This document is a product specification for the nPODM-xS series wallpod scene control devices manufactured by Acuity Brands. It provides an overview of the features, ordering information, installation instructions, and technical specifications for these lighting control products.

The related federal contract opportunity is a solicitation for a blanket purchase agreement (BPA) to provide LED light fixtures, modular wiring, lighting controls components, and other associated materials to the Federal Bureau of Investigation (FBI) for their CJIS Division campus in Clarksburg, West Virginia. The agency is seeking a small business vendor to provide these products on a best value basis, with technical acceptability being the most important factor, followed by price and delivery time. The BPA will have a period of performance of up to 12 months, with individual delivery orders not to exceed $250,000. Vendors are required to complete the provided pricing template with unit prices and lead times.

View the file

Other files

File Type Posted
RFQ 15F06724Q0000408 BPA LED Lighting AMEND 001.pdf PDF
24-005_LED Lighting BPA Price Template AMEND 001.xlsx XLSX spreadsheet
17_23. RELOC OnePass Cables - Cable - OC1 Series (Basic of Design).pdf PDF
07. nLight Controls - Eclypse Controller (Basis of Design).pdf PDF
15_21. RELOC RRL Universal Fixture Connector (Basis of Design).pdf PDF
06. Oracle Lighting - 2x2 OAT1 LED Fixture (Basis of Design).pdf PDF
18_24. RELOC OnePass Cables_Fixture Cable_OFC Series (Basic of Design).pdf PDF
24-005_LED Lighting BPA Price Template.xlsx XLSX spreadsheet
20. RELOC OnePass System Drops - Drop Cable (Basis of Design).pdf PDF
16_ 22. RELOC OnePass Convertor - OC Series (Basis of Design).pdf PDF
19_25. RELOC OnePass Splitter Splice_OSS Series (Basis of Design).pdf PDF
10. nLight Controls - Wallpod On & Off Control (Basis of Design).pdf PDF
14. Krueger Plastic Frame Adapters_Ceiling Adapters.pdf PDF
17A_8A. RELOC External Connector _ RCAT5.pdf PDF
01thru03. Lithonia BLT4R -1x4 Relight LED Fixture (Basis of Design).pdf PDF
09. nLight Controls - Occupancy Sensor (Basis of Design).pdf PDF
1x4 Retrofit Light Fixture DWG for Photometric-Model.pdf PDF
08. nLight Controls - 8-Port Bridge (Basis of Design).pdf PDF
SF1449 15F6724Q0000408.pdf PDF
RFQ 15F06724Q0000408 BPA LED Lighting.docx DOCX document
2x2 Light Fixture DWG for Photometric-Model.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight © 2014-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/24/20 nPODM-xS nPODM Example: nPODM 1SB WH

Series # of Scenes Dimming Control Dynamic Color Temp/Humidity nPODM 1SB 1 Scene control (2 buttons) 2S 2 Scene control (2 buttons) 2SB 2 Scene control (4 buttons) 4S 4 Scene control (4 buttons) 4SB 4 Scene control (8 buttons)

[blank] Standard DX1 On/off + raise/ lower control

[blank] Standard EDUTW2 Tunable White GRSC3 Grayscale COLOR3 Color control

WH White IV Ivory GY Gray AL Almond BK Black RD Red

[blank] Standard LT Low temp

OVERVIEW

The nPODM xS Series WallPods are single gang nLight-enabled devices that provide one, two, and four scene control. These units provide a convenient method of selecting a custom lighting control scene for the room in which it is installed, or requesting a global profile scene be run across several remote zones.

By default, however, the buttons of an nPODM xS are configured as on/off toggle switches. Scenes are programmed to these units utilizing available SensorView software.

The nPODM xS has soft-click push-buttons with a green LED indicator for each button. These button are field replaceable and can be custom engraved. Two RJ-45 connectors allow the nPODM xS to be daisy-chain wired with CAT-5e cabling to other nLight network devices.

The nPODM xSB offers individual on/off buttons for each scene. Pressing the “on” button will reset the expiration time of a scene back to the original programmed time.* *In order to utilize a blink warning, system gateway and additional programming is required.

nPODM xSB WallPods are not recommended for use with “preset” style scenes.

FEATURES

• Communicates w/ nLight network

• Remotely configurable/upgradable

• Runs locally stored scenes or global scenes (stored on gateway)

• Capable of Programming 4 Different Scene Types

• Local “Profile” Scene — Modifies the operational configuration of up to 80 devices in the local zone.

Stopping scene will revert devices to default settings.

• Local “Preset” Scene — Modifies on/off/dim levels for up to 16 local switch groups.

Exit scene through additional “preset” scene or WallPod control.

• Global “Profile” Scene — Modifies the operational configuration of any devices on the system.

Stopping scene will revert devices to default settings. Scene is stored on the system Gateway, model nGWY2 KIT.

• Global “Preset” Scene — Modifies on/off/dim levels for up to 128 global switch groups.

Exit scene through additional “preset” scene or WallPod control.

• Expiration timer programmable to each scene

• Programmable to initiate occ. sensor time delay sweep

• "Dynamic" options for custom button names when pairing with Acuity Brands nTUNE fixtures

ORDERING INFORMATION

Catalog Number: Date: Project:

nPODM 1SB nPODM 2S(B) nPODM 4S(B)

Notes

1. Available with 2S and 4S versions

2. Available with 4S and 4S DX versions

3. Available with 4S DX version only

Warranty Five-year limited warranty. Complete warranty terms located at:

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

http://www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODM-xS

OVERVIEW

DEFAULT SETTINGS (example) All lights on, dimming photocell enabled Sensors at 10 minute time delay & in AUTO ON/AUTO OFF mode

1 MOVIE MODE

Button in Local Scene mode

Front rows off, middle rows 75% dim, rear rows 50% dim Sensor at 20 minute time delay Sensor LEDs off Photocell Disabled

2 PRESENTER MODE

Button in Local Scene mode

Podium lights on All other rows 60% dim Photocell Disabled

3 ACCENT LIGHTS CONTROL

Button in WallPod

Press to toggle on/off

4 PARKING LOT

Button in Remote Scene mode

Runs profile stored on Gateway to turn on parking lot lights

Below is an outline of example scene configurations for the nPODM 4S. When no local scene is selected, the user configurable device default settings are active.

GRAY

SCALE

FAST

ON

OFF

WHITE

SLOW

nPODM 4S DX GRSC

Custom engraved lettering for WH, IV, AL, and GY units can be specified and ordered at:

http://www.acuitybrands.com/-/media/Files/Acuity/Products/Controls/nLight/NGRAVE%20110%20pdf.pdf?la=en

WHITE COLOR

COLOR

COLOR

ON

OFF

nPODM 4S DX COLORnPODM 4S EDUTW

GENERAL

READING

TESTING

ENERGY

nPODM 4S DX

EDUTW

ON

OFF

GENL READ

TEST ENRGY

Dynamic wallpods below are paired with Acuity Brands nTUNE fixtures for out-of-box operation.

Reference fixture cut sheets for additional details.

nPODM 4SnPODM 2S nPODM 4S DX nPODM 4L DX

SCENE

SCENE

SCENE

SCENE

ON

OFF

LEVEL

LEVEL

LEVEL

LEVEL

ON

OFF

nPODM 4S DXnPODM 4SBnPODM 1SB nPODM 2SB nPODM 2S DX

INSTALLATION

• Mount WallPod using holes that align with standard single gang switch box or low voltage ring

• Access RJ-45 ports by sliding plastic guard up

• Insert CAT-5e cable(s), T568B wiring convention recommended

• Slide guard back onto metal strap

• Interconnect unit with other nLight devices in lighting zone using CAT-5e cables

• Once power is received via CAT-5e connection, all devices in zone will automatically begin functioning together according to respective device’s defaults

SLID

E

TO RJ-45 PORT

TO RJ-45 PORT

CAT-5

CAT-5

Attention! Only use non-booted CAT5e cables.

http://www.acuitybrands.com/-/media/Files/Acuity/Products/Controls/nLight/NGRAVE%20110%20pdf.pdf?la=en

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight nPODM-xS

Electrical Input Ratings 15-24VDC, 5mA, Class 2 (nLight network power)

Mechanical Dimensions 2.74”H x 1.68”W x 1.63”D (70mm x 43mm x 41mm) - does not include ground strap

Mounting Single-Gang Box or Low Voltage Ring Connection Type RJ-45 nLight Network Ports (2)

Environmental Warrantied Operating Temperature 32°F to 140°F (0°C to 60°C)

Relative Humidity Up to 90%, Non-Condensing Standards/ Ratings Energy Management Equipment, UL916 (E167435)

RoHS

Security Complies with California Civil Code Title 1.81.26, Security of Connected Devices, approved under Senate Bill No. 327 (2018)

SPECIFICATIONS

Text Field 1:
Text Field 2:
Text Field 3:
Text Field 4:
Text Field 5:
Text Field 6:
Text Field 7:
Text Field 8:
Text Field 9:

File details come from the government source that posted it. Updated .