2-Sanpete VRF Bid Packet (1).docx

DOCX document 12 MB Posted

Attached to
NS27-3 Sanpete County Courthouse - VRF Retrofit Project
Solicitation number
NS27-3
Issued by
Summit County, Utah

About this file

This is a Bid Packet and Scope of Work document for the Sanpete County District Courthouse VRF Retrofit Project located in Manti, Utah, issued by Sanpete County Courthouse. The project involves a complete retrofit of the existing HVAC system to a Daikin Variable Refrigerant Flow (VRF) heat recovery system using a Design-Build delivery method with a Lump Sum bid type and no change orders permitted. The scope includes demolition of existing AHU/boiler systems, installation of VRF equipment (outdoor and indoor units, branch selector boxes, and controls), refrigerant piping (fully concealed), ductwork modification and balancing, electrical work, condensate drainage systems, architectural restoration to match existing finishes, and manufacturer commissioning. The project is phased over 24 months with the building remaining occupied throughout construction, requiring daily cleanup and a minimum of one week prior coordination before any work begins. Equipment specifications include four 20-ton Daikin REYA240AATJA outdoor units, multiple concealed ducted fan coil units ranging from 1.5 to 4.5 tons, ceiling cassette units from 0.5 to 1.5 tons, branch selector boxes, an Energy Recovery Ventilator (Greenheck 3200 CFM), and a ductless split for the server room. Technical submissions include piping diagrams, control layouts, wiring diagrams, and coordination documents with three days of factory-assisted startup and supervision. Questions must be submitted via the U3P-Bonfire platform by July 29, 2026 at 5:00 PM MDT, with bids due August 14, 2026 at 5:00 PM local time through electronic submission; no pre-bid conference is scheduled.

Pricing is submitted as a lump sum bid with all costs for concealed installation, phasing, access limitations, and coordination included with no change orders accepted. The project serves a historical building requiring all piping, conduit, and drains to be concealed with no exposed systems allowed; the existing system must remain operational until new systems are installed. Daikin VRF equipment only is permitted with no substitutions allowed. The contractor assumes full design, engineering, coordination, installation, commissioning, and system performance responsibility. The contractor must verify electrical requirements and provide all necessary power and controls wiring. The bid packet includes detailed submittal data sheets for all equipment components, material lists indicating quantities for each unit type across basement, main floor, and upper floor areas, system diagrams, dimensional drawings, and performance specifications validated per ASHRAE Standard 15-2022. The project is installed at 5,700 feet above sea level with an altitude correction factor of 0.8 percent applied to heating and cooling capacity calculations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SANPETE COUNTY DISTRICT

COURTHOUSE

VRF RETROFIT PROJECT

Bid Packet & Scope of Work

1. Project Information Location: Manti, Utah Delivery Method: Design-Build Bid Type: Lump Sum – No Change Orders

2. Project Description Complete retrofit of existing AHU/boiler system to Daikin VRF heat recovery system. Includes demolition, installation, electrical, controls, and restoration. (existing system must remain operable until new systems are installed). Building will remain occupied contractor must clean up material and jobsite daily. Areas of construction must be coordinated at a minimum of 1 week prior to any work being done.

3. Critical Constraints

· Historical building – no exposed systems allowed

· All piping, conduit, and drains must be concealed

· Phased construction over 24 months

· Occupied building conditions

· Pricing must be held for full duration

4. Design-Build Responsibility Contractor shall provide full design, engineering, coordination, installation, and commissioning. Contractor is responsible for system performance.

5. Equipment Requirements Daikin VRF equipment only. No substitutions allowed. Includes all indoor units, outdoor units, branch selector boxes, and controls.

6. Scope of Work Demolition:

· Remove existing HVAC systems, piping, and VAV boxes

VRF Installation:

· Install all outdoor and indoor units Install ERV system

Install Ductless Split in server room -Equipment listed below

Refrigerant Piping:

· Fully concealed piping system

Ductwork:

· Modify and balance system

Electrical:

· Provide all power and controls wiring (contractor to verify electrical requirements)

Condensate:

· Provide full drainage system to exterior with freezeproof drains.

Architectural:

· Cutting, patching, and restoration to match existing finishes.

Commissioning:

· Startup, testing, and training by manufacturer

7. No Change Order Policy All costs for concealed installation, phasing, access limitations, and coordination shall be included. No change orders will be accepted.

8. Attachments

· Daikin Equipment Selection

· Piping Diagrams

· Control Layout

· Wiring Diagrams

Energy Recovery Ventilator

Greenheck Recirculating Energy Recovery Ventilator 3200 CFM @1" SP -Elctric Pre and Post Heat -No Cooling -Indoor

Mini Split

(2) Daikin R-32 0.75 Ton Wall Mounted Daikin OTERRA Cooling only System -Wind Barne -Remote Controller -ODU Stands variable Refrigerant Volume Daikin Variable Refrigerant Volume

Lower, Main and Upper Floor

Qty
Model No
Description
4
REYA240AATJA
20 Ton, 230V R32 EMERION HR
1
BSF6A54AAVJ
Branch Selector Box (6 Port)
5
BSF8A54AAVJ

FXSA18AAVJU

Branch Selector Box (8 Port) 1.5-Ton R-32 MSP Concealed Ducted Unit

FXSA24AAVJU
2-Ton MSP Concealed Ducted Unit
1
FXSA30AAVJU
2.5-Ton R-32 MSP Concealed Ducted Unit
6
FXSA36AAVJU
3-Ton R-32 MSP Concealed Ducted Unit
8
FXSA48AAVJU
4-Ton R-32 MSP Concealed Ducted Unit
2
FXSA54AAVJU
4.5-Ton R-32 MSP Concealed Ducted Unit
8
FXZA07AAVJU
0.6-Ton R32 Vista 2x2 Casssette Unit for VRV
2
FXZA12AAVJU
1.0-Ton R32 Vista 2x2 Casssette Unit for VRV
2
FXZA15AAVJU
1.25-Ton R32 Vista 2x2 Casssette Unit for VRV

FXZA1BAAVJU KHRA25M72TA KHRA25M73TA

BHFP26P100UA

1.5-Ton R32 Vista 2x2 Casssette Unit for VRV 3 Pipe REFNET Joint 3 Pipe REFNET Joint Heat Recovery/ Dual Module Multi Connection Piping Kit

32
BRC1NRV71
R32 Navigation Remote Controller
1
BRD72A-L
D3-D4 Conversion Adaptor Kit
13
BYFQ18GU
Decoration Panel For 2X2, VRV-IUD 2X2 Cassette, R32
3
DFBS39A73
MERV 13 Filter Kit
14
DFBS55A13
MERV 13 Filter Kit for FXSQ
2
DFBS61A13
MERV 13 Filter Kit for FXSQ
1
KHFA26P100UA
Pipe Reducer Kit for VRV EMERION ODU Multi-Connection Pipe Kit
6
KHFP26A100CA

KHFP26P100UA

Closed Pipe Kit Pipe reducer kit for VRV EMERION ODU multi connection pipe kit

DCM601B71

Stand i-Touch Manager (iTM) VRV ODU Stands By ICS

Not included: Refrigerant or piping specialties.

Coordination Documents

· PDF Mark up with Estimate Piping Routes and Tag Notes by MPNSW

· Piping and Wiring Schematics from WebXpress

· System Details with Airnet/Group Addressing and BACnetlnstant ID's

3 Day of Project Supervision and Factory Assisted Startup. To Include Job Site Walk Through To Verify

· Supervision of Piping and Wiring Installation

· Supervision Mechanical Start-Up and Pressure Check/Evac

· Supervision of Controls Start-Up, Commissioning iTM and BACnet Integration

SANPETE COUNTY DISTRICT COURT HOUSE - MANTI, UT

BasementDFCU-1-1 4-Ton

Main FloorCU-1

24-Tons

1,293 sf

NEW ERV

NOTAHU

INCLUDED ROOM

BOILER ROOM

CCFCU-1-4 1.25-Ton

382 sf

CCFCU-1-5 1.25-Ton 378 sf

DFCU-2-693

3-Ton 5 sf

DFCU-2-5

duct chase

DFCU-3-2DFCU-2-7

CU-2

24-Tons292 sf

CCFCU-3-1

1-Ton

DFCU-1-2

3-Ton

1,907 sfNOT INCLUDED

DFCU-1-3

storageNOT INCLUDED

1,857 sf2,737 sf

DFCU-2-3

3-Ton

DFCU-2-1

entry

205 sfDFCU-2-2 data2,190 sf667 sf

2,326 sf

DFCU-1-6

4-Ton

DFCU-1-7

4-Ton

DFCU-1-8

2-Ton open

New Mini466 sf 740 sf DFCU-1-10 2.5-Ton CCFCU-1-9 1.5-Ton bathroom bathroom

NOT INCLUDED

129 sf 123 sf 123 sf

153 sfUnoccupied include capicity for future DFCU-3-7 2.5-Ton

NOT INCLUDED6 sf ext.

CU's on roof

9,673 sf

CU-3

24-Tons

CCFCU-3-3724 sf

DFCU-2-4

4-Ton

.5-Ton

CCFCU-3-4

.5-Ton

CCFCU-3-5

.5-Ton

CCFCU-3-6

.5-Ton

DFCU = Ducted Fan Coil Unit

Top Floor entry

NOT INCLUDED

DFCU-3-91,

duct chase

110 sf

CCFCU = Ceiling Cassette Fan Coil Unit entryopen exst. RTU exst. RTU

2,140 sfDFCU-3-8

220 sfdata bathroomoffice

DFCU-3-11

1,868 sfoffice

DFCU-3-10

DFCU-3-12

*Trying to utilize existing duct for OSA. Put ERV('s) in Basement where AHU's currently are.

208v/3phs Existing T-Bar bathroom

CCFCU-3-13

.5-Ton

157 sf 148 sf

CCFCU-3-14

1-Ton

CCFCU-3-15

.5-Tonoffice office 280 sf

FEATURES

· Low ambient cooling operation down to -4°F (-20°C) with a field setting and the addition of wind covers onto the outdoor unit

· Expanded Heating operation down to -22°F as standard

· New improved D4 net provides faster communication speeds and larger data volume compared to the D3 net up to 30 times the amount of data compared to D3 net

· Reduced install and commissioning time through auto addressing feature with D4 communications protocol

· R-32 system with lower Global Warming Potential (GWP), provides improved efficiency compared to R410A and requires lower total system charge

· Increased energy savings through new improved VRT technology with evaporation temperature control at each indoor unit (BS or SSOV required)

· New remote field setting option that allows data retrieval and field setting changes of units on the system from anywhere, without the need for physical access to each room

· New field setting that allows reuse of R410A piping network for new R32 system, eliminating need to replace for retrofit applications

· Seven segment display to read refrigerant temperatures and pressure on digital display

· Vertical separation up to 361 FT with field setting

· Ease of field piping connections to service valves

· Continuous heating during defrost capability with single module (16 T - 20 T) and all dual module systems

· Hot gas defrost circuit allows for installation without base pan heater

· High dust and moisture protection with an IP55 rated sealed E-box

· Design flexibility to enlarge system from single to a dual-module without changes to installed main pipe sizes for phased installation or tenant fit-out buildings

· Built-in data recorder to store up to 45 minutes of operational data

· Integrates with new Daikin HERO ecosystem, an loT based remote monitoring and diagnostics platform

· Engineered for ease of installation and service with three-segment panel design

· Extend benefits of inverter technology to custom terminal units and AHUs through AHU integration kits Submittal Data Sheet 12 Ton, 230V R32 EMERION HR REYA144AATJA

Daikin North America LLC, 19001 Kermier Rd, Waller, TX 77484 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 08/25/2025

PERFORMANCE

Outdoor Unit Model No.

REYA144AATJA

Outdoor Unit Name: 12 Ton, 230V R32 EMERION HR

Type:
Heat Recovery
Rated Heating Conditions:Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

Rated Heating Capacity (Btu/hr): 138,000

Rated Cooling Capacity (Btu/hr): 138,000 Nom Heating Capacity (Btu/hr): 162,000

Nom Cooling Capacity (Btu/hr): 144,000 Heating COP (Non-Ducted/Ducted): 3.30/3.35

EER (Non-Ducted/Ducted): 11.20/11

Heating COP 17F (Non-Ducted/Ducted):

2.10/2.10

IEER (Non-Ducted/Ducted): 22.7/19.70 SCHE (Non-Ducted/Ducted): 19.60/15.00

OUTDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208-230 / 60 / 3
Compressor Stage:
INVERTER
Power Supply Connections:
L1, L2, L3 GROUND
Capacity Control Range (%):
3 - 100
Min. Circuit Amps MCA (A):
50
Airflow Rate (H) (CFM):
9675

Max Overcurrent Protection (MOP) (A):

Gas Pipe Connection (inch):

1-1/8

Dimensions (Height) (in):
65-3/8
Liquid Pipe Connection (inch):
1/2
Dimensions (Width) (in):
48-13/16
H/L Pressure Connection (inch)
3/4
Dimensions (Depth) (in):
30-1/8
Sound Pressure (H) (dBA):
65
Net Weight (lb):
825
Sound Power Level (dB):
85

SYSTEM DETAILS

Refrigerant Type:
R-32
Cooling Operation Range (°F DB):
23 - 122
Holding Refrigerant Charge (lbs):
25.8
Heating Operation Range (°F WB):
-22 - 60

Additional Charge (oz/ft):

Check Install manual or selection tool

Max. Pipe Length (Vertical) (ft): 361

Max. Pipe Length (Total) (ft):3,280Cooling Range w/Baffle (°F DB):-4 - 122
Max Height Separation (Ind to Ind ft):98

DIMENSIONAL DRAWING

F EAT U RES AND B ENEF IT S

· Engineered for flexibility in design with left, right and pass through piping configuration

· R32 Compliance Features

· Safety shut off valves already integrated into all BSB units

· Backup power supply factory installed so valves close per code in the event of power loss Submittal Data Sheet Branch Selector Box (4-Port)

BSF4A54AAVJ

Submittal Data www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 7/24/2025 7:47:22 AM

· Connectible to BS-EB Ventilated Enclosure if needed

· Low built-in height and minimal installation space required

· Design flexibility – single and multi-port units can be combined in one system

· Provides low ambient cooling capacity for HP units down to -4F

· Pass through configuration allows reduction in required REFNETs

· Ease of maintenance with access to EEV heads from side access panels

· Installation simplicity with no drain pan and no drain piping needed

Image for reference only

Specifications

Model no:
BSF4A54AAVJ
Type
Multi-port
Power Supply
Single Phase 208/230V 60Hz
MCA (A)
1.2
MOP (A)
15
Number of branches
4
Max number of connectable IDUs per branch
5
Max capacity index of connectable IDUs per branch
54
Parallel configuration
Max number of connectable IDUs
19
Max capacity index of connectable IDUs
144

Series configuration

Max number of connectable IDUs
30
Max capacity index of connectable IDUs per BS unit
144

Max capacity index of connectable IDUs under BS units connected

Piping Connections

Indoor units

Liquid
in. (mm)
φ1/4 (6.4), φ3/8 (9.5)

(Brazing connection)

Gas
in. (mm)
φ1/2 (12.7), φ5/8 (15.9)

Outdoor units

Liquid
in. (mm)
φ5/8 (15.9)
Suction Gas
in. (mm)
φ1-1/8 (28.6)
HP/LP Gas
in. (mm)
φ1-1/8 (φ28.6)

(Brazing connection)

Weight
lbs. (kg)
68 (31)

Dimensions

Height
in. (mm)
9-1/2 (241)
Width
in. (mm)
19-5/16 (490)
Depth
in. (mm)
28-3/16 (716)
Refrigerant
R-32

FEATURES AND BENEFITS

· R32 Compliance Features

· Safety shut off valves already integrated into all BSB units

· Backup power supply factory installed so valves close per code in the event of power loss Submittal Data Sheet Branch Selector Box (6 Port)

BSF6A54AAVJ

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 7/24/2025 7:48:01 AM

· Connectible to BS-EB Ventilated Enclosure if needed

· Low built-in height and minimal installation space required

· Design flexibility – single and multi-port units can be combined in one system

· Provides low ambient cooling capacity for HP units down to -4F

· Pass through configuration allows reduction in required REFNETs

Specifications

Model no:
BSF6A54AAVJ
Type
Multi-port
Power Supply
Single Phase 208/230V 60Hz
MCA (A)
1.9
MOP (A)
15
Number of branches
6
Max number of connectable IDUs per branch
5
Max capacity index of connectable IDUs per branch
54
Parallel configuration
Max number of connectable IDUs
28
Max capacity index of connectable IDUs
216
Max number of connectable IDUs
30
Max capacity index of connectable IDUs per BS unit
162

Max capacity index of connectable IDUs under BS

Liquid
in. (mm)
φ1/4 (6.4), φ3/8 (9.5)
Gas
in. (mm)
φ1/2 (12.7), φ5/8 (15.9)
Liquid
in. (mm)
φ5/8 (15.9)
Suction Gas
in. (mm)
φ1-1/8 (28.6)
HP/LP Gas
in. (mm)
φ1-1/8 (28.6)

(Brazing connection)

Weight
lbs. (kg)
106 (48)
Height
in. (mm)
9-1/2 (241)
Width
in. (mm)
33-7/16 (849)
Depth
in. (mm)
28-3/16 (716)
Refrigerant
R-32

FEATURES AND BENEFITS

· R32 Compliance Features

· Safety shut off valves already integrated into all BSB units

· Backup power supply factory installed so valves close per code in the event of power loss Submittal Data Sheet Branch Selector Box (8 Port)

BSF8A54AAVJ

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 7/24/2025 7:48:21 AM

· Connectible to BS-EB Ventilated Enclosure if needed

· Low built-in height and minimal installation space required

· Design flexibility – single and multi-port units can be combined in one system

· Provides low ambient cooling capacity for HP units down to -4F

· Pass through configuration allows reduction in required REFNETs

Specifications

Model no:
BSF8A54AAVJ
Type
Multi-port
Power Supply
Single Phase 208/230V 60Hz
MCA (A)
1.9
MOP (A)
15
Number of branches
8
Max number of connectable IDUs per branch
5
Max capacity index of connectable IDUs per branch
54
Parallel configuration
Max number of connectable IDUs
38
Max capacity index of connectable IDUs
290
Max number of connectable IDUs
30
Max capacity index of connectable IDUs per BS unit
162

Max capacity index of connectable IDUs under BS

Liquid
in. (mm)
φ1/4 (6.4), φ3/8 (9.5)
Gas
in. (mm)
φ1/2 (12.7), φ5/8 (15.9)
Liquid
in. (mm)
φ5/8 (15.9)
Suction Gas
in. (mm)
φ1-1/8 (28.6)
HP/LP Gas
in. (mm)
φ1-1/8 (28.6)

(Brazing connection)

Weight
lbs. (kg)
115(52)
Height
in. (mm)
9-1/2 (241)
Width
in. (mm)
33-7/16 (849)
Depth
in. (mm)
28-3/16 (716)
Refrigerant
R-32

Branch Selector Box (8 Port)

BSF8A54AAVJ

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 7/24/2025 7:48:21 AM

· Design for installation flexibility, with a factory rear-return configuration and field convertible to bottom return configuration

· Slender design with only 9-11/16 height and requiring 11-1/4 clearance in ceiling space allowing for installation in cramped applications

· Ease of installation with auto adjusting airflow at commissioning based on external static pressure.

· Powerful static pressure capability, with up to 0.6 in.w.g. (150Pa) external static pressure.

· New minimal discharge air temperature setting to help mitigate risk of condensation on air vents

· Efficient operation and year-round energy savings through Smart Variable Refrigerant Temperature (VRT) technology

· Quiet operation for sound sensitive applications with sound levels as low as 28 dB(A).

· High degree of control for auxiliary heating devices, with independently configurable on/off temperature values.

· Integral condensate pump with up to 25-5/16 (643mm) of lift from the drain outlet

· Maintenance-friendly inspection port to easily check the conditions of the drain pan

BENEFITS

· Factory-installed integrated refrigerant leak sensor

· Dispersion Mode: Higher airflow rate for leak mitigation through circulation

· Terminal for connection, via optional relay PCB, to external alarms and monitoring systems Submittal Data Sheet 2-Ton MSP Concealed Ducted Unit - FXSA24AAVJU Project: Sanpete County District Court House Submitted by: Bo Kapelke of MECHANICAL PRODUCTS NSW LLC on 4/13/2026 Submitted to: OSE Tags: DFCU-1-8 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:10 PM

PERFORMANCE

Indoor Unit Model No.
FXSA24AAVJU
Indoor Unit Name:
2-Ton MSP Concealed Ducted Unit

Type:

Concealed Ducted

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

Rated Cooling Capacity (Btu/hr):

24,000

Rated Heating Conditions: Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

Sensible Capacity (Btu/hr):

Rated Piping Length(ft):

Cooling Input Power (kW):

Rated Height Separation (ft):

Rated Heating Capacity (Btu/hr):
27,000

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208-230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
742/618/512
Power Supply Connections:
L1, L2, G
Moisture Removal (Gal/hr):
Min. Circuit Amps MCA (A):
1.8
Gas Pipe Connection (inch):
5/8

Max Overcurrent Protection (MOP)

Liquid Pipe Connection (inch):

3/8

(A):

Dimensions (HxWxD) (in):
9-11/16 x 39-3/8 x 31-1/2
Condensate Connection (inch):

Ext. Static Pressure (Rated/Max) (inWg):

0.20 / 0.6

Sound Pressure (H/M/L) (dBA):

36/32/29

Net Weight (lb):
77
Sound Power Level (dBA):
64

ACCESSORIES

PART

NUMBER

DESCRIPTION
INCLUDED
BRC1NRV71
R32 Navigation Remote Controller
No
DCM601B71
i-Touch Manager (iTM)
No
DGE601A53
DIII Plus Adaptor Slot card (for use with the DIII Plus Adaptor (DGE601A72))
No
DGE601A72
DIII-Net Plus Adaptor (for use with the Pro Edge and iTM)
No
DTA104A61
Outdoor Unit External Control Adapter PCB
No
KRCS01-6B
Remote Sensor
No
KRP1C76
Wiring Adapter PCB
No
KRP4A71
Group Control Adaptor PCB
No
KRP4A98
Mounting plate for accessory PCB
No

· Design for installation flexibility, with a factory rear-return configuration and field convertible to bottom return configuration

· Slender design with only 9-11/16 height and requiring 11-1/4 clearance in ceiling space allowing for installation in cramped applications

· Ease of installation with auto adjusting airflow at commissioning based on external static pressure.

· Powerful static pressure capability, with up to 0.6 in.w.g. (150Pa) external static pressure.

· New minimal discharge air temperature setting to help mitigate risk of condensation on air vents

· Efficient operation and year-round energy savings through Smart Variable Refrigerant Temperature (VRT) technology

· Quiet operation for sound sensitive applications with sound levels as low as 28 dB(A).

· High degree of control for auxiliary heating devices, with independently configurable on/off temperature values.

· Integral condensate pump with up to 25-5/16 (643mm) of lift from the drain outlet

· Maintenance-friendly inspection port to easily check the conditions of the drain pan

BENEFITS

· Factory-installed integrated refrigerant leak sensor

· Dispersion Mode: Higher airflow rate for leak mitigation through circulation

· Terminal for connection, via optional relay PCB, to external alarms and monitoring systems Submittal Data Sheet 2.5-Ton R-32 MSP Concealed Ducted Unit - FXSA30AAVJU Project: Sanpete County District Court House

Tags: DFCU-1-10, FCU- 24DFCU-3-7 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:17 PM

PERFORMANCE

Indoor Unit Model No.

FXSA30AAVJU

Indoor Unit Name: 2.5-Ton R-32 MSP Concealed Ducted Unit

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

30,000

Rated Heating Conditions: Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

Sensible Capacity (Btu/hr):

Rated Piping Length(ft):

Cooling Input Power (kW):

Rated Height Separation (ft):

Rated Heating Capacity (Btu/hr):
34,000

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208-230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
812/689/565
Power Supply Connections:
L1, L2, G
Moisture Removal (Gal/hr):
Min. Circuit Amps MCA (A):
1.9
Gas Pipe Connection (inch):
5/8

Max Overcurrent Protection (MOP)

Liquid Pipe Connection (inch):

(A):

Dimensions (HxWxD) (in):
9-11/16 x 39-3/8 x 31-1/2
Condensate Connection (inch):

Ext. Static Pressure (Rated/Max) (inWg):

0.2 / 0.6

Sound Pressure (H/M/L) (dBA):

38/34/30

Net Weight (lb):
82
Sound Power Level (dBA):
65.5

2.5-Ton R-32 MSP Concealed Ducted Unit - FXSA30AAVJU Project: Sanpete County District Court House

Tags: DFCU-1-10, FCU- 24DFCU-3-7 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:17 PM

PART

DESCRIPTION
INCLUDED
BRC1NRV71
R32 Navigation Remote Controller
No
DCM601B71
i-Touch Manager (iTM)
No
DGE601A53
DIII Plus Adaptor Slot card (for use with the DIII Plus Adaptor (DGE601A72))
No
DGE601A72
DIII-Net Plus Adaptor (for use with the Pro Edge and iTM)
No
DTA104A61
Outdoor Unit External Control Adapter PCB
No
KRCS01-6B
Remote Sensor
No
KRP1C76
Wiring Adapter PCB
No
KRP4A71
Group Control Adaptor PCB
No
KRP4A98
Mounting plate for accessory PCB
No

· Design for installation flexibility, with a factory rear-return configuration and field convertible to bottom return configuration

· Slender design with only 9-11/16 height and requiring 11-1/4 clearance in ceiling space allowing for installation in cramped applications

· Ease of installation with auto adjusting airflow at commissioning based on external static pressure.

· Powerful static pressure capability, with up to 0.6 in.w.g. (150Pa) external static pressure.

· New minimal discharge air temperature setting to help mitigate risk of condensation on air vents

· Efficient operation and year-round energy savings through Smart Variable Refrigerant Temperature (VRT) technology

· Quiet operation for sound sensitive applications with sound levels as low as 28 dB(A).

· High degree of control for auxiliary heating devices, with independently configurable on/off temperature values.

· Integral condensate pump with up to 25-5/16 (643mm) of lift from the drain outlet

· Maintenance-friendly inspection port to easily check the conditions of the drain pan

BENEFITS

· Factory-installed integrated refrigerant leak sensor

· Dispersion Mode: Higher airflow rate for leak mitigation through circulation

· Terminal for connection, via optional relay PCB, to external alarms and monitoring systems Submittal Data Sheet 3-Ton R-32 MSP Concealed Ducted Unit - FXSA36AAVJU Project: Sanpete County District Court House

Tags: DFCU-1-2, DCFCU-1-3, DFCU-2-6, DFCU-2-2, DFCU-2-3, DFCU-3-2, DFCU-3-8, DFCU-3-10, DFCU-3-11, DFCU-3-12 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:26 PM

PERFORMANCE

FXSA36AAVJU

Indoor Unit Name: 3-Ton R-32 MSP Concealed Ducted Unit

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

36,000

Rated Heating Conditions: Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

Sensible Capacity (Btu/hr):

Rated Piping Length(ft):

Cooling Input Power (kW):

Rated Height Separation (ft):

Rated Heating Capacity (Btu/hr):
40,000

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208-230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
1130/953/795
Power Supply Connections:
L1, L2, G
Moisture Removal (Gal/hr):
Min. Circuit Amps MCA (A):
2.5
Gas Pipe Connection (inch):
5/8

Max Overcurrent Protection (MOP)

Liquid Pipe Connection (inch):

(A):

Dimensions (HxWxD) (in):
9-11/16 x 55-1/8 x 31-1/2
Condensate Connection (inch):

Ext. Static Pressure (Rated/Max) (inWg):

0.2 / 0.6

Sound Pressure (H/M/L) (dBA):

39/35/32

Net Weight (lb):
101
Sound Power Level (dBA):
67

3-Ton R-32 MSP Concealed Ducted Unit - FXSA36AAVJU Project: Sanpete County District Court House

Tags: DFCU-1-2, DCFCU-1-3, DFCU-2-6, DFCU-2-2, DFCU-2-3, DFCU-3-2, DFCU-3-8, DFCU-3-10, DFCU-3-11, DFCU-3-12 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:26 PM

PART

DESCRIPTION
INCLUDED
BRC1NRV71
R32 Navigation Remote Controller
No
DCM601B71
i-Touch Manager (iTM)
No
DGE601A53
DIII Plus Adaptor Slot card (for use with the DIII Plus Adaptor (DGE601A72))
No
DGE601A72
DIII-Net Plus Adaptor (for use with the Pro Edge and iTM)
No
DTA104A61
Outdoor Unit External Control Adapter PCB
No
KRCS01-6B
Remote Sensor
No
KRP1C76
Wiring Adapter PCB
No
KRP4A71
Group Control Adaptor PCB
No
KRP4A98
Mounting plate for accessory PCB
No

· Design for installation flexibility, with a factory rear-return configuration and field convertible to bottom return configuration

· Slender design with only 9-11/16 height and requiring 11-1/4 clearance in ceiling space allowing for installation in cramped applications

· Ease of installation with auto adjusting airflow at commissioning based on external static pressure.

· Powerful static pressure capability, with up to 0.6 in.w.g. (150Pa) external static pressure.

· New minimal discharge air temperature setting to help mitigate risk of condensation on air vents

· Efficient operation and year-round energy savings through Smart Variable Refrigerant Temperature (VRT) technology

· Quiet operation for sound sensitive applications with sound levels as low as 28 dB(A).

· High degree of control for auxiliary heating devices, with independently configurable on/off temperature values.

· Integral condensate pump with up to 25-5/16 (643mm) of lift from the drain outlet

· Maintenance-friendly inspection port to easily check the conditions of the drain pan

BENEFITS

· Factory-installed integrated refrigerant leak sensor

· Dispersion Mode: Higher airflow rate for leak mitigation through circulation

· Terminal for connection, via optional relay PCB, to external alarms and monitoring systems Submittal Data Sheet 4-Ton R-32 MSP Concealed Ducted Unit - FXSA48AAVJU Project: Sanpete County District Court House

Tags: DCFCU-1-6, DFCU-1-7, DCFCU-1-1, DFCU-2-5, DFCU-2-7, DFCU-2-1, DFCU-2-4, DFCU-3-9 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:34 PM

PERFORMANCE

FXSA48AAVJU

Indoor Unit Name: 4-Ton R-32 MSP Concealed Ducted Unit

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

48,000

Rated Heating Conditions: Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

Sensible Capacity (Btu/hr):

Rated Piping Length(ft):

Cooling Input Power (kW):

Rated Height Separation (ft):

Rated Heating Capacity (Btu/hr):
54,000

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208-230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
1307/1,112/918
Power Supply Connections:
L1, L2, G
Moisture Removal (Gal/hr):
Min. Circuit Amps MCA (A):
2.8
Gas Pipe Connection (inch):
5/8

Max Overcurrent Protection (MOP)

Liquid Pipe Connection (inch):

(A):

Dimensions (HxWxD) (in):
9-11/16 x 55-1/8 x 31-1/2
Condensate Connection (inch):

Ext. Static Pressure (Rated/Max) (inWg):

0.2 / 0.6

Sound Pressure (H/M/L) (dBA):

42/39/35

Net Weight (lb):
104
Sound Power Level (dBA):
70

4-Ton R-32 MSP Concealed Ducted Unit - FXSA48AAVJU Project: Sanpete County District Court House

Tags: DCFCU-1-6, DFCU-1-7, DCFCU-1-1, DFCU-2-5, DFCU-2-7, DFCU-2-1, DFCU-2-4, DFCU-3-9 www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 4/13/2026 12:27:34 PM

PART

DESCRIPTION
INCLUDED
BRC1NRV71
R32 Navigation Remote Controller
No
DCM601B71
i-Touch Manager (iTM)
No
DGE601A53
DIII Plus Adaptor Slot card (for use with the DIII Plus Adaptor (DGE601A72))
No
DGE601A72
DIII-Net Plus Adaptor (for use with the Pro Edge and iTM)
No
DTA104A61
Outdoor Unit External Control Adapter PCB
No
KRCS01-6B
Remote Sensor
No
KRP1C76
Wiring Adapter PCB
No
KRP4A71
Group Control Adaptor PCB
No
KRP4A98
Mounting plate for accessory PCB
No

· 4-way, 3-way, and 2-way blow configurability

· Independently motorized louver outlets

· High efficiency DC fan motor with Auto fan speed control

· Low profile decoration panel design measures a mere 5/16" below the ceiling

· Integral condensate pump with up to 24-13/16" (630mm) lift from the drain outlet

· Independently configurable auxiliary heat on/off temperatures

· Direct outside air integration possible

· One decoration panel design color available

R-32 FEATURES

0.5-Ton R32 Vista 2×2 Cassette Unit for VRV

FXZA05AAVJU

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:33:23 AM

· Factory-installed integrated refrigerant leak sensor

· Dispersion Mode: Higher airflow rate for leak mitigation through circulation

· Terminal for connection, via optional relay PCB, to external alarms and monitoring systems

Image for reference purpose

FXZA05AAVJU

Indoor Unit Name:

0.5-Ton R32 Vista 2×2 Cassette Unit for VRV

PERFORMANCE

Cassette

Rated Cooling Conditions:

Rated Heating Conditions:

Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208/230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
300/247/229
Power Supply Connections:
L1, L2, G
Sound Pressure (H/M/L) (dBA):
32/30/26
Min. Circuit Amps MCA (A):
0.3
Sound Power Level (dBA):
49

Max Overcurrent Protection (MOP) 15 (A):

Dimensions (HxWxD) (in):10-1/4 x 22-5/8 x 22-5/8
Net Weight (lb):35.3

· Independently motorized louver outlets

· High efficiency DC fan motor with Auto fan speed control

· Low profile decoration panel design measures a mere 5/16" below the ceiling

· Integral condensate pump with up to 24-13/16" (630mm) lift from the drain outlet

· Independently configurable auxiliary heat on/off temperatures

· Direct outside air integration possible

· One decoration panel design color available

1.0-Ton R32 Vista 2×2 Cassette Unit for VRV FXZA12AAVJU www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:40:30 AM

R-32 FEATURES

· Factory-installed integrated refrigerant leak sensor

FXZA12AAVJU

Indoor Unit Name:

1.0-Ton R32 Vista 2×2 Cassette Unit for VRV

1.0-Ton R32 Vista 2×2 Cassette Unit for VRV

FXZA12AAVJU

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:40:30 AM

Type:

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208/230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
353/300/247
Power Supply Connections:
L1, L2, G
Sound Pressure (H/M/L) (dBA):

34/30/26

Min. Circuit Amps MCA (A):
0.4
Sound Power Level (dBA):
51

Max Overcurrent Protection (MOP) 15 (A):

Dimensions (HxWxD) (in):10-1/4 x 22-5/8 x 22-5/8
Net Weight (lb):36.4

· Independently motorized louver outlets

· High efficiency DC fan motor with Auto fan speed control

· Low profile decoration panel design measures a mere 5/16" below the ceiling

· Integral condensate pump with up to 24-13/16" (630mm) lift from the drain outlet

· Independently configurable auxiliary heat on/off temperatures

· Direct outside air integration possible

· One decoration panel design color available

R-32 FEATURES

1.25-Ton R32 Vista 2×2 Cassette Unit for VRV FXZA15AAVJU www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:41:25 AM

· Factory-installed integrated refrigerant leak sensor

FXZA15AAVJU

Indoor Unit Name:

1.25-Ton R32 Vista 2×2 Cassette Unit for VRV

1.25-Ton R32 Vista 2×2 Cassette Unit for VRV

FXZA15AAVJU

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:41:25 AM

Type:

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
200/230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
405/335/282

Power Supply Connections:

L1, L2, G

Sound Pressure (H/M/L) (dBA):
37/32/28

Min. Circuit Amps MCA (A):

0.4

Sound Power Level (dBA):
54

Max Overcurrent Protection (MOP)

(A):15
Dimensions (HxWxD) (in):10-1/4 x 22-5/8 x 22-5/8
Net Weight (lb):36.4

· Independently motorized louver outlets

· High efficiency DC fan motor with Auto fan speed control

· Low profile decoration panel design measures a mere 5/16" below the ceiling

· Integral condensate pump with up to 24-13/16" (630mm) lift from the drain outlet

· Independently configurable auxiliary heat on/off temperatures

· Direct outside air integration possible

· One decoration panel design color available

R-32 FEATURES

1.5-Ton R32 Vista 2×2 Cassette Unit for VRV FXZA18AAVJU www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:41:46 AM

· Factory-installed integrated refrigerant leak sensor

FXZA18AAVJU

Indoor Unit Name:

1.5-Ton R32 Vista 2×2 Cassette Unit for VRV

1.5-Ton R32 Vista 2×2 Cassette Unit for VRV

FXZA18AAVJU

www.daikinac.com www.daikincomfort.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Date: 8/12/2025 10:41:46 AM

Type:

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph):
208/230 / 60 / 1
Airflow Rate (H/M/L) (CFM):
511/441/353
Power Supply Connections:
L1, L2, G
Sound Pressure (H/M/L) (dBA):
43/40/33
Min. Circuit Amps MCA (A):
0.6
Sound Power Level (dBA):
60

Max Overcurrent Protection (MOP)

(A) :15
Dimensions (HxWxD) (in):10-1/4 x 22-5/8 x 22-5/8
Net Weight (lb):41.9

DESCRIPTION

Note: Actual materials and sizes included may differ from photo. Models ending in A will have a black Insulations models ending

The Condensing Unit Multi Connection Piping Kit provides a factory engineered method for the connection of multiple single modules to form a multi-module system within the refrigerant piping network.

FEATURES

· Engineered for uniform refrigerant flow and refrigerant distribution

· Designed with tube diameters (I.D. and O.D.) required for VRV system installations

· Installation of ±15° from horizontal

· Pre-formed clamshell style insulation1 for cleaner and reliable application

· Designed to help with smoother oil return

· Insulation tested in accordance with ASTM E84 – Class ASPECIFICATIONS

Model No.:
BHFP26P100UA
Components Included:
Suction gas side joint, HP/LP side joint, liquid side joint, reducers, insulation and installation manual
Unit Compatibility:
REYQ_TATJU, REYQ_TAYDU, REYQ_TAYCU and RELQ_TAYCU
Unit Weight:
Estimated kit shipping weight: 9 lbs (4 kgs)
Dimensions (W x H x D):
Refer to Dimensional Drawing and VRV Express Report
Material / Finish:
Piping Material - ACR Copper Alloy C12200, Insulation Material1 - Polypropylene
# of Condensing Units2:
2
Suction Gas Side
HP/LP Gas Side
Liquid Side
# of Joints:
1
1
1
Joint Insulation Quantity:
1 pcs
1 pcs
1 pcs
Reducer Fitting3 Quantity:
3 pcs
4 pcs
4 pcs
Piping Insulation Quantity:
2 pcs (large size)
1 pc (small size)
Insulation Flammability
ASTM E84 – Class A
Flame Spread Index
< 25
Smoke Develop Index
< 50

Notes:

1) The insulation of the refrigerant piping must be reinforced based on the environment of the installation. Otherwise dew may condense on the surface of insulation.

2) Refer to Engineering Data for any restrictions.

3) Refer to Installation Manual for reducer fitting shapes and dimensions.

Heat Recovery / Dual Module Multi Connection Piping Kit BHFP26P100UA

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056 www.daikinac.com www.daikincomfort.com (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations).

DIMENSIONAL DRAWINGS*

*Refer to Installation Manual for detailed dimensional drawing

DIMENSIONAL DRAWINGS*

*Refer to Installation Manual for detailed dimensional drawing

TYPICAL INSTALLATION DRAWINGS (For Reference Only)

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

MODEL COMPATIBILITY:

Compatible with R-32 VRV Indoor units: FXTA, FXFA, FXMA, FXSA, FXAA, FXZA Compatible with VRV and VRV LifeTM Indoor unit models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXSQ, FXTQ, FXUQ, FXZQ, VAM, CXTQ Compatible with SkyAir indoor unit models: FAQ, FBQ, FCQ, FHQ, FTQ, FAA, FBA, FCA, FTA Compatible with Single and Multi-zone system indoor unit model: FFQ, FDMQ, FFA, FDMA, CDMA

SPECIFICATIONS: PRODUCT IMAGE:Model

BRC1NRV71

Description Navigation Remote Controller Maximum Connections 16 indoor units Communication Wire 18AWG-2, No polarity Stranded, Non-shielded Total Wiring Length 1,640 ft. (500 m) Communication Protocol Daikin proprietary P1P2 protocol Power 16VDC supplied by indoor unit (1.58VA maximum) Comfort Setpoint Range 60 to 90 °F (16 to 32 °C) Setback Setpoint Range 40 to 95 °F (5 to 35°C) Operating Temp Range 14 to 122°F (-10 to 50°C) Operating Humidity Range 75% or less (RH) (without condensation) Dimensions (WxHxD) 4.72x4.72x0.75 inch (120x120x19 mm) Weight (Mass)

0.42 lbs. (0.19 kg)

Note: Three display formats available – Detailed display shown

FEATURES:

1) Up to 16 indoor units are controllable within one group

2) Within one group, up to 2 Navigation Remote Controllers can be used, one as a main and one as a sub

a) The BRC1NRV71 controller cannot be combined with any other BRC-type controller models

b) The NRV controller cannot be assigned as a sub controller when paired with a non-BRC-type controller

3) Backlit LCD displays in English, Spanish or French

4) Temperature sensor built-in with configurable offset

5) Display of Temperature and Setpoint in 1°F / °C increments

6) Three configurable display options: Detailed, Standard and Simple

7) Dual setpoints (independent cooling and heating setpoints) with configurable minimum setpoint differential or Single Setpoint (occupied period)

8) Setpoint range limit for cooling and heating modes Submittal Data Sheet BRC1NRV71 – Navigation Remote Controller Project Name:

Daikin Comfort Technologies North America LLC, 19001 Kermier Road, Waller TX 77484 www.daikincomfort.com www.daikincity.com (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

9) Independent cooling and heating setback setpoints (unoccupied period)

10) Auto changeover control with configurable primary and secondary changeover dead bands and guard timer

11) Individual louver position, dual louver position and auto draft prevention (prevents air blowing directly on occupants)*

12) Built-in 7 Days, Weekdays+Weekend, Weekdays+Sat+Sun, and Everyday schedules with up to 5 actions per day with independent cooling and heating or setback setpoints

13) Automatic Setback by occupancy sensor*

14) Automatic Off by occupancy sensor*

15) Configuration for Self-cleaning filter panel*

16) Automatic adjustment for Daylight Savings Time (DST)

17) 48-hour clock/calendar battery backup (protects schedule timing in cases of short-term power loss from indoor unit)

18) Real-time monitoring of system malfunctions with immediate display of unit in error and error code

19) The buttons on the remote controller are selectable by locking out the unwanted buttons

20) The operation modes can be restricted to provide only the desired mode(s) of operation

21) Display can be configured to only show “Off” and room temperature when indoor unit is turned off

22) To prevent unwanted changes, fan speed selection and display may be hidden

23) Override timer configurable in 10-minute increments (range: 30 minutes to 10 hours)

24) Enhanced error monitoring for R32 VRV Indoor units

25) Supports new addressing scheme of D4-NET *Requires support by indoor unit.

SYSTEM DIAGRAM:

DIII-Net or D4-Net

P1P2 Up to 16 indoor units

Multiple indoor units group control

Stand-alone group control

Main Sub Two controllers used for single group control

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

FACE DECAL OPTIONS:

Face decal options are used to hide unnecessary buttons:

1. The face decal is designed to adhere to the faceplate

2. Hidden buttons can be accessed by service personnel without removing the face decal due to its flexibility

DIMENSIONS:

4-3/4” 4-3/4” ¾””

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

DOCUMENTATION:

Documentation available on www.daikincity.com and/or www.daikincomfort.com:

· Installation Manual

· Operation Manual

· Submittal

· Guide Specifications

High efficiency MERV 13 filter box designed for bolt-on installation to the FXSQ_TAVJU, FXSQ_TBVJU and FXMQ_TBVJU, FDMQ_RVJU series indoor units. The slim cabinet design measures only 7” deep features a tool-less access door to simplify the removal and replacement of the filters.

SPECIFICATIONS

Model No.:
DFBS39A13
Components Included:
Filter Cabinet MERV 13 filter set
Unit Compatibility:
FXSQ18TAVJU, FXSQ18TBVJU, FXSQ24TAVJU, FXSQ24TBVJU, FXSQ30TAVJU FXSQ30TBVJU,

FDMQ15RVJU, FDMQ18RVJU, FDMQ24RVJU, FXMQ15TBVJU, FXMQ18TBVJU, FXMQ24TBVJU, FXSA18AAVJU, FXSA24AAVJU, FXSA30AAVJU, FXMA15AAVJU, FXMA18AAVJU, FXMA24AAVJU

Unit Weight (shipping):
21 lbs (9.53 kg)
Cabinet Dimensions (W x H x D):
42.02” x 9.50” x 7.00” (1067 mm x 241 mm x 178 mm)
Cabinet Material / Finish:
20 Ga. galvanized sheet metal
Filter Dimensions (W x H x D):
Nominal 20” x 8” x 4.375” (508 mm x 203 mm x 111 mm) – Qty (2) required
Filter Material / Finish:
Synthetic, electrostatically charged, non-woven media
Filter:
Qty (2) filters included as standard
Filter Rating:
MERV 13
Filter Type:
Disposable
Replacement Filter Part No.:
(2) SQM13A20

PRESSURE DROP

Compatible Fan Coil Model
FXMQ15TBVJU, FXMA15AAVJU
FXMQ18TBVJU, FXMA18AAVJU
FXSQ18T_VJU, FXSA18AAVJU
FXSQ24T_VJU FXMQ24TBVJU, FXSA24AAVJU,

FXMA24AAVJU

FXSQ30T_VJU, FXSA30AAVJU

FDMQ15RVJU

FDMQ18RVJU

FDMQ24RVJU

CFM
560
635
600
742
812
516
675
798

Filter Initial Pressure Loss in w.g.

0.13"
0.10"
0.9”
0.13”
0.15”
0.07”
0.11”
0.14”

Submittal Data Sheet MERV 13 Filter Box w/ Filter DFBS39A13

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056 www.daikinac.com www.daikincomfort.com (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations).

SDS-DFBS39A13_1904A

Model
Dimension A
Dimension B
DFBS22A13
22.81” (579 mm)
24.06” (611 mm)
DFBS27A13
28.69” (729 mm)
29.94” (760 mm)
DFBS39A13
40.77” (1036 mm)
42.02” (1067 mm)
DFBS55A13
56.19” (1427 mm)
57.44” (1459 mm)
DFBS61A13
62.06” (1576 mm)
63.31” (1608 mm)

High efficiency MERV 13 filter box designed for bolt-on installation to the FXSQ_TAVJU, FXSQ_TBVJU, FXMQ_TBVJU series indoor unit. The slim cabinet design measures only 7” deep and features a tool-less access door to simplify the removal and replacement of the filters.

SPECIFICATIONS

Model No.:
DFBS55A13
Components Included:
Filter Cabinet MERV 13 filter set
Unit Compatibility:
FXSQ36TAVJU, FXSQ36TBVJU, FXSQ48TAVJU, FXSQ48TBVJU, FXMQ30TBVJU,

FXMQ36TBVJU, FXMQ48TBVJU, FXSA36AAVJU, FXSA48AAVJU, FXMA30AAVJU, FXMA36AAVJU, FXMA48AAVJU

Unit Weight (shipping):
28 lbs (12.7 kg)
Cabinet Dimensions (W x H x D):
57.44” x 9.50” x 7.00” (1459 mm x 241 mm x 178 mm)
Cabinet Material / Finish:
20 Ga. galvanized sheet metal
Filter Dimensions (W x H x D):
Nominal 27.6” x 8” x 4.375” (701 mm x 203 mm x 111 mm) – Qty (2) required
Filter Material / Finish:
Synthetic, electrostatically charged, non-woven media
Filter:
Qty (2) filters included as standard
Filter Rating:
MERV 13
Filter Type:
Disposable
Replacement Filter Part No.:
(2) SQM13A25

PRESSURE DROP

Compatible Fan Coil Model
FXSQ36TAVJU, FXSQ36TBVJU, FXSA36AAVJU FXMQ36TBVJU, FXMA36AAVJU
FXSQ48TAVJU, FXSQ48TBVJU, FXSA48AAVJU FXMQ48TBVJU, FXMA48AAVJU
CFM
1,130
1,377
Filter Initial Pressure Loss (in.w.g.)
0.15”
0.21”

Submittal Data Sheet MERV 13 Filter Box w/ Filter DFBS55A13 www.daikincomfort.com (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations).

SDS-DFBS55A13_1904A

Model
Dimension A
Dimension B
DFBS22A13
22.81” (579 mm)
24.06” (611 mm)
DFBS27A13
28.69” (729 mm)
29.94” (760 mm)
DFBS39A13
40.77” (1036 mm)
42.02” (1067 mm)
DFBS55A13
56.19” (1427 mm)
57.44” (1459 mm)
DFBS61A13
62.06” (1576 mm)
63.31” (1608 mm)

Submittal Data Sheet MERV 13 Filter Box w/ Filter DFBS55A13 www.daikincomfort.com (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations).

SDS-DFBS55A13_1904A

Installation Instruction:

Closed Pipe Kit for Branch Selector Box KHFP26A100CA

DESCRIPTION

Each Branch Selector boxes comes with 1 set of closed pipe kit to seal off unused piping on the indoor unit side of the branch selector box. The KHFP26A100CA is an additional set of closed pipe kit if more than 1 set of close pipe kit is required.

Components Included:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations).

Installation Instruction:

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

SPECIFICATIONS: PRODUCT IMAGE:Model

DCM601B71

Description intelligent Touch Manager (iTM) Maximum Indoor Unit Groups Max Indoor Units Max Outdoor Units Max BACnet Servers System Total with option adaptors 512 Indoor Unit Groups (1024 Indoor Units) Power Supply 24 VAC, 60 Hz Power Consumption 23 Watts Operating Temp Range 32-104°F Operating Humidity Range 85% or less (w/o condensation) Dimensions (W x H x D)

11.42 x 9.57 x 1.97 in.

Weight (Mass)

5.3 lbs. (2.4 kg) Certifications FCC Part 15 Class B DIII-NET Systems – (On board) DIII-NET Systems – (With Plus Adaptors & slot card) RJ-45 (Ethernet) 100Base-TX or 10Base-T USB Port-USB2.0 (2GB to 32GB)

RS485 (19 - 22 AWG)

Digital Input forced shutdown of all indoor unit systems Digital Input and/or Pulse Input Terminals 3 x 10 mA @ 16 VDC/ 3 x 1 pulse at 1 or 10 kWh at 100 ms interval

DCM601B71

iTouch Manager

OPTIONS:

· Software Options:

· Power Proportional Distribution (PPD) Option (DCM002A71) (1)

· Web (HTTP) Interface Software (DCM007A51)

· BACnet Client Option Software (DCM009A51)

· BACnet/IP Server Gateway Option (DCM014A51) (2)(3)

· Hardware Options:

· Plus Adapter (DGE601A72) for expanding DIII-NET ports

· Slot card for Plus adaptor (DGE601A53), added to DGE601A72 to expand available DIII-NET ports.

· WAGO I/O basic kit (60359653) and I/O modules for controlling/ monitoring of external equipment via Di, Do, Ai, Ao and Pi Submittal Data Sheet DCM601B71 – intelligent Touch Manager Project Name:

19001 Kermier Road • Waller, TX 77484 www.daikinac.com www.daikincity.com Rev.0324 (Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

· Spare Parts:

· iTM Sliding Door (Part# B72A930)

· SD Card (Part# 2336767)

Notes:

(1) The Power Proportional Distribution (PPD) option supplies the user with a reasonably calculated apportionment of the total power consumption by the Daikin air-conditioning system to individual units on the system. Because input to the PPD includes measured pulses in the refrigerant system and because the air-conditioning system includes number of variables, to include operating temperatures and pressures, piping lengths, heat exchange rates and others, no meter-type apportionment of individual user’s consumption can be made. However, the PPD feature provides an apportionment methodology that uses highly advanced technology as applied to the many variables in the air-conditioning system.

(2) The BACnet Server Gateway option cannot use together with the BACnet Client software option.

(3) BACnet/IP Server Gateway option is not compatible with the VAM unit or the Low Temp Hydrobox.

MODEL COMPATIBILITY:

The following indoor units are compatible with the iTM:

System
Model

This is the start of the file's text. The full file is on GovTribe.