VSC Fire & Security, Inc.
10640 Iron Bridge Rd., Suite G
Jessup, MD 20794
(301) 575-1500 Office
(301) 575-1571 www.vscfs.com
Inspector: James Ivison Inspection date: 10/25/16
Inspection performed in accordance with NFPA 25 Standard for the Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems
Annual Fire Sprinkler System Inspection
Inspection conducted at location:
Grounds Maint Complex & Warehouse Building #19288 1801918-02 11 North 4th Street
St. Louis, MO 63102
Phone: (410) 668-8000 Fax:
For Customer:
EBL Engineers, LLC 01088E0191 8005 Harford Rd
Baltimore, MD 21234 Phone: Fax:
Jeff McBride JMcBride@EBLEngineers.com
Page 1 of 4Grounds Maint Complex & Warehouse Building #19288
Notifications Prior to Testing Monitoring entity notified? Yes
Who was notified at Monitoring entity? Arrowhead Dispatch
Building occupants notified? Yes
Who of the building occupants were notified? All
Building management notified? Yes
Who in Building Management was notified? All
Building management time notified 7:15 AM
Notifications After Testing Building management Yes
Who in Building Management was notified? ALL
Monitoring agency Yes
Who at Monitoring Agency was notified? Arrowhead dispatch
Building occupants Yes
Who of building occupants was notified? All
Date system restored to normal operation. 10/25/2016
Time system restored to normal operation. 2:30 PM
System Summary Number of Systems at Site
Items Total Systems
Wet Sprinkler System 1
Wet Riser Main Drain/No Check valve - 1 gauge
Exterior of connection in good condition and gauge operable? Yes
Static Pressure before valve opened 65
Residual Pressure with valve open 55
Static Pressure after valve closed 75
Record time (seconds) for supply water pressure to return to original static pressure. 2
Gauges on valve, when compared to calibrated gauge is error less than 3% full or gauge has been recalibrated or replaced? No
Main Drain Test Pressures less than 10% reduction in flow from original acceptance test or previous test results? Pass
Is there adequate drainage available? Yes
New tag color or seal #. N/A
Wet Sprinkler System Inspection
Sprinkler heads free of corrosion, foreign material, paint or damage, no signs of leakage and heads installed in proper orientation? Yes
Minimum clearance maintained below all sprinklers? Yes
# replacement sprinkler heads per number installed in the head box comply: 6 per 1-300: 12 per 301 to 1,000: 24 per > 1,000? Yes
Sprinkler head wrench for each type head provided in head box? Yes
System piping free of mechanical damage, leaks, corrosion, misalignment, or other loads or pipe hung from system? Yes
Pipe hangers and seismic braces secure and undamaged? Yes
Adequate heat to maintain minimum building temperature of 40 deg F, and building free of conditions exposing pipe to freezing? Yes
All sprinklers in this building been manufactured after 1920? Yes
All sprinklers in building less than 50 years old or, if fast response, less than 20 years old, or if older, representative samples tested within the last 10 years? Yes
If dry sprinklers are installed in building, and have been in service for 10 years, have they been replaced or a representative sample tested? No
Wet Sprinkler System
Page 2 of 4Grounds Maint Complex & Warehouse Building #19288
Waterflow Alarm Switch
Area/Location Flow switch free of damage with its electrical connections secure?
Water flow activate alarm when open test connection/bypass?
Secs. to activate
M1-24 Main fire service Label- waterflow Pass Pass 24
Hydraulic Nameplate
Area/Location Nameplate securely attached to sprinkler riser & is legible?
Yes
Control Valves
Type Area/Location Condition Position Secured Size Exercised Seal
Control valves Backflow Discharge No Yes Yes 4" Yes N/A
Control valves Backflow Suction No Yes Yes 4" Yes N/A
Control valves System Control No Yes Yes 4" Yes N/A
Other Components
Fire Department Connection
FDC visible and accessible, without damage and signs in place? Pass
Couplings and swivels free of damage and rotate smoothly? Pass
Caps, plugs and gaskets in place and free from damage? Pass
Check valve clapper free from leaks and automatic drain valve in place and operating properly? Fail
Internal Pipe Exam
Internal pipe exam - System free of evidence of foreign organic and inorganic material needing to be removed by checking flushing connection end of one main and removing one sprinkler near end of branch line? No
Enter date of last pipe exam performed. no
Tamper Switch
Area/Location Visual Functional
M1-25 System Control Label- Water Tamper Pass Pass
M1-29 Backflow Disc. label- PIV Valve Pass Pass
M1-30 Backflow Suc. label- PIV Valve 2 Pass Pass
Comments
Deficiencies Fire Department Connection
Check valve clapper free from leaks and automatic drain valve in place and operating properly?
Technician Response: NO AUTOMATIC DRAIN ON FDC
Deficiencies not covered in Questions
Deficiencies found, in addition to standard questions.
Technician Response: Found 4 missing escutcheon plates 2 in confernce room by main entry 1 in offices too the left of the main entry 1 in 2nd floor storage room
Wet Sprinkler System Inspection
Page 3 of 4Grounds Maint Complex & Warehouse Building #19288
Liability Release Statement:
The owner and/or designated representative acknowledges the responsibility of the operating condition of the component parts at the time of this inspection. It is agreed that the inspection service provided by the contractor as prescribed herein is limited to performing a visual inspection and/or routine testing, and any investigation or unscheduled testing, modification, maintenance, repair, etc., of the component parts is not included as part of the inspection work performed. It is further understood that all information contained herein is provided to the best of the knowledge of the party providing such information.
Customer: JEFF-19288 GROUNDS & MAINT. COMPLEX
10/25/16 10/25/16
Technician: James Ivison
If dry sprinklers are installed in building, and have been in service for 10 years, have they been replaced or a representative sample tested?
Technician Response: 2 dry sidewalls at loading dock and 1 in spare head box are older than 10 years old dated 2002 should be sent off for testing or be replaced
Internal Pipe Exam
Internal pipe exam - System free of evidence of foreign organic and inorganic material needing to be removed by checking flushing connection end of one main and removing one sprinkler near end of branch line?
Technician Response: FIVE YEAR SERVICES ARE NOT INCLUDED IN CONTRACT/INSPECTION - SHOULD YOU DESIRE TO HAVE
THIS SERVICE PERFORMED, PLEASE CALL FOR AN ESTIMATE
Wet Riser Main Drain/No Check valve - 1 gauge
Gauges on valve, when compared to calibrated gauge is error less than 3% full or gauge has been recalibrated or replaced?
Technician Response: FIVE YEAR SERVICES ARE NOT INCLUDED IN CONTRACT/INSPECTION - SHOULD YOU DESIRE TO HAVE
THIS SERVICE PERFORMED, PLEASE CALL FOR AN ESTIMATE
Control valves Backflow Discharge Kennedy OS&Y OS&Y
Valve have proper signs, accessible and free of leaks, provided with the appropriate wrenches, if needed?
Technician Response: SIGNS MISSING
Control valves Backflow Suction Kennedy OS&Y OS&Y
Valve have proper signs, accessible and free of leaks, provided with the appropriate wrenches, if needed?
Technician Response: SIGNS MISSING
Control valves System Control Victaulic Butterfly Butterfly
Valve have proper signs, accessible and free of leaks, provided with the appropriate wrenches, if needed?
Technician Response: SIGNS MISSING
Page 4 of 4Grounds Maint Complex & Warehouse Building #19288
VSC Fire & Security, Inc.
10640 Iron Bridge Rd., Suite G
Jessup, MD 20794
(301) 575-1500 Office
(301) 575-1571 www.vscfs.com
Inspector: Daniel Bowen Inspection date: 10/31/16
Inspection conducted at location:
Grounds Maint Complex & Warehouse Building #19288 1801918A-03 11 North 4th Street
St. Louis, MO 63102
Phone: (410) 668-8000 Fax:
For Customer:
EBL Engineers, LLC 01088E0191 8005 Harford Rd
Baltimore, MD 21234 Phone: Fax:
Inspection performed in accordance with NFPA 72 National Fire Alarm Code
Annual Fire Alarm System Inspection
Jeff McBride JMcBride@EBLEngineers.com
Grounds Maint Complex & Warehouse Building #19288 Page 1 of 7
Batteries
Type Area/Location Visual Insp
Battery Voltage
Charge Test
Charger Voltage
Discharge Test
Install Date
Funct.
Test
Fire Alarm Battery - Sealed Lead Acid FACP Pass 12.18 Pass 30.05 Fail
INSTALLE
D
10/24/2008 Fail
Fire Alarm Battery - Sealed Lead Acid FACP Pass 12.93 Pass 30.05 Fail
INSTALLE
D
10/24/2008 Fail
Prior To Any Testing Monitoring entity notified? Yes
Who was notified at Monitoring entity? ARROWHEAD DISPATCH
Building occupants notified? Yes
Who of the building occupants were notified? ALL
Building management notified? Yes
Who in Building Management was notified? RICK KILLINGSWORTH
Building management time notified 10:00 AM
Specify other N/A
Other who N/A
Name of AHJ (notified) of any impairments
OWNER/OWNER'S REP. NOTIFIED IF ANY
IMPAIRMENTS FOUND
AHJ (notified) of any impairments time OWNER MUST NOTIFY AHJ OF ANY IMPAIRMENTS
Notifications Testing Is Complete Monitoring agency Yes
Who at Monitoring Agency was notified? ARROWHEAD DISPATCH.
Building management Yes
Who in Building Management was notified? RICK KILLINGSWORTH
Building occupants Yes
Who of building occupants was notified? ALL
Specify what other was notified N/A
List any devices that did not operate correctly, (enter N/A if all working properly). DEFICIENCIES, IF ANY, LISTED IN DEFICIENCY
SECTION.
Date system restored to normal operation. 10/25/2016
Time system restored to normal operation. 2:00 PM
Control Panel and Power Devices Main Fire Alarm Panel
BASEMENT ELEC. RM. SIMPLEX 4010
Lights/LEDs function properly? Pass Acknowledge/silence button functions properly? Pass Panel labels correct? Pass Central station interface - alarm signals Fail Central station interface - trouble signals Fail Central station interface - supervisory signals Fail Proper # of portable handsets for comm. system? N/A Portable handsets operate properly? N/A Ground fault detection connected? Pass Fire panel free from all grounds? Pass Batteries installed and operating properly? Fail Panel Addressable? Addressable Operating instructions posted? Pass Correct fuses installed? Pass Disconnect switches operating properly? Pass
Grounds Maint Complex & Warehouse Building #19288 Page 2 of 7
Duct Detectors
Type Address Area/Location Visual Insp Functional Test
Sensitivity Test Test Method
Duct Detector M1-18 AHU RETURN Pass Pass N/A N/A
Duct Detector M1-19 AHU SUPPLY Pass Pass N/A N/A
Smoke Detectors
Type Address Area/Location Visual Insp Functional Test
Smoke Detector Without Sensitivity M1-1 1ST FL. ELEC. RM. @ FACP Pass Pass
Smoke Detector Without Sensitivity M1-10 SUPPLY ROOM Pass Pass
Smoke Detector Without Sensitivity M1-15 2ND FL. ELEV. LOBBY Pass Pass
Smoke Detector Without Sensitivity M1-16 ELEVATOR SHAFT Pass Pass
Smoke Detector Without Sensitivity M1-2 1ST FL. ELEV. MACH. RM. Pass Pass
Smoke Detector Without Sensitivity M1-4 1ST FL. ELEV. LOBBY Pass Pass
Smoke Detector Without Sensitivity M1-8 JANITORS CLOSET Pass Pass
Heat Detectors
Type Address Area/Location Visual Insp Functional Test
Heat Detector M1-17 ELEVATOR SHAFT Pass Pass
Heat Detector M1-3 1ST FL. ELEV. MACH. RM. Pass Pass
Pull Stations
Type Area/Location Visual Insp Functional Test
Pull Station - Manual M1-11 2ND FL. MAIN FL. Pass Pass
Pull Station - Manual M1-12 TRUCK BAY Pass Pass
Pull Station - Manual M1-13 WAREHOUSE STAIRS Pass Pass
Pull Station - Manual M1-14 WAREHOUSE ENTRY Pass Pass
Pull Station - Manual M1-5 1ST FL. MECH. RM. Pass Pass
Pull Station - Manual M1-6 1ST FL. CORRIDOR Pass Pass
Pull Station - Manual M1-7 1ST FL. WAREHOUSE Pass Pass
Pull Station - Manual M1-9 2ND FL. STAIR Pass Pass
Device Summary Items Total Devices Total Inspected Total Failed
Duct Detectors 2 2 0
Fire Alarm Box Devices 8 8 0
Heat and Other Detectors 2 2 0
Miscellaneous Devices 3 3 3
Smoke Detectors-No Sensitivity 7 7 0
Total 22 22 3
Miscellaneous Devices
Type Area/Location Functional Test
Elevator Fire Hat Fail
Elevator Recall Fail
Elevator Shunt Trip Fail
Grounds Maint Complex & Warehouse Building #19288 Page 3 of 7
Comments
Grounds Maint Complex & Warehouse Building #19288 Page 4 of 7
Deficiencies Additional Deficiencies not covered in Questions
Enter information about deficiency; list name of device first, then explanation.
Technician Response: ACTIVATION OF ELEVATOR MACHINE ROOM, HOISTWAY, OR ELEVATOR LOBBY DEVICES FAILED TO INIATE EITHER ELEVATOR RECALL OR SHUNT TRIP FUNCTIONS. SHOULD BE INVESTIGATED AND RECTIFIED ASAP.
Elevator Recall
Functional Test
Technician Response: ELEVATOR CAB DID NOT RECALL ON ACTIVATION OF MACHINE ROOM, LOBBY OR HOISTWAY SMOKE
DETECTORS.
Elevator Shunt Trip
Technician Response: ELEVATOR FAILED TO SHUNT TRIP UPON ACTIVATION OF MACHINE ROOM OR HOISTWAY HEAT
DETECTORS.
Elevator Fire Hat
Technician Response: FAILED TO OPERATE.
Main Fire Alarm Panel
BASEMENT ELEC. RM. SIMPLEX 4010 4010 -
Central station interface - alarm signals
Technician Response: SIGNAL NOT RECIEVED AT ARROWHEAD DISPATCH.
Main Fire Alarm Panel
BASEMENT ELEC. RM. SIMPLEX 4010 4010 -
Central station interface - trouble signals
Technician Response: SIGNAL NOT RECIEVED AT ARROWHEAD DISPATCH.
Main Fire Alarm Panel
BASEMENT ELEC. RM. SIMPLEX 4010 4010 -
Central station interface - supervisory signals
Technician Response: SIGNAL NOT RECIEVED AT ARROWHEAD DISPATCH.
Main Fire Alarm Panel
BASEMENT ELEC. RM. SIMPLEX 4010 4010 -
Batteries installed and operating properly?
Technician Response: BATTERIES HAVE INSUFFICIENT CURRENT AND/OR VOLTAGE - REPLACEMENT NECESSARY
BATTERIES INSTALLED 10/24/2008.
Fire Alarm Battery - Sealed Lead Acid
FACP -
Discharge test
Technician Response: BATTERIES HAVE INSUFFICIENT CURRENT AND/OR VOLTAGE - REPLACEMENT NECESSARY
BATTERIES OUT OF DATE.
Fire Alarm Battery - Sealed Lead Acid
FACP -
Did battery pass or fail overall functional test?
Technician Response: BATTERIES HAVE INSUFFICIENT CURRENT AND/OR VOLTAGE - REPLACEMENT NECESSARY
BATTERIES OUT OF DATE.
Fire Alarm Battery - Sealed Lead Acid
FACP -
Discharge test
Technician Response: BATTERIES HAVE INSUFFICIENT CURRENT AND/OR VOLTAGE - REPLACEMENT NECESSARY
BATTERIES OUT OF DATE.
Grounds Maint Complex & Warehouse Building #19288 Page 5 of 7
Fire Alarm Battery - Sealed Lead Acid
FACP -
Did battery pass or fail overall functional test?
Technician Response: BATTERIES HAVE INSUFFICIENT CURRENT AND/OR VOLTAGE - REPLACEMENT NECESSARY
BATTERIES OUT OF DATE.
Grounds Maint Complex & Warehouse Building #19288 Page 6 of 7
The owner and/or designated representative acknowledges the responsibility of the operating condition of the component parts at the time of this inspection. It is agreed that the inspection service provided by the contractor as prescribed herein is limited to performing a visual inspection and/or routine testing, and any investigation or unscheduled testing, modification, maintenance, repair, etc., of the component parts is not included as part of the inspection work performed. It is further understood that all information contained herein is provided to the best of the knowledge of the party providing such information.
Customer: NPS-JEFF GROUNDS/MAINTENANCE #19288
10/25/16 10/25/16
Technician: Daniel Bowen
Grounds Maint Complex & Warehouse Building #19288 Page 7 of 7
Century Fire Sprinklers, Inc.
27 Cassens Ct.
Fenton, MO 63026 (314)692-8011 Office (314)692-8012 Fax
City State:
System #
Contract #
Owner's Section Y N/A N
Owner (Print Name):
Y N/A N Y N/A N Gauges' -Normal air and water pressure maintained Control Valves in the correct (open or closed) position Control Valves Sealed, Locked or supervised Control Valves are accessible Control Valves are free from damage or leaks Control Valves are properly identified Alarm Valves are free of damage Alarm Valves are accessible
Y N/A N Alarm Devices free of physical damage Hydraulic nameplate, if provided, securely attached. Pressure reducing valve maintaining downstream pressure
Y N/A N Proper number & type of spare sprinklers Y N/A N Proper Spare Sprinkler wrench
Visible Sprinklers free of obstruction to spray pattern?
Visible Sprinklers free of foreign materials including paint Visible Sprinklers free of physical damage
Y N/A N
Visible Pipe has no external corrosion
Inspections to be done every 5 years Alarm Valves, strainers, filters and restricted orifice pass internal inspection
Check Valves internally inspected and all parts operate properly, move freely and are in good condition
Riser FDC Check Valve is not leaking
Visible Pipe in good condition Visible Pipe free of mechanical damage & not leaking
Electrical components in service
Pressure reducing valve in good condition
Zip Code
Fire Department Connection
FDC is visible and accessible FDC swivels/couplings undamaged/rotate smoothly
Annual Inspections
Visible Sprinklers free of corrosion
Piping
Visible Pipe is properly aligned Visible Pipe has no external loads Visible pipe hangers and seismic braces not damaged or loose
Pressure Reducing Valve
FDC caps in place & undamaged FDC gaskets in place and in good condition FDC Identification sign in place FDC automatic drain valve in place and operating properly FDC free of obstructions
Sprinklers
Pressure reducing valve in open position /not leaking
Annual Report of Inspection, Testing & Maintenance of Wet Pipe Fire Sprinkler Systems
Has system remained in service without modification since last inspection?
Was the system free of actuation's devices or alarms since the last inspection?
Are all fire protection systems in service?
Address:
Has the occupancy classification and hazard of contents remained the same since last inspection?
Name of Inspected Property:
Is the building occupied?
Signature & Date
Arch Grounds Building
201 Poplar St.
St. Louis Mo 63102
Craig McGraw
3-17-17
Fenton, MO 63026 (314)692-8011 Office (314)692-8012 Fax
Y N/A N Y N/A N psi psi
Y N/A N Y N/A N
Y N/A N
Y N/A N
Y N/A N Y N/A N
Y N/A N Extra High, Very High & Ultra High Temp Sprinklers Tested Gauges checked against calibrated gauge or replaced
Y N/A N Y N/A N
Y N/A N Obstructive material discharged during waterflow test Foreign material found in dry-pipe valves, check valves or pumps Heavy discoloration of water during drain test or plugging of inspectors test Plugging of sprinklers found during activation or alteration Plugging found in piping dismantled during alterations
Record of broken main in vicinity.
abnormally frequent false-tripping of dry pipe valves
Y N/A N System is returned to service after an extended period out of service.
ALARM PANEL CLEAR
SYSTEM RETURNED TO SERVICE
PIV opened until spring or torsion is felt in rod, then turned back 1/4 turn
Fast response sprinklers in service less than 20 yrs or tested within last 10 yrs
Standard response sprinklers less than 50 yrs old or tested within last 10 years
Standard response sprinklers 75 or more years old passed test or tested within last 5 years
Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show signs of grease buildup
Defective intake screen for pump
Annual Maintenance
If sprinklers have been replaced, were they proper replacements
Backflow devices passed full flow test Test to be done every 5 years
Main Drain test conducted downstream of backflow Supply water gauge reading before flow (static) Gauge reading during stable flow (residual)
Sprinklers Are all sprinklers in service dated 1920 or later
Annual Testing Main Drain Alarm Devices
Valve Supervisory Switches indicate movement Water Flow (Vane Type & Pressure) tested and is operational Mechanical Water flow alarm (other than vane type) tested and is operational
Backflow Preventer Backflow devices passed backflow test
All control valves operated through full range and returned to normal position
Pressure regulating control valves
Are results comparable to previous test
Adequate drainage provided before flow testing
Test conducted with inspector's test connection Antifreeze Loop
Specific gravity of antifreeze correct Control Valves
All sprinkler regulating control valves pass full flow test Post Indicator Valves
If any of the following were discovered, was an obstruction investigation conducted and the system flushed
Failure to flush yard piping or surrounding public mains following new installation or repairs.
There is reason to believe the system contains sodium silicate or its derivatives
Obstruction investigation findings to be explained in comments
Operating stem of all OS&Y valves lubricated, completely closed and reopened
60 ✔
Fenton, MO 63026 (314)692-8011 Office
(314)692-8012 Fax
Company: Century Fire Sprinklers, Inc.
Company Address: 27 Cassens Ct., Fenton, MO I state that the information on this form is correct at the time and place of my inspection and that all equipment tested at this time was left in operational condition upon completion of this inspection except as noted in the comments section above.
Printed name of inspector:
Signature of Inspector
Date of inspection: License or Certification number (if applicable)
Inspector Information
Comments (any "No" answers, test failures or other problems found with the sprinkler system must be explained here)
1) there are dry sidewalls from 2002.
Water flow alarm time: 28 sec.
Cory Schulte
Additional Comments
Fenton, MO 63026 (314)692-8011 Office (314)692-8012 Fax
Model: Size: Serial Number: Air Gap
DC RP PVB
Application Device Protected
____ Hazard Class ____ Freezing ____ in ____ Pass
____ ____ Flooding ____ in ____ Fail
Date of Test Describe the Equipment that the Back-Flow Device Services
Number New ____ Existing ____ Fire Suppression ____ Process ____
Lawn Irrigation ____ Plumbing ____
Yes ____ No ____ Other
Passed Failed INITIAL TEST FINAL TEST Passed Failed
Double Check Valve Assembly:
1st CHECK held in direction of flow 1st CHECK held in direction of flow
PSID (5 PSID or more) ____ ____ _______ PSID (1 PSID or more) ____ ____
RELIEF VALVE opened at 2nd CHECK held backpressure ____ ____
____ PSID (2 PSID or more) ____ ____ No. 2 Shut Off Valve leak tight ____ ____
DIFFERENCE (1st check-relief) 2nd CHECK held in direction of flow
____ PSID (3 PSID or more) ____ ____ _______ PSID (1 PSID or more) ____ ____
2nd CHECK held backpressure ____ ____ INITIAL TEST ____ FINAL TEST ____ Passed Failed
No. 2 Shut Off Valve leak tight ____ ____ Pressure Vacuum Assembly
OPTIONAL TEST Test #1 Shutoff Valve
Relief Valve (exercised to open position) ____ ____ - held pressure tight ____ ____
Test CHECK VALVE held in direction
Comments: of flow ____ PSID (1 PSID or more) ____ ____
Test AIR INLET VALVE to open
____ PSID (1 PSID or more) ____ ____
PVB may not be repaired, must be replaced
Repaired by: (Print name and provide Signature)
Final Test By: (Print name and provide Signature)
Owner or Owner's Representative Date
Company: Century Fire Sprinklers, Inc.
Certification Number and Expiration Date:
THE ABOVE REPORT IS CERTIFIED TO BE TRUE, ACCURATE AND COMPLETE
Tested By: (Print name and provide signature)
Reduced Pressure Assembly
INITIAL TEST FINAL TEST
Is the assembly properly tagged?
Type of System
_______________________Permit Date _____________________
Century Fire SprinklersContractor
Height Off Floor
Permit Information Installation Status
Containment
Isolation Hazard Item
Fire Protection Sprinkler System
Supply
Gap
(from MO part 10.CSR 11.010) Air Gap (2xSuppy Diameter)
BACKFLOW PREVENTION ASSEMBLY TEST DATA AND MAINTENANCE REPORT
Manufacturer: Type of Device:
Describe physical location of Backflow Device:
Customer:
Address: City: Zip Code:
Address of Location of Backflow:
Arch Grounds Building
201 Poplar St. St. Louis 63102
Same
In the lower level by the loading dock.
Colt 200 4" 1226321001 ✔
2 ✔
2 ✔
3-17-17 1'-0"
1.6
1.8
Cory Schulte
07-0175 1-31-2018
Ames
Building Owner/Representative Has building occupancy, hazard, water supply or building arrangement affecting system effectiveness remained the same since last inspection (4.1.6.) Yes
Areas containing water-filled piping used for fire sprinkler systems, maintain a minimum temperature of 40°F (4°C), and are not exposed to freezing conditions. (4.1.1.1) Yes
Owner/Representative Signature
System Summary Number of Systems at Site Items Total Systems
Wet System 1
Wet System Wet System Inspection
Sprinkler heads free of leakage, corrosion, external loading, damage or loss of fluid in glass bulb element, and pointed in proper direction. (5.2.1.1.1) Pass
Escutcheons and coverplates in place, if applicable. (5.2.1.1.5) Fail Minimum clearance maintained below all sprinklers. (5.2.1.2) Pass Replacement sprinkler heads per number of installed sprinklers available in head box. (5.4.1.5.4) Fail Sprinkler head wrench for each type head provided in head box (5.4.1.6) Fail List of sprinklers installed on the property posted on head box. (5.4.1.5.6) Pass System piping free of mechanical damage, leaks, corrosion, & without external loads on or hung from piping. (5.2.2.1 & 5.2.2.2) Pass
Pipe hangars, braces & supports not damaged, loose or unattached. (5.2.3) Pass Sprinklers in the building in service for 50 years, have been replaced or sample tested. (5.3.1.1.1) N/A Sprinklers with fast-response elements in service for 20 years have been replaced or sample tested.
(5.3.1.1.1.3) N/A
Dry sprinklers in service for 10 years have been replaced or sample taken (if dry sprinklers present).
(5.3.1.1.1.6) No
Wet System Wet Riser Main Drain/No Check Valve
Wet System Riser Room Valves & trim free of physical damage, & valves in normal position. (13.4.1.1) Pass Pressure (psi) shown on System side pressure gauge. 60 Hydraulic nameplate, if applicable, securely attached and is legible (5.2.5) Pass Size of main drain 2" Pressure (psi) shown on Supply Water pressure gauge. (13.2.5) 60 Residual Pressure with valve open (13.2.5) 50 Static Pressure after valve closed (13.2.5) 75 Main Drain Test Pressure less than 10% reduction in flow from original acceptance test or previous test results (13.2.5.3) Pass
Valve Status Test - Valves open when returned to service. (13.3.3.4) Pass Gauge on valve, when compared to calibrated gauge is error less than 3% full or gauge has been recalibrated or replaced. (13.2.7.2 & 13.2.7.3)) N/I
Inspector's Test Connection Area/Location Operates properly
Wet System Maintenance @ Personel Door Pass
Grounds Bldg. Wet AIP Page 2 of 4 Powered by ASURiO Inspection Systems, Copyright 2010. All Rights Reserved ASURiO
Supervisory Devices Type Area/Location Visual Insp Functional Test
Tamper Switch Backflow #1 Riser Room Pass Pass
Tamper Switch Backflow #2 Riser Room Pass Pass
Tamper Switch Wet System Basement @ Laoding Docks Pass Pass
Control Valves Type Area/Location Model
Size Accessible Condition Secured Exercised Seal Valve Test
Control Valve -locked/tamper
Backflow #1 Riser Room
OS and Y 4" Pass Pass Pass Pass NA Pass
Control Valve -locked/tamper
Backflow #2 Riser Room
OS and Y 4" Pass Pass Pass Pass NA Pass
Control Valve -locked/tamper
Wet System Riser Room Butterfly 4" Pass Pass Pass Pass NA Pass
Alarm Devices Type Area/Location Visual Insp Functional Test
Horn/Strobe Pass Pass
Waterflow Alarm - Vane Type Wet System Basement @ Laoding Docks Pass Pass 22 Seconds
Comments
Common Components
FDC visible and accessible, and signs in place. (13.8.1) Pass Couplings and swivels free of damage and rotate smoothly. (13.8.1) Pass Caps, plugs and gaskets in place and free from damage. (13.8.1) Pass Check valve free from leaks, automatic drain valve and clapper in place and operating properly. (13.8.1) Pass Interior of the connection free of obstructions. (13.8.1) Pass Visible piping supplying FDC undamaged. (13.8.1) Pass Internal inspection of check valve - components operate properly, cleaned/repaired as needed. (13.4.2.1) N/I Hydrostatic test results of piping from FDC to check valve acceptable. (13.8.5) N/I
Deficiencies *PAR response indicated "Pass After Repair". Technician notes a deficiency of a device, and repairs the deficiency during inspection.
Wet System Inspection
Ques: Escutcheons and coverplates in place, if applicable. (5.2.1.1.5)
Technician Response: Escutcheon - Missing 4 may need to lower heads for prpoer fit.
Ques: Replacement sprinkler heads per number of installed sprinklers available in head box. (5.4.1.5.4) Technician Response: Missing Sidewall heads at garage doors.
Grounds Bldg. Wet AIP Page 3 of 4
The owner and/or designated representative acknowledges the responsibility of the operating condition of the component parts at the time of this inspection. It is agreed that the inspection service provided by the contractor as prescribed herein is limited to performing a visual inspection and/or routine testing, and any investigation or unscheduled testing, modification, maintenance, repair, etc., of the component parts is not included as part of the inspection work performed. It is further understood that all information contained herein is provided to the best of the knowledge of the party providing such information.
Customer: Bruce Cook
4/10/18 4/10/18
Tech: Andy Laskowsky
Not Inspected
Question: Internal inspection of check valve - components operate properly, cleaned/repaired as needed. (13.4.2.1) Technician Response: Review records and schedule as needed. Five year services are not part of contract. Please Call if a proposal is desired.
Question: Hydrostatic test results of piping from FDC to check valve acceptable. (13.8.5) Technician Response: Review records and schedule as needed. Five year services are not part of contract. Please Call if a proposal is desired.
Wet Riser Main Drain/No Check Valve Wet System Riser Room Question: Gauge on valve, when compared to calibrated gauge is error less than 3% full or gauge has been recalibrated or replaced. (13.2.7.2 & 13.2.7.3)) Technician Response: Review records and schedule as needed. Five year services are not part of contract. Please Call if a proposal is desired.
Wet System Inspection
Ques: Sprinkler head wrench for each type head provided in head box (5.4.1.6)
Technician Response: See photo. Wiil need wrench for sidewall head.
Ques: Dry sprinklers in service for 10 years have been replaced or sample taken (if dry sprinklers present).
(5.3.1.1.1.6)
Technician Response: Review sidewall head at man door loading docks
Grounds Bldg. Wet AIP Page 4 of 4
2425 Amann Drive
Boyer Fire Protection
Belleville, IL 62220 www.boyerfire.com
Phone: 618-222-1500 Fax: 618-222-1502
Inspection date: 04/15/2018
Deficiencies *PAR response indicated "Pass After Repair". Technician notes a deficiency of a device, and repairs the deficiency during inspection.
Ques: Escutcheons and coverplates in place, if applicable. (5.2.1.1.5)
Technician Response: Escutcheon - Missing 4 may need to lower heads for prpoer fit.
Ques: Replacement sprinkler heads per number of installed sprinklers available in head box. (5.4.1.5.4)
Technician Response: Missing Sidewall heads at garage doors.
Ques: Sprinkler head wrench for each type head provided in head box (5.4.1.6)
Technician Response: See photo. Wiil need wrench for sidewall head.
Deficiency Report
Inspection Location Grounds Building JEF04-2
201 Poplar Street
St. Louis, MO 63102
Phone: Fax:
Customer Gateway Arch National Park JEF04
11 N. 4th Street
St. Louis, MO 63102
Phone: Fax:
Grounds Bldg. Wet AIP Page 1 of 2
The owner and/or designated representative acknowledges the responsibility of the operating condition of the component parts at the time of this inspection. It is agreed that the inspection service provided by the contractor as prescribed herein is limited to performing a visual inspection and/or routine testing, and any investigation or unscheduled testing, modification, maintenance, repair, etc., of the component parts is not included as part of the inspection work performed. It is further understood that all information contained herein is provided to the best of the knowledge of the party providing such information.
Customer: Bruce Cook
4/10/18 4/10/18
Tech: Andy Laskowsky
Ques: Dry sprinklers in service for 10 years have been replaced or sample taken (if dry sprinklers present). (5.3.1.1.1.6)
Technician Response: Review sidewall head at man door loading docks
Grounds Bldg. Wet AIP Page 2 of 2
ST. LOUIS CITY
BACKFLOW DEVICE TEST REPORT
Address: ______________________________________________________________________
Company Name: _______________________________________________________________
Contractor: __________________________ Date Tested: _____________________________
Certified Tester: ______________________ License No: ______________________________
Make & Model Serial Number Size
Detailed Location
Check Valve #1 Check Valve #2 Relief Valve
Initial Test Leaked ______________ ( )
Closed Tight _________ ( )
Leaked ______________ ( )
Closed Tight _________ ( )
Opened at ___________PSI Reduced pressure
Did Not Open ________ ( )
Final Test Closed Tight _________ ( ) Closed Tight _________ ( ) Opened at ___________PSI Reduced Pressure
Contact Person: ________________________________________________________________
2425 Amann Dr., Belleville, IL 62220 5555 West Park Drive, St. Louis, MO 63110
IL Phone: (618) 222-1500 Fax: (618) 222-1502
MO Phone: (314) 241-9944 Website: www.boyerfire.com
Fire Backflow Testing
201 Poplar Street, St. Louis, MO 63101
Gateway Arch National Park - Grounds Building
Boyer Fire Protection
Andy Laskowsky 07-2995
4"
Report of Inspection/Test General Questions
OWNER SECTION
Is the building occupied? Yes
No
NA
Has the occupancy classification, hazard of contents, and/or storage method remained the same since the last inspection?
Yes
No
NA
Are all fire protection systems in service? Yes
No
NA
Has the system remained in service without modification since the last inspection?
Yes
No
NA
Was the system free of actuations of devices or alarms since the last inspection?
Yes
No
NA
FIRE DEPARTMENT CONNECTION
Is the FDC plainly visible and easily accessible? Yes
No
NA
Is the FDC easily accessible? Yes
No
NA
Are the FDC swivels and couplings not damaged? Yes
No
NA
Are the FDC caps and plugs in place and undamaged? Yes
No
NA
Are the FDC gaskets in place? Yes
No
NA
Is the FDC check valve free of leaks? Yes
No
NA
Is the clapper and automatic drain valve in place and properly operating?
Yes
No
NA
Is the FDC identification sign(s) in place? Yes
No
NA
Has the interior of the FDC been inspected for obstructions?
Yes
No
NA
Is the visible piping supplying the FDC undamaged? Yes
No
NA
If locking caps/plugs are in place, has an internal inspections been conducted?
Yes
No
NA
Was the connection free of obstructions? Yes
No
NA
SPRINKLER HEADS
Are there the proper number and type of spare sprinklers with a list in place?
Yes
No
NA
Are visible sprinklers in the proper position: upright, pendent, sidewall?
Yes
No
NA
Are visible sprinklers free of corrosion and physical damage?
Yes
No
NA
Is there proper clearance below the sprinklers? Yes
No
NA
Are visible sprinklers free of foreign materials including foreign paint?
Yes
No
NA
Is there liquid in all visible glass bulb sprinklers? Yes
No
NA
Page 1 of 6Copyright 2021 Inspect Point
Report of Inspection/Test Annual NFPA 25
2021-06-14 Property Gateway Arch Ranger Station 201 Poplar Street St. Louis MO 63102 Eric Turner 314-655-1714 Print Date: 2021-06-16 Inspection Ref #: C001325
Conducted by: Dan Love
Boyer Fire Protection 5555 W Park Ave St Louis MO 63110 314-241-9944 or 618-222-1500 inspect@boyerfire.com
Are there spare sprinklers and a sprinkler wrench? Yes
No
NA
Is the information sign attached and legible? Yes
No
NA
Are all the sprinklers dated 1920 or later? Yes
No
NA
PIPES
Are the visible pipe and fittings in good condition with no external corrosion?
Yes
No
NA
Do visible pipe and fittings have no mechanical damage or leaks?
Yes
No
NA
Does visible pipe have no external loads? Yes
No
NA
Are visible pipe hangers and seismic braces not damaged or loose?
Yes
No
NA
CONTROL VALVE AREA
Are the control valves with electrical supervision in correct (open or closed) position?
Yes
No
NA
Are the control valves with electrical supervision locked or is supervision in place?
Yes
No
NA
Are the control valves with electrical supervision accessible?
Yes
No
NA
Are the control valves with electrical supervision free from any leaks?
Yes
No
NA
Are the control valves with electrical supervision have the appropriate wrenches?
Yes
No
NA
Are the control valves with electrical supervision properly identified?
Yes
No
NA
VALVE AREA
Are all check valves externally inspected, operating properly, and are in good condition?
Yes
No
NA
Are the gauges on system operable and in good working condition?
Yes
No
NA
Are the gauges on system showing normal water supply pressure?
Yes
No
NA
Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?
Yes
No
NA
Do valve supervisory switches indicate movement? Yes
No
NA
The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes
No
NA
All control valves operated through full range and returned to normal position?
Yes
No
NA
BACKFLOW PREVENTERS
ALARMS
Are alarms and supervisory devices not damaged? Yes
No
NA
Page 2 of 6Copyright 2021 Inspect Point
Report of Inspection/Test Annual NFPA 25
2021-06-14 Property Gateway Arch Ranger Station 201 Poplar Street St. Louis MO 63102 Eric Turner 314-655-1714 Print Date: 2021-06-16 Inspection Ref #: C001325
Conducted by: Dan Love
Boyer Fire Protection 5555 W Park Ave St Louis MO 63110
MAINTENANCE
Was a drain test conducted after opening any closed valve?
Yes
No
NA
Page 3 of 6Copyright 2021 Inspect Point
Report of Inspection/Test Annual NFPA 25
2021-06-14 Property Gateway Arch Ranger Station 201 Poplar Street St. Louis MO 63102 Eric Turner 314-655-1714 Print Date: 2021-06-16 Inspection Ref #: C001325
Conducted by: Dan Love
Boyer Fire Protection 5555 W Park Ave St Louis MO 63110
MAIN DRAIN FLOW TESTS
System Initial static Residual Static Seconds to Return to
Initial Static
Flow Observed?
Did waterflow alarm operate?
Are results comparable to previous test?
Wet system 80 65 73 1 Yes Yes Yes
INSPECTORS TEST CONNECTION
System Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
Wet system Riser room ITV 35 Yes Yes Yes Yes Yes
VALVES
System Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
# of Turns
Wet system BF2 Riser room Butterfly 4 " Supervision Yes Yes Yes Yes N/A 7.5
Wet system BF2 Riser room Butterfly 4 " Supervision Yes Yes Yes Yes N/A 7.5
Page 4 of 6Copyright 2021 Inspect Point
Report of Inspection/Test Annual NFPA 25
2021-06-14 Property Gateway Arch Ranger Station 201 Poplar Street St. Louis MO 63102 Eric Turner 314-655-1714 Print Date: 2021-06-16 Inspection Ref #: C001325
Conducted by: Dan Love
Boyer Fire Protection 5555 W Park Ave St Louis MO 63110
Deficiencies - General Questions
None
Deficiencies - General Wet System Questions
None
Deficiencies - Wet system
None
Deficiencies - BF
None
Deficiencies - Inspectors Test Connection
None
Deficiencies - Valves
None
Page 5 of 6Copyright 2021 Inspect Point
Report of Inspection/Test Annual NFPA 25
2021-06-14 Property Gateway Arch Ranger Station 201 Poplar Street St. Louis MO 63102 Eric Turner 314-655-1714 Print Date: 2021-06-16 Inspection Ref #: C001325
Conducted by: Dan Love
Boyer Fire Protection 5555 W Park Ave St Louis MO 63110
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
Dan Love 2021-06-14
Client Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Client Name Signature Date Completed
Joe Brennan 2021-06-14
Page 6 of 6Copyright 2021 Inspect Point
Report of Inspection/Test Annual NFPA 25
2021-06-14 Property Gateway Arch Ranger Station 201 Poplar Street St. Louis MO 63102 Eric Turner 314-655-1714 Print Date: 2021-06-16 Inspection Ref #: C001325
Conducted by: Dan Love
Boyer Fire Protection 5555 W Park Ave St Louis MO 63110
StLCO Form: Test Rpt 0305b
C:\Documents and Settings\pw0l0b.000\Desktop\0305b Backflow Form.doc
BACKFLOW PREVENTION ASSEMBLY TEST DATA AND MAINTENANCE REPORT
Customer:
City and State: Zip Code
Address of Location of Back-Flow Device:
Describe physical location of Back-Flow Device:
Manufacturer: Model: Size: Serial Number: Type Of Device: ________ Air Gap
_______ DC _______ RP ________ PVB
Application :
__________ Containment
__________ Isolation
(from MO part 10.CSR 11.010):
Hazard Class _________
Hazard Item _________
Device protected from:
_____ Freezing
_____ Flooding
Air Gap (2 x Supply Diameter)
Supply ________ in _______ Pass
Gap ___________in _______ Fail
Date Of Test Describe the Equipment that the Back-Flow Device Services Height Off Floor
________________(FT/IN)
Permit Information
Number_________________________
Contractor____________________________
Permit Date___________________________
Installation Status
New_____ Existing_______
Is the assembly properly tagged?
Yes______ No________
Type Of System
Fire Suppression _____ Process Piping ____
Lawn Irrigation ______ Plumbing _______
Other _______________________________
INITIAL TEST_____ FINAL TEST______ PASSED FAILED
Reduced Pressure Assembly:
1st CHECK held in direction of flow
_____ PSID (5 PSID or more) ________ _______
RELIEF VALVE opened at
_____ PSID (2 PSID or more) ________ _______
DIFFERENCE (1st check-relief)
_____ PSID (3 PSID or more) ________ _______
2nd CHECK held backpressure ________ _______
No. 2 Shut-off Valve leak tight ________ _______
OPTIONAL TEST
Relief Valve (exercised to open Position) ________ _______
Comments:
INITIAL TEST____ FINAL TEST_____ PASSED FAILED
Double Check Valve Assembly:
1st CHECK held in direction of flow
______ PSID (1 PSID or more) ________ _______
2nd CHECK held backpressure ________ _______
No. 2 Shut-off Valve leak tight ________ _______
2nd CHECK held in direction of flow
______ PSID (1 PSID or more) ________ _______
FINAL TEST _______ PASSED _______ FAILED
Pressure Vacuum Breaker Assembly:
Test #1 Shutoff Valve
- held pressure tight. ________ _______
Test CHECK VALVE held in direction of flow ________ PSID (1 PSID or more) ________ _______
Test AIR INLET VALVE to open
________ PSID (1 PSID or more) ________ _______
PVB may not be repaired, must be replaced
THE ABOVE REPORT IS CERTIFIED TO BE TRUE, ACCURATE AND COMPLETE
Tested By: (Print name and provide Signature) Repaired By: (Print name and provide Signature)
Company Final Test By: (Print name and provide Signature)
Certification Number And Expiration Date Owner Or Owner’s Representative Date
1. This form is to be used and sent to St. Louis County for a failed test as well as a passed test.
Do not use one form for both the failed and passed test. Use a separate form for each.
2. This form must be filed within 30 days of test per state regulations and St. Louis County Ordinance.
3. Tester must sign this form.
Boyer Fire Protection 5555 West Park Ave.
St. Louis, MO 63110 Phone: 314-241-9944
Ames
Bike storage room
63102St. Louis, MO201 Poplar Street
Gateway Arch Ranger Station
3.8
PH-0104 ✔
✔ II
3.4 ✔
6-11-2021 Fire protection 2
Daniel Love
Boyer Fire Protection Daniel Love
SF-7372 06/30/21 6-11-2021
4Colt 200
StLCO Form: Test Rpt 0305b
C:\Documents and Settings\pw0l0b.000\Desktop\0305b Backflow Form.doc
BACKFLOW PREVENTION ASSEMBLY TEST DATA AND MAINTENANCE REPORT
Customer:
City and State: Zip Code
Address of Location of Back-Flow Device:
Describe physical location of Back-Flow Device:
Manufacturer: Model: Size: Serial Number: Type Of Device: ________ Air Gap
_______ DC _______ RP ________ PVB
Application :
__________ Containment
__________ Isolation
(from MO part 10.CSR 11.010):
Hazard Class _________
Hazard Item _________
Device protected from:
_____ Freezing
_____ Flooding
Air Gap (2 x Supply Diameter)
Supply ________ in _______ Pass
Gap ___________in _______ Fail
Date Of Test Describe the Equipment that the Back-Flow Device Services Height Off Floor
________________(FT/IN)
Permit Information
Number_________________________
Contractor____________________________
Permit Date___________________________
Installation Status
New_____ Existing_______
Is the assembly properly tagged?
Yes______ No________
Type Of System
Fire Suppression _____ Process Piping ____
Lawn Irrigation ______ Plumbing _______
Other _______________________________
INITIAL TEST_____ FINAL TEST______ PASSED FAILED
Reduced Pressure Assembly:
1st CHECK held in direction of flow
_____ PSID (5 PSID or more) ________ _______
RELIEF VALVE opened at
_____ PSID (2 PSID or more) ________ _______
DIFFERENCE (1st check-relief)
_____ PSID (3 PSID or more) ________ _______
2nd CHECK held backpressure ________ _______
No. 2 Shut-off Valve leak tight ________ _______
OPTIONAL TEST
Relief Valve (exercised to open Position) ________ _______
Comments:
INITIAL TEST____ FINAL TEST_____ PASSED FAILED
Double Check Valve Assembly:
1st CHECK held in direction of flow
______ PSID (1 PSID or more) ________ _______
2nd CHECK held backpressure ________ _______
No. 2 Shut-off Valve leak tight ________ _______
2nd CHECK held in direction of flow
______ PSID (1 PSID or more) ________ _______
FINAL TEST _______ PASSED _______ FAILED
Pressure Vacuum Breaker Assembly:
Test #1 Shutoff Valve
- held pressure tight. ________ _______
Test CHECK VALVE held in direction of flow ________ PSID (1 PSID or more) ________ _______
Test AIR INLET VALVE to open
________ PSID (1 PSID or more) ________ _______
PVB may not be repaired, must be replaced
THE ABOVE REPORT IS CERTIFIED TO BE TRUE, ACCURATE AND COMPLETE
Tested By: (Print name and provide Signature) Repaired By: (Print name and provide Signature)
Company Final Test By: (Print name and provide Signature)
Certification Number And Expiration Date Owner Or Owner’s Representative Date
1. This form is to be used and sent to St. Louis County for a failed test as well as a passed test.
Do not use one form for both the failed and passed test. Use a separate form for each.
2. This form must be filed within 30 days of test per state regulations and St. Louis County Ordinance.
3. Tester must sign this form.
Boyer Fire Protection 5555 West Park Ave.
St. Louis, MO 63110 Phone: 314-241-9944
Ames
Bike storage room
63102St. Louis, MO201 Poplar Street
Gateway Arch Ranger Station
3.8
PH-0104 ✔
✔ II
3.4 ✔
6-11-2021 Fire protection 2
Daniel Love
Boyer Fire Protection Daniel Love
SF-7372 06/30/21 6-11-2021
4Colt 200
| Grounds Backflow |
| 2012 JEFF Fire Backflow Testpg10001 |
| 2012 JEFF Fire Backflow Testpg20001 |
| Backflow Device Test Report Grounds 2014 |
| 10.25.2016 1801918 02 JEFF Ground Maint Complex Building 19288 |
| 10.31.2016 1801918A 03 JEFF Ground Maint Complex Warehouse Building 19288 Fire Alarm.2016 |
| 3.17.17 Arch Grounds Building Wet Systems Inspection Annual 1.2(1) |
| Wet Pipe Fire Sprinkler Systems |
| 3.17.17 Arch Grounds Building Backflow 3.17.17 |
| Sheet1 |
| Grounds Bldg AIP, 04-10-18 |
| Grounds Bldg AIP-Deficiency Report-04-10-18 |
| Grounds Building BF, 04-10-18 |
| Grounds Building Plbg BFs, 04-11-18 |
| Ranger Station 2018 Annual Fire Sprinkler and Backflows Inspection Agr 3 26 18 |
| Jefferson National Expansion Memorial |
| Quote DETAILS |
| Quote is Pending |
| WORK DETAILS |
| Backflow Inspection 2019 |
| Ranger Station AIP 6-14-21 |
| Ranger Station BF 6-14-21 |
File details come from the government source that posted it. Updated .