Inspection, Testing, and Maintenance Report Summary
This document is an Inspection, Testing, and Maintenance Cover Sheet and quarterly/annual fire sprinkler system report for the Ranger Club Dorm (VaB 0056) located in Valley, California, a two-story building constructed in 1999. The property is under contract with HCI Systems, Inc. (License #905493), with inspector Larry Black performing the work under Job #SV2407120072/1. The inspection was conducted on 08/14/24 and covers compliance with NFPA 25, 2011 Edition, as amended by California Code of Regulations, Title 19, §§901 to 906.
The report documents a dry pipe fire sprinkler system with one basement riser featuring a 4-inch riser diameter and 2-inch main drain diameter. The quarterly inspection was completed on 08/14/24 with an overall "Fail" status on the Automatic Sprinkler System form. However, the annual inspection dated 08/14/24 indicates a "Pass" with multiple deficiencies documented. Critical deficiencies include outdated air/water gauges, faded inspection signage requiring replacement, missing 3/4-inch brass uprights, spare head box deficiencies (recalled HSWs and expanding foam issues), non-functional pressure switches, recalled quick-response sidewall sprinklers, and damaged valve components. Main drain test results show initial static pressure of 110 psi, residual pressure of 100 psi, and final static pressure of 110 psi. Various testing data from prior inspection dates (09/19/23) are included, with multiple items marked as "Not Applicable" due to system design specifications. One additional AES 2.9 form is attached for systems with more than five risers.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .