
B101 COORDINATION LAYOUT
B200 BHS - PROPOSED LAYOUT
B400 BHS - SECTION VIEWS
B500 BHS - PROPOSED REMOVAL PATH
B501 BHS - TSA EGRESS PATH
B502 BHS - BAGGAGE INSPECTION STATION
B503 BHS - FAIL SAFE ZONE
B800 BHS - TYPICAL DETAILS
B801 BHS - TYPICAL DETAILS
B802 BHS - TYPICAL DETAILS
GENERAL ABBV DESCRIPTION
AFF ABOVE FINISHED FLOOR
ARCH PROJECT ARCHITECT
BF BETWEEN FRAME
BHS BAGGAGE HANDLING SYSTEM
BHSC BAGGAGE HANDLING SYSTEM CONTRACTOR
BIP BAGGAGE INSERTION POINT
BIS BAGGAGE INSPECTION STATION
BIT BAGGAGE INSPECTION TABLE
BLDG BUILDING
BRP BAGGAGE REMOVAL POINT
BSD BAGGAGE SYSTEM DISPLAY
BVS BAGGAGE VIEWING STATION
CBIS CHECKED BAGGAGE INSPECTION SYSTEM
CBRA CHECKED BAGGAGE RESOLUTION AREA
CL CENTERLINE
CLR CLEAR
CONT CONTINUOUS
CONV CONVEYOR
DWG DRAWING
EDS EXPLOSIVE DETECTION SYSTEM
EL ELEVATION
ENGR ENGINEER OF RECORD
EQUIP EQUIPMENT
ETD EXPLOSIVE TRACE DETECTION
EXST EXISTING
FF FINISHED FLOOR
FIN FINISH
FLA FULL LOAD AMPERAGE
FLR FLOOR
FPM FEET PER MINUTE
FSD FIRE-SECURITY DOOR
GC GENERAL CONTRACTORS
HSPD HIGH SPEED PADDLE DIVERTER
ID IDENTIFICATION
LVL LEVEL
MAINT MAINTENANCE
MAX MAXIMUM
MCP MOTOR CONTROL PANEL
MEP MECHANICAL ELECTRICAL PLUMBING
MFG MANUFACTURER
MIN MINIMUM
MTR MOTOR
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NTP NOTICE TO PROCEED
NTS NOT TO SCALE
OC ON CENTER
OPNG OPENING
OPS OPERATIONS
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
OSR ON SCREEN RESOLUTION
OTK OPERATIONAL TEST KIT
PLC PROGRAMMABLE LOGIC CONTROLLER
PVS PRIMARY VIEWING STATION
REF REFERENCE
REQD REQUIRED
ROW RIGHT OF WAY
SD SECURITY DOOR
SS STAINLESS STEEL
SVS SECONDARY VIEWING STATION
TCU THREAT CONTAINMENT UNIT
TOB TOP OF BELT
TSA TRANSPORTATION SECURITY ADMINISTRATION
TSO TRANSPORTATION SECURITY OFFICER
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
VIF VERIFY IN FIELD
CONVEYOR LEGEND FOR PLANS CONVEYOR LEGEND FOR ELEVATIONS GENERAL SYMBOLS LEGEND ABBREVIATIONS BHS DRAWING LIST
IDENTIFICATION NOMENCLATURE CONVEYOR ROW
GENERAL NOTES
No. DESCRIPTION DATE
1 Addendum No. 1 10/25/21
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
CONVEYOR
MANIFEST
B001
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
CONVEYOR MANIFEST EXISTING
EXISTING ID Family and Type
CONVEYOR
LENGTH (FT)
TC3-01 Conveyor - Transport: Existing (Load) EUG 5' - 5"
TC3-02 Conveyor - Incline: Existing - EUG 6' - 6"
TC3-03 Conveyor - Transport: Existing - EUG Feed 3' - 6"
TC3-04 Conveyor - Transport: Existing - EUG Feed 3' - 6"
TC3-05 Conveyor - Transport: Existing - EUG 3' - 6"
TC3-07 Conveyor - Transport: Existing - EUG 3' - 6"
TC3-08 Conveyor - Power Turn: Existing (45 Degree) EUG 2 3' - 0"
TC3-FD Doors - Overhead: Existing
TC3-SD Doors - Overhead: Existing
CONVEYOR MANIFEST NEW
NEW ID Family and Type
CONVEYOR
LENGTH (FT)
TC3-06 Conveyor - Transport: EDS2 - EUG 3' - 6"
TC3-09 Conveyor - Transport: Clear - EUG 4' - 0"
TC3-10 Conveyor - Power Turn: Clear (45 Degree) EUG 3' - 0"
TC3-EDS SS - CT80DR+: EDS1
No. DESCRIPTION DATE
7N 8N 9N
D.5
E
F
G
D.8
D.4
TC4TC3-01
TC3-02
TC3-03
TC3-04
TC3-05
TC3-08
TC3-07
3' - 3"
4'
1'
1"
1'
20' - 0" 20' - 0"
2'
9'
6'
7' - 7"
B400
EXISTING TABLE WITH WORKSTATION
EXISTING SUPPLY CABINET
ETD MACHINE
TC4 NIC
EXISTING BAGGAGE INSPECTION TABLE
EXISTING BHS EQUIPMENT
DEMO BHS EQUIPMENT
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − EXISTING
LAYOUT
B100
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/16" = 1'-0"1
TERMINAL LEVEL 1 - TC3 EXISTING CONDITIONS
E
F
G
D.8
D.4
B400
TC4TC3-01
TC3-02
TC3-03
TC3-04
TC3-05
TC3-08
TC3-07
3' - 3"
4'
1'
1"
1'
20' - 0" 20' - 0"
2'
9'
6'
7' - 7"
REMOVE TABLE AND WORKSTATION FROM ROOM.
COORDINATE WITH LOCAL TSA FOR NEW LOCATION IF NECESSARY
EXISTING TABLE TO BE REMOVED
RELOCATE CABINET
COORDINATE WITH LOCAL TSA FOR
NEW LOCATION OF CABINET
TC4 NIC
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
COORDINATION
LAYOUT
B101
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/16" = 1'-0"1
TERMINAL LEVEL 1 - COORDINATION LAYOUT
E
F
G
D.8
D.4
TC4
TC3-01
TC3-02
TC3-03
TC3-04
TC3-05
TC3-06
TC3-07
TC3-08
3' - 3" 7' - 7"
B400
B502
B502
20' - 0" 20' - 0"
2'
9'
6'
EL 365' - 1"
EL 366' - 6"
EL 366' - 6"
BSD SCREEN
(BY OTHERS)
SVS (TYP)
TC4 NIC
PVS
RELOCATED ETD
EL 1' - 1" AFF
EL 2' - 6" AFF
EDS DEVICE
CT-80DR+ WITH PEDESTAL
AND A/C UNIT
(PROVIDED BY TSA)
EL 2' - 6" AFF
RE-INSERTION POINT
REMOVAL POINT
2' - 0"
3' - 0"
TC3-10
TC3-09
EXISTING BHS EQUIPMENT
NEW BHS EQUIPMENT
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − PROPOSED
LAYOUT
B200
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/16" = 1'-0"1
TERMINAL LEVEL 1 - TC3
TERMINAL 1ST
LEVEL (0'- 0")
364' - 0"
TERMINAL 2ND
LEVEL (13' - 10")
377' - 10"
D.5D.8 D.4
13°
5' - 5"6' - 4"3' - 6"8' - 0"3' - 6" 3' - 6" 3' - 6"3' - 6"
TC3-01
TC3-02
TC3-03
TC3-04
TC3-05
TC3-07
6' - 7"20' - 7"
0"
EL 366' - 6"
EL 366' - 6"
33' - 7"
EL 365' - 1"
EL 2' - 6" AFF
EL 2' - 6" AFF
EL 1' - 1" AFF
TERMINAL 1ST
LEVEL (0'- 0")
364' - 0"
TERMINAL 2ND
LEVEL (13' - 10")
377' - 10"
D.5D.8 D.4
13°
TC3-01
TC3-02
TC3-03
TC3-04
TC3-05
TC3-06
TC3-07
5' - 5"6' - 4"3' - 6"8' - 0"3' - 6"3' - 6"3' - 6"3' - 6"
6' - 7"20' - 7"
0"
B502
EL 366' - 6"EL 366' - 6"
PVS (TYP)
BSD SCREENS
(BY OTHERS)
EL 2' - 6" AFFEL 2' - 6" AFF
EDS DEVICE
CT-80DR+ WITH PEDESTAL
AND A/C UNIT
(PROVIDED BY TSA)
EL 365' - 1"
EL 1' - 1" AFF
33' - 2"
TC3-09
EXISTING BHS EQUIPMENT
NEW BHS EQUIPMENT
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − SECTION
VIEWS
B400
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/8" = 1'-0"1
TC3 EXISTING
3/8" = 1'-0"2
TC3 - PROPOSED
EXISTING ETD FOR TC4 TO BE RELOCATED
E
F
G
D.8
D.4
5' - 0"
EDS REMOVAL PATH
20' - 0" 20' - 0"
2'
9'
6'
PVS (TYP)
BSD SCREENS
(BY OTHERS)
TC4 NIC
5'
- 0
5' - 0"
QUICK DISCONNECT CONVEYORS
EDS REMOVAL PATH
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − PROPOSED
REMOVAL PATH
B500
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/16" = 1'-0"1
TERMINAL LEVEL 1 - BHS - PROPOSED REMOVAL PATH
NOTES:
1. UTILIZE CASTORS AND QUICK DISCONNECT
ELECTRICAL CONNECTIONS AND
COMPONENTS TO ALLOW FOR REMOVAL OF
CONVEYORS DURING EDS REPLACEMENT
OR REMOVAL.
2. PATH MUST MAINTAIN MINIMUM 5'-0" WIDTH
CLEARANCE. MACHINE WIDTH IS 4'-6".
MACHINE LENGTH IS 8'-0".
3. CONVEYORS SHOWN AS QUICK
DISCONNECT SHALL BOTH MECHANICALLY
AND ELECTRICALLY CAPABLE OF QUICK
DISCONNECTING.
E
F
G
D.8
D.4
PVS (TYP)
TSA EGRESS PATH
BSD SCREENS
(BY OTHERS)
TC4 NIC
NEW RAISED STEEL WORK PLATFORM
REFERENCE DRAWING SHEET G002
FOR BASIS OF DESIGN
EGRESS PATH
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − TSA
EGRESS PATH
B501
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/16" = 1'-0"1
TERMINAL LEVEL 1 - BHS - TSA EGRESS PATH
7N
D.8
B502
B502
PVS (TYP)
BSD SCREENS
(BY OTHERS)
EDS DEVICE -
CT-80DR+ WITH PEDESTAL
AND A/C UNIT
(PROVIDED BY TSA)
EL 366' - 6"
EL 2' - 6" AFF
3'
"1'
1"
8'
8'
EL 366' - 6"
EL 2' - 6" AFF
TC3-08
TC3-07
TC3-06
TC3-05
TC3-04
TC3-03
TC3-09
TERMINAL 1ST
LEVEL (0'- 0")
364' - 0"
TERMINAL 2ND
LEVEL (13' - 10")
377' - 10"
D.5 D.8
B502
20' - 7"
FDRS
PVS (TYP)
BSD SCREENS
(BY OTHERS)
EL 366' - 6"
EL 366' - 6"
C
LE
A R
2'
EL 2' - 6" AFF
EL 2' - 6" AFF
EDS DEVICE -
CT-80DR+ WITH PEDESTAL
AND A/C UNIT
(PROVIDED BY TSA)
TC3-03
TC3-04 TC3-05
TC3-06
TC3-07
TC3-08
3' - 6"8' - 4"
1' - 11"8' - 5"
TERMINAL 1ST
LEVEL (0'- 0")
364' - 0"
7N
B502
BSD SCREENS
(BY OTHERS)
PVS (TYP)
EL 366' - 6"
EL 2' - 6" AFF
TC3-06
EDS DEVICE -
CT-80DR+ WITH PEDESTAL
AND A/C UNIT
(PROVIDED BY TSA)
EXISTING BHS EQUIPMENT
NEW BHS EQUIPMENT
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − BAGGAGE
INSPECTION
STATION
B502
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/8" = 1'-0"1
TERMINAL LEVEL 1 - TC3 ENLARGED PLAN
1/2" = 1'-0"2
TC3 SECTION VIEW #1
1/2" = 1'-0"3
TC3 SECTION VIEW #2
E
F
G
D.8
D.4
TC4
TC3-01
TC3-02
TC3-03
TC3-04
TC3-05
TC3-06
TC3-07
TC3-08
2' - 6" 7' - 11"
20' - 0" 20' - 0"
2'
9'
6'
FAIL SAFE LOCTION:
CONVEYOR TC3-08
FAIL SAFE STOPS TC3-07 &
TC3-08
BSD SCREENS
(BY OTHERS)
TC4 NIC1
TC3-09
TC3-10
EXISTING BHS EQUIPMENT
NEW BHS EQUIPMENT
FAIL SAFE BHS EQUIPMENT
PHONE: 203.792.3000
FAX: 203.792.4900
BNPHQ@BNPASSOCIATES.COM
1981 POST ROAD
FAIRFIELD, CT 06824 USA
ASSOCIATES, INC.
B N P
4582 S Ulster St., Suite 1100 Denver, CO 80237
303-409-9700
Oregon Registration No. 0871AF
RS&H Oregon, www.rsandh.com
Architects-Engineers-Planners, P.C.
© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.
PROJECT NUMBER
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
DATE ISSUED:
REVISIONS
SHEET NUMBER
SHEET TITLE
SEAL
CONSULTANTS
1 2 3 4 5 6
A
B
C
D
E
A
B
C
D
E
1 2 3 4 5 6 /2
/2
:1
:0
P
M B
IM
/2
E
U G
C B
IS
E xp a n si o n T
C B
H S
/2 E
U G
C
B
IS
E xp a n si o n
T C
B
H S
B
N P
R
.r vt
09/30/2021
RM
MN
2241872012
BHS − FAIL SAFE
ZONE
B503
ME
ISSUED FOR BID
Eugene Airport
CBIS TC3
Expansion
City of Eugene
28801 Douglas Drive Eugene, Oregon 97402
3/16" = 1'-0"1
TERMINAL LEVEL 1 - TC3 FAIL SAFE ZONE
PVS (TYP)
GENERAL LOAD NOTES:
THE CONVEYOR ATTACHMENT METHODS REPRESENTED ON THESE
DRAWINGS ARE FOR REFERENCE ONLY. THE BAGGAGE HANDLING
SYSTEM CONTRACTOR IS REQUIRED TO SUBMIT CONVEYOR
ATTACHMENT DETAILS INCLUDING LOADING CALCULATIONS BY A
REGISTERED PROFESSIONAL ENGINEER TO THE OWNER FOR REVIEW
AND APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
1.
2. ALL STRUCTURAL DESIGNS AND ATTACHMENTS SHALL COMPLY WITH
ALL STATE, LOCAL AND NATIONAL GOVERNING CODES AND
REGULATIONS. ALL CONVEYOR EQUIPMENT SHALL BE CAPABLE OF
SUPPORTING A SINGLE CONCENTRATED LOAD OF 250 LB.
BHS SUPPORT ATTACHMENT:
WHEN CONNECTING TO BUILDING STEEL USE BEAM CLAMPS SIZED FOR
THE BOTTOM FLANGE OF THE BEAM. USE A (MIN) 3/4" DIA THREADED
ROD FOR HANGING SUPPORT.
1.
WHEN CONNECTING TO THE…