Woodstock Facility Survey Vol 2 April2018.pdf
PDF 15 MB Posted
- Attached to
- Woodstock Job Corps Center
- Solicitation number
- 1630J2-18-R-00007
About this file
Facility Survey Vol 2
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_0002__1630J2-18-R-00007.pdf | ||
| Woodstock Facility Survey Vol 2 April2018.pdf | ||
| Final RFC.pdf | ||
| Woodstock Facility Survey Vol 1 April2018.pdf | ||
| Woodstock Vehicle Log.xls | XLS spreadsheet | |
| Amendment 0001 1630J2-18-R-00007.pdf | ||
| Woodstock Master Property List 20180323.pdf | ||
| Copy of v2 J-1 Update for Combo FFP Template.xlsx | XLSX spreadsheet | |
| Copy_of_v2_J-1_Update_for_Combo_FFP_Template.xlsx | XLSX spreadsheet | |
| Woodstock Facility Survey Vol 1 April2018.pdf | ||
| Final RFC.pdf | ||
| Amendment 0001 1630J2-18-R-00001.pdf | ||
| Woodstock Master Property List 20180323.pdf | ||
| Woodstock Vehicle Log.xls | XLS spreadsheet | |
| J_pages_1630J2-18-R-00007.docx | DOCX document | |
| 1630J2-18-R-00007_Woodstock_RFP_(_Center_+CTS)_08.16.2018.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WOODSTOCK
Job Corps Center Woodstock, MD
Facility Planning Report Volume II
Supporting Data
Final April 2018
Department of Labor/ Office of Job Corps
WOODSTOCK
Job Corps Center Woodstock, MD
Facility Planning Report Volume II
Supporting Data
Final April 2018
Center Entrance Sign
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Existing Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The Program Year 2017 Facility Survey for 301 Woodstock Job Corps Center was completed the week of October 2, 2017. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal; and active warranties
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
WOODSTOCK
JOB CORPS CENTER
WOODSTOCK, MARYLAND
WOODSTOCK
JCC
10 MI5 0
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00301 WOODSTOCK 04/06/2018
1Page: of Date:
0001 - MAIN BUILDING
0002 - ADMIN/VOC/WAREHOUSE
0003 - BUSINESS SERVICES
0004 - LANDSCAPING/CARPENTRY
0006 - BRICK/EST
0007 - ELECTRONIC SERVICES
TECHNICIAN (EST)
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0008A - STUDENT STORE
0008B - CENTER FACILITY
MAINTENANCE & STORAGE
0009 - WELDING/CENTER MAINT
0010 - SECURITY GATE HOUSE
0011 - BRICK STORAGE
0012 - VACANT
0013 - HOME BUILDERS INSTITUTE
OFFICE
0014 - GYMNASIUM
0024 - STATIONARY ENGINEERING
STORAGE
0025 - FACIL. MAINT./CARP./WELD.
0029 - WASTE WATER TREATMENT
PLANT (NOT DOL ASSET)
0034 - CLASSROOM TRAILER 1
0035 - CLASSROOM TRAILER 2
0010A - SECURITY STORAGE (6Ft x 12Ft)
0017 - STORAGE
0018 - VICTORIAN GAZEBO (15Ft x 15Ft) 0019 - SALT & PEPPER GAZEBO 2 (14Ft x 14Ft) 0020 - WELL HOUSE #2 (10Ft x 12Ft) 0021 - WELL HOUSE #3 - INACTIVE (10Ft x 12Ft) 0022 - WELL HOUSE #4 - INACTIVE (10Ft x 12Ft) 0023 - WELL HOUSE #5 - INACTIVE (10Ft x 12Ft) 0032 - COOLING TOWER (30Ft x 30Ft) 0033 - PAVILION (12Ft x 26Ft) 0038 - WATER FOUNTAIN (20Ft x 20Ft) 0040 - GAZEBO (20Ft x 20Ft) 0041 - CANOPY #1 (8Ft x 16Ft) 0042 - CANOPY #2 (8Ft X 16Ft) 0043 - CANOPY #3 (8Ft X 16Ft) 0044 - CANOPY #4 (8Ft X 16Ft) 0045 - CANOPY #5 (8Ft X 16Ft)
B1 - WELLS (#1)
B3 - WELLS (#3)
B4 - WELLS (#4)
B6 - WELLS (#6)
C - BASKETBALL COURT
D - INACTIVE WATER TOWER (22Ft x
Name GSF
214,570 26,120 17,680 5,865 5,863 1,675
10,210 2,700
13,230 1,155
9,200
2,940
3,548 1,774
2,826 1,962
5,700
Active Active Active Active Active Active
Active Active Active
Active Active Active Active Active
Active Active
Active Active
Active Active Active Active Active Active
Active Active
Active
Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building
Building Building Building
Building Building Building Building Building
Building Building
Building Building
Building Building Structure Structure Structure Structure
Structure Structure
Structure
Structure
Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Mixed Use Business, Sto Business Business Business Business
Business Business Storage
Factory/Ind.
Business Storage Mercantile Business
Assembly Storage
Storage Utility/Misc.
Business Business Storage Storage Assembly Assembly
Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Assembly Utility/Misc.
Assembly Storage Assembly Assembly Assembly Assembly Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Assembly Utility/Misc.
Good Good Good Fair
Good Fair
Fair Good Good
Fair Good Good Poor Good
Good Fair
Good Good
Good Good
Poor Poor
Poor Good
Good
Good
Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0030100002 0030100003 0030100004 0030100005 0030100007 0030100008
0030100009 0030100018 0030100028
0030100010 0030100011 0030100012 0030100013 0030108115
0030100015 0030100029
0030100030 0030108117
0030108118 0030108119 0030100020 0030100017 0030100022 0030100023
0030100024 0030100025
0030100026
0030100027
0030100037 0030100038 0030108111 0030108113 0030108122 0030108123 0030108124 0030108125 0030108126 0030108132 0030108133 0030108134 0030108135 0030108130 0030108121
BUILDINGS AND STRUCTURES
00301 WOODSTOCK 04/06/2018
2Page: of Date:
22Ft)
E - ELECTRICAL SUBSTATION
EM - EMERGENCY GENERATOR (5Ft x 12Ft)
F - PLAYING FIELD
FP - FLAG POLES
G - NEW WATER TOWER (20Ft x 20Ft) H - CONDENSING UNIT (5Ft x 20Ft) PT - PROPANE TANK (2Ft x 10Ft)
Name GSF
11,250
Active Active
Active Active Active Active Active
StatusType
Structure Structure
Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Factory/Ind.
Utility/Misc.
Assembly Utility/Misc.
Utility/Misc.
Utility/Misc.
Utility/Misc.
Good Good
Good Good Good Good Good
ConditionAsset Number
0030108128 0030108137
0030108131 0030108129 0030108120 0030108136 0030108138
20 319,903
30 27,879
50 347,782
Buildings
Structures
Total
GSF
GSF
GSF
Summary
04/06/2018
Space Utilization By Function 00301 Woodstock Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 366 Non Residents 62
428Total Students
(366)
(505)
(428)
DIFFERENCE
36,600
33,190
7,704
38,741
48,339
8,385
Lounge Shower/Toilet Sleeping excl. SPD(215 rooms; 464 beds) Storage
Academic (505) Non-Academic
6 -- ACT (Off-Ctr) 24 -- Brick Masonry + 24 -- Carpentry + 30 -- Cert. Nursing Asst.
60 -- Certified Medical Assistant 24 -- Electrical + 30 -- Electronic Service Tech (EST) 24 -- Facilities Maint. and Const. + 24 -- Landscaping + 30 -- Medical Office Specialist 60 -- Office Administration 60 -- Security Officer 20 -- Stationary Engineer + 24 -- Welding +
Vocational Theory (164)
Dining (2 Servings) Food Preparation Food Storage
3,781 2,760
29,750 2,450
6,425 14,882
3,272 3,085
1,437 1,620 2,165 1,747
2,536 3,147 2,179
2,533
3,540 1,695 3,150
3,660 4,392
26,352 2,196
5,050 5,050
1,800 1,800 1,200 1,800 1,200 1,950 1,800 1,200
2,700 1,800 1,500 1,800
1,640
3,424 2,568 1,712
-1,632 3,398
1,375 9,832
1,472 1,285
-314 -945 -330
-2,121
1,647
-873
1,438
Vocations
2,141
15,149
04/06/2018
Space Utilization By Function 00301 Woodstock Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SECURITY
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 275.25 117,808 158,832
(428)
(428)
(428)
(428)
(428)
(0)
DIFFERENCE
319,903
0.50
TOTAL GSF
NET TO GROSS RATIO
19,230
2,680
8,560
8,560
1,284
18,660
3,400
7,691
21,961
10,663
Arts & Crafts Gymnasium Miscellaneous Recreation Multipurpose Room T.V. Room Weight Room Women's Exercise Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
SECURITY
Vacant
6.26
7,670
3,220 1,770 1,930 2,440
3,400
7,691
14,902 7,059
10,663
2,680
8,560
3,424 5,136
1,284
-869
11,478 1,923
-292
RESIDENT
NON-RESIDENT
(366)
(62) 15
50 18,300
-570
-869
13,401
-292
10,663
41,024
Net Square Footage By Building Date: 04/06/2018 Page: 1
Center: WOODSTOCK (00301) of 5
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Function Suggested
NSF
29,750
3,781
2,450
2,760
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
Bldg Name Actual NSF Difference
29,750
3,781
2,450
2,760
Sub Total: 38,741
26,352
3,660
2,196
4,392
36,600
3,398
-1,632
( 366
2,141
215 rooms; 464 beds
Page: 2
Center: WOODSTOCK (00301) of 5
EDUCATION
Academic
Vocational Theory (164)
Carpentry
Electrical
Welding
Facilities Maint. and Const.
Landscaping
Non-Academic
Electronic Service Tech (EST)
Function Suggested
NSF
1,725
1,572 1,025
2,337
1,437
1,638
1,730
1,747
1,984
1,438
5,634
3,719
1,620
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0034 - CLASSROOM TRAILER 1
0001 - MAIN BUILDING
0035 - CLASSROOM TRAILER 2
0034 - CLASSROOM TRAILER 1
0009 - WELDING/CENTER MAINT
0004 - LANDSCAPING/CARPENTRY
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0006 - BRICK/EST
0004 - LANDSCAPING/CARPENTRY
0025 - FACIL. MAINT./CARP./WELD.
0006 - BRICK/EST
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0009 - WELDING/CENTER MAINT
0025 - FACIL. MAINT./CARP./WELD.
0008B - CENTER FACILITY MAINTENANCE & STORAGE
0025 - FACIL. MAINT./CARP./WELD.
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0004 - LANDSCAPING/CARPENTRY
0001 - MAIN BUILDING
0013 - HOME BUILDERS INSTITUTE OFFICE
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0009 - WELDING/CENTER MAINT
0003 - BUSINESS SERVICES
0034 - CLASSROOM TRAILER 1
0009 - WELDING/CENTER MAINT
0001 - MAIN BUILDING
0002 - ADMIN/VOC/WAREHOUSE
0007 - ELECTRONIC SERVICES TECHNICIAN (EST)
Bldg Name Actual NSF Difference
6,425
2,533
3,085
1,437
2,179
2,165
1,747
14,882
1,620
5,050
1,640
1,800
1,200
1,800
1,800
1,200
5,050
1,950
1,375
1,285
9,832
-330
( 505 )
Page: 3
Center: WOODSTOCK (00301) of 5
EDUCATION
FOOD SERVICE
Brick Masonry
Security Officer
Stationary Engineer
Medical Office Specialist
Office Administration
Cert. Nursing Asst.
Certified Medical Assistant
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
2,722
2,536
2,433
3,540
1,695
3,150
0006 - BRICK/EST
0011 - BRICK STORAGE
0003 - BUSINESS SERVICES
0008A - STUDENT STORE
0024 - STATIONARY ENGINEERING STORAGE
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0003 - BUSINESS SERVICES
0003 - BUSINESS SERVICES
0003 - BUSINESS SERVICES
0003 - BUSINESS SERVICES
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
Bldg Name Actual NSF Difference
3,272
2,536
3,147
3,540
1,695
3,150
Sub Total:
Sub Total:
48,339
8,385
1,800
1,800
1,500
2,700
1,200
1,800
3,424
2,568
1,712
33,190
7,704
1,472
1,647
-2,121
-314
-945
-873
1,438
( 428
15,149
Page: 4
Center: WOODSTOCK (00301) of 5
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
Multipurpose Room
Arts & Crafts
Gymnasium
Weight Room
Miscellaneous Recreation
T.V. Room
Women's Exercise Room
Medical/Dental
Administration
Warehouse
Operations & Maintenance
Function Suggested
NSF
2,385
7,670
1,930
1,770
2,440
3,400
2,215 5,476
7,059
2,000 4,272 7,775
0001 - MAIN BUILDING
0008A - STUDENT STORE
0001 - MAIN BUILDING
0014 - GYMNASIUM
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0002 - ADMIN/VOC/WAREHOUSE
0002 - ADMIN/VOC/WAREHOUSE
0029 - WASTE WATER TREATMENT PLANT (NOT DOL ASSE
0009 - WELDING/CENTER MAINT
0001 - MAIN BUILDING
0008B - CENTER FACILITY MAINTENANCE & STORAGE
0004 - LANDSCAPING/CARPENTRY
Bldg Name Actual NSF Difference
3,220
7,670
1,930
1,770
2,440
3,400
7,691
7,059
14,902
Sub Total:
Sub Total:
Sub Total:
Sub Total:
18,660
3,400
7,691
21,961
2,680
8,560
5,136
3,424
19,230
2,680
8,560
8,560
-869
1,923
11,478
-570
-869
13,401
Page: 5
Center: WOODSTOCK (00301) of 5
SECURITY
VACANT
SECURITY
Vacant
Function Suggested
NSF
1,964 1,755 5,550
0010 - SECURITY GATE HOUSE
0008A - STUDENT STORE
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0004 - LANDSCAPING/CARPENTRY
0001 - MAIN BUILDING
0012 - VACANT
Bldg Name Actual NSF Difference
10,663
Sub Total:
Sub Total:
10,663
1,284
1,284
-292
10,663
-292
10,663
Environmental Management Report Center: WOODSTOCK (00301)
Page: 1 Date: 04/06/2018 of 2
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building #4 (Paint Storage)
Oil-based paint (60 gals), propane gas (1000 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance4
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
Between Building 8 and 9
Between Building 8 and 9
Near Building 5
Near Building 14
10,000
10,000
4,000
2,000
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Waste Management, Inc.
Yes Oil-based paint (4 gals/month)
Conditionally Exempt Small Quantity Generator
MDD030337521
Commercial Hazardous Waste Disposal Service Atlantic Environmental Group
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
02/21/1991 Friable/Non-Friable David Bonsal 07/30/2002 Yes No N/A No No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
Petroleum - Diesel Fuel
Petroleum - Gasoline
Petroleum - Gasoline
Petroleum - Diesel Fuel
Near Building 9
Near Building 9
Near Building 9
In Building 29
No
No
No
No
No
No
N/A
Yes
Tank Status Active
Active
Active
Active
Active
Active
Active
Active
Tank Status Prevention/Detection
Environmental Management Report
Page: 2 Date: 04/06/2018 of 2
AIR POLLUTION CONTROL (CAA)
N/A None
Non-AttainmentRegional Air Quality :
Permitted Air Pollution Source :
Source Description :
Ozone
Asbestos-Containing Materials Inventory
Date: 04/06/2018Center : Woodstock (00301) Page: 1 of 2
Floor Finishes Wall Finishes Wall Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes
Floor Finishes Wall Finishes Floor Finishes
Floor Finishes Roof Repair/Replacement Floor Finishes Floor Finishes Floor Finishes
Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
9x9 floor tile, various Wall & ceiling plaster Decorative plaster 12x12 floor tile, brown/tan 12x12 floor tile, off-white 12x12 floor tile, beige 12x12 floor tile, off-white 12x12 floor tile, green 9x9 floor tile, tan 12x12 floor tile, white 12x12 floor tile, beige 12x12 floor tile, off-white 12x12 floor tile, black/gray
12x12 floor tile, white Wall plaster 9x9 floor tile, black
12x12 floor tile, tan Roof flashing 12x12 floor tile, white 12x12 floor tile, green 9x9 floor tile, gray
12x12 floor tile, white
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Bsmt., throughout Limited Areas Bsmt. conference rm.
3rd fl., SE wing 2nd fl., dorm rooms 1st fl., reading 1st fl., custodial 1st fl., infirmary 2nd fl., rec. area 1st fl. main hallway 2nd fl., NE hallway 2nd fl., RA office Bsmt., NW wing
Bsmt., trans. office Bsmt., throughout Sub-bsmt., vault rm.
Bsmt., culinary arts Roof perimeter Bsmt., bathroom Roof stairwell 3rd fl., walkway
Landscaping area
32500
Building :
Building :
Building :
Building :
0001 - MAIN BUILDING
0002 - ADMIN/VOC/WAREHOUSE
0003 - BUSINESS SERVICES
0004 - LANDSCAPING/CARPENTRY
Asbestos-Containing Materials Inventory
Page: 2 of 2
Floor Finishes Exterior Walls Floor Finishes
Floor Finishes Heating
Floor Finishes
Bldg System
Bldg System
Bldg System
12x12 floor tile, black/white Asbestos cement siding 12x12 floor tile, white
12x12 floor tile, pink Pipe insulation, air-cell
Linoleum, tan
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Location
Location
Location
Unit
Unit
Unit
Quantity
Quantity
Quantity
Electrical office Throughout Carpentry office
Maintenance office Tool room
Bathroom
Building :
Building :
Building :
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0009 - WELDING/CENTER MAINT
0010 - SECURITY GATE HOUSE
Radon
Page: 1 of 1
0001 - MAIN BUILDING
0002 - ADMIN/VOC/WAREHOUSE
0003 - BUSINESS SERVICES
0004 - LANDSCAPING/CARPENTRY
0006 - BRICK/EST
0007 - ELECTRONIC SERVICES TECHNICIAN (EST)
0008 - FACIL. MAINT./ELEC./STA. ENG'R
0008A - STUDENT STORE
0008B - CENTER FACILITY MAINTENANCE & STORA
0009 - WELDING/CENTER MAINT
0010 - SECURITY GATE HOUSE
0011 - BRICK STORAGE
0012 - VACANT
0013 - HOME BUILDERS INSTITUTE OFFICE
0014 - GYMNASIUM
0024 - STATIONARY ENGINEERING STORAGE
0025 - FACIL. MAINT./CARP./WELD.
0029 - WASTE WATER TREATMENT PLANT (NOT D
0034 - CLASSROOM TRAILER 1
0035 - CLASSROOM TRAILER 2
Bldg Name
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
10/26/1990
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
Yes
No
No
N/A
N/A
No
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial view of Woodstock JCC
Page: 1 Date: 04/06/2018 of 5
Comments:
Paving Type for Roads & Parking
Roadways at the perimeter of the campus are compacted gravel.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. The old Water Tower D is inactive.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
YesMasterN/AGround Water
Source Water Disinfection 150,000Aboveground
The storage tank and distribution system are adequate. A water study was conducted to evaluate methods for implementing better water quality with more reliability..
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 150,000 8Aboveground Tank Elevated Tank
The storage tank and distribution system are adequate. The 150,000-gallon tank is shared between the fire fighting and domestic water usage. The site has an adequate number of fire hydrants. The new storage tank was installed in 2000. The old storage tank is no longer in use.
Number of Deficiencies = 2
Number of Deficiencies = 8
Number of Deficiencies = 3
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures20 30Terraced
Surrounding
Outdoor Recreation
Forest, Rural
Basketball, Field Water Towers
Entrance Driveway
Outdoor HVAC Equipment
Playing Field
Wrought Iron with Brick Piers
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Lessor Center No Poor
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Center No Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 04/06/2018 of 5
Comments:
Sewage Treatment Flow
Plant type is activated sludge. The plant is operated and maintained by Maryland Environmental Service.
Lessor
On-site Sewage Treatment Plant
Lessor
50,000 GPD
Maintenance ResponsibilityOwnership
Comments: There are three low pressure steam boilers and two domestic hot water tanks located in the ground level boiler room of Building 9. Fuel type is No. 2 oil. Site water is treated with a water softener and filtered.
Number of Deficiencies = 23. Sanitary Sewer System/ Sewage Treatment Plant
6. Central Plant
System Capacity Adequate System Condition
Yes Good
4. Storm Water System
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Yes GoodCenter
Type Energy Source
Hot Water
Steam
Oil
Oil
Steam is provided to Buildings 1, 2, 3, 8 and 9. Domestic hot water is provided to Buildings 1, 2, 3, and 9.
Bldgs Served
Ownership Maintenance Responsibility Plant Capacity Adequate Plant Condition
Lessor Center Yes Good
5. Fuel Distribution System: None
Page: 3 Date: 04/06/2018 of 5
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Baltimore Gas and Electric
Utility power is brought underground to the state-owned Electrical Substation Structure E, located on the site just northeast of Main Building 1. Structure E is composed of a primary meter and primary switchgear having two fused switches, one for each of two 750 kVA transformers (120/208V and 480/277V wet-type), within this fenced enclosure. The majority of power being utilized on Center is routed underground from Structure E transformers to Building 1, and then from Building 1 to other buildings via underground utility tunnels. Another primary feeder from Structure E is provided for overhead distribution to pole-mounted transformers supplying power to smaller buildings (Buildings 4, 5, 6) throughout the site. The utility company has a small non-metered pad-mounted primary transformer, adjacent to Structure E, for supplying power to utility-owned and maintained pole-mounted security lighting on Center. The state-owned wastewater treatment plant, slightly remote from the main campus, has its own separate utility connection and building-mounted secondary metering. A 60 kW diesel Kohler generator and Kohler automatic transfer switch is provided at the sewage treatment plant. A 7 kW gasoline Kohler generator with Kohler automatic transfer switch, located at Building 9, provides emergency power to select stairwell and fire escape lighting at Main Building 1.
Pole and Pad Utility, Center
Utility, Center Utility, Center
No
13.2/7.6 kV, 3-Phase, 4 Wire
480/277V, 208/120V, 3-Phase and 120/208V, 1-PhaseOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 57. Electrical (Service)
Transformer Maint Resp
Utility,Center
System Capacity Adequate System Condition
Yes Good
Generator
Diesel and Gasoline
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Pole
Photocell Photocell Photocell Photocell Photocell
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Fair
Comments: A number of wall and pole-mounted light fixtures were on during day time and a large amount of wall-pack units did not function during the evening hours creating dark areas and security risks.
ATS MTS
Yes No
Number of Deficiencies = 4
Metering Master
Page: 4 Date: 04/06/2018 of 5
Comments:
Telephone Company
On-site Line Owner
Three T1 communication lines enter the server closet located on the basement level of Building 2. Buildings on Center are connected back to the server closet in a mesh configuration utilizing fiber, and VoIP is used for both data and telephone communications. An older analog phone system, still maintained by the Center, is in use for student pay phones and for emergency backup with access at a few locations. A localized intrusion detection security system which alarms at Security Gatehouse Building 10 is provided at the first-floor finance and administration area of Building 2. The fire alarm system in the Center was upgraded recently. How ever the pull stations with glass rod links were not provided with protection from being accidentally broken by students.
Buildings 1, 2, 3, 6 and 8 have cable TV connection.
Verizon
Maint. Responsibility
Center Center
Security Panel, Motion Detectors, External Building Siren
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Unknown
Lessor
Lessor
Lessor
Lessor
Lessor
Lessor
Center
Private
Lessor
Active
Active
Active
Active
Active
Active
Active
Active
Active
Underground, Regulated
Underground, Regulated
Underground, Regulated
Underground, Regulated
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Between Building 8 and 9
Between Building 8 and 9
Near Building 5
Near Building 14
Near Building 9
Near Building 9
Near Building 9
Near Building 3
In Building 29
No
No
No
No
No
No
Yes
No
No
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Diesel Fuel
Petroleum - Gasoline
Petroleum - Gasoline
Propane
Petroleum - Diesel Fuel
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
10000
10000
9. Electrical (Communication/Alarm/Security)
Heating
Heating
Heating
Heating
Generator
Equip/Veh Fueling
Equip/Veh Fueling
Cooking
Generator
Purpose
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 6
Fire Alarm Security
Page: 5 Date: 04/06/2018 of 5
ACCESSIBILITY
Yes
Curbs interfere with an accessible route.Comments:
Comments:
UnknownYesYes
On September 6, 2012, MHT concurred with the findings of the historic survey from August 2012. 4.35 acres of the campus are now eligible for listing on the NRHP as a historic district .
No
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk Low Low HighHigh MediumIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 6
Accessible Parking: Accessible Slope:
No
Curb Cuts:
No
Ramps:
YesNo
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
Yes
NO
NO
NO
Yes
Yes
Yes
5 %
Building Descriptions and Structures
BUILDING 1 - MAIN BUILDING
Building Descriptions
Page: 1 of 98
Building: 0001 - MAIN BUILDING
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete/Stone Bearing Masonry/Wood Fr. Wood/ Steel
Stone Masonry
Comments: The main wing stone wall is buckling at the first floor level inside the east courtyard. The wall has a significant bow curve to it and it must be monitored by Center maintenance staff for any significant structural cracks.
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Mixed Use 214,570 82,650 5 Leased 1867 Contributing
Comments: Two TV rooms on the second and third floor of the overpass to Building 3 do not have visual alarms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
No
No
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 3
Material
The asphalt roof shingles have a 30 year warranty.
Remaining life of roof is estimated based on visual inspection during October 2017 Facility Survey.
Half of the shingle roof on the main building wing was recently replaced with plastic slate-like shingles.
The roof was repaired after water leaks damaged the main (center) wing top floor.
These roofs are on the west and east wing 1929 additions. They are only visible on aerial photos.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles
Built-up Roofing
Synthetic slate shingles
Rolled Asphalt
Gutters and Downspouts
Gutters and Downspouts
Gutters and Downspouts
Gutters and Downspouts
Gable
Flat
Gable
Flat
Original Building
Bridge to Building
North Half of the Original Building
East and West 1929 Building
Additions
Number of Deficiencies = 2
Comments:
Comments:
Comments:
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 98
Building: 0001 - MAIN BUILDING
Wall Roof None None
INTERIOR FINISH
Carpet Ceramic Tile Concrete Quarry Tile Vinyl Tile Wood
Comments: There is quarry tile in the kitchen area.
Block Ceramic Tile Drywall Exposed Structure Plaster Wood Panel
Comments: A number of ceilings throughout the building have Factory Mutual approved foam panels.
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Elevator Metal Pan w/Concrete Stairs Metal Stairs Comments: There are four metal fire escape stairs on the exterior of the building, 12 sets of interior concrete access stairs and one metal stair to the roof hatch.
Metal Unit - Metal Frame
Casement - Aluminum Frame; Single Glazing; Double Hung - Aluminum Frame; Double Glazing;
Single Hung - Wood Frame; Single Glazing;
Acoustical Tile Gypsum Board Metal Plaster
Number of Deficiencies = 1
Number of Deficiencies = 7
Insulation4.
Exterior Doors5. Number of Deficiencies = 4
Windows6.
Floors1. Asbestos: Yes Number of Deficiencies = 7
Interior Walls2. Asbestos: Yes
3. Number of Deficiencies = 2
Interior Doors4. Number of Deficiencies = 4
Ceilings
Page: 3 of 98
Building: 0001 - MAIN BUILDING
Mechanical
Mechanical
Mechanical
Mechanical
Laundry
Kitchen
Dishwashing
Toilet/Shower
Ventilation Area ServedExhaust Ventilation
Number of Deficiencies = 10
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are a small number of fan coils, unit heaters and convectors located in bathrooms, storage areas, offices and the fourth floor of the building.
The heat pump water loop temperature is maintained by a steam-to-water heat exchanger. The steam is provided by three gas-fired boilers located in Building 9. The 2 main loop circulating pumps (one running, one standby) are manufactured by Taco, model TA1230BBN1A2L0 centrifugal pumps, each rated at 1218 GPM at 110 feet of head. They are powered by 50 HP motors equipped with variable frequency drives. The water source heat pumps are all manufactured by Trane and range from 250 CFM in dorms and offices to 3330 CFM for common areas, outdoor air units, and kitchen makeup air units. The larger heat pumps are also equipped with hot water coils in the supply ducts. By far, the most common heat pump manufactured by Trane is model WPCE00619B20L31.
Comments:
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Oil-Fired Steam Boiler
Oil-Fired Steam Boiler
Packaged Heat Pump (Water
Source)
Radiator
Fan Coil
Single Duct
Two-Pipe
Two-Pipe
Two-Pipe
Thermostatic Valves
Electric
Direct Digital Control (DDC)
Mechanical
Natural
Mechanical
None
None
None
Dining Hall
Rest Rooms
Ventilation2. Number of Deficiencies = 4
Page: 4 of 98
Building: 0001 - MAIN BUILDING
Hot water is provided from Building 9. The dishwasher has an electric booster heater.Comments:
Cast Iron, PVC Outdoor Cast Iron
Bathtub Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Portable Bottled Water Cooler Service Sink Shower Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Propane)
Comments:
Copper / Galvanized Copper / Galvanized None Central Water Softener No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Packaged Heat Pump (Water
Source)
Single Duct
None
Single Duct
Refrigerant
Refrigerant
Two-Pipe
Direct Digital Control (DDC)
Electric
Direct Digital Control (DDC)
Mechanical
Natural
Mechanical
Economizer
None
None
Dining Hall
Equipment Room
Entire Building
PLUMBING
Cooling is provided to this system by a 30 ton air cooled condensing unit, manufactured by York, model H2CA360A46C. The York indoor air handler has three refrigerant circuits.
These units serve elevator machine rooms.
The heat pump water loop temperature is maintained by a cooling tower located on the east side of the building. The 2 main loop circulating pumps (one running, one standby) are manufactured by Taco, model TA1230BBN1A2L0 centrifugal pumps, each rated at 1218 GPM at 110 feet of head. They are powered by 50 HP motors equipped with variable frequency drives. The water source heat pumps are all manufactured by Trane and range from 250 CFM in dorms and offices to 3330 CFM for common areas, outdoor air units, and kitchen makeup air units. The larger heat pumps are also equipped with hot water coils in the supply ducts. By far, the most common heat pump is manufactured by Trane, model WPCE00619B20L31.
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 1
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4. Number of Deficiencies = 1
3. Number of Deficiencies = 3Air Conditioning
Propane is used for cooking.
Page: 5 of 98
Building: 0001 - MAIN BUILDING
Wet Wet ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: There is an abandoned dry sprinkler system serving the 4th floor and the attic areas.
Comments: This building is provided with two 3-phase underground electrical services from adjacent Electrical Substation Structure E. Services enter to switchboard main disconnects located in the basement main electrical room. The 480/277V service disconnect is fused at 1200A and the 120/208V service disconnect is fused at 2000A. This building also provides power to Buildings 2, 3, 9 and 10, and to the disconnect switch and transformer at Building 12. The building has a smart meter.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Compact Fluorescent High Intensity Discharge (HID) T-8 Fluorescent Comments: Exterior lighting is controlled by photocell and time clock.
Main Switchboards 277/480V, 3-Phase, 4 Wire Panelboard, Loadcenter Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Number of Deficiencies = 24FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 18
Exterior Lighting1. Number of Deficiencies = 2
Location UL300 Compliance Status Kitchen Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
LIGHTING
Page: 6 of 98
Building: 0001 - MAIN BUILDING
Comments: Recorded footcandle levels include natural light contribution. Incandescent lamps are used in some storage and support areas. Some sleeping rooms use compact fluorescent fixtures.
Comments: A 7 kW Kohler gasoline generator (7.5R62) with Kohler automatic transfer switch, located in Building 9, provides power for emergency lighting in stairwells and on fire escape stairs.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 & T12 - Fluorescent
Inc. & T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 & T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Lounges
Lounges
Reception
Toilets
Toilets
Dining/Lunch Rooms
Food Preparation
Storage Rooms
Classrooms
Laundry Room
Housing Lounge
Shower
Sleeping Rooms
Study Room
Shaving, Make-Up, Grooming
Medical/Dental
Wards (Patient)
Recreation
Maintenance Shop
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup Emergency Exit
Interior Lighting2. Number of Deficiencies = 5
Emergency /Exit Lighting3. Number of Deficiencies = 5
Page: 7 of 98
Building: 0001 - MAIN BUILDING
FIRE ALARM
Comments: The fire alarm control panel is a EST Panel with booster panels located on each floor of each wing. The remote annunciator panel is located on the first floor across from the main entrance.
Comments: A bell system is provided. The building is connected to the Center LAN system.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Magnetic Door Holder Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None Local Cable Company
Telephone Security Public Address Television
Number of Deficiencies = 2
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The fourth floor has a large area damaged by major roof leaks. It is unfinished and separated from the dormitories by locked doors.
The wet pipe sprinkler and stand pipe systems have several deficiencies.
Several water source heat pump units have failed throughout the building.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Fair Electrical: Good
This building has been recommended for renovation in the Long Range Development Plan.
RENOVATION RECOMMENDATION
Type Location
CARBON MONOXIDE DETECTION
Detection Required Yes
Number of Deficiencies = 1
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments Included for renovation into an outdoor pavillion in the PY17 Long Range Plan.
BUILDING 2 - ADMIN/VOC/WAREHOUSE
Page: 8 of 98
Building: 0002 - ADMIN/VOC/WAREHOUSE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Concrete
Stone Masonry
Wall Roof None Rigid
Metal Unit - Metal Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business, Storage 26,120 16,254 4 Leased 1925 Contributing
Comments: A ramp provides access to the basement, but there is no access to the other floors.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
No
N/A
Yes
Yes
Yes
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2008 11 Flat Entire Building
3. Roof
Page: 9 of 98
Building: 0002 - ADMIN/VOC/WAREHOUSE
INTERIOR FINISH
Carpet Ceramic Tile Concrete Dirt Terrazzo Vinyl Tile Wood
Ceramic Tile Drywall Plaster Wood Paneling
Metal Overhead - Metal Frame Metal Unit - Metal Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Metal Pan w/Concrete Stairs Metal Stairs Comments: There is a metal fire escape on the building. There is a metal vertical ladder to the roof hatch.
Double Hung - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;
Acoustical Tile Metal Panel Plaster
Windows6. Number of Deficiencies = 1
Floors1. Asbestos: Yes Number of Deficiencies = 1
Interior Walls2. Asbestos: Yes
3.
Interior Doors4.
Page: 10 of 98
Building: 0002 - ADMIN/VOC/WAREHOUSE
Mechanical Restroom
Ventilation Area ServedExhaust Ventilation
Number of Deficiencies = 2
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating is provided to the warehouse in the basement by a split heat pump system. The outdoor condensing unit is manufactured by AAC, model HP29-090-3Y and the indoor air handler unit is manufactured by Lennox, model CBH17-95-3, with a heating capacity of 90 MBH.
Three split heat pump systems provide heating to the administrative office on the first floor. The outdoor condensing units are all manufactured by Goodman, model SSZ140--1BB. The indoor air handler units are also manufactured by Goodman, model ASPT, with electric supplemental heat ranging from 10 kW to 20 kW. The air handler units are located in the closet spaces of the ATM room, Finance/Administration Manager's office and the Finance Assistant's Office.
Heating is provided to the Center Director's office by a mini split ductless system manufactured by Daikin, model RXN18KEVJU5, with a heating capacity of 18 MBH. The mini split ductless system was built in 3/2014.
Steam is supplied from boilers located in Building 9.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Packaged Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Oil-Fired Steam Boiler
Single Duct
Single Duct
Fan Coil
Radiator
Refrigerant
Refrigerant
Refrigerant
Two-Pipe
Electric
Electric
Electric
Thermostatic Valves
Mechanical
Mechanical
Mechanical
Natural
None
None
None
None
Storage
Offices
Offices
Ventilation2. Number of Deficiencies = 2
Page: 11 of 98
Building: 0002 - ADMIN/VOC/WAREHOUSE
Domestic hot water is provided by an electric water heater, manufactured by GE Smart Water, model PE40M09AAH, with a capacity of 40 gallons and 4500 watts. The electric water heater was built in 9/2007 and located in the sub-basement.
Comments:
Cast Iron, PVC None Cast Iron
Hose Bibb Lavatory Portable Bottled Water Cooler Sink Urinal Water Closet (Flush Valve)
None
Copper Copper Electric Central Water Softener No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Single Duct
Fan Coil
Window Units
Refrigerant
Refrigerant
Refrigerant
None
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Natural
Mechanical
None
None
None
None
Storage
Offices
Offices
Classrooms and Offices
PLUMBING
Cooling is provided to the warehouse in the basement by a split heat pump system. The outdoor condensing unit is manufactured by AAC, model HP29-090-3Y and the indoor air handler unit is manufactured by Lennox, model CBH17-95-3, with a cooling capacity of 7.5 tons.
Three split heat pump systems provide heating and cooling to the administrative offices on the first floor. The outdoor condensing units are all manufactured by Goodman, model SSZ140-1BB. The cooling capacities range from 2.5 ton to 5 ton and utilizes refrigerant R-410A. The indoor air handler units are also manufactured by Goodman, model ASPT, with electric supplemental heat. The air handler units are located in the closet spaces of the ATM room, Finance/Administration Manager's office and the Finance Assistant's office.
Cooling is provided to the Center Director's office by a mini split ductless system manufactured by Daikin, model RXN18KEVJU5, with a cooling capacity of 1.5 ton. The mini split ductless system was built in 3/2014 and utilizes refrigerant R-410A.
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
3. Air Conditioning
Page: 12 of 98
Building: 0002 - ADMIN/VOC/WAREHOUSE
None Wet ABC Type Fire Extinguisher
Comments: The electrical service to the building is drawn from a switchboard located in the basement of the main building via the underground tunnel. A 600A, 480V feeder serves a 600A main distribution panel (GE, Spectra series) with a 600A main circuit breaker (MCB). This service provides power to HVAC equipment and to a 225 kVA transformer. The transformer provides 120/208V power to a single-section switchboard (Square D, QMB) fused at 600A. The electrical distribution system in the building also has three 225A panelboards with 225A MCB (one for each floor) and several 100A main-lug-only loadcenters. A 300A, 480V circuit breaker in the main distribution panel serves Gym Building 14. The building has a smart meter.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. Incandescent lamps are used in some storage and support areas.
Compact Fluorescent High Intensity Discharge (HID) Comments: Exterior lights are controlled by a building-mounted photocell. Switch controlled compact fluorescent is used by the front door.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Incandescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
LED
T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Reception
Toilets
Storage Rooms
Classrooms
Housing Lounge
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Switchboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
Number of Deficiencies = 4FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 9
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 2
Emergency /Exit Lighting3. Number of Deficiencies = 3
Page: 13 of 98
Building: 0002 - ADMIN/VOC/WAREHOUSE
FIRE ALARM
Comments: The fire alarm control panel is a Silent Knight 5700 located in the sub-basement. There is additionally a Cerberus Pyrotronics MXL IQ fire alarm panel and remote fire alarm annunciator panel located in the basement that was added with the addition of duct smoke detectors. Fire alarm audible devices are bells.
Comments: Two T1 communication lines enter Center's main data communication equipment located in the Center main server closet (MC) on the basement level. MC is provided with Cisco 1700, 1800 and two 3500 series integrated service routers and Cisco Catalyst 3500 and 6500 series switches. A smart UPS 1000 battery buffers the power surges and drops in the line voltage and maintains the power requirement of the system for several minutes. Buildings on Center are connected by fiber in a mesh configuration back to this server closet. The system uses VoIP for both data and telephone communications. A localized intrusion detection security system is provided at the first-floor finance and administration area. This system has a security panel and Safe House remote annunciator panel, motion detectors, magnetic door contacts and an external building siren, and also notifies Security Gatehouse Building 10.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector
Connected to Main System Security Panel None Local Cable Company
Telephone Security Public Address Television
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Some of the interior finishes are deteriorating. Toilet rooms are outdated and worn. Basement floor is in poor condition.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good
Type Location
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 3 - BUSINESS SERVICES
Page: 14 of 98
Building: 0003 - BUSINESS SERVICES
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry/Concrete
Concrete
Stone Masonry
Wall Roof None Rigid
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 17,680 11,481 4 Leased 1929 Contributing
Comments: The main entrance has a ramp.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
N/A
Yes
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 2
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material
Asbestos: Yes
Drainage Year Life
Remaining Type Area Served
Single Ply Gutters and Downspouts 2008 11 Flat Entire Building
3. Roof
Page: 15 of 98
Building: 0003 - BUSINESS SERVICES
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Paneling Plaster
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Metal Pan w/Concrete Stairs Metal Stairs Ramp Comments: There is a metal fire escape stair on the building. There is a vertical metal ladder to the roof hatch.
Double Hung - Wood Frame; Double Glazing; Double Hung - Wood Frame; Single Glazing;
Acoustical Tile Plaster
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 4
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Steam is supplied from boilers located in Building 9. A steam to water heat exchanger in the basement of Building 3 provides hot water to the building heating systems.
Comments:
HVAC
Heat1. Number of Deficiencies = 2
Oil-Fired Steam Boiler
Oil-Fired Steam Boiler
Oil-Fired Steam Boiler
Fan Coil
Hot Water Convector
Single Duct
Two-Pipe
Two-Pipe
Two-Pipe
Direct Digital Control (DDC)
Direct Digital Control (DDC)
D…