Remove and Install a New HVAC unit. Federal contract opportunity
Solicitation number
140P6220B0002
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document includes plans and specifications for a federal construction contract opportunity. The project involves removing and replacing the HVAC system at Fort Smith National Historic Site Visitor Center in Fort Smith, Arkansas. Work will disconnect the existing geothermal piping loop and replace it with a new fluid cooler and natural gas boiler near the Maintenance Building. The existing piping within the Visitor Center will also be replaced as indicated in the drawings. The existing heat pumps and an attic ductless split system will be replaced with new units. Energy recovery ventilators will additionally be installed. The solicitation number for this project is 140P6220B0002 and is being issued by the National Park Service Midwest Region of the Department of the Interior.

View the file

Other files for this federal contract opportunity

Other files attached to Remove and Install a New HVAC unit., newest first.
File Type Posted
B09 - Amendment5Attachment27_A101_0005.pdf PDF
B09 - Amendment5Attachment31_QandA_0005.pdf PDF
B09 - Amendment5Attachment25_075323_0005.pdf PDF
B09 - Amendment5Attachment28_A301_0005.pdf PDF
B09 - Amendment5Attachment26_087100_0005.pdf PDF
B09 - Amendment5Attachment30_S201_0005.pdf PDF
Sol_140P6220B0002_Amd_0005.pdf PDF
B09 - Amendment5Attachment29_S101_0005.pdf PDF
B09 - Amendment4Atch13Parking_0004.pdf PDF
B09 - Amendment4Atch21LowerLevelFloorPlan2000_0004.pdf PDF
B09 - Amendment4Atch17M501_Rev1_0004.pdf PDF
B09 - Amendment4Atch14Section221429_0004.pdf PDF
B09 - Amendment4Atch22UtilityDetails2000_0004.pdf PDF
B09 - Amendment4Atch24BrandNameJustification_0004.pdf PDF
B09 - Amendment4Atch15Section232500_0004.pdf PDF
Sol_140P6220B0002_Amd_0004.pdf PDF
B09 - Amendment4Atch23QuestionsandAnswers_0004.pdf PDF
B09 - Amendment4Atch20HVACPlanLowerLevel2000_0004.pdf PDF
B09 - Amendment4Atch18E103_Rev1_0004.pdf PDF
B09 - Amendment4Atch19HVACPipingPlans2000_0004.pdf PDF
Sol_140P6220B0002_Amd_0003.pdf PDF
Sol_140P6220B0002_Amd_0002.pdf PDF
140P6220B0002Amendment2Attachment_0002.pdf PDF
Base_B08 - SolicitationAtch3SenitiveAreaMap.pdf PDF
Base_B08 - SolicitationAtch9TechPic2.pdf PDF
Base_SolicitationAtch1Specifications06242020.pdf PDF
Base_B08 - SolicitationAtch11SF24BidBond.pdf PDF
Base_B08 - SolicitationAtch4Pictures1.pdf PDF
Base_B08 - SolicitationAtch10OF17.pdf PDF
Base_B08 - SolicitationAtch5SubmittalList.pdf PDF
Base_B08 - SolicitationAtch7WageDetermination.pdf PDF
Base_Sol_140P6220B0002.pdf PDF
Base_B08 - SolicitationAtch8TechPic1.pdf PDF
Amend_0001_Sol_140P6220B0002_Amd_0001.pdf PDF
Base_B08 - SolicitationAtch2Drawings.pdf PDF
Base_B08 - SolicitationAtch6CloseoutSubmittalList.pdf PDF
Base_B08 - SolicitationAtch12NoticetoContractorsCPARS.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M200

4" HPWS/R

BELOW

GRADE

M201

G

APPROXIMATE LOCATION OF

EXISTING CONDUIT BETWEEN

VISITOR CENTER AND

MAINTENANCE BUILDING

SITE PAVEMENT AND

LANDSCAPE SHOWN

FOR REFERENCE ONLY.

NOT TO SCALE.

1 1/2"

1"

EXISTING 10"

SEWER

M200

EXISTING 4"

STORM

1 1/2"

EXISTING

MAINTENANCE

BUILDING

B-1

CT-1

1"

P-1B

P-1A

FS-1

FS-1

G

3 44

WH-1

ET-1

AS-1

BOILER SHED

4"4"

1"

4"

3"3"

1" 4"

4"

1 1/2"

4"

EWH-1

2"

2"

3" VTR

4"

NATURAL GAS PIPE SIZING BASED

ON 2006 IFGC TABLE 402.4(3) FOR 2

PSI PRESSURE WITH 1.0 PSI

PRESSURE DROP. TOTAL

DEVELOPED LENGTH OF 150 FEET.

SP-1

FS-1

1 1/2"

4"

BACKFILL

M

IN

IM

U

M

TRACER TAPE/WIRE

(TYPICAL OF 2)

INSULATED HEAT PUMP

SUPPLY/RETURN MAIN

BEDDING MATERIAL

(SEE SPECS)

MINIMUM 12"MINIMUM 6" MINIMUM 6"

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

241749

00000

FORT SMITH NATIONAL HISTORIC SITE

301 PARKER AVE

FORT SMITH, AR 72901C

U s e rs \a p u llm a n n

\D o c u m e n ts \R e v it te m p

\T S

A -M

E C

H

R

F O

S M a p u llm a n n

L T

M M

V .r v t

ARP

ARP

BGJ

01/03/2020

07310.007

M200

SITE PIPING PLAN -

MECHANICAL

07310007FOSM- 5- M200 SITE PIPING PLAN - MECHANICAL

SCALE: 1" = 30'-0"

SITE PLAN - HVAC PIPING

REF. NOTES ( ):X

1 1" DCW TAP OFF EXISTING 2" WATER SERVICE. INSTALL PIPING AS HIGH

AS POSSIBLE FROM EXISTING WATER SERVICE TO NEW MECHANICAL

ROOM.

2 EXTEND GAS PIPING FROM EXISTING SERVICE TO NEW BOILER.

COORDINATE WITH UTILITY TO PROVIDE NEW METER AS REQUIRED TO

ACCOMMODATE ADDITIONAL GAS LOAD.

3 CPVC BOILER FLUE AND VENT UP THROUGH ROOF.

4 PROVIDE 4" HOUSEKEEPING PAD BELOW EQUIPMENT. SEE DETAIL 1/M401.

5 HPWS/R DOWN BELOW GRADE TO VISITOR CENTER MECHANICAL ROOM.

6 RELOCATE EXISTING CONDENSING UNITS TO NEW MECHANICAL

ENCLOSURE. PROVIDE NEW REFRIGERANT LINE SETS AND CONTROL

WIRING BETWEEN CONDENSING UNIT AND INDOOR UNIT. PROVIDE 4"

CONCRETE PAD BELOW UNITS, SEE DETAIL 1/M401

7 TOWER LOCATED ON 16" CONCRETE PAD. SEE STRUCTURAL FOR

CONSTRUCTION DETAILS.

8 REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK TO NEAREST

JOINT AS REQUIRED TO CONSTRUCT NEW PIPING. NEW CONCRETE TO

MATCH EXISTING FINISH.

9 REMOVE AND REPLACE FORT WALL SANDSTONE MARKER BACK TO JOINT

AS REQUIRED TO CONSTRUCT NEW PIPING.

10 2" TOWER DRAIN AND 2" OVERFLOW PIPING TO AREA DRAIN. AREA DRAIN

TO BE CONNECTED TO EXISTING STORM DRAIN PIPING.

11 SITE WORK TAKES PLACE IN ARCHEOLOGY SENSITIVE AREA. WORK TO

BE MONITORED BY NPS PERSONNEL.

12 SEE ELECTRICAL PLANS FOR BOILER SHUTDOWN SWITCH LOCATIONS.

COORDINATE WITH ELECTRICAL CONTRACTOR FOR INSTALLATION.

13 CONTRACTOR TO BACKFILL ALL DISTURBED AREAS INTO EXISTING

GRADE. SEED ALL DISTURBED LANDSCAPES WITH MIX APPROVED BY

PARK. MULCH ALL SEEDED AREAS WITH CLEAN STRAW FREE OF

NOXIOUS WEEDS AND OTHER HARMFUL MATERIAL.

14 PIPE SUMP PUMP OUTLET TO UTILITY SINK IN HALL. PIPE TO HAVE 1%

SLOPE TO OUTLET. PROVIDE MINIMUM 1" AIR GAP AT TERMINATION

15 CONNECT NEW STORM DRAIN TO EXISTING PIPE SERVICING EXISTING

ROOF DRAINS ON PERIMITER OF BUILDING.

SCALE: 1/4" = 1'-0"

MECHANICAL ENCLOSURE PLAN - HVAC PIPING

PLAN

NORTH

TRUE

NORTH

SCALE: NOT TO SCALE

HEAT PUMP PIPE TRENCH DETAIL

DATE INITIAL

08/06/2020 ARP

140P6220B0002 Attachemnt 16 Amendment 4

Sheets
M200 - SITE PIPING PLAN - MECHANICAL