This Statement of Work outlines the Federal Bureau of Prisons' (FBOP) requirement to purchase two 100-ton air-cooled commercial grade chillers for the Federal Correctional Institution (FCC) Beaumont, located in Beaumont, Texas. The chillers must meet or exceed the specified cooling capabilities and efficiency ratings.
The equipment specifications detail requirements including 100-ton cooling capacity (1,200,000 BTU/hr), four compressors per unit, 460V/3-phase/60Hz power supply, water flow rates of 73-600 GPM, and operating temperature range of -20°F to 125°F. The chillers must use either R-410A or low GWP R-454B refrigerant, include copper tubing, factory-installed flow switch, architectural louvered panels, and be ETL Listed to US/Canadian Safety Standards. The contract includes a 5-year warranty on parts, labor, refrigerant, and compressors, plus factory start-up and prestart inspection. Deliveries must be made between 8:00 AM - 2:30 PM Monday through Friday, excluding federal holidays. All proposed equipment requires FBOP review and approval via submission of full product detail sheets prior to award.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I. SPECIFICATIONS
A. Scope Of Work
STATEMENT OF WORK
FCC Beaumont - B & F PROJECT 25ZSAB7
- Replace GA/GB Chiller - Camp
Approved 12/31/2024 SCI\O
The Federal Bureau of Prisons (FBOP), Federal Correctional Institution (FCC) Beaumont intends to purchase two (2) 100 Ton Air Cooled Commercial Grade Chillers at FCC Beaumont, located at 5430 Knauth Road, Beaumont, Tx 77705. Chillers must have equal to or greater than cooling capabilities and efficiency ratings to the listed specifications within this Statement of Work.
All proposed equipment must be submitted with full product detail sheets and specifications for review and approval by FBOP prior to award.
B. Equipment Specifications
1. Cooling Capacity: 100 tons (equivalent to 1,200,000 BTU/hr. or approximately 352 kW)
2. Set Point Range: Between 20°F to 80°F (-7°C to 27°C)
3. Compressor Quantity: 4 compressors
4. Power Requirements: 460V / 3-phase / 60Hz electrical supply
5. Full Load Amperage (FLA): Approximately 210 to 259 amps
6. Maximum Overcurrent Protection (MOP): 250 to 300 amps
7. Single point unit power connection
8. Water Flow Rate: Minimum flow around 73 GPM, maximum up to 600 GPM
9. Water Connections: 4-inch 150 lb. RF flange in/out
10. Reservoir Capacity: Integrated pumping package
11. Operating Temperature Range: Ambient conditions from -20°F to 125°F (-29°C to 52°()
12. Refrigerant Type: R-410A or low GWP R-454B
13. Copper tubing
14. Factory installed flow switch
15. No control transformer
16. Terminal Block
17. Architectural louvered panels
18. Agency Listing - ETL Listed to US/Canadian Safety Std
19. Warranty- 5-year parts, labor, and refrigerant - 5-year compressor
20. Factory start-up and prestart inspection
C. Delivery of Equipment
1. Deliveries which are directly shipped to the institution can be received between the hours of 8:00 AM -
2:30 PM, Monday - Friday, excluding federal holidays.
End Statement of Work