This document provides the government's supplemental response to questions regarding measurement and payment for deep soil mixing on the Conconully Dam CAS Phase II Seismic Modifications project. The cubic yard quantity for the test sections is based solely on the area and depth of soil treatment, with each 20 by 20 foot test section comprising 400 square feet and 62 feet of depth, totaling 1,800 cubic yards for both sections. Contractors should reasonably fill the entire test section area with deep soil mixed columns, with overlapped columns outside and inside the test sections excluded from measurement. While a column layout detail is provided, contractors may use different patterns and the number of columns installed will depend on individual column diameter to reasonably fill the 400 square foot area. If column diameter results in a significantly larger construction area than the test section, the number of columns will be adjusted to provide the closest area to the test section for cubic yard adjustment purposes.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question: Regarding measurement and payment for Section 31 32 35 Deep Soil Mixing, how is the cubic yard of DSM measured? Would the Grouted Column Treatment Details figure shown on Sheet 21-D-60006 constitute full payment of the 1,800 cyd quantity published within the Section B Price Schedule?
Government Supplemental Response: The cubic yard quantity calculated for the test sections is based solely on the area of the test section and the depth of the soil treatment. Each test section is 20 feet by 20 feet in area (400 square feet). The depth of treatment is from excavated elevation 2242 feet to bottom of treatment elevation 2180 (62 feet total depth). Thus, each test section volume of soil treated is 400 square feet by 62 feet depth, 24,800 cubic feet and 900 cubic yards. The total volume of both test sections is then 1,800 cubic yards. Contractor’s should come reasonably close to constructing deep soil mixed columns to the full extent of each test section area. Overlapped columns outside and inside the test section are not included in the cubic yard measurement.
With respect to the grouted column treatment detail shown on Sheet 21-D-60006. This is primarily a detail of the minimum overlap for each deep soil mixed column within one possible column layout pattern. Contractors may use different column installation layouts as approved in the submittals for construction. Additionally, the detail on Sheet 21-D-60006 is not to scale. The number of columns installed to fill the 400 square feet test section will be dependent on the individual column diameter (additional columns of smaller diameter will be needed to reasonably fill the 400 square feet test section area and fewer columns of larger diameter may be needed to reasonably fill the 400 square feet test section area). Contractors are encouraged to use the largest possible column diameter (and the fewest number of columns) in each test section. In the event that the column diameter results in a column construction area significantly larger than the test section area (for instance, 12-foot diameter columns are installed which would result in 452 square feet when installing 4 columns), the number of columns will be adjusted to provide the square foot area closest to the test section area and the additional column area will be used (in conjunction with the treatment depth and subtracting the column overlap of 5 percent) to adjust the cubic yards quantity.