Atch06_06-16-2026_WO_297_YNP_Rangers_Club_Annual_Dry_Amendment_0001_0001.pdf

PDF 627 KB Posted

Attached to
Repair Fire Suppression Deficiencies at Parkwide L
Solicitation number
140P8526Q0110
Issued by

About this file

This is an Inspection, Testing, and Maintenance Report for a fire protection system at the YNP Rangers Club in Yosemite, California, conducted in accordance with NFPA 25 as amended by California Code of Regulations, Title 19.

The property inspected is the YNP Rangers Club, a Type V-A construction building with 2 stories, built in 1920, located at P.O. Box 577, Yosemite, California 95389. The contact is Stephanie Bartholomew (209-628-0186). The inspection was performed by Granite Fire Protection, Inc. (CA License #1088467, Job #297), with inspector Eusebio "JR" Aguilar conducting the work on June 16, 2026. The report was sent to the property owner and contractor on that same date. The inspection focused on the Automatic Sprinkler System (NFPA 25 Chapter 5) with one system riser located in the basement. The system is a dry pipe configuration with a 4-inch riser diameter and 2-inch main drain diameter. The main drain test recorded initial static pressure of 106 psi, residual pressure of 82 psi, and final static pressure of 106 psi, all passing. Quarterly and annual inspections and tests were completed on June 16, 2026, with all items marked as Pass or N/A (Not Applicable). Specific operational parameters recorded include: compressor start at 30 psi, compressor stop at 40 psi, air pressure at 40 psi, supply pressure at 106 psi, valve trip time of 18 seconds, and trip pressure of 19 psi. No deficiencies were identified. The system was returned to service and certified as fully operable and compliant with CCR Title 19, Sections 901 to 906.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19

Property Information:

Name: Occupancy/Use:

Address: Construction Type:

City: No. Stories:

ZIP: Year Constructed:

Contact:

Telephone:

Contractor Information: Number of System Risers

Name: Copy sent to:

Address: Owner Date:

City: Fire AHJ Date:

State: Contractor Date:

Telephone:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 Edition as amended by California Code of Regulations, Title 19, §901 to §906.

2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a)

CA License#:

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection.

Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Concerns that are not deficiencies (i.e. Non-Sprinklered Areas) Yes No

*See "Deficiencies and Comments" section at end of each respective form.

AES 1 September 3, 2013

YNP Rangers Club

Yosemite, California

Type V-A

209-628-0186

P.O. Box 1963

Oakhurst

Granite Fire Protection, Inc.

(559)676-5094

CA ✔

✔ 06/16/26

06/16/26

Eusebio "JR" Aguilar

1088467

R2

Superintendent, P.O Box 577

Stephanie Bartholomew

95389 1920

Dry Pipe Fire Sprinkler System

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

Quarterly and Annual Report 1 of 3

Property Information Contractor or Licensed Owner Information

Building Name Name

Address Address

City St. Zip

City License # Phone

Contact Person SFM Job # CSLB Misc.

Riser Information Main Drain Test (Annual) Riser No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

Final Static Pressure P,F,N/A

This building has more than 5 risers. See additional AES 2.9 form attached Number of AES 2.9 orms attached

Quarterly Inspections I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference

Date Date Date Date

1.1 I Control Valves – Identification Sign 13.3.1

1.2 I Control Valves – Inspection 13.3.2

1.3 I Waterflow Alarm Devices 5.2.5

1.4 I Supervisory Devices 5.2.5

1.5 I Gauges (Dry Pipe Systems)

Pass = Normal Pressures

5.2.4.2, 5.2.4.3 5.2.4.4

13.4.4.1.2

1.6 I Air 3ressure

5.2.4.2, 5.2.4.3

5.2.4.4 13.4.4.2.5.1 psi psi psi psi

1.7 I Water 6upply 3ressure

5.2.4.2

13.4.4.2.5.1 psi psi psi psi

1.8 I Hydraulic Design Information Sign

(for hydraulically designed systems) 5.2.6

1.9 I General Information Sign

(not required for system prior to 2007 edition of NFPA 13) 5.2.8

1.10 I Heat Tape 5.2.7

1.11 I Spare Sprinklers 5.2.1.4

1.12 I Fire Department Connections 13.7

1.13 I Dry Pipe Valves – Exterior Inspection 13.4.4.1.4

1.14 I Pressure Reducing Valves 13.5.1

1.15 Backflow Preventers 13.6.1

1.16 PRV – Fire Sprinkler Systems 13.5.1

Form AES 2.3 Sept. 3, 2013

3KRQH

N/A

P

P

P

N/A

N/A

N/A

P

P

P

P

P

P

N/A

YNP Rangers Club

Yosemite

Stephanie Bartholomew

P.O. Box 1963

Oakhurst

Granite Fire Protection, Inc.

(559)676-5094

CA 93644

C-16

06/16/26

106106

1088467

2"

Annual Inspection

P

P.O Box 577

P.O Box 577

209-628-0186

824"Basement1

A037864

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

Quarterly and Annual Report 2 of 3

Property Information Contractor or Licensed Owner Information

Building Name Name

Address Job #

City

ANNUAL INSPECTION, TESTING, AND MAINTENANCE

Include ALL Quarterly Inspections (See Previous Page)

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.17 I Buildings (Freeze 3rotection) 4.1.1.1 Owner’s Responsibility

1.18 I Sprinklers 5.2.1

1.19 I Pipe and Fittings 5.2.2

1.20 I Hangers 5.2.3

1.21 I Seismic Braces 5.2.3

1.22 I Small Hose Connections* 13.5.6.2.2

2.1 T Field Service Test Required

(Send Report to Fire Code Official) 5.3.1 If REQUIRED, Enter 'F' until results are returned from Lab

2.2 T Recalled Sprinklers

If not present = Pass; If present = Fail

Title 19 904.1(c)

2.3 T Water )low Alarm Devices

90 sec. maximum - (Enter Time )

5.3.3

13.2.6 sec.

2.4 T Main Drain Test

(Enter data on Page 1 of this form)

13.2.5 13.3.3.4

2.5 T Priming Water Level Test 13.4.4.2.1

2.6 T Dry Pipe Valve Trip Test

(Partial trip test is acceptable)

13.4.4.2.2 13.4.4.2.2.3 13.4.4.1.5

2.7 T Valve Trip Time 13.4.4.2.5.2 sec.

2.8 T Trip Air Pressure 13.4.4.2.5.1 psi

2.9 T Quick-Opening Device Test 13.4.4.2.4

2.10 T Low Air Pressure Alarm Test 13.4.4.2.6

2.11 T Low Temperature Alarm Test 13.4.4.2.7

2.12 T Automatic Air Pressure Maintenance Device Test 13.4.4.2.8

2.13 T Control Valve – Operation 13.3.3

2.14 T Valve Supervisory Devices 13.3.3.5

2.15 T Backflow Preventer Assemblies 13.6.2

2.16 T PRV – Partial Flow 13.5.1.3

* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.

Form AES 2.3 Sept. 3, 2013

06/16/26 N/A

06/16/26 P

06/16/26 P

06/16/26 P

06/16/26 P

06/16/26 N/A

06/16/26 N/A

06/16/26 N/A

06/16/26 N/A

06/16/26 P

06/16/26 N/A

06/16/26 N/A

06/16/26 N/A

06/16/26 N/A

06/16/26 P

06/16/26 P

06/16/26 P

06/16/26 N/A

06/16/26 P

06/16/26 P

06/16/26 P

06/16/26 N/A

YNP Rangers Club

Yosemite

Granite Fire Protection, Inc.

P.O Box 577

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

Quarterly and Annual Report 3 of 3

Property Information Contractor or Licensed Owner Information

Building Name Name

Address Job #

City

ANNUAL INSPECTION, TESTING, AND MAINTENANCE

Include ALL Quarterly Inspections (See Quarterly Inspections Page)

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

3.1 M Control Valves 13.3.4

3.2 M Maintenance 13.4.4.3

3.3 M Dry Pipe Valve Interior Cleaned 13.4.4.3.1

3.4 M Low 3oints in 6ystem 'rained 13.4.4.3.2

3.5 M Backflow Preventer 13.6.3

3.6 M

Obstruction Investigation 5equired (If “Yes”, see Deficiencies and Comments Section for Results.)

14.3 Yes No

3.7 M System 5eturned to 6ervice 4.5.3

15.7

Yes No

D = Deficiency C = Comment (Indicate type )

Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced

Check here if additional Deficiencies and Comments are listed on Form AES9

See Correction Form AES 10 for corrected deficiencies.

Number attached� Number attached�

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

Quarter

Check box if Annual Inspection, Testing & Maintenance ,tems are &ompleted in the ,ndicated Quarter Annual 4th Annual

Date

Print Name

Signature

Form AES 2.3 Sept. 3, 2013

Annual Annual1st �QG �UG �tK

06/16/26 P

06/16/26 P

06/16/26 P

06/16/26 P

06/16/26 N/A

06/16/26 N/A

06/16/26 P

YNP Rangers Club

Yosemite

Granite Fire Protection, Inc.

✔06/16/26 Annual Inspection is completed, system is a PASS.

Compressor start = 30 psi Compressor stop = 40 psi

Air pressure = 40 psi Supply = 106 psi Trip time = 18 seconds Trip pressure = 19 psi

P.O Box 577

Deficiencies - Cover Sheet

None

Deficiencies - Quarterly/Annual Dry Pipe

None

Report of Inspection / Test

06-19-2026 Property YNP Rangers Club

Conducted by: Eusebio "JR" Aguilar

Granite Fire Protection, Inc.

1088467 P.O. Box 1963 Oakhurst CA 93644 (559)676-5094

Copyright 2026 Inspect Point

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Eusebio "JR" Aguilar 2026-06-19

Report of Inspection / Test

06-19-2026 Property YNP Rangers Club

Conducted by: Eusebio "JR" Aguilar

Granite Fire Protection, Inc.

1088467 P.O. Box 1963 Oakhurst CA 93644 (559)676-5094

Copyright 2026 Inspect Point