This document is a Facility Planning Report for the Cascades Job Corps Center located in Sedro-Woolley, Washington. The report provides details on the current status of the campus, including the existing site layout, building and structure conditions, space utilization, environmental elements, and identified deficiencies.
The key details are:
- The Cascades Job Corps Center has a planned on-board strength of 300 students, consisting of 180 residential male and 120 residential female students.
- The center includes 24 buildings and 20 structures, with the majority constructed between 1922-1965. The buildings are in generally good condition, with some deficiencies noted in areas such as the roofing, HVAC systems, and electrical systems.
- The campus has sufficient space for housing, education, food service, recreation, medical/dental, administration, and storage/support functions. However, some spaces do not fully meet recommended standards.
- The site includes utility systems such as water, sewer, electrical, and HVAC, which are generally in good condition with some maintenance needs identified.
- The report includes detailed surveys, assessments, and supporting documentation for the center's facilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| J.9 (Revised Facility Survey Volume 1).pdf | ||
| Questions and Answers for Cascades (10-25-2024).xlsx | XLSX spreadsheet | |
| Lease Agreement.pdf | ||
| Amendment 4.pdf | ||
| J-1 (Further Revised Price Detail Template 10-17-2024).xlsx | XLSX spreadsheet | |
| Amendment 3.pdf | ||
| Amendment 2.pdf | ||
| J-1 (Revised Price Detail Template).xlsx | XLSX spreadsheet | |
| Amendment 1.pdf | ||
| Solicitation for Cascades 09-27-2024.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CASCADES
Job Corps Center Sedro-Woolley, WA
Facility Planning Report (Public) Supporting Data
Volume II
Final February 2024
CASCADES JOB CORPS CENTER
PY2023 FACILITY SURVEY REPORT
VOLUME II – TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY
2.0 SITE LAYOUT AND PLANS
Location Map
Existing Site Plan
3.0 DESCRIPTIONS
Buildings and Structures
Space Utilization by function
Environmental Management Report
Radon Report
Site Description
Building Descriptions and Structures, Floor Plans
4.0 DEFICIENCIES
APPENDICES – CORRESPONDENCE AND REPORTS
APPENDIX A
APPENDIX B
Life Safety Deficiencies and List
APPENDIX C
O&M Deficiencies List i
Survey Brief
NSF by Building
Dorm Bed Capacity
Asbestos Report
Student Questionnaire
Page Intentionally Left Blank ii
1.0 EXECUTIVE SUMMARY
1.0 EXECUTIVE
SUMMARY
EXECUTIVE SUMMARY
The Program Year 2023 facility survey for Cascades Job Corps Center was completed the week of October 16, 2023. The information presented in Volume I, Supporting Data, represents the current status of the campus.
The information includes the following:
• Existing site layout
• Overall status of existing building and structures
• Space utilization by building and function compared to recommended standards
• Status of environmental elements of the Center’s operations
• Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation
• Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey
• Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal; and active warranties
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
• Appendix A. Survey Brief Questionnaire
• Appendix B. Life Safety Deficiencies and List
• Appendix C. O&M Deficiencies List
2.0 SITE LAYOUT
AND PLANS
Page Intentionally Left Blank
3.0 DESCRIPTIONS
3.0 DESCRIPTIONS
BUILDINGS AND STRUCTURES
01003 CASCADES 01/24/2024
Page: 1 of Date:
0010 - RECREATION/GYMNASIUM
0010A - SECURITY SHACK
0012 - MOUNT RAINIER DORMITORY
0013 - DINING HALL
0015 - ACADEMICS/EVERGREEN DORMITORY
0016 - CHALLENGER DORMITORY
0017 - WHITEWATER DORMITORY
0024 - REGISTRARS OFFICE
0025 -VOCATIONAL
0026 - MAINTENANCE STORAGE
0027E - WAREHOUSE/RECEIVING
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE
SPECIALIST
0028 - CENTER MAINTENANCE SHOP
0029 - MAINTENANCE EQUIPMENT STORAGE
0030 - CULTURAL CENTER
0031 - VOCATIONS BUILDING
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0033A - FORMER STORAGE (VACANT)
0033B - TEAP MEETING ROOM
0034 - SECURITY/SAFETY
0048 - LEARNING RESOURCE CENTER/LIBRARY
0050 - WAREHOUSE STORAGE A
0057 - ADMISSIONS AND PLACEMENT
0063 - TRACTOR SHED
0051 - WAREHOUSE STORAGE B (74FT X 25FT)
0053 - STORAGE (8FT X 15FT)
0054 - STORAGE (24FT X 64FT)
0056 - ELECTRICAL MOCK-UP (15FT X 25FT)
0057A - GAZEBO (15FT DIAMETER)
0057B - GAZEBO (15FT DIAMETER)
0057C - GAZEBO (15FT DIAMETER)
0057D - GAZEBO (15FT DIAMETER)
0057E - PAVILION (35FT DIAMETER)
0057F - PAVILION (35FT DIAMETER)
0058 - CARPORT (20FT X 30FT)
0059 - CEMENT MASONRY MOCK-UP (16FT X 30FT)
0061 - STORAGE (7FT X 8FT)
0062 - STORAGE (12FT X 20FT)
0064 - GREENHOUSE (25FT X 44FT)
0065 - TRANSFORMER BUILDING (8FT X 8FT)
0067 - ELECTRICAL MOCK-UP (20FT X 21FT)
0068 - CARPORT (10FT X 12FT)
0069 - GAS FILLING STATION
0070 - SHED (12FT X 20FT)
Name GSF
15,740
17,560 26,880 17,560 18,220 29,800 2,100 2,100 7,500
12,750 13,230
3,600 1,590
11,040 13,980 31,240 1,140
1,010 1,850 1,800 1,580 1,200 1,850
1,560
1,050 1,050
1,100
Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building
Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Assembly Business Residential Assembly Residential Residential Residential Business Business Storage Storage Business
Business Storage Assembly Business Business Business Business Business Business Business Business Storage Storage Storage Storage Business Assembly Assembly Assembly Assembly Assembly Assembly Storage Business Storage Storage Utility/Misc.
Utility/Misc.
Business Storage Utility/Misc.
Storage
Fair Good Good Good Good Good Good Good Good Fair
Good Good
Good Fair
Good Good Good Fair Fair
Good Good Fair
Good Fair Fair Fair
Good Good Good Good Good Good Good Good Poor Good Fair Fair Fair
Good Good Good Good Good
Condition
24 234,130
20 10,020
44 244,150
Buildings
Structures
Total
GSF
GSF
GSF
Summary
01/24/2024
Space Utilization By Function 01003 Cascades Page: 1 of 2
HOUSING
EDUCATION
FOOD SERVICE
RECREATION
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Date:
Residents Non Residents Total Students
(300)
(300)
(300)
(300)
DIFFERENCE
32,400
16,850
7,800
15,000
43,265
38,020
13,508
15,491
Lounge Other Shower/Toilet Sleeping excl. SPD(121 rooms; 316 beds) Storage
Academic (300) Non-Academic
30 -- ACT (Off-Ctr) 15 -- Advanced A + Administrator 50 -- Cert. Nursing Asst.
30 -- Computer Tech. Network + 150 -- IT Pathway 50 -- Medical Assistant 50 -- Medical Office Specialist
Dining (1 Serving) Food Preparation Food Storage
Arts & Crafts Gymnasium Pool Hall Recreation Office Recreation Room Student Store T.V. Room Weight Room
4,171 4,073 5,892
24,659 4,470
7,430 7,412
1,952 3,812
10,938 2,695 3,781
5,772 5,573 2,163
1,463 7,770 1,970 1,417
1,395
3,000 2,400 3,600
21,600 1,800
3,000 3,000
2,000
4,500 1,500 1,500
4,800 1,800 1,200
1,171 1,673 2,292 3,059 2,670
4,430 4,412
1,502 1,812
6,438 1,195 2,281
3,773
Vocations
RESIDENT
NON-RESIDENT
(300)
(0) 15
50 15,000
10,865
21,170
5,708
01/24/2024
Space Utilization By Function 01003 Cascades Page: 2 of Date:
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SECURITY
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 310.07 93,020 162,227
(300)
(300)
(300)
(300)
(0)
DIFFERENCE
234,130
0.69
TOTAL GSF
NET TO GROSS RATIO
2,070
12,000
6,000
4,682
11,655
29,292
5,594
Medical/Dental
Administration Outreach
Operations & Maintenance Warehouse
SECURITY
Vacant
6.9
4,682
5,898 5,757
2,570 26,722
5,594
2,070
6,000 6,000
2,400 3,600
2,612
-102 -243
23,122
-180
2,612
-345
23,292
-180
5,594
69,207
Net Square Footage By Building Page: 1 of 4
Date: 01/24/2024Center: CASCADES (01003)
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
3,296 7,366 5,948 8,049
1,439 1,438
3,150
1,400 1,468 2,363
1,534 1,139 1,070
0015 - ACADEMICS/EVERGREEN DORMITORY
0016 - CHALLENGER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0017 - WHITEWATER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0017 - WHITEWATER DORMITORY
0016 - CHALLENGER DORMITORY
0016 - CHALLENGER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0012 - MOUNT RAINIER DORMITORY
0017 - WHITEWATER DORMITORY
0017 - WHITEWATER DORMITORY
0016 - CHALLENGER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0017 - WHITEWATER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0016 - CHALLENGER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
Bldg Name Actual NSF Difference
24,659
4,171
4,470
5,892
4,073
Sub Total: 43,265
21,600
3,000
1,800
3,600
2,400
32,400
3,059
1,171
2,670
2,292
1,673
( 300
10,865
13 rooms; 43 beds 40 rooms; 104 beds 29 rooms; 84 beds 39 rooms; 85 beds
Net Square Footage By Building Date: 01/24/2024 Page: 2
Center: CASCADES (01003) of 4
EDUCATION
FOOD SERVICE
Academic
Medical Assistant
Non-Academic
Advanced A + Administrator
Medical Office Specialist
Cert. Nursing Asst.
IT Pathway
Food Preparation
Food Storage
Dining (1 Serving)
Function Suggested
NSF
2,398
2,238 1,607
2,042
1,160
4,202
1,952
2,427 1,354
3,812
10,938
5,573
2,163
5,772
0015 - ACADEMICS/EVERGREEN DORMITORY
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0031 - VOCATIONS BUILDING
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPECIALIST
0017 - WHITEWATER DORMITORY
0048 - LEARNING RESOURCE CENTER/LIBRARY
0015 - ACADEMICS/EVERGREEN DORMITORY
0048 - LEARNING RESOURCE CENTER/LIBRARY
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPECIALIST
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPECIALIST
0031 - VOCATIONS BUILDING
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPECIALIST
0031 - VOCATIONS BUILDING
0013 - DINING HALL
0013 - DINING HALL
0013 - DINING HALL
Bldg Name Actual NSF Difference
7,430
2,695
7,412
1,952
3,781
3,812
10,938
5,573
2,163
5,772
Sub Total:
Sub Total:
38,020
13,508
3,000
1,500
3,000
1,500
2,000
4,500
1,800
1,200
4,800
15,950
7,800
4,430
1,195
4,412
1,502
2,281
1,812
6,438
3,773
22,070
5,708
Page: 3
Center: CASCADES (01003) of 4
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Arts & Crafts
Gymnasium
Weight Room
Student Store
Pool Hall
Recreation Room
T.V. Room
Recreation Office
Medical/Dental
Administration
Outreach
Function Suggested
NSF
1,463
7,770
1,395
1,970
4,192
5,438
3,951
1,466
0010 - RECREATION/GYMNASIUM
0010 - RECREATION/GYMNASIUM
0010 - RECREATION/GYMNASIUM
0030 - CULTURAL CENTER
0030 - CULTURAL CENTER
0030 - CULTURAL CENTER
0030 - CULTURAL CENTER
0010 - RECREATION/GYMNASIUM
0030 - CULTURAL CENTER
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0033B - TEAP MEETING ROOM
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0027E - WAREHOUSE/RECEIVING
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0031 - VOCATIONS BUILDING
0057 - ADMISSIONS AND PLACEMENT
Bldg Name Actual NSF Difference
1,463
7,770
1,395
1,970
1,417
4,682
5,898
5,757
Sub Total:
Sub Total:
Sub Total:
15,491
4,682
11,655
2,070
6,000
6,000
15,000
2,070
12,000
2,612
-102
-243
2,612
-345
Page: 4
Center: CASCADES (01003) of 4
STORAGE/SUPPORT
SECURITY
VACANT
Warehouse
Operations & Maintenance
SECURITY
Vacant
Function Suggested
NSF
8,634
11,899 1,627 3,742
1,545 1,025
1,600 2,002
1,211
0026 - MAINTENANCE STORAGE
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPECIALIST
0027E - WAREHOUSE/RECEIVING
0050 - WAREHOUSE STORAGE A
0028 - CENTER MAINTENANCE SHOP
0029 - MAINTENANCE EQUIPMENT STORAGE
0063 - TRACTOR SHED
0034 - SECURITY/SAFETY
0010A - SECURITY SHACK
0025 -VOCATIONAL
0024 - REGISTRARS OFFICE
0033A - FORMER STORAGE (VACANT)
0013 - DINING HALL
Bldg Name Actual NSF Difference
26,722
2,570
5,594
Sub Total:
Sub Total:
Sub Total:
29,292
5,594
3,600
2,400
6,000
23,122
-180
5,594
23,292
-180
5,594
Center CASCADES (01003)
Dorm Bed Capacity Date: 01/24/2024
Page: 1 of 6
Female
Resident Student
Non Resident Student Total 150
Male
Contract Strength 300 as of 01/03/2020 On Board Strength 150 as of 10/10/2023
Resident Student
Non Resident Student Total
Female Male
Total
Total
0012 - MOUNT RAINIER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0012 - MOUNT RAINIER DORMITORY
1st Floor - East Wing
1st Floor - Main Hallway
1st Floor - West Wing
2nd Floor - East Wing
2nd Floor - Main Hallway
2nd Floor - West Wing
0015 - First Floor
2nd Floor - East Wing
2nd Floor - Main Hall
2nd Floor - West Wing
Physical Capacity
#Rooms #Beds
Male
Male
Male
Male
Male
Male
Male
Male
Gender
Gender
Gender
Current Occupancy of Rooms
#Students Vacant Beds (Need Repairs)
Vacant Beds (Due to OBS)
Vacant Beds (due to no Furn)
Reason For Less than Full Occupancy
Building Name Wing Name Gender
CASCADES (01003)Center
Date: 01/24/2024
Page: 2 of 6
Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds
SP
beds Total beds
150Resident Student Female
Non Resident Student 0 Total 150
Male
Contract Strength 300 as of 01/03/2020 On Board Strength 150 as of 10/10/2023
Resident Student
Non Resident Student Total
Female Male
Total
Total
0016 - CHALLENGER DORMITORY
0016 - CHALLENGER DORMITORY
1st Floor - East Wing
1st Floor - Main Hall
1st Floor - West Wing
2nd Floor - East Wing
2nd Floor - West Wing
2nd Floor Main Hall
Physical Capacity
#Rooms #Beds
Male
Male
Male
Male
Male
Male
Male
Current Occupancy of Rooms
#Students Vacant Beds (Need Repairs)
Vacant Beds (Due to OBS)
Vacant Beds (due to no Furn)
Reason For Less than Full Occupancy
40 104 69
35 0 0
Building Name Wing Name
Gender
Date: 01/24/2024
Page: 3 of 6
Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds
SP
beds Total beds
150Resident Student Female
Non Resident Student 0 Total 150
Male
Contract Strength 300 as of 01/03/2020 On Board Strength 150 as of 10/10/2023
Resident Student
Non Resident Student Total
Female Male
Total
Total
0017 - WHITEWATER DORMITORY
0017 - WHITEWATER DORMITORY
1st Floor - East Wing
1st Floor - West Wing
2nd Floor - East Wing
2nd Floor - Main Hall
2nd Floor - West Wing
3rd Floor - East Wing
3rd Floor - Main Hall
3rd Floor - West Wing
Physical Capacity
#Rooms #Beds
Female
Female
Gender
Gender
Gender
Female
Female
Female
Current Occupancy of Rooms
#Students Vacant Beds (Need Repairs)
Vacant Beds (Due to OBS)
Vacant Beds (due to no Furn)
Reason For Less than Full Occupancy
39 85 68
17 0 0
121Grand Total 316 199 74 8 0
Building Name Wing Name
Gender
Date: 01/24/2024
Page: 4 of 6
0012 - MOUNT RAINIER
DORMITORY
0012 - MOUNT RAINIER
DORMITORY
0012 - MOUNT RAINIER
DORMITORY
0012 - MOUNT RAINIER
DORMITORY
0012 - MOUNT RAINIER
DORMITORY
0012 - MOUNT RAINIER
DORMITORY
0012 - MOUNT RAINIER
DORMITORY
0015 -
ACADEMICS/EVERGREEN
DORMITORY
0015 -
ACADEMICS/EVERGREEN
DORMITORY
0015 -
ACADEMICS/EVERGREEN
DORMITORY
0012 - MOUNT
RAINIER DORMITORY
1st Floor - East Wing
1st Floor - Main Hallway
1st Floor - West Wing
2nd Floor - East Wing
2nd Floor - Main Hallway
2nd Floor - West Wing
0015 - First Floor
2nd Floor - East Wing
2nd Floor - Main Hall
3 1
Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds
SP
beds
Total beds
Summary
150Resident Student Female
Non Resident Student 0 Total 150
Male
Contract Strength 300 as of 01/03/2020 On Board Strength 150 as of 10/10/2023
Resident Student
Non Resident Student Total
Female Male
Total
Total
Gender
Male
Male
Male
Male
Male
Male
Male
Male
Gender N
Gender N
Date: 01/24/2024
Page: 5 of 6
0015 -
ACADEMICS/EVERGREEN
DORMITORY
0016 - CHALLENGER
DORMITORY
0016 - CHALLENGER
DORMITORY
0016 - CHALLENGER
DORMITORY
0016 - CHALLENGER
DORMITORY
0016 - CHALLENGER
DORMITORY
0016 - CHALLENGER
DORMITORY
0016 - CHALLENGER
DORMITORY
0017 - WHITEWATER
DORMITORY
2nd Floor - West Wing
0016 - CHALLENGER
DORMITORY
1st Floor - East Wing
1st Floor - Main Hall
1st Floor - West Wing
2nd Floor - East Wing
2nd Floor - West Wing
2nd Floor Main Hall
0017 - WHITEWATER
DORMITORY
Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds
SP
beds
Total beds
Summary
150Resident Student Female
Non Resident Student 0 Total 150
Male
Contract Strength 300 as of 01/03/2020 On Board Strength 150 as of 10/10/2023
Resident Student
Non Resident Student Total
Female Male
Total
Total
Gender
Gender N
Male
Male
Male
Male
Male
Male
Male
Date: 01/24/2024
Page: 6 of 6
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
0017 - WHITEWATER
DORMITORY
1st Floor - East Wing
1st Floor - West Wing
2nd Floor - East Wing
2nd Floor - Main Hall
2nd Floor - West Wing
3rd Floor - East Wing
3rd Floor - Main Hall
3rd Floor - West Wing
Building Name Wing Name bed beds beds beds beds beds beds beds beds beds beds beds beds beds beds
SP
beds
Total beds
19 74 117 100 6Total Beds:
Summary
150Resident Student Female
Non Resident Student 0 Total 150
Male
Contract Strength 300 as of 01/03/2020 On Board Strength 150 as of 10/10/2023
Resident Student
Non Resident Student Total
Female Male
Total
Total
Gender
Female
Female
Gender N
Gender N
Gender N
Female
Female
Female
Environmental Management Report
Center: CASCADES (01003) Page: 1 Date: 01/24/2024 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
HAZARDOUS MATERIALS STORAGE (EPCRA)
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
Number of Regulated USTs :
Number of Un-regulated USTs :
HazMat Spill Response Plan :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
Capacity LocationID Fuel Type
Asbestos Survey Date :
Asbestos Type :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Commercial Waste Service Rural Skagit Sanitation Yes Organic solvent (< 25 gals/month)
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service Various licensed contractors
Yes Oil-based paint (200 gals), organic solvent (100 gals), propane (250 gals)
Building 29 Yes No No
Prevention/Detection Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
Number of ASTs : 1
No N/A
01/17/1991 Friable/Non-Friable
Yes
Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
1 Petroleum - Gasoline 500 Near Building 26 Yes Yes
Tank Status Active
Tank Status
Asbestos-Containing Materials Inventory Page: 1 of 2 Date: 01/24/2024Center : Cascades (01003)
Bldg System Floor Finishes Floor Finishes Roof Repair/Replacement
Bldg System Floor Finishes Floor Finishes Floor Finishes Floor Finishes
Bldg System Roof Repair/Replacement
Bldg System Floor Finishes Floor Finishes
Bldg System Roof Repair/Replacement Wall Finishes Floor Finishes
Bldg System Floor Finishes
Category Description 12x12 floor tile, brown/tan 9x9 floor tile, brown/white Roof flashing
Category Description 9x9 floor tile, gray 9x9 floor tile, tan/black 12x12 floor tile, brown/white 9x9 floor tile, tan
Category Description Roofing felt
Category Description 12x12 flr. tile, tan (covered) 12x12 floor tile, tan
Category Description Roof flashing Asbestos cement board 12x12 floor tile, tan
Category Description 12x12 floor tile, tan
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Location Weight room office Hallway, arts/crafts Around vent stacks
Location Lobby storage room 1st fl. jan. closet Stairwell landings 1st fl. closet, SW
Location Culinary arts roof
Location Dorm rooms, hallways 1st fl. jan. closet
Location Around vent stacks Plaster vocation Bathroom, office
Location Bathroom, paint shop
12000
10000
Building :
Building :
Building :
Building :
Building :
Building :
0010 - RECREATION/GYMNASIUM
0012 - MOUNT RAINIER DORMITORY
0013 - DINING HALL
0016 - CHALLENGER DORMITORY
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPECIALIS
0031 - VOCATIONS BUILDING
Asbestos-Containing Materials Inventory
Date: 01/24/2024Center : Cascades (01003) Page: 2 of 2
Floor Finishes Floor Finishes Heating Floor Finishes Roof Repair/Replacement Floor Finishes Floor Finishes
Floor Finishes
Bldg System
Bldg System
12x12 floor tile, tan 12x12 floor tile, gray Pipe fitting insulation 9x9 floor tile, green Roof flashing 9x9 floor tile, green/white 9x9 floor tile, tan/gray
9x9 floor tile, tan/red
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Unit
Unit
Quantity
Quantity
Vocational office Storage/Support Storage/Support Medical hallway Rooftop HVAC units East wing Southwest wing
Detention/isolation
14000 12500
Building :
Building :
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENTAL
0034 - SECURITY/SAFETY
Radon
Page: 1 of 2
0010 - RECREATION/GYMNASIUM
0010A - SECURITY SHACK
0012 - MOUNT RAINIER DORMITORY
0013 - DINING HALL
0015 - ACADEMICS/EVERGREEN DORMITORY
0016 - CHALLENGER DORMITORY
0017 - WHITEWATER DORMITORY
0024 - REGISTRARS OFFICE
0025 -VOCATIONAL
0026 - MAINTENANCE STORAGE
0027E - WAREHOUSE/RECEIVING
0027W- MEDICAL ASSISTANT/MEDICAL OFFICE SPE
0028 - CENTER MAINTENANCE SHOP
0029 - MAINTENANCE EQUIPMENT STORAGE
0030 - CULTURAL CENTER
0031 - VOCATIONS BUILDING
0032 - ADMINISTRATION/EDUCATION/MEDICAL-DENT
0033A - FORMER STORAGE (VACANT)
0033B - TEAP MEETING ROOM
0034 - SECURITY/SAFETY
0048 - LEARNING RESOURCE CENTER/LIBRARY
0050 - WAREHOUSE STORAGE A
0057 - ADMISSIONS AND PLACEMENT
0063 - TRACTOR SHED
Bldg Name
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
05/23/1990
11/02/2004
Test Date
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
N/A
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
Radon
Page: 2 of 2
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial view of Cascades JCC
Page: 1 Date: 02/14/2024 of 4
Comments:
Paving Type for Roads & Parking
A gravel road loops around Building 33A. Parking areas located between Administration/Education/Medical-Dental Building 32 and Vocations Building 31 and near Dining Hall Building 13 and Dormitory Buildings 15, 16 and 17 are concrete. Visitor parking at west side of Security/Safety Building 34 is compacted dirt road.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. A chain link fence with lockable gates secures the area of vocational buildings at the north-east side of campus. The site has an abundance of mature trees and well maintained green space and other plantings.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualSkagit County Public Utility District No. 1.Public Water Authority
None 0None
Water is metered at 8 locations for Job Corps buildings. Buildings 10, 12, 13, and 57 are individually metered, and all other buildings are zoned metered.
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Yes 0 4None Municipal
The Center is supported by the Sedro Woolley Fire Department, located at 325 Metcalf Street, Sedro Woolley, which is approximately 2.6 mile away and has an estimated response time of four minutes.
Number of Deficiencies = 4
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures24 20Flat
Surrounding
Outdoor Recreation
Forest
Basketball, Football, Soccer, Soft/Baseball, Volleyball Retention Pond, Two Bioswales, Underground Utility Tunnel System
Vocations Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition No Fair No Good
Number of Deficiencies = 1
Fencing
Other Features
Page: 2 Date: 02/14/2024 of 4
Comments:
Sewage Treatment Flow
The underground sewer from the Center flows into the publicly owned wastewater treatment plant by means of gravity and a lift station west of Administration Building 32.
Utility
Publicly Owned Treatment Works
Lessor
Gravity
Maintenance ResponsibilityOwnership
Comments: Propane is provided by Amerigas. A 500-gallon above-ground propane tank located in the northwest corner of Admission and Placement Building 57 provides natural propane gas to the building for heating.
Cascade Natural Gas Corporation
Comments: Steam is provided to the Center buildings from the on-site Lessor-operated power plant (Building 19). At most Center buildings, the steam is converted to hot water and used for space heating.
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
6. Central Plant
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 4
Drain Type On-Site Storm Water Management
Underground Retention Pond
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Yes GoodLessor
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Type Energy Source
Steam Natural Gas Most Cascades JCC buildings.
Bldgs Served
Ownership Maintenance Responsibility Plant Capacity Adequate Plant Condition
Lessor Lessor Yes Good
Page: 3 Date: 02/14/2024 of 4
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Puget Sound Energy (PSE)
Service is brought to the center from the main switchgear located in the lessor's powerhouse. The 4.16/2.4 kV lines are routed through a loop of transformer vaults which are either above ground or underground in the tunnel.
From these vaults the secondary 120/208V, 3-phase, 4 wire system is distributed to DOL leased buildings via their respective service disconnects and/or main distribution panels. Some buildings have their own meter while others are zone metered. Dining Hall Building 13 and Dormitory Buildings 12, 15, 16 and 17 have backup power from an emergency generator in the powerhouse for critical loads such as condensate pumps and cooking equipment. The emergency backup power is metered separately.
Vault Utility
Lessor Lessor
No
Comments:
Telephone Company
On-site Line Owner
Six T-1 lines are brought to the main telephone/server room located in Building 32. Local telephone service is provided by Frontier Communication with a T-1 line connected to the router. Long distance calls are provided via Voice over Internet Protocol (VoIP) on the Job Corps Data Center network. The data and VoIP communication networks are routed via underground fiber optic cabling. A central fire alarm control/annunciator panel in Security Building 34 monitors fire alarm panels in Dining Hall Building 13, Warehouse/Receiving Building 27E, Medical Assistant/Medical Office Specialist Building 27W, and Dormitory Buildings 12, 15, 16, and 17. Other fire alarm panels at the center are monitored by lessor's central fire alarm control/annunciator panel in the powerhouse.
Comcast provides cable TV in all dormitory lounges and other recreational spaces at the center. The security system is limited to dormitories only with door alarms for unauthorized ingress/egress detection.
Frontier Communication
Maint. Responsibility
Center Center, Lessor
Door Alarms
4.16/2.4 kV, 3-Phase, 4 Wire
120/208V, 3-Phase, 4 WireUnderground
UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 2
9. Electrical (Communication/Alarm/Security)
7. Electrical (Service)
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Sport Light
Photocell, Time Clock Photocell, Time Clock Photocell Photocell Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center, Lessor Center, Lessor Yes Good
Comments: The site lighting system, consisting of building-mounted exterior and pole-mounted fixtures, is owned and maintained by the lessor. The site lighting system is controlled by photocells and time clocks.
ATS MTS
Yes No
Number of Deficiencies = 2
Number of Deficiencies = 3
Fire Alarm Security
Metering Individual and Groups
Page: 4 Date: 02/14/2024 of 4
ACCESSIBILITY
Yes
Comments:
UnknownYesYes
The site and nine buildings were listed on the National Historical Preservation Registry in December, 2010. The nine buildings are Mount Rainier Dormitory Building 12, Dining Hall Building 13, Academic/Evergreen Dormitory Building 15, Challenger Dormitory Building 16, Whitewater Dormitory Building 17, Registrars Office Building 24, Warehouse/Receiving Building 27E, Cultural Center Building 30 and Vocations Building 31.
Yes
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
04/01/1999
04/01/1999
Center
Center
Active
Active
Aboveground
Aboveground
Near Building 26
Near Building 57
Yes
Yes
Petroleum - Gasoline
Propane
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date
Earthquake Risk
High Low LowMedium LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
ID
Reg.
Number of Deficiencies = 4
Number of Deficiencies = 1
Accessible Parking: Accessible Slope:
No
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
The site is well maintained and in good condition.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Equip/Veh Fueling
Heating
Purpose
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of Brightly or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Comments: The Center currently uses the Brightly a Computerized Maintenance Management System (CMMS) for preventive maintenance.
Yes
Yes
NO
NO
Yes
Yes
Yes
Yes
50 %
Building Descriptions and Structures
BUILDING 10 - RECREATION/GYMNASIUM
WEIGHT ROOM ARTS &
CRAFTS
KILN ROOM
ARTS & CRAFTS
LOBBY
EXERCISE
ROOM/STORAGE
GYMNASIUM
MEN'S LOCKER
ROOM
WOMEN'S
LOCKER ROOM
W M
MECH. RM
SHOWERS
SHOWERS
MECH.
TV ROOM
OFFICES
JAN
STORAGE
LAUNDRY
STORAGE
BLEACHERS
TOILET
TOILET
ELEC.
ART SUPPLY
RECREATION/GYMNASIUM
BUILDING 10
0 10' 30' 60'
CASCADES JOB CORPS CENTER
SEDRO-WOOLLEY, WASHINGTON
RECREATION
Building Descriptions Date: 02/14/2024Center : Cascades (01003) Page: 1 of 117
Building: 0010 - RECREATION/GYMNASIUM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
CMU Masonry
Comments: There is stucco finish on the exterior walls.
Wall Roof None Batt
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Assembly 15,740 11,157 1 Leased 1963 Not Evaluated
REAL ESTATE
Access to Building Ramps Entrance 2nd Egress Visual Alarm Corridor/Aisle Rooms Stairs Elevator Restrooms Drinking Fountain Telephone
Yes N/A Yes Yes Yes Yes Yes N/A N/A Yes No N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 3
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
The roof is old, and damaged. Roof life is estimated based on observation during the October 2023 Facility Survey.
Drainage Year Life
Type Area Served
Single Ply Interior Roof Drains, Scuppers 1996 0 Flat Entire Building
Number of Deficiencies = 2
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 117
Building: 0010 - RECREATION/GYMNASIUM
INTERIOR FINISH
Carpet Concrete Rubber Terrazzo Vinyl Tile Wood
Ceramic Tile Drywall Plaster
Metal Units - Metal Frame Metal Units - Wood Frame
Wood Units - Wood Frame
VERTICAL CIRCULATION
Metal Ladder Comments: There is a steel ladder to the roof hatch.
Casement - Wood Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;
Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Windows6.
Floors1. Asbestos: Yes Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating for the building is provided by seven vertical floor-mounted fan coil units, manufactured by McQuay with hot water heating coils.
There are two gas-fired water boilers, manufactured by Burnham (model P807NEI-E2, 396 MBH input, 316 MBH output, built in 10/2002) provide heating water circulated throughout the building by two in-line pumps located in the northwest mechanical room. Four wall-mounted heating and ventilating units with hot water heating coils serve the gymnasium.
Heating for the offices is provided by a ceiling mounted air handling unit with hot water heating coil.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Radiator
Unit Ventilator
Single Duct
Two-Pipe
Two-Pipe
Two-Pipe
Electric
Electric
Electric
Natural
Mechanical
Natural
None
None
None
Recreation Area
Gymnasium
Recreation Area
Ceilings
Page: 3 of 117
Building: 0010 - RECREATION/GYMNASIUM
Mechanical
Mechanical
Mechanical
Mechanical
Toilet/Shower
Recreation
Kiln Area
Restroom
Comments:
Comments:
Comments:
Comments:
Roof-mounted exhaust fans ventilate the men’s and women’s toilet/showers rooms.
Roof-mounted exhaust fans ventilate the Arts and Crafts and Exercise Room/Storage.
Wall-mounted exhaust fan, manufactured by Nutone, (model 8170) ventilates the Kiln Room.
Roof-mounted exhaust fan ventilates the men’s and women’s restrooms.
Domestic hot water is provided by a gas-fired water heater, manufactured by A. O. Smith (model BTR 197 118, with an input heating capacity of 199 MBH, 100-gallon storage capacity, recovery rate of
192.96 GPH, built in 05/14/2002) located in the mechanical room.
Comments:
Cast-Iron None Cast-Iron
Electric Water Cooler Hose Bibb Lavatory Shower Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Window Unit None Electric Natural None Recreation Area
PLUMBING
Exhaust Ventilation
Two window air conditioning units, manufactured by Whirlpool, model number ACM102XL0, provide DX-cooling to Arts and Craft.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
3. Number of Deficiencies = 1Air Conditioning
Page: 4 of 117
Building: 0010 - RECREATION/GYMNASIUM
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 75 kVA pad-mounted transformer located outside the electrical room and terminates in a 225A main circuit breaker main distribution panel (MDP) located inside. A meter is installed next to the MDP. This transformer also serves Learning Resource Center/Library Building 48.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Notifier SFP-1024 unit located in the main corridor. The building fire alarm system is monitored by the lessor's central fire alarm control/annunciator panel in the power house.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Shower
Gymnasium
Locker Room
Recreation
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
Number of Deficiencies = 1
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1. Number of Deficiencies = 1
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 2
LIGHTING
Page: 5 of 117
Building: 0010 - RECREATION/GYMNASIUM
Connected to Main System None Connected to Main System Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The single-ply membrane roof is at the end of its life expectancy.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
Not requared.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 10A - SECURITY SHACK
Page: 6 of 117
Building: 0010A - SECURITY SHACK
BUILDING ENVELOPE
Foundation RoofBuilding
Wall Roof
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Business 80 1 Owned 2020 Not Evaluated
REAL ESTATE
Access to Building Ramps Entrance 2nd Egress Visual Alarm Corridor/Aisle Rooms Stairs Elevator Restrooms Drinking Fountain Telephone
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Windows6.
Material Drainage Year Life
Type Area Served
Asphalt Shingles 2020 27 Shed Entire Building
3. Roof
Page: 7 of 117
Building: 0010A - SECURITY SHACK
INTERIOR FINISH
Ventilation Area Served
No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
VERTICAL CIRCULATION
PLUMBING
Exhaust Ventilation
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Ceilings
3. Air Conditioning
Page: 8 of 117
Building: 0010A - SECURITY SHACK
FIRE ALARM
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Telephone Security Public Address Television
Area Recommended Recorded Light Type
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas
UNKNOWN UNKNOWNUNKNOWN
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 0
Page: 9 of 117
Building: 0010A - SECURITY SHACK
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
BUILDING 12 - MOUNT RAINIER DORMITORY
BASEMENT FLOOR
UP
UNEXCAVATED
UTILITY TUNNEL
UNEXCAVATED
UNEXCAVATED
STORAGE
STORAGE
(VACANT)
BUILDING 12
0 10' 20' 40'
CASCADES JOB CORPS CENTER
SEDRO-WOOLLEY, WASHINGTON
MOUNT RAINIER DORMITORY
VACANT
Page: 10 of 117
Building: 0012 - MOUNT RAINIER DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete and Clay Tile Block
Wood w/Conc.Truss Frame
Stucco
Comments: The stucco finish is chipped.
Wall Roof None Batt
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Residential 17,560 10,605 2 Leased 1922 Listed
REAL ESTATE
Access to Building Ramps Entrance 2nd Egress Visual Alarm Corridor/Aisle Rooms Stairs Elevator Restrooms Drinking Fountain Telephone
Yes N/A Yes Yes Yes Yes Yes No N/A Yes Yes Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Fiberglass Tile Gutters and Downspouts 2010 17 Hip Entire Building
3. Roof
Entire Building
Page: 11 of 117
Building: 0012 - MOUNT RAINIER DORMITORY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Terrazzo Vinyl Tile
Ceramic Tile Drywall Plaster
Comments: Toilet partitions are metal.
Metal Units - Metal Frame Wood Units - Metal Frame
Wood Units - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Stairs Wood Stairs Comments: Exterior steel stairs (at east and west side of building) provide fire escape from second floor. A wood stair leads to the attic HVAC area.
Double Hung - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Gypsum Board Plaster
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A central heating and ventilation air handler, manufactured by Brod and McClung with hot water heating coils, located in the utility tunnel. The space heating hot water is provided by a steam to water shell and tube heat exchanger, manufactured by Helitherm (model SW1A03, serial number H-78-733 and built in 1978) located in the utility tunnel. Steam is generated at the central power plant Building 19 operated by Lessor.
The restrooms and shower areas have supplemental heat provided by floor-mounted radiators with hot water heating coils.
Heating to the laundry rooms is provided by wall mounted electric heaters.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Steam Boiler
Gas-Fired Steam Boiler
Unit Ventilator
Radiator
Two-Pipe
Two-Pipe
Direct Digital Control (DDC)
Thermostatic Valves
Mechanical
Natural
None
None
Entire Building
Dorm Rooms
Page: 12 of 117
Building: 0012 - MOUNT RAINIER DORMITORY
Mechanical Toilet/Shower
Comments: Wall-mounted exhaust fans manufactured by Multifan (model 4E25 with override controller) ventilate the toilet/showers and laundry rooms. Four central exhaust fans ventilates the building and are located in the attic.
Domestic hot water is provided by a steam to water shell and tube heat exchanger, circulating pump, and an associated 200-gallon capacity hot water insulated steel storage tank, manufactured by A. O.
Smith, located in the utility tunnel.
Comments:
Cast-Iron None None
Electric Water Cooler Hose Bibb Lavatory Portable Bottled Water Cooler Shower Sink Urinal Water Closet (Flush Valve)
None
Wet None ABC Type Fire Extinguisher
Ventilation Area Served
Copper Copper Steam Heat Exchanger
None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
None None None None Natural None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 2FIRE PROTECTION
Page: 13 of 117
Building: 0012 - MOUNT RAINIER DORMITORY
Comments: Service is brought from a 150 kVA transformer vault in the tunnel beneath the building. Equipment in the vault consists of a 150 kVA pad-mounted transformer, transformer disconnect switch, a current/transformer (C/T) cabinet, a meter and a 600A, 120/208V, 3-phase, 4 wire main distribution panel (MDP). This building also has a 60A emergency panel, which is sub-fed from emergency panel in Dining Hall Building 13.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Notifier SFP-1024 unit located in the first floor janitor closet.
A Notifier remote annunciator panel is installed at the main entrance. The building fire alarm system is monitored by the Center control/annunciator panel in Security/Safety Building 34.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Flow Switch Manual Pull Station Remote Annunciator Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Laundry Room
Housing Lounge
Shower
Sleeping Rooms
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES
Exterior Lighting1. Number of Deficiencies = 1
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 4
Page: 14 of 117
Building: 0012 - MOUNT RAINIER DORMITORY
Connected to Main System Magnetic Door/Alarm None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes NoYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
There is no plausible means by which harmful levels of CO could enter sleeping rooms.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
BUILDING 13 - DINING HALL
CULINARY
ARTS
DININIG
VACANT
ELECTRICAL
MECHANICAL/
TRANSFORMER
ROOM
DINING
AREA DINING
AREA
CONFERENCE
ROOM
KITCHEN
DISHWASH
POTWASH
FOOD PREP.
AREA
DRY FOOD
STORAGE
STOR.
REFRIGERATOR
FREEZER
REFRIGERATOR
FR
EE
ZE
R
T T
T
LOADING
DOCK
BASEMENT
FIRST FLOOR
JAN
OFFICE
KI
TC
H
EN
DISHWASHING
STAFF
BREAK
ROOM
FOOD
SERVICE
MANAGER
STR.
LOCKER
HAND
WASH
TO ATTIC
MECH. EQUIP.
T
T
T
STORAGE
STORAGE
DN
UP
STORAGESTAGING
AREA
RAMP UP
CLUB HOUSE
SERVING
DN
RAMP UP
VACANT
ST.
UP
RAMP UP
C
AN
O
PY
CHASE
LADDER TO
ATTIC MECH
EQUIPMENT
ST.
JAN
CRAWL SPACE
ACCESS DOOR
DINING HALL
BUILDING 13
0 10' 30' 60'
CASCADES JOB CORPS CENTER
SEDRO-WOOLLEY, WASHINGTON
FOOD SERVICE
VOCATION/THEORY
Page: 15 of 117
Building: 0013 - DINING HALL
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete w/Clay Tile Block Wood
Stucco
Wall Roof None Batt
Metal Overhead - Metal Frame Metal Rollup - Metal Frame Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Assembly 26,880 14,719 2 Leased 1922 Listed
REAL ESTATE
Access to Building Ramps Entrance 2nd Egress Visual Alarm Corridor/Aisle Rooms Stairs Elevator Restrooms Drinking Fountain Telephone
Yes N/A Yes Yes Yes Yes Yes Yes No Yes No N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material
Asbestos: Yes
Drainage Year Life
Type Area Served
Asphalt Shingles Gutters and Downspouts 2020 27 Hip Entire Building
3. Roof
Entire Building
Page: 16 of 117
Building: 0013 - DINING HALL
INTERIOR FINISH
Carpet Ceramic Tile Concrete Quarry Tile Terrazzo
Ceramic Tile Drywall Fiberglass Reinforced Panels Plaster Wallpaper Wood Paneling
Comments: Toilet partitions are metal.
Metal Units - Metal Frame Wood Units - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Ladder Wood Stairs Comments: There is a metal ladder to the attic mechanical room that contains three sets of wood stairs to access mechanical equipment.
Awning Units - Steel Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;
Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Perforated Fiberboard Tiles Plaster
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Page: 17 of 117
Building: 0013 - DINING HALL
Mechanical
Mechanical
Mechanical
Mechanical
Restroom
Dishwashing
Kitchen
Pizza Oven
Ventilation Area Served
Packaged Direct
Expansion (Air Source)
Packaged Heat Pump (Air
Source)
Window Unit
Single Duct
None
None
Electric
Electric
Natural
Mechanical
None
None
Offices
Classrooms
Exhaust Ventilation
Window air conditioning units provide DX-cooling to Conference Room and the adjacent room.
A wall-mounted high-efficiency heat pump, manufactured by Carrier, R-22 refrigerant, provides DX-cooling to Club House.
Comments:
Comments:
Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A heating and ventilation air handler with heating water coils serves the dining area. The space heating hot water is provided by a steam to water shell and tube heat exchanger. Steam is generated at the central power plant Building 19 operated by Lessor.
A gas-fired package unit provides tempered make-up air to the culinary arts kitchen hood.
Ceiling-hung unit heaters with heating water coils provide…