Attachment_4_264113_-_LIGHTNING_PROTECTION_FOR_STRUCTURES_(1)_0001.pdf

PDF 56 KB Posted

Attached to
SEKI REHABILITATE ASH MOUNTAIN HELIBASE
Solicitation number
140P8625R0005
Issued by

About this file

This document is a technical specification section (Section 26 41 13) for Lightning Protection for Structures, specifically prepared for the Sequoia and Kings Canyon National Parks (SEKI) project. The specification provides detailed requirements for installing a comprehensive lightning protection system, including components, installation methods, and quality assurance standards. Key technical requirements include using UL 96 and NFPA 780 compliant components from approved manufacturers such as Automatic Lightning Protection, ERICO International Corporation, and Harger Lightning Protection, with specified materials including copper roof-mounting and stack-mounting air terminals.

The specification mandates precise installation protocols, such as concealing conductors, using exothermic-welded connections, bonding vertical metal bodies over 60 feet long, and implementing a counterpoise grounding system. Installation must be performed by a certified Lightning Protection Institute (LPI) Master Installer/Designer, with mandatory inspections to obtain UL Master Label and LPI certification. Corrosion protection is also emphasized, requiring careful material selection and protective coatings to prevent electrolytic deterioration and ensure long-term system reliability.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEKI - 265122 26 41 13 - 1

051121 LIGHTNING PROTECTION FOR STRUCTURES

SECTION 26 41 13 – LIGHTNING PROTECTION FOR STRUCTURES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes lightning protection for buildings.

1.3 DEFINITIONS

A. LPI: Lightning Protection Institute.

B. NRTL: National recognized testing laboratory.

1.4 SUBMITTALS

A. Product Data: For air terminals and mounting accessories.

B. Shop Drawings: Detail lightning protection system, including air-terminal locations, conductor routing and connections, and bonding and grounding provisions. Include indications for use of raceway, data on how concealment requirements will be met, and calculations required by NFPA 780 for bonding of grounded and isolated metal bodies.

C. Qualification data for firms and persons specified in "Quality Assurance" Article to demonstrate their capabilities and experience. Include data on listing or certification by an NRTL or LPI.

D. Certification, signed by Contractor, that roof adhesive for air terminals is approved by manufacturers of both the terminal assembly and the single-ply membrane roofing material.

E. Field inspection reports indicating compliance with specified requirements.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Engage an experienced installer who is an NRTL or who is certified by LPI as a Master Installer/Designer.

B. Listing and Labeling: As defined in NFPA 780, "Definitions" Article.

SEKI - 265122 26 41 13 - 2

1.6 COORDINATION

A. Coordinate installation of lightning protection with installation of other building systems and components, including electrical wiring, supporting structures and building materials, metal bodies requiring bonding to lightning protection components, and building finishes.

B. Coordinate installation of air terminals attached to roof systems with roofing manufacturer and

Installer.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following

(or equal):

1. Automatic Lightning Protection.

2. ERICO International Corporation.

3. Harger Lightning Protection, Inc.

4. Heary Bros. Lightning Protection Co. Inc.

5. Independent Protection Co.

6. Robbins Lightning Inc.

7. Thompson Lightning Protection, Inc.

2.2 LIGHTNING PROTECTION SYSTEM COMPONENTS

A. Comply with UL 96.

B. Roof-Mounting Air Terminals: NFPA Class I, copper, unless otherwise indicated.

1. Single-Membrane, Roof-Mounting Air Terminals: Designed for single-membrane roof materials.

C. Stack-Mounting Air Terminals: Solid copper.

D. Ground Rods and Ground Loop Conductors: Comply with Division 26 Section "Grounding and

Bonding for Electrical Systems" and with standards referenced in this Section.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install lightning protection components and systems according to UL 96A and NFPA 780.

B. Install conductors with direct paths from air terminals to ground connections. Avoid sharp bends and narrow loops.

SEKI - 265122 26 41 13 - 3

C. Conceal the following conductors, except as otherwise noted.

1. System conductors.

2. Down conductors.

3. Interior conductors.

4. Conductors within normal view from exterior locations at grade within 200 feet (60 m) of building.

5. Notify Contracting Officer at least 48 hours in advance of inspection before concealing lightning protection components.

D. Cable Connections: Use approved exothermic-welded connections for all conductor splices and connections between conductors and other components, except those above single-ply membrane roofing.

E. Air Terminals on Single-Ply Membrane Roofing: Comply with adhesive manufacturer's written instructions.

F. Bond extremities of vertical metal bodies exceeding 60 feet (18 m) in length to lightning protection components.

G. A counterpoise installation based on requirements in Division 26 Section "Grounding and Bonding for Electrical Systems" may be used as a ground loop required by NFPA 780, provided counterpoise conductor meets or exceeds minimum requirements in NFPA 780.

1. Bond ground terminals to counterpoise conductor.

2. Bond grounded metal bodies on building within 12 feet (3.6 m) of ground to counterpoise conductor.

3. Bond grounded metal bodies on building within 12 feet (3.6 m) of roof to counterpoise conductor.

H. Bond lightning protection components with intermediate-level interconnection loop conductors to grounded metal bodies of building at 60-foot (18-m) intervals.

3.2 CORROSION PROTECTION

A. Do not combine materials that can form an electrolytic couple that will accelerate corrosion in the presence of moisture unless moisture is permanently excluded from junction of such materials.

B. Use conductors with protective coatings where conditions would cause deterioration or corrosion of conductors.

3.3 FIELD QUALITY CONTROL

A. UL Inspection: Provide inspections as required to obtain a UL Master Label for system.

B. Provide an inspection by an inspector certified by LPI to obtain an LPI certification.

END OF SECTION 26 41 13