This document provides clarification for Request for Proposals number 140P8322R0004 to rehabilitate the wastewater system at Log Cabin Resort in Olympic National Park, Washington. The scope of work includes rehabilitating the sewage collection and conveyance system, replacing the treatment system with a recirculating textile filter and new control building including UV disinfection, and constructing a new subsurface drip disposal drain field. Offerors must visit SAM.gov for solicitation documents and amendments. Proposals are due approximately 30 days after posting to SAM.gov. This is a best value negotiated procurement set aside for small businesses. The prime contractor must comply with limitations on subcontracting. All work will be performed under a single firm-fixed-price construction contract subject to the Wage Rate Requirements (Construction). The performance period is 390 calendar days after notice to proceed. The estimated contract value is between $1,000,000 and $5,000,000. The National Park Service Pacific West Region is the contracting agency.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP #140P8322R0004, Rehabilitate LOSS at Log Cabin Resort Olympic NP Attachment 11: Clarification 26
Clarifications #2 for Solicitation #140P8322R0004
Amendment 3 posted on 3/16/22
This document provides clarifications based on submitted queries.
Clarifications 1 – 12 are in Attachment 9; 13 – 25 are in Attachment 10.
26. Spec 26 36 00 2.3.H mentions automatic closed-transition transfer switches. The drawings show a standard configuration ATS, not a closed-transition transfer switch.
Which type of ATS is required?
Automatic closed-transition transfer switches are not necessary. The standard configuration ATS is acceptable and the drawings govern over Specification Section 26 36 00 2.3 H.