BAMBERG

Job Corps Center Bamberg, SC

Facility Planning Report Volume II

Supporting Data

Final June 2014

Department of Labor/ Office of Job Corps

BAMBERG

Job Corps Center Bamberg, SC

Facility Planning Report Volume II

Supporting Data

Final June 2014

CDSS/CPP Building 1

VOLUME I - Planning Strategy

• Acronyms and Abbreviations

• Defi nition of Terms

• Executive Summary

• Existing Site Plan

• Center Statistics

• Facility Survey Assessment Results and Recommendations

1.0 Introduction

• Objective and Scope

• Report Contents

2.0 Existing Conditions

• Background

• Ownership

• General Site Conditions

• General Building Conditions

• Preventive Maintenance

• Facility Assessment by Function

• Environmetal Management

• Resource Use/Conservation

• Sustainability

• Accessibility Standards

• Completed and Current Projects

• Defi ciency Summary

3.0 Planning Analysis

• Space Utilization Analysis

• Federal Real Property Asset Management

• Mission Dependency Site Plan

• Defi ciency Analysis

• Facility Condition Summary

• Building Condition by Function

• Building Condition Site Plan

• Planning Analysis Results and Conclusions

4.0 Recommendations

• Status of Previous Plan

• Signifi cant Issues

• Proposed Plan

• Funding Not Corrected (FNC) Defi ciencies

• Summary of Proposed Projects

• Proposed Site Plan

• Implementation Plan

• Summary List of National Projects

• Project Data Sheet

VOLUME II - Supporting Data

Acronyms and Abbreviations Defi nition of Terms

Executive Summary

1.0 Site Layout and Plans

• Vicinity Map

• Location Map

• Existing Site Plan

2.0 Descriptions

• Buildings and Structures

• Space Utilization By Function

• NSF by Building

• Environmental Management

• Environmental Management Report

• Radon Report

• Site Descriptions

• Building Descriptions

3.0 Defi ciencies

Appendices: Correspondence and Reports Appendix A. Center Review Meeting Minutes, Survey Brief and Student Questionnaire Appendix B. Life Safety Defi ciencies and List Appendix C. O&M Defi ciencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix

ACRONYMS AND ABBREVIATIONS

A Amperage

A/V Audio/Visual ABA Architectural Barriers Act ABAAS Architectural Barriers Act Accessibility Standard ARRA American Recovery and Reinvestment Act of 2009 ACT Advanced Career Training ACM asbestos-containing materials ADT Alphanumeric Display Terminal AFUE Annual Fuel Utilization Efficiency AHU Air Handling Unit AMA American Medical Association ANSI American National Standards Institute ARRA American Recovery and Reinvestment Act of 2009 ASD Active Subslab Depressurization ATS Automatic Transfer Switch BTU/hr British Thermal Unit/hour BTU/GSF/Y British Thermal Unit/Gross Square Foot/Year CAA Clean Air Act CCF Hundred Cubic Feet CCTV Closed Circuit Television Cameras CDC Child Development Center CDC Center for Disease Control and Prevention CDP Career Development Period CDSS Career Development Service System CFL Compact Fluorescent Light Bulbs CFM Cubic Foot per Minute CMMS Computerized Maintenance Management System CMU Concrete Masonry Unit CIS Center Information System CO Carbon Monoxide CO Contracting Officer COTR Contracting Officer’s Technical Representative CPP Career Preparation Period CRA Construction, Rehabilitation, and Acquisition CSOW Center Statement of Work CTP Career Transition Period CTS Career Transition Services

CTST Career Technical Skills Training (formerly Vocational Skills Training [VST])

CWA Clean Water Act DDC Direct Digital Control DFAM Division of Facilities and Asset Management DOL Department of Labor EISA Energy Independence and Security Act of 2007 EMT Emergency Medical Technician EMT Electrical Metal Tubing (Conduit) EO Executive Order EPA U.S. Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act (1986) EPDM Ethylene Propylene Diene Monomer ESC Engineering Support Contractor ESCIS Engineering Support Contractor Information System ESL English as a Second Language ESP Evaluation of Student Progress oF Degrees Fahrenheit FACP Fire Alarm Control/Annunciator Panel fc Foot Candle FCI Facility Condition Index FNC Funded Not Corrected FOP Financial Operating Plan FRPC Federal Real Property Council FY Fiscal Year GAL Gallon GAL/GSF Gallon/Gross Square Foot GAO General Accounting Office GED General Educational Development GFCI Ground Fault Circuit Interrupter gph Gallon per Hour GPRA Government Performance Results Act GSA General Services Administration GSF Gross Square Foot

HID High Intensity Discharge HP Horsepower HSD High School Diploma HVAC Heating, Ventilation, and Air Conditioning

IAC Industry Advisory Council IBC International Building Code IMC International Mechanical Code ION Inventory of Needs IPC International Plumbing code ISDN Integrated Service Digital Network IT Information Technology KBTU/GSF/YR Thousand British Thermal Unit/Gross Square Foot/Year kV Kilovolt kVA Kilovolt-Ampere JCC Job Corps Center JCDC Job Corps Data Center JCH Job Corps Handbook JTM Job Training Match KCF One Thousand Cubic Feet (Natural Gas/Propane Measure) kWh Kilowatt Hour LAN Local Area Network LED Light Emitting Diode LF Linear Foot (lin. ft.)

MBH Thousand BTUs per Hour MBTU Thousand British Thermal Unit MDP Main Distribution Panel MWH Megawatt Hour MC Mission Critical MCF Million Cubic Feet MDNC Mission Dependent, Not Critical MDP Main Distribution Panel MLO Main Lug Only m/s Meters/Second MTS Manual Transfer Switch N/A Not Applicable NEC National Electric Code NEMA National Electrical Manufacturers Association NEP National Employer Partnership NESHAP National Emissions Standards for Hazardous Air Pollutants NFPA National Fire Protection Association NJCAA National Job Corps Alumni Association NMD Not Mission Dependent

NOA Notice of Acceptance NRHP National Register of Historic Places NSF Net Square Foot OBS On Board Strength OA Outreach and Admissions OIG Office of Inspector General O&M Operations and Maintenance OMS Outcome Measurement System OSHA Occupational Safety and Health Administration PA Public Address PAG Program Assessment Guide PCB Polychlorinated Biphenyl PCDP Personal Career Development Plan pCi PicoCurie PLF Pounds Per Linear Foot PM Preventative Maintenance PM Project Manager PV Photovoltaic PVC Polyvinyl Chloride QMS Quality Measurement System RA Resident Advisor RCRA Resource Conservation and Recovery Act RTU Rooftop-Packaged Unit SGA Student Government Association SHPO State Historic Preservation Office SF Square Foot (sq. ft.)

SPCC Spill Prevention, Control and Countermeasure SPD Single Parent Dorm SST Social Skills Training T5 Fluorescent Lighting Designation (High Efficiency) T8 Fluorescent Lighting Designation T12 Fluorescent Lighting Designation (Low Efficiency) TSCA Toxic Substances Control Act of 1976 TV Television TVSS Transient Voltage Surge Suppression UEV Unevaluated UFAS Uniform Federal Accessibility Standards UL Underwriters Laboratories

USDA U. S. Department of Agriculture v Volt VCR Video Cassette Recorder VOC Volatile Organic Compound VST Vocational Skills Training w Watt WAN Wide Area Network WBL Work-Based Learning WIA Workforce Investment Act WIB Workforce Investment Board WPO Work Program Officer

DEFINITION OF TERMS

Accessibility: The degree to which a product, device, service, or environment is available to as many people as possible. Accessibility can be viewed as the "ability to access" and benefit from some system or entity. The Federal Government is required to comply with published law (Architectural Barriers Act (ABA) of 1968 , American Disabilities Act of 1990), regulations and related standards. Accessibility laws and standards have evolved over the past 12 years. DOL now follows ABA Accessibility Standards for Federal Facilities (ABAAS) adopted by the General Services Administration.

Annual Operating Cost: This FRPC performance measure reflects the cost to operate each used asset and consists of lease costs as well as costs related to recurring maintenance, utilities, janitorial, and roads and grounds expenses (Source: FRPC 2012).

Building: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a building includes an enclosure for human occupancy that serves a variety of functions (food service, education, recreation, medical/dental, storage, administration) and is likely to have full utility services (heating, cooling, etc.). A building typically is over 400 square feet.

Building Condition Rating by Function: Each building is assigned a building condition based on the physical condition of the building and the impact on the functional use of the facility. Three ratings are possible:

Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.

Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.

Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required.

Building/Structure Ratings: Each building is rated according to three ratings (good, fair, and poor) based on evaluations of the structure, exterior, interior, mechanical, and electrical elements. Three ratings are possible:

Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.

Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.

Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required

Construction Type: The International Building Code (IBC) construction classifications include the following:

Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.

Type II and III. Any type of construction where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.

Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces.

Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.

Contract Strength: The authorized number of students at a Center in accordance with the contract between the Region and Center Operator.

Deficiency: A deficiency at a Center represents the spectrum of conditions related to the Center’s mission and/or its physical, functional, or operational features do not meet related goals, standards, codes, or other measures of acceptability. Each deficiency at a JCC or CCC initially is categorized as one of the following three deficiencies: Program, Site, or Building:

Program: Program deficiencies address issues such as square footage shortages or the omission of amenities required or standard for the proper operation of a particular Job Corps function.

Site: Site deficiencies indicate adverse site and infrastructure conditions which negatively impact operations and environment (e.g., site lighting, sidewalks, roads, etc.)

Building: Building deficiencies indicate adverse conditions at the building level.

This element includes the substructure, shell, interior, services (plumbing, HVAC, fire protection, and electrical), and equipment and furnishings.

Deficiency Classifications (I to IV): Deficiency classifications are defined as follows:

Class IA - Deficiencies which address imminent life safety and health hazards.

Class II - Deficiencies which address code violations, however, do not represent imminent life safety and health hazards.

A - Deficiencies which violate code (Federal, State or Local) and may result in an interruption of center operations if not corrected.

B - Deficiencies which violate code (Federal, State or Local) and have no immediate impact on center operations if not corrected.

C- Deficiencies which are not in compliance for accessibility in accordance with the Architectural Barriers Act (ABA), Americans with Disabilities Act (ADA), Uniform Federal Accessibility Standards (UFAS), or other applicable standards.

Class III - Deficiencies which address facility repair, replacement or maintenance.

A - Deficiencies which if not corrected may result in an interruption of center operations.

B - Deficiencies which if not corrected will have minimal impact on center operations or can be mitigated through temporary measures until the deficiency is corrected.

Class IV – Deficiencies which address programmatic needs.

A - Deficiencies which if corrected produce substantial improvements in the quality of the learning and living environment.

B - Deficiencies which if corrected are desirable enhancements.

Deficiency Funding Status: The status of the deficiency included the following categories:

Funded deficiencies report indicates the funding year for funded Regional projects, which have dollar amounts shown, or deficiencies assigned to funded National and Regional projects without dollar amounts. Major Regional projects are equivalent to National projects but assigned to the Federal agency (e.g., U.S.

Department of Agriculture) that acts as the Center operator. All operations and maintenance (O&M) deficiencies are treated as funded through the Center Operators O&M contract within the Region.

Proposed deficiencies have been assigned to a proposed future National project.

Unfunded deficiencies are Regional projects unless or until they are assigned to a National project.

Deficiency Status: The deficiency status is tracked and updated during the three-year facility survey cycle, or as such deficiencies are corrected and reported. The status includes:

Uncorrected: Once a deficiency is identified, documented, reported, and assigned for correction, the deficiency remains uncorrected until such time that the deficiency is corrected, reported, and verified.

Corrected: A corrected deficiency is one that has been assigned, funded, corrected, reported, and verified. Typically, the ESC verifies completion of the deficiency through the facility survey or site visit. The Center also may report completion and provide verifiable evidence of the correction, subject to review by the ESC.

Funded Not Corrected: A deficiency that has been approved and authorized as a regional project through the CRA budget, emergency or supplemental funding, or the Life Safety Memo. Note: the funding may not have reached the Center yet as the first steps are a FOP allocation by the National Office and a contract modification by the Region.

No Longer Needed: A no longer needed deficiency is one that has been approved and funded as a Regional project, but due to subsequent circumstances, has been reported by the Center as no longer being required to be accomplished. This type of deficiency is verified and confirmed by the ESC and removed from the Funded Not Corrected deficiency category. The Center should take action with its Region to return the funds.

Facility Condition Index: This performance measure reflects the condition of each asset by comparing the current repair needs to the replacement value of the asset. The index is expressed as a percentage, with 100% being a facility with no repair needs.

Gross Square Foot: The sum of all areas on all floors of a building included within the outside faces of its exterior walls, including all vertical penetration areas, for circulation and shaft areas that connect one floor to another. Gross Area is computed by physically measuring or scaling measurements from the outside faces of exterior walls, disregarding cornices, pilasters, buttresses, etc., that extend beyond the wall faces. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Measured in terms of Gross Square Feet (GSF): GSF = Net Usable Area + Structural Space (Source: http://nces.ed.gov/pubs2006/ficm/).

Mission Dependency: The value an asset brings to the performance of the mission as determined by the governing agency. Specific elements of this category include (FRPC 2012):

Mission Critical - – Without constructed asset or parcel of land, mission is compromised.

Mission Dependent, Not critical (MDNC) - Does not fit into Mission Critical or Not Mission Dependent categories.

Not Mission Dependent (NMD) – Mission unaffected

Ownership (Owned vs Leased): If the property is owned, the Federal Government has fee simple interest for the real property asset. If the property is leased, the rights to use the asset are assigned to the Federal Government by a private entity or a non-Federal Government entity for a defined period of time in return for rental payments (FRPC 2012).

National Project: Generally large and complex projects that require professionally prepared drawings and specifications that are time phased (design and construction) and contracted by the DOL National Office.

Net Square Foot: The sum of all areas on all floors of a building assigned to, or available for assignment to, an occupant or specific use. This value is computed by physically measuring or scaling measurements from the inside faces of surfaces that form the boundaries of the designated areas. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Included should be major space use categories for assignable space (e.g., dormitories, education, recreation, etc.) that are used to accomplish the institution’s mission. Net Square foot: NASF = Sum of Areas Designated by the Major Space Use Categories (Source: http://nces.ed.gov/pubs2006/ficm/).

On Board Strength (OBS): An efficiency rating that depicts the extent to which the Centers operate at full capacity. The measure is calculated by the percent of planned capacity (number of students that center is authorized to serve on any given day) that is utilized on a cumulative basis. The national goal for OBS is 100%.

Preventive Maintenance: The care and servicing by personnel for the purpose of maintaining equipment and facilities in satisfactory operating condition by providing for systematic inspection, detection, and correction of incipient failures either before they occur or before they develop into major defects (Source: Dictionary of Military and Associated Terms, US DOD 2005).

Property Type: Indicates the asset as one of the following categories of real property:

land, building, structure.

Property Use: Since the elements defined by the FRPC do not match the space use codes employed in ESCIS, a mapping procedure will be created to align the definitions.

In the report, the Federal Real Property Council (FRPC) classifications will be printed for display. The information is available through the property registration field of Engineering Support Contractor Information System (ESCIS), and the current ESCIS designations will be correlated to the FRPC designations as follows:

ESCIS FRPC

Dormitory Dormitories/Barracks Food Service Other Institutional Uses Education School Recreation Other Institutional Uses Medical/Dental Other Institutional Uses Storage Warehouse Administration Office Structure * Storage, Service, Utility

Systems, or Other Land Institutional

* Each structure will be entered manually from the ESCIS database into one of four FRPC categories listed opposite the term “structure”.

Replacement Value: The cost of replacing the existing constructed asset at today’s building standards. It is the amount required to construct an asset of similar size and in the same location at today’s construction standards. The replacement value reported must be greater than zero (FRPC 2012).

Regional Office Project: Generally smaller projects where the funds will be transferred to the region for center execution.

Structure: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a structure serves to provide storage, service, utility systems and is not likely to have full utilities (heating, cooling, etc.). A structure typically is less than 400 square feet.

Sustainability: Formally known as the World Commission on Environment and Development, the Brundtland Commission's mission in the 1980s was to unite countries to pursue sustainable development. The Commission defined sustainability as the “development which meets the needs of current generations without compromising the ability of future generations to meet their own needs".

Sustainability also is defined as the creation or enhancement of environmental, economic, and social-cultural balance, as realized through business activities, individual actions, and community engagement. Sustainability addresses approaches, methods and practices that optimize the use of energy, water, and materials while reducing greenhouse gas emissions.”

Utilization: This performance measure assesses the degree to which each asset is utilized and is expressed as a percentage. It is calculated on a square footage basis, comparing the square footage used to the “design square footage” based on contract strength (Source: FRPC 2012).

Executive Summary

EXECUTIVE SUMMARY

The facility survey for the Bamberg was completed February 24, 2014 to February 28, 2014.

The information presented in Volume II, Supporting Data, represents the current status of the campus.

The information includes the following:

Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;

active warranties; and Federal Real Property Council (FRPC) Measures Matrix

Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:

Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix

1.0 Site Layout and Plans

2.0 Descriptions

2.0 DESCRIPTIONS

In this section, the following information on the Center and its buildings and structures is presented in tabular format:

Building and Structures – This table indicates the building type, asset number, name, use group, gross square footage (GSF), construction year, number of floors, number of sleeping room and number of beds, construction type (noted as numerical values instead of code-specified Roman numerals), status (active or closed), and overall condition. The possible International Building Code (IBC) construction classifications include the following:

Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.

Type III. This type of construction is where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.

Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces. Fire-retardant-treated wood framing complying with IBC section 2303.2 shall be permitted within exterior wall construction with a 2-hour rating or less.

Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.

The overall building/structure condition is rated in one of three categories: good, fair, or poor.

Space Utilization by Function - This table compares the DOL recommended net square footage per enrollee and for the total function (e.g., housing, education, food service, recreation, medical/dental, administration, storage/support) to the actual values.

Net Square Footage by Building - This table compares the DOL recommended net square footage for the buildings with the function (e.g., housing, education, food service, recreation, medical/dental, storage/support) to the actual values and presents a percentage difference in the two values. In some instances, a recommended value is not available for sub-elements of a function; therefore, the recommended value is shown as “0”.

Environmental Management Report – This table summarizes regulatory related solid and hazardous waste information in accordance with the Resource Conservation and Recovery Act (RCRA) and the presence or absence of hazardous material storage facilities in accordance with Emergency Planning and Community Right-to-Know Act of

1986 (EPCRA). An inventory of petroleum storage tanks is noted as well as asbestos and polychlorinated biphenyls (PCBs) in accordance with the Clean Water Act (CWA) and Toxic Substance Control Act (TSCA), respectively. In addition, this report statuses air quality as required under the Clean Air Act (CAA).Any radon testing of buildings also is documented.

Site Descriptions – Tabular information is documented for the site. Among the data presented are the topography; total number of buildings and structures; roads, parking and sidewalks; fencing; site utilities; storage tanks; accessibility; historic preservation;

natural hazards; and sustainability. The overall condition of the site is rated in one of three categories: good, fair, or poor.

Building Descriptions – Tabular information, as well as photographs and floor plan drawings, are provided for each building or structure, as appropriate, in the following categories: real estate; accessibility; building envelope; interior finishes; vertical circulation; heating, ventilation and air conditioning (HVAC); plumbing; fire protection;

electrical services; fire alarms; carbon monoxide detection; communication; and building metering. The overall condition of the building and its five key subsystems (structure, exterior, interior, mechanical, and electrical) are rated in one of three categories: good, fair, or poor. If applicable, recommendations for renovation or demolition are provided.

BUILDINGS AND STRUCTURES

00408 BAMBERG 06/12/2014

1Page: of Date:

0001 - CDSS/CPP

0002 - ACADEMIC

0003 - ADMINISTRATION/RECORDS

PROPERTY

0004 - ADMINISTRATION/FINANCE

0007 - DORMITORY-MEMORIAL

0008 - CAFETERIA

0009 - WELLNESS CENTER

0011 - STORAGE

0012A - FACILITIES

0015 - IT

0017 - DORMITORY-JENKINS

0018 - HUMAN RESOURCES

0018A - WELCOME CENTER

0020 - VOCATIONAL TRAINING

0021 - VOCATIONAL STORAGE

0029 - FOOD STORAGE ANNEX

0030 - DORMITORY - JERRY BROWN

0035 - FACILITY MAINT VOC/PLUMBING

VOC

0036 - MATERIAL HANDLER

0040 - SAFETY/SECURITY

0041 - PROPERTY LOGISTICS

0042 - RECREATION CENTER

0007A - MAINTENANCE/RESIDENTIAL

STORAGE

0009A - STORAGE

0021A - STORAGE

0022 - GATEHOUSE

0028 - STORAGE

0035A - CANOPY/SHELTER

0035B- FACILITIES MAINT AND

CONSTRUCTION STORAGE

0035C - WELDING SHELTER

0042A - PAVILION

Name GSF

10,865 5,180 3,010

1,965 10,675 6,200 4,235 1,130 2,035 1,130

25,101

1,200 15,755 2,990

4,498 7,992

4,500

4,520 17,367

Active Active Active

Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active

Active Active Active Active Active

Active Active Active Active Active Active

Active Active

StatusType

Building Building Building

Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building

Building Building Building Building Structure

Structure Structure Structure Structure Structure Structure

Structure Structure

Use Group Built Flrs Const

Business Business Business

Business Residential Assembly Business Storage Storage Business Residential Business Business Business/Fac Storage Storage Residential Business

Business Business Storage Assembly Storage

Storage Storage Traffic Securi Storage Storage Storage

Factory/Ind.

Assembly

Good Good Good

Good Fair Poor Good Fair Fair Fair

Good Good Good Good Good Good Fair

Good

Good Good Good Good Good

Fair Good Good Good Good Good

Good Good

ConditionAsset Number

0040800002 0040800003 0040800004

0040800005 0040800007 0040800008 0040800009 0040800011 0040800041 0040800014 0040800030 0040800016 0040800042 0040800018 0040800032 0040800022 0040800023 0040800029

0040808089 0040808094 0040808095 0040808096 0040800038

0040808097 0040808093 0040800033 0040800019 0040800034 0040800035

0040808099 0040808098

22 132,516

9 2,420

31 134,936

Buildings

Structures

Total

GSF

GSF

GSF

Summary

06/12/2014

Space Utilization By Function 00408 Bamberg Page: 1 of Date:

HOUSING

EDUCATION

FOOD SERVICE

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 173 Non Residents 0

173Total Students

(173)

(220)

(173)

DIFFERENCE

18,684

16,120

3,114

28,693

30,264

5,818

Lounge Other Shower/Toilet Sleeping excl. SPD(71 rooms; 219 beds) Storage

Academic (220) Non-Academic

0 -- Carpentry + 20 -- Cement Masonry + 30 -- Computer Service Tech.

30 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 0 -- Food Service + 24 -- Plumbing + 30 -- Warehousing Material Handler + 24 -- Welding +

Vocational Theory (152)

Dining (2 Servings) Food Preparation Food Storage

6,044

2,864 17,103

1,918

2,642 7,951

2,646 1,446

2,152 1,958 1,364 4,207 2,032

2,258

3,430 1,170 1,218

1,730 1,384 2,076

12,456 1,038

2,200 2,200

1,500

1,800 1,800

1,200 1,200 1,800

1,520

1,384 1,038

4,314 -620

4,647

5,751

1,146

-972

1,958

3,007

2,046

Vocations

10,009

14,144

2,704

06/12/2014

Space Utilization By Function 00408 Bamberg Page: 2 of Date:

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

VACANT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

TOTAL 316.43 54,743 96,317

(173)

(173)

(173)

(173)

(0)

DIFFERENCE

132,516

0.73

TOTAL GSF

NET TO GROSS RATIO

8,650

1,255

3,460

12,688

2,981

6,769

7,179

1,925

Arts & Crafts Gymnasium Hair Salon Learning Resource Center/Library Multipurpose Room Music Hall Recreation Office Recreation Storage Recreation/Snack Bar Weight Room

Medical Only

Administration

Operations & Maintenance Warehouse

Vacant

7.25

7,640

1,427

2,981

6,769

6,402

1,925

1,255

1,384 2,076

7,640

1,427

1,726

3,309

-607 4,326

1,925

RESIDENT

NON-RESIDENT

(173)

(0) 15

50 8,650

4,038

1,726

3,309

3,719

1,925

41,574

Net Square Footage By Building Date: 06/12/2014 Page: 1

Center: BAMBERG (00408) of 4

HOUSING

Sleeping excl. SPD

Lounge

Storage

Shower/Toilet

Other

Function Suggested

NSF

2,190 4,317

10,596

4,601

1,552

1,960

0030 - DORMITORY - JERRY BROWN

0007 - DORMITORY-MEMORIAL

0017 - DORMITORY-JENKINS

0017 - DORMITORY-JENKINS

0030 - DORMITORY - JERRY BROWN

0007 - DORMITORY-MEMORIAL

0007 - DORMITORY-MEMORIAL

0017 - DORMITORY-JENKINS

0017 - DORMITORY-JENKINS

0007 - DORMITORY-MEMORIAL

0030 - DORMITORY - JERRY BROWN

0017 - DORMITORY-JENKINS

0007 - DORMITORY-MEMORIAL

0030 - DORMITORY - JERRY BROWN

Bldg Name Actual NSF Difference

17,103

6,044

1,918

2,864

Sub Total: 28,693

12,456

1,730

1,038

2,076

1,384

18,684

4,647

4,314

-620

( 173

10,009

6 rooms; 20 beds 29 rooms; 63 beds 36 rooms; 136 beds

Page: 2

Center: BAMBERG (00408) of 4

EDUCATION

Academic

Vocational Theory (152)

Carpentry

Cement Masonry

Plumbing

Culinary Arts

Welding

Warehousing Material Handler

Computer Service Tech.

Facilities Maint. and Const.

Food Service

Non-Academic

Function Suggested

NSF

1,739

2,646

1,364

2,032

3,967

1,446

1,372

1,718

1,369 2,133

2,275

0002 - ACADEMIC

0002 - ACADEMIC

0002 - ACADEMIC

0002 - ACADEMIC

0002 - ACADEMIC

0035 - FACILITY MAINT VOC/PLUMBING VOC

0036 - MATERIAL HANDLER

0021 - VOCATIONAL STORAGE

0020 - VOCATIONAL TRAINING

0035 - FACILITY MAINT VOC/PLUMBING VOC

0020 - VOCATIONAL TRAINING

0020 - VOCATIONAL TRAINING

0036 - MATERIAL HANDLER

0021 - VOCATIONAL STORAGE

0020 - VOCATIONAL TRAINING

0035 - FACILITY MAINT VOC/PLUMBING VOC

0021 - VOCATIONAL STORAGE

0021 - VOCATIONAL STORAGE

0020 - VOCATIONAL TRAINING

0001 - CDSS/CPP

0020 - VOCATIONAL TRAINING

0001 - CDSS/CPP

0001 - CDSS/CPP

0001 - CDSS/CPP

0002 - ACADEMIC

0001 - CDSS/CPP

0007 - DORMITORY-MEMORIAL

Bldg Name Actual NSF Difference

2,642

2,258

2,646

1,364

2,032

4,207

1,446

2,152

1,958

7,951

Sub Total: 30,264

2,200

1,520

1,500

1,200

1,800

1,800

1,200

1,800

2,200

16,120

1,146

-972

3,007

1,958

5,751

( 220

14,144

Page: 3

Center: BAMBERG (00408) of 4

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

Dining (2 Servings)

Food Preparation

Food Storage

Multipurpose Room

Arts & Crafts

Gymnasium

Weight Room

Recreation/Snack Bar

Music Hall

Hair Salon

Learning Resource Center/Libr

Recreation Storage

Recreation Office

Medical Only

Function Suggested

NSF

3,430

1,170

7,640

1,427

2,981

0008 - CAFETERIA

0008 - CAFETERIA

0029 - FOOD STORAGE ANNEX

0008 - CAFETERIA

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0042 - RECREATION CENTER

0009 - WELLNESS CENTER

Bldg Name Actual NSF Difference

3,430

1,170

1,218

7,640

1,427

2,981

Sub Total:

Sub Total:

Sub Total:

5,818

12,688

2,981

1,384

1,038

1,255

3,114

8,650

1,255

2,046

1,726

2,704

4,038

1,726

Page: 4

Center: BAMBERG (00408) of 4

ADMINISTRATION

STORAGE/SUPPORT

VACANT

Administration

Warehouse

Operations & Maintenance

Vacant

Function Suggested

NSF

1,832 1,000 1,222

3,677

1,845

1,529

0018 - HUMAN RESOURCES

0015 - IT

0040 - SAFETY/SECURITY

0001 - CDSS/CPP

0003 - ADMINISTRATION/RECORDS PROPERTY

0018A - WELCOME CENTER

0004 - ADMINISTRATION/FINANCE

0041 - PROPERTY LOGISTICS

0011 - STORAGE

0012A - FACILITIES

0007 - DORMITORY-MEMORIAL

0002 - ACADEMIC

0020 - VOCATIONAL TRAINING

Bldg Name Actual NSF Difference

6,769

6,402

1,925

Sub Total:

Sub Total:

Sub Total:

6,769

7,179

1,925

3,460

2,076

1,384

3,460

3,460

3,309

4,326

-607

1,925

3,309

3,719

1,925

Environmental Management Report Center: BAMBERG (00408)

Page: 1 Date: 06/12/2014 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

Municipal Waste Service

HAZARDOUS MATERIALS STORAGE (EPCRA)

Yes BAM Building, Autobody Workshop, Maintenance

Organic solvents, cleaning supplies Yes

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Bamberg County Solid Waste Transfer No N/A

N/A N/A N/A

No Yes

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No N/A

04/24/1990 Friable/Non-Friable Lonnie Frazer 04/04/2000 No No N/A No No

ID Fuel Type Capacity Location Overfill

Prevention Secondary ContainmentTank Status

Tank Status Prevention/Detection

Asbestos-Containing Materials Inventory

Date: 06/12/2014Center : Bamberg (00408) Page: 1 of 1

Heating Heating Heating

Exterior Walls

Exterior Walls

Floor Finishes Floor Finishes

Floor Finishes

Floor Finishes

Bldg System

Bldg System

Bldg System

Bldg System

Bldg System

Bldg System

Pipe fitting insulation Pipe insulation, air-cell Debris in crawlspace

Asbestos cement board siding

Asbestos cement board siding

12x12 floor tile, gray/white Mastic beneath 12x12 tile

9x9 floor tile

Linoleum

Category Description

Category Description

Category Description

Category Description

Category Description

Category Description

Ea.

Lin. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Location

Location

Location

Location

Location

Location

Unit

Unit

Unit

Unit

Unit

Unit

Quantity

Quantity

Quantity

Quantity

Quantity

Quantity

Throughout Beneath stage Crawlspace

South entrance

South entrance

Dormitory rooms Dormitory rooms

Corridors, wait area

Culinary arts

Building :

Building :

Building :

Building :

Building :

Building :

0001 - CDSS/CPP

0002 - ACADEMIC

0004 - ADMINISTRATION/FINANCE

0007 - DORMITORY-MEMORIAL

0009 - WELLNESS CENTER

0020 - VOCATIONAL TRAINING

Radon

Page: 1 of 2

0001 - CDSS/CPP

0002 - ACADEMIC

0003 - ADMINISTRATION/RECORDS PROPERTY

0004 - ADMINISTRATION/FINANCE

0007 - DORMITORY-MEMORIAL

0008 - CAFETERIA

0009 - WELLNESS CENTER

0011 - STORAGE

0012A - FACILITIES

0015 - IT

0017 - DORMITORY-JENKINS

0018 - HUMAN RESOURCES

0018A - WELCOME CENTER

0020 - VOCATIONAL TRAINING

0021 - VOCATIONAL STORAGE

0029 - FOOD STORAGE ANNEX

0030 - DORMITORY - JERRY BROWN

0035 - FACILITY MAINT VOC/PLUMBING VOC

0036 - MATERIAL HANDLER

0040 - SAFETY/SECURITY

0041 - PROPERTY LOGISTICS

0042 - RECREATION CENTER

Bldg Name

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

05/16/1990

Test Date

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

No

Yes

No

Yes

N/A

Yes

Yes

No

No

No

No

No

Radon Testing

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

Radon

Page: 2 of 2

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

Site Description

BAMBERG

Bamberg JCC aerial view

Page: 1 Date: 06/12/2014 of 4

Paving Type for Roads & Parking Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is fully enclosed by fencing. The site has chain link on three sides and an iron fencing to the west, toward South Carlisle Street.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterBamberg Board of Public WorksPublic Water Authority

None 0None

Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time (Minutes)

Yes 0 5None Municipal

Adequate water pressure is provided

Comments:

Sewage Treatment Flow

Sewer system is gravity based.

Center

Publicly Owned Treatment Works

Center

Maintenance ResponsibilityOwnership

Number of Deficiencies = 1

Number of Deficiencies = 3

Number of Deficiencies = 1SITE FEATURES

UTILITIES

3. Sanitary Sewer System/ Sewage Treatment Plant

2. Fire Protection System

Buildings Structures22 9Flat

Surrounding

Outdoor Recreation

Residential

None

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Utility Center Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility Center Yes Good

System Capacity Adequate System Condition

Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good

Number of Deficiencies = 1

Fencing

Other Features

Page: 2 Date: 06/12/2014 of 4

Comments: Natural gas is supplied by Bamberg Board Of Public Works.

Bamberg Board Of Public Works

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Board of Public Works

The primary service is brought to the center from overhead lines along South Carlisle Street. These overhead lines provide service to Cafeteria Building 8, Infirmary Building 9 and Food Storage Annex Building 29 which are located on the west side of South Carlisle Street. The overhead lines are extended across the street to the east and provide services to other buildings on the main campus. There are four outdoor metering locations. One meter is located at the back of Building 8 and serves also Buildings 8, 9 and 29. Two other meters, installed on power poles, are located at the northeast and southwest of Vocational Training Building 20. These meters serve the campus northern and southern groups of buildings respectively. The northern group includes Buildings 1, 2, 3, 4, 11, 12A, 15, 18, 20, and 21. The southern group includes Buildings 7, 20 (main service), 30, 35, 36, 40 and 41. A fourth meter is installed on a pad-mounted transformer located outside Building 17. This meter serves Buildings 17 and 42 which are also on the southern end of the campus. Secondary services to most buildings are overhead. Buildings 17, 30, 35 and 42 have underground services. Building 42 has lightning protection installed on the roof.

Pole and Pad Utility

Utility Utility

No

4.16/2.4 kV, 3-Phase

120/240 and 120/208 Volts, 3-Phase and 1-PhaseOverhead & Underground

OverheadPrimary Service

Secondary Service

Distribution Characteristics

5. Fuel Distribution System

Number of Deficiencies = 7

4. Storm Water System

Drain Type On-Site Storm Water Management

Surface Run-off N/A

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes GoodCenter

Comments: Storm water system is based on both underground and surface runoff.

Gas Company Metering

Master

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility Center Yes Good

7. Electrical (Service)

Transformer Maint Resp

Utility

System Capacity Adequate System Condition

Yes Fair

Generator

None

ATS MTS

No No

6. Central Plant: None

Metering Individual

Page: 3 Date: 06/12/2014 of 4

Comments:

Telephone Company

On-site Line Owner

AT&T provides telephone service to the center with one T1 line, which terminate in the communications/server room in Administration/Finance Building 4. The standard analog phone system is converted to digital voice over internet protocol (VoIP) by way of Cisco IP phones with RJ-45 Ethernet connectors and internet connection.

Optical fiber cabling is used for inter-building connections. The server room also houses all data/communication network equipment. From this location Job Corps Data Center (JCDC) takes over the responsibility of providing and maintaining the VoIP telephone, LAN and WAN networks. The building fire alarm system center wide is stand alone. The security system includes interior CCTV cameras in all dormitories and the gymnasium, exterior cameras site wide, color monitors and door alarms. Interior cameras in dormitory buildings are monitored from the respective RA office. Gymnasium cameras and exterior cameras are monitored from the safety/security office in Building 18. Cable TV is provided in dormitory, gymnasium and cafeteria buildings.

AT&T

Maint. Responsibility

Center Center

Closed Circuit Television (CCTV) cameras, Color Monitors.

N/AN/AN/A NoneN/A

There are no underground or aboveground fuel tanks

NoN/A

STORAGE TANKS

Comments:

TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID

Reg.

9. Electrical (Communication/Alarm/Security)

N/A

Purpose

Yes

Stand-Alone

VOIP

System Capacity Adequate System Condition

GoodYes

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Pole, Building None

Photocell Photocell Photocell Photocell, Time Clock None

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility, Center Utility, Center Yes Good

Comments: Site lighting is provided by pole-mounted and building-mounted HID lights, which are controlled by photocells and in some locations by time clocks. The center owns and maintains the site lighting except lights that are mounted on power poles which are owned and maintained by the utility company. Lights at the fountain do not have control and operated 24/7. Flag pole lighting is controlled by the time clock located in Building 18.

Number of Deficiencies = 6

Number of Deficiencies = 12

Fire Alarm Security

Page: 4 Date: 06/12/2014 of 4

ACCESSIBILITY

Yes

NoNoNoNo

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Earthquake Risk

Medium Medium LowHigh MediumIBC Low

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Number of Deficiencies = 3

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X Good Fair Poor

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Active Energy Use Reduction Program

Active Water Use Reduction Program

Approximate or Measured Waste Recycled

Use of School Dude or CMMS for Preventative Maintenance

Green Purchasing Policy Practiced

Site Stormwater Absorption Measures in Place

Center has Onsite Renewable Energy (PV or Wind)

Center has a Chartered Green Committee & Roster

Center Uses Green Cleaning Practices

SUSTAINABILITY

Comments: Green Committee is being formed with first meeting on 03/13/14. Center is working on plan following sustainability guidelines and does purchase select Green Products)

NO

NO

NO

NO

NO

Yes

Yes

Yes

0 %

Building Descriptions and Structures

BUILDING 1 - CDSS/CPP

Building Descriptions

Page: 1 of 104

Building: 0001 - CDSS/CPP

BUILDING ENVELOPE

Foundation RoofBuilding

CMU Loadbearing Masonry Wood

Brick Masonry Stucco

Wall Roof None Rigid

Metal Unit - Metal Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Business 10,865 6,639 1 Owned 1935 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2. Number of Deficiencies = 2

Insulation4.

Exterior Doors5. Number of Deficiencies = 1

Material Drainage Year Life

Remaining Type Area Served

Metal Gutters and Downspouts 1999 25 Hip Entire Building

3. Roof

Entire Building

Area Served

Page: 2 of 104

Building: 0001 - CDSS/CPP

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Ceramic Tile Drywall

Wood Unit - Metal Frame Metal Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Stairs Ramp

Comments: There are concrete stairs and a concrete ramp leading to the entrances.

Fixed - Steel Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;

Acoustical Tile Exposed Structure

Exhaust Ventilation

Number of Deficiencies = 1

Windows6.

Floors1. Number of Deficiencies = 1

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating is provided by seven split heat pump systems. Each system serves designated areas within the building. All air handler units are manufactured by Carrier. The typical model numbers for AH-1-1, AH-1-3, AH-1-5, AH-1-6 and AH-1-7 ranges from FXDNF031 to FXDNF061, with supplemental electric heat ranging in capacities of 8 kW or 10 kW and 900 CFM to 1930 CFM. Air handler units AH-1-2 and AH-1-4 are located on the mezzanine level. Both are models 40RUQA07A0A5, with a supplemental heat of 15 kW each and a capacity of 2455 CFM. The seven heat pumps are outside on grade level.

Each heat pump is dedicated to one of the air handler units. All of the heat pumps are manufactured by Carrier. The typical model numbers for HP-1-1, HP-1-3, HP-1-5, HP-1-6 and HP-1-7 ranges from 25HBC330 to 25HNC360, with a capacity ranging from 2.5 tons to 5 tons. HP-1-2 and HP-1-4 both are models 38AUQA07A2A6 and 7.5 tons.

Comments:

HVAC

Heat1. Asbestos: Yes

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Ventilation2.

Ceilings

Page: 3 of 104

Building: 0001 - CDSS/CPP

Two electric water heaters are provided. The water heater located in the women's restroom is State model CV402SRT4, 40-gallon capacity with 4500W input. The other electric water heater is located in the basement under the stage and is State model CV402SRT1 with a 40-gallon capacity and 4500W input. The water heater located in the storage with a 6-gallon capacity is no longer in operation and has been abandoned in-place.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling is provided by seven split heat pumps systems. Each system serves designated areas within the building. All air handler units are manufactured by Carrier.