Base_B08 - SolicitationAtch2Drawings.pdf
PDF 6 MB Posted
- Attached to
- Remove and Install a New HVAC unit. Federal contract opportunity
- Solicitation number
- 140P6220B0002
About this file
This solicitation document outlines requirements for a federal contract to remove and replace the HVAC system at a National Park Service visitor center. Work includes disconnecting the existing geothermal piping loop and replacing it with a new fluid cooler and natural gas boiler located near the maintenance building. The existing piping within the visitor center will be replaced as indicated in the drawings. Existing heat pumps and an attic ductless split system will also be replaced. Energy recovery ventilators will be added. The solicitation is for qualified contractors to provide all labor, materials, equipment and supervision to complete the project. Responses are due by the date specified in the solicitation document. The contract will be awarded following proposal evaluation. Work must be completed according to specifications and drawings provided by the agency.
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTRACTOR
PARKING AREA
TEMPORARY STORAGE
AVAILABLE FOR EQUIPMENT
AND MATERIALS IN
MAINTENANCE SHOP
VISITOR CENTER
MAINTENANCE
BUILDING
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \a p u llm a n n
\D o c u m e n ts \R e v it te m p
\T S
A -M
E C
H
R
F O
S M a p u llm a n n
L T
M M
V .r v t
ARP
ARP
BGJ
01/03/2020
07310.007
G 00
COVER SHEET
EMERGENCY REPAIR AND REPLACEMENT OF GEOTHERMAL WELL-FIELD
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901
FINAL CD SUBMITTAL
01/03/2020
07310007FOSM- 0- G 00 COVER SHEET
CODE ANALYSIS
2012 INTERNATIONAL BUILDING CODE W/ APPENDICES
2009 INTERNATIONAL MECHANICAL CODE
2006 INTERNATIONAL FUEL GAS CODE
2006 INTERNATIONAL PLUMBING CODE
2009 INTERNATIONAL ENERGY CONSERVATION CODE
2017 NATIONAL ELECTRICAL CODE
SCALE: NTS
PROJECT LOCATION
ARCHITECTURAL
A 00 ARCHITECTURAL INFO SHEET
A101 FLOOR PLAN, ELEVATIONS & BUILDING SECTION
A102 MEZZANINE PLAN
A301 SCHEDULES, DOOR AND WINDOW DETAILS
GENERAL
G 00 COVER SHEET
MECHANICAL
M102 FIRST FLOOR PLAN - MECHANICAL
M103 SECOND FLOOR PLAN - MECHANICAL
M104 ATTIC LEVEL PLAN - MECHANICAL
M200 SITE PIPING PLAN - MECHANICAL
M201 LOWER LEVEL PIPING PLAN - MECHANICAL
M202 ATTIC LEVEL PIPING PLAN - MECHANICAL
M401 DETAILS - MECHANICAL
M402 DETAILS - MECHANICAL
M501 SCHEDULE - MECHANICAL
MECHANICAL
M 00 MECHANICAL INFO SHEET
M001 DEMOLITION PLAN - MECHANICAL
M002 DEMOLITION PLAN - MECHANICAL
M003 DEMOLITION PIPING PLAN - MECHANICAL
M004 DEMOLITION PIPING PLAN - MECHANICAL
M101 LOWER LEVEL PLAN - MECHANICAL
ELECTRICAL
E 00 ELECTRICAL INFO SHEET
E 01 ELECTRICAL GENERAL NOTES
E001 LOWER LEVEL - DEMOLITION
E002 MECHANICAL/ATTIC - DEMOLITION
E003 MAINTENANCE BUILDING PLAN - DEMOLITION
E101 LOWER LEVEL - POW. & AUX. SYS.
E102 MECHANICAL/ATTIC - POW. & AUX. SYS.
E103 MAINTENANCE BUILDING PLAN - ELECTRICAL
E201 SITE PLAN - ELECTRICAL
E301 ELECTRICAL SCHEDULES
STRUCTURAL
S 01 STRUCTURAL NOTES
S101 PLANS & DETAILS
S201 TYPICAL DETAILS
DRAWING INDEX
SCALE: NTS
CONTRACTOR PARKING AND STORAGE
DATE INITIAL
140P6220B0002 Attachment 2
TRUE
NORTH
PLAN
NORTH
NORTH
NORTH
ARROW
NAME
ELEVATION
LEVEL
MATCHLINE
AREA A
AREA B
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
XXXX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
150 SF
ROOM
NUMBER
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL
NUMBER
SHEET NUMBER
INDICATES DIRECTION
OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME
DESIGNATION
ROOM NUMBER
DESIGNATION
ROOM AREA
DESIGNATION
ROOM /
FRAMING
ELEVATION
EXTERIOR
ELEVATION
XX-XX
XX-XX
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
DOOR
NUMBER
DOOR NUMBER10
WINDOW
DESIGNATION
WINDOW DESIGNATION000
TA-X
TOILET
ACCESSORY
TOILET ACCESSORY
NUMBER
WALL
TYPE
LETTER
INDICATES
PARTITION OR
WALL TYPE
X
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE
DRAWING
ABBREVIATIONS
REF. DEMO NOTES ( )
REFERENCE LEGEND
ARCHITECTURAL
SHEET LIST
PROJECT ARCHITECTURAL REFERENCED DEMOLITION NOTES
GENERAL NOTES
XDX
GENERAL DEMO NOTES
PROJECT ARCHITECTURAL REFERENCED NOTES
REF. NOTES ( )
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SB SECURITY BARS
SB SPLASH BLOCK
SCH SCHEDULE
SCHED SCHEDULE
SCR SCREW
SCT STRUCTURAL CLAY TILE
SCUT SCUTTLE
SCW SOFT COLD WATER
SD STORM DRAIN
SD SUBDRAIN
SDI STEEL DECK INSTITUTE
SECT SECTION
SECY SECRETARY
SEQ SEQUENCE
SF SQUARE FOOT (FEET)
SFU STRUCTURAL FACING
UNIT
SHLD SHOULDER
SHT SHEET
SHTG SHEATHING
SHW SOFT HOT WATER
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SLBB SHORT LEG BACK TO
BACK
SM SPRINKLER MAIN
SOV SHUT OFF VALVE
SPA SPACE(ING)
SPEC SPECIFICATIONS
SPF SOUNDPROOF
SPH SPACE HEATER
SPKR SPEAKER
SPL SPECIAL
SQ SQUARE
SS SANITARY SEWER
SS STAINLESS STEEL
SSMR STANDING SEAM METAL
ROOFING
STA STATION
STAIR STAIRWAY
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STGR STRINGER
STIFF STIFFENER
STIRR STIRRUPS
STL STEEL
STN STONE
STOR STORAGE
STR STRUCTURAL
SUB FL SUB FLOOR
SUCT SUCTION
SUSP SUSPENDED
SVF SHEET VINYL FLOORING
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
T TREAD
T or TLT TOILET
TAN TANGENT
TBD TACK BOARD
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TERM TERMINAL
TGL TOGGLE
TH THRESHOLD
THK THICK
THRD THREAD
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOPO TOPOGRAPHIC
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TSTAT THERMOSTAT
TV TELEVISION
TW TEMPERED WATER
TWR TEMPERED WATER
RETURN
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UPS UNINTERRUPTIBLE
POWER SYSTEM
UR URINAL
UT UTILITY
UV UNIT VENTILATOR
V VOLT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VD VAULT DOOR
VEL VELOCITY
VENT VENTILATOR(ION)
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY
DRIVE
VOL VOLUME
VPC VERTICAL POINT OF
CURVATURE
VPI VERTICAL POINT OF
INTERSECTION
VPT VERTICAL POINT OF
TANGENCY
VS VENT STACK
VT VINYL-TILE
VTR VENT THRU ROOF
VWC VINYL WALL COVERING
W WEST
W WIDE (WIDTH)
W WIRE
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER CLOSET
WC WATER COLUMN
WD WASTE DRAIN
WD WOOD
WD BLKG WOOD BLOCKING
WD DR WOOD DOOR
WDW WINDOW
WF WIDE FLANGE
WG WIRE GLASS
WH WALL HYDRANT
WHT WHITE
WI WROUGHT IRON
WKSH WORK SHOP
WL WIND LOAD
WNSCT WAINSCOT
WP WEATHER PROOF
WP WORK POINT
WPF WATER PROOF
WPFG WATER PROOFING
WRB WARDROBE
WS WASTE STACK
WT WEIGHT
WWF WELDED WIRE FABRIC
WWM WOVEN WIRE MESH
XFMR TRANSFORMER
YD YARD or YARD DRAIN
LBS POUNDS
LD LOAD
LDG LOADING
LE LEFT END
LG LENGTH (LONG)
LIN LINEAR
LIS LAWN IRRIGATION
SYSTEM
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LP LOW POINT
LPG LIQUIFIED PETROLEUM
GAS
LPS LOW PRESSURE STEAM
LR LIVING ROOM
LS LAWN SPRINKLER
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LVT LUXURY VINYL TILE
M MIDDLE
M THOUSAND
M & B MATCHED AND BEADED
MA MAKE-UP AIR
MACH MACHINE
MAS MASONRY
MAT or
MATL
MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBH 1000 BTUH
MC MEDICINE CABINET
MC MISCELLANEOUS
CHANNELS
MECH MECHANICAL
MER MECHANICAL EQUIPMENT
ROOM
MET METAL
MFG MANUFACTURING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML METAL LATH
MLDG MOULDING
MO MASONRY OPENING
MONO MONOLITHIC
MT METAL THRESHOLD
MTD MOUNTED
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NR NOT REQUIRED
NS NEAR SIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OB WG OBSCURE WIRE GLASS
OBGL OBSCURE GLASS
OBSC OBSCURE
OC ON CENTER(S)
OCEW ON CENTER EACH WAY
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPS OPERATIONS
OS & Y OUTSIDE SCREW & YOKE
OSF OUTSIDE FACE
OV OVERFLOW VALVE
OX OXYGEN
OZ OUNCE
P PAINT
PA PUBLIC ADDRESS
PBS PUSH BUTTON STATION
PC PIECE
PC POINT OF CURVATURE
PC PRECAST
PCC PORTLAND CEMENT
CONCRETE
PCT PORCELAIN CERAMIC TILE
PD PRESSURE DROP
PE POLYETHYLENE
PEN PENETRATION
PERF PERFORATED
PH PHASE
PHAR PHARMACY
PI POINT OF INTERSECTION
PIV POST INDICATING VALVE
PL or P PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLATF PLATFORM
PLBG PLUMBING
PLG PILING
PLWD PLYWOOD
PNL PANEL
POL POLISH(ED)
PORC PORCELAIN
PPM PARTS PER MILLION
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PRESS PRESSURE
PROJ PROJECT
PRV PRESSURE REGULATING
VALVE
PS PRESSED STEEL
PSFT POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PT POINT
PT POINT OF TANGENCY
PTD PAINTED
PTN PARTITION
PVC POLYVINYL-CHLORIDE
PVMT PAVEMENT
PW PASS WINDOW
1/4 RD QUARTER ROUND
QT QUARRY TILE
QT QUART
QTRS QUARTERS
QTY QUANTITY
QTZ QUARTZ
R REGISTER
R RISER
RA RETURN AIR
RAD OR
R
RADIUS
RB RESILIENT BASE
RC REMOTE CONTROL
RCP REINFORCED CONCRETE
PIPE
RD ROOF DRAIN
RE RIGHT END
REC RECEIVER
RECP RECEPTACLE
RECR RECREATION
RECT RECTIFIER
REF REFERENCE
REFR REFRIGERANT
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCEMENT
REM REMOVE(ABLE)
REQD REQUIRED
RESIL RESILIENT
REV REVISIONS
RFG ROOFING
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RM ROOM
RND ROUND
RO ROUGH OPENING
RPM REVOLUTIONS PER
MINUTE
RT RUBBER TILE
RTU ROOF TOP UNIT
RUB RUBBER
DIAG DIAGONAL
DIM DIMENSION
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DIST DISTRIBUTION
DL DEAD LOAD
DMPR DAMPER
DN DOWN
DP DAMP PROOFING
DPT DEW POINT
DR DOOR
DRN DRAIN
DS DOWN SPOUT
DV DENTAL VACUUM
DWG DRAWING
DWLS DOWELS
DX DIRECT EXPANSION
E EAST
EA EACH
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY
RATIO
EJ EXPANSION JOINT
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
ENCL ENCLOSURE
ENT ENTERING
ENT ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EST ESTIMATE
EVAP EVAPORATOR
EW EACH WAY
EWC ELECTRIC WATER
COOLER
EXC EXCAVATE
EXD EXIT DEVICE
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPL EXPLOSION
EXPN EXPANSION
EXT EXTERIOR
F FAHRENHEIT
F FIRE
FA FRESH AIR
FCG FACING
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER
BRACKET
FEC FIRE EXTINGUISHER
CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FIX FIXTURE
FL or FLR FLOOR
FLASH FLASHING
FLEX FLEXIBLE
FLG FLANGE
FLG FLOORING
FLUOR FLUORESCENT
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPRF FIRE PROOF
FR FRAME
FRG FURRING
FS FAR SIDE
FS FLOOR SINK
FS FULL SIZE
FT FEET (FOOT)
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
G GRILLE
G NATURAL GAS
GA GAGE OR GAUGE
GAL GALLON
GALV GALVANIZED
GEN GENERAL
GFE GOVERNMENT FURNISHED
EQUIPMENT
GFE/CI GOVERNMENT FURNISHED
EQUIPMENT/CONTRACTOR
INSTALLED
GFI GROUND FAULT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GND GROUND
GOVT GOVERNMENT
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRADE
GRS GALVANIZED RIGID STEEL
CONDUIT
GRTG GRATING
GSU GLAZED STRUCTURAL
UNITS
GWB GYPSUM WALLBOARD
GWT GLAZED WALL TILE
GYP GYPSUM
H or HT HEIGHT (HIGH)
HB HOSE BIBB
HBD HARDBOARD
HC HANDICAPPED
HD HEAD
HDPE HIGH DENSITY
POLYETHYLENE
HDR HEADER
HDW HARDWARE
HIP HIGH PRESSURE
HM HOLLOW METAL
HORIZ HORIZONTAL(LY)
HP HORSE POWER
HPS HIGH PRESURE STEAM
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HSGYP HIGH STRENGTH GYPSUM
PLASTER
HTG HEATING
HTR HEATER
HW HEAD WALL
HW HOT WATER
HWH HOT WATER HEATER
HWR HOT WATER RETURN
(HEATING)
HWS HOT WATER SUPPLY
(HEATING)
HYD HYDRAULIC
I or FE IRON
IC INTERCOM
ID INSIDE DIAMETER
IE INVERT ELEVATION
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
INV INVERT OR INVERTER
IP IRON PIPE
ISF INSIDE FACE
JB JUNCTION BOX
JBOX JUNCTION BOX
JC JANITOR CLOSET
JCT JUNCTION
JST JOIST
JT JOINT
K KEY
KCP KEENE'S CEMENT
PLASTER
KIP or K KILOPOUND (1000 LBS)
KIT KITCHEN
KL KEY LOCK
KP KICK PLATE
KV KILOVOLTS
KVA KILOVOLT AMPERES
KW KILOWATT
LAB LABORATORY
LAU LAUNDRY
LAV LAVATORY
LBR LUMBER
A COMPRESSED AIR
A/C AIR CONDITIONING
AB ANCHOR BOLT
ABS ACRYLONITRILE BUTAD
STYRENE
AC ALTERNATING CURRENT
ACI AMERICAN CONCRETE
INSTITUTE
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
ACST ACOUSTIC
AD ACCESS DOOR
AD AREA DRAIN
ADMIN ADMIN ADMINISTRATION
(IVE)
AFF ABOVE FINISH FLOOR
AFFF AQUEOUS FILM FORMING
FOAM
AGG AGGREGATE
AHU AIR HANDLING UNIT
AI AREA INLET
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AL ACTIVE LEAF
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
AP ACCESS PANEL
APD AIR PRESSURE DROP
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR
ARCHITECT
ARI AMERICAN
REFRIGERATION
INSTITUTE
ASB ASBESTOS
ASPH ASPHALT
APC ACOUSTICAL PANEL
CEILING
AUTO AUTOMATIC
AV ACID VENT
AVG AVERAGE
AW ACID WASTE
AWC ACOUSTICAL WALL
COVERING
AWG AMERICAN WIRE GAUGE
L ANGLE
BATT BATT INSULATION
BB BULLETIN BOARD
BBO BOILER BLOW OFF
BC BOOKCASE
BD BOARD
BDY BOUNDARY
BEJ BRICK EXPANSION JOINT
BIT BITUMINOUS
BKR BREAKER
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BM BENCH MARK
BO BOTTOM OF
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
BUR BUILT-UP ROOFING
BW BOTH WAYS
C CENTER
C OR
CND
CONDUIT (ELECTRICAL
SHEETS)
C TO C CENTER TO CENTER
CAP CAPACITY
CB CATCH BASIN (OR CIRCUIT
BREAKER)
CC CENTER TO CENTER
CCT CIRCUIT
CD CONDENSATE DRAIN
CE COVER ELEVATION
CEM CEMENT
CF CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHIM CHIMNEY
CI CAST IRON
CI CURB INLET
CIP CAST IN PLACE
CIR CIRCULAR
CJ CONTROL JOINT
CKT CIRCUIT
CL CENTER LINE
CL WG CLEAR WIRE GLASS
CLG CEILING
CLKG CAULKING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY
UNIT
CNTR COUNTER
CO CLEAN OUT
CO2 CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINATION
COMB COMBUSTION
COMP COMPRESSIBLE
COMPR COMPRESSOR
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION
CONSTR CONSTRUCTION
CONSTR
JT
CONSTRUCTION JOINT
CONT CONTINUOUS
(CONTINUATION)
CONTR CONTRACTOR
COR CORNER
CORR COVERED
COV CORRIDOR
CPL CEMENT PLASTER
CPS CYCLES PER SECOND
(HERTZ)
CPT CARPET
CR CONDENSER WATER
RETURN
CRES CORROSIVE RESISTANT
STEEL
CRG CARRIAGE
CRSE COURSE
CS CONDENSER WATER
SUPPLY
CS COUNTER SINK
CSMT CASEMENT
CT CERAMIC TILE
CT CURRENT TRANSFORMER
CTL CARPET TILE
CU CONDENSING UNIT
CU YD CUBIC YARDS
CUH CABINET UNIT HEATER
CV CEILING VENT
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
CYL CYLINDER
D DEPTH (DEEP)
D DIFFUSER
d PENNY (as in nail - 10d)
D&M DRESSED AND MATCHED
DA DOUBLE ACTING
DB DRY BULB
dB DECIBEL
DBL DOUBLE
DC DIRECT CURRENT
DCJ DOWELED CONTROL
JOINT
DCJT DUMMY CONTROL JOINT
DCL DOOR CLOSER
DCW DOMESTIC COLD WATER
DEG DEGREE
DEMO DEMOLITION
DEPR DEPRESSION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DHW DOMESTIC HOT WATER
DI DEIONIZED WATER
DIA DIAMETER
CLO CLOSET
FR FIRE RATED
U/C UNDER CABINET
SYMBOL LEGEND
PLAN VIEW
SECTION / ELEVATION VIEW
SHEAR WALL
MASONRY-CMU
CONCRETE
GRAVEL
EARTH / COMPACTED
EARTH /
NONCOMPACTED
RIGID INSULATION
JOINT FILLER
STEEL
GYPSUM
MASONRY-VENEER
STUD WALL
FLEXIBLE INSULATION
GROUT
PLYWOOD
WOOD (FINISH)
MASONRY-CMU FACE
MASONRY-CMU
MASONRY-VENEER
A 00 ARCHITECTURAL INFO SHEET
A101 FLOOR PLAN, ELEVATIONS &
BUILDING SECTION
A102 MEZZANINE PLAN
A301 SCHEDULES, DOOR AND WINDOW
DETAILS
1 MECH EQUIP - SEE MECH
2 FLOOR SINK - SEE MECH
3 ACOUSTICAL PANEL - SEE SPECS
4 STRUCTURAL STOOP - SEE STR
5 SURFACE MOUNTED FIRE EXTINGUISHER (FE) - MOUNT 48" TO HIGHEST OPERABLE
PART TO RELEASE FROM MOUNTING BRACKET
6 PROVIDE EXPANDED METAL MESH ON INTERIOR SIDE OF CMU WALL TO COVER
DRAINAGE OPENING.
7 EXISTING MECH UNIT TO BE RELOCATED - SEE MECH
8 RELOCATED MECH UNIT - SEE MECH
9 CONC SPLASHBLOCK
10 CONC HOUSEKEEPING PAD - SEE STR
11 EXISTING DOWNSPOUT WITH UNDERGROUND STORM PIPING - CONTRACTOR TO
AVOID REMOVAL OR MODIFICATION IF POSSIBLE
12 EXISTING TREE TO REMAIN - PROVIDE PROTECTIVE FENCING AT DRIPLINE OF TREE
13 EXISTING FORT WALL WALK TO REMAIN
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL
DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.
DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,
RELOCATED, OR SALVAGED ARE SHOWN AS FULL-TONE DASHED LINES AND ARE
LISTED IN THE REFERENCED DEMOLITION NOTES. ALL OTHER ITEMS ARE INTENDED
TO REMAIN IN PLACE AND ARE SHOWN HALF-TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS BELOW OR HERE-
IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW
CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF
THE DEMOLITION REQUIRED AND AS LISTED BELOW.
C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF
ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND
APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR ACCOMMODATE ALL
NEW CONSTRUCTION WITH THE OWNER HAVING FIRST RIGHT OF REFUSAL ON ALL
ITEMS.
D. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL
REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER
HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE
CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND
REPORT THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE WORK IN
THE AFFECTED AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY WRITTEN
AGREEMENT OF THE OWNER AND CONTRACTOR.
E. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND
REMOVAL OF ALL CONSTRUCTION BARRIERS.
F. TEMPORARILY SHORE AND BRACE STRUCTURE AT ALL BEARING WALL DEMOLITION
LOCATIONS UNTIL NEW PERMANENT STRUCTURE IS ESTABLISHED. SEE
STRUCTURAL.
G. REMOVE EXISTING ELEMENTS/FINISHES NOT REQUIRED IN THE COMPLETED
PROJECT, BUT CONFLICTING WITH NEW FINISHES.
H. SEE STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL
DEMOLITION, INCLUDING, BUT NOT LIMITED TO, ALL CONCRETE SLAB REMOVAL AND
REPLACEMENT.
I. REFER TO MECHANICAL DEMOLITION PLANS FOR ADDITIONAL DEMOLITION
REQUIRED TO ACCOMMODATE NEW MECHANICAL PIPING AND ASSOCIATED
EQUIPMENT.
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND
LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER OF ANY
DISCREPANCIES OR VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO ADDITIONAL
EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS
TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE
ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE
FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO
ADDITIONAL EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS
WITH ALL OTHER TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN. FULL-
TONE LINES INDICATE NEW OR RELOCATED CONSTRUCTION.
E. FINISHED FLOOR ELEVATION (FFE) IS 110'-3", TYPICAL U.N,O.
F. DIMENSIONS ARE TYPICALLY TO FINISH FACE OF MASONRY, CONCRETE, GYPSUM
WALL BOARD, AND METAL FRAMES; OR CENTER LINE OF COLUMN OR BEAMS,
UNLESS NOTED OTHERWISE.
G. INTERIOR DOORS WITH THE HINGE-SIDE SHOWN CLOSE TO CORNERS SHALL BE
LOCATED 4 INCHES FROM ADJACENT WALL UNLESS NOTED OTHERWISE
H. CHANGES IN FLOOR MATERIALS SHALL OCCUR UNDER DOORS.
1. PROVIDE POSITIVE DRAINAGE TO ALL ROOMS WITH NEW FLOOR DRAINS.
K. ALL ANGLES ON THE FLOOR PLANS ARE 45 OR 90 DEGREES UNLESS OTHERWISE
INDICATED.
L. PROVIDE FIRE TREATED 2x6 OR LARGER WOOD BLOCKING IN WALLS AND FURRING
SPACES AS REQUIRED FOR MOUNTING OF ALL WALL SUPPORTED ITEMS. WHETHER
OR NOT DETAILED ON THE DRAWINGS, THE CONTRACTOR SHALL COORDINATE AND
INSTALL ALL STIFFENERS, BRACING, BACK-UP PLATES, AND SUPPORTING BRACKETS
AS REQUIRED FOR THE INSTALLATION OF WALL MOUNTED OR SUSPENDED
MECHANICAL, ELECTRICAL, OR MISCELLANEOUS EQUIPMENT. THESE ITEMS
INCLUDE, BUT ARE NOT LIMITED TO, DOOR WALL STOPS, FIRE EXTINGUISHER
CABINETS, CONTROL PANELS, FIRE ALARM PANELS AND MASTER CLOCKS, ETC.
P. PROVIDE CONTROL JOINT AT EACH SIDE OF DOOR FRAME, TYPICAL.
Q. ALL CONTROL JOINTS (CJ) SHALL BE CAULKED AT EXTERIOR WALL LOCATIONS AND
RAKED BACK 3/4 INCH AT ALL INTERIOR JOINTS UNLESS OTHERWISE NOTED.
R. PATCH EXISTING WALLS, FLOORS, AND CEILING SURFACES DEMOLISHED, CUT,
CORED, OR ALTERED IN ANY WAY TO ACCOMMODATE NEW CONSTRUCTION.
S. CONTRACTOR SHALL VERIFY CMU WALLS HAVE NO CHIPPED EDGES AND THAT
JOINTS HAVE BEEN TOOLED TO REMOVE ALL EXCESS MORTAR AND ARE READY TO
RECEIVE PAINT. CONTRACTOR SHALL APPROVE WALLS TO RECEIVE PAINT PRIOR TO
HAVING PAINTER INSPECT FOR APPROVAL.
T. PATCH ALL CONCRETE SLAB LOCATIONS DEMOLISHED TO INSTALL NEW
STRUCTURAL, MECHANICAL, OR ELECTRICAL WORK.
U. SEE SHEET A301 FOR DOOR AND ROOM FINISH SCHEDULES.
V. PROVIDE FIRE EXTINGUISHERS (FE) AS SHOWN ON DRAWINGS. FIRE EXTINGUISHERS
SHALL COMPLY WITH NFPA 10. FIRE EXTINGUISHERS SHALL BE MULTIPURPOSE DRY-
CHEMICAL TYPE, UL-RATED, 2A/10BC, WITH SURFACE MOUNTED BRACKET AND
DECAL SIGNAGE.
D1 SAWCUT AND REMOVE EXISTING WALL CONSTRUCTION AS REQ'D FOR NEW DOOR
OPENING. PROTECT CONSTRUCTION INDICATED TO REMAIN AGAINST DAMAGE AND
SOILING. PROVIDE LINTEL - SEE STR
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-F O
S M jf ie d le r.
rv t
JLF
JLF
MJH
01/03/2020
07310.007
A 00
ARCHITECTURAL INFO SHEET
07310007FOSM- 2- A 00 ARCHITECTURAL INFO SHEET
W. CONTROL JOINTS AT CMU WALLS SHALL BE PROVIDED PER NCMA SPACING AND
STANDARDS AND RECEIVE BACKER ROD AND SEALANT. PROVIDE CONTROL JOINTS
AS INDICATED ON THE PLANS. SEE DETAIL 6/A301 FOR TYPICAL JOINT.
FE
23'-4" 5'-0"
COOLING
TOWER
ENCLOSURE
BOILER SHED
A101
A1013
A101
100-1
101-1
100-2
101-2
A101
EXISTING
MAINTENANCE
BUILDING
D1
D1
DS
T.O. SLAB
ELEV:110'-3"
T.O. SLAB
ELEV: 110'-1"
T.O. SLAB
ELEV: 110'-2"
T.O. SLAB
ELEV: 110'-0"
T.O. SLAB
ELEV: 110'-1"
T.O. SLAB
ELEV: 110'-1"
T.O. SLAB
ELEV: 110'-0"
T.O. SLAB
ELEV: 110'-1"
T.O. SLAB
ELEV: 109'-11"
10'-0" 2'-8" 10'-8"
A101
13 ±
± 12'-6"
/8
FIRST FLOOR
110' - 3"
A101
T.O. CMU
120' - 3"
COOLING TOWER -
SEE MECH
PREFIN MET
COPING
CMU - PAINTED TO
MATCH EXISTING
CONC FTG - SEE STR
DRAINAGE
OPENING W/
EXPANDED METAL
MESH
4'-8"
CJCJ
FIRST FLOOR
110' - 3"
T.O. CMU
120' - 3"
COOLING TOWER -
SEE MECH
PREFIN MET
COPING
CMU - PAINTED TO
MATCH EXISTING
CONC FTG - SEE STRHM DOOR & FRAME -
PAINTED, TYP
101-2 100-2
EXISTING
BUILDING BEYOND
10'-8" CJ
A101
A102
A102ROOF
TERMINATION
BEYOND - SEE
6/A102
FIRST FLOOR
110' - 3"
A101
T.O. CMU
120' - 3"
CMU - PAINTED TO
MATCH EXISTING
CONC FTG - SEE STR
PREFIN MET
GUTTER &
DOWNSPOUT
4'-8"
CJCJ
FIRST FLOOR
110' - 3"
T.O. CMU
120' - 3"
COOLING TOWER -
SEE MECH
PREFIN MET
COPING
CMU - PAINTED TO
MATCH EXISTING
CONC FTG - SEE STR
BOND BEAM - SEE
STR
CONC SLAB - SEE STR
1/4" / 12"
PREFIN MET
GUTTER
MEMBRANE
ROOF
PREFIN MET TRIM
CMU -
PAINTED
TO MATCH
EXISTING
MECH EQUIP -
SEE MECH
A102
A102
A102
FIRST FLOOR
110' - 3"
T.O. CMU
120' - 3"
CONC SLAB - SEE STR
EXIST FTG
EXIST CMU WALL
MEMBRANE ROOF
EXIST ROOF &
GUTTER
A102
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-F O
S M jf ie d le r.
rv t
JLF
JLF
MJH
01/03/2020
07310.007
A101
FLOOR PLAN, ELEVATIONS &
BUILDING SECTION
07310007FOSM- 2- A101 FLOOR PLAN, ELEVATIONS & BUILDING SECTION
1 MECH EQUIP - SEE MECH
2 FLOOR SINK - SEE MECH
4 STRUCTURAL STOOP - SEE STR
5 SURFACE MOUNTED FIRE EXTINGUISHER (FE) - MOUNT 48" TO HIGHEST
OPERABLE PART TO RELEASE FROM MOUNTING BRACKET
6 PROVIDE EXPANDED METAL MESH ON INTERIOR SIDE OF CMU WALL TO
COVER DRAINAGE OPENING.
7 EXISTING MECH UNIT TO BE RELOCATED - SEE MECH
8 RELOCATED MECH UNIT - SEE MECH
9 CONC SPLASHBLOCK
10 CONC HOUSEKEEPING PAD - SEE STR
11 EXISTING DOWNSPOUT WITH UNDERGROUND STORM PIPING -
CONTRACTOR TO AVOID REMOVAL OR MODIFICATION IF POSSIBLE
12 EXISTING TREE TO REMAIN - PROVIDE PROTECTIVE FENCING AT DRIPLINE
OF TREE
13 EXISTING FORT WALL WALK TO REMAIN
REF. NOTES ( ):X
SCALE: 1/8" = 1'-0"
FLOOR PLAN - BOILER ROOM & COOLING TOWER ENCLOSURE
SCALE: 1/8" = 1'-0"
ELEVATION - WEST
SCALE: 1/8" = 1'-0"
ELEVATION - NORTH
SCALE: 1/8" = 1'-0"
ELEVATION - EAST
SCALE: 1/8" = 1'-0"
BUILDING SECTION
TRUE
NORTH
REF. DEMO NOTES ( ):DX
D1 SAWCUT AND REMOVE EXISTING WALL CONSTRUCTION AS REQ'D FOR
NEW DOOR OPENING. PROTECT CONSTRUCTION INDICATED TO REMAIN
AGAINST DAMAGE AND SOILING. PROVIDE LINTEL - SEE STR
PLAN
NORTH
SCALE: 1/8" = 1'-0"
WALL SECTION @ EXISTING
UP
B.O. PANEL
6" AFF
T.O. CMU
120' - 3"
OPEN TO BELOW ATTIC - SEE MECHMECH MEZZANINE
TYP, UNO
8'-0"
4'-0" 4'-0"
EXISTING WALL SURFACE
7/8" HAT CHANNEL - SPACING AND
ATTACHMENT PER ACOUSTIC PANEL
MANUF INSTRUCTIONS
2'x4'x2" CEMENTITIOUS WOOD FIBER
ACOUSTIC PANEL
T Y
P
PREFIN MET FLASHING W/ CLEAT
CONT TREATED WD
BLOCKING
CONT SEALANT
EACH SIDE
ANCHOR BLOCKING
TO CMU - SEE STR
BOND BEAM - SEE
STR
CMU WALL
BEYOND
FLASH JOINT
WEATHER-TIGHT
ROOF MEMBRANE
1/4:12 TAPERED RIGID
INSUL - 1" MIN THICKNESS
1/2" GYPSUM BOARD
SUBSTRATE
STL DECK - SEE STR
LT GUAGE JOISTS -
SEE STR
ANCHOR BLOCKING TO
CMU - SEE STR
PREFIN MET FLASHING
CONT SEALANT
CONT TREATED WD
BLOCKING
MEMBRANE FLASHING
BOND BEAM - SEE STR
MEMBRANE FLASHING
PREFIN MET
GUTTER AND
DOWNSPOUT
CONT
SEALANT
ROOF MEMBRANE
1/4:12 TAPERED RIGID
INSUL - 1" MIN THICKNESS
1/2" GYPSUM BOARD
SUBSTRATE
STL DECK - SEE STR
LT GUAGE JOISTS - SEE STR
BOND BEAM - SEE STR
CONT TREATED
WD BLOCKING
PREFIN MET
COUNTER
FLASHING
ANCHOR BLOCKING TO
CMU - SEE STR
HANGER STRAP
T.O. CMU
120' - 3"
CONT SEALANT
EXIST CMU WALL
STAINLESS STEEL
TERMINATION BAR
STAINLESS STEEL
FASTENER W/
NEOPRENE WASHER
CONT WATER STOP
MEMBRANE
FLASHING
1/4:12 TAPERED
RIGID INSUL - 1" MIN
THICKNESS
STL DECK - SEE STR
6" MET STUD - SEE STR
CONT SEALANT
CONT WATER STOP
STAINLESS STEEL
FASTENER W/
NEOPRENE WASHER
STAINLESS STEEL
COUNTER FLASHING
ROOF MEMBRANE
1/4:12 TAPERED RIGID
INSUL - 1" MIN THICKNESS
1/2" GYPSUM BOARD
SUBSTRATE
STL DECK - SEE STR
LT GUAGE JOISTS -
SEE STR
ANCHOR BLOCKING TO
CMU - SEE STR
PREFIN MET FLASHING
CONT SEALANT
CONT TREATED WD
BLOCKING
BOND BEAM - SEE STR
V A
R
IE
S
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-F O
S M jf ie d le r.
rv t
JLF
JLF
MJH
01/03/2020
07310.007
A102
MEZZANINE PLAN
07310007FOSM- 2- A102 MEZZANINE PLAN
SCALE: 1/8" = 1'-0"
FLOOR PLAN - VISITOR CENTER MEZZANINE
1 MECH EQUIP - SEE MECH
3 ACOUSTICAL PANEL - SEE SPECS
REF. NOTES ( ):X
SCALE: 1 1/2" = 1'-0"
ACOUSTIC PANEL ATTACHMENT
SCALE: 1 1/2" = 1'-0"
CMU WALL CAP
SCALE: 1 1/2" = 1'-0"
MEMBRANE ROOF - HIGH SIDE
SCALE: 1 1/2" = 1'-0"
MEMBRANE ROOF - GUTTER
SCALE: 1 1/2" = 1'-0"
DETAIL @ TERMINATION
DATE INITIAL
SCALE: 1 1/2" = 1'-0"
MEMBRANE ROOF - CURB
2" SEE SCHEDULE 2"
S E
E S
C H
E D
U L E
2" SEE SCHEDULE 2"
S E
E S
C H
E D
U L E
F1
HOLLOW METAL
F2
HOLLOW METAL
SEE SCHEDULE
S E
E S
C H
E D
U L E
SEE SCHEDULE
S E
E S
C H
E D
U L E
4" 6"
F NV
HM FRAME
(PAINT)
-GROUT FULL
DOOR - SEE
SCHED.
SEALANT
BOTH SIDES
BOND BEAM - SEE STR
SEALANT BOTH
SIDES
CMU WALL
HM FRAME (PAINT)
-GROUT FULL
DOOR - SEE
SCHED.
DOOR - SEE SCHED
THRESHOLD SET IN SEALANT
STRUCTURAL STOOP - SEE STR
1/2" EXPANSION JOINT
HM FRAME
(PAINT)
DOOR - SEE
SCHED.
SEALANT
BOTH SIDES
STEEL BEAM
LINTEL - SEE STR
CMU SOAPS - BOTH
SIDES OF STL LINTEL
SEALANT BOTH
SIDES
EXIST CMU WALL
HM FRAME (PAINT)
DOOR - SEE
SCHED.
GROUT CMU CELL
CLOSED CELL BACKER ROD
W/ SEALANT - @ EXPOSED
TO VIEW LOCATIONS ONLY
REINFORCED CMU JAMB
BLOCK, GROUT SOLID,
SEE ELEV. FOR TYPE -
SEE STR
RUBBER CONTROL JOINT
DUR-O-WALL NO. 6 OR
APPROVED EQUAL
CLOSED CELL BACKER ROD
W/ SEALANT - @ EXPOSED
TO VIEW LOCATIONS ONLY
3/8"
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \j fi e d le r\ D o c u m e n ts \R e v it te m p
\0
-A R
C H
R
-F O
S M jf ie d le r.
rv t
JLF
JLF
MJH
01/03/2020
07310.007
A301
SCHEDULES, DOOR AND
WINDOW DETAILS
07310007FOSM- 2- A301 SCHEDULES, DOOR AND WINDOW DETAILS
DOOR & FRAME TYPES
SCALE: 1/4" = 1'-0"
ROOM SCHEDULE
ROOM NO ROOM NAME
FLOOR
MATL
FLOOR
FINISH
BASE
MATL
CEILING NORTH WALL EAST WALL SOUTH WALL WEST WALL
REMARKSHEIGHT MATL FINISH MATL FINISH MATL FINISH MATL FINISH MATL FINISH
100 COOLING TOWER
ENCLOSURE
CONC SEALED -- -- -- -- CMU P CMU P CMU P EXIST EXIST
1, 2
101 BOILER SHED CONC SEALED -- VARIES EXP STR -- CMU P CMU P CMU P EXIST EXIST 1, 2
DOOR SCHEDULE
DOOR NO
DOOR SIZE DOOR FRAME DETAIL
SET NO REMARKSWIDTH HEIGHT THICK TYPE MATL GLASS TYPE MATL HEAD JAMB JAMB SILL
100-1 3' - 0" 7' - 0" 0' - 1 3/4" F HM -- F2 HM 4/A301 5/A301 5/A301 -- 2 1, 2
100-2 PR 3' - 0" 7' - 0" 0' - 1 3/4" F HM -- F2 HM 1/A301 2/A301 2/A301 3/A301 1 1
101-1 3' - 0" 7' - 0" 0' - 1 3/4" F HM -- F2 HM 4/A301 5/A301 5/A301 -- 3 1
101-2 PR 3' - 0" 7' - 0" 0' - 1 3/4" F HM -- F2 HM 1/A301 2/A301 2/A301 3/A301 1 1, 2
DOOR SCHEDULE REMARKS
1. INTRUSION ALARM - COORDINATE DOOR HARDWARE W/ NPS ALARM PROVIDER FOR INSTALLATION AND WIRING REQUIREMENTS
2. INSULATED
ROOM SCHEDULE REMARKS
1. HOLLOW METAL DOORS AND FRAMES TO BE PAINTED TO MATCH CMU.
2. INTERIOR AND EXTERIOR SIDE OF CMU TO BE PAINTED TO MATCH EXISTING BUILDING.
SCALE: 3" = 1'-0"
HM HEAD @ CMU
SCALE: 3" = 1'-0"
HM JAMB @ CMU
SCALE: 3" = 1'-0"
DOOR SILL
SCALE: 3" = 1'-0"
HM HEAD @ EXIST CMU
SCALE: 3" = 1'-0"
HM JAMB @ EXIST CMU
SCALE: 1 1/2" = 1'-0"
TYPICAL CMU CONTROL JOINT DETAIL
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \e h o ff \D o c u m e n ts
\R e v it te m p \0
-S T
R U
C
R
-F O
S M e h o ff s c h e m m e r.
c o m .r v t
ECH
ECH
KMW
01/03/2020
07310.007
S 01
STRUCTURAL NOTES
07310007FOSM- 3- S 01 STRUCTURAL NOTES
APPLICABLE CODES AND STANDARDS
2012 INTERNATIONAL BUILDING CODE
1. ACI 318-11 - BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
2. ACI 530-11 - BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
3. AISC 360-10 - SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
4. AISI S100-07/SI-10 - NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS, WITH SUPPLEMENT 1,
DATED 2010
DESIGN CRITERIA
FLOOR LIVE LOAD PSF
1. FLOOR 100
ROOF LIVE LOAD PSF
1. ROOF LIVE LOAD (MINIMUM, NON-REDUCIBLE) 20
OTHER LIVE LOADS
1. OFFICE PARTITIONS (LIVE LOAD): 15 PSF
2. PARTITIONS (LATERAL LOAD): 5 PSF
3. RAILING (LATERAL LOAD AT TOP): 50 PLF OR 200 LB
4. MECHANICAL EQUIPMENT ROOM 150 PSF OR EQUIP.
WEIGHT IF GREATER
ROOF SNOW LOAD
1. GROUND SNOW LOAD (Pg): 10 PSF
2. FLAT-ROOF SNOW LOAD (Pf): 15 PSF
3. RAIN ON SNOW SURCHARGE: 5 PSF
4. DRIFT SNOW LOAD PER ASCE 7-10
5. SNOW EXPOSURE FACTOR (Ce): 1.0
6. SNOW LOAD IMPORTANCE FACTOR (I): 1.0
7. THERMAL FACTOR (Ct): 1.1
WIND DESIGN DATA
1. ULTIMATE DESIGN WIND SPEED (Vult): 115 MPH
2. NOMINAL DESIGN WIND SPEED (Vasd): 90 MPH
3. RISK CATEGORY: II
4. WIND EXPOSURE: CATEGORY C
5. INTERNAL PRESSURE COEFFICIENT (GCpi): +/-0.18
6. COMPONENTS AND CLADDING DESIGN WIND PRESSURE:
A. ROOF - ZONE 1 26.4 PSF
B. ROOF - ZONE 2 31.3 PSF
C. ROOF - ZONE 3 31.3 PSF
D. WALL - ZONE 4 26.9 PSF
E. WALL - ZONE 5 29.9 PSF
EARTHQUAKE DESIGN DATA
1. SEISMIC IMPORTANCE FACTOR (I): 1.0
2. RISK CATEGORY: II
3. 0.2 SEC SPECTRAL RESPONSE ACCELERATION (SS): 0.172
4. 1.0 SEC SPECTRAL RESPONSE ACCELERATION (S1): 0.092
5. SITE CLASS: D
6. 0.2 SEC SPECTRAL RESPONSE COEFFICIENT (SDS): 0.183
7. 1.0 SEC SPECTRAL RESPONSE COEFFICIENT (SD1): 0.144
8. SEISMIC DESIGN CATEGORY: C
9. BASIC SEISMIC-FORCE-RESISTING SYSTEM:
A. CMU SHEAR WALLS
10. DESIGN BASE SHEAR (V): 0.57 KIPS
11. SEISMIC RESPONSE COEFFICIENT (CS): 0.092
12. RESPONSE MODIFICATION FACTOR (R): 2.0
13. ANALYSIS PROCEDURE USED:
A. EQUIVALENT LATERAL FORCE PROCEDURE
STRUCTURAL NOTES
1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE APPLICABLE
BUILDING CODE.
2. THE STRUCTURE HAS BEEN DESIGNED TO RESIST DESIGN LOADS ONLY AS
A COMPLETED STRUCTURE
A. APPLICATION OF ANY LOADS TO THE PARTIALLY COMPLETED
STRUCTURE SHALL BE CONSIDERED BY THE CONTRACTOR AND SO
INCLUDED IN THE DESIGN OF THE SHORING, BRACING, FORMWORK,
AND ANY OTHER SUPPORTING ELEMENTS PROVIDED FOR
CONSTRUCTION OF THE STRUCTURE.
B. WHERE CONSTRUCTION MATERIAL AND EQUIPMENT ARE TEMPORARILY
STORED ON THE ROOF OR FLOOR FRAMING, THEY SHALL BE
DISTRIBUTED SO THAT THE DESIGN LIVE LOAD AT THE LOADED AREA IS
NOT EXCEEDED.
C. DO NOT BACKFILL AGAINST WALLS OR OTHER STRUCTURAL ELEMENTS
UNTIL SUCH ELEMENTS HAVE REACHED THEIR INTENDED STRENGTH,
HAVE BEEN ADEQUATELY BRACED, AND/OR HAVE OTHER INTEGRAL
STRUCTURAL ELEMENTS IN PLACE WHICH ARE INTENDED TO RESIST
THE LATERAL EARTH LOADS.
3. LATERAL LOAD RESISTING SYSTEM: ALL LATERAL LOAD RESISTANCE AND
STABILITY IN THE COMPLETED STRUCTURE IS PROVIDED BY:
A. N-S DIRECTION: CMU SHEAR WALL
B. E-W DIRECTION: CMU SHEAR WALL
C. ROOF DIAPHRAGM: METAL ROOF DECK
4. DETAILS ON THE DRAWINGS INDICATED AS "TYPICAL" APPLY IN ALL AREAS
WHERE CONDITIONS SIMILAR TO THE DETAIL OCCUR.
5. THE STRUCTURAL DRAWINGS ARE NOT INTENDED FOR USE AS SHOP
ERECTION DRAWINGS. REPRODUCTION OF THESE DRAWINGS IN LIEU OF
PREPARATION OF SHOP ERECTION DRAWINGS SIGNIFIES THE USERS'
ACCEPTANCE THAT ALL INFORMATION SHOWN IS CORRECT AND
APPROPRIATE FOR SHOP DRAWINGS AND THAT THE USER WILL BE FULLY
RESPONSIBLE FOR EXPENSES THAT MAY OCCUR FROM SAID ACCEPTANCE.
6. UNLESS SPECIFICALLY NOTED, THERE ARE NO PROVISIONS MADE FOR
FUTURE FLOORS, ROOFS, OR OTHER LOADS.
MATERIAL DATA
CONCRETE AND REINFORCING
1. CONCRETE STRENGTH (f'c @ 28 DAYS)
A. FOOTINGS 4,500 PSI
B. GRADE SUPPORTED SLABS 4,500 PSI
2. CEMENT TYPE: PORTLAND TYPE I
3. AGGREGATES
A. NORMAL WEIGHT, 1 1/2" MAX. SIZE - ASTM C33
B. PROVIDE AGGREGATES FREE OF MATERIALS WITH DELETERIOUS
REACTIVITY TO ALKALI IN CEMENT, FROM A SINGLE SOURCE WITH
DOCUMENTED SERVICE RECORD DATA OF AT LEAST 10 YEARS
SATISFACTORY SERVICE IN SIMILAR APPLICATIONS AND SERVICE
CONDITIONS USING SIMILAR AGGREGATES AND CEMENTITIOUS
MATERIALS.
4. REINFORCING STEEL ASTM A615, GRADE 60
5. REINFORCING STEEL ASTM A706, WELDABLE
6. WELDED WIRE FABRIC ASTM A185
7. PREFORMED EXPANSION JOINT (1/2") ASTM D1751
MASONRY
1. MASONRY STRENGTH (f'm @ 28 DAYS) 1,500 PSI
2. CONCRETE UNITS ASTM C90 NORMAL
WEIGHT
3. UNIT COMPRESSIVE STRENGTH 1,900 PSI (BASED ON
NET AREA)
4. MORTAR TYPE ASTM C270, TYPE S
5. GROUT TYPE ASTM C476, 3/8" MAX.
AGGREGATE SIZE
6. MORTAR STRENGTH (28 DAYS) 1,800 PSI
7. GROUT STRENGTH (28 DAYS) ASTM C476 - 2,000 PSI
8. WIRE REINFORCING ASTM A82, STD. LADDER
TYPE - 9 GAUGE ZINC
COATED PER ASTM A116 -
(DUR-O-WALL OR
APPROVED EQUAL @ 16"
O.C. VERTICAL SPACING)
STEEL
1. STRUCTURAL STEEL (WIDE FLANGES) ASTM A992, GRADE 50
2. STRUCTURAL STEEL (ALL OTHER TYPES) ASTM A36
3. ANCHOR RODS ASTM F1554, GRADE 55
WITH WELDING
SUPPLEMENT S1
4. LIGHT GAUGE STEEL STUDS/JOISTS
A. 12 TO 16 GAUGE (G60 GALV.) ASTM A1003 GRADE ST50H
(Fy=50 KSI)
B. 18+ GAUGE (G60 GALV.) ASTM A1003 GRADE ST33H
(Fy=33 KSI)
GEOTECHNICAL
1. BASIS OF DESIGN: THE FOUNDATION SYSTEM DESIGN IS BASED ON THE
PRESUMPTIVE LOAD BEARING VALUES OF SOILS LISTED IN TABLE 1806.2 OF
THE INTERNATIONAL BUILDING CODE.
2. FOUNDATION SYSTEM: SHALLOW FOOTINGS
3. MAXIMUM ALLOWABLE SOIL BEARING CAPACITY 1,500 PSF
4. LATERAL EARTH PRESSURE:
A. PASSIVE RESISTANCE 180 PCF
B. ACTIVE PRESSURE 50 PCF
C. AT-REST PRESSURE 65 PCF
5. SUBGRADE PREPARATION:
A. HEAVILY ORGANIC OR ROOT INFESTED TOPSOIL SHALL BE EXCAVATED
AND DISCARDED OR STOCKPILED FOR LATER USE IN COVERING
FINISHED LANDSCAPED AREAS AFTER CONSTRUCTION. REMOVE
TOPSOIL TO A MINIMUM DEPTH OF 8 INCHES. DEEPER STRIPPING SHALL
BE DONE IF ORGANIC MATERIALS REMAIN BELOW A DEPTH OF 8
INCHES.
B. REMOVE ALL EXISTING STRUCTURES TO BE DEMOLISHED PRIOR TO
GRADING. THIS INCLUDES PAVING, SIDEWALKS, AND OTHER
MISCELLANEOUS SMALL STRUCTURES.
6. STRUCTURAL FILL REQUIREMENTS:
A. CLEAN, INORGANIC, LOW TO MEDIUM PLASTICITY LEAN CLAY (CL) OR
SILT (ML), OR A COMBINATION OF THESE TWO MATERIALS
B. MAXIMUM LIQUID LIMIT (LL) 45
C. MAXIMUM PLASTICITY INDEX 22
D. WATER CONTENT (% OF OPTIMUM) +/-3%
E. MAXIMUM LOOSE LIFT 8"
F. MINIMUM COMPACTION 95% (STANDARD
PROCTOR TEST
ASTM D-698)
7. SPREAD FOOTINGS SHALL BE PLACED ON NEAT, CLEAN AND DRY
EXCAVATIONS. EXTREME CARE SHALL BE TAKEN WHEN EXCAVATING NEAR
THE BEARING SURFACE. FOOT TRAFFIC SHALL BE KEPT TO A MINIMUM
NECESSARY TO PLACE THE FOOTING REINFORCEMENT AND CONCRETE.
8. CONTRACTOR SHALL PROVIDE FOR ADEQUATE DRAINAGE OF SURFACE
WATER AWAY FROM THE STRUCTURE AND EXCAVATED AREAS DURING
CONSTRUCTION. THIS INCLUDES NECESSARY PUMPING, TRENCHING,
BACKFILL AND/OR DIKE CONSTRUCTION.
9. GRANULAR SUBBASE UNDER SLAB ON GRADE:
A. MINIMUM THICKNESS SEE PLAN
B. MINIMUM COMPACTION 95% (STANDARD
PROCTOR TEST
ASTM D-698)
C. GRADATION REQUIREMENTS
a. 100% PASSING THE 3/4" SIEVE
b. LESS THAN 15% PASSING THE 100 SIEVE
c. LESS THAN 2% PASSING THE 200 SIEVE
CAST-IN-PLACE CONCRETE
(REFERENCE SPECIFICATION SECTION 033000 IN PROJECT MANUAL)
GENERAL CONCRETE REQUIREMENTS
1. CONCRETE BATCH DESIGN(S) SHALL BE PROPORTIONED AND PRODUCED IN
ACCORDANCE WITH ACI 318, IN PARTICULAR CHAPTER 5, AND ACI 301. MIX
AND DELIVER IN ACCORDANCE WITH ASTM C94.
2. CONCRETE STRENGTH: SEE MATERIAL DATA NOTES & SPECIFICATION
SECTION 033000
3. SLUMP LIMITS: SEE SPECIFICATION SECTION 033000
4. MAXIMUM W/C RATIO: SEE SPECIFICATION SECTION 033000
5. AIR ENTRAINMENT: SEE SPECIFICATION SECTION 033000
6. ADMIXTURES: SEE SPECIFICATION SECTION 033000
7. FLY ASH: SEE SPECIFICATION SECTION 033000
8. CONCRETE TO CONCRETE COLD JOINTS - PROVIDE 1/4" INTENTIONALLY
ROUGHENED SURFACE AT ALL HORIZONTAL JOINTS.
9. EXPOSED CORNERS: PROVIDE A 3/4" CHAMFER AT ALL EXPOSED
CONCRETE CORNERS.
10. CURING: SEE SPECIFICATION SECTION 033000
11. REINFORCING BAR WELDING: ABSOLUTELY NO WELDING OF REINFORCING
BARS OR TORCHING TO BEND REINFORCING BARS SHALL BE ALLOWED
WITHOUT THE SPECIFIC APPROVAL OF THE ENGINEER.
12. MINIMUM CONCRETE CLEAR COVER:
A. FOOTINGS
a. TOP 2"
b. BOTTOM 3"
c. SIDES 3"
B. INTERIOR SLABS (TOP) SEE TYPICAL SLAB JOINT DETAIL
ON SHEET S2-01
C. EXTERIOR SLABS (TOP) 2"
D. OTHER COVER REQUIREMENTS SHALL BE AS NOTED IN APPLICABLE
DETAILS.
13. NON-METALLIC, SHRINKAGE-RESISTANT GROUT: SEE SPECIFICATION
SECTION 051200
SLAB ON GRADE REQUIREMENTS
1. SLAB THICKNESS: SEE PLAN
2. SLAB REINFORCING: SEE PLAN
3. GRANULAR SUBBASE: SEE GEOTECHNICAL NOTES
4. VAPOR RETARDER: SEE SPECIFICATION SECTION 033000. LAP AND TAPE
ALL JOINTS AND HOLES.
5. CRACK CONTROL JOINTS (WHETHER CONSTRUCTION JOINTS OR SAWED
JOINTS) IN SLABS ON GRADE SHALL OCCUR AS SHOWN AND ACROSS ALL
DOOR OPENINGS. LOCATE JOINTS AT RE-ENTRANT CORNERS OF SLABS.
A. MAXIMUM SPACING OF CONTROL JOINTS: 12 FEET
6. CURING: CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A
MINIMUM OF SEVEN DAYS AFTER ITS PLACEMENT. APPROVED CURING: SEE
SPECIFICATION SECTION 033000
7. SEAL ALL EXPOSED CONSTRUCTION/CRACK CONTROL JOINTS.
A. SEALANT: SEE ARCHITECTURE.
8. FLOOR FINISH & FLATNESS CRITERIA: SEE SPECIFICATION SECTION 033000
ANCHORAGE REQUIREMENTS
1. HEADED CONCRETE ANCHORS (HCA): AUTOMATICALLY END WELDED IN THE
SHOP OR FIELD IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS. ANCHOR WELDS SHALL BE TESTED PER AWS
SECTION 7.7.
2. POST-INSTALLED MECHANICAL ANCHORS: INSTALL USING MINIMUM
TORQUE, EMBEDMENTS, EDGE DISTANCES AND SPACING (UNLESS
OTHERWISE NOTED) AS RECOMMENDED BY THE ANCHOR MANUFACTURER.
3. POST-INSTALLED ADHESIVE ANCHORS: INSTALLATION TO MEET
MANUFACTURER'S RECOMMENDATIONS (UNLESS NOTED OTHERWISE)
INCLUDING MINIMUM EMBEDMENTS, EDGE DISTANCES, SPACING,
PROCEDURES, AND CURING TIME PRIOR TO LOADING.
4. POST-INSTALLED ANCHORS SHALL BE LOCATED PER THE DETAILS.
5. AVOID CUTTING OR DAMAGING EXISTING REINFORCING. SHOULD
LOCATIONS OF DRILLED HOLES BE FOUND DIRECTLY ALIGNED WITH
REINFORCING BARS, NOTIFY ENGINEER FOR NECESSARY ADJUSTMENTS TO
THE DESIGN.
UNIT MASONRY
(REFERENCE SPECIFICATION SECTION 042000 IN PROJECT MANUAL)
1. DESIGN CRITERIA: MASONRY SHALL BE CONSTRUCTED PER THE
REQUIREMENTS OF ACI 530.
2. UNIT TYPES: SEE SPECIFICATION SECTION 042000
3. UNIT COMPRESSIVE STRENGTH: SEE MATERIAL DATA NOTES AND
SPECIFICATION SECTION 042000
4. MORTAR: SEE MATERIAL DATA NOTES AND SPECIFICATION SECTION 042000
5. GROUT: SEE MATERIAL DATA NOTES AND SPECIFICATION SECTION 042000
6. CMU REINFORCING: UNLESS NOTED OTHERWISE, REINFORCE ALL CMU
WALLS WITH VERTICAL #5 @ 32" O.C. FILL ALL REINFORCED CELLS WITH
GROUT. MINIMUM GROUT BETWEEN MASONRY AND REINFORCING SHALL
BE 1/2". MINIMUM GROUT BETWEEN PAIRS OF REINFORCING BARS SHALL
BE 3/4".
A. PROVIDE #5 VERTICAL REINFORCING AT THE FOLLOWING LOCATIONS:
a. AT ALL CORNERS OF CMU WALLS
b. AT ALL ENDS OF CMU WALLS
c. EACH SIDE OF CONTROL JOINTS
d. EACH SIDE OF WALL OPENINGS
B. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF CONTROL JOINTS.
7. BOND BEAMS
A. LOCATED AT TOP OF ALL CMU WALLS AND WHERE INDICATED IN
DETAILS
B. MINIMUM DEPTH UNLESS OTHERWISE NOTED = 8".
C. REINFORCING - (2) #4 CONTINUOUS. LAP SPLICE = 28 IN.
D. CORNER DOWELS - (2) #4 RIGHT ANGLE DOWELS THAT LAP A MINIMUM
OF 2'-0" WITH ADJACENT BOND BEAM REINFORCING. IF BOND BEAMS AT
INTERSECTING WALLS MEET AT DIFFERENT ELEVATIONS, EXTEND BOTH
BOND BEAMS AROUND INTERSECTING CORNER TO FIRST INTERIOR
REINFORCED CELL, BUT NOT LESS THAN 4 FEET.
E. EXTEND BOND BEAMS THROUGH CONTROL JOINTS, BUT INTERRUPT
BOND BEAM REINFORCING AT CONTROL JOINTS.
8. LINTEL BEARING: PROVIDE A MINIMUM OF 8 INCHES BEARING AT EACH END.
9. CONTROL JOINTS: EXCEPT WHERE OFFSETS OR SLIP JOINTS ARE SHOWN,
CONTROL JOINTS SHALL BE A CONTINUOUS VERTICAL LINE FROM TOP OF
FOOTING TO TOP OF MASONRY WALL. SPACE CONTROL JOINTS AS
FOLLOWS:
A. INTERIOR WALLS 36 FT. O.C. MAX.
B. EXTERIOR WALLS 24 FT. O.C. MAX.
STEEL DECKING
(REFERENCE SPECIFICATION SECTION 053100 IN PROJECT MANUAL)
1. DECK GOVERNING CRITERIA: THE DESIGN, FABRICATION, AND ERECTION OF
METAL DECKING SHALL BE IN ACCORDANCE WITH THE CURRENT EDITION
OF THE SDI SPECIFICATIONS AND THE SDI DIAPHRAGM DESIGN MANUAL.
2. ROOF DECK CONNECTIONS: ROOF DECKING SHALL BE CONNECTED TO THE
STRUCTURE AS INDICATED IN THE ROOF DECK SCHEDULE. MAINTAIN
OVERALL STRUCTURAL BRACING UNTIL ALL DECKING HAS BEEN INSTALLED.
3. DECK PROTECTION: SEE SPECIFICATION SECTION 053100
STRUCTURAL STEEL FRAMING
(REFERENCE SPECIFICATION SECTION 051200 IN PROJECT MANUAL)
GENERAL STRUCTURAL STEEL REQUIREMENTS
1. DESIGN CRITERIA: STRUCTURAL STEEL SHALL BE INSTALLED PER THE
REQUIREMENTS OF AISC 360.
2. STRUCTURAL STEEL GRADES: SEE MATERIAL DATA NOTES AND
SPECIFICATION SECTION 051200
3. ANCHOR AND BOLT GRADES: SEE MATERIAL DATA NOTES AND
SPECIFICATION SECTION 051200
4. WELD ELECTRODES: SEE MATERIAL DATA NOTES AND SPECIFICATION
SECTION 051200
5. BEARING CONNECTIONS: UNLESS OTHERWISE NOTED, ALL BEAM
CONNECTIONS SHALL BE SIMPLE FRAMED SHEAR BEARING CONNECTIONS
IN ACCORDANCE WITH THE AISC "SPECIFICATIONS FOR STRUCTURAL
JOINTS USING ASTM A325 OR A490 BOLTS."
6. DESIGN OF CONNECTIONS: BEAM CONNECTIONS SHALL BE AS DETAILED ON
THE PLANS. ALTERNATIVE CONNECTIONS, DESIGNED BY A LICENSED
ENGINEER FOR THE FABRICATOR, MAY BE UTILIZED PROVIDED THE
ALTERNATIVE CONNECTION PROVIDES THE SAME LOAD CARRYING
CAPACITY OF THE ORIGINAL DESIGN.
7. SPLICES: STEEL FABRICATOR SHALL VERIFY WITH ENGINEER ALL BEAM
SPLICES OTHER THAN THOSE SHOWN ON THE PLANS. ANY FULL
PENETRATION SHOP SPLICES APPROVED BY THE ENGINEER SHALL BE
INSPECTED BY RADIOGRAPHIC METHODS BY A TESTING LABORATORY
APPROVED BY THE ENGINEER AND PAID FOR BY THE FABRICATOR.
8. OPPOSING CONNECTIONS: WHERE BEAMS ARE BOLTED ON TWO SIDES OF
A COMMON PLATE OR WEB, THE CONNECTIONS SHALL BE DETAILED WITH
AN ADDITIONAL ROW OF BOLTS ON ONE SIDE THAT IS NOT SHARED WITH
THE OTHER SIDE TO ALLOW INDEPENDENT BOLTING DURING ERECTION.
9. STEEL PROTECTION: ALL STRUCTURAL STEEL SHALL BE CLEANED AND
PAINTED WITH PRIMER PER SPECIFICATION SECTION 051200, UNLESS
NOTED OTHERWISE.
10. SHOP DRAWINGS: SEE SPECIFICATION SECTION 051200 FOR SUBMITTAL
REQUIREMENTS.
11. SLIDE BEARINGS: WHERE SHOWN ON THE DRAWINGS, TEFLON SLIDE
BEARING PADS SHALL BE PROVIDED. BEARING PADS SHALL BE DURA-SLIDE
AS MANUFACTURED BY TOBI ENGINEERING, INC. OR APPROVED EQUAL.
12. WELDING: ALL WELDING SHALL BE PERFORMED BY QUALIFIED WELDERS
PER AWS STANDARD QUALIFICATION PROCEDURES.
13. COMPLETE PENETRATION WELDS: COMPLETE PENETRATION WELDED
CONNECTIONS SHALL BE PROVIDED WHERE INDICATED. A MINIMUM OF 10%
OF ALL FIELD AND SHOP FULL PENETRATION WELDS SHALL BE TESTED BY
X-RAY OR ULTRASONIC PROCEDURES. (SEE SPECIFICATIONS FOR OTHER
TESTING.)
L -1
L -1
C .J
C
.J
T.O. SLAB
EL. SEE ARCH.
EL. = SEE PLAN
FIN. FLOOR
EL. = SEE PLAN
T.O.F.
@ 16" O.C.
600S250-43 LIGHT GAUGE JOISTS
OPEN
S101
S101
S101 5
S101 5
S101
GB1-6
GB1-6
GB1-6
G B
-6
S101
S101
TYP.
GRANULAR FILL
UNDISTURBED SOIL
CONC. SLAB - SEE PLAN
EQUIPMENT - SEE PLAN
12" DEEP CONCRETE FOUNDATION PAD
W/ #5 @ 12" O.C. E.W. TOP & BOTTOM
NOTES:
1. CONTRACTOR SHALL ANCHOR EQUIPMENT PER EQUIPMENT
MANUFACTURER REQUIREMENTS USING HILTI KWIK BOLT III
EXPANSION ANCHORS OR HILTI HIT-HY 200 EPOXY ANCHORS.
2. CONTRACTOR SHALL VERIFY AND COORDINATE LENGTH AND
WIDTH OF PAD WITH EQUIPMENT MANUFACTURER.
3. CONTRACTOR SHALL VERIFY AND COORDINATE ALL OPENING
SIZES AND LOCATIONS REQUIRED IN FOUNDATION PAD.
PROVIDE DOWEL TO MATCH
AND LAP VERT. WALL REINF.
PAVING OR
FINISHED GRADE
AS OCCURS
CENTERLINE OF CMU WALL
= CENTERLINE OF FOOTING
CONC. FOOTING -
SEE PLAN & SCHED.
FOR SIZE & REINF.
GROUT BOTTOM
COURSE SOLID
CMU WALL - SEE PLAN &
SCHED. FOR SIZE & REINF.
1/2" EXPANSION JOINT
CONC. SLAB ON
GRADE - SEE PLAN
CMU WALL - SEE
PLAN AND SCHED.
FOR SIZE AND REINF.
ROOFING AND INSULATION -
SEE ARCH.
METAL DECKING - SEE PLAN &
SCHED. FOR SIZE & ATTACH.
LIGHT GAUGE
JOIST - SEE PLAN
CONT. RIM TRACK
8" BOND COURSE W/ (2)
#4 CONT. - GROUT SOLID
CONT. L4X4X3/8 ANGLE
W/ 1/2" DIA. HILTI KIWK
BOLT 3 ANCHORS @ 24"
O.C. (3 1/2" EMBED.)
(2) #10 SCREWS
@ EACH JOIST
CONT. 2X PLATE W/ 1/2" DIA.
HILTI KIWK BOLT 3 ANCHORS
@ 24" O.C. (3 1/2" EMBED.)
CMU WALL - SEE PLAN AND
SCHED. FOR SIZE AND REINF.
ROOFING AND INSULATION -
SEE ARCH.
METAL DECKING - SEE PLAN &
SCHED. FOR SIZE & ATTACH.
LIGHT GAUGE
JOIST - SEE PLAN
ATTACH JOIST TO CMU W/ (2)
HILTI X-U KNURLED SHANK
FASTENERS @ 12" O.C.
8" BOND COURSE W/ (2)
#4 CONT. - GROUT SOLID
CONT. 2X PLATE W/ 1/2" DIA.
HILTI KIWK BOLT 3 ANCHORS
@ 24" O.C. (3 1/2" EMBED.)
W8X15 STEEL LINTEL
3/4" BEARING PLATE OVER 3/4" NON-
SHRINK GROUT W/ (2) 1/2" DIA. HILTI
HIT-HY 270 EPOXY ANCHORS IN LONG
SLOTTED HOLES (4 1/2" EMBED.)
GROUT MASONRY CELL
BELOW LINTEL BEARING
SOLID (FULL HEIGHT)
EXIST. CMU
TOOTH IN NEW CMU
JAMB BLOCK EACH
END OF OPENING NEW WALL OPENING -
SEE ARCH. FOR EXTENTS
5/16" STEEL PLATE WHERE CMU
EXTENDS BEYOND BEAM FLANGE BY
MORE THAN 3/4" ON EITHER SIDE -
PLATE WIDTH SHALL BE 1" LESS THAN
WALL THICKNESS (FIELD VERIFY)
1 1/2" SOLID BLOCKS TO COVER
BEAM WHEN EXPOSED TO VIEW
(NOT SHOWN FOR CLARITY)
REMOVE AND REPLACE ADDITIONAL CMU
ABOVE WALL OPENING AS REQUIRED
FOR INSTALLATION OF STEEL LINTEL
EXISTING CMU WALL
ROOFING AND INSULATION -
SEE ARCH.
METAL DECKING - SEE PLAN &
SCHED. FOR SIZE & ATTACH.
LIGHT GAUGE
JOIST - SEE PLAN
ATTACH JOIST TO EXISTING
CMU W/ (2) HILTI X-U KNURLED
SHANK FASTENERS @ 12" O.C.
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
241749
00000
FORT SMITH NATIONAL HISTORIC SITE
301 PARKER AVE
FORT SMITH, AR 72901C
U s e rs \e h o ff \D o c u m e n ts
\R e v it te m p \0
-S T
R U
C
R
-F O
S M e h o ff s c h e m m e r.
c o m .r v t
ECH
ECH
KMW
01/03/2020
07310.007
S101
PLANS & DETAILS
07310007FOSM- 3- S101 PLANS & DETAILS
PLAN NOTES:
REF. NOTES ( ):X
1 STRUCTURAL STOOP - SEE SHEET S102 FOR TYPICAL DETAIL. REFERENCE
ARCHITECTURAL DRAWINGS FOR STOOP DIMENSIONS.
2 4" CONCRETE SLAB ON GRADE W/ 6X6 W2.9XW2.9 W.W.F. OVER 4"
GRANULAR FILL. - TYP. REFERENCE ARCH DRAWINGS FOR SLOPE
REQUIREMENTS AS NEEDED.
3 'C.J.' INDICATES CONTROL JOINT - SEE TYPICAL DETAIL ON SHEET S201
4 DRILL & EPOXY LONG. FOOTING REINF. INTO EXIST FOOTING (6" MIN.
EMBED.)
5 1 1/2" 'B' 22 GA. METAL ROOF DECK. SEE METAL ROOF DECK SCHEDULE
FOR MORE INFORMATION
6 MECHANICAL EQUIPMENT MAX OPERATING WEIGHT OF 12,000 LBS.
7 EXISTING DOWNSPOUT WITH UNKNOWN PIPING LOCATION. CONTRACTOR
SHALL TAKE CARE TO CONSTRUCT FOOTINGS AROUND PIPE PER TYPICAL
DETAIL ON S201.
A. REFERENCE SHEET S01 FOR STRUCTURAL NOTES.
B. REFERENCE SHEET S201 FOR TYPICAL DETAILS NOT NECESSARILY
INDICATED ON PLAN.
C. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
D. TOP OF FOOTING (T.O.F.) ELEVATION IS 109’-7”, TYPICAL U.N.O.
E. FINISHED FLOOR ELEVATION (F.F.E.) IS 110’-3”, TYPICAL U.N.O.
F. GRADE BEAMS ARE REQUIRED AT ALL EXTERIOR WALLS. BOTTOM OF
GRADE BEAM SHALL HAVE A MINIMUM DEPTH OF 24” BELOW EXTERIOR
GRADE.
G. STRUCTURAL STOOPS ARE REQUIRED AT ALL EXTERIOR SWING DOORS.
SEE TYPICAL DETAIL ON SHEET S201.
H. CONTRACTOR FIELD VERIFY EXISTING CONDITIONS AND NOTIFY ENGINEER
OF RECORD OF ANY DISCREPANCIES WITH CONSTRUCTION DOCUMENTS.
SCALE: 1/8" = 1'-0"
FRAMING PLAN
SCALE: 1/8" = 1'-0"
FOUNDATION PLAN
GRADE BEAM SCHEDULE
MARK WIDTH DEPTH LONGITUDINAL REINFORCING STIRRUPS
GB1-6 1' - 6" 2' - 0" (3) #5 BARS BOT., (3) #5 BARS TOP #4 @ 24" O.C.
MASONRY WALL REINF. SCHEDULE
MARK WIDTH
REINFORCING
VERTICAL HORIZONTAL
A 0' - 8" #5 @ 32" O.C. MAX. LADDER TYPE - 2 - W1.7 WIRES @ 16" O.C.
MASONRY LINTEL SCHEDULE
MARK BEARING REINFORCING
L-1 8" 16" BOND BEAM W/ (2) #5 CONT. @ BOT.
SCALE: 1/2" = 1'-0"
EXTERIOR EQUIPMENT PAD DETAIL
SCALE: 3/4" = 1'-0"
EXTERIOR MASONRY WALL AT CONCRETE GRADE BEAM
SCALE: 3/4" = 1'-0"
LIGHT GAUGE JOIST BEARING AT CMU WALL
SCALE: 3/4" = 1'-0"
LIGHT GAUGE JOIST AT CMU WALL
METAL DECKING SCHEDULE
LOCATION
DEPTH
(IN.)
GAUGE MIN. I MIN. S FINISH
CONNECTION TO
SUPPORTING MEMBERS
(#12 TEK SCREWS)
SIDE LAPS
(#10 SCREWS)
REMARKS
ROOF 1 1/2 22 0.155 0.186 GALVANIZED 36/4 PATTERN
(1) SIDE LAP FASTENERS
#10 TEK SCREWS - EA.
JOIST SPACE
TYPE "B"
SCALE: 3/4" = 1'-0"
STEEL LINTEL ABOVE NEW OPENING IN EXISTING MASONRY WALL
SCALE: 3/4" = 1'-0"
SECTION AT EXISTING WALL
NOTE: PROVIDE TYPE 'A' WALLS AT ALL CMU WALLS, TYPICAL U.N.O.
OPTION 'A': LEAN CONCRETE FILL OPTION 'B': STRUCTURAL SLAB
CONC. FOOTING -
SEE PLAN & SCHED.
FOR SIZE & REINF.
1/2" EXPANSION JOINT
6" CONC. W/ #4
@ 12" O.C. E.W.
LEAN CONCRETE FILL
SEE PLANS FOR
REQUIRED WIDTH
OF EACH STOOP
1/2" EXPANSION JOINT
SEE PLAN
S L O
P E
V O
ID
SEE PLAN
S L O
P E
CONC. FOOTING -
SEE PLAN & SCHED.
FOR SIZE & REINF.
1/2" EXPANSION JOINT 4 1/2" CONC. W/ #4 @ 12" O.C.
E.W. OVER 1 1/2", 'C', 20 GA.
GALV. (G90) METAL DECKING
(6" TOTAL THICKNESS)
EXTERIOR PAVING
(SEE CIVIL)
1/2" EXPANSION JOINT
#4 BENTS @ 1'-0"
O.C. ALL SIDES TYP.
18"
8"
8" X 3'-4" CONC. FTG. W/
(2) #5 TOP & BOTTOM &
#4 VERT. @ 24" O.C.
T
T /4
3/16".
TYPICAL CONTROL JOINT (C.J.)
TYPICAL KEYED CONSTRUCTION JOINT
SAWCUT JOINT & SEAL
SPECIFIED SLAB
REINFORCEMENT
- SEE PLAN
5/8" DIA. DOWELS
@ 12" O.C. X 1'-6"
SEALANT
NOTES:
1. ALL FLOOR SLABS SHALL BE PLACED IN PAVING LANE PATTERN. A MAXIMUM
JOINT SPACING OF 12'-0" U.N.O. AND A MAXIMUM SLAB PANEL ASPECT RATIO
(LENGTH/WIDTH) OF 1.5 SHALL BE OBSERVED.
2. ALL JOINTS TERMINATING A POUR SHALL BE KEYED CONSTRUCTION JOINTS.
3. TIME SAW CUTTING OPERATION TO PRECLUDE SHRINKAGE, CRACKING AND
DISLODGING OF AGGREGATE.
T /3
VERTICAL REINF. TO
MATCH AND LAP VERT.
WALL REINF.
GROUT FULL DEPTH
OF LINTEL, USE OPEN
END UNITS
REINF. PER
SCHEDULE
"P E
R S
C H
E D
L
IN
T E
L D
E P
T H
TYPICAL CMU LINTEL
2' - 0".
C.J.
TOP OF MASONRY
WALL SUPPORT
VERT. REINF. IN
GROUTED CELLS
FULLY GROUTED
BLOCK UNDER BRG.
6'-0" LENGTH OF
HORIZ. JOINT REINF.
IN FIRST COURSE
LINE BELOW LINTEL
16 OZ. COPPER SHEET CUT
BACK 1/2" FROM FACES OF
BLOCK (AT C.J. ONLY)C.J.
MASONRY OR
STEEL LINTEL
BOND BEAM ABOVE
STEEL LINTELS ONLY
BEARING LENGTH
SPAN
NOTE:
SEE LINTEL SCHEDULE FOR
REQUIRED BEARING LENGTH.
DOOR, WINDOW, OR
OTHER OPNG. PER
ARCH. DRAWINGS
SINGLE BAR
DOUBLE BAR
< MAX. SPACING
E Q
E
Q
FULLY GROUTED CELLS
END OF WALL,
CORNER OF WALL,
OR CONTROL JOINT
NOTE:
SPLICE VERTICAL
BARS A MIN. 48 BAR
DIAMETERS
D
D
< MAX. SPACING
STAGGER SPLICES 24
BAR DIAMETERS IN 8"
NOMINAL WALLS
FULLY GROUTED CELLS
END OF WALL,
CORNER OF WALL,
OR CONTROL JOINT
NOMINAL WALL
THICKNESS
D (INCHES)
ALLOWABLE
TOLERANCE
8" 5.25 +/- 1/2"
10" 7.25 +/- 1/2"
12" 9.00 +/- 3/4"
BAR…