2022200022_A2_Attachment A_Drawings_AMENDED_10-22-21pdf.pdf

PDF 11 MB Posted

Attached to
ITB 2022200022 Airport Checked Baggage System Expansion
Solicitation number
S-KE0010-00000996
Issued by
Lane County, Oregon

About this file

This document is the Attachment A - Drawings for ITB 2022200022 Airport Checked Baggage System Expansion, a contract opportunity issued by Lane County and the City of Eugene, Oregon. The project involves modifying existing checked baggage inspection areas and installing one new CT-80 DR+EDS to TC3 screening line. The work includes electrical, conveyor system installation, compliance testing, equipment training, general finishing, and other related services.

The contract is for a state and local government project within Lane County and the City of Eugene. No additional pricing terms, set asides, incumbents, funding requirements, or other salient information is provided in this attachment.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AEC PROJECT NUMBER

NOT ISSUED FOR

CONSTRUCTION

REVISIONS

/3

/2

:2

:5

P

M B

IM

/2

E

U G

C B

IS

E x p a n s io n T

C B

H S

/2

E

U G

C

B

IS

E x p a n s io n

T C

B

H S

A

R

.r v t

2241872012

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

ISSUED FOR BID

BNP Associates, Inc.

1999 Broadway, Suite 4250

Denver, Colorado 80202

BAGGAGE HANDLING

Copyright © 2021. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

© 2021 RS&H, INC

303-409-9700

4582 S Ulster St., Suite 1100 Denver, Colorado 80237-2603 www.rsandh.com

Oregon Registration No. 0871AF

EUGENE AIRPORT CBIS TC3 EXPANSION

NO. DESCRIPTION DATE

9/30/2021

As Amended per Addendum 1

A. THE WORK CAN BE DESCRIBED IN SUMMARY AS FOLLOWS:

THE MODIFICATION OF EXISTING CHECKED BAGGAGE INSPECTION AREAS TO ACCOMMODATE THE INSTALLATION OF ONE

(1) NEW CT-80 DR + EDS TO TC3 SCREENING LINE.

THERE WILL BE NO CHANGE IN USE CLASSIFICATION, OCCUPANCY, OR EGRESS DUE TO REVISIONS IN THIS PROJECT.

USE GROUP CLASSIFICATION: COVERED MALL (SECTION 402)

TYPE OF CONSTRUCTION: TYPE III-B (CHAPTER 6)

AREA LIMITATION: NOT LIMITED (SECTION 402.6)

HEIGHT LIMITATION: 3 STORIES (SECTION 402.6)

CODE ANALYSIS

APPLICABLE CODES

MINIMUM STANDARD CODES :

2019 OREGON STRUCTURAL SPECIALTY CODE (OSSC)

2019 OREGON MECHANICAL SPECIALTY CODE (OMSC)

2021 OREGON ELECTRICAL SPECIALTY CODE (OESC)

2021 OREGON PLUMBING SPECIALTY CODE (OPSC)

2021 OREGON ENERGY ENERGY EFFICIENCY SPECIALTY CODE (OEESC)

ADA: 2019 OSSC, CHAPTER 11: ACCESSIBILITY (ANSI A117.1)

OCCUPANCY CLASSIFICATION (IBC/LSC)

GROUP A2/ASSEMBLY: RESTAURANT

GROUP A3/ASSEMBLY: WAITING AREAS, CONFERENCE ROOMS, TABLE AND CHAIR SEATING

GROUP B/BUSINESS: OFFICE AREAS AND AIR TRAFFIC CONTROL TOWER (ATCT)

BUILDING DATA

TOTAL EXISTING GROSS BUILDING SQUARE FOOTAGE: 143,200 SF

LEVEL 1: 113,000 SF

LEVEL 2: 29,700 SF

NUMBER OF FLOORS: 2

HEIGHT OF BUILDING: 37'-8" OVERALL

SPRINKLERED: YES

CONSTRUCTION CLASSIFICATION (IBC)

PROJECT DESCRIPTION

AREA OF WORK

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

4582 S Ulster St., Suite 1100

Denver, CO 80237

303-409-9700

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /3

/2

:5

:3

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

A

R

.r vt

09/30/2021

GG

KS

2241872012

PROJECT

DEFINITIONS,

CODE INFO &

SHEET INDEX

G001

GG

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

SHEET INDEX

SHEET NUMBER SHEET NAME

N

PN

SCALE: 1" = 50'-0"

ARCHITECTURAL PROJECT DESCRIPTION

No. DESCRIPTION DATE

9/30/2021

B000 SYMBOLS, LEGENDS, ABBREVIATIONS & SHEET LIST

B001 CONVEYOR MANIFEST

B100 BHS - EXISTING LAYOUT

B101 COORDINATION LAYOUT

B200 BHS - PROPOSED LAYOUT

B400 BHS - SECTION VIEWS

B500 BHS - PROPOSED REMOVAL PATH

B501 BHS - TSA EGRESS PATH

B502 BHS - BAGGAGE INSPECTION STATION

B503 BHS - FAIL SAFE ZONE

B800 BHS - TYPICAL DETAILS

B801 BHS - TYPICAL DETAILS

B802 BHS - TYPICAL DETAILS

COVER SHEET

G001 PROJECT DEFINITIONS, CODE INFO & SHEET INDEX

G002 GENERAL NOTES, ABBREVIATIONS AND SYMBOLS

E001 ELECTRICAL GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS

EL111 FIRST FLOOR REFLECTED CEILING PLAN - AREA H

EP111 FIRST FLOOR ELECTRICAL POWER PLAN - AREA H

Grand total: 9.1

ARCHITECTURAL ABBREVIATIONS PLAN SYMBOLS

1-HOUR RATED WALL 2-HOUR RATED WALL

SMOKE RATED WALL

BATT INSULATION CONCRETE

EARTH EXPOSED & FINISHED WOOD TRIM

GYPSUM / PLASTER MASONRY - BRICK

PLYWOOD

RIGID INSULATION

STEEL

MATERIAL SYMBOLS

MASONRY - CONCRETE BLOCK

XX

View Name

SCALE:1/8" = 1'-0"

DOOR TAG

CALLOUT HEAD & REGION

A101

A1

SIM

BUILDING SECTION

KEYNOTE

BUILDING SECTION LEVEL HEAD

A1

A101

SIM

A1

A101

SIM

A1

A101

SIM

A1

A101

SIM

Name Elevation

ROOM TAG WALL TAG

XXX

DETAIL SECTION

WINDOW & STOREFRONT TAG

MATERIAL TAG

VIEW REFERENCE

REVISION TAG

NORTH ARROW

XX

A-101 A-101

ELEVATION - EXTERIOR ELEVATION - INTERIOR

WALL SECTION

CEILING TAG

GENERAL NOTES

1. ALL DIMENSIONS ARE IN FEET / INCHES UNLESS NOTED OTHERWISE.

2. THESE GENERAL NOTES ARE NOT INTENDED TO REPLACE SPECIFICATIONS - REFER TO SPECIFICATIONS FOR REQUIREMENTS IN ADDITION TO GENERAL NOTES.

3. THE TERMS RENOVATE AND REHABILITATE ARE USED INTERCHANGEABLY IN THESE DOCUMENTS.

4. ROOM AREAS AND PERIMETERS ARE APPROXIMATE AND FOR REFERENCE ONLY. VERIFY QUANTITIES AND DIMENSIONS IN FIELD.

5. NO DEVIATIONS FROM THESE CONTRACT DOCUMENTS SHALL BE MADE WITHOUT THE PRIOR WRITTEN APPROVAL OF THE ARCHITECT.

6. DO NOT SCALE DIMENSIONS FROM DRAWINGS - THE CONTRACTOR SHALL REQUEST NECESSARY DIMENSIONS NOT SHOWN ON THE DRAWINGS FROM THE ARCHITECT.

7. ALL DIMENSIONS ORIGINATE FROM EXISTING FACE OF WALLS & ARE TO FACE OF FRAMING AT NEW WORK OR CENTER OF DOORS, WINDOWS AND OPENINGS UNLESS NOTED OTHERWISE - ALL NON-DIMENSIONED DOOR LOCATIONS SHALL BE OFFSET 4" FROM THE ADJACENT WALL TO THE HINGE SIDE OF THE DOOR OPENING. ALL DOORS MUST BE INSTALLED TO MEET ALL APPLICABLE CODES, INCLUDING ADA.

8. DETAILS SHOWN ON DRAWINGS ARE TYPICAL FOR ALL SIMILAR CONDITIONS.

9. DRAWING NOTES AND SPECIFICATIONS ARE INSTRUCTIONS TO THE CONTRACTOR AND APPLY TO ALL THE WORK UNLESS MORE SPECIFIC INFORMATION IS SHOWN ELSEWHERE ON THE DRAWINGS OR WRITTEN IN THE SPECIFICATIONS - IN THE EVENT OF CONFLICTING INSTRUCTIONS, THE ARCHITECT SHALL DETERMINE WHAT CONTROLS THE CONTRACT DOCUMENTS ARE COMPLEMENTARY WHAT IS REQUIRED BY ONE SHALL BE REQUIRED BY

ALL.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR SCHEDULING AND COORDINATING THE WORK OF THE SUB-CONTRACTORS - THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH THE BUILDING OWNER, TENANT OR HIS REPRESENTATIVES THE DELIVERY AND INSTALLATION OF ITEMS BEING PROVIDED AND INSTALLED BY OTHERS.

11. ELECTRICAL WORK RELATED TO DEMOLITION AND NEW INSTALLATION OF COMPONENTS SHALL COMPLY WITH ALL APPLICABLE CODES.

12. ALL MATERIALS, FABRICATION AND INSTALLATION SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS AND SPECIFICATIONS FOR EACH DIVISION OF WORK.

13. CONSTRUCTION MUST COMPLY WITH APPLICABLE CODES AND ORDINANCES, LAWS AND SAFETY ORDERS AS DIRECTED BY LOCAL JURISDICTION.

14. CONTRACTOR SHALL BE RESPONSIBLE FOR THE TIMELY ORDERING OF MATERIALS INCLUDED IN THESE CONTRACT DOCUMENTS - SOME ITEMS IN THESE DOCUMENTS MAY REQUIRE LONG LEAD TIMES OR SPECIAL COORDINATION. SUBSTITUTIONS WILL NOT BE ALLOWED FOR MATERIAL NOT ORDERED IN A TIMELY FASHION.

15. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS, (BOTH NEW AND EXISTING) REPORTING ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO ORDERING MATERIALS OR PROCEEDING WITH

ANY PHASE OF THE WORK.

16. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS PRIOR TO COMMENCING CONSTRUCTION - ALL DISCREPANCIES SHALL BE NOTED AND SENT TO THE ARCHITECT WITH ADEQUATE TIME TO REVIEW PRIOR TO STARTING

THAT PORTION OF THE WORK IN ORDER TO AVOID PROJECT DELAYS.

17. CONTRACTOR SHALL CLEAN, PATCH AND REPAIR ALL SURFACES DAMAGED BY DEMOLITION, ALTERATION OR INSTALLATION OF THE WORK.

18. CONTRACTOR SHALL PROVIDE ADDITIONAL FURRING (THE ENTIRE LENGTH OF THE WALL) TO FULLY CONCEAL ELECTRICAL OR IT ITEMS THAT PROJECT FROM THE FACE OF THE WALL OR PARTITION AND ARE NOT SPECIFICALLY

NOTED TO BE SURFACE MOUNTED.

19. CONTRACTOR TO PROVIDE PORTABLE FIRE EXTINGUISHERS IN ACCORDANCE WITH LOCAL JURISDICTION AND NFPA 10. MAXIMUM TRAVEL DISTANCE TO NEAREST FIRE EXTINGUISHER FROM ANY POINT IN THE BUILDING SHALL NOT EXCEED 75 FEET. EXISTING FIRE EXTINGUISHERS SHALL BE TESTED AND RE-USED IF FULLY OPERATIONAL. FIRE EXTINGUISHERS SHALL BE SIZED FOR NO LESS THAN ORDINARY HAZARD.

20. ALL REQUESTS FROM INFORMATION PROMPTED BY THE BUILDING OFFICIALS SHALL INCLUDE A COPY OF THE BUILDING OFFICIALS’ COMMENTS AND THE BUILDING INSPECTORS FIELD REPORT TO ENSURE AN ACCURATE AND

TIMELY RESPONSE.

21. CONTRACTOR AND SUBCONTRACTOR SHALL ALL BE LICENSED TO PERFORM THEIR REQUESTED DUTIES AS REQUIRED IN ACCORDANCE WITH LOCAL STANDARDS.

22. ALL EXISTING EQUIPMENT AND FINISHES THAT ARE SCHEDULED OR NOTED TO REMAIN WILL BE PROTECTED BY THE CONTRACTOR. PHOTOGRAPHS OF EXISTING CONDITIONS SHALL BE PROVIDED BY THE CONTRACTOR TO

DOCUMENT PRE-EXISTING DAMAGE & FINISH CONDITIONS.

23. THE CONTRACTOR SHALL COORDINATE ALL DEMO AND NEW WORK ACTIVITIES WITH THE AIRPORT PRIOR TO PROCEEDING. THE EXISTING TSA BAG SCREENING LINE, TC4 WILL REMAIN IN OPERATION DURING CONSTRUCTION WORK FOR THIS PROJECT, AND NEW CONSTRUCTION ACTIVITIES SHALL NOT IMPEDE CURRENT TSA OR AIRPORT OPERATIONS. COORDINATE ALL WORK ACTIVITIES WITH THE AIRPORT PRIOR TO THE COMMENCEMENT OF THE WORK TO MINIMIZE DISRUPTIONS TO TSA, AIRPORT OPERATIONS, AND TRAVELING PASSENGERS.

24. MOCK UPS (AS REQUIRED) SHALL BE CONSTRUCTED BY THE CONTRACTOR PRIOR TO BEGINNING DEMOLITION WORK.

25. DO NOT USE ESCALATORS OR STAIRS FOR MOVING EQUIPMENT AND OR MATERIALS UNLESS COORDINATED WITH AIRPORT FACILITIES/OPERATIONS. WHEN USING ELEVATOR, ELEVATOR WALL, SIDES AND CEILING MUST BE PROTECTED FROM DAMAGE, ALL DAMAGE IS THE RESPONSIBILITY OF GENERAL CONTRACTOR AND MUST BE CORRECTED PRIOR TO PROJECT COMPLETION.

26. THE CONTRACTOR IS TO PROTECT EXISTING FINISHES, AND MAKE REPAIRS TO THE EXISTING FINISHES AND FIRE PROOFING WHERE DAMAGED AS PART OF THE NEW WORK ASSOCIATED WITH THIS PROJECT.

27. WHERE MATERIALS ARE APPLIED TO, OR ARE IN DIRECT CONTACT WITH WORK INSTALLED BY ANOTHER SUBCONTRACTOR, COMMENCEMENT OF WORK IMPLIES ACCEPTANCE OF THE SUBSTRATE AS SUITABLE FOR THE

APPLICATION INTENDED.

A. ISOLATE DISSIMILAR METALS TO PREVENT GALVANIC CORROSION.

28. OPENINGS IN RATED WALL, FLOOR, CEILING AND ROOF ASSEMBLIES SHALL BE SEALED WITH PENETRATION SEALANT SYSTEMS MEETING OR EXCEEDING THE REQUIRED FIRE RESISTIVE RATINGS.

29. MAINTAIN THE FIRE RATING OF CONSTRUCTION AROUND CABINETS, PANELS, AND BOXES RECESSED IN FIRE RATED WALL, FLOOR, AND CEILING ASSEMBLIES.

30. PROVIDE CONTINUOUS PERIMETER FIRE SAFING BETWEEN FLOORS AND COORDINATE THE INSTALLATION WITH THE EXTERIOR WALL. FIRE RATING OF SAFING SHALL MATCH FIRE RATING OF FLOOR CONSTRUCTION.

31. FIELD MEASURE AND CONFIRM DIMENSIONS FOR OWNER PROVIDED EQUIPMENT AND FURNISHINGS.

32. PROVIDE STIFFENERS, BRACING, BACKING PLATES AND BLOCKING REQUIRED FOR SECURE INSTALLATION OF MISCELLANEOUS EQUIPMENT, AND SUSPENDED ELECTRICAL EQUIPMENT.

33. DO NOT OBSTRUCT ACCESS TO EXISTING EXITS, OR REDUCE THE WIDTH OF PUBLIC CORRIDORS.

34. PENETRATIONS IN THE EXTERIOR BUILDING WALL ARE NOT ALLOWED, INCLUDING THOSE REQUIRED FOR OUTLETS AND BLOCKING.

35. FINISH FLOOR ELEVATIONS ARE TO TOP OF CONCRETE UNLESS OTHERWISE NOTED.

36. GANG MULTIPLE SWITCHES TOGETHER INTO ONE BOX WITH A SINGLE COVER PLATE WHENEVER POSSIBLE. MULTIPLE SWITCHES, WHICH CANNOT BE GANGED TOGETHER IN THE SAME BOX, SHALL BE LOCATED CLOSE

TOGETHER AS POSSIBLE AND MOUNTED AT THE SAME HEIGHT.

37. WALL OUTLETS SHALL BE INSTALLED AT 18" AFF UNLESS OTHERWISE NOTED. INSTALL SWITCH PLATES AT 42" AFF UNLESS OTHERWISE NOTED.

38. DO NOT INSTALL OUTLET OR J-BOXES BACK-TO-BACK ON OPPOSITE SIDES OF THE WALL. BOXES MUST BE SEPARATED BY A STUD.

39. SPECIAL INSPECTION REQUIRED FOR POST-INSTALLED CONCRETE ANCHORS PER OSSC, SECTION 1705.1.1)

XXXX 12'-0" AFF

CEILING TYPE

CEILING HEIGHT

*NOTE - REFER TO PARTITION TYPE SHEET FOR INFO ON TAG

PT-1

A1 1A11

FURNITURE & EQUIPMENT TAG TOILET ACCESSORY TAG

1i 1i

TILE / CARPET

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

4582 S Ulster St., Suite 1100

Denver, CO 80237

303-409-9700

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /1

/2

:1

:3

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

A

R

.r vt

09/30/2021

GG

KS

2241872012

GENERAL NOTES,

ABBREVIATIONS

AND SYMBOLS

G002

GG

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

LB. POUND

LDG. LANDING

LONG. LONGITUDINAL

LRV. LOUVER

LT. LIGHT

LTG. LIGHTING

LVP LUXURY VINYL PLANK

LVT LUXURY VINYL TILE

M.O. MASONRY OPENING

MATL. MATERIAL

MAX. MAXIMUM

MECH MECHANICAL

MEP MECHANICAL, ELECTRICAL, & PLUMBING

MFGR. MANUFACTURER

MGR. MANAGER

MIN. MINIMUM

MOD MODIFIED

MSC. MISCELLANEOUS

MTL METAL

MUFID MULTI-USER FLIGHT INFORMATION DISPLAY

N.I.C. NOT IN CONTRACT

N.T.S. NOT TO SCALE

N/A NOT APPLICABLE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NO. NUMBER

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

OFCI OWNER FUNISHED CONTRACTOR INSTALLED

OPG OPENING

OPP. OPPOSITE

OSHA OCCUPATIONAL SAFETY AND HEALTH ACT

OVHD OVERHEAD

P.LAM. PLASTIC LAMINATE

PBB PASSENGER BOARDING BRIDGE

PBB PASSENGER BOARDING BRIDGE

PDU POWER DISTRIBUTION UNIT

PLYWD. PLYWOOD

PNL. PANEL

PR. PAIR

PRE-FAB PRE-FABRICATED

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT, PRESSURE TREATED

PVC POLYVINYL CHLORIDE

Q.T. QUARRY TILE

R RADIUS

R.A.F. RAISED ACCESS FLOOR

R.A.G. RETURN AIR GRILLE

R.D. ROOF DRAIN

R.O. ROUGH OPENING

RB RUBBER BASE

RECEP. RECEPTION, RECEPTIONIST

REF. REINFORCING, REINFORCEMENT

REQ'D. REQUIRED

REV. REVISED, REVISION

S.F. SQUARE FEET

S.G.P. SEMI-GLOSS PAINT

S.S. SERVICE SINK

SC SEALED CONCRETE

SCHED. SCHEDULE

SCW. SOLID CORE WOOD

SECT. SECTION

SFRM SPRAYED FIRE RESISTIVE MATERIAL

SHT. SHEET

SHTS. SHEETS

SIM. SIMILAR

SPECS. SPECIFICATIONS

SQ. SQUARE

SQ. IN. SQUARE INCHES

STC SOUND TRANSMISSION CLASS

STD. STANDARD

STL. STEEL

STOR. STORAGE

STRUCT STRUCTURAL, STRUCTURE

SUSP. SUSPENDED

T&G TONGUE & GROOVE

T.O. STL. TOP OF STEEL

T.O.B. TOP OF BRICK, TOP OF BEAM

T.O.S. TOP OF STEEL, TOP OF SLAB

T.O.SH. TOP OF SHEATHING

T.O.W. TOP OF WALL

TEL. TELEPHONE

TG TEMPERED GLASS

TYP. TYPICAL

U.L. UNDERWRITERS LABORATORIES

U.O.N. UNLESS OTHERWISE NOTED

VB VAPOR BARRIER

VCT OR VT VINYL COMPOSITION TILE

VDC VIRTUAL DESIGN & CONSTRUCTION

VERT. VERTICAL

VR VIRTUAL REALITY

W.C. WATER CLOSET

W/ WITH

WCO WALL CLEANOUT

WD WOOD

WMP WIRE MESH PARTITION

WWF WELDED WIRE FABRIC

YD. YARD

Ø DIAMETER

& AND

@ AT

A.B. ANCHOR BOLT

A.F.S. ABOVE FLOOR SLAB

A.W.I. ARCHITECTURAL WOODWORK INSTITUTE

A/C AIR CONDITIONER

ACT ACOUSTICAL CEILING TILE

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALUM ALUMINUM

ANOD. ANODIZED

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

APPROX. APPROXIMATE OR APPROXIMATELY

ARCH ARCHITECTURE, ARCHITECTURAL

AVG AVERAGE

B.H.M.I. BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION, INC.

B.O. BOTTOM OF

B.U.R. BUILT-UP ROOFING

BHS BAGGAGE HANDLING SYSTEM

BID BAGGAGE INFORMATION DISPLAY

BIM BUILDING INFORMATION MODELING

BLDG. BUILDING

BM. BEAM

C.J. CONTROL JOINT

CBIS CHECKED BAGGAGE INSPECTION STATION

CFMF COLD FORMED METAL FRAMING

CL CENTERLINE

CL O.T.S. CENTERLINE OF TENANT SEPARATION

CLG. CEILING

CLO. CLOSET

CLR. CLEAR

CMU CONCRETE MASONRY UNIT

COL. COLUMN

COLS. COLUMNS

CONC. CONCRETE

CONT. CONTINUOUS

D.S. DOWNSPOUT

DIA. DIAMETER

DR. DOOR

DTL. OR DET. DETAIL

DWG. DRAWING

E.F.S. EXTERIOR FACE OF SHEATHING

E.J. EXPANSION JOINT

E.O.S. EDGE OF SLAB

E.P. ELECTRICAL PANEL

E.R.D. EMERGENCY ROOF DRAIN

E.T.D. ESTIMATED TRAVEL DISTANCE

E.W.C. ELECTRIC WATER COOLER

EA. EACH

ELEC. ELECTRIC, ELECTRICAL

ELEV. ELEVATION

ENG. ENGINEER, ENGINEERING

EPDM ethylene propylene diene monomer

EQ. EQUAL

EQUIP. EQUIPMENT

EXIST. EXISTING

EXP. EXPANSION, EXPOSED

EXT. EXTERIOR

F.D. FIRE DAMPER, FLOOR DRAIN

F.F. FINISHED FLOOR

F.F.E. FINISHED FLOOR ELEVATION

F.O. FACE OF

F.O.B. FACE OF BRICK

F.O.P. FACE OF POST

F.V. FIELD VERIFY

FDC FIRE DEPARTMENT CONNECTION

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FID FLIGHT INFORMATION DISPLAY

FIN. FINISH, FINISHED

FLR. FLOOR

FRP FIBER REINFORCED PANEL

FT. FEET

FTG. FOOTING

G.P. GLOSSY PAINT

GA. GAUGE

GALV. GALVANIZED

GBF GYPSUM BOARD FURRING

GID GATE INFORMATION DISPLAY

GL. GLASS

GWB GYPSUM WALL BOARD

GYP. GYPSUM

HB HOSE BIB

HDW HARDWARE

HGT. OR HT. HEIGHT

HKS HOOKS

HM HOLLOW METAL

HORIZ. HORIZONTAL

HVAC HEATING VENTILATION & AIR CONDITIONING

I.D. INSIDE DIAMETER

i.e. THAT IS, SUCH AS

I.F.S. INTERIOR FACE OF STUD

IN. INCH, INCHES

INSUL. INSULATION

INT. INTERIOR

JAN. JANITOR

JST. JOIST

JT. JOINT

K.P. KICK PLATE

LAM. LAMINATE

LAV. LAVATORY

1. PROVIDE AND INSTALL A RAISED WORK PLATFORM SIMILAR TO WHAT WAS PREVIOUSLY INSTALLED AT THE ADJACENT TC5 LINE, SHOWN IN THE ATTACHED IMAGE ON THIS DRAWING. THIS SELF-SUPPORTED PLATFORM IS A FREE-STANDING UNIT WITH NO REQUIRED ATTACHMENTS TO ANY BUILDING ELEMENT. THE DESIGN INTENT IS TO PROVIDE A SAFE WALKWAY THAT IS FREE OF TRIPPING HAZARDS, SUCH AS CONDUIT OR CABLING FOR TSA PERSONNEL TO ACCESS THE

EDS, CT-80 DR+ MACHINE.

PROVIDE AND INSTALL ONE (1) EACH 97" X 24" GLOBAL INDUSTRIAL MODEL NO. WLOS597242. VERIFY FIELD DIMENSIONS AND COORDINATE WITH BHS EQUIPMENT AND ELECTRICAL COMPONENTS. A LINK TO THE BASIS OF DESIGN EQUIPMENT IS

BELOW.

HTTPS://WWW.GLOBALINDUSTRIAL.COM/P/97-X-24-ADJUSTABLE-HEIGHT-5-8-STEEL-WORK-PLATFORM

REFERENCE BHS DRAWING SHEET B501 FOR PLAN LOCATION

WORK NOTE:

No. DESCRIPTION DATE

WORK PLATFORM(S) INSTALLED AT

ADJACENT TC5 SCREENING LINE

9/30/2021

ELECTRICAL ABBREVIATIONS GENERAL NOTESELECTRICAL SYMBOLS

1. ALL ELECTRICAL WORK SHALL COMPLY WITH NATIONAL ELECTRICAL CODE, NFPA 70, THE NATIONAL FIRE CODES, THE AMERICANS WITH DISABILITIES ACT, AND OTHER BUILDING CODES AS APPLICABLE FOR THE SITE.

2. THE CONTRACTOR SHALL THOROUGHLY REVIEW THE PROJECT TO ENSURE THAT ALL WORK SHALL MEET OR EXCEED THE ABOVE REQUIREMENTS. ANY ALLEGED DISCREPANCIES SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION.

3. THE CONTRACTOR IS DIRECTED TO OBTAIN COPIES OF ALL RELATED PLANS, SPECIFICATIONS, SHOP DRAWINGS AND

ADDENDA TO COORDINATE THE RELATED WORK AND SCHEDULING.

4. THE ELECTRICAL SERVICE TO AND FOR EQUIPMENT IS BASED ON EQUIPMENT DESIGN DATA. THE ACTUAL VALUES MAY DIFFER DEPENDING UPON THE EQUIPMENT TO BE FURNISHED. ANY MODIFICATION TO THE ELECTRICAL INSTALLATION, BASED UPON ACTUAL EQUIPMENT SELECTION, SHALL RESULT IN NO ADDITIONAL COST TO THE OWNER.

5.

6. THE CONTRACTOR SHALL THOROUGHLY FAMILIARIZE HIMSELF/HERSELF WITH THE WORK TO BE PERFORMED BY OTHER TRADES AND THE PHYSICAL CHARACTERISTICS OF THE STRUCTURE IN ORDER TO SCHEDULE AND INSTALL EQUIPMENT AND TO MINIMIZE POSSIBLE INTERFERENCE. FAILURE TO PROPERLY COMMUNICATE AND SCHEDULE WORK WITH OTHER TRADES THAT RESULTS IN ADDITIONAL WORK AND MATERIAL, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE MODIFICATIONS REQUIRED TO RESOLVE THE CONFLICT SHALL BE DECIDED BY THE ENGINEER.

7. ALL PANELBOARDS MODIFIED AS A RESULT OF WORK PERFORMED SHALL BE FURNISHED AND INSTALLED WITH A TYPEWRITTEN SCHEDULE SHOWING CIRCUIT NUMBERS AND A COMPLETE DESCRIPTION OF EACH CIRCUIT, INCLUDING

OFFICIAL ROOM NUMBER.

8. ALL LIGHT SWITCHES AND DUPLEX RECEPTACLES SHALL BE RATED FOR 20 AMPERES AT 120/277 VOLTS AC. WIRING

DEVICES SHALL BE SPECIFICATION GRADE.

9. THE LUMINAIRE SCHEDULE IS FOR REFERENCE ONLY. MODEL NUMBERS LISTED MAY NOT INCLUDE ALL REQUIRED OPTIONS, HOWEVER, THESE OPTIONS SHALL BE FURNISH AND INSTALLED WITH THE LUMINAIRES. ALL SUBSTITUTIONS

ARE SUBJECT TO PRIOR APPROVAL AS EQUAL BY THE ENGINEER OF RECORD.

10. ALL EXIT LIGHTS, INCLUDING LIGHTS REQUIRING RELOCATION AS A RESULT OF THIS PROJECT, SHALL BE FURNISH AND INSTALLED WITH UNIVERSAL MOUNTING BRACKETS. THE CONTRACTOR SHALL VERIFY ALL DIRECTIONAL ARROWS WITH

ARCHITECTURAL EGRESS PLANS PRIOR TO ORDERING LUMINAIRES.

11. ALL RECESSED LUMINAIRES IN FIRE RATED CEILINGS SHALL BE TENTED TO COMPLY WITH THE APPLICABLE CEILING

RATING. THE CONTRACTOR SHALL VERIFY REQUIREMENTS.

12. ALL COMMUNICATIONS OUTLET BOXES SHALL BE MIN. 4" WIDE BY 4" HIGH BY 2 1/2" DEEP WITH SINGLE GANG MUD RING.

13. FURNISH AND INSTALL 1" C FROM COMMUNICATIONS OUTLET TO THE ACCESSIBLE CEILING SPACE, UON. CONTRACTOR SHALL FURNISH AND INSTALL CABLING AS REQUIRED. CABLE ROUTING WILL BE VIA CONDUIT (INACCESSIBLE SPACES) OR 'J' HOOKS AND CABLE TRAY SYSTEM (ACCESSIBLE SPACES) TO COMMUNICATION ROOM OR ROOM OF TERMINATION.

FURNISH AND INSTALL RACEWAY SYSTEM OVER THE INACCESSIBLE CEILING SPACE AS INDICATED ON PLANS.

COMMUNICATION CONDUITS ARE TO BE LONG RADIUS TYPE AND SHALL CONTAIN PULL STRINGS. FURNISH AND INSTALL

PLATES FOR ALL OUTLETS. CAT6 CABLES SHALL BE PLENUM RATED.

14. ALL SPECIAL PURPOSE OUTLETS SHALL BE FURNISHED AND INSTALLED TO MATCH EQUIPMENT TO BE SUPPLIED.

15. ALL CONDUITS SHALL INCLUDE A SEPARATE GREEN EQUIPMENT GROUNDING CONDUCTOR.

16. ANY EXISTING UTILITIES LOCATED IN THE AREA OF CONSTRUCTION THAT REQUIRE RELOCATION OR TIE-IN SHALL BE

COORDINATED WITH THE OWNER'S REPRESENTATIVE. PROVIDE 72 HOUR ADVANCE NOTICE.

17. ALL DISCONNECT SWITCHES SHALL BE THE HEAVY DUTY TYPE, FUSED DISCONNECTS SHALL HAVE LITTLEFUSE TIME DELAY, CLASS RK5 AND INDICATING CLASS RK5, OR AS REQUIRED PER EQUIPMENT MANUFACURER DATA SHEETS.

18. ALL EMPTY CONDUITS SHALL CONTAIN JET LINE #232 POLYOLEFIN 200 LB. TEST PULL STRING.

19. ALL WORK SHOWN ON THE ELECTRICAL PLANS SHALL BE PERFORMED BY THE CONTRACTOR, UON.

20. ALL EXIT FIXTURES SHALL BE CONNECTED TO THE BUILDING LIFE SAFETY PANEL AND/OR HAVE INTEGRAL EMERGENCY

BATTERY.

21. ALL SURGE PROTECTED OUTLETS SHALL BE EQUAL TO HUBBELL #5352.

22. EQUIPMENT INSTALLED WITHIN CONCEALED SPACES SHALL HAVE REASONABLE ACCESS PANELS FURNISH AND INSTALLED NEARBY FOR INSPECTION, TESTING, AND SERVICE CONSIDERATIONS. LOCATION OF ACCESS PANELS PER

APPROVAL OF ARCHITECT.

23. THE CONTRACTOR SHALL VERIFY CEILING TYPES AND INSTALLATION REQUIREMENTS PRIOR TO ORDERING LUMINAIRES.

24. WHERE CABLES OR CONDUITS ARE REQUIRED TO PASS THROUGH A FIRE RATED WALL, FLOOR, OR CEILING THEY SHALL BE SEALED WITH FIRESTOP. THE APPROVED FIRESTOP METHOD SHALL COMPLY WITH ARTICLES 300.21 OF NEC AND SHALL BE UL LISTED UNDER "THROUGH-PENETRATION FIRESTOP SYSTEM (XHEZ)" IN UL FIRE RESISTANCE DIRECTORY.

ALL UNSPRINKLERED FACILITES SHALL BE CONSIDERED TO HAVE INTERIOR CORRIDORS WITH FIRE RATED WALLS, UNO.

ANY PENETRATION THROUGH THESE WALLS AND OTHER FIRE RATED WALLS SHALL BE SEALED WITH FIRESTOP.

FURNISH AND INSTALL MINIMUM 1" EMT THROUGH WALL PENETRATIONS.

25. CONDUITS, WIREWAYS, AND CABLE TRAYS SHALL BE SUPPORTED FROM BUILDING STRUCTURE AND NOT FROM OTHER

PIPES, DUCTS, OR EXISTING RACKS, UON.

26. EXTERIOR BURIED CONDUIT RUNS SHALL BE MINIMUM 24" BELOW FINISHED GRADE. FURNISH AND INSTALL CAUTION TAPE 12" BELOW GRADE. FURNISH AND INSTALL (1) SPARE WITH EACH UNDERGROUND RUN. DUCTBANKS SHALL BE CONCRETE ENCASED WITH LOCATION PLAQUES PLACED EVERY 50' AND BEFORE AND AFTER EVERY TURN, UON.

SUBMIT SHOP DRAWINGS BEFORE DIGGING.

27. FURNISH AND INSTALL GROUND STRAP ACROSS ALL CABLE TRAY JOINTS. GROUND CABLE TRAY TO SERVICE GROUND

WITH #1/0 AWG BARE COPPER.

28. ALL CONDUIT BENDS FOR COMMUNICATIONS WIRING SHALL BE SMOOTH LONG RADIUS TYPE. "LB" TYPE FITTINGS SHALL

NOT BE USED FOR FOR COMMUNICATION RACEWAY.

29. DO NOT LOCATE ELECTRICAL OUTLETS AND DEVICES ON WALL PANEL JOINTS. FIELD VERIFY FOR WALL PANEL LAYOUT

AND PANEL JOINT LOCATIONS.

30. CONTRACTOR SHALL FURNISH AND INSTALL A SEPARATE NEUTRAL FOR EACH PHASE CONDUCTOR OF SINGLE POLE BRANCH CIRCUITS THAT SERVE HIGH HARMONIC LOADS, SUCH AS, BALLAST OR SWITCH MODE POWER SUPPLIES (I.E.

PERSONAL COMPUTERS AND SERVERS).

31. RACEWAYS INSTALLED IN OUTDOOR LOCATIONS SHALL BE HOT DIPPED GALVINIZED, AT MINIMUM, FOR CORROSION RESISTANCE. FOR HIGHLY CORROSIVE ENVIRONMENTS, SUCH AS COASTAL AREAS, ALUMINUM, STAINLESS STEEL, OR

PVC COATED RACEWAYS SHALL BE REQUIRED.

32. POWER CHANGE EXPENSES RESULTING FROM EQUIPMENT SUBSTITUTIONS THAT DIFFER FROM ITEMS CALLED FOR IN DRAWINGS OR SPECIFICATIONS SHALL BE BORNE BY THE CONTRACTOR OR THEIR SUB. THESE SHALL INCLUDE CHANGES IN VOLTAGE OR FULL LOAD AMPS RESULTING IN LARGER FEEDERS AND OR CIRCUIT BREAKERS.

33. COORDINATE FINAL ELECTRICAL DEVICE AND LUMINAIRE LOCATIONS WITH FINAL SPRINKLER HEAD LOCATIONS TO

COMPLY WITH NFPA REQUIREMENTS.

34. ALL EXISTING ELECTRICAL DEVICES THAT ARE NOT SHOWN ARE EXISTING TO REMAIN, UON.

35. COORDINATE DISCONNECT REQUIREMENTS WITH EQUIPMENT FOR THE SCOPE OF PROJECT. CONTRACTOR SHALL FURNISH AND INSTALL DISCONNECTS FOR THOSE DEVICES THAT DO NOT COME WITH FACTORY INSTALLED

DISCONNECTS.

36. BEFORE INITIATING ANY UNDERGROUND WORK, CONTRACTOR MUST LOCATE ALL UTILITIES.

37. INTERIOR FIRE ALARM CONDUCTORS SHALL BE INSTALLED IN RED EMT CONDUIT. EXTERIOR FIRE ALARM CONDUIT

SHALL BE RED RMC CONDUIT.

LIGHTING SYMBOLS

GENERAL NOTE: UPPER CASE LETTER INDICATES LUMINAIRE TYPE, SEE LUMINAIRE SCHEDULE. LOWER

CASE LETTER INDICATES SWITCH CIRCUIT.

POWER SYSTEMS

RECESSED LUMINAIRE WITH OUTLET

RECESSED EMERGENCY OR NIGHTLIGHT LUMINAIRE WITH OUTLET

RECESSED OR SURFACE STANDBY LUMINAIRE WITH OUTLET

SURFACE LUMINAIRE WITH OUTLET

SURFACE EMERGENCY OR NIGHTLIGHT LUMINAIRE WITH OUTLET

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

4582 S Ulster St., Suite 1100

Denver, CO 80237

303-409-9700

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /1

/2

:4

:4

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

E

R

.r vt

09/30/2021

CJB

2241872012

ELECTRICAL

GENERAL NOTES,

SYMBOLS, AND

ABBREVIATIONS

E001

TSK

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

SCCR SHORT CIRCUIT CURRENT RATING

SCHWP SECONDARY CHILLED WATER PUMP

SD SUB-DISTRIBUTION CABINET

SE SOUTH ENTRANCE

SEC SECURITY

SEGB SERVICE ENTRANCE GROUND BAR

SF SUPPLY FAN

SHWP SECONDARY HOT WATER PUMP

SIM SIMILAR

SLC SIGNAL LINE CIRCUIT

SN SOLID NEUTRAL

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE SINGLE THROW

SQ SQUARE

SS STAINLESS STEEL

SSF SIDE STREAM FILTER

ST SHUNT TRIP COIL

STC SECURITY TERMINAL CABINET

STR STARTER

STS STAINLESS STEEL

STS STATIC TRANSFER SWITCH

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

T TRANSFORMER

TB TELEPHONE BACKBOARD

TE THERMAL ELEMENT

TEFC TOTALLY ENCLOSED FAN COOLED

TEL TELEPHONE

TGB TELECOMMUNICATIONS

GROUNDING BUS BAR

TMGB TELECOMMUNICATIONS MAIN

GROUNDING BUS BAR

TR TAMPER RESISTANT

TS TAMPER SWITCH

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UDS UTILITY DISTRIBUTION SYSTEM

UG UNDERGROUND

UGC UNDERGROUND COMMUNICATIONS

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UNSW UNSWITCHED

UON UNLESS OTHERWISE NOTED

UT UTILITY

UTR UP THROUGH ROOF

V VOLTS

VAV VARIABLE AIR VOLUME (HVAC)

VFD VARIABLE FREQUENCY DRIVE

VFI VACUUM FAULT INTERRUPTER

VT VOLTAGE TRANSFORMER

W WIRE

W WALL MOUNTED

W WATTS

W WEST

WP WEATHERPROOF

WR WEATHER-RESISTANT

Y WYE (CONNECTED)

Z ZONE

Z IMPEDANCE

FAPS FIRE ALARM POWER SUPPLY

FATC FIRE ALARM TERMINAL CABINET

FCU FAN COIL UNIT

FID FLIGHT INFORMATION DISPLAY

FLA FULL LOAD AMPS

FLR FLOOR

FO FIBER OPTIC

FPB FAN POWERED TERMINAL BOX

FPU FAN POWERED TERMINAL UNIT

FS FLOW SWITCH

FSPC FLUSH/FAUCET SENSOR POWER

CONVERTER

FTU FAN POWERED VAV TERMINAL UNIT

G GROUND

GC GENERAL CONTRACTOR

GDF GAS DUCT FURNACE

GF GROUND FAULT

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFGI GOVERNMENT FURNISHED

GOVERNMENT INSTALLED

GFP GROUND FAULT PROTECTION

GID GATE INFORMATION DISPLAY

GPU GROUND POWER UNIT

GR GROUND ROD

GRC GALVANIZED RIGID CONDUIT

GUH GAS UNIT HEATER

GWH GAS WATER HEATER

HB HIGH BAY

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HP HORSE POWER

HVAC HEATING, VENTILATING & AIR

CONDITIONING

IC INTERCOM

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

ITC INTERCOM TERMINAL CABINET

J JUNCTION

JB JUNCTION BOX

KAIC (THOUSAND) AMPERE

INTERRUPTING CAPACITY

Kcmil THOUSANDS OF CIRCULAR MILS

KO KNOCK OUT

KVA KILOVOLT-AMPERES

KW KILOWATT

LBS LOAD BREAK SWITCH

LC LIGHTING CONTACTOR

LED LIGHT EMITTING DIODE

LSI LONG TIME, SHORT TIME,

INSTANTANEOUS

LSIG LONG TIME, SHORT TIME,

INSTANTANEOUS, GROUND FAULT

LT LIGHT

LTG LIGHTING

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MNS MASS NOTIFICATION SYSTEM

MTD MOUNTED

MTS MANUAL TRANSFER SWITCH

MUFID MULTI-USER FLIGHT INFORMATION

DISPLAY

N NEUTRAL

N NORTH

N/A NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CIRCUIT

NE NORTH ENTRANCE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOC

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NUMBER

NTS NOT TO SCALE

O.C. ON CENTER

OAE OR APPROVED EQUAL

OAHU OUTSIDE AIR HANDLING UNIT

OH OVERHEAD

OS OCCUPANCY SENSOR

P PHASE

PBB PASSENGER BOARDING BRIDGE

PBX PRIVATE BRANCH EXCHANGE

PCHWP PRIMARY CHILLED WATER PUMP

PIV POST INDICATOR VALVE

PNEU PNEUMATIC

PNL PANELBOARD

PNL PANEL

POE POWER OVER ETHERNET

PP POWER PANEL

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PVC POLYVINYLCHLORIDE

RAF RETURN AIR FAN

RECP RECEPTACLE

REF REFRIGERATOR

RGS RIGID GALVANIZED STEEL

RM ROOM

RMC RIGID METAL CONDUIT

RTU ROOF TOP UNIT

S SOUTH

SCADA SUPERVISORY CONTROL AND DATA

ACQUISITION

A AMPERES

A/C AIR CONDITIONING

AC ABOVE COUNTER

AC AIR COMPRESSOR

ACCU AIR COOLED CONDENSER UNIT

ACT ACOUSTIC CEILING TILE

ACU AIR CONDITIONING UNIT

ADA AMERICANS WITH DISABILITIES ACT

ADAAG AMERICANS WITH DISABILITIES ACT

ACCESSIBILITY GUIDELINES

AF AMP FUSE

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFD ADJUSTABLE FREQUENCY DRIVE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPS INTERRUPTING CURRENT

AIR AMPERE INTERUPTING RATING

AL ALUMINUM

AMP AMPERE

AMS ACCESS MANAGEMENT SYSTEM

AP ACCESS PANEL

APU AUXILIARY POWER UNIT

AT/FP ANTITERRORISM/FORCE

PROTECTION

ATR ALL THREADED ROD

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BCW BARE COPPER WIRE

BDCT BUILDING DESIGN AND

CONSTRUCTION TEAM

BFG BELOW FINISHED GRADE

BHS BAGGAGE HANDLING SYSTEM

BID BAGGAGE INFORMATION DISPLAY

BTS BEAM TRANSPORT SYSTEM

C CONDUIT

CAT6 CATEGORY 6 ETHERNET CABLE

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CC CRANE CONTROL

CCP CONCRETE CAMERA POLE

CCTV CLOSED CIRCUIT TELEVISION

CE COMMUNICATIONS ENCLOSURE

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CFL COMPACT FLUORESCENT

CH CHILLER

CKT CIRCUIT

CLP CONCRETE LIGHT POLE

CMH COMMUNICATIONS MANHOLE

CMU CONCRETE MASONRY UNIT

CNTRL CONTROLLER

CO CONDUIT ONLY

COMM COMMUNICATION

CONC CONCRETE

CP CONSOLIDATION POINT

CR CARD READER

CRU COMPUTER ROOM UNIT

CT COOLING TOWER

CT CURRENT TRANSFORMER

CTWP COOLING TOWER WATER PUMP

CU COPPER

CUB CENTRAL UTILITIES BUILDING

DACT DIGITAL ALARM COMMUNICATOR

TRANSMITTER

DAS DISTRIBUTED ANTENNA SYSTEM

DC DIRECT CURRENT

DCU DUCTLESS SPLIT AIR CONDITIONING

OUTDOOR UNIT

DDC DIRECT DIGITAL CONTROL PANEL

DH DOOR HOLDER

DHZ DAYLIGHT HARVESTING ZONE

DISC DISCONNECT

DTCO DOUBLE THROW CENTER OFF

DWG DRAWING

E EXISTING

E EAST

EC ELECTRICAL CONTRACTOR

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EL ELEVATION

EL EMERGENCY LIGHT

ELEC ELECTRIC/ELECTRICAL

EM EMERGENCY

EMCS ENERGY MANAGEMENT CONTROL

SYSTEM

EMH ELECTRICAL MANHOLE

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

EOR ENGINEER OF RECORD

EPO EMERGENCY POWER-OFF

EQ EQUAL

ER EXISTING TO BE REMOVED

ERU ENERGY RECOVERY UNIT

ESS ENERGY SELECTION SYSTEM

ETSP ELECTRONIC TRAP SEAL PRIMER

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EX EXISTING TO REMAIN

EXR EXISTING TO BE RELOCATED

F/P FAX / PRINTER

FA FIRE ALARM

FAAA FIRE ALARM AUDIO AMPLIFIER

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAGA FIRE ALARM GRAPHIC

ANNUNCIATOR

FAIC FIRE ALARM INTERFACE CABINET

No. DESCRIPTION DATE

TSK

THE CONTRACTOR SHALL THOROUGHLY REVIEW THE PROJECT REQUIREMENTS TO ASSURE THAT ELECTRICAL SERVICE FOR ALL ITEMS AND/OR EQUIPMENT REQUIRING ELECTRICAL SERVICE IS INCLUDED. ANY ITEM AND/OR EQUIPMENT NOT FURNISH AND INSTALLED WITH ELECTRICAL SERVICE, REQUIRING ELECTRICAL SERVICE, SHALL BE

BROUGHT TO THE ENGINEER'S ATTENTION.

GENERAL NOTES

A. LUMINARE LOCATIONS ARE APPROXIMATE.

4N4N

5N5N

6N6N

7N7N

8N8N

9N9N

10N10N

11N11N

D

D

D.5

D.5

E

E

F

F

G

G

H

H

D.8

D.8

D.4

D.4

C

C

TSA SCREENING

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

4582 S Ulster St., Suite 1100

Denver, CO 80237

303-409-9700

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /1

/2

:4

:4

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

E

R

.r vt

09/30/2021

CJB

2241872012

FIRST FLOOR

REFLECTED

CEILING PLAN −

AREA H

EL111

TSK

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

N

PN

SCALE: 3/32" = 1'-0"

A1

FIRST FLOOR REFLECTED CEILING PLAN - AREA H

KEYNOTES

1 REPLACE EXISTING LUMINARES WITH LED LUMINAIRES.

No. DESCRIPTION DATE

TSK

GENERAL NOTES

A. MEZZANINE ELECTRICAL ROOM LOCATION IS LOCATED IN THE GENERAL AREA ABOVE THE NEW

INSTALLATION AREA. ELECTRICAL CONTRACTOR SHALL VERIFY LOCATION AND INSTALLATION

CONSIDERATIONS REQUIRED FOR SCOPE OF THIS INSTALLATION.

4N4N

5N5N

6N6N

7N7N

8N8N

9N9N

10N10N

11N11N

D

D

D.5

D.5

E

E

F

F

G

G

H

H

D.8

D.8

D.4

D.4

C

C

TSA SCREENING

1 2 3 4

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

4582 S Ulster St., Suite 1100

Denver, CO 80237

303-409-9700

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /1

/2

:4

:4

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

E

R

.r vt

09/30/2021

CJB

2241872012

FIRST FLOOR

ELECTRICAL

POWER PLAN −

AREA H

EP111

TSK

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

N

PN

SCALE: 3/32" = 1'-0"

A1

FIRST FLOOR ELECTRICAL POWER PLAN - AREA H

KEYNOTES

1 REMOVE CIRCUIT AND RACEWAY WHICH ARE IN PLACE FOR EXPLOSIVE DETECTION

SYSTEM (EDS) AND CHECKED BAGGAGE INSPECTION SYSTEM (CBIS) INSTALLATION.

2 FURNISH AND INSTALL NEW 30 AMP CIRCUIT INCLUDING RACEWAY, WIRING, 2-POLE 30

AMP 208VAC CIRCUIT BREAKER, AND ANY OTHER MATERIAL REQUIRED FROM PANEL

NPX-1 TO THE EDS AND CBIS.

3 PERFORM 30 DAY LOAD STUDY ON NPX-1

4 CONTRACTOR SHALL FURNISH AND INSTALL FIBER OPTIC CONNECTION FROM EXISTING

COMMUNICATIONS JUNCTION BOX LOCATED ON THE OPPOSITE WALL OF THE PROJECT

AREA FOR INSTALLATION OF EDS.

TSK

CHECK AND FIELD VERIFY ALL BHS RELATED DIMENSIONS ON THE JOB SITE

BEFORE PROCEEDING WITH WORK AND BE RESPONSIBLE FOR THEIR ACCURACY.

IF DISCREPANCIES ARE FOUND BETWEEN THE BHS DRAWINGS, SPECIFICATIONS

AND FIELD CONDITIONS, REPORT THEM TO THE OWNER.

THE FOLLOWING REQUIREMENTS, TOGETHER WITH THE PROJECT SPECIFICATIONS AND

BHS DRAWINGS SHALL APPLY.

FINISHED FLOOR ELEVATIONS PROVIDED FOR INFORMATION ONLY.

NO DIMENSIONS SHALL BE SCALED. DRAWING DIMENSIONS SHOWN SHALL BE

USED.

BHS CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING BHS RIGHT-OF-WAY ISSUES

AND REPORTING THEM TO THE OWNER.

ALL DIMENSIONS ARE FROM GRID TO OUTER EXTENT OF CONVEYOR SIDEGUARD,

UNLESS NOTED.

ALL OTHER TRADES SHALL MAINTAIN 3' CLEAR RIGHT-OF-WAY (UNLESS NOTED)

FROM TOP OF BELT TO NEAREST OBSTRUCTION. HANGING ANY EQUIPMENT

COMPONENTS (E.G. MECHANICAL, ELECTRICAL, PLUMBING, HVAC). FROM THE

CONVEYOR, CATWALK OR ASSOCIATED SUPPORTS IS NOT ACCEPTABLE.

ALL BHS RIGHTS-OF-WAY SHALL TAKE PRECEDENCE OVER ALL OTHER BUILDING

SERVICES (E.G. MECHANICAL, DUCT WORK AND PIPES, CONDUIT, FIRE

PROTECTION, PLUMBING).

SUPPLY SAFETY DEVICES PER CONTRACT SPECIFICATIONS.

1.

2.

3.

4.

5.

6.

7.

8.

STANDARD

CONVEYOR

TOP OF

BELT

C

LR

3'

R O

W

4'

CONV

3' - 6"

ROW

5' - 6"

MINIMUM 12" CLEARANCE

AROUND ALL BHS

ELEMENTS UNLESS

OTHERWISE NOTED

XXY-ZZ

NEW OR REWORKED CONVEYOR ID

SEQUENTIAL NUMBER OF

COMPONENTS IN TRAIN

SEQUENTIAL NUMBER OF

SUBSYSTEMS OF THIS TYPE

SUBSYSTEM DESCRIPTION

IDENTIFIER

SUBSYSTEM DESCRIPTION IDENTIFIERS

TC - TICKET COUNTER

SHEET NUMBER DESIGNATIONS

B2.10

SEQUENCE DRAWING #

WORK AREA

DISCIPLINE DESIGNATOR

45° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

45° SPIRAL POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

90° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

90° SPIRAL POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

INCLINE CONVEYOR

END ROLLER

QUEUE CONVEYOR

45° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

90° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

90° SPIRAL POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

END ROLLER

QUEUE CONVEYOR

45° SPIRAL POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

INCLINE CONVEYOR

BHS FLOW DIRECTION

TOP OF BELT ELEVATION

UNLESS NOTED

EXISTING BHS EQUIPMENT

DEMOLISHED BHS EQUIPMENT

NEW BHS EQUIPMENT

CONTROL PANEL

ITEM NUMBER

EXISTING EQUIPMENT

ITEM NUMBER

NEW EQUIPMENT

ITEM NUMBER

CONTROL EQUIPMENT

CONVEYOR CROSS SECTION

CONVEYOR WITH DRIVE

CROSS SECTION

XXY-ZZ

XXY-ZZ

XXY-ZZ

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

SYMBOLS,

LEGENDS,

ABBREVIATIONS

& SHEET LIST

B000

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

SHEET NO DESCRIPTION

B000 SYMBOLS, LEGENDS, ABBREVIATIONS & SHEET LIST

B001 CONVEYOR MANIFEST

B100 BHS - EXISTING LAYOUT

B101 COORDINATION LAYOUT

B200 BHS - PROPOSED LAYOUT

B400 BHS - SECTION VIEWS

B500 BHS - PROPOSED REMOVAL PATH

B501 BHS - TSA EGRESS PATH

B502 BHS - BAGGAGE INSPECTION STATION

B503 BHS - FAIL SAFE ZONE

B800 BHS - TYPICAL DETAILS

B801 BHS - TYPICAL DETAILS

B802 BHS - TYPICAL DETAILS

GENERAL ABBV DESCRIPTION

AFF ABOVE FINISHED FLOOR

ARCH PROJECT ARCHITECT

BF BETWEEN FRAME

BHS BAGGAGE HANDLING SYSTEM

BHSC BAGGAGE HANDLING SYSTEM CONTRACTOR

BIP BAGGAGE INSERTION POINT

BIS BAGGAGE INSPECTION STATION

BIT BAGGAGE INSPECTION TABLE

BLDG BUILDING

BRP BAGGAGE REMOVAL POINT

BSD BAGGAGE SYSTEM DISPLAY

BVS BAGGAGE VIEWING STATION

CBIS CHECKED BAGGAGE INSPECTION SYSTEM

CBRA CHECKED BAGGAGE RESOLUTION AREA

CL CENTERLINE

CLR CLEAR

CONT CONTINUOUS

CONV CONVEYOR

DWG DRAWING

EDS EXPLOSIVE DETECTION SYSTEM

EL ELEVATION

ENGR ENGINEER OF RECORD

EQUIP EQUIPMENT

ETD EXPLOSIVE TRACE DETECTION

EXST EXISTING

FF FINISHED FLOOR

FIN FINISH

FLA FULL LOAD AMPERAGE

FLR FLOOR

FPM FEET PER MINUTE

FSD FIRE-SECURITY DOOR

GC GENERAL CONTRACTORS

HSPD HIGH SPEED PADDLE DIVERTER

ID IDENTIFICATION

LVL LEVEL

MAINT MAINTENANCE

MAX MAXIMUM

MCP MOTOR CONTROL PANEL

MEP MECHANICAL ELECTRICAL PLUMBING

MFG MANUFACTURER

MIN MINIMUM

MTR MOTOR

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NTP NOTICE TO PROCEED

NTS NOT TO SCALE

OC ON CENTER

OPNG OPENING

OPS OPERATIONS

OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

OSR ON SCREEN RESOLUTION

OTK OPERATIONAL TEST KIT

PLC PROGRAMMABLE LOGIC CONTROLLER

PVS PRIMARY VIEWING STATION

REF REFERENCE

REQD REQUIRED

ROW RIGHT OF WAY

SD SECURITY DOOR

SS STAINLESS STEEL

SVS SECONDARY VIEWING STATION

TCU THREAT CONTAINMENT UNIT

TOB TOP OF BELT

TSA TRANSPORTATION SECURITY ADMINISTRATION

TSO TRANSPORTATION SECURITY OFFICER

TYP TYPICAL

UPS UNINTERRUPTIBLE POWER SUPPLY

VIF VERIFY IN FIELD

CONVEYOR LEGEND FOR PLANS CONVEYOR LEGEND FOR ELEVATIONS GENERAL SYMBOLS LEGEND ABBREVIATIONS BHS DRAWING LIST

IDENTIFICATION NOMENCLATURE CONVEYOR ROW

GENERAL NOTES

No. DESCRIPTION DATE

1 Addendum No. 1 10/25/21

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

CONVEYOR

MANIFEST

B001

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

CONVEYOR MANIFEST EXISTING

EXISTING ID Family and Type

CONVEYOR

LENGTH (FT)

TC3-01 Conveyor - Transport: Existing (Load) EUG 5' - 5"

TC3-02 Conveyor - Incline: Existing - EUG 6' - 6"

TC3-03 Conveyor - Transport: Existing - EUG Feed 3' - 6"

TC3-04 Conveyor - Transport: Existing - EUG Feed 3' - 6"

TC3-05 Conveyor - Transport: Existing - EUG 3' - 6"

TC3-07 Conveyor - Transport: Existing - EUG 3' - 6"

TC3-08 Conveyor - Power Turn: Existing (45 Degree) EUG 2 3' - 0"

TC3-FD Doors - Overhead: Existing

TC3-SD Doors - Overhead: Existing

CONVEYOR MANIFEST NEW

NEW ID Family and Type

CONVEYOR

LENGTH (FT)

TC3-06 Conveyor - Transport: EDS2 - EUG 3' - 6"

TC3-09 Conveyor - Transport: Clear - EUG 4' - 0"

TC3-10 Conveyor - Power Turn: Clear (45 Degree) EUG 3' - 0"

TC3-EDS SS - CT80DR+: EDS1

No. DESCRIPTION DATE

7N 8N 9N

D.5

E

F

G

D.8

D.4

TC4TC3-01

TC3-02

TC3-03

TC3-04

TC3-05

TC3-08

TC3-07

3' - 3"

4'

1'

1"

1'

20' - 0" 20' - 0"

2'

9'

6'

7' - 7"

B400

EXISTING TABLE WITH WORKSTATION

EXISTING SUPPLY CABINET

ETD MACHINE

TC4 NIC

EXISTING BAGGAGE INSPECTION TABLE

EXISTING BHS EQUIPMENT

DEMO BHS EQUIPMENT

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − EXISTING

LAYOUT

B100

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/16" = 1'-0"1

TERMINAL LEVEL 1 - TC3 EXISTING CONDITIONS

E

F

G

D.8

D.4

B400

TC4TC3-01

TC3-02

TC3-03

TC3-04

TC3-05

TC3-08

TC3-07

3' - 3"

4'

1'

1"

1'

20' - 0" 20' - 0"

2'

9'

6'

7' - 7"

REMOVE TABLE AND WORKSTATION FROM ROOM.

COORDINATE WITH LOCAL TSA FOR NEW LOCATION IF NECESSARY

EXISTING TABLE TO BE REMOVED

RELOCATE CABINET

COORDINATE WITH LOCAL TSA FOR

NEW LOCATION OF CABINET

TC4 NIC

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

COORDINATION

LAYOUT

B101

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/16" = 1'-0"1

TERMINAL LEVEL 1 - COORDINATION LAYOUT

E

F

G

D.8

D.4

TC4

TC3-01

TC3-02

TC3-03

TC3-04

TC3-05

TC3-06

TC3-07

TC3-08

3' - 3" 7' - 7"

B400

B502

B502

20' - 0" 20' - 0"

2'

9'

6'

EL 365' - 1"

EL 366' - 6"

EL 366' - 6"

BSD SCREEN

(BY OTHERS)

SVS (TYP)

TC4 NIC

PVS

RELOCATED ETD

EL 1' - 1" AFF

EL 2' - 6" AFF

EDS DEVICE

CT-80DR+ WITH PEDESTAL

AND A/C UNIT

(PROVIDED BY TSA)

EL 2' - 6" AFF

RE-INSERTION POINT

REMOVAL POINT

2' - 0"

3' - 0"

TC3-10

TC3-09

EXISTING BHS EQUIPMENT

NEW BHS EQUIPMENT

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − PROPOSED

LAYOUT

B200

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/16" = 1'-0"1

TERMINAL LEVEL 1 - TC3

TERMINAL 1ST

LEVEL (0'- 0")

364' - 0"

TERMINAL 2ND

LEVEL (13' - 10")

377' - 10"

D.5D.8 D.4

13°

5' - 5"6' - 4"3' - 6"8' - 0"3' - 6" 3' - 6" 3' - 6"3' - 6"

TC3-01

TC3-02

TC3-03

TC3-04

TC3-05

TC3-07

6' - 7"20' - 7"

0"

EL 366' - 6"

EL 366' - 6"

33' - 7"

EL 365' - 1"

EL 2' - 6" AFF

EL 2' - 6" AFF

EL 1' - 1" AFF

TERMINAL 1ST

LEVEL (0'- 0")

364' - 0"

TERMINAL 2ND

LEVEL (13' - 10")

377' - 10"

D.5D.8 D.4

13°

TC3-01

TC3-02

TC3-03

TC3-04

TC3-05

TC3-06

TC3-07

5' - 5"6' - 4"3' - 6"8' - 0"3' - 6"3' - 6"3' - 6"3' - 6"

6' - 7"20' - 7"

0"

B502

EL 366' - 6"EL 366' - 6"

PVS (TYP)

BSD SCREENS

(BY OTHERS)

EL 2' - 6" AFFEL 2' - 6" AFF

EDS DEVICE

CT-80DR+ WITH PEDESTAL

AND A/C UNIT

(PROVIDED BY TSA)

EL 365' - 1"

EL 1' - 1" AFF

33' - 2"

TC3-09

EXISTING BHS EQUIPMENT

NEW BHS EQUIPMENT

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − SECTION

VIEWS

B400

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/8" = 1'-0"1

TC3 EXISTING

3/8" = 1'-0"2

TC3 - PROPOSED

EXISTING ETD FOR TC4 TO BE RELOCATED

E

F

G

D.8

D.4

5' - 0"

EDS REMOVAL PATH

20' - 0" 20' - 0"

2'

9'

6'

PVS (TYP)

BSD SCREENS

(BY OTHERS)

TC4 NIC

5'

- 0

5' - 0"

QUICK DISCONNECT CONVEYORS

EDS REMOVAL PATH

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − PROPOSED

REMOVAL PATH

B500

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/16" = 1'-0"1

TERMINAL LEVEL 1 - BHS - PROPOSED REMOVAL PATH

NOTES:

1. UTILIZE CASTORS AND QUICK DISCONNECT

ELECTRICAL CONNECTIONS AND

COMPONENTS TO ALLOW FOR REMOVAL OF

CONVEYORS DURING EDS REPLACEMENT

OR REMOVAL.

2. PATH MUST MAINTAIN MINIMUM 5'-0" WIDTH

CLEARANCE. MACHINE WIDTH IS 4'-6".

MACHINE LENGTH IS 8'-0".

3. CONVEYORS SHOWN AS QUICK

DISCONNECT SHALL BOTH MECHANICALLY

AND ELECTRICALLY CAPABLE OF QUICK

DISCONNECTING.

E

F

G

D.8

D.4

PVS (TYP)

TSA EGRESS PATH

BSD SCREENS

(BY OTHERS)

TC4 NIC

NEW RAISED STEEL WORK PLATFORM

REFERENCE DRAWING SHEET G002

FOR BASIS OF DESIGN

EGRESS PATH

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − TSA

EGRESS PATH

B501

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/16" = 1'-0"1

TERMINAL LEVEL 1 - BHS - TSA EGRESS PATH

7N

D.8

B502

B502

PVS (TYP)

BSD SCREENS

(BY OTHERS)

EDS DEVICE -

CT-80DR+ WITH PEDESTAL

AND A/C UNIT

(PROVIDED BY TSA)

EL 366' - 6"

EL 2' - 6" AFF

3'

"1'

1"

8'

8'

EL 366' - 6"

EL 2' - 6" AFF

TC3-08

TC3-07

TC3-06

TC3-05

TC3-04

TC3-03

TC3-09

TERMINAL 1ST

LEVEL (0'- 0")

364' - 0"

TERMINAL 2ND

LEVEL (13' - 10")

377' - 10"

D.5 D.8

B502

20' - 7"

FDRS

PVS (TYP)

BSD SCREENS

(BY OTHERS)

EL 366' - 6"

EL 366' - 6"

C

LE

A R

2'

EL 2' - 6" AFF

EL 2' - 6" AFF

EDS DEVICE -

CT-80DR+ WITH PEDESTAL

AND A/C UNIT

(PROVIDED BY TSA)

TC3-03

TC3-04 TC3-05

TC3-06

TC3-07

TC3-08

3' - 6"8' - 4"

1' - 11"8' - 5"

TERMINAL 1ST

LEVEL (0'- 0")

364' - 0"

7N

B502

BSD SCREENS

(BY OTHERS)

PVS (TYP)

EL 366' - 6"

EL 2' - 6" AFF

TC3-06

EDS DEVICE -

CT-80DR+ WITH PEDESTAL

AND A/C UNIT

(PROVIDED BY TSA)

EXISTING BHS EQUIPMENT

NEW BHS EQUIPMENT

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − BAGGAGE

INSPECTION

STATION

B502

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/8" = 1'-0"1

TERMINAL LEVEL 1 - TC3 ENLARGED PLAN

1/2" = 1'-0"2

TC3 SECTION VIEW #1

1/2" = 1'-0"3

TC3 SECTION VIEW #2

E

F

G

D.8

D.4

TC4

TC3-01

TC3-02

TC3-03

TC3-04

TC3-05

TC3-06

TC3-07

TC3-08

2' - 6" 7' - 11"

20' - 0" 20' - 0"

2'

9'

6'

FAIL SAFE LOCTION:

CONVEYOR TC3-08

FAIL SAFE STOPS TC3-07 &

TC3-08

BSD SCREENS

(BY OTHERS)

TC4 NIC1

TC3-09

TC3-10

EXISTING BHS EQUIPMENT

NEW BHS EQUIPMENT

FAIL SAFE BHS EQUIPMENT

PHONE: 203.792.3000

FAX: 203.792.4900

BNPHQ@BNPASSOCIATES.COM

1981 POST ROAD

FAIRFIELD, CT 06824 USA

ASSOCIATES, INC.

B N P

4582 S Ulster St., Suite 1100 Denver, CO 80237

303-409-9700

Oregon Registration No. 0871AF

RS&H Oregon, www.rsandh.com

Architects-Engineers-Planners, P.C.

© 2021 RS&H Oregon, Architects-Engineers-Planners, P.C.

PROJECT NUMBER

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

DATE ISSUED:

REVISIONS

SHEET NUMBER

SHEET TITLE

SEAL

CONSULTANTS

1 2 3 4 5 6

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6 /2

/2

:1

:0

P

M B

IM

/2

E

U G

C B

IS

E xp a n si o n T

C B

H S

/2 E

U G

C

B

IS

E xp a n si o n

T C

B

H S

B

N P

R

.r vt

09/30/2021

RM

MN

2241872012

BHS − FAIL SAFE

ZONE

B503

ME

ISSUED FOR BID

Eugene Airport

CBIS TC3

Expansion

City of Eugene

28801 Douglas Drive Eugene, Oregon 97402

3/16" = 1'-0"1

TERMINAL LEVEL 1 - TC3 FAIL SAFE ZONE

PVS (TYP)

GENERAL LOAD NOTES:

THE CONVEYOR ATTACHMENT METHODS REPRESENTED ON THESE

DRAWINGS ARE FOR REFERENCE ONLY. THE BAGGAGE HANDLING

SYSTEM CONTRACTOR IS REQUIRED TO SUBMIT CONVEYOR

ATTACHMENT DETAILS INCLUDING LOADING CALCULATIONS BY A

REGISTERED PROFESSIONAL ENGINEER TO THE OWNER FOR REVIEW

AND APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.

1.

2. ALL STRUCTURAL DESIGNS AND ATTACHMENTS SHALL COMPLY WITH

ALL STATE, LOCAL AND NATIONAL GOVERNING CODES AND

REGULATIONS. ALL CONVEYOR EQUIPMENT SHALL BE CAPABLE OF

SUPPORTING A SINGLE CONCENTRATED LOAD OF 250 LB.

BHS SUPPORT ATTACHMENT:

WHEN CONNECTING TO BUILDING STEEL USE BEAM CLAMPS SIZED FOR

THE BOTTOM FLANGE OF THE BEAM. USE A (MIN) 3/4" DIA THREADED

ROD FOR HANGING SUPPORT.

1.

WHEN CONNECTING TO THE…