2-SLCI26065 Attachment 2 Scope of Work.docx
DOCX document 34 KB Posted
- Attached to
- 500 Gallon Chemical Injection Skid
- Solicitation number
- SLCI26065
- Issued by
- Salt Lake County, Salt Lake City, Utah
About this file
This is a Scope of Work and Technical Specifications document for Salt Lake City Corporation's solicitation of a 500-gallon chemical injection skid, outlined in procurement SLCI26065. The specification details a comprehensive chemical injection system with a 500-gallon elliptical white polyethylene main water tank featuring a 16-inch opening, anti-siphon fill system, and anti-surge tank baffles. The system requires two 30-gallon poly cone-bottom chemical tanks with three-way calibration valves, low-level sensors, and 2-speed agitation capabilities. The spray equipment shall include an NSC-20108-V2 Boomless nutating seven-section spray head or city-approved equivalent, solid brass nozzles, cab-controlled 30-degree tilt and 90-degree swing functionality, a nine-section solenoid-regulator with QD connections, and a Norstar RS600-TASC 6300 mechanical cab control system or equivalent. The skid must be equipped with two TeeJet MT 500 peristaltic pumps with .05-350 ounces per minute output, a 9HP Honda GX-270 clutch-driven Hypro centrifugal water pump or city-approved equal, and cab-controlled start/stop with flow meter and ground speed radar capabilities. Additional requirements include an NSC-90500 hose reel with 150 feet of hose and electric rewind, skid-mounted adjustable spray bar, forklift receiver pockets, and NSC-90157 two-tank closed chemical loading system. Equipment shall be shipped to 3851 W 1200 N, Salt Lake City, Utah 84116, with delivery training provided for all operators and technicians.
The bidder must specify warranty term and hours in the response, with the document noting a typical minimum of 12 months after equipment receipt. Training requirements include instruction on all operations at delivery and provision of comprehensive maintenance, operation, and parts manuals via electronic USB stick. The document contains internal review comments requesting clarification on tank specifications, valve quantities, spray head specifications, plumbing connections, maintenance kit requirements, hose reel materials, and industry terminology, indicating the specification was in draft review stage at the time of document preparation. No pricing information, set-asides, incumbent contractors, funding sources, or contract term renewal options are specified in this technical specifications document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-SLCI26065 Attachment 1 City PO terms conditions.pdf | ||
| 3-SLCI26065 Attachment 3 Cost Sheet.xlsx | XLSX spreadsheet | |
| 4-SLCI26065 RFB.pdf | ||
| 5-Confidential+and+Proprietary+Info+Declaration+Form.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT “B”
TECHNICAL SPECIFICATIONS
Chemical Injection Skid
Must be filled out completely for the bid to be valid.
NOTICE TO BIDDERS: Any bidder who willfully falsifies responses indicating compliance or noncompliance with the minimum requirements listed below will be subject to suspension and/or debarment from bidding.
Each item below must have a yes or no response in the appropriate column. For all “no” responses, attach a separate sheet with a full explanation of the “no” response, including a description of the alternative to be supplied.
MINIMUM REQUIREMENT
YES
NO
1. MAIN WATER TANK
A. Shall have a 500-gallon elliptical white poly main water tank with a large 16” opening Comment by Lococo, Aron: Does it have to be elliptical?
B. Shall have an anti-siphon fill system
C. Shall have anti-surge tank baffles
2. CHEMICAL TANKS
A. Shall have two 30-gallon poly cone-bottom chemical tanks
B. Shall come with three-way calibration valves Comment by Lococo, Aron: Do we need to specify how many, or a minimum quantity of valves?
C. Shall have low-level sensors
D. Shall have 2-speed agitation
3. SPRAY HEADS, NOZZLES, & PUMPS
A. Shall be equipped with one NSC-20108-V2 Boomless nutating seven-section spray head or city-approved equivalent
B. Shall have solid brass nozzles Comment by Lococo, Aron: Do we need to specify quantity, size, etc..
C. Shall have cab cab-controlled 30-degree tilt and 90 90-degree swing in-out Comment by Lococo, Aron: We should add a little more clarity to what this means.
D. Shall have a nine-section solenoid-regulator with QD connection from the spray head Comment by Lococo, Aron: What is “QD”?
E. Shall be equipped with a Norstar RS600-TASC 6300 chemical rate-mechanical cab control system or city-approved equivalent
F. Shall have two TeeJet MT 500 peristaltic chemical pumps with .05-350 ounces per minute output or city-approved equal
G. All plumbing shall have QD for ease of clean-up and winterizing Comment by Lococo, Aron: Same question as above
H. Shall have a 9HP Honda GX-270 clutch-driven Hypro centrifugal water pump or City approved equal (?)
I. Shall have cab cab-controlled start/stop, water pump on-off, 1” flow meter, and ground speed radar
J. Shall be equipped with a maintenance kit Comment by Lococo, Aron: Do we have any minimum requirements of what’s included in the maintenance kit?
K. Shall have cannon plug connectors that disconnect the skid from the cab controls
4. ACCESSORIES
A. NSC-90500 hose reel ½”x150’ with electric rewind and SS rollers or city-approved equivalent Comment by Lococo, Aron: Stainless steel? If so please spell it out.
B. Skid-mounted NSC-90500 adjustable spray bar or city-approved equivalent
C. Shall have forklift receiver pockets
D. Shall have NSC-90157 2-tank closed chemical loading with chemical probe Comment by Lococo, Aron: Is this some standard industry term? If it’s specific to a manufacturer are equivalents allowable?
E. Shipping to 3851 W 1200 N, Salt Lake City, UT 84116 shall be included
5. WARRANTY Comment by Lococo, Aron: I typically like to state warranty shall be a minimum of 12 months after receipt of the equipment. Then allow bidders to tell us if they offer anything above and beyond that.
A. Bidder shall specify length of term or hours:______________________
6. TRAINING
A. At the time of delivery, the selected bidder shall supply training on all operations to all operators and technicians.
B. Shall include a full set of maintenance, operation, and parts manuals via electronic USB stick.