2-Drawings and Specs.pdf
PDF 3 MB Posted
- Solicitation number
- 20-161-TO-55
- Issued by
- Marion County, Orlando City, Florida
About this file
This file comprises technical drawings, specifications, and guarantee documentation for a PVC roof membrane system manufactured by Siplast for the Marion County Library Headquarters reroof project located at 2720 E Silver Springs Boulevard, Ocala, Florida. The project involves recovering the existing modified bitumen roof with an 80-mil Parasolo PVC KEE fleeceback membrane system, replacing wet or damaged insulation with a 4,000 square foot allowance, installing a retrofit roof drain, and completing all associated flashing and accessory work while maintaining the existing parapet cap and roof slope. The specification calls for a Siplast-certified contractor or approved equivalent manufacturer to perform the work, which must be permitted through the City of Ocala. A mandatory on-site pre-bid meeting was scheduled for July 28 at 9:00 AM. The contractor must submit a completed proposal form, addendum acknowledgement, bid proposal affidavit, list of subcontractors within twenty-four hours of bid time, and various required exhibits including general requirements, trade scope of work, project close-out requirements, safety rules, security guidelines, environmental policy, and substance abuse policy.
The specification establishes detailed technical requirements for the 80-mil Parasolo PVC KEE membrane system, which must contain a minimum of 25 percent KEE polymer by weight and be heat-welded with lap welds between 1 and 1.5 inches for automatic machine welding and 2 inches for hand welding. All materials must be manufacturer-supplied, stored properly, and handled to prevent damage or contamination. The contractor is responsible for substrate preparation, moisture scanning to identify wet areas requiring removal and replacement, application of roofing accessories including walkways and protection pads, installation of roof drains and termination bars, and completion of a final inspection with the manufacturer's representative. Upon successful completion and post-installation procedures, the owner receives a 30-year labor and materials guarantee covering the roof membrane and flashing system without deductibles or limitations on coverage amount. The guarantee excludes damage from lightning, windstorms exceeding 74 mph, hail, earthquakes, tornados, hurricanes, structural defects, falling objects, unauthorized repairs, changes in building use, and moisture entering through adjoining walls or building components not waterproofed with approved Siplast materials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1--Bid Package.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
Rev:
14911 Quorum Drive, Suite 600 - Dallas, Texas - 75254 (800) 922-8800 www.siplast.com
Scale: NTS Detail Number:
06.08.2023
DE-SP-36-13a
REF: CHANGE OF DECK PLAIN - PARASOLO - INSULATED
CHANGE OF DECK PLAIN DETAIL
PARASOLO ROOF MEMBRANE - INSULATED (ALL SYSTEMS)
NOTES:
1. FOR HEAT-WELDING LAPS USE 1" MINIMUM WELD TO 1-1/2" MAXIMUM WELD.
2. ALL OTHER SLOPES 1:12 OR GREAT NEED TO BE FASTENED AT ANGLE CHANGE.
ROOF DECK/ SUBSTRATE
HEAT-WELD LAP (SEE NOTE #1)
PARAFAST PLATES & FASTENERS
AT SPECIFIED FASTENING PATTERN.
PARASOLO REINFORCED
MEMBRANE
ROOF INSULATION
LEGEND
HEAT WELD
https://www.siplast.com/
Sheets and Views
Model
DE-SP-36-04c
REF: ROOF EDGE - PARASOLO - INSULATED
COATED METAL ROOF EDGE
4" 4"
PARASOLO COATED METAL EDGE
(set in Parasolo Flexseal Caulk Grade
Sealant & fasten 3" o.c. staggered, reference the joint treatment detail for joints)
REINFORCED PARASOLO SMOOTH STRIPPING PLY
(8 inches wide, see note #1)
CONTINUOUS CLEAT FOR METAL EDGE
INSULATION
1. METAL EDGE AND PARASOLO STRIPPING PLY SHOULD BE INSTALLED TOGETHER IN A SAME-DAY APPLICATION.
2. FOR HEAT-WELDING LAPS USE 1" MINIMUM WELD TO 1-1/2" MINIMUM WELD.
3. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
APPROVED COVERBOARD
PARASOLO REINFORCED MEMBRANE
(adhere to horizontal surfaces as shown, extend dry down the vertical face)
HEAT WELDED LAP (see note #2)
HEAT WELDED LAP (see note #2)
8"
SEALANT
Sheets and Views
Model
DE-SP-36-08b
REF: END LAP DETAIL-ADHERED - PARASOLO
END LAP DETAIL W/ T-JOINT COVER PATCH
1. FOR HEAT-WELDING LAPS USE 1" MIN. WELD TO 1-1/2" MAXIMUM WELD.
2. T-JOINT PATCHES ARE NOT REQUIRED FOR 50 & 60 MIL PARASOLO PVC AND PARASOLO PVC KEE MEMBRANE, ALL PARASOLO TPX AND 80 MIL. PARASOLO PVC AND PVC KEE MEMBRANES REQUIRE T-JOINT PATCHES.
REINFORCED PARASOLO
MEMBRANE FIELD SHEETS
(NOT TO SCALE)
3"
MIN.
HEAT-WELDED LAP,
SEE NOTE #1
UNREINFORCED PREFABRICATED
PARASOLO® T-JOINT COVER PATCH
OR FIELD-FABRICATED
UNREINFORCED T-JOINT PATCH
MIN. 4" (102 mm) DIAMETER
Sheets and Views
Model
DE-SP-36-06a
REF: EXPANSION JOINT ROOF TO ROOF - PARASOLO - INSULATED
EXPANSION JOINT (Roof to Roof) WITH PARASOLO FLASHING
WOOD CURB
METAL EXPANSION
JOINT COVER
(fasteners w/ neoprene washers secure 18" o.c.)
GALVANIZED ROOF NAILS
(fasten a maximium of 12" o.c.)
M
IN
MEMBRANE (apply to vertical and horizontal surfaces as shown)
PARAFAST FLAT TERMINATION BAR
(fastened 8 inches o.c.)
HEAT WELDED LAP (see note #1)
PARASOLO WATER-BLOCK SEALANT
REINFORCED PARASOLO SMOOTH
MEMBRANE LOOP W/BATT INSULATION
ROOF DECK/SUBSTRATE
2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
3. PARASOLO BONDING ADHESIVE CAN BE USED UP TO A MAXIMUM FLASHING HEIGHT OF 54 INCHES. ADDITIONAL TERMINATION IS REQUIRED FOR FLASHING
HEIGHTS ABOVE 54 INCHES WHEN PARASOLO BONDING ADHESIVE IS USED. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR ADDITIONAL INFORMATION.
(adhered with Parasolo Bonding Adhesive or Parasolo Quick Spray Adhesive. See note #3)
Sheets and Views
Model
06.22.2023
DE-SP-36-15b
REF: INSIDE CORNER FABRICATION 2 - STEP JOINT PATCH - PARASOLO - INSULATED
INSIDE CORNER FABRICATION - 2 STEP JOINT PATCH DETAIL
ONE PIECE FOLD WITH "JOINT
PATCH" (DO NOT CUT) ALL
SEGMENTS MUST BE WELDED
CURB OR WALL
PARASOLO JOINT PATCH AT
MEMBRANE OVERLAP
HEAT-WELDED LAP
(see note #3)
(see note #3)
1. ALL SEGMENTS OF THE EAR MUST BE WELDED TOGETHER AND WELDED TO THE WALL.
2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.
3. FOR HEAT-WELDING LAPS USE 1" MINIMUM WELD 1-1/2" MAXIMUM WELD.
4. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING
5. PARASOLO BONDING ADHESIVE CAN BE USED UP TO A MAXIMUM FLASHING HEIGHT OF 54 INCHES. ADDITIONAL TERMINATION IS REQUIRED FOR FLASHING
HEIGHTS ABOVE 54 INCHES WHEN PARASOLO BONDING ADHESIVE IS USED. CONTACT THE SIPLAST TECHINCAL DEPARTMENT FOR ADDITIONAL INFORMATION.
1 PIECE FOLD METHOD
FOLD LINES
"ONE PIECE" TRANSITION STRIP
· FOLD "ONE PIECE" MEMBRANE AS
SHOWN ABOVE (DO NOT CUT).
· HEAT WELD ALL SEGMENTS
TOGETHER (2" min. weld)
· APPLY THE MEMBRANE AND JOINT
PATCH AS DEPICTED ON THE
RIGHT HAND SIDE.
Parasolo Quick Spray Adhesive. See note #5)
Sheets and Views
Model
DE-SP-36-01d
REF: INSULATED CURB - PARASOLO - INSULATED
INSULATED CURB
INSULATED METAL
CURB
COUNTER FLASHING
(apply to vertical and horizontal surfaces as shown)
PARAFAST FASTENERS & PLATES 12" (305 mm) O.C.
PARASOLO FLEXSEAL CAULK GRADE SEALANT
4"
2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
3. PARASOLO BONDING ADHESIVE CAN BE USED UP TO A MAXIMUM FLASHING HEIGHT OF 54 INCHES. ADDITIONAL TERMINATION IS REQUIRED FOR FLASHING
HEIGHTS ABOVE 54 INCHES WHEN PARASOLO BONDING ADHESIVE IS USED. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR ADDITIONAL INFORMATION.
Sheets and Views
Model
DE-SP-36-10e
REF: LIGHTNING PROTECTION TERMINAL-ROOF MOUNT - PARASOLO - INSULATED
LIGHTNING PROTECTION TERMINAL - ROOF MOUNT DETAIL
1. DAMAGE TO PARASOLO MEMBRANE IS EXCLUDED FROM GURANTEE COVERAGE.
2. THE PARASOLO PATCHES SHOULD BE INSTALLED BY A SIPLAST SELECT CONTRACTOR.
3. THE INSTALLATION OF THE LIGHTNING PROTECTION SYSTEM SHOULD FOLLOW THE SPECIFICATIONS OF THE LIGHTNING PROTECTION SYSTEM MANUFACTURER.
4. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
LIGHTNING ROD
CABLE LINE/LIGHTNING ROD BASE
SURFACED 6" X 6" PATCH
ROOF DECK
SECTION A
HEAT WELDED (min. 2" weld)
5" M
AX
HEAT WELDED
(min. 2" weld both sides)
SECTION A
PARASOLO FLEXSEAL
CAULK GRADE SEALANT
Sheets and Views
Model
DE-SP-36-15e
REF: OUTSIDE CORNER REINFORCEMENT - UNIVERSAL CORNER - PARASOLO - INSULATED
OUTSIDE CORNER REINFORCEMENT - UNIVERSAL CORNER DETAIL
ALTERNATE
MEMBRANE ATTACHMENT
STEP 1
STEP 2
REFERENCE THE
PARAPET AND
WALL DETAIL FOR
TERMINATION
HEAT-WELDED LAPS
(see note #2)
CONTINUOUS PERIMETER
HEAT-WELDED LAP(see note #2)
1. CORNERS MAY ALSO BE FIELD-FABRICATED USING UNREINFORCED SMOOTH MEMBRANE.
2. FOR HEAT-WELDING LAPS USE 1" MINIMUM WELD TO 1.5'' MAXIMUM WELD.
3. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
4. PARASOLO BONDING ADHESIVE CAN BE USED UP TO A MAXIMUM FLASHING HEIGHT OF 54 INCHES. ADDITIONAL TERMINATION IS REQUIRED FOR FLASHING
HEIGHTS ABOVE 54 INCHES WHEN PARASOLO BONDING ADHESIVE IS USED. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR ADDITIONAL INFORMATION.
PARASOLO REINFORCED FIELD
MEMBRANE (adhere)
PARASOLO UNIVERSAL CORNER
REINFORCED
PARASOLO ROOF
MEMBRANE HEAT-WELDED
LAPS (see note #2)
1/4"
Sheets and Views
Model
PARAPET WITH COPING AND PARASOLO FLASHING
14911 Quorum Drive, Suite 600 - Dallas, Texas - 75254
(800) 922-8800
DE-SP-36-05a
REF: PARAPET COPING - PARASOLO - INSULATED
" M
AX
METAL COPING ASSEMBLY
(installed per manufacturer's/SMACNA guidelines)
PARASOLO ROOF MEMBRANE
(apply to vertical and horizontal surfaces as shown)
PARAFAST FLAT TERMINATION BAR
(fastened 8 inches o.c.)
PARASOLO WATER-BLOCK SEALANT
2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE
DRAWING.
3. PARASOLO BONDING ADHESIVE CAN BE USED UP TO A MAXIMUM FLASHING HEIGHT OF 54 INCHES. ADDITIONAL TERMINATION IS
REQUIRED FOR FLASHING HEIGHTS ABOVE 54 INCHES WHEN PARASOLO BONDING ADHESIVE IS USED. CONTACT THE SIPLAST
TECHNICAL DEPARTMENT FOR ADDITIONAL INFORMATION.
Sheets and Views
Model
06.22.2023
DE-SP-36-03e
REF: PENETRATION - PARASOLO - INSULATED - PPRO - PFLEX
Note: This detail applies to PVC & PVC KEE systems only
PENETRATION WITH PARAPRO/PARAFLEX 531 LIQUID FLASHING
PENETRATION
(see note #3 for preparation)
6"
IM
U
R
EC
O
EN
D
ED
ROOF DECK/SUBSCRIBE
STRUCTURAL SUPPORT
4"
3" MIN. .
PARAFAST FASTENERS/PLATES
(four fasteners & plates around penetration)
PARASOLO KEE MEMBRANE
TARGET (see note #2)
4" MIN.
1. FOR HEAT-WELDING LAPS USE 1" MINIMUM. WELD TO 1-1/2" MAXIMUM WELD.
2. PARASOLO KEE MEMBRANE IS REQUIRED AT LOCATIONS TO RECEIVE PARAFLEX 531 LIQUID FLASHING SYSTEMS. PARAFLEX 531 LIQUID FLASHING CAN BE UTILIZED
WITH PARASOLO PVC KEE ONLY.
3. REFER TO SIPLAST PREPARATION GUIDELINES FOR PROPER SURFACE TREATMENT OF ALL MATERIALS PRIOR TO APPLICATION OF PARAPRO OR PARAFLEX 531 LIQUID
FLASHING MATERIALS.
4. PENETRATIONS TO RECEIVE THE PARAPRO 123 FLASHING SYSTEM OR PARAFLEX 531 LIQUID FLASHING MUST BE SECURED TO THE STRUCTURE TO PREVENT MOVEMENT.
5. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
PRO PASTE
PARAPRO 123 FLASHING SYSTEM or
PARAFLEX 531 LIQUID FLASHING
(fully adhere, see notes # 2 & 3)
Sheets and Views
Model
DE-SP-36-02a
REF: ROOF DRAIN - PARASOLO - INSULATED
ROOF DRAIN
INSULATION (slope to drain)
1. ROOF DRAIN COMPONENTS AND INSTALLATION GUIDELINES ARE SUPPLIED BY THE DRAIN MANUFACTURER.
2. SET PARASOLO MEMBRANE IN PARASOLO WATER-BLOCK SEALANT. SET MEMBRANE IN FULL BED (USE FULL TUBE) OF THE SPECIFIED WATER BLOCK
SEALANT OVER THE DRAIN FLANGE PRIOR TO SECUREMENT OF CLAMPING RING.
3. MEMBRANE MUST EXTEND MINIMUM 1" BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUST PENETRATE THE MEMBRANE.
4. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN THE CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
PARASOLO WATER-BLOCK SEALANT (see note #2)
PARASOLO REINFORCED MEMBRANE (adhere, see note #3)
CLAMPING RING
1"
Sheets and Views
Model
DE-SP-36-07b
REF: ROOF MEMBRANE LAYOUT-ADHERED - PARASOLO - INSULATED
ROOF MEMBRANE LAYOUT - ADHERED DETAIL
PARASOLO ROOF MEMBRANE - INSULATED (ADHERED SYSTEM)
1. SEE PARASOLO ADHERED SYSTEM TECHNICAL GUIDELINES TO DETERMINE PERIMETER AND PENETRATION FASTENER SPACING FOR VARIOUS DECK TYPES.
PARAPET WALL
PA
R
AP
ET
W
AL
L
ALTERNATE
SEE NOTE #1
REFERENCE PARASOLO
SERIES PARAPET WALL &
CURB FLASHING DETAILS
FOR WALL TERMINATION
PARASOLO MEMBRANE
HEAT-WELDED SEAMS
REFERENCE PARASOLO SERIES
ROOF EDGE FLASHING DETAILS
FOR EDGE TERMINATION
Sheets and Views
Model
.\SIPLAST_LOGO_3C 2004 (1).jpg
DE-SP-36-08a
REF: SIDE LAP DETAIL-ADHERED - PARASOLO - INSULATED
SIDE LAP DETAIL - ADHERED SYSTEM
PARASOLO ROOF MEMBRANE - INSULATED (FULLY ADHERED SYSTEM)
1. FOR HEAT-WELDING LAPS USE 1" MIN. WELD TO 1-1/2" MAXIMUM WELD.
HEAT-WELDED LAP, SEE NOTE #1
PARASOLO MEMBRANE
REINFORCED
ROOF
DECK/SUBSTRATE
Sheets and Views
Model
DE-SP-36-10a
REF: HEAT-WELDED WALKWAY - PARASOLO - INSULATED
HEAT WELDED WALKWAY INSTALLATION
PARASOLO ROOF MEMBRANE - INSULATED
DETAIL @ LAP
PARASOLO WALKWAY PAD
CUT FROM WALKWAY ROLL
(see note #1)
2. DO NOT CROSS ROOF MEMBRANE SEAMS WITH WALKWAY PADS, KEEP PADS A MINIMUM OF 6" AWAY FROM SEAMS.
3. REQUIRED AT ALL ROOF ACCESS POINTS.
4. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
30"6" MIN.
6"
6" SEE DETAIL @ LAP
ROUND CORNERS
(see note #1)
PARASOLO WALKWAY PAD
CUT FROM ROLL
Sheets and Views
Model
A. SIPLAST, SHALL BE LIABLE UNDER
THIS GUARANTEE ONLY IF:
1. The Membrane is installed according to
SIPLAST specifications;
2. The installation is by a roofing contractor approved in advance by SIPLAST;
3. The use of SIPLAST materials has been approved in advance by SIPLAST.
4. All costs of installation have been paid, including those of the installing contractor.
B. OWNER OBLIGATIONS
1. Leak Complaints & Claims. Leak complaints must be formally registered by the Owner directly to Siplast. Contact can be made by calling 1-800-922-8800 or through the Siplast website www.siplast.com. Any claim hereunder shall be deemed waived unless the owner shall have given SIPLAST formal notice thereof within thirty (30) days after a leak is discovered or should by reasonable diligence have been discovered. Leak repairs resulting from a cause not covered by the Guarantee are the direct responsibility of the Owner.
2. Temporary Emergency Repairs. The Owner is permitted to effect temporary repairs in the event of a roof leak as appropriate to protect the building and its contents and to protect the roof system from water intrusion. Such repairs must be limited to the immediate area causing the leak using materials compatible with the Membrane. Permanent repairs must be completed by a SIPLAST Select Contractor authorized by SIPLAST in advance.
3. Maintenance Items. Owner required maintenance consists of periodic inspection and replacement as needed of sealants at Membrane terminations such as pitch pans, counter-flashings, termination bars, and penetration flashings or similar conditions not covered by this Guarantee.
4. Guarantee Transferability. This Guarantee may be transferred or assigned to a new owner provided the functional use of the building has not significantly changed, and provided all Siplast procedures have been properly effected as well as all fees for such transfer have been paid in full by the new owner of the property. Owner shall have given formal notice to SIPAST for a request for guarantee transfer. This Guarantee is not automatically transferable or assignable by contract or operation of law, either directly or indirectly.
SIPLAST THERMOPLASTIC ROOF MEMBRANE
GUARANTEE
SAMPLE
Guarantee Date: Expiration Date: Guarantee No.:
WHEREAS, SIPLAST, INC., (SIPLAST) Highway 67 South, Arkadelphia, Arkansas has sold materials which have been used in applying a Roof Membrane to a building, owned and described as follows:
Siplast 14911 Quorum Drive, Suite 600 Dallas, TX 75254-1491
201 Bewicke Ave., Suite 208 North Vancouver, BC, Canada V7M 3M7
Customer Service in North America
1.800.922.8800 www.siplast.com
LIMITATION OF DAMAGES; MEDIATION; JURISDICTION; CHOICE OF LAW: THIS GUARANTEE IS EXPRESSLY IN LIEU OF ANY OTHER GUARANTEES OR WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, and of any other obligations or liability of Siplast, whether any claim against it is based upon negligence, breach of warranty, or any other theory. In NO event shall Siplast be liable for any CONSEQUENTIAL OR INCIDENTAL DAMAGES of any kind, including, but not limited to, interior or exterior damages and/or mold growth. The parties agree that, as a condition precedent to litigation, any controversy or claim relating to this guarantee shall be first submitted to mediation before a mutually acceptable mediator. In the event that mediation is unsuccessful, the parties agree that neither one will commence or prosecute any lawsuit or proceeding other than before the appropriate state or federal court in the State of New Jersey. This guarantee shall be governed by the laws of the State of New Jersey without regard to principles of conflicts of laws. Each party irrevocably consents to the jurisdiction and venue of the above identified courts.
SIPLAST, INC.
By: SAMPLE Kir k Goodrum
, Vice President and General
Manager
Rev. 06/2023
OWNER:
ADDRESS OF OWNER:
JOB NAME & AREA:
ADDRESS OF BUILDING:
USE OF BUILDING:
MEMBRANE:
STRUCTURAL DECK:
INSULATION:
TOTAL AREA:
CONTRACTOR:
COMPLETION DATE:
5. Traffic Surfaces / Overburden.
The expense of removing and replacing traffic surfaces or other overburden systems built over the roof shall be borne by the Owner.
C. EXCLUSIONS FROM COVERAGE
This Guarantee does not cover leaks which result from either occurrences beyond the control of SIPLAST or mistreatment both of which include but are not limited to the following:
1. Damage to the Membrane caused by loss of adhesion of any existing roofing materials from the underlying substrate to which the existing roofing materials were directly applied.
2. Damage to the Membrane caused by loss of adhesion from the existing roofing materials to which the Membrane was directly applied.
3. Damage to the Membrane caused by lightning, windstorm (defined as winds in excess of 74 mph), hail, earthquake, tornado, hurricane, or similar unusual weather occurrences.
4. Damage to the Membrane caused by any deliberate or negligent act in maintaining the roof.
5. Damage to the Membrane caused by unauthorized repairs, or subsequent work on or through the Membrane without prior written approval by SIPLAST of the methods and materials to be used.
6. Damage to the Membrane caused by structural defects or failure of any substrate component, i.e. non- Siplast materials used as insulation or vapor retarder, including defects in design or application of the substrate components.
7. Damage to the Membrane caused by falling objects.
8. Damage to the Membrane caused by movement of metal work used in conjunction with the Membrane.
9. Damage to the Membrane caused by installation of a sprinkler system or air conditioning equipment, radio or television antenna, framework for signs or photovoltaic arrays, water tower or other installation on the Membrane after the installation of the Membrane without a prior written approval by SIPLAST of the
10. Damage to the Membrane resulting from other than occasional traffic across its surface or from its use as a storage area or recreational surface, or platform for mechanical equipment of any type, or for any other similar purposes.
11. Damage to the Membrane caused by a change in use of the building without prior written approval of SIPLAST.
12. Damage to the Membrane resulting from chemical attack or from other compounds demonstrated to be deleterious to the composition of the membrane.
13. Damage to the Membrane caused by moisture entering the roof membrane system through adjoining walls and wall copings, roof membrane terminations, roof penetrations or other adjoining building components which are not waterproofed and detailed using approved SIPLAST materials, specifications and recommendations.
14. Damage to the Membrane caused by moisture/condensation resulting from building or roof system design flaws, or similar conditions beyond the control of
SIPLAST.
D. LIMITATION OF LIABILITY
SIPLAST shall be liable only for the cost of repair of such existing Membrane or installation of a replacement Membrane by a SIPLAST Select Contractor.
SIPLAST, shall not be liable for damages to other components of the roof, the building or the contents or for consequential damages. It shall be a condition to the liability of SIPLAST hereunder that SIPLAST have access to the roof area (including all scaffolding, staging and rigging as may be required by SIPLAST for such access and to be provided by the Owner) during business hours throughout the term of the Guarantee.
NOW, THEREFORE, SIPLAST, HEREBY GUARANTEES TO THE ABOVE OWNER: (Subject to the following terms and conditions), that said Roof Membrane (herein “Membrane”)(which includes roofing and flashing) shall remain in a leak-free condition resulting from a defect in manufacturing, workmanship deficiencies associated with membrane installation, or through typical weather or wear and tear for a term of twenty-five (25) years, ending on the expiration date indicated above; or SIPLAST in its sole determination and in good faith shall repair the leak in the Membrane at its own expense. This Guarantee is an unlimited type without proration or deductibles on dollar coverage amount for remedying leak causes as generally defined above. This Guarantee shall be subject to the following additional terms and conditions:
http://www.siplast.com/
A. SIPLAST, SHALL BE LIABLE UNDER
THIS GUARANTEE ONLY IF:
1. The Membrane is installed according to
SIPLAST specifications;
2. The installation is by a roofing contractor approved in advance by SIPLAST;
3. The use of SIPLAST materials has been approved in advance by SIPLAST.
4. All costs of installation have been paid, including those of the installing contractor.
B. OWNER OBLIGATIONS
1. Leak Complaints & Claims. Leak complaints must be formally registered by the Owner directly to Siplast. Contact can be made by calling 1-800-922-8800 or through the Siplast website www.siplast.com. Any claim hereunder shall be deemed waived unless the owner shall have given SIPLAST formal notice thereof within thirty (30) days after a leak is discovered or should by reasonable diligence have been discovered. Leak repairs resulting from a cause not covered by the Guarantee are the direct responsibility of the Owner.
2. Temporary Emergency Repairs. The Owner is permitted to effect temporary repairs in the event of a roof leak as appropriate to protect the building and its contents and to protect the roof system from water intrusion. Such repairs must be limited to the immediate area causing the leak using materials compatible with the Membrane. Permanent repairs must be completed by a SIPLAST Select Contractor authorized by SIPLAST in advance.
3. Maintenance Items. Owner required maintenance consists of periodic inspection and replacement as needed of sealants at Membrane terminations such as pitch pans, counter-flashings, termination bars, and penetration flashings or similar conditions not covered by this Guarantee.
4. Guarantee Transferability. This Guarantee may be transferred or assigned to a new owner provided the functional use of the building has not significantly changed, and provided all Siplast procedures have been properly effected as well as all fees for such transfer have been paid in full by the new owner of the property. Owner shall have given formal notice to SIPAST for a request for guarantee transfer. This Guarantee is not automatically transferable or assignable by contract or operation of law, either directly or indirectly.
SIPLAST THERMOPLASTIC ROOF MEMBRANE
GUARANTEE
SAMPLE
Guarantee Date: Expiration Date: Guarantee No.:
WHEREAS, SIPLAST, INC., (SIPLAST) Highway 67 South, Arkadelphia, Arkansas has sold materials which have been used in applying a Roof Membrane to a building, owned and described as follows:
Siplast 14911 Quorum Drive, Suite 600 Dallas, TX 75254-1491
201 Bewicke Ave., Suite 208 North Vancouver, BC, Canada V7M 3M7
Customer Service in North America
1.800.922.8800 www.siplast.com
LIMITATION OF DAMAGES; MEDIATION; JURISDICTION; CHOICE OF LAW: THIS GUARANTEE IS EXPRESSLY IN LIEU OF ANY OTHER GUARANTEES OR WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, and of any other obligations or liability of Siplast, whether any claim against it is based upon negligence, breach of warranty, or any other theory. In NO event shall Siplast be liable for any CONSEQUENTIAL OR INCIDENTAL DAMAGES of any kind, including, but not limited to, interior or exterior damages and/or mold growth. The parties agree that, as a condition precedent to litigation, any controversy or claim relating to this guarantee shall be first submitted to mediation before a mutually acceptable mediator. In the event that mediation is unsuccessful, the parties agree that neither one will commence or prosecute any lawsuit or proceeding other than before the appropriate state or federal court in the State of New Jersey. This guarantee shall be governed by the laws of the State of New Jersey without regard to principles of conflicts of laws. Each party irrevocably consents to the jurisdiction and venue of the above identified courts.
SIPLAST, INC.
By: SAMPLE Kir k Goodrum
, Vice President and General
Manager
Rev. 06/2023
OWNER:
ADDRESS OF OWNER:
JOB NAME & AREA:
ADDRESS OF BUILDING:
USE OF BUILDING:
MEMBRANE:
STRUCTURAL DECK:
INSULATION:
TOTAL AREA:
CONTRACTOR:
COMPLETION DATE:
5. Traffic Surfaces / Overburden.
The expense of removing and replacing traffic surfaces or other overburden systems built over the roof shall be borne by the Owner.
C. EXCLUSIONS FROM COVERAGE
This Guarantee does not cover leaks which result from either occurrences beyond the control of SIPLAST or mistreatment both of which include but are not limited to the following:
1. Damage to the Membrane caused by loss of adhesion of any existing roofing materials from the underlying substrate to which the existing roofing materials were directly applied.
2. Damage to the Membrane caused by loss of adhesion from the existing roofing materials to which the Membrane was directly applied.
3. Damage to the Membrane caused by lightning, windstorm (defined as winds in excess of 74 mph), hail, earthquake, tornado, hurricane, or similar unusual weather occurrences.
4. Damage to the Membrane caused by any deliberate or negligent act in maintaining the roof.
5. Damage to the Membrane caused by unauthorized repairs, or subsequent work on or through the Membrane without prior written approval by SIPLAST of the
6. Damage to the Membrane caused by structural defects or failure of any substrate component, i.e. non- Siplast materials used as insulation or vapor retarder, including defects in design or application of the substrate components.
7. Damage to the Membrane caused by falling objects.
8. Damage to the Membrane caused by movement of metal work used in conjunction with the Membrane.
9. Damage to the Membrane caused by installation of a sprinkler system or air conditioning equipment, radio or television antenna, framework for signs or photovoltaic arrays, water tower or other installation on the Membrane after the installation of the Membrane without a prior written approval by SIPLAST of the
10. Damage to the Membrane resulting from other than occasional traffic across its surface or from its use as a storage area or recreational surface, or platform for mechanical equipment of any type, or for any other similar purposes.
11. Damage to the Membrane caused by a change in use of the building without prior written approval of SIPLAST.
12. Damage to the Membrane resulting from chemical attack or from other compounds demonstrated to be deleterious to the composition of the
13. Damage to the Membrane caused by moisture entering the roof membrane system through adjoining walls and wall copings, roof membrane terminations, roof penetrations or other adjoining building components which are not waterproofed and detailed using approved SIPLAST materials, specifications and recommendations.
14. Damage to the Membrane caused by moisture/condensation resulting from building or roof system design flaws, or similar conditions beyond the control of
SIPLAST.
D. LIMITATION OF LIABILITY
SIPLAST shall be liable only for the cost of repair of such existing Membrane or installation of a replacement Membrane by a SIPLAST Select Contractor.
SIPLAST, shall not be liable for damages to other components of the roof, the building or the contents or for consequential damages. It shall be a condition to the liability of SIPLAST hereunder that SIPLAST have access to the roof area (including all scaffolding, staging and rigging as may be required by SIPLAST for such access and to be provided by the Owner) during business hours throughout the term of the Guarantee.
NOW, THEREFORE, SIPLAST, HEREBY GUARANTEES TO THE ABOVE OWNER: (Subject to the following terms and conditions), that said Roof Membrane (herein “Membrane”)(which includes roofing and flashing) shall remain in a leak-free condition resulting from a defect in manufacturing, workmanship deficiencies associated with membrane installation, or through typical weather or wear and tear for a term of thirty (30) years, ending on the expiration date indicated above; or SIPLAST in its sole determination and in good faith shall repair the leak in the Membrane at its own expense.
This Guarantee is an unlimited type without proration or deductibles on dollar coverage amount for remedying leak causes as generally defined above.
This Guarantee shall be subject to the following additional terms and conditions:
http://www.siplast.com/
PS-43-2 07 54 19 - 1 Polyvinyl Chloride Roofing
Roofing Specification For:
Marion County Library PVC KEE Recover
Ocala, Florida
Prepared by:
Siplast
1000 Rochelle Blvd.
Irving, Texas 75062
(800) 922-8800
This specification is provided as a general guide for use of Siplast products based on typical building conditions and standard roofing practices. Siplast is strictly a manufacturer of roofing and waterproofing systems and has no experience, training or expertise in the areas of architecture/engineering or in the area of consulting with respect to matters related to such areas.
Siplast recommends that the Owner's representative independently verify the accuracy and appropriateness of a specification provided for a specific project.
6/26/2026
PS-43-2 07 54 19 - 2 Polyvinyl Chloride Roofing
SECTION 07 54 19 POLYVINYL CHLORIDE ROOFING (Rev 07/2019)pq
PART 1 GENERAL
1.01 SECTION INCLUDES:
A. Preparation of Substrate to Receive Roofing Materials
B. Roof Insulation Application to Prepared Substrate
C. Roof Membrane Application
D. Roof Flashing Application
E. Incorporation of Sheet Metal Flashing Components and Roofing Accessories into the Roof System
1.02 PRODUCTS INSTALLED BUT NOT FURNISHED UNDER THIS SECTION
A. Sheet Metal Flashing and Trim
B. Roof Specialties
1.03 RELATED SECTIONS
A. Section [----] - Rough Carpentry
B. Section [----] - Roof Decks
C. Section [----] - Sheet Metal Flashing and Trim
D. Section [----] - Roof Specialties
1.04 REFERENCE STANDARDS
References in these specifications to standards, test methods and codes, are implied to mean the latest edition of each such standard adopted. The following is an abbreviated list of associations, institutions, and societies which may be used as references throughout this specification section.
ASTM American Society for Testing and Materials Philadelphia, PA
FM Factory Mutual Engineering and Research Norwood, MA
NRCA National Roofing Contractors Association Rosemont, IL
OSHA Occupational Safety and Health Administration Washington, DC
PS-43-2 07 54 19 - 3 Polyvinyl Chloride Roofing
SMACNA Sheet Metal and Air Conditioning Contractors National Association Chantilly, VA
UL Underwriters Laboratories Northbrook, IL
1.05 DESCRIPTION OF WORK
The basic work descriptions required in this specification are referenced below.
Project Type: Recover
Deck: Gypsum Slope: 1/8th
Moisture Scan A moisture scan must be completed prior to installation of membranes to identify wet areas that must be removed and replaced.
Existing Assembly: Siplast Paradiene 20/30 System over polyiso and fiber board. Replace the areas of wet//deteriorated insulation and membrane using compatible materials, bringing them back level with surrounding surfaces.
Prep of existing roof: Lightly pressure wash, vacuum, or power broom existing Paradiene 30 cap sheet to remove any loose granules.
Roof System: 80 mil Parasolo PVC KEE Fleeceback, containing a minimum of 25% KEE polymer by weight, applied in Parafast T low rise foam.
Flashing System: 80 mil Parasolo PVC KEE Smooth, containing a minimum of 25% KEE polymer by weight, applied in bonding adhesive, in conjunction with a PMMA 2 part liquid flashing system - Parapro 123.
1.06 SUBMITTALS
All submittals which do not conform to the following requirements will be rejected.
A. Submittals Prior to Contract Award:
1. Letter from the proposed primary roofing manufacturer confirming that the bidder is an acceptable Contractor authorized to install the proposed system.
2. Letter from the primary roofing manufacturer stating that the proposed application will comply with the manufacturer's requirements in order to qualify the project for the specified guarantee.
B. Submittals Prior to Project Close-out:
1. Manufacturer's printed recommendations for proper maintenance of the specified roof system including inspection frequencies, penetration addition policies, temporary repairs, and leak call procedures.
PS-43-2 07 54 19 - 4 Polyvinyl Chloride Roofing
1.07 QUALITY ASSURANCE
A. Acceptable Products: Primary roofing products, including each type of sheet, all manufactured in the United States, shall be supplied by a single manufacturer which has been successfully producing the specified types of primary products for not less than 10 years. The primary roofing products shall have maintained a consistent composition for a minimum of five years.
B. Product Quality Assurance Program: Primary roofing materials shall be manufactured under a quality management system that is monitored regularly by a third party auditor under the ISO 9001 audit process. A certificate of analysis (COA) for reporting/confirming the tested values of the actual material being supplied for the project will be required prior to project close-out.
C. Acceptable Contractor: Contractor shall have a minimum of 2 years experience in successfully installing the same or similar roofing materials and be certified in writing by the roofing materials manufacturer to install the primary roofing products.
D. Scope of Work: The work to be performed under this specification shall include but is not limited to the following: Attend necessary job meetings and furnish competent and full time supervision, experienced roof mechanics, all materials, tools, and equipment necessary to complete, in an acceptable manner, the roof installation in accordance with this specification.
Comply with the latest written application instructions of the manufacturer of the primary roofing products. In addition, application practice shall comply with requirements and recommendations contained in the latest edition of the National Roofing Contractor's Association (NRCA) Roofing Manual as published by the National Roofing Contractor's Association.
E. Local Regulations: Conform to regulations of public agencies, including any specific requirements of the city and/or state of jurisdiction.
F. Manufacturer Requirements: Ensure that the primary roofing materials manufacturer provides direct trained company personnel to attend necessary job meetings, perform periodic inspections as necessary, and conducts a final inspection upon successful completion of the project.
1.08 PRODUCT DELIVERY STORAGE AND HANDLING
A. Delivery: Deliver materials in the manufacturer's original sealed and labeled containers and in quantities required to allow continuity of application.
B. Storage: Refer to the manufacturer’s published literature for storage guidelines.
C. Handling: Handle all materials in such a manner as to preclude damage and contamination with moisture or foreign matter. Handle rolled goods to prevent damage to edges or ends.
D. Damaged Material: Any materials that are found to be damaged or stored in any manner other than stated above will be automatically rejected, removed and replaced at the Contractor's expense.
PS-43-2 07 54 19 - 5 Polyvinyl Chloride Roofing
1.09 PROJECT/SITE CONDITIONS
A. Requirements Prior to Job Start
1. Notification: Give a minimum of 5 days notice to the Owner and manufacturer prior to commencing any work and notify both parties on a daily basis of any change in work schedule.
2. Permits: Obtain all permits required by local agencies and pay all fees which may be required for the performance of the work.
3. Safety: Familiarize every member of the application crew with all fire and safety regulations recommended by OSHA, NRCA and other industry or local governmental groups.
B. Environmental Requirements
1. Precipitation: Do not apply roofing materials during precipitation or in the event there is a probability of precipitation during application. Take adequate precautions to ensure that materials, applied roofing, and building interiors are protected from possible moisture damage or contamination.
2. Temperature Restrictions - adhesive: Refer to the manufacturer’s published guidelines for temperature restrictions for adhesive applications.
C. Protection Requirements
1. Membrane Protection: Provide protection against staining and mechanical damage for newly applied roofing and adjacent surfaces throughout this project.
2. Limited Access: Prevent access by the public to materials, tools and equipment during the course of the project.
3. Debris Removal: Remove all debris daily from the project site and take to a legal dumping area authorized to receive such materials.
4. Site Condition: Complete, to the owner's satisfaction, all job site clean-up including building interior, exterior and landscaping where affected by the construction.
1.10 GUARANTEE/WARRANTY
A. Roof Membrane Guarantee: Upon successful completion of the project, and after all post installation procedures have been completed, furnish the Owner with the manufacturer's 30 year labor and materials guarantee covering the roof membrane/flashing system. The guarantee shall be a term type, without deductibles or limitations on coverage amount, and shall be issued at no additional cost to the Owner.
> Siplast 30-year Parasolo PVC KEE Roof Membrane Guarantee
PART 2 PRODUCTS
PS-43-2 07 54 19 - 6 Polyvinyl Chloride Roofing
2. 02 DESCRIPTION OF SYSTEMS
A. Roofing Membrane: A fleecebacked roof membrane consisting of one ply of a prefabricated, polyester scrim-reinforced, polyvinyl chloride (PVC) membrane formulated with an Elvaloy® Ketone Ethylene Ester (KEE) copolymer, applied over a prepared substrate. The roof membrane shall have a factory-adhered polyester fleece backing on the bottom side. The roof system shall meet or exceed the minimum criteria established by ASTM D4434 Standard Specification for Poly(Vinyl Chloride) Sheet Roofing (Type III). The minimum thickness of the membrane shall be 80 mils not including thickness of the fleece, as established by ASTM D751 Standard Test Method for Coated Fabrics. The minimum thickness of the flashing membrane over the reinforcement scrim shall be 27 mils (0.685 mm), as established by ASTM D7635 Standard Test Method for Measurement of Thickness of Coatings Over Fabric Reinforcement.
> Siplast Parasolo KEE Fleeceback roof system – 80 mil > Must contain 25% or more KEE polymer by weight
B. Flashing Ply (smooth): A smooth-surface roof membrane consisting of one ply of a prefabricated, polyester scrim-reinforced, polyvinyl chloride (PVC) membrane formulated with an Elvaloy® Ketone Ethylene Ester (KEE) copolymer, applied over a prepared substrate. The roof system shall meet or exceed the minimum criteria established by ASTM D4434 Standard Specification for Poly(Vinyl Chloride) Sheet Roofing (Type III). The thickness of the flashing membrane shall be 80 mils, as established by ASTM D751 Standard Test Method for Coated Fabrics. The thickness of the flashing membrane over the reinforcement scrim shall be 27 mils (0.685 mm), as established by ASTM D7635 Standard Test Method for Measurement of Thickness of Coatings Over Fabric Reinforcement.
> Siplast Parasolo PVC KEE flashing system – 80 mil > Must contain 25% or more KEE Polymer by weight
C. Catalyzed Acrylic Resin Flashing System: A specialty flashing system consisting of a liquid-applied, fully reinforced, multi-component acrylic membrane installed over a prepared or primed substrate. The flashing system consists of a catalyzed acrylic resin primer, basecoat and topcoat, combined with a non-woven polyester fleece. The resin and catalyst are pre-mixed immediately prior to installation. The use of the specialty flashing system shall be specifically approved in advance by the membrane manufacturer for each application.
> Parapro 123 Flashing System by Siplast; Irving, TX
D. Substitute Systems: The following substitute systems shall be considered in lieu of the specified basis of design. Both to have a thickness of 80 mils:
- KEE Stone by The Garland Company
- TremPly by Tremco
2.03 ROOFING ACCESSORIES
A. Roofing Adhesives
PS-43-2 07 54 19 - 7 Polyvinyl Chloride Roofing
1. Flashing Membrane Adhesive: A solvent-based, low VOC, rubberized adhesive designed for bonding PVC single-ply roofing membranes and flashings to various roofing substrates.
> Parasolo PVC Bonding Adhesive by Siplast; Irving, TX
2. Pourable Sealer: A single component, moisture cure, self-leveling sealant designed for use around penetrations in pitch pan details.
> Parasolo PVC 1-part Pourable Sealant White by Siplast; Irving, TX
B. Sealant: A solvent-based, UV resistant synthetic elastomeric sealant for the completion of details.
>Parasolo Flexseal Caulk Grade by Siplast; Irving, TX
C. Water Block: A single component butyl-based high viscosity sealant for sealing the flashing membrane to the substrate behind exposed termination bars and at drain flanges.
> Parasolo Water Block by Siplast; Irving, TX
E. Membrane Conditioner/Cleaner: A solvent-based agent used to clean exposed or contaminated seams prior to heat welding to remove any residue that may compromise lap welding.
>Parasolo Membrane Conditioner by Siplast; Irving, TX
F. Membrane Separation Pad: A non-woven polyester mat, having a weight of 3 oz./yd. (85 g/m2), used beneath mechanically attached single-ply membranes in re-cover applications, as well as on top of the roof membrane in ballasted systems.
>Parasolo Poly Separation Layer by Siplast; Irving, TX
G. PVC Membrane Flashing Accessories
1. Outside Corner Flashing: A molded PVC membrane having a thickness of 0.075 inch
(1.9 mm), designed to accommodate outside corners of base and curb flashing details.
The molded flashing component shall be hot-air welded directly to the specified PVC
>Parasolo PVC Outside Corner by Siplast; Irving, TX
2. Inside Corner Flashing: A molded PVC membrane designed to accommodate inside corners of base and curb flashing details. The molded flashing component shall be hot-air welded directly to the specified PVC membrane.
>Parasolo PVC Inside Corner by Siplast; Irving, TX
3. Fluted Corner Flashing: A molded PVC membrane having a thickness of 0.055 inch (1.4 mm), designed to accommodate corners of base and curb flashing details having dimensions that cannot be addressed using standard pre-formed PVC inside or outside corner flashing components. The molded flashing component shall be hot-air welded directly to the specified PVC membrane.
PS-43-2 07 54 19 - 8 Polyvinyl Chloride Roofing
>Parasolo PVC Fluted Corner by Siplast; Irving, TX
4. Flashing Strip: An 8-inch wide molded PVC membrane strip having a thickness of 0.045 inch (1.14 mm), designed for general repairs and to strip-in PVC coated metal flanges.
>Parasolo PVC Flashing Strip by Siplast; Irving, TX
5. Termination Bar with Receiver: An extruded aluminum termination bar with rounded edges and an angled sealant receiver and lower leg bulb stiffener, having factory-punched, slotted holes spaced on 6-inch (152 mm) centers.
>Parafast Lip Termination Bar 6 Inch on Center by Siplast; Irving, TX
6. Termination Bar with Receiver: An extruded aluminum termination bar with rounded edges and an angled sealant receiver and lower leg bulb stiffener, having factory-punched, slotted holes spaced on 8-inch (203 mm) centers.
>Parafast Lip Termination Bar 8 Inch on Center by Siplast; Irving, TX
7. Flat Termination Bar: A flat, extruded aluminum termination bar with rounded edges, having factory-punched, slotted holes spaced on 6-inch (152 mm) centers.
>Parafast Flat Termination Bar 6 Inch on Center by Siplast; Irving, TX
8. Flat Termination Bar: A flat, extruded aluminum termination bar with rounded edges, having factory-punched, slotted holes spaced on 8-inch (203 mm) centers.
>Parafast Flat Termination Bar 8 Inch on Center by Siplast; Irving, TX
9. Pre-formed Vent Boots: A molded PVC membrane used to flash pipe and conduit penetrations having a diameter of 1 to 6 inches (25 to 152 mm). The pre-formed vent boots shall be hot-air welded directly to the PVC roof membrane.
>Parafast PVC Conical Pipe Boot by Siplast; Irving, TX
10. Cover Patches at T-Joints: A molded PVC membrane used to reinforce the T-joints of the specified PVC membrane system.
>Parasolo PVC T-Joint Cover Patch by Siplast; Irving, TX H. Walktread: A prefabricated, extruded and embossed PVC protection pad with a skid-resistant surface.
1. Thickness: 1/8 inch (3.2 mm)
2. Width: 30 in (76.2 cm)
> Parasolo Walkway by Siplast; Irving, TX
PART 3 EXECUTION
3.01 PREPARATION
PS-43-2 07 54 19 - 9 Polyvinyl Chloride Roofing
A. General: Sweep or vacuum all surfaces, removing all loose aggregate and foreign substances prior to commencement of roofing. A light pressure wash is also acceptable in a recover application.
B. Remove All Existing:
- Base flashings
- Edge metal
- Flanged metal flashings
- Cants
- Walkways
- Non functional penetrations/curbs
- Drain assemblies
- Metal trim, counterflashing
C. Wet Areas. Remove any areas of the existing assembly where moisture is present and replace with compatible materials, bringing the area back to level with surrounding surfaces.
3.03 ROOF MEMBRANE INSTALLATION
A. Membrane Application: Apply roofing in accordance with roofing system manufacturer's instructions and the following requirements. Application of roofing membrane components shall immediately follow application of base sheet and/or insulation as a continuous operation.
B. Aesthetic Considerations: Construction of an aesthetically pleasing overall appearance of the finished roof application is a standard requirement for this project. Make necessary preparations, utilize recommended application techniques, apply the specified materials and exercise care in ensuring that the finished application is acceptable to the Owner.
C. Roofing Application: Apply roofing to be free of wrinkles, creases or fishmouths. Use a blower and/or broom to remove any dirt or debris from the substrate surface.
1. Unroll the specified fleece-back PVC sheets in place and fold back sheets in the long dimension to allow adhering of membrane, one half of sheet at a time. Alternatively, align a full roll of membrane with the factory-applied lap line on the previously installed sheet.
Roll out the roll approximately 20 feet (6.1 m) checking to see that the edge of the new roll is straight with the line. Pick up the tail end of the previously rolled-out membrane and pull back over top of the roll of membrane.
2. Apply the specified low-rise foam adhesive in a “spatter pattern” over the substrate to yield a heavily textured, even coating of approximately 1/4- inch (6.2 mm) to 1/2- inch (12 mm) nominal thickness height on the peaks of the spattered adhesive. Allow the adhesive to rise and apply the roof membrane before the adhesive begins to “skin” over.
3. Lay half of the membrane into the wet adhesive and roll into place with a clean 150 lb.
roller. Repeat the process for the other half of sheet. If following the alternative method, pull the sheet back to its original position, and roll into place. Make sure that the lap line is followed when re-installing the sheet.
4. Where the substrate angle changes in excess of 5 degrees (i.e. 1-inch slope), mechanically attach the membrane into the structural deck on 12-inch centers, keeping
PS-43-2 07 54 19 - 10 Polyvinyl Chloride Roofing the fasteners 1/4 to 3/4 inch from the angle change. At curbs and walls, mechanically attach the membrane into the structural deck on 12-inch centers, keeping the fasteners 1/4 to 3/4 inch from the membrane edge. Alternatively, at walls/curbs extend the membrane a minimum of 3 inches up the vertical flashing substrate and mechanically attach the specified flat termination bar at the top edge of the membrane. The termination bar must be installed within 1.5 to 2 inches (38 to 51 mm) of the horizontal plane of the roof, with a minimum of 1-inch (25 mm) of membrane extending above the termination bar. Prior to mechanical attachment of the termination bar, apply the specified water block sealant on the flashing substrate behind the membrane where the termination bar will be installed.
5. Install a minimum of 4 fasteners evenly spaced around all round, square, “L”-beam or “H”-beam penetrations, keeping the fasteners 1/4 to 3/4 inches from the penetration. At penetrations having a larger diameter, install fasteners around the penetration on 12-inch centers.
6. Clean the laps of membrane that have become dirty or contaminated using the specified conditioner. Heat weld all side and end laps of the membrane during each day’s application. All welds must be continuous, without voids, and free of burns and scorch marks. Weld shall be a minimum width of 1.5 inches (38 mm) for automatic machine welding and 2 inches (51 mm) for hand welding. Contact the manufacturer of the heat-welding equipment for specific guidelines on operating the equipment. Hand-roll the side laps and head laps of the membrane behind the heat welder when hand welding.
D. Flashing Application - General: Locate all penetrations at least 24 inches from curbs, walls, and edges to provide access for proper application of the specified flashing materials.
Reinforce all coated metal and membrane flashing corners using preformed corners or non-reinforced membrane. Hot-air weld all flashing membranes, accessories, and coated metal to have a minimum 2-inch (51 mm) hand-welded or minimum 1.5-inch (38 mm) automatic machine-welded lap. Reference the manufacturer’s standard details for all flashing conditions.
E. Flashing Application - Coated Metal Flashings: Form coated metal flashings in accordance with the manufacturer’s published specifications. Reference the manufacturer’s standard details for all flashing conditions. Gap joints of coated metal edge, and flashing sections by a 1/4-inch (6 mm) to allow for expansion and contraction. Apply 2-inch (51 mm) aluminum tape over the joint as a bond-breaker, to prevent welding in this area. Hot-air weld a 6-inch (152 mm) unsupported membrane flashing strip to both sides of the joint, with approximately 1-inch (25 mm) on either side of the joint left un-welded to allow for expansion and contraction. Lap all joints of coated metal sealant pans, scupper inserts, corners of roof edging and base flashing, or pop-rivet a separate metal piece to create a continuous flange condition. Hot-air weld a 6-inch (152 mm) strip of reinforced membrane flashing over all seams that will not be sealed during subsequent flashing installation.
F. Reinforced Smooth Flashing Application - Adhered Membrane Flashing (solvent based adhesive): Apply the solvent-based bonding adhesive to both the underside of the membrane and the substrate at the minimum rate published by the manufacturer. Allow the bonding adhesive to dry until tacky to the touch before application of the flashing membrane.
* NOTE: For adhered flashing with a horizontal lap orientation, apply the flashing sheet in maximum sheet widths of 54 inches.
PS-43-2 07 54 19 - 11 Polyvinyl Chloride Roofing
G. Water Cut-Off: At end…
This is the start of the file's text. The full file is on GovTribe.