The document addresses three key inquiries regarding project specifications. For door and screen/storm door requirements, contractors must replace the existing storm door with a new custom-fabricated unit approximately 41" wide by 79½" high (to be verified before ordering). The door must feature charcoal grey aluminum 1.5-inch frame construction with reinforced internal corner brackets, heavy-duty steel push-button closer, interchangeable glass and screen with thermally tempered safety glass, lever handle latch with exterior keyed lock (black or grey finish), door sweep, tamper-proof hinges, and weatherstripping. The government clarifies that "screen door" and "storm door" refer to the same assembly. Regarding HVAC mini-split equipment, the response explicitly states "NO substitutions," indicating that specified basis-of-design equipment is mandatory with no approved-equivalent alternatives permitted. For wall patching in curatorial and artifact storage rooms, contractors must use embossed white galvanized steel panels matching existing in-kind material and texture, pop-riveted over existing panels and sealed with silicon caulking. Patching requires 2x4 blocking around the opening interior for support, rigid XPS insulation with a minimum R-25 value, flame spread rating below 25, and a vapor barrier.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PECO Replace Siding and HVAC

Questions and Answers 2

# Questions Response 1 Door and Screen/Storm Door

Requirements

Please provide or confirm the required specifications, dimensions, materials, finish, hardware, and other product requirements for the replacement door and screen/storm door. Please also clarify whether the reference to a “screen door” and “storm door” in the contract documents refers to the same assembly.

Replace existing storm door with new, custom fabricated storm door. Existing storm door is approx.

41”w x 79 ½” h (verify size and mounting prior to ordering). Charcoal grey aluminum 1.5 in. frame construction with reinforced aluminum internal corner brackets Heavy-duty steel, push-button closer Interchangeable Glass & Screen. Thermally tempered safety glass. Storm door latch to be lever handle operated with exterior keyed lock (black or grey finish). Door Sweep, Tamper-Proof Hinges, Weatherstripping.

Yes, screen door and storm door refers to the same assembly.

2 HVAC / Mini-Split Equipment

Requirements

Please confirm the required specifications for the new split-system HVAC units. Are the units required to be a specific manufacturer/brand, or will approved-equivalent equipment meeting the specified performance requirements be accepted? If the identified basis-of-design equipment is mandatory, please confirm.

NO substitutions

3 Wall Patching in Curatorial /

Artifact Storage Rooms

For existing wall openings that require patching within the curatorial/artifact storage rooms, will the Government approve the use of FRP

(Fiberglass Reinforced Plastic) panels as the finished patch material? If FRP is not

Embossed White galvanized steel (match in-kind material and texture). Pop rivet into place over existing panel. Seal with silicon caulking between existing siding and patch panel. Provide 2x4 blocking around inside of opening for patch panel support.

INSULATION

Rigid XPS R 25 value min insulation Flame spread rating <25 acceptable, please provide the required wall patch assembly, finish material, fire-rating requirements, and finish/color requirements.

Provide vapor barrier