BACKFLOW PREVENTER INFORMATION

FACILITY LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP.

Arch #1 Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 4/15/2003 Passed 1/8/2004 Arch #2 Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 4/15/2003 Passed 1/8/2004 Arch #3 South Mech. Rm. Watts 900 NA 423340 3/4" Hot Water Heat Fill Fail 1/8/2004 Arch #4 Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 4/15/2003 Passed 1/8/2004 Arch #5 Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 4/15/2003 Passed 1/8/2004 Arch #6 B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 4/15/2003 Passed 1/8/2004 Arch #7 North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 4/15/2003 Passed 1/8/2004 Arch #8 North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 10/2/2003 Passed 1/8/2004 Arch #9 North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 10/2/2003 Passed 1/8/2004 Arch #10 North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 10/2/2003 Passed 1/8/2004 Arch #11 Pump Room Watts 909 MIQT RP Na 349799 1 1/2" Tower Makeup 4/15/2003 Passed 1/8/2004 Arch #12 Pump Room Febco DC 870V F0309130625 6" Fire Sprinklers 10/16/2003 Passed 1/8/2004

Grounds # 1 Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Sprinklers 1/8/2003 Passed 1/8/2004 Grounds # 2 Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 11/14/2003 Passed 1/8/2004 Grounds # 3 Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 11/14/2003 Passed 1/8/2004 Grounds # 4 Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 11/14/2003 Passed 1/8/2004

No backflow preventers at the OCH for the fire sprinklers and domestic water No backflow preventer on the condensate coolers in the south mechanical room.

Note: Arch #3 is not in use, it is valved off and locked out.

FACILITY LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL

Arch #1 Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 4/6/2004 Passed Arch #2 Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 4/6/2004 Passed Arch #3 South Mech. Rm. Watts 900 NA 423340 3/4" Hot Water Heat Fill 4/6/2004 Removed Arch #4 Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 4/6/2004 Repaired Arch #5 Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 4/6/2004 Passed Arch #6 B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 4/6/2004 Passed Arch #7 North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 4/6/2004 Passed Arch #8 North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 4/6/2004 Passed Arch #9 North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 4/6/2004 Passed Arch #10 North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 4/6/2004 Passed Arch #11 Pump Room Watts 909 MIQT RP Na 349799 1 1/2" Tower Makeup 4/6/2004 Passed Arch #12 Pump Room Febco DC 870V F0309130625 6" Fire Sprinklers 4/13/2004 Passed

Grounds # 1 Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Sprinklers 4/13/2004 Passed Grounds # 2 Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 4/6/2004 Repaired Grounds # 3 Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 4/6/2004 Passed Grounds # 4 Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 4/6/2004 Passed

Actions needed as a result of testing on 4/6/04

Arch #3 needs to be pulled out of service (removed from the piping) Arch #4 needs to be rebuilt Grounds #2 needs to be rebuilt Murphy Company is going to prepare a bid to address these problems

All of the issues listed above have been resolved and all have passed as of 4/13/04

No backflow preventers at the OCH for the fire sprinklers and domestic water

NEXT INSP.

4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 4/6/2005 1/8/2004 4/6/2005 4/6/2005

Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 6/12/2005 Passed 8/5/2006 Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 7/13/2005 Passed 8/5/2006 Arch #3 P South Mech. Rm. Watts 900 NA 423340 3/4" Hot Water Heat Fill 4/6/2004 Removed 8/5/2006 Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 7/13/2005 Passed 8/5/2006 Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 7/13/2005 Passed 8/5/2006 Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 7/13/2005 Passed 8/5/2006 Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 7/13/2005 Passed 8/5/2006 Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 7/12/2005 Passed 8/5/2006 Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 7/13/2005 Passed 8/5/2006

Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 7/13/2005 Passed 8/5/2006 Arch #11 M Pump Room Watts 909 MIQT RP Na 349799 1 1/2" Tower Makeup 7/13/2005 Passed 8/5/2006 Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Sprinklers 4/13/2004 Passed 8/5/2006 Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Sprinklers 4/13/2004 Failed 8/5/2006 Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 7/12/2005 Passed 8/5/2006 Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 7/12/2005 Passed 8/5/2006 Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 7/13/2005 Passed 8/5/2006

P = Plumbing As Of 9/13/05 M = Mechanical F = Fire Sprklr

Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 4/12/2006 Passed 4/12/2007 Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 4/12/2006 Passed 4/12/2007 Arch #3 P South Mech. Rm. Watts 900 NA 423340 3/4" Hot Water Heat Fill Removed Removed Removed Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 4/12/2006 Passed 4/12/2007 Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 Passed Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 4/12/2006 Passed 4/12/2007 Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 4/12/2006 Passed 4/12/2007 Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 4/12/2006 Passed 4/12/2007 Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 4/12/2006 Passed 4/12/2007

Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 4/12/2006 Passed 4/12/2007 Arch #11 M Pump Room Watts 909 MIQT RP Na 349799 1 1/2" Tower Makeup 4/12/2006 Passed 4/12/2007 Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Sprinklers 9/6/2006 Passed 9/6/2007 Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Sprinklers 9/6/2006 Passed 9/6/2007 Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 4/12/2006 Passed 4/12/2007 Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 4/12/2006 Passed 4/12/2007 Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 4/12/2006 Passed 4/12/2007

P = Plumbing As Of 11/1/06 M = Mechanical F = Fire Sprklr

BACKFLOW PREVENTER INFORMATION Mar-08

Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 4/23/2008 Pass 4/23/2009 Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 4/23/2008 Pass 4/23/2009 Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 4/23/2008 Pass 4/23/2009 Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 4/23/2008 Pass 4/23/2009 Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 4/23/2008 Pass 4/23/2009 Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 4/23/2008 Pass 4/23/2009 Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 4/23/2008 Pass 4/23/2009 Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 4/23/2008 Pass 4/23/2009

Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 4/23/2008 Pass 4/23/2009 Arch #11 M Pump Room Watts 909 MIQT RP Na 349799 1 1/2" Tower Makeup 4/23/2008 Pass 4/23/2009 Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Sprinklers Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Sprinklers Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 4/23/2008 Pass 4/23/2009 Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 4/23/2008 Pass 4/23/2009 Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 4/23/2008 Pass 4/23/2009

P = Plumbing M = Mechanical Locations and Info as of 4/08 F = Fire Sprklr

5 Plumbing 8 Mechanical

2 Fire

BACKFLOW PREVENTER INFORMATION Mar-08

Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser

Arch #3 P South Mech. Rm. Watts 900 NA 423340 3/4" Hot Water Heat Fill Removed Removed Removed Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass

Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up Arch #11 M Pump Room Watts 909 MIQT RP Na 349799 1 1/2" Tower Makeup Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Sprinklers Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Sprinklers Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup

P = Plumbing M = Mechanical F = Fire Sprklr

5 Plumbing 8 Mechanical

2 Fire

Backflow Preventer/ Line Testing Information

Date: 5/1/2010

FACILITY Builiding LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP. Remarks Arch #1 P 19274 Arch Visitor Center Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 5/14/2010 Pass 5/1/2011 Arch #2 M 19275 Arch Visitor Center Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 5/14/2010 Pass 5/1/2011 Arch #4 M 19276 Arch Visitor Center Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 5/14/2010 Pass 5/1/2011 Removed Arch #5 M 19277 Arch Visitor Center Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 5/14/2010 Pass 5/1/2011 Arch #6 M 19278 Arch Visitor Center B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 5/14/2010 Pass 5/1/2011 Rebuilt Arch #7 M 19279 Arch Visitor Center North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 5/14/2010 Pass 5/1/2011 Arch #8 P 19280 Arch Visitor Center North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 5/14/2010 Pass 5/1/2011 Arch #9 P 19281 Arch Visitor Center North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 5/14/2010 Pass 5/1/2011 Arch #10 M 19282 Arch Visitor Center North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 5/14/2010 Pass 5/1/2011 Arch #11 M 19283 Arch Visitor Center Pump Room Watts 909 MIQT RP NA 349799 1 1/2" Tower Makeup 5/14/2010 Pass 5/1/2011 Arch #12 F 19284 Arch Visitor Center Pump Room Febco DC 870V F0309130625 6" Fire Suppression 5/20/2010 Pass 5/1/2011 OCH #1 F 19279 Old Courthouse Basement SE Corner AMES 2000ss NA HC-0173 4" Fire Suppression 5/20/2010 Pass 5/1/2010 Grds # 1 F 19288 Grounds Complex Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Suppression 5/20/2010 Pass 5/1/2011 Grds # 2 P 19288 Grounds Complex Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 3/24/2010 Pass 5/1/2010 Grds # 3 P 19288 Grounds Complex Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 3/24/2010 Pass 5/1/2010 Grds # 4 M 19288 Grounds Complex Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 3/24/2010 Pass 5/1/2010 Rebuilt

P = Plumbing 5 Plumbing M = Mechanical 8 Mechanical F = Fire Suppression 2 Fire

* No backflow preventer at the OCH for the fire sprinklers and domestic water

* No backflow preventer on the condensate coolers in the south mechanical room.

2010 Testing: Grounds wet pipe fire testing conducted on 9/10/2010 2010 Testing: Arch wet pipe fire testing conducted on 9/13/2010

Date: 5/23/2011

FACILITY LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP. Remarks Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 5/24/2011 Pass Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 5/24/2011 Pass Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 5/24/2011 Removed Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 5/24/2011 Pass Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 5/24/2011 Removed Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 5/24/2011 Pass Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 5/24/2011 Pass Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 5/24/2011 Pass Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 5/24/2011 Pass Arch #11 M Pump Room Watts 909 MIQT RP NA 349799 1 1/2" Tower Makeup 5/24/2011 Pass Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Suppression 5/13/2011 Pass 5/1/2012 OCH #1 F Basement SE Corner AMES 2000ss NA HC-0173 4" Fire Suppression 5/13/2011 Pass 5/1/2012 Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Suppression 5/13/2011 Pass 5/1/2012 Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 5/24/2011 Pass Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 5/24/2011 Pass Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 5/24/2011 Pass Rebuilt

P = Plumbing 5 Plumbing M = Mechanical 8 Mechanical F = Fire Suppression 3 Fire

* No backflow preventer at the OCH for the fire sprinklers and domestic water

2010 Testing: Grounds wet pipe fire testing conducted on 9/10/2010 2010 Testing: Arch wet pipe fire testing conducted on 9/13/2010

Date: 5/23/2011

FACILITY LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP. Remarks Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 5/8/2012 Pass Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 5/8/2012 Pass Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 5/8/2012 Pass Reinstalled Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 5/8/2012 Pass Rebuilt Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 removed 5/10 Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 5/8/2012 Pass Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South 5/8/2012 Pass Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 5/8/2012 Pass Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 5/8/2012 Pass Arch #11 M Pump Room Watts 909 MIQT RP NA 349799 1 1/2" Tower Makeup 5/8/2012 Pass Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Suppression 5/9/2012 Pass OCH #1 F Basement SE Corner AMES 2000ss NA HC-0173 4" Fire Suppression 5/9/2012 Pass Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Suppression 5/9/2012 Pass Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 5/8/2012 Pass Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 5/8/2012 Pass Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 5/8/2012 Pass

P = Plumbing 5 Plumbing M = Mechanical 8 Mechanical F = Fire Suppression 3 Fire

* No backflow preventer at the OCH for the domestic water

Date:

FACILITY LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP. Remarks Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 5/7/2013 PASS Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 5/7/2013 PASS Arch #3 M South Projector Office Watts 007MI OT NA 15544 3/4 '' dubal check va) Humidifier cru-I lieber 5/7/2013 PASS RELOCATED Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 5/7/2013 PASS Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 5/7/2013 PASS KIT & COVER Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 5/7/2013 PASS removed 5/10 Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 5/7/2013 PASS Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South and back restrooms 5/7/2013 PASS Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 5/7/2013 PASS Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 5/7/2013 PASS Arch #11 M Pump Room Watts 909 MIQT RP NA 349799 1 1/2" Tower Makeup 5/7/2013 PASS Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Suppression 5/13/2013 PASS OCH #1 F Basement SE Corner AMES 2000ss NA HC-0173 4" Fire Suppression 5/13/2013 PASS Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Suppression 5/13/2013 PASS Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 5/7/2013 PASS Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 5/7/2013 PASS Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 5/7/2013 PASS Grds # 5 P Warehouse Dock Watts 099 M2 QT NA A62840 1" Grnds south drinking fountains 5/7/2013 PASS INSTALED

P = Plumbing 6 Plumbing M = Mechanical 9 Mechanical F = Fire Suppression 3 Fire l Date:

LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP. Remarks Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains 4/22/2014 PASS 4/22/2015 Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser 4/22/2014 PASS 4/22/2015

South Projector Office Watts 007MI OT NA 15544 3/4 '' dubal check va) Humidifier cru-I lieber 4/22/2014 PASS 4/22/2015 North Mech. Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 4/22/2014 PASS 4/22/2015

Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 4/22/2014 PASS 4/22/2015 OFF B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 4/22/2014 PASS 4/22/2015 removed 5/10

Cust. Store Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 4/22/2014 PASS 4/22/2015 removed 4/14 North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South and back restrooms 4/22/2014 PASS 4/22/2015 North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass 4/22/2014 PASS 4/22/2015 North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up 4/22/2014 PASS 4/22/2015

Pump Room Watts 909 MIQT RP NA 349799 1 1/2" Tower Makeup 4/22/2014 PASS 4/22/2015 Pump Room Febco DC 870V F0309130625 6" Fire Suppression 4/30/2014 PASS 4/30/2015

Basement SE Corner AMES 2000ss NA HC-0173 4" Fire Suppression 4/30/2014 FAILED 4/30/2015 neads repairing Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Suppression 4/30/2014 PASS 4/30/2015 Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 4/22/2014 PASS 4/22/2015 Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 4/22/2014 PASS 4/22/2015 Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 4/22/2014 PASS 4/22/2015 Warehouse Dock Watts 099 M2 QT NA A62840 1" Grnds south drinking fountains 4/22/2014 PASS 4/22/2015

6 Plumbing 9 Mechanical Sauder Plumbing tested 4-22-14 3 Fire

Century Fire Sprinklers testded 4-30-14 Basement SE Corner Amse 200ss NA HC-173 4 Fire Suppession 7/14/2014 PASS 4/30/2015 Repaired and tested l Date: FY2015

FACILITY LOCATION MANUF. SERIES MODEL S/N SIZE FEEDS INSP. DATE PASS / FAIL NEXT INSP. Remarks Arch #1 P Fab Shop Watts 909 QT RPZ NA 5148337 1" O/S Drinking Fountains Arch #2 M Fab Shop Conbraco 40-200 40203A2 I5419 1/2" Metro Condenser Arch #3 M South Projector Office Watts 007MI OT NA 15544 3/4 '' dubal check va) Humidifier cru-I liebert Arch #7 M North Mech. Rm. Watts 009 QT RP NA 165357 1/2" Humidifier AHU 7 Arch #5 M Exhibits Watts 009 QT RP NA 165334 1/2" Humidifier AHU 8 Arch #6 M B&U Shop Watts 009 QT RP NA 165365 1/2" Humidifier AHU 9 Arch #4 M Cust. Store Rm. Watts 009 QT RP NA 165336 1/2" Humidifier AHU 10 Arch #8 P North Mech. Rm. Watts 909 MIQT RP NA 397810 2" Pond - South and back restrooms Arch #9 P North Mech. Rm. Watts 909 MIQT RP NA 395015 1 1/2" Cond. Coolers/CW makeup bypass Arch #10 M North Mech. Rm. Watts 909 QT RPZ NA 561709 1" Chilled Water Make-up Arch #11 M Pump Room Watts 909 MIQT RP NA 349799 1 1/2" Tower Makeup 8/25/2015 PASS Yes Arch #12 F Pump Room Febco DC 870V F0309130625 6" Fire Suppression HOLD OCH #1 F Basement SE Corner AMES 2000ss NA HC-0173 4" Fire Suppression 9/2/2015 PASS Yes Grds # 1 F Warehouse Dock Ames 2000 ss NA 122632 1001 4" Fire Suppression 9/2/2015 PASS Yes Grds # 2 P Warehouse Dock Watts 009 M20I RP NA 153894 2" Domestic Cold 8/25/2015 PASS Yes Grds # 3 P Warehouse Dock Watts 009 M2 QT NA 65253 1 1/2" Hydrants 8/1/2515 PASS Yes Grds # 4 M Mechanical Room Watts 009 M3 QT NA 80136 3/4" Heating Water Makeup 8/25/2015 PASS Yes Grds # 5 P Warehouse Dock Watts 099 M2 QT NA A62840 1" Grnds south drinking fountains

P = Plumbing 6 Plumbing sauder Plumbing tested 8/25/2015 M = Mechanical 9 Mechanical F = Fire Suppression 3 Fire Century Fire Sprinklers tested 9/2/2015

1 Backflow Preventer Info. 2003
Sheet1
2 Backflow Preventer 4-04 test results
Sheet1
3 Backflow Preventer 8-05 test results
Sheet1
4 Backflow Preventer 2006 test results
Sheet1
5 Backflow Preventer Test 2008
Sheet1
6 Backflow Preventers removed Mar 2008
Sheet1
2010 Backflow Preventer Line Testing
Sheet1
2011 Backflow Preventer Line Testing
Sheet1
2012 Backflow Preventer Line Testing
Sheet1
2013 Backflow Preventer Line Testing
Sheet1
2014 Backflow Preventer Line Testing
Sheet1
2015 Backflow Preventer Line Testing
Sheet1