A512.pdf

PDF 348 KB Posted

Attached to
Building Masonry Repair at Quantico, Virginia
Solicitation number
15DDHQ18Q00000171
Issued by

About this file

Drawing A512

View the file

Other files

File Type Posted
RFQ_Addendum_0006.pdf PDF
RFQ_15DDHQ18Q00000171_Addendum_0005.pdf PDF
RFQ_15DDHQ18Q00000171_Addendum_0004.pdf PDF
RFQ_15DDHQ18Q00000171_Addendum_0003.pdf PDF
QRFI_Masonry_Repair_Quantico_VA.pdf PDF
A301.pdf PDF
Request_for_Access_Form.pdf PDF
A401.pdf PDF
RFQ_15DDHQ18Q00000171.pdf PDF
A302.pdf PDF
A505.pdf PDF
A303.pdf PDF
A305.pdf PDF
A402.pdf PDF
A507.pdf PDF
A503.pdf PDF
A306.pdf PDF
A508.pdf PDF
A304.pdf PDF
A504.pdf PDF
A502.pdf PDF
A509.pdf PDF
A511.pdf PDF
A513.pdf PDF
A506.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A512

DETAIL

SCALE:1 1/2"=1'-0"

SCALE:1 1/2"=1'-0"

DETAIL2

A512

SCALE:1 1/2"=1'-0"

DETAIL3

A512

A512

DETAIL

SCALE:1 1/2"=1'-0"

SCALE:1 1/2"=1'-0"

DETAIL6

A512

A512

DETAIL

SCALE:1 1/2"=1'-0"

ROOF SLAB

360'-0"

CONCRETE SLAB

2' -8

2"

1'-1 5/8"4 3/4"

1'-0" 6" 1/2" TYP.

1'-3" 3"

1'-4 1/4"1 3/4" 1/2" TYP.

1'-4"

4"7 5/8"4 3/8" 6"

2" 5" 1"2"1'-0"

3" 1'-

9" 2"

1/ 2"

1/ 2"

1/ 2"

3/ 8"

1'- 4"

2"

2' -8

1'-6" 6"

1'-2"4"

2' -8

1/ 2"

1'-7" 3"

1'-6" 4"

3"1'-3"

1'-4 1/4"1 3/4"

7 5/8" 6"

8"

2'-0" TYP.

SL. 1/2"/FT

SL.

SL.

SHT MET-3 COPING

WITH CLEATS

TREATED WOOD BLOCKING

SEALANT

PAVER-1 BALLAST

INSUL-1 RIGID INSULATION

SPR-1

FULLY ADHERED MEMBRANE

FLASHING TURN UP

UNDER COPING

LIGHTWEIGHT CONCRETE

FILL TAPER 1/2"/FT TO

MIN.1" THICK @ ROOF DRAIN

CONCRETE BEAM SEE STRUCTURAL

8" NOM. CMU

HORIZONTAL JOINT REINF.

AIR SPACE

BRICK VENEER

STEEL ANGLE BRACE

LATERAL SUPPORT SEE

STRUCTURAL DETAILS

GAP SPACE TO ALLOW FOR

ANTICIPATED STRUCTURAL

VERTICAL MOVEMENT

LOOSE LINTEL ANGLE

PER SCHEDULE SEE STRUCT

PAINT ALL EXPOSED SURFACES

TO MATCH BRICK, TYP.

ADJUSTABLE DOVETAIL

WITH CONCRETE INSET

@ 16" OC HORIZ.& VERT.

CMU BOND BEAM LINTEL

PER SCHEDULE SEE

STRUCTURAL DRAWINGS

SUSPENDED FINISH CEILING

PER SCHEDULE

PREFAB ALUMINUM BLIND

POCKET

ALUMINUM WINDOW FRAME

PER SCHEDULE

CONTINUOUS SEALANT

CAST STONE CONCRETE

SILL TYPICAL @

WINDOW OPENINGS

THRU-WALL SILL FLASHING

WITH WEEPS @ 24" OC

(MIN. 2 PER OPENING)

TURN FLASHING UP @ JAMB

TO FORM ENDDAM TYP.

PREFAB ALUMINUM STOOL

TO RECEIVE GYB BD. STOOL

FINISH SAME AS WINDOW FRAME

BASE & FINISH FLOOR PER

SCHEDULE

THRU-WALL FLASHING

WEEPHOLES @ 24" OC, TYP.

SOFT JOINT WITH SEALANT

BELOW SHELF ANGLE, TYP.

ADJUSTABLE CONCRETE

INSERTS @ 24" OC MAXIMUM

SPACING, TYP. UNLESS

OTHERWISE NOTED. SEE

STRUCTURAL DRAWINGS

FOR REINFORCING &

ADDITIONAL NOTES

5"X5"X3/8" GALVANIZED

BRICK SHELF ANGLE

FILL GAP SPACE WITH

SAFING INSULATION

SEALANT

MP-2 METAL WALL PANEL

SYSTEM ON METAL FURRING

1/2" SEALANT JOINT

FLASHING WITH WEEPS

PRECAST PANEL

CONNECTION POCKET

FILL POCKET WITH

CONCRETE AFTER

PRECAST IS SET

SAFING INSULATION

APC-1

SEALANT

CONTINUOUS DRIP GROOVE

TYPICAL

RADIANT HEATING PANEL

WITH REVEALED MOUNTING

TRIM SEE MECHANICAL

DRWGS FOR LOCATION

GYB BD BULKHEAD ON

METAL STUD FRAMING

1" INSULATED GLASS

PER SCHEDULE

ALUMINUM STOREFRONT

FRAME WITH THERMAL

BREAK SEE STOREFRONT

SCHEDULE FOR SIZES

& DIMENSIONS

SUSPENDED FINISH CEILING

8" WIDE

PREFAB ALUMINUM STOOL

TO RECEIVE GYB BD

FINISH STOOL SAME AS

STOREFRONT FRAME

INSUL-21

MP-2 SPANDREL WITH

INSULATION SET IN

STOREFRONT FRAME

BASE & FINISH FLOOR

PER SCHEDULE

METAL SILL FLASHING

WITH WEEPS

1/2" SEALANT & BACKER

ROD

APC-1 SEE TYPICAL NOTES

& DIMENSIONS DETAIL 3/A512

PRECAST CONNECTION

POCKET

CONCRETE BEAM SEE

STRUCTURAL DRWGS.

FILL WITH SAFING INSULATION

INSUL-21

RADIANT PANEL SEE MECHANICAL

NOTE:

PRECAST PANEL CONNECTION DETAILS SHOWN

ARE SCHEMATIC. PRECAST MANUFACTURER

SHALL DESIGN ALL CONNECTION DETAILS.

ALL RELATED TRADES SHALL COORDINATE

WITH PRECAST CONNECTIONS & DIMENSIONS

SL.

ALUMINUM STOREFRONT

PER SCHEDULE

1" INSULATING TEMPERED

GLASS

PEDESTAL MOUNTED FINNED

TUBE HOUSING SEE MECH.

FOR SIZE & LOCATION

1/8" BREAK METAL

CLOSURE PLATE @ SILL

TYPICAL

SAFING INSULATION

APC-1

SEE 3/A512 FOR ADDITIONAL

NOTES & DIMENSIONS

CONTINUOUS DRIP GROOVE

1/2" METAL TRIM EDGE

REVEAL

PLS-11 SOFFIT DESIGN

FOR UPLIFT FORCE

ALUMINUM STOREFRONT

FRAME PER SCHEDULE

5/8" EXTERIOR GYB BD SHEATHING

ON METAL STUD FRAMING

STEEL ANGLE SUPPORT FRAME @

48" OC MAX SPACING FOR STOREFRONT

VAPOR BARRIER

INSUL-21

ALUMINUM WINDOW FRAME PER SCHEDULE

1" INSULATING GLASS

SEALANT TYP. BOTH SIDES

CAST STONE CONCRETE SILL

SILL FLASHING WITH WEEPS

BRICK VENEER

AIR SPACE

BITUMINUOUS DAMPPROOFING

PEA GRAVEL

THRU-WALL FLASHING WITH

WEEPS @ 24" OC

GROUT SOLID BELOW FLASHING

APPROXIMATE FINISH GRADE

SEE CIVIL DRWGS.

2" INSUL-1 PERIMETER INSULATION

24" WIDE TYPICAL

VAPOR BARRIER

COMPACT GRAVEL

CONCRETE FOUNDATION FOOTING

SEE STRUCTURAL FOR DETAILS

& DIMENSIONS

SEE TYPICAL WALL

CONSTRUCTION 2/A501 8" NOM. CMU

COL

SPECIAL SHELF BRICK @ ANGLE TYP.

LINEAR DIFFUSER

SEE MECH. DRWGS.

LINEAR DIFFUSER

LINEAR DIFFUSER

5"

3"

MIN

3"

MIN

C-11

TYPE

LIGHT

FIXTURE

A512

DETAIL

SCALE:1 1/2"=1'-0"

SCALE:1 1/2"=1'-0"

DETAIL2

A512

SCALE:1 1/2"=1'-0"

DETAIL3

A512

A512

DETAIL

SCALE:1 1/2"=1'-0"

SCALE:1 1/2"=1'-0"

DETAIL6

A512

A512

DETAIL

SCALE:1 1/2"=1'-0"

ROOF SLAB

360'-0"

CONCRETE SLAB

2' -8

2"

1'-1 5/8"4 3/4"

1'-0" 6" 1/2" TYP.

1'-3" 3"

1'-4 1/4"1 3/4" 1/2" TYP.

1'-4"

4"7 5/8"4 3/8" 6"

2" 5" 1"2"1'-0"

3" 1'-

9" 2"

1/ 2"

1/ 2"

1/ 2"

3/ 8"

1'- 4"

2"

2' -8

1'-6" 6"

1'-2"4"

2' -8

1/ 2"

1'-7" 3"

1'-6" 4"

3"1'-3"

1'-4 1/4"1 3/4"

7 5/8" 6"

8"

2'-0" TYP.

SL. 1/2"/FT

SL.

SL.

SHT MET-3 COPING

WITH CLEATS

TREATED WOOD BLOCKING

SEALANT

PAVER-1 BALLAST

INSUL-1 RIGID INSULATION

SPR-1

FULLY ADHERED MEMBRANE

FLASHING TURN UP

UNDER COPING

LIGHTWEIGHT CONCRETE

FILL TAPER 1/2"/FT TO

MIN.1" THICK @ ROOF DRAIN

CONCRETE BEAM SEE STRUCTURAL

8" NOM. CMU

HORIZONTAL JOINT REINF.

AIR SPACE

BRICK VENEER

STEEL ANGLE BRACE

LATERAL SUPPORT SEE

STRUCTURAL DETAILS

GAP SPACE TO ALLOW FOR

ANTICIPATED STRUCTURAL

VERTICAL MOVEMENT

LOOSE LINTEL ANGLE

PER SCHEDULE SEE STRUCT

PAINT ALL EXPOSED SURFACES

TO MATCH BRICK, TYP.

ADJUSTABLE DOVETAIL

WITH CONCRETE INSET

@ 16" OC HORIZ.& VERT.

CMU BOND BEAM LINTEL

PER SCHEDULE SEE

STRUCTURAL DRAWINGS

SUSPENDED FINISH CEILING

PER SCHEDULE

PREFAB ALUMINUM BLIND

POCKET

ALUMINUM WINDOW FRAME

PER SCHEDULE

CONTINUOUS SEALANT

CAST STONE CONCRETE

SILL TYPICAL @

WINDOW OPENINGS

THRU-WALL SILL FLASHING

WITH WEEPS @ 24" OC

(MIN. 2 PER OPENING)

TURN FLASHING UP @ JAMB

TO FORM ENDDAM TYP.

PREFAB ALUMINUM STOOL

TO RECEIVE GYB BD. STOOL

FINISH SAME AS WINDOW FRAME

BASE & FINISH FLOOR PER

SCHEDULE

THRU-WALL FLASHING

WEEPHOLES @ 24" OC, TYP.

SOFT JOINT WITH SEALANT

BELOW SHELF ANGLE, TYP.

ADJUSTABLE CONCRETE

INSERTS @ 24" OC MAXIMUM

SPACING, TYP. UNLESS

OTHERWISE NOTED. SEE

STRUCTURAL DRAWINGS

FOR REINFORCING &

ADDITIONAL NOTES

5"X5"X3/8" GALVANIZED

BRICK SHELF ANGLE

FILL GAP SPACE WITH

SAFING INSULATION

SEALANT

MP-2 METAL WALL PANEL

SYSTEM ON METAL FURRING

1/2" SEALANT JOINT

FLASHING WITH WEEPS

PRECAST PANEL

CONNECTION POCKET

FILL POCKET WITH

CONCRETE AFTER

PRECAST IS SET

SAFING INSULATION

APC-1

SEALANT

CONTINUOUS DRIP GROOVE

TYPICAL

RADIANT HEATING PANEL

WITH REVEALED MOUNTING

TRIM SEE MECHANICAL

DRWGS FOR LOCATION

GYB BD BULKHEAD ON

METAL STUD FRAMING

1" INSULATED GLASS

PER SCHEDULE

ALUMINUM STOREFRONT

FRAME WITH THERMAL

BREAK SEE STOREFRONT

SCHEDULE FOR SIZES

& DIMENSIONS

SUSPENDED FINISH CEILING

8" WIDE

PREFAB ALUMINUM STOOL

TO RECEIVE GYB BD

FINISH STOOL SAME AS

STOREFRONT FRAME

INSUL-21

MP-2 SPANDREL WITH

INSULATION SET IN

STOREFRONT FRAME

BASE & FINISH FLOOR

PER SCHEDULE

METAL SILL FLASHING

WITH WEEPS

1/2" SEALANT & BACKER

ROD

APC-1 SEE TYPICAL NOTES

& DIMENSIONS DETAIL 3/A512

PRECAST CONNECTION

POCKET

CONCRETE BEAM SEE

STRUCTURAL DRWGS.

FILL WITH SAFING INSULATION

INSUL-21

RADIANT PANEL SEE MECHANICAL

NOTE:

PRECAST PANEL CONNECTION DETAILS SHOWN

ARE SCHEMATIC. PRECAST MANUFACTURER

SHALL DESIGN ALL CONNECTION DETAILS.

ALL RELATED TRADES SHALL COORDINATE

WITH PRECAST CONNECTIONS & DIMENSIONS

SL.

ALUMINUM STOREFRONT

PER SCHEDULE

1" INSULATING TEMPERED

GLASS

PEDESTAL MOUNTED FINNED

TUBE HOUSING SEE MECH.

FOR SIZE & LOCATION

1/8" BREAK METAL

CLOSURE PLATE @ SILL

TYPICAL

SAFING INSULATION

APC-1

SEE 3/A512 FOR ADDITIONAL

NOTES & DIMENSIONS

CONTINUOUS DRIP GROOVE

1/2" METAL TRIM EDGE

REVEAL

PLS-11 SOFFIT DESIGN

FOR UPLIFT FORCE

ALUMINUM STOREFRONT

FRAME PER SCHEDULE

5/8" EXTERIOR GYB BD SHEATHING

ON METAL STUD FRAMING

STEEL ANGLE SUPPORT FRAME @

48" OC MAX SPACING FOR STOREFRONT

VAPOR BARRIER

INSUL-21

ALUMINUM WINDOW FRAME PER SCHEDULE

1" INSULATING GLASS

SEALANT TYP. BOTH SIDES

CAST STONE CONCRETE SILL

SILL FLASHING WITH WEEPS

BRICK VENEER

AIR SPACE

BITUMINUOUS DAMPPROOFING

PEA GRAVEL

THRU-WALL FLASHING WITH

WEEPS @ 24" OC

GROUT SOLID BELOW FLASHING

APPROXIMATE FINISH GRADE

SEE CIVIL DRWGS.

2" INSUL-1 PERIMETER INSULATION

24" WIDE TYPICAL

VAPOR BARRIER

COMPACT GRAVEL

CONCRETE FOUNDATION FOOTING

SEE STRUCTURAL FOR DETAILS

& DIMENSIONS

SEE TYPICAL WALL

CONSTRUCTION 2/A501 8" NOM. CMU

COL

SPECIAL SHELF BRICK @ ANGLE TYP.

LINEAR DIFFUSER

SEE MECH. DRWGS.

LINEAR DIFFUSER

LINEAR DIFFUSER

5"

3"

MIN

3"

MIN

C-11

TYPE

LIGHT

FIXTURE

Washington, D.C. 20009 Comm Number 7782 921A

1875 Connecticut Ave. NW Suite 600

SUPV

SUBMITTED BY

TITLE

CHKDRWN

CH ENGR

408 404 40504B

D/M/YR

D/M/YRAPPROVED

APPROVED

EFD FOR COMMANDER, NAVFAC

D/M/YR

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

CHESAPEAKE DIVISION, WASHINGTON D.C.

SCALE SPEC SHEET 21-92-0193 OF

SIZE CODE IDENT NO.

Drug Enforcement Administration Justice Training CenterQuantico, Virginia

F 80091 CONSTR. CONTR. NO.

NAVFAC DRWING NUMBER

N62477-92-C-0193

E.I.C. 403 40204

09A 401

LTR

REVISION

DESCRIPTION DATE APPRV'D.

NS ACH

WMC CFK

CHIEF ARCHITECT

A512

3080631

GRAPHIC 87 329

EXTERIOR SECTIONAL DETAILS

1-1/2" = 1'-0"

1'9"6"0 3"

SCALE MUST BE USED.

REDUCTION, GRAPHIC

IF DRAWING IS A

CAUTION:

1 RFI # 214-CLARIFICATION 3-24-98

RECORD DRAWING November 14, 2002

2 PC # 117

Model
Layout1