This solicitation is for repair and alteration services for three buildings at the 158th Fighter Wing in South Burlington, Vermont. The projects include renovations to Building 180 to accommodate machine shop and welding shop operations, renovations to Building 327 to update a munitions shop, and renovations to Building 384 to enclose part of the building for AME storage. The work involves interior demolition and construction, installation of HVAC, electrical, and communication systems. The estimated value is between $1-5 million. The NAICS code is 238220 and it is set aside for small businesses. The pre-bid conference is on the date specified in the solicitation. Questions must be submitted by email by the deadline. The bid opening date is in the solicitation. Plans and specifications are available on beta.SAM.gov and amendments will be posted there. Interested parties must register on beta.SAM.gov to access the documents. This is a single award firm fixed price contract for repair and alteration services at three buildings to support F-35 operations at the Vermont Air National Guard in South Burlington.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF 1419 Abstract of Offers W50S9C-20-B-0001 - Certified-Signed.pdf | ||
| W50S9C20B0001 - Amendment 0002.pdf | ||
| Q and A as of 30 Jun 20 W50S9C20B0001 Repair Multi-Facilities.pdf | ||
| Q and A as of 26 Jun 20 W50S9C20B0001 Repair Multi-Facilities.pdf | ||
| Q and A as of 25 Jun 20 W50S9C20B0001 Repair Multi-Facilities.pdf | ||
| Q and A as of 16 Jun 20 W50S9C20B0001 Repair Multi-Facilities.pdf | ||
| Pre-Bid Minutes - Attendance - Power Point Slides W50S9C20B0001.pdf | ||
| W50S9C20B0001 - Amendment 0001.pdf | ||
| 0001 - B-180 PROJECT MANUAL_Rev 051120.pdf | ||
| 0001 - B-180 DRAWINGS_100419.pdf | ||
| W50S9C20B0001.pdf | ||
| 3001 - B-384 DRAWINGS_100419.pdf | ||
| 3001 - B-384 PROJECT MANUAL_Rev 051120.pdf | ||
| 2001 - B-327 PROJECT MANUAL_Rev 051120.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIST OF DRAWINGS
C O N S U L T A N T S
A R C H I T E C T S
1 1 7 S t P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V t.
0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7
F: 8 0 2 • 8 6 3 • 0 0 9 3
ALVAR E Z
SIENKIEWYCZ
S M I T H
SAS PROJECT NO. 1002
DRAWING SYMBOLS
INTERIOR ELEVATION
BUILDING SECTION
WALL SECTION
DETAIL
ENLARGED DETAIL
WINDOW TYPE
DOOR NUMBER
VERTICAL ELEVATION
A
Elevation reference number
EL. 100'-0"
A-7
A-2 See this detail...
...on this drawing
A-6
B A-4
B A-4See this section...
...on this drawing
MATERIALS
ABBREVIATIONS
ABI additive bid item ACT acoustic ceiling tile ADJ adjustable AFF above finish floor ALUM aluminum ANC anchor, anchorage ARCH architect(ural) BSMT basement BIT bituminous BLKG blocking BD board BOT bottom BRK brick BLDG building BTWN between CB catch basin CJ control joint CLG ceiling CT ceramic tile CO clean out CL closet CLR clear(ance) COL column CONC concrete CMU concrete masonry unit CONT continuous or continue DP dampproofing DEM demolish, demolition DET detail DIA diameter DWG drawing
DF drinking fountain ELEC electric(al) EL elevation ELEV elevator EQ equal EXG existing EXT exterior FG fiberglass FIN finish FF finish floor FE fire extinguisher FLG flashing FD floor drain FRT fire retardant FTG footing FND foundation GA gage, gauge GALV galvanized GC general contract(or)
GFE-GI government furnished equipment-government installed
GFI-CI government furnished equipment-contractor installed
GWB gypsum wall board HPDL high pressure decorative laminate HWD hardwood HVAC heating, ventilating & air conditioning HT height HOR horizontal
ROOM FINISH SCHEDULE
Room finish schedule reference number for walls
Room finish schedule reference number for base/floors
W1 B1 F1
CODE CLASSIFICATIONS
ID inside diameter INS insulation JAN janitor JT joint LAV lavatory MAX maximum MECH mechanical MFR manufacturer MH manhole MO masonry opening MTL metal MIN minimum NIC not in contract NTS not to scale OC on center OD outside diameter OPNG opening PNT paint(ed) PR pair PL plate PT pressure treated PWD plywood REF refrigerator R riser RM room RO rough opening SAC suspended acoustic ceiling SHTH sheathing SIM similar
SPEC specification(s) SQ square SS stainless steel STD standard SD storm drain STRUC structural SYS system TBP tile backing panel TDO thermoset decorative overlay TEL telephone TG tempered glass THK thick(ness) TH threshold T&G tongue & groove TOC top of concrete TOM top of masonry TOS top of steel TOW top of wall T tread TYP typical UNO unless noted otherwise VERT vertical VCT vinyl composition tile VR vapor retarder VT vinyl tile WG wire glass W/O with out WD wood
STONE
(PLAN/ELEV.)
COMPACTED
GRANULAR
FILL
CONCRETE
CONCRETE BLOCK
BRICK
BATT
INSULATION
RIGID
INSULATION
STEEL OR HEAVY
GAUGE
METAL
FINISH
WOOD
ROUGH
WOOD
PLYWOOD
GYPSUM
BOARD
STONE
(SECTION)
SOUND
ATTENUATION
BATTS
PARTICLE
BOARD OR MDF
TILE BACKING
PANEL
W1 or
INTERNATIONAL BUILDING CODE - IBC-2015
USE & OCCUPANCY CLASSIFICATIONS:
B-327 - HIGH-HAZZARD (H-1),
CONSTRUCTION TYPE - IBC SECTION 602: 2B, UNPROTECTED,
NON- COMBUSTIBLE
EXISTING BUILDING HEIGHT & AREA: (MOST RESTRICTIVE)
B-327:
• ONE STORY BUILDING
• TOTAL GROSS BUILDING AREA: 1,102 SF (1,088 PER FORM 1391)
• BUILDING HEIGHT: 14 FT
• ALLOWABLE HEIGHT/AREA: H-1 OCCUPANCY / 2B CONSTRUCTION:
1 STORIES / 55 FT / 7,000 SF
ALTER B-327
CURZ 182803
ALTER B-327 MUNITIONS SHOP
VERMONT AIR NATIONAL GUARD
SOUTH BURLINGTON, VERMONT
CURZ 182803
CONSTRUCTION DRAWINGS
OCTOBER 4, 2019
NFPA 101, LIFE SAFETY CODE- 2015 EDITION
CLASSIFICATION OF OCCUPANCY: B-327 - INDUSTRIAL HIGH-HAZZARD
ANTICIPATED OCCUPANCY:
B-327 • AVERAGE DAILY: 8 PEOPLE
NUMBER OF MEANS OF EGRESS:
NOT LESS THAN (2) MEANS OF EGRESS SHALL BE PROVIDED FROM EVERY STORY
OR SECTION OF EACH FACILITY.
ARRANGEMENT OF MEANS OF EGRESS: (MOST RESTRICTIVE)
B-327: INDUSTRIAL, HIGH-HAZARD (UNSPRINKLERED PER VTANG)
• COMMON PATH OF TRAVEL: PROHIBITED
• DEAD-END CORRIDOR LIMIT: PROHIBITED
• MAXIMUM TRAVEL DISTANCE: PROHIBITED
BUILDING CODE SUMMARY IS BASED ON 2019 FEDERAL FIRE & BUILDING SAFETY CODES INCLUDING
THE FOLLOWING:
INTERNATIONAL BUILDING CODE - IBC-2015
NFPA 101, LIFE SAFETY CODE, 2015 EDITION
2012 ADA STANDARDS FOR ACCESSIBLE DESIGN
CIVIL DRAWINGS
X-1 EXISTING CONDITIONS SITE PLAN
C-1 CIVIL SITE PLAN
M E C H A N I C A L/ E L E C T R I C A L/ F P
S T R U C T U R A L
RICHARD M. DOHERTY, P.E.
595 DORSET STREET, #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-660-8403
C I V I L
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
C O S T E S T I M A T I O N
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578 F: 603-444-2364 www.yeatonassociates.com
TOM BARDEN
BARDEN INSPECTION
AND CONSULTING
196 BALDWIN ROAD
HINESBURG, VERMONT
05461
P: 802-482-6607 F: 802-482-6609
ARCHITECTURAL DRAWINGS
XC-1 EXISTING CONDITIONS FLOOR PLAN, ELEVATIONS AND SECTION
A-1 FLOOR PLAN, REFLECTED CEILING PLAN, WALL TYPES AND DETAILS
A-2 EXTERIOR ELEVATIONS AND BUILDING SECTION
A-3 WALL SECTIONS AND DETAILS
MECHANICAL DRAWINGS
M0.1 MECHANICAL LEGENDS AND NOTES
MD1.1 MECHANICAL DEMOLITION PLAN
M1.1 MECHANICAL FLOOR PLAN DETAILS AND SCHEDULES
ELECTRICAL DRAWINGS
E0.1 ELECTRICAL LEGENDS AND NOTES
E1.1 FLOOR PLANS - DEMOLITION, LIGHTING, POWER AND SYSTEMS
EPH1.1 FLOOR PLAN - PHOTOMETRICS
GEN
OFFICER
FW/CCFW/CVMSG/CC
OG
/C C
MDG
/CC
GEN
OFFICER
FW/CCFW/CVMSG/CC
OG
/C C
MDG
/CC
BASE LOCATION MAP • ALTER B-327 MUNITIONS SHOP
NOT TO SCALE
PROJECT
NORTH
TAXIWAY E
TA
X
IW
A
Y F
N C
O D
R
IV
E
323321 322
N
CO
D
RIV
E
N C
O D
R
IV
E
FA
LCON ST
REET
FAA
TOWERS
NATIONAL
BASE
ENTRANCE
319 300
G U
A
RD
A V
EN
U
E
GATE
HOUSE
HAUL
ROUTE
NORTH
GATE
HOUSE
NORTH
CONSTRUCTION
ENTRANCE
PV ARRAY
TA
X
IW
A
Y F
NOTE: BUILDING 327 IS WITHIN
THE SECURE MUNITIONS FACILITY
AND REQUIRES AN ESCORT MUNITION SECURITY GATE
VEHICULAR ACCESS
RICHARD M. DOHERTY, P.E.
595 DORSET STREET #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-8660-8403
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578
STRUCTURAL
SCALE:
R E V I S I O N S
CHECKED:
DATE:
P R O J E C T
DRAWN: SWH
P: 8 0 2 * 8 6 3 * 2 2 2 7
F: 8 0 2 * 8 6 3 * 0 0 9 3
ALVAR E Z
A R C H I T E C T S
SIENKIEWYCZ
S M I T H
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 05401
MECHANICAL/
ELECTRICAL
X-1
Existing Conditions Site Plan
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
CIVIL
1" = 10'
VERMONT AIR
NATIONAL
GUARD
10/4/2019
SOUTH BURLINGTON,
VERMONT
ALTER B-327
MUNITIONS
SHOP
TOM BARDEN
BARDEN INSPECTION AND
CONSULTING
196 BALDWIN ROAD
HINESBURG, VT 05461
P: 802-482-6607 F: 802-482-6609
COST ESTIMATION:
KL - PROJECT NO: 18295
CURZ: 182803
SAS- PROJECT NO: 1002
AutoCAD SHX Text D
AutoCAD SHX Text Y
AutoCAD SHX Text H
AutoCAD SHX Text
WV
AutoCAD SHX Text S
AutoCAD SHX Text Sewer manhole Rim=330.79'
AutoCAD SHX Text Building 328
AutoCAD SHX Text ff=332.60'x
AutoCAD SHX Text
TB6
AutoCAD SHX Text
TB7
AutoCAD SHX Text
TB8
AutoCAD SHX Text x330.77
AutoCAD SHX Text x330.64
AutoCAD SHX Text
ex. CB
AutoCAD SHX Text 332.5x
AutoCAD SHX Text 332.5x
AutoCAD SHX Text
BUILDING 327
AutoCAD SHX Text D
AutoCAD SHX Text Existing dry well
AutoCAD SHX Text Existing 2" PE gas
AutoCAD SHX Text Abandoned underground power
AutoCAD SHX Text Abandoned underground power
AutoCAD SHX Text Existing 6" PVC sanitary sewer
AutoCAD SHX Text Existing 8" water
AutoCAD SHX Text Equipment pad
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text Existing 2" comm conduit
AutoCAD SHX Text N
AutoCAD SHX Text Vermont State Plane
AutoCAD SHX Text Grid North (NAD83)
AutoCAD SHX Text Legend
AutoCAD SHX Text
314.7 x
AutoCAD SHX Text Notes:
AutoCAD SHX Text
1. This plan is not a boundary survey. The property lines shown are considered This plan is not a boundary survey. The property lines shown are considered approximate. 2. The underground utilities shown on this plan are based on visible utilities located during The underground utilities shown on this plan are based on visible utilities located during a topographic survey performed by Krebs & Lansing in 7/2016 and AutoCAD utility mapping files provided by Vermont Air National Guard. Underground utilities are approximate and not warranted to be exact or complete. Dig Safe, Vermont Air National Guard, and other non-member utilities shall be contacted at least 48 hours prior to any excavation. 3. Elevations are based on the NAVD 88 (Geoid 12A) vertical datum. Elevations are based on the NAVD 88 (Geoid 12A) vertical datum. 4. Project Horizontal Coordinates derived from GPS observation using reference frame Project Horizontal Coordinates derived from GPS observation using reference frame NAD83 (2011) 2010.00 epoch. 5. Site information shown outside of the survey limits was taken from previous plans by Site information shown outside of the survey limits was taken from previous plans by Krebs and Lansing, and is shown with dashed line type and should be considered approximate. 6. Location of monitor wells, air sparge wells, air extraction wells, and process trenches Location of monitor wells, air sparge wells, air extraction wells, and process trenches shown is based on a record drawing AutoCAD file provided by the Vermont Air National Guard and is not warranted to be exact or complete.
AutoCAD SHX Text Existing Overhead Electric Line/Power Pole
AutoCAD SHX Text Existing Overhead Utility
AutoCAD SHX Text Existing Sewer Line/Manhole
AutoCAD SHX Text Existing Storm Line/Manhole/Basin
AutoCAD SHX Text Existing Guardrail
AutoCAD SHX Text Existing Gas Line/Valve
AutoCAD SHX Text Existing Chain Link Fence
AutoCAD SHX Text Existing Water Line/Hydrant/Valve/Shutoff
AutoCAD SHX Text Approximate Property Line
AutoCAD SHX Text
GV
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
WV
AutoCAD SHX Text
AutoCAD SHX Text Survey Control Point
AutoCAD SHX Text Existing Sign
AutoCAD SHX Text Existing Light Pole
AutoCAD SHX Text Existing Deciduous Tree
AutoCAD SHX Text Existing Evergreen Tree
AutoCAD SHX Text Existing Spot Grade Elevation
AutoCAD SHX Text Existing Tree Line
AutoCAD SHX Text Existing Contour
AutoCAD SHX Text
AutoCAD SHX Text Existing Subsurface Process Trench
AutoCAD SHX Text Existing Barbed Wire Fence
AutoCAD SHX Text Existing Stockade Fence
AutoCAD SHX Text Existing Underground Electric
AutoCAD SHX Text Existing Communications Line
AutoCAD SHX Text Existing Site Lite Line
AutoCAD SHX Text mw
AutoCAD SHX Text Monitor Well or Air Sparge Well
AutoCAD SHX Text Soil Vapor Extraction Well
AutoCAD SHX Text mw
AutoCAD SHX Text MPE Well with concrete apron
AutoCAD SHX Text 18295/B327-base.dwg
AutoCAD SHX Text Existing paved areas
AutoCAD SHX Text Existing concrete areas
AutoCAD SHX Text Bar Scale
AutoCAD SHX Text 10'
AutoCAD SHX Text 0'
AutoCAD SHX Text 5'
AutoCAD SHX Text 20'
AutoCAD SHX Text 1" = 10'
AutoCAD SHX Text 30'
AutoCAD SHX Text 40'
AutoCAD SHX Text 50'
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text Existing underground grounding loop
RICHARD M. DOHERTY, P.E.
595 DORSET STREET #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-8660-8403
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578
STRUCTURAL
SCALE:
R E V I S I O N S
CHECKED:
DATE:
P R O J E C T
DRAWN: SWH
P: 8 0 2 * 8 6 3 * 2 2 2 7
F: 8 0 2 * 8 6 3 * 0 0 9 3
ALVAR E Z
A R C H I T E C T S
SIENKIEWYCZ
S M I T H
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 05401
MECHANICAL/
ELECTRICAL
C-1
Civil Site Plan
KL - PROJECT NO: 18295
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
CIVIL
1" = 10'
VERMONT AIR
NATIONAL
GUARD
10/4/2019
SOUTH BURLINGTON,
VERMONT
TOM BARDEN
BARDEN INSPECTION AND
CONSULTING
196 BALDWIN ROAD
HINESBURG, VT 05461
P: 802-482-6607 F: 802-482-6609
COST ESTIMATION:
CURZ: 182803
ALTER B-327
MUNITIONS
SHOP
SAS- PROJECT NO: 1002
AutoCAD SHX Text D
AutoCAD SHX Text Y
AutoCAD SHX Text H
AutoCAD SHX Text
WV
AutoCAD SHX Text Building 328
AutoCAD SHX Text ff=332.60'x
AutoCAD SHX Text
TB6
AutoCAD SHX Text
TB7
AutoCAD SHX Text x330.77
AutoCAD SHX Text x330.64
AutoCAD SHX Text
ex. CB
AutoCAD SHX Text 332.5x
AutoCAD SHX Text
BUILDING 327
AutoCAD SHX Text D
AutoCAD SHX Text Existing dry well
AutoCAD SHX Text Existing 2" PE gas
AutoCAD SHX Text Abandoned underground power
AutoCAD SHX Text Abandoned underground power
AutoCAD SHX Text Existing 6" PVC sanitary sewer
AutoCAD SHX Text Existing 8" water
AutoCAD SHX Text Equipment pad
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text Existing 2" comm conduit
AutoCAD SHX Text N
AutoCAD SHX Text Vermont State Plane
AutoCAD SHX Text Grid North (NAD83)
AutoCAD SHX Text Legend
AutoCAD SHX Text
314.7 x
AutoCAD SHX Text Notes:
AutoCAD SHX Text
1. This plan is not a boundary survey. The property lines shown are considered approximate. This plan is not a boundary survey. The property lines shown are considered approximate. 2. The underground utilities shown on this plan are based on visible utilities located during a The underground utilities shown on this plan are based on visible utilities located during a topographic survey performed by Krebs & Lansing in 7/2016 and AutoCAD utility mapping files provided by Vermont Air National Guard. Underground utilities are approximate and not warranted to be exact or complete. Dig Safe, Vermont Air National Guard, and other non-member utilities shall be contacted at least 48 hours prior to any excavation. 3. Elevations are based on the NAVD 88 (Geoid 12A) vertical datum. Elevations are based on the NAVD 88 (Geoid 12A) vertical datum. 4. Project Horizontal Coordinates derived from GPS observation using reference frame NAD83 Project Horizontal Coordinates derived from GPS observation using reference frame NAD83 (2011) 2010.00 epoch. 5. Site information shown outside of the survey limits was taken from previous plans by Krebs Site information shown outside of the survey limits was taken from previous plans by Krebs and Lansing, and is shown with dashed line type and should be considered approximate. 6. Location of monitor wells, air sparge wells, air extraction wells, and process trenches shown Location of monitor wells, air sparge wells, air extraction wells, and process trenches shown is based on a record drawing AutoCAD file provided by the Vermont Air National Guard and is not warranted to be exact or complete.
AutoCAD SHX Text Existing Overhead Electric Line/Power Pole
AutoCAD SHX Text Existing Overhead Utility
AutoCAD SHX Text Existing Sewer Line/Manhole
AutoCAD SHX Text Existing Storm Line/Manhole/Basin
AutoCAD SHX Text Existing Guardrail
AutoCAD SHX Text Existing Gas Line/Valve
AutoCAD SHX Text Existing Chain Link Fence
AutoCAD SHX Text Existing Water Line/Hydrant/Valve/Shutoff
AutoCAD SHX Text Approximate Property Line
AutoCAD SHX Text
GV
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
WV
AutoCAD SHX Text
AutoCAD SHX Text Survey Control Point
AutoCAD SHX Text Existing Sign
AutoCAD SHX Text Existing Light Pole
AutoCAD SHX Text Existing Deciduous Tree
AutoCAD SHX Text Existing Evergreen Tree
AutoCAD SHX Text Existing Spot Grade Elevation
AutoCAD SHX Text Existing Tree Line
AutoCAD SHX Text Existing Contour
AutoCAD SHX Text
AutoCAD SHX Text Existing Subsurface Process Trench
AutoCAD SHX Text Existing Barbed Wire Fence
AutoCAD SHX Text Existing Stockade Fence
AutoCAD SHX Text Existing Underground Electric
AutoCAD SHX Text Existing Communications Line
AutoCAD SHX Text Existing Site Lite Line
AutoCAD SHX Text mw
AutoCAD SHX Text Monitor Well or Air Sparge Well
AutoCAD SHX Text Soil Vapor Extraction Well
AutoCAD SHX Text mw
AutoCAD SHX Text MPE Well with concrete apron
AutoCAD SHX Text 18295/B327-base.dwg
AutoCAD SHX Text Existing paved areas
AutoCAD SHX Text Existing concrete areas
AutoCAD SHX Text Bar Scale
AutoCAD SHX Text 10'
AutoCAD SHX Text 0'
AutoCAD SHX Text 5'
AutoCAD SHX Text 20'
AutoCAD SHX Text 1" = 10'
AutoCAD SHX Text 30'
AutoCAD SHX Text 40'
AutoCAD SHX Text 50'
AutoCAD SHX Text New underground gas service. Coordinate with Vermont Gas.
AutoCAD SHX Text New Underground gas service
AutoCAD SHX Text Restore all disturbed areas with topsoil, seed, and mulch.
AutoCAD SHX Text gr
AutoCAD SHX Text gr
AutoCAD SHX Text Existing underground grounding loop
AutoCAD SHX Text
CONTRACT LIMIT LINE
Contract Limit Line
N
B-327 FLOOR PLAN
1/4" = 1'-0"
A
XC-1
A
XC-1
1 2 3 4
A
B
POWER PANEL
PHONE
RECESSED FIRE
EXTINGUISHER CABINET
SECURITY PANELS
C O N S U L T A N T S
A R C H I T E C T S
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7
F: 8 0 2 • 8 6 3 • 0 0 9 3
ALVAR E Z
SIENKIEWYCZ
S M I T H
R E V I S I O N S
DATE: 9/1/2019
SCALE: AS NOTED
CHECKED: SS
DRAWN: SAL
P R O J E C T
COPYRIGHT 2017 SMITH ALVAREZ SIENKIEWYCZ ARCHITECTS, PC
CIVIL
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
STRUCTURAL
RICHARD M. DOHERTY, P.E.
595 DORSET STREET, #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-660-8403
MECHANICAL/
ELECTRICAL:
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578
COST ESTIMATION:
TOM BARDEN
BARDEN INSPECTION
AND CONSULTING
196 BALDWIN ROAD
HINESBURG, VERMONT 05461
P: 802-482-6607 F: 802-482-6609
SAS PROJECT NO. 1002
CURZ 182803
ALTER B-327
MUNITIONS
SHOP
VERMONT AIR
NATIONAL
GUARD
SOUTH BURLINGTON,
VERMONT
B-327 BUILDING SECTION A-A
3/8" = 1'-0"
A B
CORRUGATED
METAL SIDING
STANDING SEAM
METAL ROOFING
INSULATION
BATTS/BLANKET W/ VB
STEEL JOIST
OH DOOR
OH DOOR TRACK
POWER PANEL
PHONE
RECESSED FIRE
EXTINGUISHER CABINET
SECURITY PANELS
CONCRETE SLAB ON GRADE CONCRETE FOUNDATION
STEEL GIRT
INSULATION
BATTS/BLANKET W/ VB
STEEL BEAM
DIAGONEL STEEL
TUBE BRACE
STEEL GIRT
CORRUGATED METAL
ROOF DECK
XC-1
EXISTING CONDITIONS
BUILDING 327 PLAN,
ELEVATIONS AND
SECTION
WEST ELEVATION
3/16" = 1'-0"
EAST ELEVATION
3/16" = 1'-0"
PAINTED STEEL DOOR
AND FRAME
CMU BASE
SPEAKER
LOUVER
LIGHT
LOUVER
BUILDING SIGN
CORRUGATED
METAL SIDING
PAINTED METAL
OH DOOR
BOLLARD
METAL TRIM
PAINTED STEEL DOOR
AND FRAME
LIGHT
CORRUGATED
METAL SIDING
METAL TRIM
1 2 3 4 1234
NORTH ELEVATION
3/16" = 1'-0"
SOUTH ELEVATION
3/16" = 1'-0"
CMU BASE
CORRUGATED
METAL SIDING
METAL TRIM
APPROXIMATE GRADE
A B AB
NOTE:
ALL DIMENSIONS AND RELATIONSHIPS OF THE EXISTING
BUILDING ARE APPROXIMATE. THESE DRAWINGS ARE
BASED ON DRAWINGS PROVIDED BY VTANG AND FIELD
MEASUREMENTS BY SAS IN JANUARY OF 2019.
100 101
N
FLOOR PLAN
1/4" = 1'-0"
A
A-2
A
A-2 1 2 3 4
A
B
+/- 18'-0"
- 2
5' -4
+/- 10'-0" +/- 20'-0" +/- 10'-0"
+/- 41'-4"
- 2
6' -8
MUNITIONS SHOP
39'4" x 24'8"
970.22 S.F.
B1
F1 W1
1 TYPICAL
1 ABOVE 2 BELOW
EXISTING 3'x 7' METAL DOOR AND
FRAME TO REMAIN. PREPARE AND
PAINT. REPLACE DOOR SEALS AND
THERMALLY BROKEN ALUMINUM
THRESHOLD. EXISTING HARDWARE
TO REMAIN. TYPICAL OF TWO.
REPLACE 18'-0" WIDE x 10'-0" OH DOOR W/ 2"
INSULATED METAL OH SECTIONAL DOOR,
OVERHEAD DOOR SERIES 592 OR EQUAL.
MATCH EXISTING LITES.
EXISTING STEEL
COLUMNS
EXG.
POWER PANEL
EXG. PHONE
REMOVE, RELOCATE AND
REINSTALL EXG. FULLY
RECESSED FIRE
EXTINGUISHER CABINET.
FE (GFE-GI)
EXG. SECURITY PANELS
A-3
A-3
A-3
AIR HANDLING
UNIT
NOTE: TEMPORARILY
SUPPORT WALL MOUNTED
EQUIPMENT AS REQUIRED TO
MODIFY AND INSULATE THE
WALL. PROVIDE BLOCKING
INSIDE WALL AS REQUIRED
TO SUPPORT EQUIPMENT.
WALL MOUNTED FIRE
EXTINGUISHER.
PROVIDE WALL
BRACKET. FE (GFE-GI)
NEW TELECOM PANEL
CONSTRUCTION
DRAWINGS
C O N S U L T A N T S
A R C H I T E C T S
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7
F: 8 0 2 • 8 6 3 • 0 0 9 3
ALVAR E Z
SIENKIEWYCZ
S M I T H
R E V I S I O N S
DATE: 10/4/2019
SCALE: AS NOTED
CHECKED: SS
DRAWN: SAL
P R O J E C T
COPYRIGHT 2017 SMITH ALVAREZ SIENKIEWYCZ ARCHITECTS, PC
CIVIL
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
STRUCTURAL
RICHARD M. DOHERTY, P.E.
595 DORSET STREET, #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-660-8403
MECHANICAL/
ELECTRICAL:
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578
COST ESTIMATION:
TOM BARDEN
BARDEN INSPECTION
AND CONSULTING
196 BALDWIN ROAD
HINESBURG, VERMONT 05461
P: 802-482-6607 F: 802-482-6609
SAS PROJECT NO. 1002
CURZ 182803
ALTER B-327
MUNITIONS
SHOP
VERMONT AIR
NATIONAL
GUARD
SOUTH BURLINGTON,
VERMONT
A-1
FLOOR PLAN,
REFLECTED CEILING
PLAN, WALL TYPES
AND DETAILS
ROOM FINISH SCHEDULE
FINISH REMARKS
CEILING
C1 GWB TAPE & PAINT
WALLS
W1 GWB TAPE & PAINT
BASE/ TYPE
B1 RUBBER
FLOORS
F1 RESINOUS FLOORING
LEGEND
WALL FINISHES
BASE FINISH
FLOOR FINISH
B1 F1
W1 INDICATES ALL WALLS
WALL TYPE 1
6 SUBDESIGNATION
CEILING FINISH
C1 11'-6" CEILING HEIGHT
DRAWING KEY
NEW CONSTRUCTION
EXISTING CONSTRUCTION TO BE REMOVED
EXISTING CONSTRUCTION TO REMAIN
N
REFLECTED CEILING PLAN
1/4" = 1'-0"
A
A-2
A
A-2 1 2 3 4
A
B
- 2
5' -4
+/- 10'-0" +/- 20'-0" +/- 10'-0"
+/- 41'-4"
- 2
6' -8
MUNITIONS SHOP
39'4" x 24'8"
970.22 S.F.
C1 VARIES
(11'-6"E to 12'-2"W)
REMOVE EXISTING LIGHTS,
SALVAGE AND DELIVER TO
OWNER. INSTALL NEW LED
LIGHTS.
EXISTING STEEL JOISTS
AND BOTTOM CHORD X
BRACING
LINE OF OH DOOR IN
OPEN POSITION
A-3
A-3
A-3
DOOR SCHEDULE
DOOR SIZE DOOR FRAME
NO. WIDTH HEIGHT THK ELEV MAT ELEV MAT HEAD JAMB THR HWD SET REMARKS
100 18'5 1/2" 10'0" 2" 1 INS METAL EXG EXG 8 7 EXG. - REPLACE OH PANEL DOOR
101 3'0" 7'0" 1 3/4" EXG EXG EXG EXG 3 6 4 - REPLACE THRESHOLD AND DOOR SEALS
102 3'0" 7'0" 1 3/4" EXG EXG EXG EXG 3 SIM. 5 4 SIM. - REPLACE THRESHOLD AND DOOR SEALS
DOOR ELEVATIONS
1/4" = 1'-0"
A.
18'0"
REFER TO HARDWARE NOTE #1
REFER TO HARDWARE NOTE #1
HARDWARE NOTE #1: REPLACE DOOR THRESHOLD WITH NGP 315A (OR EQUAL).
REPLACE WEATHER SEALS WITH ZERO 429A (OR EQUAL).
REPLACE DOOR SWEEP WITH ZERO 8198AA (OR EQUAL).
INSULATE EXG. EXT. WALL (R-41)
1 1/2"=1'-0"1
• EXG. CORRUGATED PREFINISHED METAL SIDING
• EXG. 10" STEEL GIRT
• REMOVE EXISTING INTERIOR CORRUGATED METAL WALL PANELS
• REMOVE EXG. LAMINATED FG BATT INSULATION W/ INTEGRAL VB
• 1" SPRAY APPLIED URETHANE INSULATION
• 3 5/8", 20 GA. METAL STUDS @ 16" O.C.
• 9" DENSE PACK CELLULOSE INSULATION
• 5/8" FC GWB, TAPE AND PAINT
INSULATE EXG. EXT. WALL (R-31)
1 1/2"=1'-0"2
• EXG. SCORED SPLIT FACE CMU BASE
• EXG. 8" STEEL FRAMING (ASSUMED, VIF)
• REMOVE EXISTING CORRUGATED METAL WALL PANELS
• REMOVE EXG. LAMINATED FG BATT INSULATION W/ INTEGRAL VB
• 1" SPRAY APPLIED URETHANE INSULATION
• 3 5/8", 20 GA. METAL STUDS @ 16" O.C.
• 7" DENSE PACK CELLULOSE INSULATION
• 5/8" FC GWB, TAPE AND PAINT
8"
FACE OF EXG. CONCRETE
FOUNDATION BELOW
FACE OF EXG. CONCRETE
FOUNDATION BELOW
1/
4"
WALL TYPES
OH DOOR HEAD
3" = 1'-0"8
REPLACE 18'-0" WIDE x
10'-0" HIGH OH DOOR W/ 2"
INSULATED METAL OH
SECTIONAL DOOR,
OVERHEAD DOOR SERIES
592 OR EQUAL. MATCH
EXISTING LITES. REPLACE
TRACK AND MOTER
OPERATOR.
EXISTING STEEL
LINTEL, PAINT
SPRAY URETHANE
AROUND FLANGE OF
STEEL JAMB TO ENCLOSE,
1" MIN. COVER.
REMOVE EXG. SEALANT
AND REPLACE AT
PERIMETER OF DOOR
FRAME
EXG. METAL TRIM
EXG. CORRUGATED
METAL WALL PANELS
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
REMOVE EXG.
LAMINATED FG BATT
INSULATION W/
INTEGRAL VB
1" SPRAY APPLIED
URETHANE
INSULATION
9" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
LINE OF EXG. STEEL
COLUMN BEYOND
COMPRESSIBLE
MINERAL WOOL
FILLER
FIRE SEALANT
OH DOOR TRACK
6" x 18 GA. METAL
HEADER, FILL WITH
RIGID INSULATION
DOOR HEAD
3" = 1'-0"3
EXISTING HM
STEEL DOOR
FRAME, PAINT
EXISTING STEEL
DOOR, PAINT
REMOVE EXG.
SEALANT AND
REPLACE AT
PERIMETER OF
DOOR FRAME
EXG. METAL TRIM
EXG. CORRUGATED
METAL WALL PANELS
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
EXG. 10" STEEL GIRT
REMOVE EXG.
LAMINATED FG BATT
INSULATION W/
INTEGRAL VB1" SPRAY APPLIED
URETHANE
INSULATION
9" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
EXG. WOOD BLOCKING
(ASSUMED, VIF)
2 xWOOD BLOCKING
5/8" GWB RETURN W/
TAPABLE 'L' BEAD
EXG. MASONRY AT
JAMB BEYOND
(METAL AT SIMILAR)
DOOR THRESHOLD
3" = 1'-0"4
EXISTING STEEL
DOOR, PAINT
EXG. MASONRY AT
JAMB BEYOND
(METAL AT SIMILAR)
EXISTING CONCRETE
SLAB
APPROXIMATE GRADE
EXISTING CONCRETE
FLOUNDATION WALL
1/4" x 3" ALUMINUM HALF
SADDLE THRESHOLD
ALUMINUM SWEEP
OH DOOR JAMB
3" = 1'-0"7
DOOR JAMB
3" = 1'-0"6
EXG. SCORED SPLIT
FACE CMU
EXG. 8" STEEL
FRAMING
(ASSUMED, VIF)
REMOVE EXISTING
INTERIOR
CORRUGATED METAL
WALL PANELS
REMOVE EXG.
LAMINATED FG BATT
INSULATION W/
INTEGRAL VB
(ASSUMED)
1" SPRAY APPLIED
URETHANE
INSULATION
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
7" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
REMOVE EXG.
METAL TRIM
5/8" GWB RETURN W/
TAPABLE 'L' BEAD
EXISTING HM STEEL
DOOR FRAME, PAINT
EXISTING STEEL
DOOR, PAINT
REMOVE EXG. SEALANT
AND REPLACE AT
PERIMETER OF DOOR
FRAME
EXG. SCORED SPLIT
FACE CMU
LINE OF EXG.
CORRUGATED STEEL
PANELS ABOVE
LINE OF EXG. CONC.
FOUNDATION BELOW
5/8" FC GWB, TAPE
AND PAINT
EXG. STEEL
COLUMN
EXISTING STEEL
JAMB, PAINT
SPRAY URETHANE
AROUND FLANGE OF
STEEL JAMB TO ENCLOSE,
1" MIN. COVER.
SPRAY URETHANE
AROUND FLANGE OF
STEEL JAMB TO ENCLOSE,
1" MIN. COVER.
COMPRESSIBLE
MINERAL WOOL
FILLER
FIRE SEALANT
OH DOOR TRACK
REPLACE 18'-0" WIDE x 10'-0" HIGH OH
DOOR W/ 2" INSULATED METAL OH
SECTIONAL DOOR, OVERHEAD DOOR
SERIES 592 OR EQUAL. MATCH
EXISTING LITES. REPLACE TRACK
AND MOTER OPERATOR.
REMOVE EXISTING
INTERIOR
CORRUGATED METAL
WALL PANELS
DOOR JAMB
3" = 1'-0"5
EXISTING HM
STEEL DOOR
FRAME, PAINT
EXISTING STEEL
DOOR, PAINT
REMOVE EXG.
SEALANT AND
REPLACE AT
PERIMETER OF
DOOR FRAME
EXG. METAL TRIM
EXG. CORRUGATED
METAL WALL PANELS
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
EXG. 10" STEEL GIRT
REMOVE EXG.
LAMINATED FG BATT
INSULATION W/
INTEGRAL VB1" SPRAY APPLIED
URETHANE
INSULATION
9" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
5/8" GWB RETURN W/
TAPABLE 'L' BEAD
THRESHOLD BELOW
EXG. 10" STEEL
FRAMING
(ASSUMED, VIF)
REMOVE EXISTING
INTERIOR
CORRUGATED METAL
WALL PANELS
REMOVE EXG.
METAL TRIM
TYPICAL DRAWING NOTES
1. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL DIMENSIONS IN THE FIELD AND
WILL PROMPTLY NOTIFY THE ARCHITECT OF ANY DISCREPANCIES. IN THE CASE OF
DISCREPANCIES THE ARCHITECT WILL ISSUE REVISIONS IN WRITING WITHIN SEVEN
CALENDAR DAYS.
2. ALL DIMENSIONS ARE FROM THE FACE OF FRAMING, CMU, CONCRETE, OR EXISTING
FINISH UNLESS OTHERWISE NOTED.
3. REVIEW FINAL LOCATION OF ALL FIRE EXTINGUISHERS IN THE FIELD WITH THE OWNER.
RESINOUS FLOOR TO CONCRETE
Actual Size9
2"
SCHULTER RENO RAMP
K SS TRANSITION
BEHIND OH DOOR
CONCRETE SLAB
RESINOUS FLOOR OH DOOR
CONSTRUCTION
DRAWINGS
C O N S U L T A N T S
A R C H I T E C T S
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7
F: 8 0 2 • 8 6 3 • 0 0 9 3
ALVAR E Z
SIENKIEWYCZ
S M I T H
R E V I S I O N S
DATE: 10/4/2019
SCALE: AS NOTED
CHECKED: SS
DRAWN: SAL
P R O J E C T
COPYRIGHT 2017 SMITH ALVAREZ SIENKIEWYCZ ARCHITECTS, PC
CIVIL
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
STRUCTURAL
RICHARD M. DOHERTY, P.E.
595 DORSET STREET, #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-660-8403
MECHANICAL/
ELECTRICAL:
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578
COST ESTIMATION:
TOM BARDEN
BARDEN INSPECTION
AND CONSULTING
196 BALDWIN ROAD
HINESBURG, VERMONT 05461
P: 802-482-6607 F: 802-482-6609
SAS PROJECT NO. 1002
CURZ 182803
ALTER B-327
MUNITIONS
SHOP
VERMONT AIR
NATIONAL
GUARD
SOUTH BURLINGTON,
VERMONT
A-2
EXTERIOR
ELEVATIONS AND
BUILDING SECTION
WEST ELEVATION
1/4" = 1'-0"
EAST ELEVATION
1/4" = 1'-0"
EXG. SCORED SPLIT
FACE CMU BASE.
CLEAN.
EXG. SPEAKER
EXG. LED LIGHT
FIXTURE TO REMAIN
EXG. BUILDING SIGN
EXG. CORRUGATED
METAL SIDING
EXG. BOLLARD
EXG. METAL TRIM
EXG. CORRUGATED
METAL SIDING
EXG. METAL TRIM
1 2 3 4 1234
EXISTING 3'x 7' METAL DOOR AND
FRAME TO REMAIN. PREPARE AND
PAINT. REPLACE DOOR SEALS AND
THERMALLY BROKEN ALUMINUM
THRESHOLD. EXISTING HARDWARE
TO REMAIN.
REPLACE 18'-0" WIDE x 10'-0" HIGH OH DOOR
W/ 2" INSULATED METAL OH SECTIONAL
DOOR, OVERHEAD DOOR SERIES 592 OR
EQUAL.
EXISTING 3'x 7' METAL DOOR AND
FRAME TO REMAIN. PREPARE AND
PAINT. REPLACE DOOR SEALS AND
THERMALLY BROKEN ALUMINUM
THRESHOLD. EXISTING
HARDWARE TO REMAIN.
APPROXIMATE EXG. GRADE
EXG. FINISH FLOOR
EXG. SIGN
EXG. LOUVER TO REMAIN. ABANDON
IN PLACE. INSTALL 12 GA. PREFINISHED
SHEET METAL CLOSURE PANEL OVER
LOUVER. MATCH EXG. SIDING COLOR.
SET METAL PANEL IN CONTINUOUS
BEAD OF SEALANT AND SCREW TO
FACE OF LOUVER.EXG. LOUVER TO REMAIN.
ABANDON IN PLACE. INSTALL 12
GA. PREFINISHED SHEET METAL
CLOSURE PANEL OVER LOUVER.
MATCH EXG. SIDING COLOR.
SET METAL PANEL IN
CONTINUOUS BEAD OF
SEALANT AND SCREW TO FACE
OF LOUVER.
EXG. LED LIGHT
FIXTURE TO REMAIN
SOUTH ELEVATION
1/4" = 1'-0"
EXG. SCORED, SPLIT FACE
CMU BASE, CLEAN
EXG. CORRUGATED
METAL SIDING
EXG. METAL TRIM
AB
APPROXIMATE EXG. GRADE
EXG. ELECTRICAL ENTRANCE
8' -0
3' -0
A-3
A-3
A-3
BUILDING SECTION A-A
1/2" = 1'-0"
A B
EXG. CORRUGATED
METAL SIDING
EXG. STEEL JOISTS
OH DOOR TRACK
EXG. POWER PANEL
PHONE (GFE-CI)
REMOVE, RELOCATE AND
REINTALL EXG. RECESSED
FIRE EXTINGUISHER
CABINET. FE (GFE-CI)
(EXTIGUISHER IS GFE-GI)
EXG. SECURITY PANELS
EXG. CONCRETE SLAB ON
GRADE, PREPARE AND
EPOXY COAT
EXG. CONCRETE
FOUNDATION
EXG. STEEL GIRT
REMOVE EXG.
INSULATION
BATTS/BLANKET
W/ VB
EXG. STEEL BEAM
EXG. DIAGONAL STEEL
TUBE BRACE BEYOND
EXG. STEEL GIRT
BEYOND
TYPICAL ROOF (R-58)
• EXG. STANDING SEAM PREFINISHED METAL ROOFING
• EXG. 22 GA. 1 1/2", WIDE RIB ROOF DECK (ASSUMED)
• EXG. 14" STEEL JOISTS
• REMOVE EXG. LAMINATED FG BATT INSULATION W/
INTEGRAL VB
• 1" SPRAY IN PLACE URETHANE INSULATION
(SOLID TO 1" BELOW THE BOTTOM OF THE DECK)
(PROVIDE 1" COVER AROUND THE PROFILE OF
THE TOP CHORD OF EACH STEEL JOIST)
• 1 1/2", 20 GA. METAL "Z" FURRING @ 16" O.C.
• 14 1/2" DENSE PACK CELLULOSE INSULATION
• 5/8" FC GWB, TAPE AND PAINT
REMOVE EXG. METAL WALL
PANELS, INSTALL INSULATION
AND GWB
LOUVER IN WALL BEYOND
AIR HANDLING UNIT
FLUES
DUCT, PAINT
LED LIGHT BEYOND
4" RUBBER BASE
LED LIGHT ABOVE OH DOOR
GALV. STEEL OH
SECTIONAL DOOR
NOTE: TEMPORARILY SUPPORT WALL
MOUNTED EQUIPMENT AS REQUIRED
TO MODIFY AND INSULATE THE
WALL. PROVIDE BLOCKING INSIDE
WALL AS REQUIRED TO SUPPORT
EQUIPMENT.
NEW TELECOM
PANEL
3/4" PWD BACKBOARD,
PAINT
6' -8
4' -0
+/- 9'-6"
5' -0
NORTH ELEVATION
1/4" = 1'-0"
EXG. SCORED, SPLIT FACE
CMU BASE, CLEAN
EXG. CORRUGATED
METAL SIDING
EXG. METAL TRIM
A B
APPROXIMATE EXG. GRADE
PREFINISHED METAL
LOUVER. MATCH SIDING
COLOR
PREFINISHED METAL
PANEL AT BOILER FLUES.
MATCH SIDING COLOR
EXISTING METAL TRIM
EXISTING WOOD
BLOCKING (ASSUMED)
EXISTING STEEL BEAM
3"x 3" x 20 GA. CONT.
STEEL CLIP ANGLE FOR
GWB ATTACHMENT
EXG. STEEL BOTTOM
CHORD BRACING
EXISTING CONCRETE
FOUNDATION AND
FOOTING (ASSUMED,
DEPTH UNKNOWN)
APPROXIMATE
EXISTING GRADE
WALL SECTION 3
1" = 1'-0"3
EXISTING STEEL GIRT
EXISTING STEEL ANGLE
(ASSUMED). SPRAY URETHANE
AROUND ANGLE TO ENCLOSE,
1" MIN. COVER.
A-3
EXISTING STEEL ANGLE
(ASSUMED). SPRAY URETHANE
AROUND ANGLE TO ENCLOSE,
1" MIN. COVER.
EXISTING METAL TRIM
EXISTING WOOD
BLOCKING (ASSUMED)
EXISTING STEEL BEAM
3"x 3" x 20 GA. CONT.
STEEL CLIP ANGLE FOR
GWB ATTACHMENT
EXG. STEEL BOTTOM
CHORD BRACING
EXISTING CONCRETE
FOUNDATION AND
FOOTING (ASSUMED,
DEPTH UNKNOWN)
APPROXIMATE
EXISTING GRADE
WALL SECTION 2
1" = 1'-0"2
CONSTRUCTION
DRAWINGS
C O N S U L T A N T S
A R C H I T E C T S
1 1 7 S t. P a u l S t r e e t 3 r d F l o o r
B u r l i n g t o n, V T 0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7
F: 8 0 2 • 8 6 3 • 0 0 9 3
ALVAR E Z
SIENKIEWYCZ
S M I T H
R E V I S I O N S
DATE: 10/4/2019
SCALE: AS NOTED
CHECKED: SS
DRAWN: SAL
P R O J E C T
COPYRIGHT 2017 SMITH ALVAREZ SIENKIEWYCZ ARCHITECTS, PC
CIVIL
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375 F: 802-878-9618
STRUCTURAL
RICHARD M. DOHERTY, P.E.
595 DORSET STREET, #6
SO. BURLINGTON, VT
05403 P: 802-660-9212 F: 802-660-8403
MECHANICAL/
ELECTRICAL:
YEATON ASSOCIATES
66 JACKSON ST.
LITTLETON, NH 03561
P: 603-444-6578
COST ESTIMATION:
TOM BARDEN
BARDEN INSPECTION
AND CONSULTING
196 BALDWIN ROAD
HINESBURG, VERMONT 05461
P: 802-482-6607 F: 802-482-6609
SAS PROJECT NO. 1002
CURZ 182803
ALTER B-327
MUNITIONS
SHOP
VERMONT AIR
NATIONAL
GUARD
SOUTH BURLINGTON,
VERMONT
A-3
WALL SECTIONS
AND DETAILS
TYPICAL ROOF (R-58)
• EXG. STANDING SEAM PREFINISHED METAL ROOFING
• EXG. 22 GA. 1 1/2", WIDE RIB ROOF DECK (ASSUMED)
• EXG. 14" STEEL JOISTS W/ STRAPPING ABOVE
• REMOVE EXG. LAMINATED FG BATT INSULATION
W/ INTEGRAL VB
• 1" SPRAY IN PLACE URETHANE INSULATION
(SOLID TO 1" BELOW THE BOTTOM OF THE DECK)
(PROVIDE 1" COVER AROUND THE PROFILE OF
THE TOP CHORD OF EACH STEEL JOIST)
• 1 1/2", 20 GA. METAL "Z" FURRING @ 16" O.C.
• 14 1/2" DENSE PACK CELLULOSE INSULATION
• 5/8" FC GWB, TAPE AND PAINT
EXISTING STEEL ANGLE
(ASSUMED). SPRAY
URETHANE AROUND
ANGLE TO ENCLOSE, 1"
MIN. COVER.
EXISTING METAL TRIM
EXISTING WOOD
BLOCKING (ASSUMED)
EXISTING STEEL BEAM
3"x 3" x 20 GA. CONT.
STEEL CLIP ANGLE FOR
GWB ATTACHMENT
EXG. STEEL BOTTOM
CHORD BRACING
EXISTING STEEL GIRT
REMOVE EXISTING INTERIOR METAL WALL
PANELS FROM GIRT TO FLOOR. FRAMING AND
SUPPORT FOR THE EXISTING INTERIOR METAL
WALL PANELS IS UNKNOWN. REMOVE EXG.
FRAMING AND SUPPORTS IF IT INTERFERES
WITH THE NEW WALL SYSTEM FRAMING.
REVIEW IN FIELD WITH THE ARCHITECT
AFTER DEMOLITION IS COMPLETE.
REMOVE EXG. LAMINATED FG BATT
INSULATION W/ INTEGRAL VB,
ASSUMED TO EXISTING BEHIND THE
EXISTING METAL WALL PANELS
EXISTING STEEL BASE
ANGLE (ASSUMED)
EXISTING METAL
BASE TRIM
EXISTING METAL
WALL PANELS
EXISTING CONCRETE SLAB ON
GRADE. CLEAN AND PREPARE SLAB
FOR EPOXY COATING
4" RUBBER BASE
EXISTING CONCRETE
FOUNDATION AND
FOOTING (ASSUMED,
DEPTH UNKNOWN)
APPROXIMATE
EXISTING GRADE
WALL SECTION 1
1" = 1'-0"1
A-3
FLUE/PIPE PENETRATION
3" = 1'-0"4
EXG. CORRUGATED
METAL WALL PANELS,
CUT AS REQUIRED FOR
NEW WALL PENETRATION
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
REMOVE EXG.
LAMINATED FG BATT
INSULATION W/
INTEGRAL VB
1" SPRAY APPLIED
URETHANE
INSULATION
9" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
2" 3"
REMOVE EXG. INTERIOR
CORRUGATED METAL
WALL PANELS
PIPE PENETRATION
ESCUTCHEON
SEALANT
NOTE: EXTERIOR TRIM MUST
BE INSTALLED BEFORE THE
WALL INSULATION AND
INTERIOR WALL FINISH IS
INSTALLED. SET MOUNTING
PLATE AND 'J' TRIM BEHIND
THE EXISTING CORRUGATED
WALL PANEL AS SHOWN, RIVET
FROM THE EXTERIOR.
WALL CAP. SET IN CONT. BEAD OF
SEALANT. PROVIDE WEATHERTIGHT
INSTALLATION. PROVIDE EXTERIOR
ESCUTCHEAN AT SIMILAR GAS PIPE
PENTRATION.
1/
2"
14 GA. PREFINISHED METAL
FLAT MOUNTING PLATE
PREFINISHED 'J' TRIM AT
PERIMETER. MATCH SIDING
COLOR. PROVIDE WEEP HOLES
AT HEAD TRIM
CONT. BEAD OF SEALANT
BETWEEN MOUNTING PLATE
AND 'J' TRIM
LOUVER JAMB
3" = 1'-0"5
EXG. CORRUGATED
METAL WALL PANELS,
CUT AS REQUIRED FOR
NEW WALL PENETRATION
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
REMOVE EXG.
LAMINATED FG BATT
INSULATION W/
INTEGRAL VB
1" SPRAY APPLIED
URETHANE
INSULATION
9" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
REMOVE EXG. INTERIOR
CORRUGATED METAL
WALL PANELS
PREFINISHED 'J' TRIM W/ CLIP AT
LOW RIB. RIVET TO HIGH RIBS.
MATCH SIDING COLOR.
10", 20 GA. METAL
STUDS
DUCT
BACKER ROD AND SEALANT
PREFINISHED METAL
LOUVER WITH INSECT
SCREEN
1/
2"
CLIP ANGLES
LOUVER HEAD AND SILL
3" = 1'-0"6
EXG. CORRUGATED METAL WALL
PANELS, CUT AS REQUIRED FOR
NEW WALL PENETRATION
REMOVE EXG. LAMINATED FG
BATT INSULATION W/
INTEGRAL VB
1" SPRAY APPLIED
URETHANE
INSULATION
9" DENSE PACK
CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
PREFINISHED METAL SILL TRIM.
MATCH SIDING COLOR.
BACKER ROD AND SEALANT
PREFINISHED METAL 'J' TRIM
W/ WEEP HOLES. MATCH
SIDING COLOR.
10", 20 GA. METAL
STUDS
DUCT
PREFINISHED METAL
LOUVER WITH INSECT
SCREEN
CLIP ANGLES
PREFINISHED METAL DRIP
EDGE. MATCH SIDING COLOR.
NOTE: EXTERIOR HEAD TRIM
MUST BE INSTALLED BEFORE
THE FRAMING, INSULATION
AND INTERIOR WALL FINISH IS
INSTALLED. SET 'J' TRIM AND
DRIP EDGE BEHIND THE
EXISTING CORRUGATED WALL
PANEL AS SHOWN, RIVET FROM
THE EXTERIOR.
3"
1/
2"
4"
1"
1/
2" 1"
1/ 4"
NOTE: EXTERIOR SILL TRIM
MUST BE INSTALLED BEFORE
THE FRAMING, INSULATION
AND INTERIOR WALL FINISH IS
INSTALLED. SET BACK PLATE
BEHIND THE EXISTING
CORRUGATED WALL PANEL AS
SHOWN, RIVET FROM THE
EXTERIOR. RIVET SILL TRIM
TO BACK PLATE AS SHOWN.
PREFINISHED METAL BACK
PLATE. MATCH SIDING COLOR.
WALL DETAIL
3" = 1'-0"7
EXISTING STEEL GIRT
EXG. CORRUGATED
METAL WALL PANELS
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
REMOVE EXG. LAMINATED
FG BATT INSULATION W/
INTEGRAL VB
1" SPRAY APPLIED URETHANE
INSULATION. PROVIDE 1" MIN.
COVER AT GIRT
9" DENSE PACK CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
7" DENSE PACK CELLULOSE
INSULATION
EXG. METAL DRIP EDGE
EXG. SPLIT FACE CMU VENEER
EXISTING WOOD
BLOCKING, ASSUMED
1" SPRAY APPLIED URETHANE
INSULATION
REMOVE AND REPLACE
BACKER ROD AND SEALANT
WALL DETAIL
3" = 1'-0"8
EXISTING STEEL GIRT
EXG. CORRUGATED
METAL WALL PANELS
3 5/8", 20 GA. METAL
STUDS @ 16" O.C.
REMOVE EXG. LAMINATED
FG BATT INSULATION W/
INTEGRAL VB
1" SPRAY APPLIED URETHANE
INSULATION. PROVIDE 1" MIN.
COVER AT GIRT
9" DENSE PACK CELLULOSE
INSULATION
5/8" FC GWB, TAPE
AND PAINT
EXISTING WOOD
BLOCKING, ASSUMED
REMOVE EXG. INTERIOR
METAL WALL PANELS
A R C H I T E C T S
1 1 7 S t. P a u l S t r e e t
3 r d F l o o r
B u r l i n g t o n, V T
0 5 4 0 1
P: 8 0 2 • 8 6 3 • 2 2 2 7
F: 8 0 2 • 8 6 3 • 0 0 9 3
ALVAR E Z
SIENKIEWYCZ
S M I T H
R E V I S I O N S
P R O J E C T
DATE: 10/04/2019
SCALE: AS NOTED
CHECKED:
DRAWN:
CIVIL
KREBS & LANSING
164 MAIN ST.
COLCHESTER, VT 05446
P: 802-878-0375
F: 802-878-9618
STRUCTURAL
RICHARD M. DOHERTY, P.E.
595 DORSET STREET, #6
SO. BURLINGTON, VT
05403
P: 802-660-9212
F: 802-660-8403
MECHANICAL/
ELECTRICAL:
YEATON ASSOCIATES
646 Union Street - Suite 200
Littleton, NH 03561 P: 603-444-6578
YA#19V03ME
COST ESTIMATION:
TOM BARDEN
BARDEN INSPECTION
AND CONSULTING
196 BALDWIN ROAD
HINESBURG, VERMONT 05461
P: 802-482-6607
F: 802-482-6609
SAS PROJECT NO. 1002
CURZ 182803
ALTER B-327
MUNITIONS
SHOP
VERMONT AIR
NATIONAL
GUARD
SOUTH BURLINGTON,
VERMONT
ST
A T E O F V ERMONT
P R
O
F E S S I O N A L E N G IN
EE
R
R E G I S T E R
E D
NO. 5915
W A
YNE G. FILLIO
N
MECHANICAL
LEGENDS & NOTES
M0.1
RCN
RCN
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
AUTOMATIC CONTROL VALVE (2-WAY)
AutoCAD SHX Text
STRAINER WITH BLOWDOWN
AutoCAD SHX Text
SQUARE ELBOW W/TURNING VANES (T.V.)
AutoCAD SHX Text
EQUIPMENT TAG / MBH HEAT
AutoCAD SHX Text
RETURN DUCT
AutoCAD SHX Text
GRILLE, REG., DIFF. & LOUVER SYMBOL
AutoCAD SHX Text G
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
THERMOSTAT PER SPEC.
AutoCAD SHX Text
CONN. POINT OF NEW WORK TO EXISTING
AutoCAD SHX Text
THERMOSTAT WITH GUARD
AutoCAD SHX Text
SMOKE DETECTOR (FOR EQUIP. SHUTDOWN)
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
PRESSURE RELIEF VALVE
AutoCAD SHX Text
AUTO BALANCING VALVE
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
ACV
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
UNION
AutoCAD SHX Text
DIRECTION OF FLOW (WATER)
AutoCAD SHX Text
CONCENTRIC REDUCER
AutoCAD SHX Text
ECCENTRIC REDUCER
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
PIPE RISE
AutoCAD SHX Text
PIPE DROP
AutoCAD SHX Text
SUPPLY DUCT
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
DIRECTION OF FLOW (AIR)
AutoCAD SHX Text
SELF-CONTAINED VALVE
AutoCAD SHX Text
SCV
AutoCAD SHX Text
EXHAUST DUCT
AutoCAD SHX Text ACD AD AFF A.L. APD ATC CFM C.M. CTE (E) EA EAT E.C. EF ESP EWT FAI FC FD F.O. FPM FTR G.C. GPM H.C. HP LAT LWT MBH MOD M.C. N.C. N.I.C. N.O. NTS OA P.C. RA RPM SA SCT SCV SD TSP TYP. U/C UH VD WPD WTD WTR
AutoCAD SHX Text AUTOMATIC CONTROL DAMPER ACCESS DOOR ABOVE FINISHED FLOOR ACOUSTICALLY LINED AIR PRESSURE DROP AUTOMATIC TEMPERATURE CONTROL CUBIC FEET PER MINUTE CONSTRUCTION MANAGER CONNECT TO EXISTING EXISTING EXHAUST AIR ENTERING AIR TEMPERATURE ELECTRICAL CONTRACTOR EXHAUST FAN EXTERNAL STATIC PRESSURE ENTERING WATER TEMPERATURE FRESH AIR INTAKE FLEX CONNECTION FIRE DAMPER FLAT OVAL FEET PER MINUTE FIN-TUBE RADIATION GENERAL CONTRACTOR GALLONS PER MINUTE HARDWARE CLOTH HORSEPOWER LEAVING AIR TEMPERATURE LEAVING WATER TEMPERATURE THOUSAND BTU'S PER HOUR MOTOR OPERATED DAMPER MECHANICAL CONTRACTOR NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN NOT TO SCALE OUTSIDE AIR PLUMBING CONTRACTOR RETURN AIR REVOLUTIONS PER MINUTE SUPPLY AIR SELF-CONTAINED THERMOSTAT SELF-CONTAINED THERMOSTATIC VALVE SMOKE DAMPER TOTAL STATIC PRESSURE TYPICAL UNDER CUT DOOR UNIT HEATER VOLUME DAMPER WATER PRESSURE DROP WATER TEMPERATURE DROP WATER TEMPERATURE RISE
AutoCAD SHX Text
CIRCUIT SETTER (C.S./SHUTOFF VALVE)
AutoCAD SHX Text
GENERAL MECHANICAL WORK NOTES
AutoCAD SHX Text
1. ALL EQUIPMENT AND DUCTWORK SHOWN DIAGRAMMATICALLY ONLY. EXACT ALL EQUIPMENT AND DUCTWORK SHOWN DIAGRAMMATICALLY ONLY. EXACT LOCATION TO BE DETERMINED AND COORDINATED IN THE FIELD BY ALL TRADES INVOLVED. 2. COORDINATE ALL GRILLE AND DIFFUSER LOCATIONS WITH ARCHITECT'S COORDINATE ALL GRILLE AND DIFFUSER LOCATIONS WITH ARCHITECT'S REFLECTED CEILING PLANS. 3. WATERPROOF BOTTOM AND SIDES OF ALL INTAKE, EXHAUST AND RELIEF WATERPROOF BOTTOM AND SIDES OF ALL INTAKE, EXHAUST AND RELIEF PLENUMS. 4. SEAL ALL DUCTWORK PENETRATIONS THRU FIRE RATED AND NON-RATED SEAL ALL DUCTWORK PENETRATIONS THRU FIRE RATED AND NON-RATED SMOKE PARTITIONS, WALLS AND FLOORS PER SPEC. SECTION 07841. 5. FLEXIBLE DUCTS NOT TO BE OVER 6 FEET LONG WITH APPROVED TRANSITIONS FLEXIBLE DUCTS NOT TO BE OVER 6 FEET LONG WITH APPROVED TRANSITIONS AND SMOOTH BENDS TO TERMINAL CONNECTIONS. 6. PITCH DUCT CONNECTIONS TO LOUVERS TO DRAIN TOWARD LOUVER. PITCH DUCT CONNECTIONS TO LOUVERS TO DRAIN TOWARD LOUVER. 7. FLEX DUCT TO MATCH RUNOUT SIZE UNLESS NOTED OTHERWISE. FLEX DUCT TO MATCH RUNOUT SIZE UNLESS NOTED OTHERWISE. 8. FLEX DUCT SHALL NOT EXCEED 5'-0" IN LENGTH. FLEX DUCT SHALL NOT EXCEED 5'-0" IN LENGTH. 9. MOUNTING HEIGHTS FOR THERMOSTATS, EQUIPMENT ON/OFF SWITCHES, ETC., MOUNTING HEIGHTS FOR THERMOSTATS, EQUIPMENT ON/OFF SWITCHES, ETC., LOCATED IN HANDICAP ACCESSIBLE SPACES SHALL BE 48" TO TOP OF CONTROL UNLESS NOTED OTHERWISE BY ARCHITECT. REFER TO ARCHITECTURAL ELEVATIONS FOR FURTHER DETAILS. 10. ALL EQUIPMENT AND PIPING SHOWN DIAGRAMMATICALLY ONLY. EXACT LOCATION ALL EQUIPMENT AND PIPING SHOWN DIAGRAMMATICALLY ONLY. EXACT LOCATION TO BE DETERMINED AND COORDINATED IN THE FIELD BY ALL TRADES INVOLVED. 11. ALL ROUGH OPENINGS THRU EXTERIOR WALLS SHALL BE SEALED/CAULKED ALL ROUGH OPENINGS THRU EXTERIOR WALLS SHALL BE SEALED/CAULKED WATERTIGHT WITH ELASTOMERIC SEALANT. 12. REFER TO SPEC. SECTION 07841 FOR ALL FIRE STOPPING REQUIREMENTS.REFER TO SPEC. SECTION 07841 FOR ALL FIRE STOPPING REQUIREMENTS.
AutoCAD SHX Text
1. NOTES BELOW ARE NOT INTENDED TO REPLACE SPECIFICATIONS. SEE SPECIFICATIONS FOR REQUIREMENTS IN NOTES BELOW ARE NOT INTENDED TO REPLACE SPECIFICATIONS. SEE SPECIFICATIONS FOR REQUIREMENTS IN ADDITION TO GENERAL NOTES. 2. CONTRACTOR SHALL VISIT THE SITE AND BECOME INFORMED AS TO THE NATURE AND SCOPE OF WORK REQUIRED CONTRACTOR SHALL VISIT THE SITE AND BECOME INFORMED AS TO THE NATURE AND SCOPE OF WORK REQUIRED BY CONTRACT DOCUMENTS PRIOR TO BIDDING PROJECT. 3. PROVIDE ALL REQUIRED MATERIALS, LABOR, EQUIPMENT, AND SERVICES NECESSARY FOR THE INSTALLATION OF THE PROVIDE ALL REQUIRED MATERIALS, LABOR, EQUIPMENT, AND SERVICES NECESSARY FOR THE INSTALLATION OF THE WORK AS SHOWN ON THESE DRAWINGS OR SPECIFIED BY THE BASE BUILDING DRAWING AND SPECIFICATIONS. 4. REFER TO AND CAREFULLY CHECK ARCHITECTURAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS AND REFER TO AND CAREFULLY CHECK ARCHITECTURAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS AND DETAILS, NOTES, LOCATIONS WHERE WALLS, PARTITIONS, CEILINGS, AND OTHER SURFACES ARE FURRED, LOCATIONS OF SHAFTS, SOFFITS, AND CONFLICTS WITH WORK OF OTHER TRADES, AND ARRANGE WORK ACCORDINGLY. FURNISH ALL OFFSETS, DAMPERS, CONNECTORS, ETC., REQUIRED TO MEET SUCH CONDITIONS. 5. DUE TO SCALE OF DRAWINGS, ALL REQUIRED OFFSETS, DAMPERS, ETC., MAY NOT BE INDICATED. DUE TO SCALE OF DRAWINGS, ALL REQUIRED OFFSETS, DAMPERS, ETC., MAY NOT BE INDICATED. 6. COORDINATE DIFFUSERS LOCATIONS AND DUCT WITH LIGHTING FIXTURES AND SPRINKLER HEADS. SEE COORDINATE DIFFUSERS LOCATIONS AND DUCT WITH LIGHTING FIXTURES AND SPRINKLER HEADS. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND DETAILS OF PARTITIONS, SUSPENDED CEILINGS, AND SOFFITS. 7. ALL DUCT PASSING THROUGH FIRE, SMOKE RATED OR SMOKE/FIRE RATED BARRIERS (WALLS, FLOOR) SHALL BE ALL DUCT PASSING THROUGH FIRE, SMOKE RATED OR SMOKE/FIRE RATED BARRIERS (WALLS, FLOOR) SHALL BE PROVIDED WITH FIRE, SMOKE OR SMOKE/FIRE DAMPERS. LOCATIONS OR RATED WALLS SEE ARCHITECTURAL DRAWINGS. CONTRACTOR SHALL VERIFY QUANTITY OF ALL DAMPERS IN ACCORDANCE WITH FINAL CONTRACT DOCUMENTS. ALL REQUIRED SMOKE DETECTORS PROVIDED BY DIV 23 SHALL BE CONNECTED TO FIRE ALARM SYSTEM. 8. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND ARRANGE FOR ALL REQUIRED INSPECTIONS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND ARRANGE FOR ALL REQUIRED INSPECTIONS IN ACCORDANCE WITH STATE AND LOCAL GOVERNING CODES. 9. THE TERM "PROVIDE" SHALL MEAN "TO FURNISH, INSTALL, AND CONNECT COMPLETELY". THE TERM "PROVIDE" SHALL MEAN "TO FURNISH, INSTALL, AND CONNECT COMPLETELY". 10. TURN OVER TO THE OWNER ALL MANUFACTURER'S WARRANTIES FOR EQUIPMENT AND MATERIALS PROVIDED. TURN OVER TO THE OWNER ALL MANUFACTURER'S WARRANTIES FOR EQUIPMENT AND MATERIALS PROVIDED. 11. WHERE THE CONTRACTOR PROPOSES TO USE AN ITEM OF EQUIPMENT OTHER THAN THAT SPECIFIED OR DETAILED WHERE THE CONTRACTOR PROPOSES TO USE AN ITEM OF EQUIPMENT OTHER THAN THAT SPECIFIED OR DETAILED ON THE DRAWINGS WHICH REQUIRES ANY REDESIGN OF THE STRUCTURE, PARTITIONS, FOUNDATIONS, PIPING, WIRING OR ANY OTHER PART OF THE MECHANICAL, ELECTRICAL OR ARCHITECTURAL LAYOUT, ALL SUCH REDESIGN AND ALL NEW DRAWINGS AND DETAILING REQUIRED THEREFORE, SHALL BE PREPARED AT THE CONTRACTOR'S EXPENSE AND ARE SUBJECT TO THE REVIEW AND APPROVAL OF THE OWNER OR HIS AUTHORIZED REPRESENTATIVE. OWNER RESERVES THE RIGHT TO HAVE THE ARCHITECT OR ENGINEER OF HIS CHOICE PREPARE ANY REDESIGN WORK. 12. CONTRACTOR SHALL COORDINATE ELECTRICAL REQUIREMENTS OF MECHANICAL EQUIPMENT WITH DIVISION 26. CONTRACTOR SHALL COORDINATE ELECTRICAL REQUIREMENTS OF MECHANICAL EQUIPMENT WITH DIVISION 26. 13. ALL WORK SHALL BE DONE WITH LICENSED WORKMEN IN ACCORDANCE WITH STATE AND LOCAL GOVERNING ALL WORK SHALL BE DONE WITH LICENSED WORKMEN IN ACCORDANCE WITH STATE AND LOCAL GOVERNING AUTHORITIES. 14. BEFORE SELECTING MATERIAL AND EQUIPMENT, AND PROCESSING THE WORK, INSPECT AREAS WHERE MATERIAL AND BEFORE SELECTING MATERIAL AND EQUIPMENT, AND PROCESSING THE WORK, INSPECT AREAS WHERE MATERIAL AND EQUIPMENT ARE TO BE INSTALLED TO INSURE SUITABILITY AND CHECK NEEDED SPACE FOR PLACEMENT AND CLEARANCES. 15. BEFORE CUTTING AND DRILLING INTO BUILDING ELEMENTS, INSPECT AND LAYOUT WORK TO AVOID DAMAGING BEFORE CUTTING AND DRILLING INTO BUILDING ELEMENTS, INSPECT AND LAYOUT WORK TO AVOID DAMAGING STRUCTURAL ELEMENTS AND BUILDING UTILITIES. 16. CONTRACTOR RESPONSIBLE FOR REPAIR AND PAYMENT FOR ALL UTILITIES DAMAGE DURING CONSTRUCTION. CONTRACTOR RESPONSIBLE FOR REPAIR AND PAYMENT FOR ALL UTILITIES DAMAGE DURING CONSTRUCTION. 17. CONTRACTOR TO CONFIRM DUCTWORK LOCATIONS, ELEVATIONS AND SIZES BEFORE ANY WORK IS STARTED. IF ANY CONTRACTOR TO CONFIRM DUCTWORK LOCATIONS, ELEVATIONS AND SIZES BEFORE ANY WORK IS STARTED. IF ANY DISCREPANCIES ARE FOUNDED, NOTIFY ENGINEER BEFORE PROCEEDING WITH WORK. (SEE "COORDINATION DRAWINGS"). 18. FOLLOW MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF PROVIDED EQUIPMENT. FOLLOW MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF PROVIDED EQUIPMENT. 19. CONTRACTOR TO REPLACE ALL SUSPENDED CEILING TILES DAMAGED AS A RESULT OF HVAC SYSTEM INSTALLATION. CONTRACTOR TO REPLACE ALL SUSPENDED CEILING TILES DAMAGED AS A RESULT OF HVAC SYSTEM INSTALLATION. 20. ALL SHOP DRAWINGS OF INDIVIDUAL COMPONENTS ARE TO BE SUBMITTED AS A COMPLETE PACKAGE. ALL SHOP DRAWINGS OF INDIVIDUAL COMPONENTS ARE TO BE SUBMITTED AS A COMPLETE PACKAGE. 21. HVAC DRAWINGS DO NOT NECESSARY SHOW ALL CONDITIONS OF BUILDING. CONTRACTOR TO USE ALL DRAWINGS HVAC DRAWINGS DO NOT NECESSARY SHOW ALL CONDITIONS OF BUILDING. CONTRACTOR TO USE ALL DRAWINGS AND SPECIFICATIONS OF CONTRACT DOCUMENTS AND INSPECTION OF FIELD CONDITIONS FOR DIVISION 23. 22. HVAC PLANS, DETAILS AND ONE LINE DIAGRAMS SHOW THE GENERAL LOCATION AND ARRANGEMENT OF THE HVAC PLANS, DETAILS AND ONE LINE DIAGRAMS SHOW THE GENERAL LOCATION AND ARRANGEMENT OF THE SYSTEM. THESE ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, HANGERS, ACCESS DOORS, ETC. WHICH THE CONTRACTOR MUST PROVIDE TO COMPLETE THE SYSTEM. 23. ALL WORK IN INTERIOR FINISHED SPACES EXCEPT INDICATED IS TO BE CONCEALED ABOVE CEILING. PROVIDE ALL ALL WORK IN INTERIOR FINISHED SPACES EXCEPT INDICATED IS TO BE CONCEALED ABOVE CEILING. PROVIDE ALL NECESSARY CUTTING, PATCHING, REPAINTING AND/OR REPLACEMENT OF FINISHES AS REQUIRED TO PERFORM COORDINATE WITH OTHER DIVISIONS. 24. IF MANUFACTURER OF EQUIPMENT REQUIRES LARGER CAPACITY CIRCUITRY AND/OR EQUIPMENT THE CONTRACTOR IF MANUFACTURER OF EQUIPMENT REQUIRES LARGER CAPACITY CIRCUITRY AND/OR EQUIPMENT THE CONTRACTOR SHALL PROVIDE SUCH CAPACITY AND/OR EQUIPMENT UNDER THIS CONTRACT AT NO COST TO THE OWNER. 25. SUPPORT DUCTWORK ABOVE SUSPENDED CEILING FROM CONSTRUCTION ABOVE AS CLOSE AS POSSIBLE TO BOTTOM SUPPORT DUCTWORK ABOVE SUSPENDED CEILING FROM CONSTRUCTION ABOVE AS CLOSE AS POSSIBLE TO BOTTOM OF SLABS, BEAMS, MAINTAINING HEADROOM AT ALL TIMES. 26. DO NOT SCALE DRAWINGS. CHECK EXISTING SPACE CONDITIONS AT THE JOB SITE. DO NOT SCALE DRAWINGS. CHECK EXISTING SPACE CONDITIONS AT THE JOB SITE. 27. ALL DUCTWORK SHALL BE HUNG FROM STRUCTURE ABOVE. ALL DUCTWORK SHALL BE HUNG FROM STRUCTURE ABOVE. 28. PROVIDE FLEXIBLE CONNECTIONS BETWEEN MECHANICAL EQUIPMENT AND DUCTWORK AND PIPING. PROVIDE FLEXIBLE CONNECTIONS BETWEEN MECHANICAL EQUIPMENT AND DUCTWORK AND PIPING. 29. PROVIDE VOLUME DAMPERS ON ALL BRANCHES OF DUCTWORK (SUPPLY, RETURN, EXHAUST). PROVIDE VOLUME DAMPERS ON ALL BRANCHES OF DUCTWORK (SUPPLY, RETURN, EXHAUST). 30. FLEXIBLE DUCTWORK CONNECTIONS ALLOWED FOR ALL CEILING MOUNTED SUPPLY DIFFUSERS. (MAXIMUM 3'-0" FLEXIBLE DUCTWORK CONNECTIONS ALLOWED FOR ALL CEILING MOUNTED SUPPLY DIFFUSERS. (MAXIMUM 3'-0" LONG). 31. REFER TO SPECIFICATION SECTION 078413 "THROUGH PENETRATION FIRESTOP SYSTEMS" FOR ALL MATERIALS AND REFER TO SPECIFICATION SECTION 078413 "THROUGH PENETRATION FIRESTOP SYSTEMS" FOR ALL MATERIALS AND METHODS FOR PENETRATION THROUGH FIRE AND SMOKE RATED ASSEMBLIES. 32. ALL PENETRATIONS THRU WALLS, ROOF, AND FLOORS TO BE COORDINATED BEFORE SITE WORK EXECUTION WITH ALL PENETRATIONS THRU WALLS, ROOF, AND FLOORS TO BE COORDINATED BEFORE SITE WORK EXECUTION WITH STRUCTURAL ENGINEERS. 33. THERMOSTAT AND TEMPERATURE SENSOR LOCATIONS TO BE COORDINATED WITH INTERIOR WALL LAYOUT, REFER TO THERMOSTAT AND TEMPERATURE SENSOR LOCATIONS TO BE COORDINATED WITH INTERIOR WALL LAYOUT, REFER TO ARCHITECTURAL PLANS. 34. CEILING DIFFUSER AND REGISTER LOCATIONS TO BE COORDINATED WITH CEILING GRID, LIGHTING & SPRINKLER CEILING DIFFUSER AND REGISTER LOCATIONS TO BE COORDINATED WITH CEILING GRID, LIGHTING & SPRINKLER LAYOUT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN. 35. PROVIDE MINIMUM OF 20' DUCT LINER AT EACH AIR HANDLING UNIT (SUPPLY AND RETURN CONNECTIONS). PROVIDE MINIMUM OF 20' DUCT LINER AT EACH AIR HANDLING UNIT (SUPPLY AND RETURN CONNECTIONS). 36.