Project Package No: 211313-0006-0
Date: 11/05/2015
Submittal Transmittal
Arch Visitor Center Renovation, JEFF 199869 Project # 003850.000 Tel: Fax:
Transmitted To:
ReturnedStatusDave Daley
St Louis Automatic Sprinkler Company Inc
3928 Clayton Avenue St. Louis, MO 63110 Phone: 314-533-7710 Fax: 314-533-4559
Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
Description
Notes
Item # StatusSpec Sec Sub Sec RevDescriptionType Revision Notes
1954 Approved as Noted
211313 1.5D 0Hydraulic Calculations: Zones 8 & 9
Shop Drawings
1955 Approved as Noted
211313 1.5C 0Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
Shop Drawings
Transmitted By: Cody Keller
Company Contact
Copies To
Page 1 of 1Printed On: 11/5/15 7:08:03AM
Project Package No: 211313-0006-0
Date: 10/23/2015
Submittal Transmittal
Arch Visitor Center Renovation, JEFF 199869 Project # 003850.000 Tel: Fax:
Transmitted To:
SubmittedStatusJason Longshore 11/06/2015Date DueNational Park Service – Denver Service Center
12795 W. Alameda Parkway PO Box 25287 Denver, CO 80225 Phone: 303-969-2831
Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
Description
Notes
Item # StatusSpec Sec Sub Sec RevDescriptionType
1954 In Review211313 1.5D 0Hydraulic Calculations:
Zones 8 & 9
Shop Drawings
1955 In Review211313 1.5C 0Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
Shop Drawings
Transmitted By: Cody Keller
Company Contact
Copies To
Page 1 of 1Printed On: 10/23/15
Submittal Approval Page By Submittal Item
Arch Visitor Center Renovation, JEFF 199869 Project Package No: 211313-0006-0
Project # 003850.000 Tel: Fax:
Preparer Approval McCarthy Approval
This review is for general conformance with Plans and Specifications only. Any deviations from same not clearly noted by the Preparer have not been reviewed. Review shall not constitute a complete check of detailed dimensions or count or serve to relieve the Preparer of contractual responsibility for any error or deviation from contract requirements.
Date:By:
Submittal Package No: 211313-0006-0
Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
Cody Keller
Spec Section Revision Sub Section Item No 1.5C 1,955 0
Approved for Submission
St Louis Automatic Sprinkler Company Inc
By: Dave Daley
211313
Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
A. Approved as noted for Architectural Review
B. Revise & Resubmit
C. Rejected
10/23/2015
X
Engineer ApprovalNational Park Service – Denver Service Center Approval
12795 W. Alameda Parkway PO Box 25287
Denver, CO 80225
Page 1 of 1Printed On: 10/23/15 ehogue Stamp ehogue Typewritten Text The submittal has been reviewed to meet compliance with spec requirements and have been found to be in compliance. Hydraulic, and seismic calculations are the responsibility of the sprinkler contractor's professional engineer of record.
ehogue Rectangle ehogue Typewritten Text X
Submittal Approval Page By Submittal Item
Arch Visitor Center Renovation, JEFF 199869 Project Package No: 211313-0006-0
Project # 003850.000 Tel: Fax:
Preparer Approval McCarthy Approval
This review is for general conformance with Plans and Specifications only. Any deviations from same not clearly noted by the Preparer have not been reviewed. Review shall not constitute a complete check of detailed dimensions or count or serve to relieve the Preparer of contractual responsibility for any error or deviation from contract requirements.
Date:By:
Submittal Package No: 211313-0006-0
Wet/Dry Standpipe Shop Drawings: Zones 8 & 9
Cody Keller
Spec Section Revision Sub Section Item No 1.5D 1,954 0
Approved for Submission
St Louis Automatic Sprinkler Company Inc
By: Dave Daley
211313
Hydraulic Calculations: Zones 8 & 9
A. Approved as noted for Architectural Review
B. Revise & Resubmit
C. Rejected
10/23/2015
X
Engineer ApprovalNational Park Service – Denver Service Center Approval
12795 W. Alameda Parkway PO Box 25287
Denver, CO 80225
Page 1 of 1Printed On: 10/23/15 ehogue Stamp ehogue Typewritten Text The submittal has been reviewed to meet compliance with spec requirements and have been found to be in compliance. Hydraulic, and seismic calculations are the responsibility of the sprinkler contractor's professional engineer of record.
ehogue Rectangle ehogue Typewritten Text X
SD
BR
SD
BR
SD
BR
SD
BR
SD
BR
10'-5
ZONE #9
ZONE #8
Z
O
N
E
ZONE #9 ZONE #9 ZONE #9
ZONE #8
ZONE #9
ZONE 16
ZONE 15
ZONE 12
ZONE 9
ZONE 7
ZONE 8
ZONE 6
ZONE 3 ZONE 4
LOCATION MAP
File details come from the government source that posted it. Updated .