This document appears to be a features and specifications sheet for the RELOC-Ready Luminaire (RRL) Universal Fixture Connector, which is designed to enable a simple and consistent factory-installed option across all ABL luminaire brands. The RRL connector is compliant with various electrical and safety standards and can be used with the OnePass system. It provides a touch-safe design and wiping contact allowing for safe disconnect under load. The document outlines the electrical specifications, system features, and wiring instructions for different voltage configurations and control applications.

The related federal contract opportunity is for a Blanket Purchase Agreement (BPA) to establish a single award contract for LED light fixtures, modular wiring, lighting controls components, and other associated materials for the FBI CJIS Division Campus in Clarksburg, West Virginia. This is an open market, brand name or equal, simplified acquisition set aside 100% for small businesses. The FBI is requesting pricing and lead time information for the items listed in the attached Materials List, which includes the RRL connector as an option. The award will be based on a best value determination, with technical acceptability being the most important factor, followed by price and delivery/lead time. Questions are due by June 24, 2024, and quotes are due by July 3, 2024.

View the file

Other files

File Type Posted
RFQ 15F06724Q0000408 BPA LED Lighting AMEND 001.pdf PDF
24-005_LED Lighting BPA Price Template AMEND 001.xlsx XLSX spreadsheet
17_23. RELOC OnePass Cables - Cable - OC1 Series (Basic of Design).pdf PDF
07. nLight Controls - Eclypse Controller (Basis of Design).pdf PDF
06. Oracle Lighting - 2x2 OAT1 LED Fixture (Basis of Design).pdf PDF
18_24. RELOC OnePass Cables_Fixture Cable_OFC Series (Basic of Design).pdf PDF
24-005_LED Lighting BPA Price Template.xlsx XLSX spreadsheet
20. RELOC OnePass System Drops - Drop Cable (Basis of Design).pdf PDF
16_ 22. RELOC OnePass Convertor - OC Series (Basis of Design).pdf PDF
19_25. RELOC OnePass Splitter Splice_OSS Series (Basis of Design).pdf PDF
10. nLight Controls - Wallpod On & Off Control (Basis of Design).pdf PDF
14. Krueger Plastic Frame Adapters_Ceiling Adapters.pdf PDF
17A_8A. RELOC External Connector _ RCAT5.pdf PDF
01thru03. Lithonia BLT4R -1x4 Relight LED Fixture (Basis of Design).pdf PDF
09. nLight Controls - Occupancy Sensor (Basis of Design).pdf PDF
11. nLight Controls - Wallpod Scene Control (Basis of Design).pdf PDF
1x4 Retrofit Light Fixture DWG for Photometric-Model.pdf PDF
08. nLight Controls - 8-Port Bridge (Basis of Design).pdf PDF
SF1449 15F6724Q0000408.pdf PDF
RFQ 15F06724Q0000408 BPA LED Lighting.docx DOCX document
2x2 Light Fixture DWG for Photometric-Model.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEATURES & SPECIFICATIONS

INTENDED USE

The RELOC®-Ready Luminaire (RRL) connectors enables a simple and consistent factory installed option across all ABL luminaire brands. When ordered on a RELOC fixture cable (OFC), fixture cord drops (OCS or OCU) and fixture drop cables (OD); the line side of the connector will be factory attached to all the wire leads except for the ground wire. When ordered with the luminaire, the load side of the connector will be prewired based on the appropriate wiring instruction selection.

ELECTRICAL

• 18 AWG solid wire only; stranded not available.

• Tin-bonded 18 AWG (≤16 strand) acceptable.

• Current Interruption 10 cycles.

SYSTEM FEATURES

• RRL connector used with the OnePass system.

• Load side of connector factory attached to luminaire. Refer to luminaire spec sheet for ordering information.

• 4-pole mating connector with push-in terminations allows for simple installation.

• Touch-safe design on both halves, meets UL/CSA requirement.

• Wiping contact design allows safe disconnect under load.

LISTINGS

• UL 2459

• CSA- C22.2 NO. 2459

• NEC 2008 410.130(G) Compliant

• CEC 30-308(4) Compliant

Catalog Number

Notes Type

One Lithonia Way Conyers, GA 30012 Phone: 800-241-4750 www.relocwiring.com techsupportreloc@acuitybrands.com © 2013-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/29/18

RELOC®-Ready Luminaire

RRL

Universal Fixture Connector

RRL Load Side shown

OD with RRL line side shown OFC with RRL line side shown

RRL

Series Wiring Instructions

A Ballast/driver wired to pin position #1 (120V,277V,347V - Phase A) Ballast/driver wired to pin position #1 & #4 (208V, 240V, 480V - Phase A)

B Ballast/driver wired to pin position #2 (120V,277V,347V - Phase B) Ballast/driver wired to pin position #2 & #4 (208V, 240V, 480V - Phase B)

C Ballast/driver wired to pin position #3 ( 120V,277V,347V - Phase C ) AB Outboard ballast/driver wired to pin position #1 (120V,277V,347V - Phase A) 2

Inboard ballast/driver wired to pin position #2 (120V, 277V, 347V - Phase B) AE Ballast/driver wired to pin position #1 (120V,277V,347V - Phase A)

Emergency ballast/driver wired to pin position #2 (120V,277V,347V - Phase B) 3

ABE Ballast/driver wired to pin position #1 (120V,277V,347V - Phase A) 2

Ballast/driver wired to pin position #2 (120V,277V,347V - Phase B) Emergency ballast/driver wired to pin position #3 (120V,277V,347V - Phase C) 3

C12S Ballast/driver wired to pin position #1 (120V,277V,347V - Phase A) Low voltage wire (positive/purple) (data1) wired to pin position #2 Low voltage wire (common/gray) (data2) wired to pin position #3 4

Ballast/driver wired to pin position #1 & #2 (208V, 240V, 480V - Phase A) 4

Low voltage wire (positive/purple) (data1) wired to pin position #2 Low voltage wire (common/gray) (data2) wired to pin position #3 4

22N Ballast/driver wired to pin position #2 and pin position #3 (120V,277V,347V - Phase B) 122N Ballast/driver wired to pin position #1 and #4 (120V,277V,347V - Phase A)

Ballast/driver wired to pin position #2 and #3 (120V,277V,347V - Phase B)

RRL1

• RoHS Compliant

WARRANTY

• 5-year limited warranty. Complete warranty terms located at:

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Actual performance may differ as a result of end-user environment and application.

Note: Specifications subject to change without notice.

Load Side RELOC®-Ready Luminaire

NOTES

1. Not available with IBG Haleon sensor options.

2. Not available with LED luminaries. Only compatible with products that are wired for outboard/inboard control.

3. AE and ABE Commercial fixtures should disconnect the TSPL before unplugging the RRL so it does not go into discharge mode.

4. RRLC12S option is to be used with the OnePass OCU, OCS, OD, OFC and OD for 0-24V integrated single-circuit or 0-10V low voltage controls applications. Not available with integral dimming sensors.

Fixture Ordering Example:

IBG 15000LM SEF AFL GND 277 GZ10

40K 80CRI PS30250 RRLAE BPK DWH

FIXTURE ORDERING LOGIC

For shortest lead times, configure product using bolded options.

Line Side RELOC®

Series

RRL

RELOC® Ordering Example:

OFC 277 12/2G 13 RRL G

OCS 480 10 RRL

OD 277 12/3G 15 RRL

RRL

NOTE

1. All hot conductors and neutral wires present in RELOC cable, drop cable.

2. G option required for OFC fixture cables.

3. Ground wire will include poke-in wire connector.

4. Visit RELOC® to order with RELOC systems.

http://www.relocwiring.com http://www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx https://reloc.acuitybrands.com/

RRL RELOC®-Ready Luminaire

RRL

Position # Function Standard Wiring Applications

120V,277V,347V

1 Hot 1 X X

2 Hot 2 X X

3 Hot 3 X

4 Neutral X X X X

Wiring Instruction RRLA RRLB RRLC RRLAB

DIMENSIONS

Dimensions are shown in inches (millimeters)

LOAD SIDE

Connects to Fixture. Installed on fixture at factory or by customer.

LINE SIDE

Connects to RELOC Fixture Cable.

Installed on Reloc cable at the factory.

WIRING INSTRUCTIONS

Pin position and conductor functions by voltage.

Position # Function Normal and Emergency

Applications 120V, 277V, 347V

1 Hot 1 X X

2 Hot 2 X X

3 Hot 3 X

4 Neutral X X

Wiring Instruction RRLAE RRLABE

Position # Function Class I Class II Wiring Ap-plications 120V, 277V

1 Hot 1 X

2 Data 1, Positive ( + ) X

3 Data 2, Common ( - ) X

4 Neutral X

Wiring Instruction RRLC12S

Position # Function Two Neutral Applications

120V, 277V, 347V

1 Hot 1 X

2 Hot 2 X X

3 Neutral 2 X X

4 Neutral 1 X

Wiring Instruction RRL22N RRL122N

Position # Function Special Industrial Voltage

Applications 208V, 240V, 480V

1 Hot 1 X

2 Hot 2 X

3 Hot 3

4 Hot 4 X X

Wiring Instruction RRLA RRLB

Position # Function Class I Class II Wiring

Applications 208V, 240V, 480V

1 Hot 1 X

2 Data 1, Positive ( + ) X

3 Data 2, Common ( - ) X

4 Hot 2 X

Wiring Instruction RRLC12S

One Lithonia Way Conyers, GA 30012 Phone: 800-241-4750 www.relocwiring.com techsupportreloc@acuitybrands.com © 2013-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/29/18 http://www.relocwiring.com