This document is an analytical report from Hawaii Analytical Laboratory regarding asbestos and lead testing conducted on samples collected from the Nahuku Restroom at Hawaii Volcanoes National Park on March 19, 2024.
The report provides the results of the asbestos and lead testing for various paint, tile, and other building material samples. The asbestos testing found no asbestos present in any of the samples. The lead testing found elevated lead levels in the exterior brown paint (28,000 mg/kg) and lower levels in the interior white paint (120 mg/kg) and floor tile (240 mg/kg). The report includes details on the analytical methods used and general comments regarding the testing and results. This report appears to be supporting documentation for the federal contract opportunity related to the "CHAIN OF CRATERS COMFORT STATIONS" project, Solicitation Number 140P8224R0002, for restroom rehabilitation work at the Nahuku facility within Hawaii Volcanoes National Park.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Tuesday, March 26, 2024
Hawaii Analytical Laboratory
ANALYTICAL REPORT
Hawaii Volcanoes National Park Service 1 Crater Rim Drive
Lab Job No: 202403302
Your Project: Nahuku Restroom, 3/19/24
Pahoa HI 96718
Date Submitted: 3/26/2024
Facsimile:
Phone Number: (808)938-8691
Email: alvin_asato@nps.gov
Your Sample ID / Description Asbestos Present?
%v/vSample No. Date Analyzed
MatrixOther Fibrous
Bulk Asbestos Determination Type %v/v
Exterior Brown Paint Sample NONE
DETECTED
202424045 3/26/2024
Brown paint
None detected
Paint + other
Comments
Layer
Interior White Paint Sample NONE
DETECTED
202424046 3/26/2024
Brown/black wood
Wood fiber (undulose)
Other
Comments
Layer
Interior White Paint Sample NONE
DETECTED
202424046 3/26/2024
White paint
None detected
Paint + other
Comments
Layer
Interior Floor Tile NONE
DETECTED
202424047 3/26/2024
Gray caulking / paint
None detected
Binder + paint
Comments
Layer
Interior Floor Tile NONE
DETECTED
202424047 3/26/2024
Gray ceramic tile
None detected
Ceramic
Comments
Layer
Interior Floor Tile NONE
DETECTED
202424047 3/26/2024
Gray grout
None detected
Calcite + other
Comments
Layer
Hawaii Analytical Laboratory is a NIST NVLAP accredited laboratory (NVLAP Lab Code 200655-0) and is accredited in accordance with the recognized ISO/ IEC 17025:2017. Controlled doc.: Asbestos Report, rev. 4 – 20240311
Page 1 of 23615 Harding Avenue, Ste. 308, Honolulu, HI 96816 - Telephone: (808) 735-0422 - Fax: (808) 735-0047
Wednesday, March 27, 2024
Hawaii Analytical Laboratory
ANALYTICAL REPORT
Hawaii Volcanoes National Park Service 1 Crater Rim Drive
Lab Job No: 202403302
Pahoa HI 96718
Date Submitted: 3/26/2024
Facsimile:
Phone Number: (808)938-8691
Email: alvin_asato@nps.gov
Your Project: Nahuku Restroom, 3/19/24
Total Lead (paint chips)
Sample No. Your Sample ID / Description Results Units Date
Analyzed
NIOSH Method: 7082m LEAD by FAAS
202424045 Exterior Brown Paint Sample Comments
28000 mg/kg 3/27/2024
202424046 Interior White Paint Sample Comments
120 mg/kg 3/27/2024
202424047.1 Interior Floor Tile
Comments
240 mg/kg 3/27/2024
Total Recoverable Lead #
Sample No. Your Sample ID / Description Results Units Date
Analyzed
EPA Method: 3051m / 7000Bm
202424047 Interior Floor Tile Comments
40 mg/kg 3/27/2024<
Hawaii Analytical Laboratory (101812) is accredited by the AIHA LAP, LLC in the EMLAP, IHLAP, and ELLAP programs for the scope of work listed on www.aihaaccreditedlabs.org, in accordance with the recognized ISO/ IEC 17025:2005. AIHA is a
NLLAP recognized accrediting body. Controlled doc.: Lead Report, rev. 3 – 20181015
3615 Harding Avenue, Ste. 308, Honolulu, HI 96816 - Telephone: (808) 735-0422 - Fax: (808) 735-0047
Hawaii Volcanoes National Park Service 1 Crater Rim Drive
Lab Job No: 202403302
Pahoa HI 96718
Date Submitted: 3/26/2024
Facsimile:
Phone Number: (808)938-8691
Email: alvin_asato@nps.gov
Your Project: Nahuku Restroom, 3/19/24
General Comments The sample[s] analysis subject of this analytical report were conducted in general accordance with the procedures associated with the ”analytical method" referenced above. Modifications to this methodology may have been made based upon the analyst's professional judgment and / or sample matrix effects encountered. The analysis of sample relates only to the sample analyzed, and may or may not be representative of the original source of the material submitted for our analysis. All analysts participate in interlaboratory quality control testing to continuously document profiency. This report is not to be duplicated except in full without the expressed written permission of Hawaii Analytical Laboratory. This report should not be construed as an endorsement for a product or a service by the AIHA LAP, LLC or any affiliated organizations. Sample and associated sampling / collection data is reported as provided by client. TWA values have been calculated based on information supplied by the client that the laboratory has not independently verified. Results have not been corrected for blank determinations unless noted in remarks. Unless otherwise indicated the sample condition at the time of receipt was acceptable.
Results and Symbols Definitions > This testing result is greater than the numerical value listed.
< This testing result is less than the numerical value listed.
# = Analytical methods marked with an "#" are not within our AIHA LAP, LLC Scope of Accreditation.
MRL = Method Reporting Limit.
Jennifer Hsu Liao Laboratory Manager
All Quality Control data are acceptable unless otherwise noted.
MRL for lead air is 5ug.
MRL for lead wipe is 10ug.
MRL for lead paint or soil is 40 mg/kg for a 0.25g sample.
Hawaii Analytical Laboratory (101812) is accredited by the AIHA LAP, LLC in the EMLAP, IHLAP, and ELLAP programs for the scope of work listed on www.aihaaccreditedlabs.org, in accordance with the recognized ISO/ IEC 17025:2005. AIHA is a
NLLAP recognized accrediting body. Controlled doc.: Lead Report, rev. 3 – 20181015
3615 Harding Avenue, Ste. 308, Honolulu, HI 96816 - Telephone: (808) 735-0422 - Fax: (808) 735-0047
Hawaii Volcanoes National Park Service 1 Crater Rim Drive
Lab Job No: 202403302
Your Project: Nahuku Restroom, 3/19/24
Pahoa HI 96718
Date Submitted: 3/26/2024
Facsimile:
Phone Number: (808)938-8691
Email: alvin_asato@nps.gov
Your Sample ID / Description Asbestos Present?
%v/vSample No. Date Analyzed
MatrixOther Fibrous
Bulk Asbestos Determination Type %v/v
Interior Floor Tile NONE
DETECTED
202424047 3/26/2024
Off-white mastic
None detected
Binder
Comments
Layer
Interior Floor Tile NONE
DETECTED
202424047 3/26/2024
White mortar
None detected
Calcite + other
Comments
Layer
Jennifer Hsu Liao Laboratory Manager
General Comments The bulk sample[s] analysis subject of this analytical report were conducted in general accordance with the procedures outlined in the United States Environmental Protection Agency’s “Interim Method for the Determination of Asbestos in Bulk Insulation Samples” (EPA-600/M4-82- 020, Dec. 1982) and / or “Method for Determination of Asbestos in bulk Building Materials” (EPA-600/R-93-116, July 1993). The analysis of each bulk sample relates only to the material examined, and may or may not represent the overall composition of its original source. Floor tile and other resinously bound materials, when analyzed by the EPA methods referenced above may yield false negative results because of limitations in separating closely bound fibers and in detecting fibers of small length and diameter. Gravimetric treatment, which HAL does not offer, may also be appropriate for certain NOB (non-friable organically bound) materials. Unless specifically requested by clients, NOB samples can be subcontracted to a NVLAP accredited lab, or else, they will be analyzed by HAL using regular PLM technique. In addition, alternative methods of identification, including Transmission Electron Microscopy (TEM) may or may not be applicable. We utilize calibrated visual area estimation on a routine basis and do not conduct point counting unless specifically requested to do so. Estimated error for the visual determinations presented are 75% relative (1 to 2%), 50% relative (3 to 5%); 25% relative (6 to 25%) and 20% (>26% v/v). We will not separate layers which in our opinion are not readily discernable. This report is not to be duplicated except in full without the expressed written permission of Hawaii Analytical Laboratory. This report must not be used by the client to claim product certification, approval or endorsement by NVLAP, NIST or any agency of Federal Governement. Unless otherwise indicated, the sample condition at the time of receipt was acceptable.
Results and Symbols Definitions > This testing result is greater than the numerical value listed.
< This testing result is less than the numerical value listed.
None Detected = asbestos was not observed in the sample. If trace amount of asbestos was detected below our quantifiable limits of 1.0%, <1% (trace) would be indicated and the asbestos type listed. Point counting, where applicable, are recommended to improve accuracy.
Hawaii Analytical Laboratory is a NIST NVLAP accredited laboratory (NVLAP Lab Code 200655-0) and is accredited in accordance with the recognized ISO/ IEC 17025:2017. Controlled doc.: Asbestos Report, rev. 4 – 20240311
Page 2 of 23615 Harding Avenue, Ste. 308, Honolulu, HI 96816 - Telephone: (808) 735-0422 - Fax: (808) 735-0047