150083_ATT11_Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- FA813726R0008
About this file
This document is a set of contract drawings for the "Repair Transformer Vault 6, B9001" project at Tinker Air Force Base, Oklahoma, with an issue date of December 12, 2025. The project is designated WWYK150083 and is managed by the Air Force Materiel Command's 72nd Air Base Wing Civil Engineer Directorate.
The scope of work includes demolition and replacement of electrical equipment within Transformer Vault 6. Key demolition tasks involve removing existing switchgear units 6C and 6D (including 2000 KVA step-down transformers), primary load break switches, main/tie/distribution sections, and associated busways, while retaining primary 13.8 KV circuits and secondary 480V busducts for reconnection. New work includes installation of Square D Power Zone switchgear with remote racking, Kirk-key switching interlock, forced fan cooling, and temperature monitoring; installation of new medium voltage rated cable compatible with existing systems; installation of 480V, 3-phase, 3-wire, 1600-ampere busduct; cable tray systems with 9-500 KCMIL and 1-#4/0 EGC; and fire alarm system modifications including removal and reinstallation of notification devices. The project requires compliance with applicable codes including UFC 1-200-01, UFC 3-301-01, IBC 2024, ACI 318-19, ASCE 7-22, and Tinker Air Force Base Facility Standards. The drawings include architectural floor plans and elevations, structural plans and general notes, and comprehensive electrical plans, one-line diagrams, details, and schedules for both demolition and new work phases.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RU
NW
AY
/36
RUNWAY 13/31
TA
XI
W
AY
G
TAXIW
AY H
TAXIWAY B
TAXIWAY C
TAXIWAY M
TA
XI
W
AY
K
TAXIWAY E
TAXIWAY A
TA
XIW
AY EE
TAXIWAY F
TAXIWAY D
TAXIWAY E
TAXIWAY J
TA
XI
W
AY
G
TAXIWAY A
TAXIW
AY H
TAXIWAY C
TAXIWAY D
TAXIWAY EE
TAXIWAY F
Crutcho Creek
Kuhlman Creek
Kuhlman Creek
Elm C reek
East Crutcho Creek
Elm Creek
El m
C re ek
Elm Creek
Elm C reek
Elm CreekElm C reek
Ku hlm an C re ek
Ea st
C ru tc ho
C re ek
Elm C ree k
West Crutcho Creek
W es t C ru tc ho
C re ek
Elm Creek
Elm C reek
Soldier CreekSoldier Creek
Ea st
C ru tc ho
C re ek
Elm Creek
Ea st
C ru tc ho
C re ek
East C rutcho C reek
So ld ie r C re ek
East C rutch o Creek
Soldier C reek
Soldier C reek
So ld ie r C re ek
East Crutcho Creek
Elm C reek
416506
21222121
59475946
11401128
62540
61089
838837
62509
62528
62523
62501X
43774
62512
62516
62525
3592135916
99999
62543
32101
71086
32091021
53902
50414
55300
56601
930G
948-E
911-E
948-W
61019
911-W
33001
35913
62501
65672
930S
45134
43609
42116
62517
62515
62526
62527
62503
62513
61289
62542
62501OK
11289
99999
62501
15930
15908
15904 15904
15908
15908
15904
15904
15908
62502
41046
62501
62514
62501
61018
71089
99999
45134
96022
43120
41157
44045
45815
40592
40935
43610
62522
41163
15930
15930
11824
Arnold St.
Ea st
Dr
SE 74th St
SE 59th St.
Ai r D ep ot
Patrol Rd.
St aff
D r.
Reserve Rd.
5th Ave
"A " A ve
Mu nit ion s R d.
W ar eh ou se
R d.
"B " A ve
7th St.
"H " A ve
Mc Na rn ey
A ve
Mitchell Ave
Al er t R d.
Co ok
A ve
W es t D r.
"E "A ve
Extender Dr.
Sentry Rd.
34th St.
Twining Dr.
5th Ave.
Jo ne s
Globemaster Dr.
To we r R d.
Vanaman Rd.
Ind us tria l B lvd
So uth
S
t. 1st St.
Do oli ttle A ve
Picnic Rd.
Ja me s D r.
W olfe Dr.
Ai r D ep ot
Ai r D ep ot
"D " A ve
Rawlings Ave.
Perimeter Rd.
Rapcon Rd.
Reserve Rd
"L " A ve
Hercules /Mercury Rd.
"F " A ve
1st St.
Br ow n D r.
Po nd
R d.
Ol d A ir D ep ot
Airey Dr.
General Motors Dr
Bradley Dr.
Entrance Road "C"
Entrance Road "A"
"C " A ve
"C " A ve
Garden Plot Rd.
Hilltop Rd.
Do rm ito ry
Rd
Dormitory Rd.
"M " A ve
Chennault Dr.
Mitchell Ave.
Vandenburg St.
Engine Test Dr.
Doolittle Ave
W hit e D r.
3rd Ave.
"D " D riv e
Ba ll P ar k R d.
Joint STARS Dr.
Ai r D ep ot
Bl vd
Turbine Dr. Turbine Dr.
Central Plant Dr.
6th St.6th St.
Falcon Dr.
Blac kbi rd D r.
W eyland loop
Propulsion Dr.
Thunderbolt D r.
Munitions Rd. Ext.
Codding Rd.
Starlifter Dr.
Chidlaw Ct.
Co rsa ir D r.
Rap tor
Ct.
Ni gh t H aw k C t.
Ph an tom D r.
Franklin
Po we rh ou se D r.
Sk ym as ter
D r.
Spaatz Ct.
La wr en ce
Mu nd ell
Nabors Dr.
Intruder Dr.
McNickle
Mi lle r D r.
Tail Feather Dr.
Holden Dr.
Air ey
Ci r.
Smith Ct.
Raven Ct.
Mitchell Ave
Air Dep ot Ai r D ep ot
Vanaman Rd.
1st St.
1st St.
TINKER AFB, OK
VICINITY MAP
EAKER GATE
FIRE DEPARTMENT
B117
BASE OPERATIONS
B240
CONTRACTING
B3
VANCE
GATE
GOTT
GATE
TINKER GATE
(TEMPORARILY
CLOSED)
LIBERATOR GATE
(TEMPORARILY CLOSED)
HOPE
GATE
LANCER
GATE
TRUCK
GATE
PIAZZA GATE
(TEMPORARILY CLOSED)
HRUSKOCY
GATE
BASE CIVIL ENGINEER
B400
PEGASUS
GATE
PASS & ID
B6611
Extender Dr.
Globemaster Dr.
Joint STARS Dr.
Central Plant Dr.
Propulsion Dr.
Po we rh ou se
D r.
G
EN
ER
AL
SH
EE
T
IN
D
EX
VI
C
IN
IT
Y M
AP
A
N D
BU
IL
D
IN
G K
EY
P
LA
N
G-001
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
REVIEWED BY:
REVIEWED BY:
USING AGENCY:
ASBESTOS EVALUATION:
SAFETY:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
INDUSTRIAL HYGIENE:
DATE:
SHT. SHEET TITLE
SIGNATURES
CORROSION ENGINEER: (CECE)
CE OPERATIONS: (CECO)
COMMUNICATIONS: (COMM)
CHIEF ENGINEER DIR: (CECE)
CHIEF DESIGN BRANCH: (CECE)
DESIGN MANAGER: (CECE)
ZONE MANAGER:
CONSTRUCTION MANAGEMENT: (CECE)
ENVIRONMENTAL:
BASE CIVIL ENGINEER: (CE)
FIRE DEPARTMENT: (CEFT)
PROJECT LOCATION
PROJECT
LOCATION
WWYK150083
REPAIR TRANSFORMER
VAULT 6, B9001
PROJECT DRAWING INDEX
SHT. SHEET TITLE
G-001 SHEET INDEX, VICINITY MAP AND BUILDING KEY PLAN
A-101 ARCHITECTURAL FLOOR AND ROOF PLANS, ELEVATIONS IMAGES
ARCHITECTURAL
ELECTRICAL LEGEND, SYMBOLS AND ABBREVIATIONS
ELECTRICAL
E-001
ELECTRICAL PLAN - DEMOLITIONED101
ELECTRICAL ONE-LINE DIAGRAM - DEMOLITIONED601
ELECTRICAL PLAN - NEW WORKE-101
ELECTRICAL ONE-LINE DIAGRAM - NEW WORKE-601
FIRE ALARM - DEMOLITION AND NEW WORK PLAN
FIRE PROTECTION
F-101
ELECTRICAL DETAILSE-501
STRUCTURAL GENERAL NOTES
STRUCTURAL
S-001
STRUCTURAL PLAN - NEW WORKS-101
ELECTRICAL SCHEDULESE-602
X
Y
TRANSFORMER
VAULT
N
XS
XY N
X YN
38 373837
T.O.P 21' - 6"
T.O.P 21' - 6"
F.F 0' - 0"
F.F 0' - 0"
AR
C
H
IT
EC
TU
R
AL
FL
O
O R
A N
D R
O O
F
PL
AN
S, E
LE
VA
TI
O N
S
IM
AG
ES
A-101
AM
JS
R A
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
GENERAL NOTES:
1. DRAWINGS & SPECIFICATIONS ARE COMPONENTS OF
THE CONTRACT DOCUMENTS. REVIEW ALL DRAWINGS
& SPECIFICATIONS FOR THE COMPLETE SCOPE OF
WORK. NOTIFY CONSTRUCTION INSPECTOR
IMMEDIATELY FOR CLARIFICATION IF
INCONSISTENCIES, CONTRADICTIONS, OR OMISSIONS
ARE DISCOVERED.
2. DO NOT SCALE DRAWINGS. IF DIMENSIONAL
INFORMATION IS REQUIRED & NOT FOUND, NOTIFY
CONSTRUCTION INSPECTOR IMMEDIATELY FOR
CLARIFICATION.
3. ALL DIMENSIONS ARE TO COLUMN CENTERLINES,
FACE OF FINISHED WALLS, OR SURFACES, UNLESS
NOTED OTHERWISE.
4. REFER TO OTHER DISCIPLINE DRAWINGS FOR ITEMS
NOT SHOWN.
5. EXISTING SAFETY TIE OFF ANCHORAGES, TO BE USED
FOR ATTACHMENT OF PERSONAL FALL ARREST
EQUIPMENT, SHALL BE RE-CERTIFIED BY A QUALIFIED
PERSON FOR FALL PROTECTION IN ACCORDANCE
WITH ANSI Z359.1.
SEAL HOLES AND PENETRATIONS WITH NEW METAL
SIDING PATCH AND/OR SEALANT. ASSUME 30
PENETRATIONS TO BE REPAIRED WITH METAL PATCH.
ANY HOLE IN THE EXISTING METAL SIDING LARGER THAN
1/4" IN DIAMETER IS TO USE A 24 GAUGE SHEET METAL
PATCH THAT IS AT LEAST 6 INCHES SQUARE OR
PROVIDES AT LEAST 3 INCHES OF COVERAGE AROUND
THE HOLE - WHICHEVER IS LARGER. SHEET METAL
PATCH IS TO BE ADDED IN A CONTINUOUS SILICONE
SEALANT BEAD AROUND THE EXISTING OPENING IN THE
METAL PANEL. SECURE SHEET METAL PATCH PANEL
WITH AT LEAST EIGHT (8) APPROPRIATELY SIZED SFS
INTEC ZAC IMPAX FASTENERS (FOR A MINIMUM 6" X 6"
SHEET METAL PATCH PANEL). PROVIDE SHEET METAL
PATCH PANEL IN BRONZE COLOR TO APPROXIMATE
EXISTING FINISH COLOR. SEALANT COLOR TO MATCH
EXISTING BRONZE-COLORED FINISH.
NEW DOOR THRESHOLD AND WEATHER SEAL KIT AT
EXISTING HOLLOW METAL DOORS. BASIS OF DESIGN:
PEMKO 177 SADDLE TYPE THRESHOLD WITH SEAL AND
PEMKO CLOSED CELL SPONGE NEOPRENE TAPE
WEATHERSTRIPPING.
ELECTRICAL CONDUIT. SEAL PENETRATIONS IN METAL
WALL PANELS.
NEW UPSIZED ZINC ALLOY TYPE METAL WALL
FASTENERS. BASIS-OF-DESIGN FASTENER: SFS INTEC
ZAC IMPAX FASTENERS.
NEW WORK KEY NOTES:
46'-10"
'-1
0"
A-101
A-101
ARCHITECTURAL FLOOR PLAN
SCALE: 1/8" = 1'-0"
A-101
SOUTH ELEVATION
SCALE: 1/8" = 1'-0"
A-101
NORTH ELEVATION
SCALE: 1/8" = 1'-0"
A-101
WEST ELEVATION
SCALE: 1/8" = 1'-0"
A-101
EAST ELEVATION
SCALE: 1/8" = 1'-0"
A-101
REMOVE EXISTNG THRESHOLDS AND WEATHER
SEALS FROM PERSONNEL DOORS
REMOVE ALL EXTERIOR METAL WALL PANEL
FASTENERS.
REMOVE ALL EXISTING SEALANT AT WALL PANELS,
FLASHING PENETRATIONS AND ASSEMBLY
INTERFACES.
REMOVE EXISTING ANTENNA AND SAVE FOR
RE-INSTALLATION. COORDINATE WITH GOVERNMENT
FOR REINSTALLATION.
DEMO KEY NOTES:
IMAGE
SCALE: 1/8" = 1'-0"
A-101
IMAGE
SCALE: 1/8" = 1'-0"
A-101
IMAGE
SCALE: 1/8" = 1'-0"
A-101
A-101
A-101
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RUBARRON
Stamp
GENERAL
G1. SCOPE
THE NOTES ON THIS SHEET AND THE STANDARD STRUCTURAL DETAILS ARE GENERAL AND APPLY
TO THE ENTIRE PROJECT WHETHER SPECIFICALLY CALLED OUT OR NOT, EXCEPT WHERE THERE
ARE SPECIFIC INDICATIONS TO THE CONTRARY ON STRUCTURAL SHEETS. IF THERE ARE
QUESTIONS, THEY SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER AND ANSWERED IN
WRITING PRIOR TO CONSTRUCTION.
G2. APPLICABLE SPECIFICATIONS AND CODES
A. UFC 1-200-01 WITH CHANGE 4, DATED 17 DECEMBER 2024
B. UFC 3-301-01 WITH CHANGE 4, DATED 3 JUNE 2025
C. INTERNATIONAL BUILDING CODE, IBC 2024 WITH APPLICABLE EDITIONS OF THE CODE
REFERENCED STANDARDS.
D. TINKER AIR FORCE BASE FACILITY STANDARDS
E. ACI 318-19
F. ASCE 7-22
G. INTERNATIONAL EXISTING BUILDING CODE, IEBC 2024
G3. EXISTING DRAWINGS
THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING
CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED
CHANGES FOR APPROVAL. THE PLANS AND DETAILS FOR THE EXISTING STRUCTURES
PRESENTED IN THE DRAWINGS ARE FOR REFERENCE ONLY BASED ON THE FOLLOWING
AS-BUILT DRAWINGS:
1. NEW MANUFACTURING PLANT FOR OKLAHOMA INDUSTRIES AUTHORITY TENANCY BY GM
ASSEMBLY DIVISION DATED NOVEMBER 1977.
G4. DESIGN CRITERIA
1. APPLIES TO ALL STRUCTURES (UNO)
A. DEAD LOAD:
1. ACTUAL TRIBUTARY STRUCTURE WEIGHT
2. ELECTRICAL EQUIPMENT SELF-WEIGHT
B. LIVE LOAD:
1. VAULT: 100 PSF
2. ROOF: 20 PSF (NON-REDUCIBLE)
C. WIND:
1. RISK CATEGORY: III
2. ULTIMATE WIND SPEED; VULT: 115 MPH
3. ALLOWABLE STRESS WIND SPEED; VASD: 89 MPH
4. EXPOSURE: C
5. DESIGN WIND PRESSURE: 28 PSF
6. TORNADO WIND SPEED (VT) = 80 MPH
7. TORNADO WIND PRESSURE = 16 PSF
D. SEISMIC:
1. RISK CATEGORY: III
2. IMPORTANCE FACTOR: 1.25
3. SPECTRAL RESPONSE ACCELERATION, SS = 0.32g
4. SPECTRAL RESPONSE ACCELERATION, S1 = 0.08g
5. SITE CLASS: D
6. SEISMIC DESIGN CATEGORY: B
7. SPECTRAL RESPONSE ACCELERATION, SDS = 0.23g
8. SPECTRAL RESPONSE ACCELERATION, SD1 = 0.11g
9. BASIC SEISMIC FORCE RESISTING SYSTEM: SYSTEMS NOT SPECIFICALLY
DETAILED FOR SEISMIC RESISTANCE
10. ANALYSIS PROCEDURE: ASCE CHAPTER 13 - NON-STRUCTURAL
COMPONENTS
11. SEISMIC DESIGN FORCE (MAX): 1.6*SDS*IP*WEIGHT
12. BUILDING RESPONSE MODIFICATION FACTOR, Rp= 3.5
13. COMPONENT IMPORTANCE FACTOR, Ip = 1.0
14. STRUCTURE DUCTILITY REDUCTION FACTOR (Ru): 1.3
15. COMPONENT RESONANCE DUCTILITY FACTOR (CAR): 1.0
16. COMPONENT STRENGTH FACTOR (Rpo): 1.5
E. SNOW LOAD:
1. GROUND SNOW LOAD; P/g: 20 PSF
2. FROST DEPTH: 18 INCHES
F. ICE LOADS:
1. ICE THICKNESS: 1.74 INCHES
2. ICE THICKNESS HEIGHT FACTOR: 1.002
3. DESIGN ICE THICKNESS: 1.74 INCHES
4. DESIGN WEIGHT OF ICE: 8.14 PSF
G. ROOF RAIN LOAD:
1. 15-MINUTE PRECIPITATION INTENSITY: 8.66 IN/HR
2. 60-MINUTE PRECIPITATION INTENSITY: 4.41 IN/HR
G5. SAFETY
SAFETY AND STRUCTURE STABILITY DURING CONSTRUCTION ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. STRUCTURES HAVE BEEN DESIGNED TO RESIST THE DESIGN LIVE LOADS ONLY
AS A COMPLETED STRUCTURE.
G6. OPENINGS
OPENINGS FOR PIPES, DUCTS, CONDUITS, ETC. ARE NOT ALL SHOWN ON THE STRUCTURAL
DRAWINGS. COORDINATE AND PROVIDE OPENINGS AS REQUIRED TO ACCOMMODATE ALL WORK
SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND OTHERWISE REQUIRED FOR THE
FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT. REINFORCE AROUND OPENINGS PER
STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE SHOWN.
G7. SPECIAL INSPECTIONS
THE CONTRACTOR MUST EMPLOY ONE OR MORE APPROVED AGENCIES TO PERFORM INSPECTIONS
DURING CONSTRUCTION ON THE TYPES OF WORK LISTED UNDER SECTION 1705 OF THE IBC
REQUIRING VERIFICATION AND INSPECTION. THESE INSPECTIONS ARE IN ADDITION TO THE
INSPECTIONS DEFINED IN SECTION 110. THE INSPECTING AGENCY MUST PROVIDE REPORTS OF THE
SPECIAL INSPECTIONS DIRECTLY TO THE CONTRACTING OFFICER.
G8. STANDARD DETAILS
THE STANDARD DETAILS DEPICT TYPICAL DETAILING TO BE USED ON THIS PROJECT. IF CONDITIONS ARE NOT EXPLICITLY SHOWN ON THE DRAWINGS THEY SHALL BE MADE SIMILAR TO THE STANDARD
DETAILS. OBTAIN APPROVAL OF ENGINEER IN WRITING FOR SIMILAR CONDITIONS PRIOR TO
CONSTRUCTION.
G9. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING
CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED CHANGES
FOR APPROVAL.
G10. CONTRACTOR TO SUBMIT FOR REVIEW ALL EQUIPMENT SIZES, OPERATING WEIGHTS, VIBRATION
FORCES, SUPPORT LOCATIONS, ALONG WITH ANY FLOOR OPENINGS, NOTCHES, AND RECESSES
REQUIRED BY SUCH EQUIPMENT. CONCRETE SUPPORT PADS AND/OR FRAMING REQUIRED TO
SUPPORT SAID EQUIPMENT SHALL NOT BE FABRICATED AND PLACED UNTIL THE CONCRETE
SUPPORT PADS AND/OR FRAMING IS APPROVED TO SUPPORT THE EQUIPMENT.
GENERAL STRUCTURAL NOTES (GSN)
DEFERRED SUBMITTALS:
1. DEFINITION:
DELEGATE DESIGN SUBMITTALS ARE ITEMS FOR WHICH THE FINAL DESIGN OF A SPECIFIC
ELEMENT OF THE PERMANENT CONSTRUCTION WORK EXPRESSLY DELEGATED TO A
PROPERLY LICENSED AND REGISTERED DESIGN PROFESSIONAL LICENSED IN THE STATE OF
OKLAHOMA RETAINED OR EMPLOYED BY THE CONTRACTOR, SUBCONTRACTOR, SUPPLIER OF
ANY TIER. "DELEGATED DESIGN" APPLIES ONLY TO PERMANENT WORK THAT WILL BE PART OF
THE COMPLETED PROJECT AS A FUNCTIONING WHOLE.
2. DELEGATED DESIGN LIST:
THE FOLLOWING IS A LIST OF DELEGATED SUBMITTALS THAT ARE EXPECTED TO CONTAIN
STAMPED STRUCTURAL CALCULATIONS OF SAFETY-RELATED SYSTEM INFORMATION FOR
REVIEW. THESE SUBMITTALS APPLY TO DELEGATED DESIGN SYSTEMS PRIOR TO INSTALLATION
OF THE INDICATED STRUCTURAL ELEMENT, EQUIPMENT, DISTRIBUTION SYSTEM, COMPONENT
OR ITS ANCHORAGE. THE CONTRACTOR SHALL SUBMIT THE REQUIRED ENGINEER
CERTIFICATION, SUPPORTING DATA, AND DRAWINGS FOR REVIEW AND ACCEPTANCE BY THE
CONTRACTING OFFICER.
DEFERRED SUBMITTALS
SPEC SECTIONS ITEM
STEEL
S1. DESIGN STRENGTHS:
ALL OTHER PLATES AND SHAPES: Fy=36 KSI
S2. DIMENSIONS:
TO CENTERLINES OF COLUMNS AND BEAMS, TOP SURFACES OF BEAMS AND TUBES AND
BACKS OF CHANNELS AND ANGLES UNO.
S3. ELEVATIONS:
TOP OF STEEL REFERS TO TOP SURFACE OF MEMBER OR FLANGE UNO.
S4. WHEN FILLET WELD SIZE IS NOT INDICATED, PROVIDE MAXIMUM WELD SIZE BASED ON
MATERIAL THICKNESS IN ACCORDANCE WITH AISC SPECIFICATIONS.
S5. ALL BOLTED STRUCTURAL CONNECTIONS ARE BEARING TYPE CONNECTIONS UNLESS
OTHERWISE SPECIFIED TO BE SLIP-CRITICAL. PROVIDE LOAD INDICATING WASHERS AT
SLIP-CRITICAL CONNECTIONS.
S6. CONFORM TO AISC 360, STEEL CONSTRUCTION MANUAL AND AISC 341, SEISMIC DESIGN
MANUAL.
VARIOUS
ANY EQUIPMENT OR COMPONENT IN WHICH A
TECHNICAL SPECIFICATION REQUIRES SUBMITTAL
OF EQUIPMENT OR ANCHORAGE SYSTEM
CALCULATIONS
MODIFICATIONS TO EXISTING CONCRETE:
EC1. DRILLED HOLE FOR DOWEL SHALL BE THOROUGHLY CLEANED BY WIRE BRUSHING AND
AIR PRESSURE OR VACUUM TO REMOVE ALL DRILLING DUST. THE HOLE SHALL THEN BE
PARTIALLY FILLED WITH EPOXY AND THE UNCOATED BAR INSERTED, TWISTED AND LEFT IN
PLACE.
EC2. AT LOCATIONS WHERE NEW PENETRATIONS FOR CONDUITS ARE REQUIRED
CONTRACTOR SHALL NON-DESTRUCTIVELY LOCATED EXISTING REINFORCING PRIOR TO
DRILLING HOLES. LOCATE CONDUITS TO NOT DAMAGE REINFORCING.
EC3. NEW OPENINGS IN EXISTING CONCRETE SHALL BE CUT 1 INCH OVERSIZE, COATED WITH
EPOXY BONDING COMPOUND, AND MORTAR FINISHED TO THE REQUIRED FINISH SIZE.
EC4. STRUCTURAL DIMENSIONS RELATED TO OR CONTROLLED BY EXISTING STRUCTURES SHALL
BE VERIFIED IN FIELD BY THE CONTRACTOR PRIOR TO CONCRETE WORK.
POST INSTALLED ANCHORS
P1. POST-INSTALLED ANCHORS SHALL INCLUDE ADHESIVE ANCHORS (THREADED RODS, BOLTS OR
REINFORCING BARS), EXPANSION ANCHORS, AND UNDERCUT ANCHORS INSTALLED INTO
HARDENED CONCRETE.
P2. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE INDICATED ON THE DRAWINGS.
CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER PRIOR TO USING POST-INSTALLED
ANCHORS FROM MISSING OR MISPLACED CAST-IN-PLACE ANCHORS.
P3. CARE SHOULD BE TAKEN TO AVOID CONFLICTS WITH EXISTING REINFORCING STEEL AND OTHER
EMBEDDED ITEMS WHEN DRILLING HOLES. REINFORCING BARS SHALL NOT BE DAMAGED DURING
DRILLING OR ANCHOR INSTALLATION. HOLES SHALL BE DRILLED AND CLEANED PER THE PRODUCT
MANUFACTURER'S INSTRUCTIONS. ANCHORS SHALL BE INSTALLED PER THE PRODUCT
MANUFACTURER'S INSTRUCTIONS AT NOT LESS THAN MINIMUM EDGE DISTANCES AND/OR SPACING
INDICATED IN THE MANUFACTURER'S LITERATURE.
P4. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE INDICATED ON THE DRAWINGS
SHALL BE SUBMITTED TO ENGINEER FOR REVIEW AND APPROVAL. CURRENT PRODUCT ICC-ESR
EVALUATION REPORTS SHALL BE INCLUDED WITH THE SUBMITTAL PACKAGE. IF METHODS AND
PROCEDURES REQUIRED BY THE BUILDING CODE MAY BE REQUIRED AS PART OF THE SUBMITTAL
PACKAGE.
P5. UNLESS NOTES OTHERWISE, THE MINIMUM EMBEDMENT PROVIDED FOR ADHESIVE ANCHORED
REINFORCING BARS SHALL DEVELOP THE FULL TENSILE STRENGTH OF THE BARS.
P6. SPECIAL INSPECTION WILL BE PROVIDED FOR ALL POST-INSTALLED ANCHORS AS INDICATED IN
SPECIAL INSPECTION REQUIREMENTS PER SPECIFICATION SECTION 05 05 20.
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
ST
R U
C
TU
R
AL
G
EN
ER
AL
N O
TE
S
S-001
C M
R
N KT
12/10/2025
45'-0" (*)
'-0
7'-6" (*)
(TYP)
'-0
'-0
'-0
2' -0
" 2' -0
2'-5" (*)
6' -6
2'-5" (*)
6' -6
2'-5" (*)
6' -6
4'-3" (*)
2' -1
0"
2' -0
Y
XN
DETAIL
SCALE: 3/4" = 1'-0"
S-101
1/4TYP 1/4
MAXIMUM EXISTING OPENING
SIZE PER PLAN
L3x3x5/16" x CONT, TYP
5/16" THICK GALV CHECKER PLATE
W/ HILTI X-FCP DISK ATTACHED W/
X-ST-GR M85 P8 OR EQ @ 8"OC
AROUND PERIMETER
EXISTING STL CLOSURE
PLATE AROUND THE
PERIMETER OF OPENING
NOTE:
1. IF STEEL CLOSURE PLATE IS NOT PRESENT, PROVIDE 5/8"
HILTI KWIK HUS EZ ANCHORS IN VERTICAL LEG OF ANGLE
OR EQUAL WITH 5 1/2" EMBED SPACED AT 10" OC AND 3"
MAX FROM ENDS.
2. REFERENCE ELECTRICAL DEMO PLANS FOR LOCATIONS
OF EXISTING BUSDUCT TERMINATIONS TO BE PATCHED.
1/4 3-12 TYP
EXIST STL BEAM
SEE PLAN, TYP
XS
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
ST
R U
C
TU
R
AL
PL
AN
- N
EW
W O
R K
S-101
C M
R
N KT
GENERAL NOTES:
1. SEE STANDARD DRAWINGS FOR GENERAL STRUCTURAL NOTES AND
STANDARD DETAILS.
2. (*) INDICATES EXISTING DIMENSION TO BE FIELD VERIFIED BY
CONTRACTOR.
3. EXISTING BUILDING INFORMATION IS AS INDICATED ON THE AS-BUILT
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER
OF ANY DISCREPANCIES.
4. CONTRACTOR SHALL REVIEW AS-BUILT DRAWING NEW MANUFACTURING
PLANT FOR OKLAHOMA INDUSTRIES AUTHORITY TENANCY BY GM
ASSEMBLY DIVISION DATED NOVEMBER 1977.
5. O - INDICATES EXISTING FLOOR OPENING.
EX
IS
TI
N
G W x4
EXISTING HOIST IS NOT IN CONTRACT. CONTRACTOR SHALL NOT USE THE
EXISTING HOIST FOR THE REMOVAL OR INSTALLATION OF THE NEW
EQUIPMENT IN THE VAULT.
EXISTING FLOOR OPENING TO BE COVERED. SEE DETAIL 2 ON THIS SHEET.
EXISTING CONCRETE ON METAL DECK ROOF SYSTEM.
KEY NOTES:
EX
IS
TI
N
G W x5
EX
IS
TI
N
G W x5
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EX
IS
TI
N
G W x4
EXISTING TRUSS T-20
EX
IS
TI
N
G W x2
EX
IS
TI
N
G W
8x
EX
IS
TI
N
G W
8x
EX
IS
TI
N
G T
R U
SS
T
-2 1A
EXISTING W12x27
EXISTING TRUSS T-19
EXISTING W8x24
ABOVE
EXISTING TRUSS T-20
EXISTING TRUSS T-19A
EXISTING
W8x24 ABOVE
EXISTING W4x78
COLUMN ABOVE;
W14x119 BELOW
EXISTING W8x24
COLUMN ABOVE
EXISTING W14x78
COLUMN ABOVE;
W14x119 BELOW
EXISTING
W8x24
ABOVE
EXISTING W14x78
COLUMN ABOVE;
W14x119 BELOW
EXISTING W4x78
COLUMN ABOVE;
W14x119 BELOW
EXISTING TRUSS T-7
EX
IS
TI
N
G T
R U
SS
T
-2 1A
EXISTING FLOOR
OPENING (TYP)O
0 2' 4' 8'
SCALE: 1/4"=1'-0" (IN FEET)
EXISTING
W12 (TYP)
O
O
O
STRUCTURAL FLOOR FRAMING PLAN - NEW WORK
SCALE: 1/4" = 1'-0"
S-101
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
LE
G
EN
D
, S
YM
BO
LS
AB
BR
EV
IA
TI
O N
S
E-001
BJ
AS
KL
ELECTRICAL LEGEND, SYMBOLS AND ABBREVIATIONS
SYMBOL NOTES
1. THESE SYMBOLS APPLY TO THE ENTIRE SET OF CONTRACT DRAWINGS.
2. ALL SYMBOLS ARE NOT NECESSARILY USED IN THE DRAWINGS FOR THIS PROJECT. LISTING OF
SYMBOLS DOES NOT IMPLY THAT ALL SYMBOLS ARE USED IN THE CONTRACT DRAWINGS.
3. COLORS FOR ALL OUTLETS AND SWITCHES SHALL BE AS SHOWN ON ARCHITECTURAL PLANS.
4. ALL MOUNTING HEIGHTS SHOWN IN SYMBOL LEGEND SHALL BE AS PER TAS/ADA
REQUIREMENTS UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS.
5. BRANCH CIRCUIT NUMBERS MAY BE SHOWN NEXT TO SYMBOLS IN MULTIWIRE CIRCUITS.
6. EQUIPMENT IDENTIFIERS, MATCHING EQUIPMENT SCHEDULES, ARE DISPLAYED ATTACHED TO
SYMBOLS BY LEADER ARROWS, UON.
7. SYMBOL ORIENTATION DOES NOT IMPLY DEVICE OR EQUIPMENT ORIENTATION, UNLESS NOTED AS SUCH. SEE REFLECTED CEILING PLANS FOR LIGHT FIXTURE POSITIONS AND ORIENTATIONS.
8. SYMBOL SIZE DOES NOT IMPLY EQUIPMENT SIZE, UON.
9. LOWER CASE LETTER IN POSITION "X" INDICATES FIXTURES CONTROLLED BY SAME LETTER.
10. PLAN SYMBOLS USE THE FOLLOWING LINE TYPE CONVENTION AND ARE REPRESENTED AS
FOLLOWS:
LINETYPE, DENOTES EXISTING TO REMAIN
LINETYPE, DENOTES EXISTING TO BE DEMOLISHED
LINETYPE, DENOTES NEW U.G. OR CONCEALED CONSTRUCTION
LINETYPE, DENOTES NEW CONSTRUCTION
A AMPERES OR TRIP
AMPERES
AC ALTERNATING CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC SYMMETRICAL AMPS
INTERRUPTING CAPACITY
AWG AMERICAN WIRE GAUGE
A/R AS REQUIRED
ARR. ARRESTOR
BLDG BUILDING
BRKT BRACKET
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CL CURRENT LIMITING
CO CONDUIT ONLY
CTL CONTROL
DC DIRECT CURRENT
D.T.C. DATA TERMINAL CABINET
EMCS ENERGY MONITORING AND
CONTROL SYSTEM
FACP FIRE ALARM CONTROL
PANEL
FT FOOT, FEET
GFCI GROUND FAULT CIRCUIT
INTERRUPTER, 5MA
PERSONNEL PROTECTION
UNLESS OTHERWISE NOTED.
GRD GROUND
HZ HERTZ
IAW IN ACCORDANCE WITH
IG ISOLATED GROUND
IN INCH, INCHES
IR INFRARED
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPS REACTIVE
KWH KILOWATT HOURS
L-L LINE TO LINE
L-N LINE TO NEUTRAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MTD MOUNTED
MTG MOUNTING
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NEUT NEUTRAL
N.O. NORMALLY OPEN
NLT NOT LESS THAN
NMT NOT MORE THAN
OH OVERHEAD
PAS PUBLIC ADDRESS SYSTEM
PE PHOTOELECTRIC
PH PHASE
PLCS PLACES
PNL PANELBOARD
PVC POLYVINYL CHLORIDE
ELECTRICAL RACEWAY
USED ONLY U.G., CARLON
OR EQUIVALENT
RC RIGID STEEL CONDUIT
REF REFERENCE
REQ'D REQUIRED
RGC RIGID GALVANIZED STEEL
CONDUIT
RM ROOM
RMC RIGID METALIC CONDUIT
SHT SHEET
SOB STANDOFF BRACKET
SPACE SPACE(S) ONLY (NO
BREAKER DEVICE)
SPARE SPARE BREAKER OR
DEVICE
SPDT SINGLE-POLE,
DOUBLE-THROW
SPECS CONTRACT SPECIFICATIONS
SPST SINGLE-POLE,
SINGLE-THROW
S/N SOLID NEUTRAL
TB TELEPHONE BACKBOARD
TYP TYPICAL
UG UNDERGROUND
UL LISTED BY UNDERWRITER'S
LABORATORIES
UON UNLESS OTHERWISE NOTED
V VOLTS
VA VOLT AMPERES
W WATT
WAP WIRELESS ACCESS POINT
WH WEATHERHEAD
W/ WITH
Ø PHASE
2W+G CIRCUIT TYPE
3W+G CIRCUIT TYPE
4W+G CIRCUIT TYPE
ABBREVIATIONS
POWER SYMBOLS LEGEND
DESCRIPTIONSYMBOL
RECEPTACLE, DUPLEX, 20A, 120V, GROUNDING 2W+G, NEMA
5-20R
RECEPTACLE, DUPLEX, FLOOR MOUNTED, FLUSH, 20A, 120V,
GROUNDING 2W+G NEMA 5-20R.
RECEPTACLE, DUPLEX, CEILING MOUNTED, 20A, 120V,
GROUNDING 2W+G, NEMA 5-20R
RECEPTACLE, QUADRAPLEX
RECEPTACLE/EQUIPMENT CONNECTION, SPECIAL PURPOSE
RECEPTACLE, CLOCK
JUNCTION BOX, ABOVE CEILING
JUNCTION BOX, WALL MOUNTED, SERVING COMPUTER LOAD.
RECEPTACLE, DUPLEX, SERVING COMPUTER LOAD. 20A, 120V,
GROUNDING 2W+G RECEPTACLE, NEMA 5-20R
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), SINGLE-POLE, MOUNT 54" AFF
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), THREE-WAY, SPDT. MOUNT 54" AFF
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), FOUR-WAY, SPDT. MOUNT 54" AFF
SWITCH, DIMMER, 120V, 1500 WATT. MOUNT 54" AFF
BRANCH CIRCUIT HOME RUN WITH NEUTRAL, PHASE AND
EQUIPMENT GROUND RESPECTIVELY
RACEWAY, ABOVE FLOOR
COMBINATION STARTER/DISCONNECT WITH HOA
SWITCH-COORDINATE WITH MECH. CONTRACTOR.
SWITCH, DISCONNECT
PANELBOARD, SURFACE MOUNTED
PANELBOARD, RECESSED
DESCRIPTIONSYMBOL
TRANSFORMER, POWER, KVA RATING, WINDING VOLTAGES AND
CONNECTIONS ARE SHOWN NEXT TO SYMBOL
ONE-LINE & CONTROL SCHEMATIC LEGEND
TRANSFORMER, CURRENT, TURNS RATIO, SHOWN NEXT TO
SYMBOL
GROUNDING CONNECTION. WHEN USED WITH TRANSFORMER
WINDING SYMBOL IT INDICATES A NEUTRAL GROUNDING
CONNECTION (ON SECONDARY SIDE ONLY)
GROUNDED WYE WINDING CONNECTION
DELTA CONNECTED
RELAY OR CONTACTOR CONTACTS
SEPARABLE (PLUG-IN) CONNECTOR OR CONNECTION FOR
DRAWOUT ASSEMBLIES
SCHEMATIC, CIRCUIT CONNECTIONS
CIRCUIT BREAKER, MOLDED CASE, TRIP CURRENT [A] AND
QUANTITY OF POLES [P] SHOWN NEXT TO SYMBOL
SWITCH, DISCONNECT, NON-FUSED, LOAD BREAK. CONTINUOUS
CURRENT RATING [A] AND QUANTITY OF POLES [P] SHOWN NEXT
TO SYMBOL
SWITCH, DISCONNECT, FUSED, LOAD BREAK. FUSE AMPERE
RATING [A] AND FUSE TYPE SHOWN NEXT TO SYMBOL
FUSE, AMPERE RATING [A] AND FUSE TYPE SHOWN NEXT TO
SYMBOL
MOTOR THERMAL OVERLOAD PROTECTOR
INTEGRAL PHOTOELECTRIC CELL AND RELAY (PHOTOCONTROL)
WATTHOUR METER
KIRK KEY
SURGE ARRESTER, VALVE TYPE ARRESTER KV RATING SHOWN
NEXT TO SYMBOL
EQUIPMENT ENCLOSURE
SYMBOL MODIFIERS
DESCRIPTIONSYMBOL
AUDIBLE AND VISUALAV
EXISTINGE
FIXED TEMPERATUREF
GROUND FAULT CIRCUIT INTERRUPTERGFI
NEWN
ITEM OR DEVICE RECESSED INTO MOUNTING SURFACER
RADIO FREQUENCYRF
WEATHERPROOFWP
DEVICE MOUNTED ABOVE COUNTER TOPAC
RECEPTACLE SERVING COMPUTER LOAD.C
GROUNDING LEGEND
DESCRIPTIONSYMBOL
CONDUCTOR, BARE, UON
GROUNDING CONNECTION, COUNTERPOISE TO GROUND ROD.
B
SCHEMATIC CIRCUIT
ELECTRICAL BUSS
CABLE OR WIRE
D
WYE CONNECTEDY
LIGHTING SYMBOLS LEGEND
RACEWAY, RISER UP
RACEWAY, RISER DOWN
THERMOSTAT BY MECHANICAL CONTRACTORT
POWER SYMBOLS LEGEND (CONTINUED)
DESCRIPTIONSYMBOL
RECEPTACLE, DUPLEX, SPECIAL PURPOSE
TELEPHONE RECEPTACLE, WALL MOUNTED
BELL
SPEAKER, CEILING MOUNTED
MICROPHONE, CEILING MOUNTED
SPEAKER CONTROL
SOUND CABINET
AUDIO/VISUAL PROJECTOR
CEILING FAN
CABLE TV OUTLET
MOTOR
SWITCH, MOTOR
HORIZONTAL WIREMOLD
240 VOLT 20 AMP RECEPTACLE
SWITCH, TOGGLE, WALL MOUNTED, 20A., 120/277V RATED (AC
ONLY), DOUBLE-POLE, MOUNT 54" AFF
DESCRIPTIONSYMBOL
LED, PENDANT, CEILING MOUNTED
LED, WALL MOUNTED
LED PENDANT WITH INTEGRAL EMERGENCY BATTERY
CFL/HID/LED FIXTURE, RECESSED CEILING MOUNTED
CFL/HID/LED FIXTURE, WALL MOUNTED
EXIT SIGN, LIGHTED, SURFACE OR PENDANT, CEILING MOUNTED
W/LIGHTED FACE AND DIRECTIONAL ARROW.
EXIT SIGN, LIGHTED, WALL MOUNTED.
EMERGENCY LIGHT, 2 LAMPS, BATTERY POWERED
BRANCH CIRCUIT HOME RUN
CFL/HID/LED FIXTURE, SURFACE OR PENDANT
TRANSFORMER, DRY TYPE
NIGHT LIGHTNL
DATA RECEPTACLE, WALL MOUNTED
TELEPHONE/DATA RECEPTACLE, WALL MOUNTED
SURGE PROTECTION DEVICE
DIGITAL POWER METER
VARIABLE FREQUENCY DRIVER
C
F
C
J
C J
S
S2
S3
S4
SDM
SM
T
S
M
TV
M
VFD
3P 1200A
M
K
SPD
DPM
LIGHTING SWITCHLEG
SITE UTILITIES LEGEND
DESCRIPTIONSYMBOL
DUCT BANK, OVERHEAD PRIMARY
DUCT BANK, OVERHEAD SECONDARY
E
ES
CFL/HID/LED FIXTURE, AREA LIGHT POLE
MANHOLE, ELECTRIC
HANDHOLE, ELECTRIC
E
E
POWER POLE, ELECTRIC
CCTV SECURITY CAMERA
DUCT BANK, UNDERGROUND PRIMARY
DUCT BANK, UNDERGROUND SECONDARY
E
ES
E
ES
E
ES
OS
SWITCH, OCCUPANCY SENSOR, 120V, 1500 WATT.
MOUNT 54" AFFSOS
VERTICAL WIREMOLD
ISOLATED GROUND RECEPTACLE, DUPLEX, ORANGE TYPE. 20A,
120V, GROUNDING 2W+2G RECEPTACLE, NEMA 5-20R
IG
GENERAL NOTES:
(APPLICABLE TO ALL ELECTRICAL SHEETS)
1. ALL WORKS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH
TINKER AFB ELECTRICAL STANDARDS (JAN 2019)
2. EQUIPMENT INTERRUPTING CAPACITIES SPECIFIED IN THE CONTRACT
DOCUMENTS ARE BASED UPON EQUIPMENT CHARACTERISTICS AND
IMPEDANCES SHOWN ON THE DRAWINGS. IF ACTUAL INSTALLED EQUIPMENT
DEVIATES FROM THESE CHARACTERISTICS OR HAS LOWER IMPEDANCES. THE
CONTRACTOR SHALL INCREASE THE INTERRUPTING CAPACITIES OF ALL ITEMS
ON THE LOAD SIDE OF THE DEVIANT EQUIPMENT IN DIRECT PROPORTION TO
THE CHANGED CHARACTERISTICS. INTERRUPTING CAPACITIES SHALL NOT BE
REDUCED TO VALUES LESS THAN THOSE REQUIRED BY THE CONTRACT
DOCUMENTS.
3. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL
EQUIPMENT OR SYSTEMS PENETRATE FIRE RATED WALLS. SEE
ARCHITECTURAL PLANS FOR RATED WALL LOCATIONS.
4. CONTROL WIRING P&ID'S FOR MECHANICAL EQUIPMENT ARE NOT SHOWN ON
THESE SHEETS.
5. RISER AND ONE-LINE DIAGRAMS ARE MEANT TO SHOW ELECTRICAL
RELATIONSHIPS FOR EQUIPMENT, AND THEREFORE MAY NOT INCLUDE ALL
REQUIRED EQUIPMENT DEVICES, AND ACCESSORIES.
OCCUPANCY SENSOR, CEILING MOUNTED.
MANUAL ON/INTEGRAL MANUAL DIMMING
S3
TRANSFORMER
VAULT
Y
XN
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
PL
AN
- D
EM
O
LI
TI
O
N
ED101
BJ
AS
KL
ELECTRICAL PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"
ED101
GENERAL NOTES:
1. THIS DRAWING WAS PREPARED FROM EXISTING AS-BUILTS AND LIMITED
ACCESS FOR FIELD OBSERVATIONS AND VERIFICATIONS. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND UPDATE AS-BUILT DRAWINGS FOR
RECORD.
2. REFER TO ONE-LINE DIAGRAM ON SHEET ED601 FOR ADDITIONAL INFORMATION.
3. ALL DEMO WORK SHALL BE PLANNED IN PHASES TO MINIMIZE IMPACT TO
PRODUCTION. COORDINATE ALL WORK WITH THE FACILITY USER GROUP.
EXISTING
TRANSFORMER '6A'
TO REMAIN
(N.I.C.)
EXISTING PRIMARY
FEEDER/SWITCHES
'6E' TO REMOVE
EXISTING
SWITCHGEAR '6C'
REMOVE SWITCHGEAR '6C' AND '6D' INCLUDING 2000KVA STEP-DOWN
TRANSFORMERS, PRIMARY LOAD BREAK SWITCHES, MAIN/TIE/DISTRIBUTION
SECTIONS, AND TIE BUSWAY. RETAIN PRIMARY 13.8KV CIRCUITS AND
SECONDARY 480V BUSDUCTS FOR RECONNECTION IN NEW WORK.
EXISTING HOIST IS NOT IN CONTRACT. CONTRACTOR SHALL NOT USE THE
EXISTING HOIST FOR THE REMOVAL OR INSTALLATION OF THE NEW
EQUIPMENT IN THE VAULT.
DISCONNECT EXISTING EMCS TRANSMITTERS AND ANTENNAS. REMOVE
EXISTING CONDUIT/CONDUCTORS.
DISCONNECT EXISTING GROUND BUS FROM SWITCHGEAR TO BE REMOVED.
RETAIN FOR RECONNECTION TO NEW SWITCHGEAR.
DISCONNECT AND REMOVE A PORTION OF EXISTING BUSDUCT CONNECTING
TO EXISTING SWITCHGEAR AS INDICATED. REFER TO DEMOLITION ONE-LINE
DIAGRAM FOR ADDITIONAL INFORMATION.
DISCONNECT AND REMOVE ALL INTERIOR LIGHT FIXTURES AND CONTROLS.
REMOVE CONDUCTORS AND CONDUITS BACK TO SWITCH JUNCTION BOXES.
EXISTING HOMERUN CIRCUITS TO REMAIN AND BE REUSED FOR NEW WORK.
REMOVE ABANDONED BUSWAY THROUGH FLOOR SLAB AND PROVIDE AN
ENDCAP TO MAKE SAFE IN THE CEILING BELOW.
KEY NOTES:
EXISTING
TIE BUSWAY
(ABOVE)
EXISTING
SWITCHGEAR '6D'
2 EXISTING HOIST
(N.I.C.)
TRANSFORMER
VAULT 6
EXISTING 1"
GROUND BUS 4
J
(TYP.)
EXISTING
TRANSFORMER '6E'
TO REMAIN
(N.I.C.)
EXISTING PRIMARY
FEEDER/SWITCHES
'6A' TO REMOVE
(TYP.)
(TYP.)
EXISTING BUSDUCT
BELOW (TYP.)
EXISTING
HATCH
EXISTING
HATCH
EXISTING
HATCH
EXISTING
BUSDUCT '6D3'
EXISTING
BUSDUCT '6D1'
EXISTING
BUSDUCT '6D2'
EXISTING
BUSDUCT '6C2'
EXISTING
BUSDUCT '6C3'
(TYP.)
EXISTING
EM-LP-T-6
EXISTING
LP-TR-6
XFMR 6C
UID #9001-
XFMR-1325
SECONDARY SWITCHGEAR 6C
UID #9001-SWG-1326A
XFMR 6D
UID #9001-
XFMR-1327
SECONDARY SWITCHGEAR 6D
UID #9001-SWG-1328
6D-1 1600A
6D-2 1600A
EXISTING 1600A PLUG-IN
BUSWAY '6D1', 3-PH, 3-W
6C-3 1600A
6C-2 1600A
6C-1
SPACE
EXISTING 1600A PLUG-IN
BUSWAY '6C3', 3-PH, 3-W
EXISTING 1600A PLUG-IN
BUSWAY '6C2', 3-PH, 3-W
3000A TIE BUSWAY
480V, 3ɸ, 3W
TIE 6C
3000A
MAIN 6C
3000A
3000A BUS
2000KVA
13.8KV-
480Y/277V
2000KVA
13.8KV-
480Y/277V
MAIN 6D
3000A
TIE 6D
3000A
3000A BUS
EXISTING 1600A PLUG-IN
BUSWAY '6D3', 3-PH, 3-W
EXISTING 1600A PLUG-IN
BUSWAY '6D2', 3-PH, 3-W
6D-3 1600A
2-6 N.C.
1-6 N.O.
6C/D-PRI
1200A
100E 100E
XFMR 6A
CKT 1-6
13.8KV
2000KVA
13.8KV-
480Y/277V
1-6 N.C.
2-6 N.O.
6A/B-PRI
1200A
100E 100E
XFMR 6E
2000KVA
13.8KV-
480Y/277V
1-6 N.C.
2-6 N.O.
6E-PRI
1200A
100E 100E
CKT 2-6
13.8KV
TO MV SWGR
IN POWER
HOUSE BLDG
TO MV SWGR
IN POWER
HOUSE BLDG
TO SWGR 5A
IN VAULT #5
TO SWGR 5D
IN VAULT #5
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
O N
E-
LI
N E
D
IA
G R
AM
- D
EM
O
LI
TI
O N
ED601
BJ
AS
KL
ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION
SCALE: NTS
ED601
GENERAL NOTES:
1. THIS DRAWING WAS PREPARED FROM EXISTING AS-BUILTS AND LIMITED
ACCESS FOR FIELD OBSERVATIONS AND VERIFICATIONS. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND UPDATE AS-BUILT DRAWINGS FOR
RECORD.
2. UNLESS NOTED OTHERWISE, ALL EXISTING EQUIPMENT TO REMAIN. EXISTING
CIRCUIT BREAKERS AS INDICATED ARE 3-POLE.
3. ALL DEMO WORK SHALL BE PLANNED IN PHASES TO MINIMIZE IMPACT TO
PRODUCTION. COORDINATE ALL WORK WITH THE FACILITY USER GROUP.
REMOVE EXISTING SWITCHGEAR, TRANSFORMERS, MAIN/TIE/DISTRIBUTION
SECTIONS AND TIE BUSWAY.
RETAIN PRIMARY FEEDERS FOR RECONNECTION TO NEW SWITCHGEAR.
RETAIN 480V BUSDUCTS FOR RECONNECTION TO NEW SWITCHGEAR
DISTRIBUTION SECTIONS.
DISCONNECT EXISTING TRANSFORMER FROM PRIMARY SWITCHES. REMOVE
ALL WIRES AND ABANDON EQUIPMENT IN PLACE FOR FUTURE REMOVAL.
DISCONNECT AND REMOVE A PORTION OF EXISTING BUSDUCT CONNECTING
TO EXISTING SWITCHGEAR AS INDICATED. REFER TO NEW WORK FOR
ADDITIONAL INFORMATION.
KEY NOTES:
3 (TYP.)
2 22
4 4
5 (TYP.)
Y
XN
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
PL
AN
- N
EW
W O
R K
E-101
BJ
AS
KL
ELECTRICAL PLAN - NEW WORK
SCALE: 1/4" = 1'-0"
E-101
GENERAL NOTES:
1. THIS DRAWING WAS PREPARED FROM EXISTING AS-BUILTS AND LIMITED
ACCESS FOR FIELD OBSERVATIONS AND VERIFICATIONS. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND UPDATE AS-BUILT DRAWINGS FOR
RECORD.
2. COORDINATE PLACEMENT OF ELECTRICAL EQUIPMENT WITH OTHER TRADES
PRIOR TO ROUGH-IN.
3. REFER TO ONE-LINE DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.
4. PROVIDE TEMPORARY POWER TRANSFER AS REQUIRED DURING SWITCHGEAR
REPLACEMENT. COORDINATE CONSTRUCTION PHASING PLAN PRIOR TO
COMMENCING WORK.
5. CONTRACTOR SHALL PROVIDE FIELD LABEL AND AFFIX TO PANELBOARD
ENCLOSURE THE AVAILABLE FAULT CURRENT / DATE OF THE CALCULATION IN
ACCORDANCE WITH NEC 2020, ARTICLE 408. REFER TO SPECIFICATIONS AND
TINKER AFB ELECTRICAL STANDARDS FOR FIELD LABELING REQUIREMENTS.
EXISTING XFMR '6A'
TO REMAIN
EXISTING XFMR ''6E'
TO REMAIN
XFMR
6C
XFMR
6D
CKT 1-6
CKT 2-6
6D MAIN
6D TIE
6C TIE
6C MAIN
SWITCHGEAR '6C'
SWITCHGEAR '6D'
SWITCHGEAR
TIE BUSWAY
(ABOVE)
KEY NOTES:
1EXISTING HOIST
TRANSFORMER
VAULT 6
EXISTING 1"
GROUND BUS
CKT 1-6
CKT 2-6
CKT 1-6
CKT 2-6
PRIMARY NON-FUSED
SWITCHES '6A'
PRIMARY NON-FUSED
SWITCHES '6E'
(TYP.)
(TYP.)
NEW CABLE TRAY
BELOW (TYP.)
EXISTING BUSDUCT
BELOW (TYP.)
EXISTING
HATCH (TYP.)
(TYP.)
A
LP-TR-6:B
A
LP-TR-6:B
A
LP-TR-6:B
A
LP-TR-6:B
A
LP-TR-6:B
A
LP-TR-6:B
A
LP-TR-6:B
EX
LP-TR-6:B
EX
LP-TR-6:B
EXISTING
EM-LP-T-6
EXISTING
LP-TR-6
AE
LP-TR-6:B
AE
LP-TR-6:B
AE
LP-TR-6:B
AE
LP-TR-6:B
EXISTING HOIST IS NOT IN CONTRACT. CONTRACTOR SHALL NOT USE THE
EXISTING HOIST FOR THE REMOVAL OR INSTALLATION OF THE NEW
EQUIPMENT IN THE VAULT.
PROVIDE 1" GROUNDING STRAPS TO BOND AND GROUND SWITCHGEAR TO
EXISTING GROUND BUS. NEW GROUNDING STRAPS SHALL MATCH EXISTING.
1600A CABLE TAPBOX. REFER TO ONE-LINE, E-601, FOR ADDITIONAL
INFORMATION.
PROVIDE 18" CABLE TRAY, 9-500KCMIL, 1-#4/0EGC. REFER TO SHEET E-501 FOR
ADDITIONAL INFORMATION.
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
D
ET
AI
LS
E-501
BJ
AS
KL
GENERAL NOTES:
1. COORDINATE PLACEMENT OF ELECTRICAL EQUIPMENT WITH OTHER TRADES
PRIOR TO ROUGH-IN.
2. REFER TO ONE-LINE DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.
TYPICAL DETAIL - 1600A FEEDER CONSTRUCTION
SCALE: NTS
TYPICAL DETAIL - 1600A BUSWAY SUPPORT
SCALE: NTS
TYPICAL DETAIL - 3000A TIE BUS SUPPORT
SCALE: NTS
TYPICAL DETAIL - SEISMIC RESTRAINT
SCALE: NTS
TYPICAL DETAIL - CABLE TRAY GROUND
SCALE: NTS
/2 3/
R
EV
. 1
EXISTING 1600A PLUG-IN
BUSWAY '6D1', 3-PH, 3-W
3000A TIE BUSWAY
480V, 3ɸ, 3W
3000A BUS
2000KVA
13.8KV-
480Y/277V
2000KVA
13.8KV-
480Y/277V
3000A BUS
EXISTING 1600A PLUG-IN
BUSWAY '6D3', 3-PH, 3-W
EXISTING 1600A PLUG-IN
BUSWAY '6D2', 3-PH, 3-W
6C/D-PRI
600A
100E 100E
K
XFMR 6C
UID #9001-
XFMR-1325
SECONDARY SWITCHGEAR 6C
UID #9001-SWG-1326A
XFMR 6D
UID #9001-
XFMR-1327
SECONDARY SWITCHGEAR 6D
UID #9001-SWG-1328
6D-1 1600A
6D-2 1600A
6C-3 1600A
6C-2 1600A
6C-1
SPACE
EXISTING 1600A PLUG-IN
BUSWAY '6C3', 3-PH, 3-W
EXISTING 1600A PLUG-IN
BUSWAY '6C2', 3-PH, 3-W
TIE 6C
3000A
MAIN 6D
3000A
TIE 6D
3000A
6D-3 1600A
K K
DPMDPM
DPM DPM DPM DPM DPM
N.O. N.O.N.C.
PRIMARY
NON-FUSED
SWITCHES
6A
1-6 N.C.
2-6 N.C.
6A/B-PRI
600A
1-6 N.C.
2-6 N.C.
6E-PRI
600A
2-6 N.O.
1-6 N.C.
BUSS
SPACE
BUSS
SPACE
CKT 1-6
13.8KV
CKT 2-6
13.8KV
TO MV SWGR
IN POWER
HOUSE BLDG
TO MV SWGR
IN POWER
HOUSE BLDG
TO SWGR 5A
IN VAULT #5
TO SWGR 5D
IN VAULT #5
PRIMARY
NON-FUSED
SWITCHES
6E
BUSS
SPACE
BUSS
SPACE
SPD
K
MAIN 6C
3000A N.C.
SPD
60A60A
LSIG LSIG LSIG LSIG
LSIGLSIGLSIGLSIGLSIG
UNIT-SUBSTATION
GROUND BUS
GROUNDING STRAP
BUILDING STRUCTURAL STEEL
EXOTHERMIC WELD
#4/0AWG
#4/0AWG
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
O N
E-
LI
N E
D
IA
G R
AM
- N
EW
W
O R
K
E-601
BJ
AS
KL
ELECTRICAL ONE-LINE DIAGRAM - NEW WORK
SCALE: NTS
E-601
GENERAL NOTES:
1. THIS DRAWING WAS PREPARED FROM EXISTING AS-BUILTS AND LIMITED
ACCESS FOR FIELD OBSERVATIONS AND VERIFICATIONS. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND UPDATE AS-BUILT DRAWINGS FOR
RECORD.
2. UNLESS NOTED OTHERWISE, ALL EXISTING EQUIPMENT TO REMAIN. EXISTING
CIRCUIT BREAKERS AS INDICATED ARE 3-POLE.
3. CONTRACTOR SHALL VERIFY ALL UPSTREAM OVERCURRENT PROTECTION AND
SETTINGS FOR SHORT FAULT CURRENT CALCULATION AND ARC FLASH
LABELING. PROVIDE APPROPRIATE ARC-FLASH LABELING PER ANALYSIS.
4. PROVIDE TEMPORARY POWER TRANSFER AS REQUIRED DURING SWITCHGEAR
REPLACEMENT. COORDINATE CONSTRUCTION PHASING PLAN PRIOR TO
COMMENCING WORK.
5. CONTRACTOR SHALL PROVIDE FIELD LABEL AND AFFIX TO PANELBOARD
ENCLOSURE THE AVAILABLE FAULT CURRENT / DATE OF THE CALCULATION IN
ACCORDANCE WITH NEC 2020, ARTICLE 408. REFER TO SPECIFICATIONS AND
TINKER AFB ELECTRICAL STANDARDS FOR FIELD LABELING REQUIREMENTS.
PROVIDE SQUARE D POWER ZONE SWITCHGEAR WITH REMOTE RACKING,
KIRK-KEY SWITCHING INTERLOCK, FORCED FAN COOLING, TEMPERATURE
MONITORING WITH LOCAL ALARM, AND REMOTE ALARM CAPABILITIES. ALL
INTERNAL WIRING TO BE DERIVED FROM INTEGRAL CPTs SO NO EXTERNAL
CIRCUITS ARE REQUIRED FOR OPERATION.
CONNECT EXISTING MV FEEDERS TO NEW SWITCHGEAR PRIMARY SECTIONS.
CONNECT EXISTING 480V BUSDUCT TO CABLE TAP BOX AND EXTEND AS
NEEDED. BUSDUCT EXTENSION SHALL BE SQUARE D AND COMPATIBLE WITH
EXISTING.
PROVIDE T-FITTING BUSDUCT AS INDICATED FOR FUTURE
EXPANSION/CONNECTIONS.
PROVIDE MEDIUM VOLTAGE RATED CABLE TO MATCH WITH EXISTING. PROVIDE
PULL BOX AS REQUIRED FOR RECONNECTION TO EXISTING ONE.
PROVIDE 480V, 3PH, 3W, 1600A BUSDUCT TAPPED TO EXISTING BUSDUCT AND
TERMINATE IN SWITCHGEAR. REFER TO DETAILS ON SHEET E-501 FOR
ADDITIONAL INFORMATION.
IDENTIFY SWITCHGEAR GEC TEST POINT PER SECTION 3.1.4 C 1 OF THE TAFB
ELECTRICAL STANDARDS IAW AFI 32-1065.
KEY NOTES:
(TYP)
(TYP)
(TYP)
(TYP)
#3/0
GEC
#3/0
GEC
7 7
GROUNDING RISER DETAIL
SCALE: NTS
E-601
1600A
TAPBOX
(TYP)
ELECTRICAL ARC FLASH STICKER DETAIL
SCALE: NTS
E-601
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC
FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT CAN BE MODIFIED PROVIDED THAT THE INFORMATION REQUIRED BY
UFC 3-501-01 IS INCLUDED.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE
WEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.
A.THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY > NAVFAC CADD
RESOURCES > NAVFAC CADD DETAILS.
B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:
HTTP://WWW.WBDG.ORG/CCB/BROWSE/CAT.PHP?C=232
6. THE CONTRACTOR SHALL UNDERTAKE FAULT CURRENT CALCULATIONS (PREPARED BY A
QUALIFIED PROFESSIONAL ENGINEER) AND ARC FLASH ANALYSIS PERFORMED USING "EASY
POWER" SOFTWARE AND THE ANALYSIS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR
TO EQUIPMENT SELECTION. SUBMIT TO 72ABW/CENMP.
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
EL
EC
TR
IC
AL
SC
H
ED
U
LE
S
E602
BJ
AS
KL
TRANSFORMER
VAULT
F
F
75 CD
E
E
75 CD
E E
EE
Y
XN
XS
AIR FORCE MATERIEL COMMAND
72 ABW CIVIL ENGINEER DIRECTORATE
TINKER AFB, OK
TI
N
KE
R
A
IR
F O
R C
E
BA
SE
, O
KL
AH
O M
A
PR
O
JE
C
T
IN
FO
R
M
AT
IO
N
R
EV
IS
IO
N S
M
AR
K
D
ES
IG
N
G R
O U
P:
D R
AW
N
B Y:
C H
EC
KE
D B
Y:
D
ES
IG
N
ED
B
Y:
D
AT
E D
ES
C
R
IP
TI
O
N
1 2 3 4 5
E
D
C
B
A
M
AN
AG
EM
EN
T
IN
FO
R M
AT
IO
N
1 2 3 4 5
E
D
C
B
A
IS
SU
E D
AT
E:
SHEET NUMBER
SH
EE
T
TI
TL
E
D
ES
IG
N
F
IL
E
LO
C
AT
IO
N
W W
YK
R
EP
AI
R
T R
AN
SF
O R
M
ER
VA
U
LT
, B
D
EC
H D
R
FI
R E
AL
AR
M
D
EM
O
LI
TI
O
N A
N D
N
EW
W O
R K
PL
AN
F-101
D E
JR
M JM
FIRE ALARM - DEMOLITION AND NEW WORK PLAN
SCALE: 1/4" = 1'-0"
F-101
FIRE ALARM GENERAL NOTES:
1. WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 70, NFPA 72,
APPLICABLE ETL'S, TINKER ELECTRICAL STANDARDS AND UFC 3-600-01.
THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE GENERAL
ARRANGEMENTS OF SYSTEMS AND WORK, BUT DO NOT INCLUDE ALL
INTERCONNECTIONS BETWEEN OTHER SYSTEMS. PROVIDE CONDUIT,
J-BOXES, BACK BOXES, AND CABLE AS REQUIRED.
2. COORDINATE WORK WITH OTHER TRADES. FAILURE TO PROVIDE SUCH
COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE CAUSE
FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY RESULT
IN REJECTION OF THE WORK.
3. THE BUILDING'S FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL AT ALL
TIMES. SUPERVISE ALL FIRE PROTECTION IMPAIRMENTS IN ACCORDANCE
WITH UFC 3-601-02.
4. PROVIDE MATERIALS, BEARING LABELS OR MARKING INDICATING THIRD
PARTY TESTING AND APPROVAL, SUITABLE FOR THE APPLICATION
INTENDED.
5. SUPPORT CONDUIT AND BACK BOXES BY MEANS OF ANCHORS, RODS,
HANGERS, ETC., TO MAINTAIN ALIGNMENT AND PREVENT MOVEMENT.
6. IDENTIFY CONDUCTORS AT EACH JUNCTION BOX, OUTLET BOX, CABINET,
PULL BOX, ETC., WITH VINYL HEAT SHRINK TAGS INDICATING PANEL AND
CIRCUIT NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER
APPROPRIATE INFORMATION.
7. PERFORM WORK ON DE-ENERGIZED SYSTEMS ONLY TO PREVENT
PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE.
8. ALL NEW FIRE ALARM SYSTEM CONDUIT SHALL BE FACTORY PAINTED RED.
FIRE ALARM SYMBOLS LEGEND
MANUAL STATION, FIRE ALARMF
FIRE ALARM AUDIBLE/VISBLE COMBO WALL, CLEAR LENS,
SELECTABLE CD
E SUBSCRIPT DENOTES EXISTING DEVICE TO REMAIN.
DEMOLITION KEY NOTES:
REMOVE THE EXISTING WALL MOUNTED FIRE ALARM
NOTIFICATION DEVICES TO ACCOMMODATE
CONSTRUCTION. DEMO EXISTING RACEWAY SERVING
THE NOTIFICATION DEVICES. WHERE EXISTING RACEWAY
IS INSTALLED WITHIN THE ELECTRICAL WORKING
SPACES, AS DEFINED BY NEC 110.26 AND 110.30,
CONDUIT AND CABLE SHALL ALSO BE REMOVED.
FIRE ALARM DEMOLITION NOTES:
1. CONTRACT DOCUMENTS WERE PREPARED FROM FIELD SURVEYS. THEY
ARE NOT INTENDED TO DEPICT UNFORESEEN CONDITIONS THAT MAY
ADVERSELY AFFECT DEMOLITION OR INSTALLATION. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO STARTING ANY
WORK.
2. COORDINATE DEMOLITION WITH NEW WORK. IF UNDOCUMENTED
CONDITIONS EXIST, CONTACT THE CONTRACTING OFFICER BEFORE
PROCEEDING.
KEY NOTES:
1 INSTALL NEW FIRE ALARM AUDIBLE/VISIBLE DEVICE AND TIE
INTO THE EXISTING FIRE ALARM SYSTEM NOTIFICATION
CIRCUIT(S).
FIRE ALARM RACEWAY SHALL NOT BE ALLOWED TO REMAIN OR
BE INSTALLED WITHIN ELECTRICAL WORKING SPACES, AS
DEFINED BY NEC 110.26 AND 110.30. RE-USE AND RECONFIGURE
EXISTING FIRE ALARM RACEWAY AS NECESSARY TO REMOVE
FROM ELECTRICAL WORKING SPACES.
REMOVE AND SAFEGUARD SMOKE DETECTORS AS NECESSARY
TO ACCOMMODATE WORK WITHIN THE VAULT. RE-INSTALL
SMOKE DETECTORS UPON COMPLETION OF THE WORK.
SMOKE DETECTOR
3 3
| GENERAL |
| G-001 - GENERAL SHEET INDEX VICINITY MAP AND BUILDING KEY PLAN |
| ARCHITECTURE |
| A-101 - ARCHITECTURAL FLOOR AND ROOF PLANS, ELEVATIONS IMAGES |
| STRUCTURAL |
| S-001 - STRUCTURAL GENERAL NOTES |
| S-101 - STRUCTURAL PLAN - NEW WORK |
| ELECTRICAL |
| E-001 - ELECTRICAL LEGEND, SYMBOLS & ABBREVIATIONS |
| ED101 - ELECTRICAL PLAN - DEMOLITION |
| ED601 - ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION |
| E-101 - ELECTRICAL PLAN - NEW WORK |
| E-501 - ELECTRICAL DETAILS |
| E-601 - ELECTRICAL ONE-LINE DIAGRAM - NEW WORK |
| E602 - ELECTRICAL SCHEDULES |
| FIRE PROTECTION |
| F-101 - FIRE ALARM - DEMOLITION AND NEW WORK PLAN |
File details come from the government source that posted it. Updated .