This specification document outlines requirements for an ethylene-propylene-diene-monomer (EPDM) roofing system. Key details include mechanically fastened EPDM membrane roofing over insulation and substrate board. The project requires white EPDM membrane and sheet metal flashing for all roof locations in climate zones 3 and 4. Insulation must be polyisocyanurate or wood fiberboard with minimum R-values. The roofing system must meet wind uplift resistance standards and be FM Approvals listed. The contractor must provide a 20-year warranty on materials and workmanship. Relatedly, the federal contract opportunity is to remove an existing HVAC unit at a visitor center and replace it with a new geothermal fluid cooler, natural gas boiler, ductless split heat pumps, and energy recovery ventilators near an existing maintenance building.
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOSM – 241749 075323 - 1
031414 ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING
SECTION 075323
ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Mechanically fastened, ethylene-propylene-diene-terpolymer (EPDM) roofing system.
2. Substrate board.
3. Roof insulation.
4. Sheet Metal Flashing and Trim.
5. Gutter and downspouts.
1.2 Vents and plumbing boots PREINSTALLATION MEETINGS
A. Preliminary Conference: Conduct conference at Project site.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Include roof plans, sections, details, and attachments to other work, including the following:
1. Layout and thickness of insulation.
2. Base flashings and membrane terminations.
3. Flashing details at penetrations.
4. Tapered insulation, thickness, and slopes.
5. Roof plan showing orientation of steel roof deck and orientation of roof membrane and fastening spacings and patterns for mechanically fastened roofing system.
6. Insulation layout plans including tapered roof insulation and cricket locations clearly identified, and indicate all roof slopes.
C. Samples: For the following products:
1. Roof membrane and flashings of color required.
D. Wind Uplift Resistance Submittal: For roofing system, indicating compliance with wind uplift performance requirements.
1.4 INFORMATIONAL SUBMITTALS
A. Manufacturer Certificates:
1. Performance Requirement Certificate: Signed by roof membrane manufacturer, certifying that roofing system complies with requirements specified in "Performance Requirements" Article.
a. Submit evidence of complying with performance requirements.
FOSM – 241749 075323 - 2
2. Special Warranty Certificate: Signed by roof membrane manufacturer, certifying that all materials supplied under this Section are acceptable for special warranty.
B. Product Test Reports: For components of roof membrane and insulation, for tests performed by a qualified testing agency, indicating compliance with specified requirements.
C. Research reports.
D. Field Test Reports:
1. Fastener-pullout test results and manufacturer's revised requirements for fastener patterns.
E. Field quality-control reports.
F. Sample warranties.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: A qualified firm that is approved, authorized, or licensed by roofing system manufacturer to install manufacturer's product and that is eligible to receive manufacturer's special warranty.
1.7 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of roofing system that fail in materials or workmanship within specified warranty period.
1. Warranty Period: 20 years from Date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Accelerated Weathering: Roof membrane shall withstand 2000 hours of exposure when tested according to ASTM G152, ASTM G154, or ASTM G155.
B. Impact Resistance: Roof membrane shall resist impact damage when tested according to ASTM D3746, ASTM D4272, or the Resistance to Foot Traffic Test in FM Approvals 4470.
C. Wind Uplift Resistance: Design roofing system to resist the following wind uplift pressures when tested according to FM Approvals 4474, UL 580, or UL 1897:
1. Zone 1 (Roof Area Field): <18.4 lbf/sq. ft. (kPa/sq. m)>.
2. Zone 2 (Roof Area Perimeter): <30.9 lbf/sq. ft. (kPa/sq. m)>.
a. Location: From roof edge to 4 feet minimum inside roof edge, or as required by roofing manufacturer for warranty if more distance is required.
FOSM – 241749 075323 - 3
3. Zone 3 (Roof Area Corners): <46.5 lbf/sq. ft. (kPa/sq. m)>.
a. Location: 4 feet minimum in each direction from building corner, or as required by roofing manufacturer for warranty if more distance is required.
D. FM Approvals' RoofNav Listing: Roof membrane, base flashings, and component materials shall comply with requirements in FM Approvals 4450 or FM Approvals 4470 as part of a roofing system, and shall be listed in FM Approvals' RoofNav for Class 1 or noncombustible construction, as applicable. Identify materials with FM Approvals Certification markings.
1. Fire/Windstorm Classification: Class 1A-60.
2. Hail-Resistance Rating: FM Global Property Loss Prevention Data Sheet 1-34 SH.
2.2 ETHYLENE-PROPYLENE-DIENE-TERPOLYMER (EPDM) ROOFING
A. EPDM Sheet: ASTM D4637/D4637M, Type I, non-reinforced, EPDM sheet.
1. Carlisle Syn Tec Incorporated.
2. Firestone Building Products.
3. Gen Flex Roofing Systems.
4. Johns Manville: a Berkshire Hathaway Company
5. Verisco Roofing Systems.
6. Other approved manufacturers
7. Thickness: 60 mils (1.5 mm), nominal.
8. Exposed Face Color:
a. White on black for all roof locations in Climate Zones 3 and 4 per the International Energy Conservation Code (IECC) Climate Zone Map..
2.3 AUXILIARY ROOFING MATERIALS
A. General: Auxiliary materials recommended by roofing system manufacturer for intended use and compatible with other roofing components.
1. Adhesive and Sealants: Comply with VOC limits of authorities having jurisdiction.
B. Sheet Flashing: 60-mil- (1.5-mm-) thick EPDM, partially cured or cured, according to application.
C. Bonding Adhesive: Manufacturer's standard.
D. Seaming Material: Single-component, butyl splicing adhesive and splice cleaner or Manufacturer's standard, synthetic-rubber polymer primer and 3-inch- (75-mm-) wide minimum, butyl splice tape with release film.
E. Lap Sealant: Manufacturer's standard, single-component sealant, colored to match membrane roofing.
F. Water Cutoff Mastic: Manufacturer's standard butyl mastic sealant.
G. Metal Termination Bars: Manufacturer's standard, predrilled stainless steel or aluminum bars, approximately 1 by 1/8 inch (25 by 3 mm) thick; with anchors.
H. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening components to substrate, and acceptable to roofing system manufacturer.
http://www.arcomnet.com/sustainable_design.aspx?topic=150 http://www.arcomnet.com/sustainable_design.aspx?topic=150
FOSM – 241749 075323 - 4
I. Miscellaneous Accessories: Provide pourable sealers, preformed cone and vent sheet flashings, molded pipe boot flashings, preformed inside and outside corner sheet flashings, reinforced EPDM securement strips, T-joint covers, in-seam sealants, termination reglets, cover strips, and other accessories.
1. Provide white flashing accessories for white EPDM membrane roofing.
2.4 SUBSTRATE BOARDS
A. Substrate Board: ASTM C1177/C1177M, glass-mat, water-resistant gypsum board or ASTM C1278/C1278M, fiber-reinforced gypsum board.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. CertainTeed Corporation.
b. Georgia-Pacific Gypsum LLC.
c. National Gypsum Company.
d. USG Corporation.
e. Other approved manufacturers.
2. Thickness: [1/2 inch (13 mm)].
3. Surface Finish: Unprimed.
B. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening substrate panel to roof deck.
2.5 ROOF INSULATION
A. Polyisocyanurate Board Insulation: ASTM C1289, Type II, Class 1, Grade 3 (25 psi), felt or glass-fiber mat facer on both major faces.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Atlas EPS; a division of Atlas Roofing Corporation.
b. Carlisle SynTec Incorporated.
c. Firestone Building Products.
d. Johns Manville; a Berkshire Hathaway Company.
e. Other approved manufacturers
2. Thermal Resistance: R-value of 5.0 per inch (25.4 mm).
3. Size: 48 by 48 inches (1219 by 1219 mm).
4. Thickness:
a. Base Layer: 1 inches.
b. Upper Layer: 1 inches.
B. Tapered Insulation: Provide factory-tapered insulation boards.
1. Material: Match roof insulation.
2. Minimum Thickness: 1/4 inch (6.35 mm).
http://www.specagent.com/Lookup?ulid=5110 http://www.specagent.com/Lookup?uid=123457146859 http://www.specagent.com/Lookup?uid=123457146858 http://www.specagent.com/Lookup?uid=123457146860 http://www.specagent.com/Lookup?uid=123457146862 http://www.specagent.com/LookUp/?ulid=5110&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=5110&mf=04&src=wd http://www.specagent.com/Lookup?ulid=8992 http://www.specagent.com/Lookup?uid=123457146866 http://www.specagent.com/Lookup?uid=123457146867 http://www.specagent.com/Lookup?uid=123457146868 http://www.specagent.com/LookUp/?ulid=8992&mf=04&src=wd http://www.specagent.com/LookUp/?ulid=8992&mf=04&src=wd
FOSM – 241749 075323 - 5
3. Slope:
a. Roof Field: 1/4 inch per foot (1:48) unless otherwise indicated on Drawings.
b. Saddles and Crickets: 1/2 inch per foot (1:24) unless otherwise indicated on
Drawings.
2.6 INSULATION ACCESSORIES
A. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening roof insulation to substrate, and acceptable to roofing system manufacturer.
2.7 SHEET METAL FLASHING AND TRIM
A. Performance Requirements:
1. General: Sheet metal flashing and trim assemblies shall withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failure due to defective manufacture, fabrication, installation, or other defects in construction.
Completed sheet metal flashing and trim shall not rattle, leak, or loosen, and shall remain watertight.
2. Sheet Metal Standard for Flashing and Trim: Comply with National Roofing Contractors Association’s (NRCA's) "The NRCA Roofing Manual" and Sheet Metal and Air Conditioning Contractors National Association’s (SMACNA's) "Architectural Sheet Metal Manual" requirements for dimensions and profiles shown unless more stringent requirements are indicated.
3. Single Ply Roofing Industry (SPRI) Wind Design Standard: Manufacture and install copings and roof edge flashings tested according to SPRI ES-1 and capable of resisting the following design pressure:
a. Design Pressure: 30 psf vertical design pressure.
4. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes to prevent buckling, opening of joints, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
B. Sheet Metal:
1. General: Protect mechanical and other finishes on exposed surfaces from damage by applying strippable, temporary protective film before shipping.
2. Metallic-Coated Steel Sheet: Provide zinc-coated (galvanized) steel sheet according to ASTM A 653/A 653M, G90 coating designation or aluminum-zinc alloy-coated steel sheet according to ASTM A 792/A 792M, Class AZ50 coating designation, Grade 40;
prepainted by coil-coating process to comply with ASTM A 755/A 755M.
a. Surface: Smooth, flat.
b. Exposed Coil-Coated Finish:
1) Two-Coat Fluoropolymer. American Architectural Manufacturers Association (AAMA) 621. Fluoropolymer finish containing not less than 70 percent Polyvinylidene Fluoride (PVDF) resin by weight in color coat. Prepare, FOSM – 241749 075323 - 6 pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions.
c. Color: As selected by COR from manufacturer's full range.
1) Metal Flashings: Match the standard color for the existing buildings “sheet metal color”.
d. Concealed Finish: Pretreat with manufacturer's standard white or light-colored acrylic or polyester backer finish, consisting of prime coat and wash coat with minimum total dry film thickness of 0.5 mil.
C. Underlayment Materials:
1. Synthetic Underlayment: Laminated or reinforced, woven polyethylene or polypropylene, synthetic roofing underlayment; bitumen free; slip resistant; suitable for high temperatures over 111 deg C (220 deg F); and complying with physical requirements of ASTM D 22/D 226M for Type I and Type II felts.
D. Miscellaneous Materials:
1. General: Provide materials and types of fasteners, solder, protective coatings, sealants, and other miscellaneous items as required for complete sheet metal flashing and trim installation and as recommended by manufacturer of primary sheet metal or manufactured item unless otherwise indicated.
2. Fasteners: Wood screws, annular threaded nails, self-tapping screws, self-locking rivets and bolts, and other suitable fasteners designed to withstand design loads and recommended by manufacturer of primary sheet metal or manufactured item.
a. General: Blind fasteners or self-drilling screws, gasketed, with hex-washer head.
1) Exposed Fasteners: Heads matching color of sheet metal using plastic caps or factory-applied coating. Provide metal-backed Ethylene Propylene Diene Monomer (EPDM) or Polyvinyl Chloride (PVC) sealing washers under heads of exposed fasteners bearing on weather side of metal.
2) Blind Fasteners: High-strength aluminum or stainless-steel rivets suitable for metal being fastened.
b. Fasteners for Zinc-Coated (Galvanized) or Aluminum-Zinc Alloy-Coated Steel Sheet: Series 300 stainless steel or hot-dip galvanized steel according to ASTM A 153/A 153M or ASTM F 2329.
3. Sealant Tape: Pressure-sensitive, 100 percent solids, polyisobutylene compound sealant tape with release-paper backing. Provide permanently elastic, nonsag, nontoxic, nonstaining tape 13 mm (1/2 inch) wide and 3 mm (1/8 inch) thick.
4. Elastomeric Sealant: ASTM C 920, elastomeric polymer sealant; of type, grade, class, and use classifications required to seal joints in sheet metal flashing and trim and remain watertight.
5. Butyl Sealant: ASTM C 1311, single-component, solvent-release butyl rubber sealant;
polyisobutylene plasticized; heavy bodied for hooked-type expansion joints with limited movement.
E. Manufactured Reglets:
1. Reglets: Units of two piece, type, material, and profile required, formed to provide secure interlocking of separate reglet and counterflashing pieces, and compatible with flashing
FOSM – 241749 075323 - 7
indicated with factory-mitered and welded corners and junctions. Provide with interlocking counterflashing on exterior face, of same metal as reglet.
a. Material: Aluminum, 0.61 mm (0.024 inch) thick.
b. Finish: Mill.
c. Type: 2 piece with reglet and removable counterflashing allowing for future roof re-work without removal of the reglet.
F. Fabrication General:
1. General: Custom fabricate sheet metal flashing and trim to comply with details shown and recommendations in cited sheet metal standard that apply to design, dimensions, geometry, metal thickness, and other characteristics of item required. Fabricate sheet metal flashing and trim in shop to greatest extent possible.
a. Fabricate sheet metal flashing and trim in thickness or weight needed to comply with performance requirements, but not less than that specified for each application and metal.
b. Obtain field measurements for accurate fit before shop fabrication.
c. Form sheet metal flashing and trim to fit substrates without excessive oil canning, buckling, and tool marks; true to line, levels, and slopes; and with exposed edges folded back to form hems.
d. Conceal fasteners and expansion provisions where possible. Do not use exposed fasteners on faces exposed to view.
2. Fabrication Tolerances: Fabricate sheet metal flashing and trim that is capable of installation to a tolerance of ¼ inch in 20 feet on slope and location lines indicated on Drawings and within 1/8-inch offset of adjoining faces and of alignment of matching profiles.
3. Expansion Provisions: Form metal for thermal expansion of exposed flashing and trim.
a. Form expansion joints of intermeshing hooked flanges, not less than 25 mm (1 inch) deep, filled with butyl sealant concealed within joints.
b. Use lapped expansion joints only where indicated on Drawings.
4. Sealant Joints: Where movable, nonexpansion-type joints are required, form metal to provide for proper installation of elastomeric sealant according to cited sheet metal standard.
5. Fabricate cleats and attachment devices from same material as accessory being anchored or from compatible, noncorrosive metal.
6. Fabricate cleats and attachment devices of sizes as recommended by cited sheet metal standard for application, but not less than thickness of metal being secured.
7. Seams: Fabricate nonmoving seams with flat-lock seams. Form seams and seal with elastomeric sealant unless otherwise recommended by sealant manufacturer for intended use.
G. Roof-Drainage Sheet Metal Fabrications:
1. Hanging Gutters: Fabricate to cross section required, complete with end pieces, outlet tubes, and other accessories as required. Fabricate in minimum 2400-mm- (96-inch-) long sections. Furnish flat-stock gutter brackets and gutter spacers and straps fabricated from same metal as gutters, of size recommended by cited sheet metal standard but with thickness not less than twice the gutter thickness. Fabricate expansion joints, expansion-joint covers, and gutter accessories from same metal as gutters. Shop fabricate interior and exterior corners.
FOSM – 241749 075323 - 8
a. Aluminum: 0.61 mm (0.024 inch) thick.
2. Downspouts: Fabricate in style, size and shape to match existing downspouts to dimensions indicated, or to replace existing downspouts complete with mitered elbows.
Furnish with metal hangers from same material as downspouts and anchors. Shop fabricate elbows.
a. Aluminum: 0.61 mm (0.024 inch) thick.
H. Low-Slope Roof Sheet Metal Fabrications:
1. Roof-Edge Flashing and Fascia Cap: Fabricate in minimum 96-inch- long, but not exceeding 12-foot- long, sections. Furnish with 6-inch- wide, joint cover plates.
a. Joint Style: Butted with expansion space and 6-inch-wide, concealed backup plate.
b. Fabricate from the Following Materials:
1) Aluminum-Zinc Alloy-Coated Steel: .0.024 inch thick.
2. Copings: Fabricate in minimum 96-inch- long, but not exceeding 12-foot- long, sections.
Fabricate joint plates of same thickness as copings. Furnish with continuous cleats to support edge of external leg and drill elongated holes for fasteners on interior leg. Miter corners, seal, and solder or weld watertight.
a. Coping Profile: As shown in the drawings.
b. Joint Style: Butted with expansion space and 6-inch-wide, concealed backup plate.
c. Fabricate from the following materials:
1) Aluminum-Zinc Alloy-Coated Steel: 0.024 inch thick.
3. Base Flashing: Fabricate from the following materials:
a. Aluminum-Zinc Alloy-Coated Steel: 0.024 inch thick.
4. Counterflashing and Flashing Receivers: Fabricate from the following materials:
a. Aluminum-Zinc Alloy-Coated Steel: 0.024 inch thick.
5. Roof-Penetration Flashing: Fabricate from the following materials:
2.8 Aluminum-Zinc Alloy-Coated Steel: 0.024 inch thick.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements and other conditions affecting performance of the Work.
3.2 INSTALLATION OF ROOFING, GENERAL
A. Install roofing system according to roofing system manufacturer's written instructions, FM Approvals' RoofNav assembly requirements, and FM Global Property Loss Prevention Data Sheet 1-29.
FOSM – 241749 075323 - 9
B. Complete terminations and base flashings and provide temporary seals to prevent water from entering completed sections of roofing system at end of workday or when rain is forecast.
Remove and discard temporary seals before beginning work on adjoining roofing.
C. Install roof membrane and auxiliary materials to tie in to existing roofing to maintain weathertightness of transition.
3.3 INSTALLATION OF SUBSTRATE BOARD
A. Install substrate board with long joints in continuous straight lines, with end joints staggered not less than 24 inches (610 mm) in adjacent rows.
1. At steel roof decks, install substrate board at right angle to flutes of deck.
a. Locate end joints over crests of steel roof deck.
2. Tightly butt substrate boards together.
3. Cut substrate board to fit tight around penetrations and projections, and to fit tight to intersecting sloping roof decks.
4. Fasten substrate board to top flanges of steel deck according to recommendations in FM
Approvals' RoofNav listed roof assembly requirements for specified Windstorm Resistance Classification and FM Global Property Loss Prevention Data Sheet 1-29.
3.4 INSTALLATION OF INSULATION
A. Coordinate installing roofing system components so insulation is not exposed to precipitation or left exposed at end of workday.
B. Comply with roofing system and insulation manufacturer's written instructions for installing roof insulation.
C. Installation Over Metal Decking:
1. Install base layer of insulation with joints staggered not less than 24 inches (610 mm) in adjacent rows and with long joints continuous at right angle to flutes of decking.
a. Locate end joints over crests of decking.
b. Trim insulation neatly to fit around penetrations and projections, and to fit tight to intersecting sloping roof decks.
c. Make joints between adjacent insulation boards not more than 1/4 inch (6 mm) in width.
d. Fill gaps exceeding 1/4 inch (6 mm) with insulation.
e. Cut and fit insulation within 1/4 inch (6 mm) of nailers, projections, and penetrations.
2. Install upper layers of insulation and tapered insulation with joints of each layer offset not less than 12 inches (305 mm) from previous layer of insulation.
a. Staggered end joints within each layer not less than 24 inches (610 mm) in adjacent rows.
b. Trim insulation neatly to fit around penetrations and projections, and to fit tight to intersecting sloping roof decks.
c. Make joints between adjacent insulation boards not more than 1/4 inch (6 mm) in width.
d. Trim insulation so that water flow is unrestricted.
FOSM – 241749 075323 - 10
e. Fill gaps exceeding 1/4 inch (6 mm) with insulation.
f. Cut and fit insulation within 1/4 inch (6 mm) of nailers, projections, and penetrations.
g. Adhere each layer of insulation to substrate using adhesive according to FM
Approvals' RoofNav listed roof assembly requirements for specified Windstorm Resistance Classification and FM Global Property Loss Prevention Data Sheet 1- 29, as follows:
3.5 MECHANICALLY FASTENED MEMBRANE ROOFING INSTALLATION
A. Mechanically fasten roof membrane over area to receive roofing according to roofing system manufacturer's written instructions.
B. Unroll roofing membrane and allow to relax before installing.
C. For in-splice attachment, install roof membrane with long dimension perpendicular to steel roof deck flutes.
D. Accurately align roof membrane, and maintain uniform side and end laps of minimum dimensions required by manufacturer. Stagger end laps.
E. Mechanically fasten or adhere roof membrane securely at terminations, penetrations, and perimeter of roofing.
F. Apply roof membrane with side laps shingled with slope of roof deck where possible.
G. Tape Seam Installation: Clean and prime both faces of splice areas, apply splice tape.
1. Firmly roll side and end laps of overlapping roof membrane to ensure a watertight seam installation.
2. Apply lap sealant and seal exposed edges of roofing terminations.
H. In-Splice Attachment: Secure one edge of roof membrane using fastening plates or metal battens centered within splice, and mechanically fasten roof membrane to roof deck. Field splice seam.
3.6 Adhere protection sheet over roof membrane at locations indicated.INSTALLATION OF BASE
FLASHING
A. Install sheet flashings and preformed flashing accessories, and adhere to substrates according to roofing system manufacturer's written instructions.
B. Apply bonding adhesive to substrate and underside of sheet flashing at required rate, and allow to partially dry. Do not apply to seam area of flashing.
C. Flash penetrations and field-formed inside and outside corners with cured or uncured sheet flashing.
D. Clean splice areas, apply splicing cement, and firmly roll side and end laps of overlapping sheets to ensure a watertight seam installation. Apply lap sealant and seal exposed edges of sheet flashing terminations.
E. Terminate and seal top of sheet flashings and mechanically anchor to substrate through termination bars.
FOSM – 241749 075323 - 11
3.7 PROTECTING AND CLEANING
A. Protect roofing system from damage and wear during remainder of construction period. When remaining construction does not affect or endanger roofing system, inspect roofing system for deterioration and damage, describing its nature and extent in a written report, with copies to
NPS COR.
B. Correct deficiencies in or remove roofing system that does not comply with requirements, repair substrates, and repair or reinstall roofing system to a condition free of damage and deterioration at time of Substantial Completion and according to warranty requirements.
C. Clean overspray and spillage from adjacent construction using cleaning agents and procedures recommended by manufacturer of affected construction.
3.8 SHEET METAL FLASHING AND TRIM INSTALLATION
A. Examination:
1. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances, substrate, and other conditions affecting performance of the Work.
a. Verify compliance with requirements for installation tolerances of substrates.
b. Verify that substrate is sound, dry, smooth, clean, sloped for drainage, and securely anchored.
c. Verify that air- or water-resistant barriers have been installed over sheathing or backing substrate to prevent air infiltration or water penetration.
2. Proceed with installation only after unsatisfactory conditions have been corrected.
B. Underlayment Installation:
1. Synthetic Underlayment: Install synthetic underlayment, wrinkle free, according to manufacturers’ written instructions, and using adhesive or self-adhered products only, no mechanical fasteners will be allowed.
C. General Installation:
1. General: Anchor sheet metal flashing and trim and other components of the Work securely in place, with provisions for thermal and structural movement. Use fasteners, solder, protective coatings, separators, sealants, and other miscellaneous items as required to complete sheet metal flashing and trim system.
a. Install sheet metal flashing and trim true to line, levels, and slopes. Provide uniform, neat seams with minimum exposure of solder, welds, and sealant.
b. Install sheet metal flashing and trim to fit substrates and to result in watertight performance. Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal.
c. Space cleats not more than 300 mm (12 inches) apart. Attach each cleat with at least two fasteners. Bend tabs over fasteners.
d. Install exposed sheet metal flashing and trim with limited oil canning, and free of buckling and tool marks.
e. Torch cutting of sheet metal flashing and trim is not permitted.
f. Do not use graphite pencils to mark metal surfaces.
FOSM – 241749 075323 - 12
2. Metal Protection: Where dissimilar metals contact each other, or where metal contacts pressure-treated wood or other corrosive substrates, protect against galvanic action or corrosion by painting contact surfaces with bituminous coating or by other permanent separation as recommended by sheet metal manufacturer or cited sheet metal standard.
a. Coat concealed side of sheet metal flashing and trim with bituminous coating where flashing and trim contact wood, ferrous metal, or cementitious construction.
b. Underlayment: Where installing sheet metal flashing and trim directly on cementitious or wood substrates, install underlayment and cover with slip sheet.
3. Expansion Provisions: Provide for thermal expansion of exposed flashing and trim. Space movement joints at maximum of 3 m (10 feet) with no joints within 600 mm (24 inches) of corner or intersection.
a. Form expansion joints of intermeshing hooked flanges, not less than 25 mm (1 inch) deep, filled with sealant concealed within joints.
b. Use lapped expansion joints only where indicated on Drawings.
4. Fasteners: Use fastener sizes that penetrate substrate not less than recommended by fastener manufacturer to achieve maximum pull-out resistance.
5. Conceal fasteners and expansion provisions where possible in exposed work and locate to minimize possibility of leakage. Cover and seal fasteners and anchors as required for a tight installation.
6. Seal joints as required for watertight construction.
a. Embed hooked flanges of joint members not less than 1 inch into sealant.
b. Form joints to completely conceal sealant.
c. When ambient temperature at time of installation is between 40 and 70 deg F, set joint members for 50 percent movement each way. Adjust setting proportionately for installation at higher ambient temperatures.
d. Do not install sealant-type joints at temperatures below 40 deg F.
D. Roof-Drainage System Installation:
1. General: Install sheet metal roof-drainage items to produce complete roof-drainage system according to cited sheet metal standard unless otherwise indicated. Coordinate installation of roof perimeter flashing with installation of roof-drainage system.
2. Expansion-Joint Covers: Install expansion-joint covers at locations and of configuration indicated. Lap joints a minimum of 4 inches (100 mm) in direction of water flow.
E. Roof Flashing Installation:
1. General: Install sheet metal flashing and trim to comply with performance requirements, sheet metal manufacturer's written installation instructions, and cited sheet metal standard. Provide concealed fasteners where possible, and set units true to line, levels, and slopes. Install work with laps, joints, and seams that are permanently watertight and weather resistant.
2. Roof Edge Flashing: Anchor to resist uplift and outward forces according to recommendations in SMACNA's "Architectural Sheet Metal Manual" and as indicated.
Interlock bottom edge of roof edge flashing with continuous cleat anchored to substrate at staggered 3-inch centers.
FOSM – 241749 075323 - 13
3. Copings: Anchor to resist uplift and outward forces according to recommendations in SMACNA's "Architectural Sheet Metal Manual" and as indicated.
a. Interlock exterior bottom edge of coping with continuous cleat anchored to substrate at 24-inch centers.
b. Anchor interior leg of coping with washers and screw fasteners through slotted holes at 24-inch centers.
4. Pipe or Post Counterflashing: Install counterflashing umbrella with close-fitting collar with top edge flared for elastomeric sealant, extending minimum of 100 mm (4 inches) over base flashing. Install stainless-steel draw band and tighten.
5. Counterflashing: Coordinate installation of counterflashing with installation of base flashing. Insert counterflashing in reglets and fit tightly to base flashing. Extend counterflashing 100 mm (4 inches) over base flashing. Install counterflashing to allow for a minimum 200 mm (8 inches) high base flashing detail typical. Secure in waterproof manner by means of snap-in installation and sealant or lead wedges and sealant unless otherwise notes.
a. Roof-Penetration Flashing: Coordinate installation of roof-penetration flashing with installation of roofing and other items penetrating roof. Seal with elastomeric or butyl sealant and clamp flashing to pipes that penetrate roof per manufacturer’s recommendations.
b. Coordinate with manufacturer’s with manufacturer’s standard requirements for counterflashing’s and note the 4 inch and 8 inch requirements listed above are minimum’s to be provided.
F. Cleaning and Protection:
1. Clean exposed metal surfaces of substances that interfere with uniform oxidation and weathering.
2. Clean off excess sealants.
3. Remove temporary protective coverings and strippable films as sheet metal flashing and trim are installed unless otherwise indicated in manufacturers written installation instructions. On completion of sheet metal flashing and trim installation, remove unused materials and clean finished surfaces as recommended by sheet metal flashing and trim manufacturer. Maintain sheet metal flashing and trim in clean condition during construction.
a. Replace sheet metal flashing and trim that have been damaged or that have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.
END OF SECTION