16 Att 06 Contractor As Built Dwgs For Controls.pdf

PDF 7 MB Posted

Attached to
Amend 002 - IIJA LIT ATCT, HVAC, Replace Boiler, Controls System Federal contract opportunity
Solicitation number
6973GH-25-R-00125
Issued by
Department of Transportation Federal Aviation Administration Franchise Acquisition Services

About this file

This document is a detailed set of mechanical and control system design drawings for an FAA Control Tower System Upgrade located in Little Rock, Arkansas. The comprehensive drawing set, prepared by Powers of Arkansas, covers multiple system components including air handling units (AHU-81.91 and AHU-1), variable refrigerant flow (VRF) systems, condensing units (CRU-1,2,3), exhaust fans, hot water systems, and associated control panel configurations.

The drawings provide extensive technical specifications for replacing existing HVAC controls and equipment, featuring Siemens Apogee automation systems and network layouts. Key technical elements include new DDC (direct digital control) controllers, temperature and humidity sensors, damper actuators, communication interfaces, and control panel migrations. The design emphasizes system integration, remote monitoring capabilities, and sequential operational sequences for various mechanical systems like air handlers, exhaust fans, and hot water pumps. The upgrade appears designed to modernize the facility's environmental control infrastructure with advanced, networked control technologies.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL CONTRACTOR:

ENGINEERING FIRM:

FAA CONTROL TOWER

SYSTEM UPGRADE

LITTLE ROCK, AR

CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

c COPYRIGHT

ENGINEER

FAA Control Tower Sys Upgrade Little Rock, AR

C4431

Cover Sheet

C:\JOBS\C4431\MDT\CVRSHEET.DWG

DWJ DWJ JLJ 12/11/15 12/29/15Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion 5440 Northshore Drive N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

COMFORT SYSTEMS USA

FAA

1 12/29/2015 DWJ SUBMITTALS

CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

c COPYRIGHT

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

Table of Contents

TOCA

N:\DT Resources\JOBS\C4431\MDT\TOC-000.dwg

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas ALL RIGHTS RESERVED1994-15

REVISION HISTORY

DWG DESCRIPTION

GENERAL

Cover Sheet

000 Riser Diagram LEG Legend & Abbreviations

CONTROL DRAWINGS

001 AHU-81.91

006 AHU-81.91 PANEL

007 AHU-81.91 EXISTING MBC

008 AHU-81.91

009 AHU-1

014 AHU-1 PANEL

015 AHU-1 EXISTING MBC

016 AHU-1

017 CRU45

019 CRU45 PANEL

020 FURN-1&2 CU-2&

022 FURN-1&2 CU-2& PANEL

023 VRF

024 NOTES

025 HOT WATER SYSTEM

026 MISC1

027 MISC2

028 MISC3

029 CRU-1,2,3

030 EF-8,9

DDC PANEL LAYOUTS

002 AHU-81.91 LAYOUT

003 PXCM2p002 004 PXCM2p003 005 PXCM2p004

010 AHU-1 LAYOUT

011 PXCM1p002 012 PXCM1p003 013 PXCM1p004

018 CRU45 PXCC

021 FURN-1&2 PXCC

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

Legend & Abbreviations

LEG

C:\Jobs\C4431\MDT\Legend.dwg

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas ALL RIGHTS RESERVED1994-15

REVISION HISTORY

TRUNK NUMBER

CABINET NUMBER

LAN TRUNK

DROP NUMBER

POINT NUMBER

TRUNK NUMBER

CABINET NUMBER

LAN TRUNK

DROP NUMBER

POINT NUMBER

DDC ELECTRICAL POINT DDC PNEUMATIC POINT

ELECTRICAL TERMINATION

PNEUMATIC TERMINATION

STANDARD DDC TERMINATION

NOTE OR REVISION

BLN NUMBER

FLN TRUNK

CABINET NUMBER

DROP NUMBER

POINT NUMBER

DETAILS

APOGEE: PII - EXAMPLE

CONTROL

SYMBOL

AC

AD

AE

AF

AFS

AP

APS

AT

ATD

BELL

BOIL

CBL

CKV

CM

CP

CPU

CRT

CS

CVC

D

DP

DPR

DPS

DPTE

DPTP

DPU

EC

EP

ES

ET

FHC

FM

FMS

FS

FTP

G

CONTROL SYMBOL

DESCRIPTION

AIR COMPRESSOR

AIR DRYER

ACTUATOR ELECTRIC

AIR FILTER

AIR FLOW STATION

ACTUATOR PNEUMATIC

AUX. POWER SUPPLY

AUTOMATIC TRAP

AUTO TANK DRAIN

BELL

BOILER

CABLES

CHECK VALVE

CONSTRUCTION MATERIALS

COMPONENT PANEL

CENTRAL PROCESSING UNIT

CATHODE RAY TUBE

CURRENT SWITCH

CONSTANT VOLUME CONTROLLER

DAMPER

DEW POINT TRANSMITTER

DIFFERENTIAL PRESS. REGULATOR

DIFFERENTIAL PRESSURE SWITCH

DIFF. PRESS. TRANSMITTER ELEC.

DIFFERENTIAL PRESSURE PNEUMATIC

DIGITAL POINT UNIT

ENTHALPY COMPARITOR

ELECTRO-PNEUMATIC VALVE

END SWITCH

ENTHALPY TRANSMITTER

FUME HOOD CONTROLLER

FLOW MTR. (FLOW METER STATION)

FIRE MGMT. SYSTEM

FLOW SWITCH

FLOW TRANSMITTER PNEU.

GAUGE

DESCRIPTION

CONTROL SYMBOL

LOGICAL POINT NAME

TRANSFORMER

TRANSDUCER

WELL

VELOCITY TRANSMITTER ELECTRICAL

VARIABLE AIR VOLUME CONTROLLER

TEC VALVE ACTUATOR

VALVE SERVICE PARTS

UNIT VENT CONTROLLER

UNIT CONDITIONER CONTROLLER

UNITARY CONTROLLER

TEMPERATURE TRANSMITTER PNEUMATIC

TEMPERATURE TRANSMITTER ELECTRIC

TIMER, TIME CLOCK

TELCOM INTERFACE UNIT

TRUNK INTERFACE

THERMOMETER

TERMINAL EQUIPMENT CONTROLLER

THERMOSTAT, ELECTRIC

TIME DELAY RELAY

TERMINAL CONTROL UNIT

TEMPERATURE CONTROLLER(S200)

TERMINAL BOX CONTROLLER

ROOM THERMOSTAT, PNEUMATIC

SWITCH PNEUMATIC

SOLENOID VALVE

STATIC PRESSURE REGULATOR

SPEAKER

SWITCH ELECTRIC

SMOKE DETECTOR

STAND ALONE CONTROL UNIT

STEP CONTROLLER

SOFTWARE

RELIEF VALVE

RESTRICTOR

RELAY PNEUMATIC

RELAY ELECTRIC

XFMR

XDR

W

VTE

VB

VA

V*

UVC

UCC

UC

TTP

TTE

TMR

TIU

TI

TH

TEC

TE

TDR

TCU

TC

TBC

T

SW

SV

SPR

SPKR

SE

SD

SCU

SC

S/W

RV

RS

RP

RE

DESCRIPTION

CONTROL SYMBOL

SYMBOL

CONTROL

REMOTE CONTROL UNIT

RECEIVER CONTROLLER

PILOT VALVE

PRINTER

PRESSURE TRANSMITTER PNEUMATIC

PRESSURE TRANSMITTER ELECTRIC

PITOT TUBE

PULL STATION

POSITION SENSOR ELECTRIC

POSITIONING SWITCH

PRESSURE REDUCING VALVE

PRESSURE REG. CONTROLLER

PANEL

POWER MONITOR

PILOT LIGHT

PRESSURE ELECTRIC SWITCH

PROGRAMMABLE CLOCK TIMER

PULSE ACCUMULATOR

OBSOLETE

MOTOR STARTER

MULTI-POINT UNIT

MAGNEHELIC GAUGE

ELECTRONIC ACTUATOR

MODEM

LOW TEMP. DETECTOR PNEUMATIC

LOW TEMP. DETECTOR ELECTRIC

POWER SUPPLY 24VAC/24VDC

LIQUID LEVEL TRANS.

LIQUID LEVEL SWITCH

LIMIT CONTROLLER (LIMITEM)

ELECTRIC KILOWATT METER

INTERCOM

HUMIDITY TRANSMITTER PNEUMATIC

HUMIDITY TRANSMITTER ELECTRIC

HIGH TEMPERATURE DETECTOR

HEAT PUMP CONTROLLER

HORN

HAND-OFF-AUTO SWITCH

RCU

RC

PV

PTR

PTP

PTE

PT

PST

PSE

PS

PRV

PRC

PNL

PM

PL

PE

PCT

PA

OBS

MS

MPU

MG

ME

MDM

LTDP

LTDE

LPR

LLT

LLS

LC

KWM

INT

HTP

HTE

HTD

HPC

HORN

HOA

CONTROL

SYMBOL

DIGITAL INPUT

TO CONTROL

DEVICE

AH1LTD

0.10.3.10.27È

R

S

S

AOP

DETAIL XX

DETAIL 5A

DETAIL MC

READ AS " SEE PAGE 5A FOR MORE DETAIL "

PAGE REFERENCEDETAIL XX

APOGEE ETHERNET MICROSERVERAEM

ANALOG OUTPUT, PNEUMATICAOP

ACTUATOR TECATEC

AUTOZERO MODULEAZM

CURRENT TRANSDUCERCT

DDC DUAL DUCT CONTROLLER

DEM DEMAND ENERGY MONITOR

EXPANSION PANELEXP

HAND-HELD OPERATOR'S TERMINAL

HL HIGH LIMIT

H

HHC

HYGROSTATS

FAN FAN

GD GAS DETECTOR

HE HUMIDIFIER ELECTRIC

MODULAR BUILDING CONTROLLERMBC

MEC MODULAR EQUIPMENT CONTROLLER

P PUMP

RBC REMOTE BUILDING CONTROLLER

OPERATOR DATA PANELODP

SPP STATIC PRESSURE PROBE

TIE TRUNK ISOLATOR EXTENDER

VALVEV

VAC VIBRATION ISOLATOR

READ AS " SEE PAGE 5A FOR MORE DETAIL "

DIGITAL INPUT

APOGEE: ETHERNET - EXAMPLE

LOGICAL POINT NAME

POINT NUMBER

DROP NUMBER

NODE NUMBER

REFERENCE NUMBER

FLN TRUNK

DETAIL MC

DETAIL 5A

AH1LTD

0001:3.10.27È

PXCC PX COMPACT CONTROLLER

BUS INTERFACE MODULEBIM

TXIO TX-I/O FAMILY CONTROLLER MODULES

PXCM PXC-MODULAR CONTROLLER

POINT PICKUP MODULEPPM

LOCAL USER INTERFACELUI

CO2 TEMP TRANSMITTER ELECCTTE

PTNAME

0 00 0 00 00È È00000000

PTNAME

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

Riser Diagram

C:\JOBS\C4431\MDT\RISER.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

System 600

POWERS

System 600

POWERS

POWERS

TEC

POWERS

System 600

STATUS

TX

RX

UC 1-

POWERS

TEC

POWERS

TEC

NEW WORKSTATION

BASE BUILDING

ESU BUILDING

ATCT BUILDING

(VERIFY LOCATION)

LOCATED IN MECH ROOM

VAV BOX CONTROLLERS

TO OTHER BOXES

TOTAL 18

TO FIELD

POINTS

TO FIELD

POINTS

TO FIELD

POINTS

POINTS

TO FIELD

POINTS

TO FIELD

NETWORK LAYOUT1

PXCM 1-

PXCM 2-

PXCC 1-

PXCC 2-

CPU 1-

POWERS

System 600

STATUS

TX

RX

UC 2-

MBC-2

MBC-1

DIAGRAM IS A GRAPHICAL REPRENSENTATION AND IS FOR REFERENCE ONLY.

FOR FINAL LAYOUT SEE SYSTEM PROFILE.

ETHERNET CONNECTIONS TO NEW DEVICES SHALL BE COORDINATED WITH THE

DATA CONTRACTOR.

ALL FIELD LEVEL DEVICES ARE TO BE DAISY CHAIN CONFIGURATION

AT THE COMMUNICATION TRUNK.

S/W 1-

S/W 2-

SW 1-

SW 2-

SW 2-

VRF

PANEL

4 SWITCHES PROVIDED AND INSTALLRD BY POWWERS.

ETHERNET

FLN

ETHERNET

ETHERNET

ETHERNET

5 COMPUTER TO BE UPDATED AND THE LATEST SIEMENS SOFTWARE LOADED.

INSTALLATION NOTES:

Control Qty Product Number Manufacturer Document Description

Device Number

Field Mounted Devices

CPU 1 1 DELL DELL MARKETING LP DELL DEL DESKTOP/TOWER PER QUOTE

S/W 1 1 INS SIEMENS 149333 INSIGHT ADVANCED

S/W 2 1 571-181 SIEMENS 149 402 RENO OPTION FOR INSIGHT

S/W 3 1 571-188 SIEMENS BACnetOpt BACNET CLIENT LIC ( INSIGHT 3.7 OR HIGH

SW 1 1 DGS-1008G D-LINK DGS-1008G D-LINK 8 PORT GIGABIT

SW 2 1 DGS-1008G D-LINK DGS-1008G D-LINK 8 PORT GIGABIT

SA

RA

S Q B

AE 2

0/10 VDC

SAC2RAD

0001:0.8.8

È

AHU-81 & 91 FLOW DIAGRAM1

001 LOCATION: 8TH LEVEL

SEE SHEET M21 FOR LOCATION

SAC2AC1

0001:0.1.2È

SAC2AC2

0001:0.1.3È

XD

LPS

0/10 VOLTS

SACHUME

0001:0.3.5È

NC

6'MIN

LANDIS&GYRPOWERS

24 VAC

LANDIS&GYRPOWERS

24 VAC

SPP 4-SPP 3-

SAC2SSD

0001:0.4.16È

CS 2

SAC2FAN (PROOF)

0001:0.4.1

È

RE 2

SAC2FAN (ON/OFF)

0001:0.1.1

È

NO

RA

SPACE SENSORS

POWERS

HTE 1

0/95 %RH

SACRMH

0001:0.5.5

È

POWERS

TTE 8

-40/240DEG F

SACRMT

0001:0.7.8

È

S Q B

AE 1

0/10 VDC

SAC1RAD

0001:0.8.7

È

SAC1AC1

0001:0.2.1È

SAC1AC2

0001:0.2.2È

XD

LANDIS&GYRPOWERS

24 VAC

LANDIS&GYRPOWERS

24 VAC

SPP 2-SPP 1-

SAC1SSD

0001:0.4.15È

NOTE: ?? AFF

BY DIVISION OTHERS.

SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

REUSE EXISTING CONDUIT WHERE POSSIBLE.

REUSE CONDUIT ON THE EXTERIOR OF THE WALL FOR

COMPONENT PANEL.

REPLACE REMOVED CONTROLS WITH NEW DEVICES.

AHUS TO BE REPLACED WITH NEW AHUS.

CONTROL TRANSFORMERS AND RELAYS MOUNTED INCS 1

SAC1FAN (PROOF)

0001:0.4.2

È

RE 1

SAC1FAN (ON/OFF)

0001:0.1.4

È

NO

NC

NC

OA

RA

SAC1HEAT1

0001:0.2.3È

SAC2HEAT1

0001:0.1.5È

TTE 2

20/120 DEG F

SAC1MAT

0001:0.6.5

È

TTE 6

20/120 DEG F

SAC2MAT

0001:0.6.4

È

TTE 1

20/120 DEG F

SACOAT

0001:0.8.6

È

TTE 7

20/120 DEG F

SACRAT

0001:0.5.1

È

AE -3

0/10 VDC

SACOAD

È0001:0.8.2

AE -4

0/10 VDC

SACRAD

È0001:0.8.3

TTE 4

-40/240 DEG F

SACSAT

0001:0.5.7

È

CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

c COPYRIGHT

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

AHU-81.91

N:\DT RESOURCES\JOBS\C4431\MDT\AHU-81.91.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

SAC1HEAT2

0001:0.2.4È

SAC2HEAT2

0001:0.1.6È

TTE 3

20/120 DEG F

SAC1SAT

0001:0.6.2

DETAIL MR

È

TTE 5

20/120 DEG F

SAC2SAT

0001:0.5.8

È

HI LIMIT WIRED

TO HUMIDIFIER SAFETY CIRCUIT

CU-8

SAC1AC1

0001:0.2.1È

SAC1AC2

0001:0.2.2È

TO DX

COILS

TO DX

COILS

CU-9

SAC2AC1

0001:0.1.2È

SAC2AC2

0001:0.1.3È

TO DX

COILS

TO DX

COILS

WIRE PATH TO CONDENSING UNITS.

DPTE 1

0/10 in H2O

SAC1FP

0001:0.5.2

L

H

È

DPTE 2

0/10 in H2O

SAC2FP

0001:0.5.3

L

H

È

T

PTE 1

RANGEPSI

CU8.CMP1.PRS

0001:0.9.1

È

T

PTE 2

RANGEPSI

CU8.CMP2.PRS

0001:0.9.2

È

T

PTE 3

RANGEPSI

CU9.CMP1.PRS

0001:0.9.3

È

T

PTE 4

RANGEPSI

CU9.CMP2.PRS

0001:0.9.4

È

PT 1- PT 2-

PT 3- PT 4-

0001 PXCM2 2

REF# FIELD PANEL NAME FIELD PANEL NODE NAME

6 SOLENOID VALVES FURNISHED BY OTHERS.

INSTALLATION NOTES:

E N G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

A H U

L A Y O U T

N D T

R E S O U R C E S J O B S C M D T P X C M D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

A R

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

PXCM - 00000 PXC100-PE96.A

PXC MODULAR

Module: Rail:1 / 1

TXIO - 0000X TXS1.12F4

POWER SUPPLY 24 Volt 4A

Module: Rail:2 / 1

(3)

(2)

(1)

32(6)

(5)

(4) 20

SAC2FAN

0.1.1

L2SL ON/OFF

SAC 2 ENABLE

RE 2

AHU-81.91

SAC2AC1

0.1.2

LDO ON/OFF

SAC2 AC1

AHU-81.91

SAC2AC2

0.1.3

LDO ON/OFF

SAC2 AC2

AHU-81.91

SAC2HEAT2

0.1.6

LDO ON/OFF

SAC2 HEAT2

AHU-81.91

SAC2HEAT1

0.1.5

LDO ON/OFF

SAC2 HEAT1

AHU-81.91

SAC1FAN

0.1.4

L2SL ON/OFF

SAC 1 ENABLE

RE 1

AHU-81.91

TXIO- 00001 TXM1.6R-M 1

Module: Rail:3 / 1

(3)

(2)

(1)

32(6)

(5)

(4) 20

SAC1AC1

0.2.1

LDO ON/OFF

SAC1 AC1

AHU-81.91

SAC1AC2

0.2.2

LDO ON/OFF

SAC1 AC2

AHU-81.91

SAC1HEAT1

0.2.3

LDO ON/OFF

SAC1 HEAT1

AHU-81.91

SF1

0.2.6

L2SL ON/OFF

STAIRWELL FAN

AHU-81.91

EF2E

0.2.5

L2SL ON/OFF

EX FAN 2 ENABLE

AHU-81.91

SAC1HEAT2

0.2.4

LDO ON/OFF

SAC1 HEAT2

AHU-81.91

TXIO- 00002 TXM1.6R-M 2

Module: Rail:4 / 1

(3)

(2)

(1)

32(6)

(5)

(4) 20

EX7ENA

0.3.1

L2SL ON/OFF

EXFAN7 ENABLE

AHU-81.91

EX7HI

0.3.2

LDO ON/OFF

EXFAN7 HI LO

AHU-81.91

SVF1

0.3.3

L2SL ON/OFF

SVF1 EXH VENT

AHU-81.91 0.3.6

LDO

SACHUME

0.3.5

LDO ON/OFF

HUMIDIFER

AHU-81.91

SVF2

0.3.4

L2SL ON/OFF

SVF2 EXH VENT

AHU-81.91

TXIO- 00003 TXM1.6R-M 3

Module: Rail:5 / 1

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

P X C M p

N D T

R E S O U R C E S J O B S C M D T P X C M P D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

(4)

(3)

(2)

(1)

(12)

(11)

(10)

(9)

(8)

(7)

(5)

(6)

(16)

(15)

(13)

(14)

EF2E

0.4.8

L2SL PROOF

EX FAN 2 ENABLE

AHU-81.91

SF1

0.4.7

L2SL PROOF

STAIRWELL FAN

AHU-81.91

SVF2

0.4.6

L2SL PROOF

SVF2 EXH VENT

AHU-81.91

SVF1

0.4.5

L2SL PROOF

SVF1 EXH VENT

AHU-81.91

SAC2FAN

0.4.1

L2SL PROOF

SAC 2 ENABLE

CS 2

AHU-81.91

SAC1FAN

0.4.2

L2SL PROOF

SAC 1 ENABLE

CS 1

AHU-81.91

SAC4PRF

0.4.3

LDI STATUS

SAC4 FAN PROOF

AHU-81.91

SAC3PRF

0.4.4

LDI STATUS

SAC3 FAN PROOF

AHU-81.91

SAC2SSD

0.4.16

LDI STATUS

SUP SMK DET

SD 2

AHU-81.91

CU5PRF

0.4.14

LDI STATUS

CU5 FAN PROOF

AHU-81.91

CU4PRF

0.4.13

LDI STATUS

CU4 FAN PROOF

AHU-81.91

EF4

0.4.9

LDI STATUS

EX FAN 4 PROOF

AHU-81.91

FPMP

0.4.10

LDI STATUS

FIRE PMP PROOF

AHU-81.91

FAS2

0.4.11

LDI STATUS

FIRE ALARM

AHU-81.91

EX7ENA

0.4.12

L2SL PROOF

EXFAN7 ENABLE

AHU-81.91

SAC1SSD

0.4.15

LDI STATUS

SUP SMK DET

SD 1

AHU-81.91

TXIO- 00004 TXM1.16D 4

Module: Rail:6 / 1

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

P X C M p

N D T

R E S O U R C E S J O B S C M D T P X C M P D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

TXIO - 0000X TXS1.12F4

POWER SUPPLY 24 Volt 4A

Module: Rail:1 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00005 TXM1.8X 5

V

V

V

V

V

V

V

SACRAT

0.5.1

LAI VALUE CURRENT

RET AIR TEMP

TTE 7

AHU-81.91

SAC1FP

0.5.2

LAI VALUE CURRENT

FILTER PRESSURE

DPTE 1

AHU-81.91

V

CU4FP

0.5.4

LAI VALUE CURRENT

FILTER PRESSURE

AHU-81.91

SAC2FP

0.5.3

LAI VALUE CURRENT

FILTER PRESSURE

DPTE 2

AHU-81.91 SACSAT

0.5.7

LAI VALUE THERMISTOR

SUP AIR TEMP

TTE 4

AHU-81.91

SACRMH

0.5.5

LAI VALUE CURRENT

CAB ROOM HUMI

HTE 1

AHU-81.91

CU5FP

0.5.6

LAI VALUE CURRENT

FILTER PRESSURE

AHU-81.91

SAC2SAT

0.5.8

LAI VALUE RTD

SUP AIR TEMP

TTE 5

AHU-81.91

Module: Rail:2 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00006 TXM1.8X 6

V

V

V

V

V

V

V

EF2ST

0.6.1

LAI VALUE RTD

SPACE TEMP

AHU-81.91

SAC1SAT

0.6.2

LAI VALUE RTD

SUP AIR TEMP

TTE 3

AHU-81.91

V

SAC2MAT

0.6.4

LAI VALUE RTD

MIX AIR TEMP

TTE 6

AHU-81.91

FPRMT

0.6.3

LAI VALUE RTD

FIRE PUMP RM TMP

AHU-81.91 CU4CT

0.6.7

LAI VALUE RTD

COIL TEMP

AHU-81.91

SAC1MAT

0.6.5

LAI VALUE RTD

MIX AIR TEMP

TTE 2

AHU-81.91

CU5CT

0.6.6

LAI VALUE RTD

COIL TEMP

AHU-81.91

SAC1AC1H

0.6.8

LAI VALUE VOLTAGE

SAC1 AC1 HIGH

AHU-81.91

Module: Rail:3 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00007 TXM1.8X 7

V

V

V

V

V

V

V

SAC1AC1L

0.7.1

LAI VALUE VOLTAGE

SAC1 AC1 LOW

AHU-81.91

SAC1AC2H

0.7.2

LAI VALUE VOLTAGE

SAC1 AC2 HIGH

AHU-81.91

V

SAC2AC1H

0.7.4

LAI VALUE VOLTAGE

SAC2 AC1 HIGH

AHU-81.91

SAC1AC2L

0.7.3

LAI VALUE VOLTAGE

SAC1 AC2 LOW

AHU-81.91 SAC2AC2L

0.7.7

LAI VALUE VOLTAGE

SAC2 AC2 LOW

AHU-81.91

SAC2AC1L

0.7.5

LAI VALUE VOLTAGE

SAC2 AC1 LOW

AHU-81.91

SAC2AC2H

0.7.6

LAI VALUE VOLTAGE

SAC2 AC2 HIGH

AHU-81.91

SACRMT

0.7.8

LAI VALUE RTD

CAB ROOM TEMP

TTE 8

AHU-81.91

Module: Rail:4 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00008 TXM1.8X-ML 8

V

V

V

V

V

V

V

SACRSP

0.8.1

LAI VALUE RTD

TOWER SETPT

AHU-81.91

SACOAD

0.8.2

LAO VALUE VOLTAGE

OA DAMPER

AE 3

AHU-81.91

V

CU4FB

0.8.4

LAO VALUE VOLTAGE

FACE BYPASSDMP

AHU-81.91

SACRAD

0.8.3

LAO VALUE VOLTAGE

RA DAMPER

AE 4

AHU-81.91 SAC1RAD

0.8.7

LAO VALUE VOLTAGE

RA DAMPER

AE 1

AHU-81.91

CU5FB

0.8.5

LAO VALUE VOLTAGE

FACE BYPASSDMP

AHU-81.91

SACOAT

0.8.6

LAI VALUE RTD

OUTSIDE AIR TMP

TTE 1

AHU-81.91

SAC2RAD

0.8.8

LAO VALUE VOLTAGE

RA DAMPER

AE 2

AHU-81.91

Module: Rail:5 / 2

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

P X C M p

N D T

R E S O U R C E S J O B S C M D T P X C M P D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00009 TXM1.8X 9

V

V

V

V

V

V

V

CU8.CMP1.PRS

0.9.1

LAI VALUE CURRENT

REF PRESSURE

PTE 1

AHU-81.91

CU8.CMP2.PRS

0.9.2

LAI VALUE CURRENT

REF PRESSURE

PTE 2

AHU-81.91

V

CU9.CMP2.PRS

0.9.4

LAI VALUE CURRENT

REF PRESSURE

PTE 4

AHU-81.91

CU9.CMP1.PRS

0.9.3

LAI VALUE CURRENT

REF PRESSURE

PTE 3

AHU-81.91

0.9.7 X

0.9.5 X

0.9.6 X

0.9.8 X

Module: Rail:6 / 2

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

AHU-81.91 PANEL

C:\JOBS\C4431\MDT\AHU-81.91A.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

120 VAC DEDICATED POWER CIRCUIT PROVIDED BY ELEC IS EXISTING.

RE-USE EXISTING PANELS AND CONDUIT WHEN POSSIBLE.2

AHU CONTROL PANEL1

006 LOCATE PANEL AS SHOWN ON SHEET M.5

SERVES ANIMAL PROCESSING AHU'S

NOT TO SCALE

PNL 1-

1 1/4" x 3" NIPPLE TYP 1 1/4" x 3" NIPPLE TYP

1"

SB 1-

PXA ENC34

3/4" FOR 120VAC

3/4" FOR 120VAC

FOR CONTROLS

3/4" - 1" EMT TYP

6"x6"x48" WIRE TROUGH

XFMR 1

100 VA

6' AFF

PXCM 1-

TXIO 1.1-

TXIO 1-

TXIO 2-

TXIO 3-

PSM 1-

AK 1-

TXIO 1.2-

TXIO 4-

T 1 (25)-

MC 1 (2)-

EB 1-

8 7 6 5 4 3 2 1 C H

TERMINAL BLOCKS

DIAGRAMS ARE GRAPHICAL AND MAY CHANGE DUE TO SITE CONDITIONS.

CIRCUIT N-24

INSTALLATION NOTES:

FROM EXISTING NODE 50

TXIO 5-

TXIO 6-

TXIO 7-

TXIO 8-

#1

#2

#3

#4

#5

#6

#7

#8

PSM 2-

REUSE EXISTING POWER FEED.

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

A H U

E X I S T I N G

M B C

C J O B S C M D T M B C D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

20B20A

19A

18A

19B

18B

17A

16A

15A

14A

13A

12A

11A

17B

16B

15B

14B

13B

12B

11B

10A

9A

8A

7A

6A

5A

4A

10B

9B

8B

7B

6B

5B

4B

3A

2A

1A

3B

2B

1B

POWER MODULE

545 714

OPEN PROCESSOR

RS485 / 72 MB

562-001

MBC 002

X

SAC2FAN

SAC 2 ENABLE

0.2.0.2.1

COM (PT1)

NC (PT1)

NO (PT1)

0.2.0.2.2

COM (PT2)

NC (PT2)

NO (PT2)

0022q250M

X

SAC2AC1

SAC2 AC1

0.2.0.4.1

COM (PT1)

NC (PT1)

NO (PT1) SAC2AC2

SAC2 AC2

0.2.0.4.2

COM (PT2)

NC (PT2)

NO (PT2)

0042q250M

X

SAC2HEAT1

SAC2 HEAT1

0.2.0.6.1

COM (PT1)

NC (PT1)

NO (PT1) SAC2HEAT2

SAC2 HEAT2

0.2.0.6.2

COM (PT2)

NC (PT2)

NO (PT2)

0062q250M

X

SAC1FAN

SAC 1 ENABLE

0.2.0.8.1

COM (PT1)

NC (PT1)

NO (PT1)

0.2.0.8.2

COM (PT2)

NC (PT2)

NO (PT2)

0082q250M

X

SAC1AC1

SAC1 AC1

0.2.0.10.1

COM (PT1)

NC (PT1)

NO (PT1) SAC1AC2

SAC1 AC2

0.2.0.10.2

COM (PT2)

NC (PT2)

NO (PT2)

0102q250M

X

SAC1HEAT1

SAC1 HEAT1

0.2.0.12.1

COM (PT1)

NC (PT1)

NO (PT1) SAC1HEAT2

SAC1 HEAT2

0.2.0.12.2

COM (PT2)

NC (PT2)

NO (PT2)

0122q250M

X

EF2E

EX FAN 2 ENABLE

0.2.0.14.1

COM (PT1)

NC (PT1)

NO (PT1) SF1

STAIRWELL FAN

0.2.0.14.2

COM (PT2)

NC (PT2)

NO (PT2)

0142q250M

X

EX7ENA

EXFAN7 ENABLE

0.2.0.16.1

COM (PT1)

NC (PT1)

NO (PT1) EX7HI

EXFAN7 HI LO

0.2.0.16.2

COM (PT2)

NC (PT2)

NO (PT2)

0162q250M

X

SVF1

SVF1 EXH VENT

0.2.0.18.1

COM (PT1)

NC (PT1)

NO (PT1) SVF2

SVF2 EXH VENT

0.2.0.18.2

COM (PT2)

NC (PT2)

NO (PT2)

0182q250M

X

SACHUME

HUMIDIFER

0.2.0.20.1

COM (PT1)

NC (PT1)

NO (PT1)

0.2.0.20.2

COM (PT2)

NC (PT2)

NO (PT2)

0202q250M

8 SAC2FAN SAC 2 ENABLE0.2.0.26.1

B (PT1)

A (PT1)

SAC1FAN SAC 1 ENABLE0.2.0.26.2

B (PT2)

A (PT2) 0.2.0.26.3

B (PT3)

A (PT3)

0.2.0.26.4

B (PT4)

A (PT4)

0264d20

8 0.2.0.28.1

B (PT1)

A (PT1)

SAC4PRF SAC4 FAN PROOF0.2.0.28.2

B (PT2)

A (PT2) SAC3PRF SAC3 FAN PROOF0.2.0.28.3

B (PT3)

A (PT3)

SVF1 SVF1 EXH VENT0.2.0.28.4

B (PT4)

A (PT4)

0284d20

8 0.2.0.30.1

B (PT1)

A (PT1)

SVF2 SVF2 EXH VENT0.2.0.30.2

B (PT2)

A (PT2) SF1 STAIRWELL FAN0.2.0.30.3

B (PT3)

A (PT3)

0.2.0.30.4

B (PT4)

A (PT4)

0304d20

8 EF2E EX FAN 2 ENABLE0.2.0.32.1

B (PT1)

A (PT1)

EF4 EX FAN 4 PROOF0.2.0.32.2

B (PT2)

A (PT2) FPMP FIRE PMP PROOF0.2.0.32.3

B (PT3)

A (PT3)

FAS2 FIRE ALARM0.2.0.32.4

B (PT4)

A (PT4)

0324d20

8 EX7ENA EXFAN7 ENABLE0.2.0.34.1

B (PT1)

A (PT1)

CU4PRF CU4 FAN PROOF0.2.0.34.2

B (PT2)

A (PT2) CU5PRF CU5 FAN PROOF0.2.0.34.3

B (PT3)

A (PT3)

0.2.0.34.4

B (PT4)

A (PT4)

0344d20

8 SACRAT

RET AIR TEMP

0.2.0.1.2

SIG (PT2)

COM (PT2)

SACSAT

SUP AIR TEMP

0.2.0.1.1

SIG (PT1)

COM (PT1)

0012n100k

8 SAC2SAT

SUP AIR TEMP

0.2.0.3.2

SIG (PT2)

COM (PT2)

0.2.0.3.1

SIG (PT1)

COM (PT1)

0032n100k

8 SAC1SAT

SUP AIR TEMP

0.2.0.5.2

SIG (PT2)

COM (PT2)

EF2ST

SPACE TEMP

0.2.0.5.1

SIG (PT1)

COM (PT1)

0052n100k

0.2.0.7.2

SIG (PT2)

COM (PT2)

FPRMT

FIRE PUMP RM TMP

0.2.0.7.1

SIG (PT1)

COM (PT1)

0072n100k

8 SAC1MAT

MIX AIR TEMP

0.2.0.9.2

SIG (PT2)

COM (PT2)

SAC2MAT

MIX AIR TEMP

0.2.0.9.1

SIG (PT1)

COM (PT1)

0092n100k

8 CU4CT

COIL TEMP

0.2.0.11.2

SIG (PT2)

COM (PT2)

CU5CT

COIL TEMP

0.2.0.11.1

SIG (PT1)

COM (PT1)

0112n100k

8 SAC1FP

FILTER PRESSURE

0.2.0.13.1

26V (PT1)

SIG (PT1)

SAC2FP

FILTER PRESSURE

0.2.0.13.2

26V (PT2)

SIG (PT2)

0132i420

8 CU4FP

FILTER PRESSURE

0.2.0.15.1

26V (PT1)

SIG (PT1)

SACRMH

CAB ROOM HUMI

0.2.0.15.2

26V (PT2)

SIG (PT2)

0152i420

0.2.0.17.1

26V (PT1)

SIG (PT1)

CU5FP

FILTER PRESSURE

0.2.0.17.2

26V (PT2)

SIG (PT2)

0172i420

8 SAC1AC1H

SAC1 AC1 HIGH

0.2.0.19.1

SIG (PT1)

COM (PT1)

24V (PT1) SAC1AC1L

SAC1 AC1 LOW

0.2.0.19.2

SIG (PT2)

COM (PT2)

24V (PT2)

0192u10

8 SAC1AC2H

SAC1 AC2 HIGH

0.2.0.21.1

SIG (PT1)

COM (PT1)

24V (PT1) SAC1AC2L

SAC1 AC2 LOW

0.2.0.21.2

SIG (PT2)

COM (PT2)

24V (PT2)

0212u10

8 SAC2AC1H

SAC2 AC1 HIGH

0.2.0.23.1

SIG (PT1)

COM (PT1)

24V (PT1) SAC2AC1L

SAC2 AC1 LOW

0.2.0.23.2

SIG (PT2)

COM (PT2)

24V (PT2)

0232u10

8 SAC2AC2H

SAC2 AC2 HIGH

0.2.0.25.1

SIG (PT1)

COM (PT1)

24V (PT1) SAC2AC2L

SAC2 AC2 LOW

0.2.0.25.2

SIG (PT2)

COM (PT2)

24V (PT2)

0252u10

8 SACRAD

RA DAMPER

0.2.0.29.2

+ (PT2)

- (PT2)

24V (PT2)

SACOAD

OA DAMPER

0.2.0.29.1

+ (PT1)

- (PT1)

24V (PT1)

0292y10sm

8 CU5FB

FACE BYPASSDMP

0.2.0.31.2

+ (PT2)

- (PT2)

24V (PT2)

CU4FB

FACE BYPASSDMP

0.2.0.31.1

+ (PT1)

- (PT1)

24V (PT1)

0312y10sm

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

AHU-81.91

N:\DT Resources\JOBS\C4431\MDT\AHU-81.91-K00.dwg

DWJ DWJ JLJ 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas ALL RIGHTS RESERVED1994-15

REVISION HISTORY

Control Qty Product Number Manufacturer Document Description

Device Number

Field Mounted Devices

AE 1-3 3 GCA161.1U SIEMENS 154001 MOD(V) SR,24V, MED.

AE 4 1 GCA161.1P SIEMENS 154001 MOD(V) SR,24V, MED. PLNM

AK 1 1 TXA1.K24 SIEMENS 149476 ADDRESS KEY 1-24

CS 1-2 2 H609 VERIS H609 Current Switch,Split-Core,Adj,N.O.,120V

DPTE 1-2 2 PXULX05S VERIS INDU px_d07101 PXULX05S,Pressure,Dry,Universal,LCD

EB 1 1 6G38-E-DIN KELE INC 6G38 3/8" END SECTION - DIN MOUNT

HTE 1 1 QFA3001.WU SIEMENS 149479 RM RH 2% 3-WIRE! ORDER QFA3001.WU-2-WIRE

MC 1 2 MSK KELE INC 6G38 END BRACKET FOR 6G38-TSKK-DIN 2 REQUIRED

PNL 1 1 PXA-ENC34 SIEMENS 149475 ENCLOSURE ASSY 34

PSM 1-2 2 TXS1.12F4 SIEMENS 149476 24VDC SUPPLY 1200MA, 4 A FUSE

PTE 1-4 4 209-500P-G2M11-A1SETRA 209Series SETRA 0-5--# TRANSMITTER

PXCM 1 1 PXC100-PE96.A SIEMENS 149478 PXC MOD, P2, TX-I/O, 96 NODE, APOGEE

RE 1-2 2 V645 VERIS V645 V645,24VAC/DC/120VAC,LED,SPDT RELAY

SB 1 1 PXA-SB115V192VA SIEMENS 553131 SERVICE BOX 115V, 24VAC, 192VA

SPP 1-4 4 269-062 SIEMENS 269-062 PR269 ACCESSORY, SENSING TUBE

T 1 25 6G38-TSKK-DIN KELE INC 6G38 DIN RAIL MOUNTED TERMINAL BLOCK

TTE 1-3 3 544-342-24 SIEMENS 149261 FLEX AVER SNSR, PT 1K OHM, 24FT PROBE

TTE 4 1 544-339-18 SIEMENS 149261 DCT PT SNSR, PT 1K OHM, (375), 18" PROBE

TTE 5-7 3 544-342-24 SIEMENS 149261 FLEX AVER SNSR, PT 1K OHM, 24FT PROBE

TTE 8 1 540-760A N/A 149312 SENSING ONLY. NO DISPLAY, BEIGE

TXIO 1-3 3 TXM1.6R-M SIEMENS 149476 6 RELAY OUTPUT MODULE W/OVD

TXIO 4 1 TXM1.16D SIEMENS 149476 16 DIGITAL INPUT MODULE

TXIO 5-7 3 TXM1.8X SIEMENS 149476 8 UNIV I/O MODULE W/ 4-20MA

TXIO 8 1 TXM1.8X-ML SIEMENS 149476 8 UNIV I/O W/ 4-20MA, OVD&LCD

TXIO 9 1 PXX-485.3 SIEMENS 149478 PXC MOD EXPANSION MODULE, 3 RS-485

TXIO 10 1 TXS1.EF4 SIEMENS 149476 BUS CONNECTION MODULE, 4A FUSE

Control Qty Product Number Manufacturer Document Description

Device Number

XFMR 1 1 X100CAA VERIS x_d XFrmr,100VA,120-24VAC,CB,Ft & Single Hub

The constant volume air handling unit consists of a mixed air section with outdoor air and return air dampers, pre-filter, DX cooling coil, gas heating section and supply fan. The unit is DDC controlled using electric actuation.

The air handling unit is scheduled for automatic operation on a time of day basis for Occupied and Unoccupied modes.

Within the Occupied mode, the system can enter the Warm-Up mode when the space temperature is below set point or the Cool-Down mode when the space temperature is above set point. The system stays in the Warm-Up or Cool-Down mode until the mode set point is satisfied. Within the Unoccupied mode, Night Heating is available when the space temperature drops below 65 degrees F (18 degrees C) and Night Cooling is available when the space temperature rises above 85 degrees F (29 degrees C). The latest start time is the scheduled occupancy for the space.

The air handling unit operates in Warm-Up, Cool-Down, Occupied, Unoccupied, Night Heating, Night Cooling and Safety modes as follows (All suggested set points and settings are adjustable.):

Occupied

The supply air temperature set point is reset based on the room temperature set point.

The fan starts or continues to run and the unit is controlled as follows:

When the outside air dry bulb temperature is below the economizer changeover value, the mixing dampers modulate with the gas heating and DX cooling staging to maintain supply air temperature set point with a low limit of 48 degrees F

(9 degrees C) at the mixed air sensor. The mixing dampers ramp open slowly to minimize overshooting.

When the outside air dry bulb temperature is above the economizer changeover value, the mixing dampers are placed in the minimum outdoor air position. The gas heating and DX cooling stage in sequence without overlap to maintain the supply air temperature set point.

Return air humidity overrides control of DX cooling to maintain 55% relative humidity.

Unoccupied

The supply fan is off, the DX cooling is off, gas heating is off and mixing dampers close to the outdoor air.

Night Heating

The supply fan starts with the gas heating staging to maintain the supply air temperature set point for a minimum space temperature of 65 degrees F (18 degrees C). The DX cooling remains off and the mixing dampers are closed to the outdoor air.

Night Cooling

The supply fan starts with the DX cooling staging and mixing dampers modulating in sequence without overlap to maintain the supply air temperature set point for a maximum space temperature of 85 degrees F (29 degrees C). When the outside air dry bulb temperature is above the economizer changeover value, the mixing dampers are closed. The gas heating remains off.

Safety

Smoke detectors in the supply and return air streams de-energize the supply fan upon activation. The DX cooling and gas heating are off. All dampers position to their normal position after the fan is de-energized.

A current switch is installed in the supply fan starter. The DDC system uses this switch to confirm the fan is in the desired state (i.e. on or off) and generates an alarm if status deviates from DDC start/stop control.

CC

SA

OA

RA

C

H

PREFILTER

SA

MTD 2/3RDS DOWN

MAIN SUPPLY DUCT

RELAY MOUNTED IN

MOTOR STARTER

NOTE: H.O.A. SWITCH AND CONTROL

TRANSFORMER FURNISHED

WITH MOTOR STARTER AND

SUPPLIED BY OTHERS.

OL'S

L3L2L1

M

S T S P

S T A T U S

SMOKE

DETLTDE-1DPS-1

CU-1

VERIFY WIRING FOR

LIQ LINE SOLENOID VALVES

SMOKE DETECTOR

FURNISHED BY

OTHERS

OTHERS

SMOKE DETECTOR

FURNISHED BY

T

0/100PSI

AH1RPA

0002:0.4.2È

GPM

AHUHWF

0002:0.4.6È

AH1DX1

0002:0.1.2È

RE-1

C 13 14

AHU-1 WIRING DIAGRAM2

009 ( TYPICAL OF 1 )

CSRE 1

24 VAC

AH1FAN (ON/OFF)

0002:0.1.3

È AH1FAN (PROOF)

0002:0.3.1È

DPTE 4

0/10 in H2O

AHU1 AFMS2

0002:0.4.4 H

È

S

M

F

AH

-+ DPTE 5

0/10 in H2O

AH1DSP

0002:0.4.5

H

È

V 1

RANGEVOLTS

AH1HWV

0002:0.8.3

NC C

NO

È

HWS

HWR

POWERS

DPTE 2

1.0 in H2O

AH1F2P

0002:0.4.2

H L

È

AH1RSM

0002:0.3.13È

TTE 1

-40/150 DEG F

AH1RAT

0002:0.5.8

È

NC

S Q B

AE 1

0/10 VDC

AH1OAD

0002:0.8.1

È

POWERS

DPS 1

4 in H2O

AH1HS

0002:0.3.16

L H

È

DPTE 3

0/10 in H2O

AHU1 AFMS1

0002:0.4.3 H

È

S

M

F

AH

LTDE 1

38 deg F

AH1LTD

0002:0.3.15È

TTE 2

-40/240 deg F

AH1MAT

0002:0.7.5

È

AH1DSM

0002:0.3.14È

TTE 3

40/150 deg F

AH1SAT

0002:0.6.1

È

POWERS

DPTE 1

1.0 in H2O

AH1F1P

0002:0.4.1

H L

È

AHU-1 FLOW DIAGRAM1

009 TYPICAL OF 1

AIR HANDLING UNIT NO.1:

THE UNIT WILL BE STARTED AND STOPPED IN ACCORDANCE WITH A PREDEFINED

TIME SCHEDULE. WHEN THE UNIT STARTS THE OSA DAMPER WILL OPEN TO ITS

MINIMUM POSITION SETTING. THE CONTROLLER WILL MODULATE THE SUPPLY

FAN INLET VANE DAMPER TO MAINTAIN SUPPLY DUCT STATIC PRESSURE

SETPOINT. THE CONTROLLER WILL CYCLE THE DX COOLING COMPRESSOR AS

REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT OF 55 DEG F

(ADJUSTABLE). THE CONTROLLER WILL OPERATE THE UNIT IN A HEATING MODE

WHEN THE RETURN AIR TEMPERATURE DROPS BELOW 60 DEG (ADJUSTABLE). IN

THE HEATING MODE THE OSA DAMPER WILL CLOSE, HOT WATER FLOW CONTROL

VALVE WILL MODULATE TO FULL OPEN POSITION, AND THE INLET GUIDE VANES

WILL BE REFRENCED TO 100 PERCENT. THE ASSOCIATED VAV BOX PRIMARY AIR

DAMPERS WILL BE FULLY OPEN AND THE ZONE SPACE SENSORS WILL OPEN HOT

WATER FLOW CONTROL VALVES TO MAINTAIN 68 DEGREES (ADJUSTABLE)

SETPOINT. WHEN THE RETURN AIR RISES TO 65 DEGREES F (ADJUSTABLE),

THE AHU WILL RETURN TO THE COOLING MODE. DUCT MOUNTED SMOKE DETECTOR

STATIC PRESSURE HI LIMIT OR MIXED AIR LOW TEMP THERMOSTAT IF ACTIVATED

WILL SHUT DOWN THE UNIT.

SEQUENCE OF OPERATION:

AUTO

OFF

HAND

CHECKED BYDRAFTER LAST EDIT DATEINITIAL RELEASE

c COPYRIGHT

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

AHU-1

C:\JOBS\C4431\MDT\AHU-1.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

FREQUENCY

DRIVE

52.03

POWER ALARM

VARIABLE

AH1FAN (ON/OFF)

0002:0.1.3È

AH1FAN (PROOF)

0002:0.3.1È

AH1IV

0002:0.8.2È

460 V

3 PH

10 HP

RE-2

C 13 14

AH1DX2

0002:0.1.1È

BY DIVISION OTHERS.

SMOKE DETECTOR PROVIDED, MOUNTED, AND WIRED

REUSE EXISTING CONDUIT WHERE POSSIBLE.

REUSE CONDUIT ON THE EXTERIOR OF THE WALL FOR

COMPONENT PANEL.

REPLACE REMOVED CONTROLS WITH NEW DEVICES.

AHUS TO BE REPLACED WITH NEW AHUS.

CONTROL TRANSFORMERS AND RELAYS MOUNTED IN

WIRE PATH TO CONDENSING UNITS.

6 VFD IS EXISTING AND TO BE REUSED.

0002 PXCM1 1

REF# FIELD PANEL NAME FIELD PANEL NODE NAME

7 AI FLOW MEASURING STATION EXISTING AND TO BE REUSED.

INSTALLATION NOTES:

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

A H U

L A Y O U T

C J O B S C M D T P X C M D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

PXCM - 00000 PXC100-PE96.A

PXC MODULAR

Module: Rail:1 / 1

TXIO - 0000X TXS1.12F4

POWER SUPPLY 24 Volt 4A

Module: Rail:2 / 1

(3)

(2)

(1)

32(6)

(5)

(4) 20

AH1DX2

0.1.1

LDO ON/OFF

DX COIL 2

AHU-1

AH1DX1

0.1.2

LDO ON/OFF

DX COIL 1

AHU-1

AH1FAN

0.1.3

L2SL ON/OFF

AHU1 FAN

CSRE 1

AHU-1

BOILER

0.1.6

LDO ON/OFF

BOILER ENABLE

AHU-1

HWP1E

0.1.5

L2SL ON/OFF

HOT WTR PMP

AHU-1

HWP2E

0.1.4

L2SL ON/OFF

HOT WTR PMP

AHU-1

TXIO- 00001 TXM1.6R-M 1

Module: Rail:3 / 1

(3)

(2)

(1)

32(6)

(5)

(4) 20

EF5FAN

0.2.1

L2SL ON/OFF

EXHAUST FAN 5

AHU-1

EF6FAN

0.2.2

L2SL ON/OFF

EXHAUST FAN 6

AHU-1

CR1ENA

0.2.3

L2SL ON/OFF

CRU 1

AHU-1 0.2.6

LDO

CR3ENA

0.2.5

L2SL ON/OFF

CRU 3

AHU-1

CR2ENA

0.2.4

L2SL ON/OFF

CRU 2

AHU-1

TXIO- 00002 TXM1.6R-M 2

Module: Rail:4 / 1

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

P X C M p

C J O B S C M D T P X C M P D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

(4)

(3)

(2)

(1)

(12)

(11)

(10)

(9)

(8)

(7)

(5)

(6)

(16)

(15)

(13)

(14)

HWP2E

0.3.8

L2SL PROOF

HOT WTR PMP

AHU-1

CRU3ALM

0.3.7

LDI STATUS

LIBERT 3 ALARM

AHU-1

CRU2ALM

0.3.6

LDI STATUS

LIBERT 2 ALARM

AHU-1

CRU1ALM

0.3.5

LDI STATUS

LIBERT 1 ALARM

AHU-1

AH1FAN

0.3.1

L2SL PROOF

AHU1 FAN

AHU-1

CR1ENA

0.3.2

L2SL PROOF

CRU 1

AHU-1

CR2ENA

0.3.3

L2SL PROOF

CRU 2

AHU-1

CR3ENA

0.3.4

L2SL PROOF

CRU 3

AHU-1

AH1HS

0.3.16

LDI STATUS

HI STATIC

AHU-1

AH1DSM

0.3.14

LDI STATUS

SUP SMK DET

AHU-1

AH1RSM

0.3.13

LDI STATUS

RET SMK DET

AHU-1

HWP1E

0.3.9

L2SL PROOF

HOT WTR PMP

AHU-1

EF5FAN

0.3.10

L2SL PROOF

EXHAUST FAN 5

AHU-1

EF6FAN

0.3.11

L2SL PROOF

EXHAUST FAN 6

AHU-1

FAS1

0.3.12

LDI STATUS

FIRE ALARM

AHU-1

AH1LTD

0.3.15

LDI STATUS

LOW LIMIT DET

AHU-1

TXIO- 00003 TXM1.16D 3

Module: Rail:5 / 1

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

P X C M p

C J O B S C M D T P X C M P D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

TXIO - 0000X TXS1.12F4

POWER SUPPLY 24 Volt 4A

Module: Rail:1 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00004 TXM1.8X 4

V

V

V

V

V

V

V

AH1F1P

0.4.1

LAI VALUE CURRENT

FILTER 1 PRESSUR

DPTE 1

AHU-1

AH1RPA

0.4.2

LAI VALUE CURRENT

REF PRESSUR

DPTE 2

AHU-1

V

AHU1 AFMS2

0.4.4

LAI VALUE CURRENT

AIR FLO ST

DPTE 4

AHU-1

AHU1 AFMS1

0.4.3

LAI VALUE CURRENT

AIR FLO ST

DPTE 3

AHU-1 CRU1RH

0.4.7

LAI VALUE CURRENT

RETURN HUMIDITY

AHU-1

AH1DSP

0.4.5

LAI VALUE CURRENT

DUCT STATIC

DPTE 5

AHU-1

AHUHWF

0.4.6

LAI VALUE CURRENT

HOT WATER FLOW

FM 1

AHU-1

CRU2RH

0.4.8

LAI VALUE CURRENT

RETURN HUMIDITY

AHU-1

Module: Rail:2 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00005 TXM1.8X 5

V

V

V

V

V

V

V

CRU3RH

0.5.1

LAI VALUE CURRENT

RETURN HUMIDITY

AHU-1

CRU1FP

0.5.2

LAI VALUE CURRENT

FILTER PRESSUR

AHU-1

V

CRU3FP

0.5.4

LAI VALUE CURRENT

FILTER PRESSUR

AHU-1

CRU2FP

0.5.3

LAI VALUE CURRENT

FILTER PRESSUR

AHU-1 HWP2F

0.5.7

LAI VALUE CURRENT

HOT WATER FLOW

AHU-1

HWRF

0.5.5

LAI VALUE CURRENT

HOT WATER FLOW

AHU-1

HWP1F

0.5.6

LAI VALUE CURRENT

HOT WATER FLOW

AHU-1

AH1RAT

0.5.8

LAI VALUE THERMISTOR

RET AIR TEMP

TTE 1

AHU-1

Module: Rail:3 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00006 TXM1.8X 6

V

V

V

V

V

V

V

AH1SAT

0.6.1

LAI VALUE THERMISTOR

SUP AIR TEMP

TTE 3

AHU-1

CRU1RT

0.6.2

LAI VALUE THERMISTOR

RET AIR TEMP

AHU-1

V

CRU3RT

0.6.4

LAI VALUE THERMISTOR

RET AIR TEMP

AHU-1

CRU2RT

0.6.3

LAI VALUE THERMISTOR

RET AIR TEMP

AHU-1 CRU3SAT

0.6.7

LAI VALUE THERMISTOR

SUP AIR TEMP

AHU-1

CRU1SAT

0.6.5

LAI VALUE THERMISTOR

SUP AIR TEMP

AHU-1

CRU2SAT

0.6.6

LAI VALUE THERMISTOR

SUP AIR TEMP

AHU-1

HWST

0.6.8

LAI VALUE THERMISTOR

BLD SUPPLY

AHU-1

Module: Rail:4 / 2

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00007 TXM1.8X 7

V

V

V

V

V

V

V

HWRT

0.7.1

LAI VALUE THERMISTOR

BLD RETURN

AHU-1

HWP1ST

0.7.2

LAI VALUE THERMISTOR

HW PMP1 SUP

AHU-1

V

OATEMP

0.7.4

LAI VALUE THERMISTOR

OUTDOOR AIR

AHU-1

HWP2ST

0.7.3

LAI VALUE THERMISTOR

HW PMP2 SUP

AHU-1

0.7.7 X

AH1MAT

0.7.5

LAI VALUE RTD

MIX AIR TEMP

TTE 2

AHU-1

AH1RPA

0.7.6

LAI VALUE CURRENT

REF 1 PRESSUR

DPTE 1

AHU-1

0.7.8

Module: Rail:5 / 2

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

P X C M p

C J O B S C M D T P X C M P D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

TXIO- 00008 TXM1.8X-ML 8

V

V

V

V

V

V

V

AH1OAD

0.8.1

LAO VALUE VOLTAGE

OA DAMPER

AE 1

AHU-1

AH1IV

0.8.2

LAO VALUE VOLTAGE

INLET VANES

AE 2

AHU-1

V

0.8.4 X

AH1HWV

0.8.3

LAO VALUE VOLTAGE

HOT WTR VLV

V 1

AHU-1

0.8.7 X

0.8.5 X

0.8.6 X

0.8.8

Module: Rail:6 / 2

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

AHU-1 PANEL

C:\JOBS\C4431\MDT\AHU-1A.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

120 VAC DEDICATED POWER CIRCUIT PROVIDED BY ELEC IS EXISTING.

RE-USE EXISTING PANELS AND CONDUIT WHEN POSSIBLE.2

AHU CONTROL PANEL1

014 LOCATE PANEL AS SHOWN ON SHEET M.5

SERVES ANIMAL PROCESSING AHU'S

NOT TO SCALE

PNL 1-

1 1/4" x 3" NIPPLE TYP 1 1/4" x 3" NIPPLE TYP

1"

SB 1-

PXA ENC34

3/4" FOR 120VAC

3/4" FOR 120VAC

FOR CONTROLS

3/4" - 1" EMT TYP

6"x6"x48" WIRE TROUGH

XFMR 1

100 VA

6' AFF

PXCM 1-

TXIO 1.1-

TXIO 1-

TXIO 2-

TXIO 3-

PSM 1-

AK 1-

TXIO 1.2-

TXIO 4-

T 1 (25)-

MC 1 (2)-

EB 1-

8 7 6 5 4 3 2 1 C H

TERMINAL BLOCKS

DIAGRAMS ARE GRAPHICAL AND MAY CHANGE DUE TO SITE CONDITIONS.

CIRCUIT N-24

INSTALLATION NOTES:

FROM EXISTING NODE 50

TXIO 5-

TXIO 6-

TXIO 7-

TXIO 8-

#1

#2

#3

#4

#5

#6

#7

#8

PSM 2-

REUSE EXISTING POWER FEED.

G I N E E R

D R A F T E R

C H E C K E D

B Y

I N I T I A L

R E L E A S E

L A S T

E D I T

D A T E c C O P Y R I G H T

F A A

C o n t r o l

T o w e r

S y s

U p g r a d e

L i t t l e

R o c k

A R

C

A H U

E X I S T I N G

M B C

C J O B S C M D T A H U B D W G

P o w e r s o f

A r k a n s a s

W W W P O W E R S A R C O M

C o n t r o l s

D i v s i o n

N o r t h s h o r e

D r i v e

N

L i t t l e

R o c k

U S A

P H O N E

F A X

D W J

D W J

J L J

R E V I S I O N

H I S T O R Y

Powers of Arkansas All Rights Reserved

20B20A

19A

18A

19B

18B

17A

16A

15A

14A

13A

12A

11A

17B

16B

15B

14B

13B

12B

11B

10A

9A

8A

7A

6A

5A

4A

10B

9B

8B

7B

6B

5B

4B

3A

2A

1A

3B

2B

1B

POWER MODULE

545 714

OPEN PROCESSOR

RS485 / 72 MB

562-001

MBC 001

8 AH1SAT

SUP AIR TEMP

0.1.0.1.2

SIG (PT2)

COM (PT2)

AH1RAT

RET AIR TEMP

0.1.0.1.1

SIG (PT1)

COM (PT1)

0012n100k

8 CRU1RT

RET AIR TEMP

0.1.0.3.2

SIG (PT2)

COM (PT2)

0.1.0.3.1

SIG (PT1)

COM (PT1)

0032n100k

8 CRU3RT

RET AIR TEMP

0.1.0.5.2

SIG (PT2)

COM (PT2)

CRU2RT

RET AIR TEMP

0.1.0.5.1

SIG (PT1)

COM (PT1)

0052n100k

8 CRU2SAT

SUP AIR TEMP

0.1.0.7.2

SIG (PT2)

COM (PT2)

CRU1SAT

SUP AIR TEMP

0.1.0.7.1

SIG (PT1)

COM (PT1)

0072n100k

8 HWST

BLD SUPPLY

0.1.0.9.2

SIG (PT2)

COM (PT2)

CRU3SAT

SUP AIR TEMP

0.1.0.9.1

SIG (PT1)

COM (PT1)

0092n100k

8 HWP1ST

HW PMP1 SUP

0.1.0.11.2

SIG (PT2)

COM (PT2)

HWRT

BLD RETURN

0.1.0.11.1

SIG (PT1)

COM (PT1)

0112n100k

X

AH1DX2

DX COIL 2

0.1.0.2.1

COM (PT1)

NC (PT1)

NO (PT1) AH1DX1

DX COIL 1

0.1.0.2.2

COM (PT2)

NC (PT2)

NO (PT2)

0022q250M

X

AH1FAN

AHU1 FAN

0.1.0.4.1

COM (PT1)

NC (PT1)

NO (PT1)

0.1.0.4.2

COM (PT2)

NC (PT2)

NO (PT2)

0042q250M

X

HWP2E

HOT WTR PMP

0.1.0.8.1

COM (PT1)

NC (PT1)

NO (PT1) HWP1E

HOT WTR PMP

0.1.0.8.2

COM (PT2)

NC (PT2)

NO (PT2)

0082q250M

X

BOILER

BOILER ENABLE

0.1.0.10.1

COM (PT1)

NC (PT1)

NO (PT1) EF5FAN

EXHAUST FAN 5

0.1.0.10.2

COM (PT2)

NC (PT2)

NO (PT2)

0102q250M

X

EF6FAN

EXHAUST FAN 6

0.1.0.12.1

COM (PT1)

NC (PT1)

NO (PT1) CR1ENA

CRU 1

0.1.0.12.2

COM (PT2)

NC (PT2)

NO (PT2)

0122q250M

X

CR2ENA

CRU 2

0.1.0.14.1

COM (PT1)

NC (PT1)

NO (PT1) CR3ENA

CRU 3

0.1.0.14.2

COM (PT2)

NC (PT2)

NO (PT2)

0142q250M

8 AH1F1P

FILTER 1 PRESSUR

0.1.0.15.1

26V (PT1)

SIG (PT1)

AH1F2P

FILTER 2 PRESSUR

0.1.0.15.2

26V (PT2)

SIG (PT2)

0152i420

8 CRU3ALM LIBERT 3 ALARM0.1.0.26.1

B (PT1)

A (PT1)

HWP2E HOT WTR PMP0.1.0.26.2

B (PT2)

A (PT2) HWP1E HOT WTR PMP0.1.0.26.3

B (PT3)

A (PT3)

EF5FAN EXHAUST FAN 50.1.0.26.4

B (PT4)

A (PT4)

0264d20

8 EF6FAN EXHAUST FAN 60.1.0.28.1

B (PT1)

A (PT1)

0.1.0.28.2

B (PT2)

A (PT2) 0.1.0.28.3

B (PT3)

A (PT3)

FAS1 FIRE ALARM0.1.0.28.4

B (PT4)

A (PT4)

0284d20

8 AHU1 AFMS1

AIR FLO ST

0.1.0.18.1

26V (PT1)

SIG (PT1)

AHU1 AFMS2

AIR FLO ST

0.1.0.18.2

26V (PT2)

SIG (PT2)

0182i420

8 0.1.0.20.1

B (PT1)

A (PT1)

AH1FAN AHU1 FAN0.1.0.20.2

B (PT2)

A (PT2) 0.1.0.20.3

B (PT3)

A (PT3)

0.1.0.20.4

B (PT4)

A (PT4)

0204d20

8 CR1ENA CRU 10.1.0.22.1

B (PT1)

A (PT1)

CR2ENA CRU 20.1.0.22.2

B (PT2)

A (PT2) CR3ENA CRU 30.1.0.22.3

B (PT3)

A (PT3)

0.1.0.22.4

B (PT4)

A (PT4)

0224d20

8 0.1.0.24.1

B (PT1)

A (PT1)

0.1.0.24.2

B (PT2)

A (PT2) CRU1ALM LIBERT 1 ALARM0.1.0.24.3

B (PT3)

A (PT3)

CRU2ALM LIBERT 2 ALARM0.1.0.24.4

B (PT4)

A (PT4)

0244d20

0.1.0.35.2

+ (PT2)

- (PT2)

24V (PT2)

AH1HWV

HOT WTR VLV

0.1.0.35.1

+ (PT1)

- (PT1)

24V (PT1)

0352y10sm

8 AH1IV

INLET VANES

0.1.0.33.2

+ (PT2)

- (PT2)

24V (PT2)

AH1OAD

OA DAMPER

0.1.0.33.1

+ (PT1)

- (PT1)

24V (PT1)

0332y10sm

8 OATEMP

OUTDOOR AIR

0.1.0.13.2

SIG (PT2)

COM (PT2)

HWP2ST

HW PMP2 SUP

0.1.0.13.1

SIG (PT1)

COM (PT1)

0132n100k

8 AH1DSP

DUCT STATIC

0.1.0.19.1

26V (PT1)

SIG (PT1)

AHUHWF

HOT WATER FLOW

0.1.0.19.2

26V (PT2)

SIG (PT2)

0192i420

8 CRU1RH

RETURN HUMIDITY

0.1.0.21.1

26V (PT1)

SIG (PT1)

CRU2RH

RETURN HUMIDITY

0.1.0.21.2

26V (PT2)

SIG (PT2)

0212i420

8 CRU3RH

RETURN HUMIDITY

0.1.0.23.1

26V (PT1)

SIG (PT1)

CRU1FP

FILTER PRESSUR

0.1.0.23.2

26V (PT2)

SIG (PT2)

0232i420

8 CRU2FP

FILTER PRESSUR

0.1.0.25.1

26V (PT1)

SIG (PT1)

CRU3FP

FILTER PRESSUR

0.1.0.25.2

26V (PT2)

SIG (PT2)

0252i420

8 HWRF

HOT WATER FLOW

0.1.0.27.1

26V (PT1)

SIG (PT1)

HWP1F

HOT WATER FLOW

0.1.0.27.2

26V (PT2)

SIG (PT2)

0272i420

8 HWP2F

HOT WATER FLOW

0.1.0.29.1

26V (PT1)

SIG (PT1)

0.1.0.29.2

26V (PT2)

SIG (PT2)

0292i420

0.1.0.31.2

SIG (PT2)

COM (PT2)

AH1MAT

MIX AIR TEMP

0.1.0.31.1

SIG (PT1)

COM (PT1)

0312n100k

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

AHU-1

N:\DT Resources\JOBS\C4431\MDT\AHU-1-K00.dwg

DWJ DWJ JLJ 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas ALL RIGHTS RESERVED1994-15

REVISION HISTORY

Control Qty Product Number Manufacturer Document Description

Device Number

Field Mounted Devices

AE 1 1 SQB61.1 SIEMENS N/A RETURN DMPR ACT OBS/ BY GCA151.1U

AK 1 1 TXA1.K24 SIEMENS 149476 ADDRESS KEY 1-24

CSRE 1 1 H735 VERIS 1006cut009 CURRENT SENSOR W/RELAY

DPS 1 1 141-0575 SIEMENS 155 052 AIR FLOW SWITCH.05/12 MAN REST

DPTE 1-6 6 PXULX05S VERIS INDU px_d07101 PXULX05S,Pressure,Dry,Universal,LCD

LTDE 1 1 134-1504 SIEMENS 155 016 T'STAT, LOW TEMP,15/55,MANUAL

MC 1 2 MSK KELE INC 6G38 END BRACKET FOR 6G38-TSKK-DIN 2 REQUIRED

PNL 1 1 PXA-MEC34KIT SIEMENS MEC34KIT MEC LARGE ENCL MIGRATION KIT

PS 1 1 209-500P-G2M11-A1SETRA 209Series SETRA 0-5--# TRANSMITTER

PXCM 1 1 PXC100-PE96.A SIEMENS 149478 PXC MOD, P2, TX-I/O, 96 NODE, APOGEE

RE 1-2 2 V645 VERIS V645 V645,24VAC/DC/120VAC,LED,SPDT RELAY

SB 1 1 PXA-SB115V192VA SIEMENS 553131 SERVICE BOX 115V, 24VAC, 192VA

T 1 25 6G38-TSKK-DIN KELE INC 6G38 DIN RAIL MOUNTED TERMINAL BLOCK

TTE 1-2 2 544-339-18 SIEMENS 149261 DCT PT SNSR, PT 1K OHM, (375), 18" PROBE

TXIO 1-3 3 TXM1.6R-M SIEMENS 149476 6 RELAY OUTPUT MODULE W/OVD

TXIO 4 1 TXM1.16D SIEMENS 149476 16 DIGITAL INPUT MODULE

TXIO 5-7 3 TXM1.8X SIEMENS 149476 8 UNIV I/O MODULE W/ 4-20MA

TXIO 8 1 TXM1.8X-ML SIEMENS 149476 8 UNIV I/O W/ 4-20MA, OVD&LCD

TXIO 9 1 PXX-485.3 SIEMENS 149478 PXC MOD EXPANSION MODULE, 3 RS-485

TXIO 10 1 TXS1.EF4 SIEMENS 149476 BUS CONNECTION MODULE, 4A FUSE

XFMR 1 1 X100CAA VERIS x_d XFrmr,100VA,120-24VAC,CB,Ft & Single Hub

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

CRU45

C:\JOBS\C4431\MDT\CRU45.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

XD

(SEE UNIT WIRING)

ACC-4

VERIFY WIRING FOR LLSV)

RA SA

FAN ENABLE

CONTROL

COMPARTMENT

CRU-4 CRU-5

SARA

VERIFY WIRING FOR LLSV)

ACC-5

(SEE UNIT WIRING)

XD

DAMPER AND

MOTOR FURNISHED

& WIRED WITH UNIT

WIRED TO

UNIT CONTROL

PANEL.

& WIRED WITH UNIT

MOTOR FURNISHED

DAMPER AND

WIRED TO

UNIT CONTROL

PANEL.

SAFTIES

SMOKE

DETECTOR

NOTE: CRU FURNISHED WITH PREWIRE

FACTORY MOUNTED CONTROLS.

DDC STARTS UNIT AND

PROVIDES REMOTE MONITORING

ONLY

ONLY

PROVIDES REMOTE MONITORING

DDC STARTS UNIT AND

FACTORY MOUNTED CONTROLS.

NOTE: CRU FURNISHED WITH PREWIRE

CRU-4,5 ACC-4,5 WIRING1

017 TYPICAL OF 2

CR4ENA

0004:0.0.20È

CR5ENA

0004:0.0.21È

RE-1 (2)

C 13 14

CU4SMK

0004:0.0.14È

TTE 2

-40/240 deg F

CU4SAT

0004:0.0.2

È

POWERS

DPTE 1

SETPTIN WG

CU4FP

0004:0.0.7

H L

È

POWERS

DPS 1

1.5 in H2O

CR4S

0004:0.0.10

L H

È

TTE 1

-40/240 deg F

CU4RAT

0004:0.0.1

È

È

0004:0.0.3

CU4RAH

%RH0/100

1HTE

È

0004:0.0.6

CU5RAH

%RH0/100

2HTE

TTE 3

-40/240 deg F

CU5RAT

0004:0.0.4

È

POWERS

DPS 2

1.5 in H2O

CR5S

0004:0.0.12

L H

È

POWERS

DPTE 2

SETPTIN WG

CU5FP

0004:0.0.8

H L

È

TTE 4

-40/240 deg F

CU5SAT

0004:0.0.5

È

CU5SMK

0004:0.0.15È

NC

NC

PS 1

0/50 PSI

CU4ALM

0004:0.0.11È

T

PT 1-

T

PT 2-

PS 2

0/50 PSI

CU5ALM

0004:0.0.13È

S Q B

AE 1

0-10 VOLTS

D 1

NC

INTERLOCKED WITH

ELEVATOR CONTROLS

�Control �Qty�Product Number �Manufacturer �SD �Document �Description � �Device � � � �Number �Number � �

�Field Mounted Devices �

�DPS 1-2 � 2�141 0518 �LANDIS & GYR �PC5-9 �155 052 �SWITCH,AIR FLOW,1.0/12 WG �

�DPTE 1-2 � 2�C264-2 �SETRA � � �0-2" DIFF PRSS TRANS �

�HTE 1-2 � 2�534 636 �LANDIS & GYR �S600-61 �149 099 �DUCT RH TRANSMITTER +/-2% �

�PS 1-2 � 2�A70AB-1 �PENN � � �PRESS SWITCH �

�RE 1 � 2�V635 �VERIS � � �SOLID STATE RELAY 120/24VAC �

�TTE 1-4 � 4�544 339 �LANDIS & GYR �S600-58 �149 261 �D/PT TEMP SENSOR,RTD,-40/240F �

CRU-4 AND 5

CRU-1,2 AND 3 WILL BE STARTED AND STOPPED BY THE DDC SYSTEM. EACH UNIT

IS SIZED FOR 1/2 CAPACITY SO ONLY TO UNITS WILL RUN AT ANY TIEM WITH THE

3RD ACTING AS A BACK-UP UNIT. EVERY 7 DAYS THE UNITS WILL BE ALTERNATED

TO RUN. THE UNITS ARE CONTROLLED BY THEIR FACTORY FURNISHED CONTROL

SYSTEM AND THE DDC SYSTEM WILL MONITOR AND ENABLE AND DISABLE ONLY.

ELEVATOR CONTROL DAMPER:

THE DAMPER WILL BE INTERLOCKED TO OPEN WHEN THE ELEVATOR IS IN USE.

SEQUENCE OF OPERATION:

0004 PXCC2 PXCC2

REF# FIELD PANEL NAME FIELD PANEL NODE NAME

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

CRU45 PXCC

N:\DT RESOURCES\JOBS\C4431\MDT\PXCC2.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

USB

~24V

24VDC

24VDC

HMI

UI1

26-

CU4RAT

0.0.1

LAI VALUE RTD

RET AIR TEMP

CRU45

UI2

26-

CU4SAT

0.0.2

LAI VALUE RTD

SUP AIR TEMP

CRU45

UI3

29-

CU4RAH

0.0.3

LAI VALUE CURRENT

RET AIR HUMI

CRU45

U4

29-

CU5RAT

0.0.4

LAI VALUE RTD

RET AIR TEMP

CRU45

U5

32-

CU5SAT

0.0.5

LAI VALUE RTD

SUP AIR TEMP

CRU45

U6

32-

CU5RAH

0.0.6

LAI VALUE CURRENT

RET AIR HUMI

CRU45

U7

35-

CU4FP

0.0.7

LAI VALUE VOLTAGE

CU4 FILTER P

CRU45

U8

35-

CU5FP

0.0.8

LAI VALUE VOLTAGE

CU5 FILTER P

CRU45

U9

42-

0.0.9

U10

42-

CR4S

0.0.10

LDI STATUS

CRU4 FAN PRF

CRU45

U11

45-

CU4ALM

0.0.11

LDI STATUS

CRU4 ALARM

CRU45

U12

45-

CR5S

0.0.12

LDI STATUS

CRU5 FAN PRF

CRU45

SU13

48-

CU5ALM

0.0.13

LDI STATUS

CRU5 ALARM

CRU45

SU14

48-

CU4SMK

0.0.14

LDI STATUS

CRU4 SMOKE

CRU45

SU15

51-

CU5SMK

0.0.15

LDI STATUS

CRU5 SMOKE

CRU45

SU16

51- 0.0.16

AO17

54-

0.0.17

AO18

56-

0.0.18

AO19

56-

0.0.19

DO20 4NC

5C

6NO

CR4ENA

0.0.20

LDO ON/OFF

CRU4 ENABLE

CRU45

DO21 7NC

8C

9NO

CR5ENA

0.0.21

LDO ON/OFF

CRU5 ENABLE

CRU45

DO22 10NC

11C

12NO

0.0.22

DO23 13NC

14C

15NO

0.0.23

DO24 16NC

17C

18NO

0.0.24

R U N

F A U L T

L O W

B A T T

SIEM

EN

S

C O M M

R S T X

R S R X

P X C C

-PXCC 000

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

CRU45 PANEL

N:\DT RESOURCES\JOBS\C4431\MDT\CRU45A.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

STATUS

TX

RX

APOGEE Automation

PXCC 1-

REUSE EXISTING CONTROL PANEL.

REUSE EXISTING CONDUIT AND WIRING TO TERMINATE TO

ADD A UC MIGRATION KIT TO THE EXISITNG PANEL.

NEW SIEMENS CONTROLLER TO BE MOUNTED IN THE EXISTING PANEL.

TO NEW SIEMENS CONTROLLER.

INSTALLATION NOTES:

EXISITNG CONTROL ENCLOSURE1

XFMR-1

PNL 1-

Control Qty Product Number Manufacturer Document Description

Device Number

Field Mounted Devices

XFMR 1 1 X050BAA N/A N/A XFormer,50VA,120-24Vac,Ft Single Hub Mnt

Panel Mounted Devices

PNL 1 1 PXA-UCKIT SIEMENS pxauckit DIN RPLMT KIT FOR UC OR FLNC

PXCC 1 1 PXC24.2-PE.A SIEMENS 149454 APOGEE 24PT, P2 ETHERNET

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

FURN-1&2 CU-2&

\\DELLSERVER\ENGINEERING DOCUMENTS\DT RESOURCES\JOBS\C4431\MDT\FURN-1&2 CU-2&3.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

XD

(SEE UNIT WIRING)

(SEE UNIT WIRING) (SEE UNIT WIRING)

CU-2(3)

VERIFY WIRING FOR LLSV)

OA

RA

SA

SA

RA

OA

VERIFY WIRING FOR LLSV)

CU-2(3)

(SEE UNIT WIRING)(SEE UNIT WIRING)

(SEE UNIT WIRING)

XD

HOT

CLG STG1

HTG STG1

FAN

COMMON

CONTROL

COMPARTMENT

FURN-1 FURN-2

SMOKE DETECTOR

FURNISHED BY

OTHERS

SMOKE DETECTOR

FURNISHED BY

OTHERS

POWERS

DPTE 1

SETPTIN WG

F1FP

0003:0.0.2

H L

È

TTE 2

-40/240 deg F

F1DAT

0003:0.0.14

È

D 1

NC

S Q B

AE 1

24 VAC

F1OAD

0003:0.0.18

È

F1SMK

0003:0.0.11È

POWERS

TTE 1

40/120 DEG F

F1ST

0003:0.0.4

È

PS 1

0/50 PSI

F1RALM

0003:0.0.9È

T

PT 1-

FURNACE-1, CU-2 AIR FLOW1

FURNACE-2, CU-3 AIR FLOW2

T

PT 2-

PS 2

0/50 PSI

F2RALM

0003:0.0.10È

POWERS

TTE 3

40/120 DEG F

F2ST

0003:0.0.5

È

F2SMK

0003:0.0.12È

S Q B

AE 2

24 VAC

F2OAD

0003:0.0.19

È

D 2

NC

TTE 4

-40/240 deg F

F2DAT

0003:0.0.15

È

POWERS

DPTE 2

SETPTIN WG

F2FP

0003:0.0.3

H L

È

RE-2 (2)

C 13 14

RE-3 (2)

C 13 14

RE-4 (2)

C 13 14

RE-1 (2)

C 13 14

F2FAN

0003:0.0.21È

F2C1

0È

F2H1

0È

F1FAN

0003:0.0.20È

F1C1

0È

F1H1

0È

FURN-1,2 & CU-2,3 WIRING4

020 TYPICAL OF 2

CABINENT FURN WITH UNIT

ELECTRIC HEAT STRIP

H

E

A

T

I

N

G

C

O

I

L

POWERS

TE 1

40/90 DEG F

68 DEG F

UNIT HEATER-1,2,3 CONTROL3

020 TYPICAL OF 3

FURNACES FURN-1 AND 2:

FURNACES WILL BE STARTED AND STOPPED BY THE DC SYSTEM. WHEN THE

FAN IS STARTED THE OSA DAMPER WILL BE OPENED. WHEN THE SPACE

TEMPERATURE IS ABOVE SETPOINT THE CONDENSING UNIT WILL BE CYCLED AS

REQUIRED TO MAINTAIN SETPOINT. WHEN THE SPACE TEMPERATURE IS BELOW

SETPOINT ELECTRIC HEAT STRIPS WILL BE CYCLED AS REQUIRED TO MAINTAIN

SPACE TEMPERATURE SETPOINT.

UNIT HEATER :

THE ELECTRIC SPACE MOUNTED THERMOSTAT WILL CYCLE THE FAN AND ELECTRIC

HEAT AS REQUIRED TO MAINTAIN SEPOINT.

SEQUENCE OF OPERATION:

0003 PXCC1 PXCC1

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

FURN-1&2 PXCC

C:\JOBS\C4431\MDT\PXCC1.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

USB

~24V

24VDC

24VDC

HMI

UI1

26-

GENRMT

0.0.1

LAI VALUE RTD

GEN RM TEMP

FURN-1&2 CU-2&3

UI2

26-

F1FP

0.0.2

LAI VALUE VOLTAGE

FILTER PRESS

FURN-1&2 CU-2&3

UI3

29-

F2FP

0.0.3

LAI VALUE VOLTAGE

FILTER PRESS

FURN-1&2 CU-2&3

U4

29-

F1ST

0.0.4

LAI VALUE RTD

SPACE TEMP

FURN-1&2 CU-2&3

U5

32-

F2ST

0.0.5

LAI VALUE RTD

SPACE TEMP

FURN-1&2 CU-2&3

U6

32- 0.0.6

U7

35-

GENPRF

0.0.7

LDI STATUS

EM GEN PROOF

FURN-1&2 CU-2&3

U8

35-

EF9PRF

0.0.8

LDI STATUS

EF9 PROOF

FURN-1&2 CU-2&3

U9

42-

F1RALM

0.0.9

LDI STATUS

F1 REFIG ALM

FURN-1&2 CU-2&3

U10

42-

F2RALM

0.0.10

LDI STATUS

F2 REFIG ALM

FURN-1&2 CU-2&3

U11

45-

F1SMK

0.0.11

LDI STATUS

FURN 1 SMOKE

FURN-1&2 CU-2&3

U12

45-

F2SMK

0.0.12

LDI STATUS

FURN 2 SMOKE

FURN-1&2 CU-2&3

SU13

48-

EF8PRF

0.0.13

LDI STATUS

EF 8 PROOF

FURN-1&2 CU-2&3

SU14

48-

F1DAT

0.0.14

LAI VALUE RTD

SUP AIR TEMP

FURN-1&2 CU-2&3

SU15

51-

F2DAT

0.0.15

LAI VALUE RTD

SUP AIR TEMP

FURN-1&2 CU-2&3

SU16

51- 0.0.16

AO17

54-

EF8HI

0.0.17

LAO VALUE VOLTAGE

EF8 HI SPEEDFURN-1&2 CU-2&3

AO18

56-

F1OAD

0.0.18

LAO VALUE VOLTAGE

OA DAMPERFURN-1&2 CU-2&3

AO19

56-

F2OAD

0.0.19

LAO VALUE VOLTAGE

OA DAMPERFURN-1&2 CU-2&3

DO20 4NC

5C

6NO

F1FAN

0.0.20

LDO ON/OFF

FAN ENABLE

FURN-1&2 CU-2&3

DO21 7NC

8C

9NO

F2FAN

0.0.21

LDO ON/OFF

FAN ENABLE

FURN-1&2 CU-2&3

DO22 10NC

11C

12NO

0.0.22

LDO ON/OFF

DO23 13NC

14C

15NO

EF8LOW

0.0.23

LDO ON/OFF

EF 8 LOW SPD

FURN-1&2 CU-2&3

DO24 16NC

17C

18NO

EF9FAN

0.0.24

LDO ON/OFF

EF 9 ENABLE

FURN-1&2 CU-2&3

R U N

F A U L T

L O W

B A T T

SIEM

EN

S

C O M M

R S T X

R S R X

P X C C

-PXCC 000

ENGINEER

FAA Control Tower Sys Upgrade

Little Rock, AR

C4431

FURN-1&2 CU-2& PANEL

N:\DT RESOURCES\JOBS\C4431\MDT\FURN-1&2 CU-2&3A.DWG

DWJ DWJ JLJ 12/11/15 12/29/15

Powers of Arkansas

WWW.POWERSAR.COM

Controls Divsion

5440 Northshore Drive

N. Little Rock, AR 72118

USA

PHONE: 501-374-5420

FAX: 501-370-9298

Powers of Arkansas All Rights Reserved1994-15

REVISION HISTORY

STATUS

TX

RX

APOGEE Automation

PXCC 1-

REUSE EXISTING CONTROL PANEL.

REUSE EXISTING CONDUIT AND WIRING TO TERMINATE TO

ADD A UC MIGRATION KIT TO THE EXISITNG PANEL.

NEW SIEMENS CONTROLLER TO BE MOUNTED IN THE EXISTING PANEL.

TO NEW SIEMENS CONTROLLER.

INSTALLATION NOTES:

EXISITNG CONTROL ENCLOSURE1

XFMR-1

PNL 1-

Control Qty Product Number Manufacturer Document Description

Device Number

Field Mounted Devices

XFMR 1 1 X050BAA N/A N/A XFormer,50VA,120-24Vac,Ft Single…