B09 - Amendment4Atch17M501_Rev1_0004.pdf

PDF 781 KB Posted

Attached to
Remove and Install a New HVAC unit. Federal contract opportunity
Solicitation number
140P6220B0002
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document contains a mechanical equipment schedule and related specifications for a federal contract project to replace the HVAC system at a National Park Service visitor center. Key equipment to be provided includes a new fluid cooler, natural gas boiler, heat pumps, energy recovery ventilators, pumps, and associated ductwork and piping. The project scope involves disconnecting the existing geothermal loop and replacing it with the new fluid cooler and boiler located near the maintenance building. Existing piping and heat pumps in the visitor center will also be replaced. Manufacturers are specified for major equipment such as heat pumps, fans, and pumps. Relevant details involving equipment capacities, electrical specifications, and connection requirements are included.

View the file

Other files for this federal contract opportunity

Other files attached to Remove and Install a New HVAC unit., newest first.
File Type Posted
B09 - Amendment5Attachment28_A301_0005.pdf PDF
B09 - Amendment5Attachment26_087100_0005.pdf PDF
B09 - Amendment5Attachment27_A101_0005.pdf PDF
B09 - Amendment5Attachment31_QandA_0005.pdf PDF
B09 - Amendment5Attachment25_075323_0005.pdf PDF
B09 - Amendment5Attachment30_S201_0005.pdf PDF
Sol_140P6220B0002_Amd_0005.pdf PDF
B09 - Amendment5Attachment29_S101_0005.pdf PDF
B09 - Amendment4Atch22UtilityDetails2000_0004.pdf PDF
B09 - Amendment4Atch24BrandNameJustification_0004.pdf PDF
B09 - Amendment4Atch15Section232500_0004.pdf PDF
Sol_140P6220B0002_Amd_0004.pdf PDF
B09 - Amendment4Atch13Parking_0004.pdf PDF
B09 - Amendment4Atch21LowerLevelFloorPlan2000_0004.pdf PDF
B09 - Amendment4Atch16M200_Rev1_0004.pdf PDF
B09 - Amendment4Atch14Section221429_0004.pdf PDF
B09 - Amendment4Atch23QuestionsandAnswers_0004.pdf PDF
B09 - Amendment4Atch20HVACPlanLowerLevel2000_0004.pdf PDF
B09 - Amendment4Atch18E103_Rev1_0004.pdf PDF
B09 - Amendment4Atch19HVACPipingPlans2000_0004.pdf PDF
Sol_140P6220B0002_Amd_0003.pdf PDF
Sol_140P6220B0002_Amd_0002.pdf PDF
140P6220B0002Amendment2Attachment_0002.pdf PDF
Base_B08 - SolicitationAtch4Pictures1.pdf PDF
Base_B08 - SolicitationAtch10OF17.pdf PDF
Base_B08 - SolicitationAtch5SubmittalList.pdf PDF
Base_B08 - SolicitationAtch7WageDetermination.pdf PDF
Base_Sol_140P6220B0002.pdf PDF
Base_B08 - SolicitationAtch3SenitiveAreaMap.pdf PDF
Base_B08 - SolicitationAtch9TechPic2.pdf PDF
Base_SolicitationAtch1Specifications06242020.pdf PDF
Base_B08 - SolicitationAtch11SF24BidBond.pdf PDF
Base_B08 - SolicitationAtch8TechPic1.pdf PDF
Amend_0001_Sol_140P6220B0002_Amd_0001.pdf PDF
Base_B08 - SolicitationAtch2Drawings.pdf PDF
Base_B08 - SolicitationAtch6CloseoutSubmittalList.pdf PDF
Base_B08 - SolicitationAtch12NoticetoContractorsCPARS.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FLOOR

HOT WATER BOILER

ET-1

STRAINER

AUTOMATIC

AIR VENT

AS-1

DRAIN VALVE

B-1

HPWS

HPWR

THERMOMETER (TYP)

P-1B

BELOW GRADE

TO VISITOR CENTER

B O

IL

E

R

O

O M

T O

W

N

C L

O S

U R

E

SEE DETAIL 5/M402

FOR PUMP

SPECIALITIES

P-1A

CT-1

SEE DETAIL 2/M402

FOR TOWER

CONNECTION

DETAIL

SEE DETAIL 3/M402

FOR AIR

SEPARATOR AND

EXPANSTIN TANK

CONNETIONS

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

241749

00000

FORT SMITH NATIONAL HISTORIC SITE

301 PARKER AVE

FORT SMITH, AR 72901C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

F O

S M a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

01/03/2020

07310.007

M501

SCHEDULE - MECHANICAL

07310007FOSM- 5- M501 SCHEDULE - MECHANICAL

NOTES: 1. UNIT TO HAVE MERV 8 FILTERS, BACNET CONTROL INTERFACE, AND MOTORIZED OUTDOOR AND RETURN AIR DAMPER

ERV-2 MECH 1,065 1/2 0.75 750 1/3 0.75 99.1/79.6 89.8/74.8 88.2/69.8 58% 14.7/11.9 34.5/29.6 41.9/40.3 67% 10.7 15.0 208 1 60 GREENHECK ECV-20H-FM 1

ERV-1 ATTIC 1,330 3/4 0.75 1,000 1/2 0.75 99.1/79.6 85.7/72.4 92.5/72.6 56% 17.4/11.9 43.3/36.4 31.1/30.9 64% 6.8 15.0 208 3 60 GREENHECK ECV-20H-FM 1

CFM

FAN POWER

(HP) ESP (IN WG) CFM

FAN POWER

(HP) ESP (IN WG)

O/A

DB / WB

SUPPLY DB

/ WB

EXHAUST

DB / WB

MIN TOTAL

EFFECT.

O/A

DB / WB

SUPPLY DB

/ WB

EXHAUST

DB / WB

MIN TOTAL

EFFECT. MCA MOCP VOLTS PH HZMARK LOCATION

VENTILATION AIR SIDE RELIEF AIR SIDE SUMMER PERFORMANCE WINTER PERFORMANCE ELECTRICAL DATA

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

ENERGY RECOVERY VENTILATOR SCHEDULE

INTERNAL REDUNDANCY, MULTIPE UNITS TO BE PROVIDED.

3. BOILER IS SIZED FOR FULL REDUNDANCY AT 1,000 MBH WITH ONE INTERNAL MODULE DOWN. IF ALTERNATE IS PROVIDED WITHOUT

2. PROVIDE WITH CONDENSATE NEUTRALIZER KIT.

NOTES: 1. PROVIDE WITH BAS INTERFACE.

B-1 BOILER ROOM CONDENSING 1,500 60 >95% 15:1 58 68 RIELLO AR1500 1-3

EWT (°F) LWT (°F)MARK LOCATION TYPE

INPUT MBH

(NAT GAS)

MAX BOILER

FLOW (GPM)

COMBUSTION

EFFICIENCY (%)

TURNDOWN

RATIO

WATERSIDE DATA BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

GAS FIRED HOT WATER BOILER SCHEDULE

3. PROVIDE WITH SOUND ATTENUATION PACKAGE WITH COMPRESSOR AND HEAT EXCHANGER VIBRATION ISOLATION, INSULATED COMPRESSOR ENCLOSURE, AND GASKETED UNIT CASING.

2. PROVIDE WITH BACNET CONTROL INTERFACE, HOT GAS REHEAT, DUCTED FILTER RACK, AND CONDENSATE OVERFLOW SENSOR.

NOTES: 1. EXISITNG HEAT PUMP UNITS TO HAVE NEW PIPING SPECIALITIES REPLACED AND HEAT EXCHANGER CLEANED PRIOR TO RECONNECTION TO NEW PIPING SYSTEM.

HP-15 OFFICE 300 25 0.5 1.4 1.8 86 102.2 8.8 7.3 11.4 12.4 0.76 68 55.5 11.1 8.7 4.56 208 1 5.23 15 TRANE GEHE009 2

HP-14 OFFICE 425 30 0.5 2.2 2.4 86 120.2 13.7 10.5 17.8 12.9 1.19 68 55.7 17.8 13.5 4.3 208 1 10.58 15 TRANE GEHE015 2

HP-13 OFFICE 400 25 0.5 1.8 1.8 86 102.3 11.4 9.5 14.7 13.2 0.97 68 55.7 14.3 11.1 4.7 208 1 8.58 15 TRANE GEHE012 2

HP-12 (E) ELV. MECH. 912 -- 0.7 5.4 2.9 86 100.8 32.4 23.5 40.2 16.8 2.27 68 55.3 43.9 34.2 5.5 208 3 15.25 20 EXISTING TRANE EXVF036

HP-11 OFFICE 575 30 0.5 2.7 3.1 86 102.7 17.4 13.9 22.5 13.0 1.5 68 55.5 21.7 16.9 4.4 208 1 14.1 20 TRANE GEHE018 2

HP-10 (E) BREAK ROOM 1,197 60 0.7 11.6 10.6 86 94.5 40.4 30.4 49.4 16.8 2.65 68 60.3 55.6 44.4 5.3 208 3 20.9 30 EXISTING TRANE EXHF042 1

HP-9 OFFICE 570 50 0.7 5.0 9.2 86 95.0 17.6 13.9 22.4 13.0 1.4 68 60.8 22.9 18.0 4.47 208 1 14.1 20 TRANE GEHE018 2

HP-8 (E) OFFICE 912 20 0.7 7.2 4.2 86 97.2 33.0 24.0 40.5 17.0 2.2 68 58.3 44.5 34.9 5.4 208 3 15.25 20 EXISTING TRANE EXHF036 1

HP-7 (E) LIBRARY 570 120 0.6 4.0 3.78 86 97.4 18.6 14.5 22.9 16.7 1.24 68 58.5 23.9 18.9 5.1 208 1 13.5 20 EXISTING TRANE EXHF018 1

HP-6 (E) OFFICE 570 20 0.6 4.0 3.78 86 97.4 18.6 14.5 22.9 16.7 1.24 68 58.5 23.9 18.9 5.1 208 1 13.5 20 EXISTING TRANE EXHF018 1

HP-5 EXHIBIT 9,000 450 0.5 87.5 18.3 86 94.8 319.8 240.3 382.8 13.9 22.73 68 61.3 366.4 294.4 4.3 208 3 122.83 150 TRANE GEVE300 2-3

HP-4 (E) EXHIBIT 6,400 500 0.6 40.0 7.5 86 101.1 251.1 183.5 302.8 15.1 19.39 68 57.5 263.3 210.3 4.6 208 3 81.73 110 EXISTING TRANE GEVE240 1

HP-3 LOBBY 3,500 615 0.6 35.0 27.1 86 94.4 124.2 91.9 147.3 14.5 8.18 68 61.7 134.2 109.6 4.5 208 3 40.9 50 TRANE GEVE120 2

HP-2 AV 2,400 600 0.45 9.0 12.1 86 106.6 75.9 61.2 92.8 15.2 5.89 68 53.7 79.4 64.2 4.6 208 3 26.7 35 TRANE GEVE072 2

HP-1 JAIL 2,900 465 0.35 26.3 18.9 86 94.6 94.4 73.8 112.6 15.1 6.26 68 61.6 102.2 84.3 4.5 208 3 31.8 45 TRANE GEVE090 2

EWT (°F) LWT (°F)

TOTAL CAP

(MBTUH)

SENSIBLE

CAP

(MBTUH)

HT REJ

(MBTUH) AHRI EER

TOTAL

POWER

(KW) EWT (°F) LWT (°F)

TOTAL CAP

(MBTUH)

HT ABS

(MBTUH) AHRI COP VOLTS PH

MIN CIRC

AMPS

MAX FUSE

AMPS

BASIS OF DESIGN

MANUFACTURER AND MODEL

NUMBER REMARKSMARK SERVES

SUPPLY

AIR (CFM)

OUTDOOR

AIR (CFM)

ESP (IN.

W.G.)

FLOW

RATE

(GPM)

PRESS.

DROP (FT

WATER)

COOLING DATA HEATING DATA ELECTRICAL DATA

WATER SOURCE HEAT PUMP SCHEDULE

3. CONTRACTOR TO CONFIRM SIZE OF EXISTING OPENING PRIOR TO ORDERING.

2. LOUVER TO BE PAINTED TO MATCH ADJACENT CONSTRUCTION.

NOTES: 1. PROVIDE WITH BIRSCREEN.

L-1 ERV-2 ALUMINUM 750 0.1 36 22 6 PRIMER GREENHECK ESD-635 1-3

W H DMARK SERVES MATERIAL CFM

MAX SP (IN

WG)

SIZE (INCHES)

FINISH

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

LOUVER SCHEDULE

NOTES: 1. UNIT WEIGHS 362 LBS. DEVICE TO BE SUPPORTED INDEPENDENT OF DUCT FROM FLOOR BELOW WITH UNISTRUT STAND.

DS-1 DUCT SILENCER HP-5 MEZZANINE 4,500 CFM,0.05 IN WG APD -- KINETICS 24-KCCS-F-4-B2-48 1

ET-1 EXPANSION TANK HOT WATER SYSTEM BOILER RM SYSTEM GALLONS = 640, TEMP. RANGE = 50°F -- TACO CBX-84

AS-1 AIR SEPARATOR HOT WATER SYSTEM BOILER RM 240 GPM @ 2.0 FT WAT PD -- SPIROTHERM VDT400

MARK FUNCTION SERVES LOCATION OPERATING CONDITIONS CAPACITY AND MOTOR HP

BASIS OF DESIGN MANUFACTURER

AND MODEL NUMBER REMARKS

MISCELLANEOUS MECHANICAL EQUIPMENT SCHEDULE

4. PROVDIE WITH PIGGYBACK FLOAT SWITCH.

3. PROVIDE 24" X 30" POLYETHYLENE BASIN. WITH AIR TIGHT COVER.

2. PROVDIE WITH SUCTION DIFFUSER.

NOTES: 1. PROVIDE WITH INVERTER DUTY MOTOR AND SHAFT GROUNDING RING.

SP-1 BOILER RM SAN SUMP PUMP 57 25 --- 3,450 1/2 115 1 60 ZOELLER M163 3-4

P-1A/B BOILER RM HPWS/R END SUCTION 240 140 78 1760 15 208 3 60 TACO CI2506D 1-2

RPM HP VOLTS PH HZMARK LOCATION SERVES TYPE FLOW GPM

HEAD FT

WG MIN % EFF

ELECTRICAL DATA BASIS OF DESIGN

MANUFACTURER AND MODEL

NUMBER REMARKS

PUMP SCHEDULE

NOTES: 1. GRILLLE TO BE INSTALLED ON EACH SIDE OF DOOR. INSTALL GRILLE IN BOTTOM HALF OF DOOR.

R-1 RETURN GRILLE 30X24 30X24 WHITE 0.05 NA CT-700L 1

S-1 SUPPLY DIFFUSER 24X24 SEE PLAN WHITE 0.1 25 TMSA

MARK SERVES TYPE

FACE SIZE

(IN.)

NECK SIZE

(IN.) FINISH

MAX PD (IN

WG)

MAX NC AT

PD SHOWN

TITUS MODEL

NUMBER REMARKS

DIFFUSER, REGISTER AND GRILLE SCHEDULE

3. TOWER TO HAVE COPPER COIL AND BASIN HEATER.

2. TOWER HAS (2) FANS POWERED BY SINGLE MOTOR.

NOTES: 1. FAN AND PUMP VFD SUPPLIED BY ELECTRICAL CONTRACTOR.

CT-1 GRADE HPWS/R 47,280 WATER 240 98.0 86.0 5.6 79.0 143 7.5 3 208 3 60 MARLEY MHF7103 1-3

FAN HP PUMP HP VOLT PH HZMARK LOCATION SERVES FAN CFM FLUID

FLUID FLOW

(GPM) EWT (°F) LWT (°F)

MAX PD

(PSI)

WET BULB

TEMP (°F)

TOTAL

CAPACITY

(MBH)

ELECTRICAL

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

CLOSED CIRCUIT COOLLING TOWER SCHEDULE

2. WALL HYDRANT TO HAVE INTEGRAL VACUUM BREAKER.

NOTES: 1. FLOOR SINK TO HAVE BOTTOM DOME STRAINER.

WH-1 WALL HYDRANT -- 3/4" -- -- -- 24" A.F.F. -- WOODFORD 65 2

FS-1 FLOOR SINK -- -- SEE PLANS 2" -- FLOOR -- ZURN Z1926 1

HOT

WATER

COLD

WATER WASTE VENT OTHER FIXTURE ACCESSORY #1 REMARKSMARK DESCRIPTION

FIXTURE CONNECTIONS

MOUNTING HEIGHT FLOW RATE

BASIS OF DESIGN MANUFACTURER AND MODEL NUMBER

PLUMBING FIXTURE SCHEDULE

NOTES: 1. PROVIDE WITH SURFACE MOUNT FRAME AND INTEGRAL THERMOSTAT AND DISCONNECT.

EWH-1 BOILER ROOM 6,825 2.0 208 1 60 12" BERKO FRC4020F 1

BTUH KW VOLTS PH HZMARK LOCATION

HEATER ELECTRICAL DATA

RECOM'D MOUNTING

HEIGHT

BASIS OF DESIGN

MANUFACTURER AND

MODEL NUMBER REMARKS

ELECTRIC UNIT HEATER SCHEDULE

PRODUCT MANUFACTURERS LISTED ON EQUIPMENT SCHEDULES

ARE THE BASIS OF DESIGN AND INDICATE MINIMUM SYSTEM

PERFORMANCE REQUIREMENTS. SEE MECHANICAL SPECIFICATIONS

FOR EQUIPMENT MANUFACTURER EQUALS AND EQUIPMENT AND

PRODUCT SALIENT CHARACTERISTICS.

SCALE: NOT TO SCALE

MECHANICAL SYSTEM ONE-LINE

DATE INITIAL

08/06/2020 ARP

140P6220B0002 Attachment 17 Amendment 4

Sheets
M501 - SCHEDULE - MECHANICAL