A4_-_mammoth_cave_as-builts_0002.pdf
PDF 4 MB Posted
- Attached to
- MACA-UPGRADE INADEQUATE VC HVAC CONTROLS Federal contract opportunity
- Solicitation number
- 140P5325Q0015
About this file
These are technical design and control system drawings for the Mammoth Cave National Park Visitor's Center - Phase Two project located in Mammoth Cave, Kentucky. The documents detail the temperature control, network architecture, installation details, and mechanical system configurations for the facility's HVAC infrastructure, including:
Key technical specifications include multiple air handling units (AHU-1, AHU-2), fan coil units (FCU), variable air volume (VAV) terminal units, chilled water systems, and control network architecture. The drawings cover detailed wiring diagrams, controller configurations, device schedules, valve and damper specifications, and sequence of operations for various HVAC components. The project involves upgrading and expanding the existing HVAC control systems, with specific focus on temperature management, air circulation, and building environmental control across the main floor, attic, and basement levels of the visitor center.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A5_-_Questions_and_Answers_0002.pdf | ||
| Sol_140P5325Q0015_Amd_0002.pdf | ||
| A3_-_042525_MAC_VC_HVAC_Contractor_Site_Visit_0002.pdf | ||
| Sol_140P5325Q0015_Amd_0001.pdf | ||
| Sol_140P5325Q0015.pdf | ||
| Statement_of_Work.pdf | ||
| DOL_Wage_Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAMMOTH CAVE NATIONAL PARK
VISITOR'S CENTER - PHASE TWO
MAMMOTH CAVE, KENTUCKY
Consulting
Engineer:
Architect:
Mechanical
Contractor:
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PROFESSIONAL MECHANICAL CONTRACTORS, INC.
ASHEVILLE, NC
AF
MIKE BERGER
1271 6/15/10
TC01
Page No.:
Total Project Pages:
Date:ECT Services Job Number:
Engineer :
CADD Design:
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
DATE INITIALS REVISION TYPE
A
9/2/10 AF ENGINEERING CHANGES
B
8/9/12 C2M REVISED AS-BUILT
C
D
SINCE 1981
TEMPERATURE CONTROL DRAWINGS
PAGE
NUMBER
DESCRIPTION
TEMPERATURE CONTROL DRAWINGS
PAGE
NUMBER
DESCRIPTION
NOTE:
THIS JOB IS AN EXTENSION
OF PHASE-I.
ECT JOB # 1061
B
REV.
B
REV.
B
REV.
Installation responsibilities
Mechanical Contractor shall be responsible for installing control valves, immersion temperature sensor wells, water differential pressure switches, water pressure sensors, water flow meters, etc.
These devices shall be provided to the mechanical contractor for installation. TC Installer will be responsible for all wiring on these devices.
Sheet Metal Contractor shall be responsible for installing control dampers, airflow measuring stations, etc. These devices shall be provided to the sheet metal contractor for installation. TC Installer will be responsible for mounting actuators and all wiring on these devices.
MS/TP
TECHNOLOGIES, INC.
R
MS/TP
TECHNOLOGIES, INC.
R
MS/TP
TECHNOLOGIES, INC.
R wht blk shield shield shield shield
22/2 22/2 wht wht blk blk blk wht o h m o h m
INSTALL 120 OHM END OF LINE
RESISTOR AS SHOWN ON FIRST
AND LAST CONTROLLER IN EACH
NETWORK TRUNK. SEE NETWORK
RISER DIAGRAM FOR ADDITIONAL
DETAILS.
INSTALL 120 OHM END OF LINE
RESISTOR AS SHOWN ON FIRST
AND LAST CONTROLLER IN EACH
NETWORK TRUNK. SEE NETWORK
RISER DIAGRAM FOR ADDITIONAL
DETAILS.
FIRST CONTROLLER
IN NETWORK TRUNK
TYPICAL CONTROLLER
LAST CONTROLLER
IN NETWORK TRUNK
NETWORK WIRING DETAIL
W
C
MOUNT SPACE TEMPERATURE SENSORS
AT 48" ABOVE FINISHED FLOOR.
CONFIRM MOUNTING HEIGHT WITH
CONSTRUCTION MANAGER.
FIELD VERIFY ALL SPACE
TEMPERATURE SENSOR
MOUNTING LOCATIONS
WITH CONSTRUCTION
MANAGER.
SPACE TEMPERATURE SENSOR INSTALLATION DETAILS
ST
1. USE ORANGE (PLENUM RATED, 2-CONDUCTOR, 22 GAUGE,
TWISTED SHIELED) WIRE FOR ALL NETWORK WIRING.
2. LAND SHIELD TO CHASSIS GROUND ONLY AT ONE POINT IN
NETWORK TRUNK. ALL OTHER SHIELDS SHOULD BE TIED
TOGETHER AND PROTECTED WITH ELECTRICAL TAPE.
ANY CAPILARY ENTRY INTO DUCT WORK MUST BE PROTECTED FROM THE CUT AWAY SECTION
OF DUCT. PROTECTION CAN BE ACCOMPLISHED WITH PLASTIC TUBING, RUBBER GROMMET OR
BUSHINGS. TO ELIMINATE RUBBING AND WEAR OF THE ELEMENT OR CAPILLARY IN A DUCT WITH
A LOT OF AIR MOVEMENT, ANCHOR THE ELEMENT AT ADDITIONAL POINTS.
FOR LOW LIMIT INSTALLATIONS ALWAYS BEGIN THE INSTALLATION OF CAPILLARY AT THE TOP
OF COIL (WITHIN 6") AND THEN MAKE CALCULATIONS TO DETERMINE HEIGHT OF SERPENTINE TO
COMPLETE THE INSTALLATION TO BOTTOM OF COIL. IF MORE THAN ONE LOW LIMIT IS
SPECIFIED, MOUNT ADDITIONAL LOW LIMIT ELEMENTS SO COIL SURFACE AREA IS DIVIDED
EQUALLY AMONG ALL LOW LIMIT THERMOSTATS.
AVERAGING TEMPERATURE SENSOR INSTALLATION DETAIL
LOW LIMIT THERMOSTAT INSTALLATION DETAIL
NOTICE
Any points or sequences shown in control specification will be limited to the capabilities of the factory controls that are supplied with the equipment.
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-0.2
INSTALLATION DETAILS
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
AREA SERVED: AHU-1
CONTROLLER TYPE: 1188
DEVICE INSTANCE: 1001
PANEL
LOCATION: TCP-01
AREA SERVED: AHU-1
CONTROLLER TYPE: 1600
DEVICE INSTANCE: 1002
PANEL
LOCATION: TCP-01
AREA SERVED: CW SYSTEM
CONTROLLER TYPE: 660
DEVICE INSTANCE: 1003
PANEL
LOCATION: TCP-01
AREA SERVED: ROOMS 112, 114, 116
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1004
CONFIG: VAV
AREA SERVED: ROOMS 114, 116
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1005
CONFIG: FCU
AREA SERVED: GREAT HALL
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1006
CONFIG: VAV
AREA SERVED: GREAT HALL
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1007
CONFIG: FCU_2
AREA SERVED: GREAT HALL
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1008
CONFIG: VAV
AREA SERVED: GREAT HALL
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1009
CONFIG: FCU
AREA SERVED: GREAT HALL
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1010
CONFIG: VAV
AREA SERVED: GREAT HALL
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1011
CONFIG: FCU
AREA SERVED: GREAT HALL
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1012
CONFIG: VAV
AREA SERVED: GREAT HALL
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1013
CONFIG: FCU_2
AREA SERVED: ROOMS 101, 102,
103, 123
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1014
CONFIG: FCU
AREA SERVED: ROOMS 105, 106,
108, 109
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1015
CONFIG: FCU
AREA SERVED: ROOMS 112, 116
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1016
CONFIG: FCU
AREA SERVED: GREAT HALL
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1017
CONFIG: VAV
AREA SERVED: MECH/ELEC 111
CONTROLLER TYPE: VAVI-SD
DEVICE INSTANCE: 1018
CONFIG: VAV_HEAT
JACE 403
DEVICE INSTANCE: 1000
LAPTOP COMPUTER
SUPPLIED BY
ECT SERVICES
DESKTOP COMPUTER
SUPPLIED BY
ECT SERVICES
PRINTER SUPPLIED
BY ECT SERVICES
REQ.: 1200 X 12OO DPI RESOLUTION
MIN. CAP. 250 SHEETS
MIN. 120 CHARACTERS / SECOND
CHILLER
TRANE LON INTERFACE
BOARD
MAMMOTH CAVE
VISITOR'S CENTER
LAN
LOCATED IN IDF ROOM 113
JACE 120V POWER FED FROM
PANEL RP2 - CIRCUIT #20
BLUE 22/2
NON-SHIELDED
ECHELON CABLE
TERMINATES ON TB-J3 1 & 2
IN CHILLER
END OF LINE
RESISTOR
(120 OHM)
END OF LINE
RESISTOR
(120 OHM)
AREA SERVED: BOOKSTORE 130
EXHAUST
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1022
CONFIG: VAV2
AREA SERVED: MECH. ROOM 201
CONTROLLER TYPE: VLC-1188
DEVICE INSTANCE: 1046
CONFIG: AHU2a
AREA SERVED: MECH. ROOM 201
CONTROLLER TYPE: VLC-1600
DEVICE INSTANCE: 1021
CONFIG: AHU2b
AREA SERVED: CW SYSTEM
CONTROLLER TYPE: 444
DEVICE INSTANCE: 1045
LOCATION: TCP-01
AREA SERVED: STORAGE 132
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1023
CONFIG: FCU
AREA SERVED: BOOKSTORE 130
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1024
CONFIG: FCU
AREA SERVED: FCU-15, 16
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1025
CONFIG: VAV2
AREA SERVED: MECH. ROOM 201
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1026
CONFIG: FCU
AREA SERVED: FCU-17, 18
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1027
CONFIG: VAV2
AREA SERVED: SHIFT OFFICE 124
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1028
CONFIG: FCU
AREA SERVED: BASEMENT & SHIFT
OFFICE 124 EXHAUST
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1030
CONFIG: VAV2
AREA SERVED: BASEMENT
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1031
CONFIG: VAV2
AREA SERVED: FCU-22, 23
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1032
CONFIG: VAV2
AREA SERVED: EXHIBIT 133 SE
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1033
CONFIG: FCU
AREA SERVED: MANAGER 127
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1029
CONFIG: FCU
AREA SERVED: EXHIBIT 133 SW
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1034
CONFIG: FCU_CO2
AREA SERVED: GALLERY 129
EXHAUST
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1035
CONFIG: VAV2
AREA SERVED: FCU-19, 20, 21
CONTROLLER TYPE: VAViH-SD
DEVICE INSTANCE: 1036
CONFIG: VAV2
AREA SERVED: GALLERY 129
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1037
CONFIG: FCU
AREA SERVED: EXHIBIT 133 NE
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1038
CONFIG: FCU_CO2
AREA SERVED: EXHIBIT 133 NW
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1039
CONFIG: FCU
AREA SERVED: ELEV. MACH.
ROOM 010
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1040
CONFIG: FCU_HEAT
AREA SERVED: WILD CAVE TOUR
STG. 002
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1041
CONFIG: FCU_HEAT
AREA SERVED: BREAK ROOM 003
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1042
CONFIG: FCU
AREA SERVED: STAFF WK. AREA 004
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1043
CONFIG: FCU
AREA SERVED: LIBRARY 005
CONTROLLER TYPE: VLC-651
DEVICE INSTANCE: 1044
CONFIG: FCU
AREA SERVED: MECH/ELEC 111
CONTROLLER TYPE: 651
DEVICE INSTANCE: 1019
CONFIG: FCU
AREA SERVED: MECH ROOM 111
CONTROLLER TYPE: VIEWPORT
DEVICE INSTANCE: 1020
DATE INITIALS REVISION TYPE
A
8/9/12 C2M CHANGED DEVICE TYPES AS-BUILT
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-0.3
NETWORK ARCHITECTURE
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
REV.
A
DATE INITIALS REVISION TYPE
8/9/12 C2M CHANGED DEVICE TYPES AS-BUILT
B
C
D
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-0.4
NETWORK DEVICES
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
A
REV.
A
REV.
A
REV.
**CABLE #
22-4 SH.
RED
**NOTE:
SEE AHU CONTROLLER PAGE
FOR WIRING OF CONTROLLER I/O
(SAME CABLES)
GRN
GRN
GRN
RED
**CABLE #
22-4 SH.
GRN
**CABLE #
22-4 SH.
RED
GRN
CABLE #
22-4 SH.
R2
V-100
CABLE #
22-4 SH.
R3
V-100
RED
RED
RED
**CABLE #
18-3 SH.
**CABLE #
18-3 SH.
**CABLE #
18-3 SH.
RED
RED
**SEE NOTE
**SEE NOTE
**SEE NOTE
**SEE NOTE
**SEE NOTE
**SEE NOTE
V
C
BLU
HOT
R1
R2
R3
BRN
COM
R1
10 16
R2
10 16
R3
P A
N E
L
P
O W
E R
T R
A N
S F
O R
M E
R
WHITE
TERM. BLOCKS
GRAY
TERM. BLOCKS
BLACK
TERM. BLOCKS
RED
TERM. BLOCKS
BLU - 24V HOT
BRN - 24V COM
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-0.5
AHU SAFETY CIRCUIT
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
Mechanical/Electrical Room 111
CHILLED WATER CONTROL
Enable
Setpoint
Call for Pumps
LON LON
Air-Cooled Chiller
CWP-1
Start/Stop
Status
Current
CWP-2
Start/Stop
Status
Current
Temp
TS-2104-GH-10
Temp
TS-2104-GH-10
To Phase 1
Equipment
From Phase 1
Equipment
To Phase 2
Equipment
From Phase 2
Equipment
2-Way Valve
LRB24-SR
A B
A
C
C
Typical
Phase 2
Coil &
Valve
C
C
Typical
Phase 1
Coil &
Valve
C
C
CRU-1
w/ Factory
Valve
Check
Valve
New CP-1
Start/Stop
Status
Revised
CRU-1 Piping
Note:
Refer to Job #1061 for Phase 1 of this project.
New (Phase 2)
Loop DP
V-PWXX04S
A
H
L
DATE INITIALS REVISION TYPE
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-1.1
CHW SYSTEM LAYOUT
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
EXISTING VLC-651
CONFIG Chilled_Water_System
DEVICE 1003 LOCATED IN TCP-01
UNIVERSAL
INPUTS
IN00
Chilled Water Supply Temp
IN01
Chilled Water Return Temp
IN02 CWP-1 Status
IN03 CWP-2 Status
IN04 CHILLER CALL FOR CWP PUMPS
IN05
BO00 CWP-1 S/S
BO01 CWP-2 S/S
BO02 CHILLER START/STOP
BO03 FOR FUTURE USE
BO04 FOR FUTURE USE
BO05 CHILLER SETPOINT
POINT DESCRIPTION
BINARY
OUTPUTS
POINT DESCRIPTION
CHILLED WATER
SUPPLY TEMP
WHT
CABLE #44
08 IN00
COM
BLK
22-2 SH.
TS-2104-GH-10-AA
CHILLED WATER
RETURN TEMP
WHT
CABLE #45
10 IN01
COM
BLK
22-2 SH.
TS-2104-GH-10-AA
RED
CABLE #50
11 IN02
COM
GRN
22-4 SH.
OUT
COM
V-H908
CWP-1 STATUS
V-H908
RED
CABLE #51
13 IN03
COM
GRN
22-4 SH.
OUT
COM
V-H908
CWP-2 STATUS
V-H908
WHT
14 IN04
COM
BLK
WHT
16 IN05
COM
BLK
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
23+
23+
24-
24-
WHT
WHT
BLK
BLK
WHT
CABLE #50
BO00 21
COM
BLK
22-4 SH.
R
CWP-1 S/S
V-100 N.O.
V-100_NO
WHT
CABLE #51
BO01 23
COM
BLK
22-4 SH.
R
CWP-2 S/S
V-100 N.O.
V-100_NO
BO02 25
COM
BO03 03
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO04 05
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
* NOTE:
FOR TRANSFORMER
DETAIL SEE TC03
24V COM 24 VAC
ERG
K
O R
5T E I S
L D
PE
N
E N
E
T R
0 5
I M
U N
Q P
E
MEANA
Y
M
GE NT
A
M P
M
X
HIGHHIGH
CAUTIONCAUTION
VOLTAGEVOLTAGE
R
BO2
7 8
BO1
R
BO0
R
64 531 2
OFF
MAC ADDRESSMAC ADDRESS
0.5A MAX
24VAC
GND
BO 3
COM
AO 0
BO 4
COM
IN 1
COM
COM
IN 3
IN 2
IN 0 / MSET
24VAC LOADS
POWER:
MOUNTING
ONLY
MADE IN USA
24VDC SOURCES 150mA
MAX LOAD - 40VA
NO BO'S - 10VA
FOR INDOOR USE ONLY
SUITABLE FOR PLENUM
USE COPPER CONDUCTORS
CLASS 2 WIRING DEVICE
FUSE, AGC-4 AMP FAST
120VAC @ 15A
240/277VAC @ 10A
120VAC 1HP
MOTOR LOAD -
RELAY RATINGS:
277VAC 3/4HP
240VAC 2HP
MS/TP
COM
IN 5
IN 4
24VDC
DATA
DATA
BACnet
250 OHM, 1% RESISTOR
ACROSS INPUT AND COM
SW1 = VLC MAC ADDRESS
4-20mA INPUTS REQUIRE
-1
-4
-7
R
BO3
BO4
R
R
STATUSSTATUS
(12FLA)
(6.9FLA)
(15FLA)
GENERAL PURPOSE -
24V COM
AO00 06
BLK
WHT
CABLE 55
18-2 SH.
WHT
CABLE #52
BLK
22-2 SH.
R
V-100 N.O.
CHILLER START/STOP
PANEL: 1TB3
V-100_NO
CHILLER SETPOINT
(FIELD VERIFY)
CHILLER SETPOINT CONNECTION NOT
AVAILABLE (IU2 OPTIONS MODULE REQUIRED)
[CABLE PULLED BUT NOT USED]
UNUSED
SPARE TERMINALS
NOT BEING USED
CABLE #00
22-4 SH.
CHILLER CALL FOR
CWP PUMPS
PANEL: 1TB4
FOR FUTURE USE
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-1.2
EXISTING CHW DEVICE 1003
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
01 IN00
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
RED
03 IN01
COM
GRN
RED
GRN
(* OTHER CONDUCTORS USED)
H535NS
06 IN03
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
23+
23+
24-
24-
WHT
WHT
BLK
BLK
BO00 27
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
WHT
BO01 29
COM
BLK
R
H535NS
WHT
BLK
LINE
LOAD
(* OTHER CONDUCTORS USED)
BO02 30
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO03 32
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
AO00 40
24V COM
24VAC
WHT
RED
BLK
AO01 42
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
AO02 43
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
AO03 45
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BLK
WHT
04 IN02
COM
Chilled Water Loop
Differential Pressure
24VAC
RED
V-PWLX04S
DATE INITIALS REVISION TYPE
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-1.3
NEW CHW DEVICE 1045
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
TCP-01 LAYOUT
LOCATED IN MECH/ELEC ROOM 111
P-24" X 20" X 6"
(PANEL FRONT) (INSIDE PANEL)
TCP-01
TEMPERATURE CONTROLS
DESIGNED BY:
ECT SERVICES, INC.
LOUISVILLE, KENTUCKY
W
I R
E
T
R A
C K
2" WIRE TRACK
W
I R
E
T
R A
C K
2" WIRE TRACK
10 AMP MAIN
BREAKER
DEVICE 1001
AHU-1 PRIMARY
PANEL
TRANS-
FORMER
100 VA
VERIS
V-X100CAA
OFF = 0-10V
ON = 4-20mA
AO'S 0-7
BO 6
BO 7
BO 5
BO 4
BO 2
BO 3
BO 1
S
S
E
R
D
D
A
6 AMP MAX
BO 0
STATUS
MS/TP
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
AO 2 - 43
COM - 44
AO 3 - 45
AO 4 - 46
COM - 47
AO 5 - 48
AO 6 - 49
COM - 50
AO 7 - 51
BACnet MS/TP
24 - DATA -
23 - DATA +
22 - 24 VDC
21 - COM
20 - IN 10
19 - IN 9
18 - COM
17 - IN 8
DRY CONTACT
THERMISTOR or
0 - 5VDC or 4-20mA
0 - 10VDC
INPUT SETUP JUMPERS
1 2 3 4
POWER:
MAX LOAD - 106VA
NO BO'S - 10VA
24VAC LOADS @ 0.5A MAX
24VDC SOURCES 100mA
TOTAL
FUSE: AGC-6 AMP FAST
CLASS 2 CIRCUITS ONLY
USE COPPER CONDUCTORS
ONLY
FOR INDOOR USE ONLY
SUITABLE FOR PLENUM
MOUNTING
SW1 = VLC MAC ADDRESS
SW2 = AO SETUP:
ON = 4-20mA
OFF = 0-10VDC
4-20mA INPUTS REQUIRE
250 OHM, 1% RESISTOR
ACROSS INPUT AND COM
BO 4 - 34
GND - 35
BO 5 - 36
BO 6 - 37
GND - 38
BO 7 - 39
AO 0 - 40
COM - 41
AO 1 - 42
24VAC - 25
GND - 26
BO 0 - 27
GND - 28
BO 1 - 29
BO 2 - 30
GND - 31
BO 3 - 32
GND - 33
EQUIPMENT 5K05
OPEN ENERGY MANAGEMENT
1 - IN 0 / MSET
2 - COM
3 - IN 1
4 - IN 2
5 - COM
6 - IN 3
7 - COM
8 - 24 VDC
LBL-VLC-1188-A
ASSEMBLED IN USA
VLC-1188
9 - IN 4
10 - COM
11 - IN 5
12 - IN 6
13 - COM
14 - IN 7
15 - COM
16 - 24 VDC
MS/TP
STATUS
ADDRESS
G
18 - DATA
17 - DATA +
16 - (NOT USED)
15 - 24VDC
14 - COM
13 - IN 7
12 - IN 6
11 - COM
10 - IN 5
ASSEMBLED IN USA
VLC-1600
L B
L V
L C
A
9 - 24VDC
8 - COM
7 - IN 4
6 - IN 3
5 - COM
4 - IN 2
3 - IN 1
2 - COM
1 - IN 0 / MSET
EQUIPMENT 5K05
OPEN ENERGY MANAGEMENT
IN 11 - 26
COM - 25
IN 10 - 24
IN 9 - 23
COM - 22
IN 8 - 21
GND - 20
24VAC - 19
24VDC - 34
COM - 33
IN 15 - 32
COM - 31
IN 14 - 30
IN 13 - 29
COM - 28
IN 12 - 27
SUITABLE FOR PLENUM MOUNTING
FOR INDOOR USE ONLY
USE COPPER CONDUCTORS ONLY
CLASS 2 CIRCUITS ONLY
ACROSS INPUT AND COM
250 OHM, 1% RESISTOR
4-20mA INPUTS REQUIRE
24VDC SOURCES 100mA TOTAL
POWER: MAX LOAD - 10VA
cause undesired operation.
including interference that may accept any interference received, interference, and (2) this device must
This device may not cause harmful to the following two conditions: (1) of the FCC Rules. Operation is subject
This device complies with Part 15
DEVICE 1002
AHU-1 SECONDARY
ERG
K
O R
5T E I S
L
D
P E
N E
N E
T R
0 5
I M
U N
Q P
E
MEAN A
Y
M
GE
N T
DEVICE 1003
CW SYSTEMS
120VAC FED FROM
PANEL RP2 -
CIRCUIT #12
DEVICE 1045
CW SYSTEMS
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-1.4
PANEL LAYOUT - TCP-1
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
E n e r g y
W h e e l
Pressure
V-PXDLX02S
Temp
TS-2008-GD-10
%RH
V-HD3XVSX
Smoke Det.
By Others
Filter DP
V-PXDLX02S
HIGH
LOW
HEAT WHEEL
BYPASS N.C.
DAMPER
HEAT WHEEL DP
V-PXDLX02S
Low
High
RF VFD
Enable/Disable
Status
Speed Signal
BYPASS
Hi Limit
AFS-460-DSS
N.C. Damper
AF24-SR
EXHAUST
AIR
OUTSIDE
AIR
ENERGY WHEEL
START/STOP
STATUS
N.C. Damper
AF24-SR
Filter DP
V-PXDLX02S
Low
High
Freezestat
FS-50
CHW Valve
B330+AF24-SR
ABA
B
ELECTRIC
HEATING
0-10 VDC
SF VFD
Enable/Disable
Status
Speed Signal
AMPS
BYPASS
Hi Limit
AFS-460-DSS
Temp
TS-5012-RD-10
Temp
TS-2008-GD-10
Pressure
V-PXDXX02S
Air Flow Monitor
Factory-Provided
Low
(SP)
High
(TP)
%RH
V-HD3XVSX
Temp
TS-2008-GD-10
AHU-2 DUCT LAYOUT
DATE INITIALS REVISION TYPE
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
8/9/12 C2M EDITED CABLE NUMBERS AS-BUILT
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-2.1
AHU2 DUCT LAYOUT
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
B
REV.
B
OFF = 0-10V
ON = 4-20mA
AO'S 0-7
BO 6
BO 7
BO 5
BO 4
BO 2
BO 3
BO 1
S
S
E
R
D
D
A
6 AMP MAX
BO 0
STATUS
MS/TP
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
AO 2 - 43
COM - 44
AO 3 - 45
AO 4 - 46
COM - 47
AO 5 - 48
AO 6 - 49
COM - 50
AO 7 - 51
BACnet MS/TP
24 - DATA -
23 - DATA +
22 - 24 VDC
21 - COM
20 - IN 10
19 - IN 9
18 - COM
17 - IN 8
DRY CONTACT
THERMISTOR or
0 - 5VDC or 4-20mA
0 - 10VDC
INPUT SETUP JUMPERS
1 2 3 4
POWER:
MAX LOAD - 106VA
NO BO'S - 10VA
24VAC LOADS @ 0.5A MAX
24VDC SOURCES 100mA
TOTAL
FUSE: AGC-6 AMP FAST
CLASS 2 CIRCUITS ONLY
USE COPPER CONDUCTORS
ONLY
FOR INDOOR USE ONLY
SUITABLE FOR PLENUM
MOUNTING
SW1 = VLC MAC ADDRESS
SW2 = AO SETUP:
ON = 4-20mA
OFF = 0-10VDC
4-20mA INPUTS REQUIRE
250 OHM, 1% RESISTOR
ACROSS INPUT AND COM
BO 4 - 34
GND - 35
BO 5 - 36
BO 6 - 37
GND - 38
BO 7 - 39
AO 0 - 40
COM - 41
AO 1 - 42
24VAC - 25
GND - 26
BO 0 - 27
GND - 28
BO 1 - 29
BO 2 - 30
GND - 31
BO 3 - 32
GND - 33
EQUIPMENT 5K05
OPEN ENERGY MANAGEMENT
1 - IN 0 / MSET
2 - COM
3 - IN 1
4 - IN 2
5 - COM
6 - IN 3
7 - COM
8 - 24 VDC
LBL-VLC-1188-A
ASSEMBLED IN USA
VLC-1188
9 - IN 4
10 - COM
11 - IN 5
12 - IN 6
13 - COM
14 - IN 7
15 - COM
16 - 24 VDC
01 IN00
COM
BLK
WHT
03 IN01
COM
WHT
04 IN02
COM
BLK
WHT
06 IN03
COM
BLK
09 IN04
24V COM
24VAC
RED
BLK
WHT
BLK
WHT
11 IN05
COM
24VAC
RED
BLK
WHT
12 IN06
COM
24VAC
RED
BLK
WHT
14 IN07
COM
24VAC
RED
WHT
BO00 27
COM
BLK
R
V-100 N.O.
WHT
BLK WHT/YEL
WHT/BLU
YEL
ORG
WHT
BO01 29
COM
BLK
R
V-100 N.O.
WHT
BLK WHT/YEL
WHT/BLU
YEL
ORG
WHT
BO02 30
COM
BLK
R
V-100 N.O.
WHT
BLK WHT/YEL
WHT/BLU
YEL
ORG
BO03 32
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO04 34
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO05 36
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO06 37
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO07 39
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BLK
WHT
RED
V-PXDLX02S
HEAT WHEEL DP
24VAC
DATE INITIALS REVISION TYPE
A 8/9/12 C2M
MOVED TEMP SENSOR AND ADDED HEAT
WHEEL DP TO DEVICE
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-2.2
CONFIG - AHU2a (SHT 1 OF 2)
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
WHT
17 IN08
COM
BLK
PANEL TERMINALS OUT
SUPPLY FAN STATUS -- AMPS
WHT
19 IN09
COM
BLK
WHT
20 IN10
COM
BLK
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
23+
23+
24-
24-
WHT
WHT
BLK
BLK
WHT
AO00 40
COM
BLK
PANEL TERMINALS OUT
SUPPLY FAN SPEED OUTPUT
WHT
AO01 42
COM
BLK
PANEL TERMINALS OUT
EXHAUST FAN SPEED OUTPUT
WHT
AO02 43
COM
BLK
PANEL TERMINALS OUT
ELECTRIC HEAT OUTPUT
AO03 45
24V COM
24VAC
WHT
RED
BLK
AO04 46
24V COM
24VAC
WHT
RED
BLK
(NO)
AO05 48
24V COM
24VAC
WHT
RED
BLK
(NO)
AO06 49
24V COM
24VAC
WHT
RED
BLK
(NO)
AO07 51
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
(FIELD VERIFY)
DATE INITIALS REVISION TYPE
A
8/9/12 C2M EDITED TERMINAL NUMBERS
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-2.3
CONFIG - AHU2b (SHT 2 OF 2)
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
OUTSIDE AIR
TEMPERATURE
WHT
01 IN00
COM
BLK
TS-2008-GD-10-AA
03 IN01
OUTSIDE AIR
HUMIDITY
24V COM
24VAC
RED
BLK
WHT
V-HD2XVSX
BLK
WHT
04 IN02
COM
OUTSIDE AIR FILTER STATUS
24VAC
RED
V-PXDLX02S
BLK
WHT
06 IN03
COM
EXHAUST AIR FILTER STATUS
24VAC
RED
V-PXDLX02S
07 IN04
24V COM
BLK
WHT
SUPPLY HIGH STATIC LIMIT
AFS-460-DSS
10 IN05
24V COM
BLK
WHT
EXHAUST HIGH STATIC LIMIT
AFS-460-DSS
BLK
WHT
LOW TEMPERATURE
PROTECTION - DPDT
12 IN06
COM
FS-50
13 IN07
COM
IN08 21
COM
WHT
IN09 23
COM
BLK
(FIELD VERIFY)
PANEL TERMINALS IN
SUPPLY FAN VFD BYPASS STATUS
WHT
IN10 24
COM
BLK
(FIELD VERIFY)
PANEL TERMINALS IN
EXHAUST FAN VFD BYPASS STATUS
WHT
IN11 26
COM
BLK
HEAT WHEEL STATUS
V-H908
IN12 27
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN13 29
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN14 30
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN15 32
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
DATE INITIALS REVISION TYPE
A 8/9/12 C2M
REMOVED DUCT SMOKE INPUT AND MOVED
HEAT WHEEL DP SENSOR TO DEV.1020
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-2.4
CONFIG - AHU2b
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
TCP-2
P-18 LAYOUT
TEMPERATURE CONTROLS
Designed By:
ECT SERVICES
Louisville, Kentucky
PANEL
TRANS-
FORMER
100 VA
FUNCTIONAL DEVICES
TR100VA001
TCP-2 LAYOUT
P-18" X 16" X 6"
LOCATED IN MAMMOTH CAVE VISITORS CTR
ATTIC MECHANICAL ROOM 201
10 AMP MAIN
BREAKER
(PANEL FRONT) (INSIDE PANEL)
1-1/2" WIRE TRACK
1-1/2" WIRE TRACK
W
I R
E
T
R A
C K
W
I R
E
T
R A
C K
OFF = 0-10V
ON = 4-20mA
AO'S 0-7
BO 6
BO 7
BO 5
BO 4
BO 2
BO 3
BO 1
S
S
E
R
D
D
A
6 AMP MAX
BO 0
STATUS
MS/TP
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
AO 2 - 43
COM - 44
AO 3 - 45
AO 4 - 46
COM - 47
AO 5 - 48
AO 6 - 49
COM - 50
AO 7 - 51
BACnet MS/TP
24 - DATA -
23 - DATA +
22 - 24 VDC
21 - COM
20 - IN 10
19 - IN 9
18 - COM
17 - IN 8
DRY CONTACT
THERMISTOR or
0 - 5VDC or 4-20mA
0 - 10VDC
INPUT SETUP JUMPERS
1 2 3 4
POWER:
MAX LOAD - 106VA
NO BO'S - 10VA
24VAC LOADS @ 0.5A MAX
24VDC SOURCES 100mA
TOTAL
FUSE: AGC-6 AMP FAST
CLASS 2 CIRCUITS ONLY
USE COPPER CONDUCTORS
ONLY
FOR INDOOR USE ONLY
SUITABLE FOR PLENUM
MOUNTING
SW1 = VLC MAC ADDRESS
SW2 = AO SETUP:
ON = 4-20mA
OFF = 0-10VDC
4-20mA INPUTS REQUIRE
250 OHM, 1% RESISTOR
ACROSS INPUT AND COM
BO 4 - 34
GND - 35
BO 5 - 36
BO 6 - 37
GND - 38
BO 7 - 39
AO 0 - 40
COM - 41
AO 1 - 42
24VAC - 25
GND - 26
BO 0 - 27
GND - 28
BO 1 - 29
BO 2 - 30
GND - 31
BO 3 - 32
GND - 33
EQUIPMENT 5K05
OPEN ENERGY MANAGEMENT
1 - IN 0 / MSET
2 - COM
3 - IN 1
4 - IN 2
5 - COM
6 - IN 3
7 - COM
8 - 24 VDC
LBL-VLC-1188-A
ASSEMBLED IN USA
VLC-1188
9 - IN 4
10 - COM
11 - IN 5
12 - IN 6
13 - COM
14 - IN 7
15 - COM
16 - 24 VDC
CONFIG AHU2a
CONFIG AHU2b
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-2.5
PANEL LAYOUT - TCP-2
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
VAV
Controller
LOCATED: Refer to Schedule
Config: VAV2 -- QTY 8
COOLING-ONLY VAV TERMINAL UNIT
Unit Heater
UH-4 or 5
S/S
QTY 2 – Refer to Config FCU_Heat
DEV. 1040, 1041
ELECTRIC CABINET UNIT HEATER
Space Temp
TS-1101-WA-10
AB A
C
C
Microset II
MS-2000-BT
1FS
FLOAT
SWITCH
LOCATED: See Schedule
Config: FCU -- QTY 9, Config: FCU_Heat – Qty 2, DEV. 1040, 1041
FAN COIL UNIT
Electric Heating
Coil
Temp
TS-2004-FB-10
VLC-660
DDC Controller
BACnet
MS/TP
(2) #14 THHN
AB A
C
C
Microset II
MS-2000-BT
1FS
FLOAT
SWITCH
LOCATED: See Schedule
Config: FCU_CO2 -- QTY 2
DEV. 1034, 1038
FAN COIL UNIT W/CO2 SENSOR
Electric Heating
Coil
Temp
TS-2004-FB-10
VLC-660
DDC Controller
BACnet
MS/TP
(2) #14 THHN
CO2 SENSOR
V-CWLSXX
BACnet
+ 24VAC
Power
MS/TP
AB A
C
C
Microset II
MS-2000-BT
1FS
FLOAT
SWITCH
LOCATED: See Schedule
Config: FCU -- Qty 2
DEV. 1028, 1037
FAN COIL UNIT (BLOWER-COIL UNIT)
Electric Heating
Coil
Temp
TS-2004-FB-10
VLC-660
DDC Controller
BACnet
MS/TP
(2) #14 THHN
Refer to Sheets FP-1.3 & M3
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-3.1
TERMINAL DUCT LAYOUT
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
24V COM24 VAC
VAViH-SD
BACNET
MS/TP
IN00 9
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN01 11
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN02 12
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN03 14
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
IN04 16
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
23+
23+
24-
24-
WHT
WHT
BLK
BLK
BO005
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO016
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO027
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
BO058
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
DATE INITIALS REVISION TYPE
A
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-3.2
CONFIG - VAV2
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ORG
BLK
WHT
RED
BLK
WHT
24 VAC
2 COM
ROOM TEMPERATURE
SENSOR
08 IN00
MS-2000-BT
WHT
10 IN01
COM
BLK
V-H300
SUPPLY FAN STATUS
WHT
11 IN02
COM
BLK
TS-2004-FB-10-AA
DISCH AIR TEMP.
BLK
WHT
13 IN03
COM
SPACE CO2
(4-20 mA)
V-CWLSXX
17 24VDC
RED
14 IN04
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
CONDENSATE
OVERFLOW ALARM
16 IN05
COM
WHT
BO00 21
COM
BLK
PANEL TERMINALS OUT
FAN START/STOP
WHT
BO01 23
COM
BLK
PANEL TERMINALS OUT
HEAT STAGE 1
BO02 25
COM
03 BO03
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
05 BO04
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
CHILLED
WATER VALVE
06 AO00
TF24-SR
02 24V GRD
01 24VAC
WHT
RED
BLK
TF24-SR-V
24V COM
24 VAC
IN00 MICROSET II Thermostat
IN01
IN02
IN03
BO00 Supply Fan Start/Stop
BO01 Heat Stage 1
BO02 FOR FUTURE USE
BO03 FOR FUTURE USE
UNIVERSAL
INPUTS POINT DESCRIPTION
BINARY
OUTPUTS POINT DESCRIPTION
VLC-651R
CONFIG FCU_CO2
AO00 Chilled Water Valve Control
ANALOG
OUTPUTS POINT DESCRIPTION
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
18+
18+
19-
19-
WHT
WHT
BLK
BLK
IN04
IN05
Discharge Air Temperature
FOR FUTURE USE
BO04 FOR FUTURE USE
FOR FUTURE USE
Space CO2 Sensor
ER
G
K
O R
5T E I S
L D
PE
N
E N
E
T R
0 5
I M
U N
Q P
E
MEANA
Y
M
GE
NT
Supply Fan Status
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
(POWER FROM FCU)
07 COM
250 Ohm Resistor
500 Ohm Resistor
DATE INITIALS REVISION TYPE
A 8/9/12 C2M
EDITED DEVICE TYPE, ADDED RESISTORS AND
MOVED CONDENSATE ALARM INPUT AS-BUILT
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-3.3
CONFIG - FCU_CO2
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
A
REV.
A
REV.
WHT
RED
BLK
WHT
24 VAC
2 COM
MS-2000-BT
ROOM TEMPERATURE
SENSOR
08 IN00
WHT
10 IN01
COM
BLK
V-H300
SUPPLY FAN
STATUS
WHT
11 IN02
COM
BLK
TS-2004-FB-10-AA
DISCH AIR TEMP.
13 IN03
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
WHT
14 IN04
COM
BLK
MANUFACTURER
SUPPLIED
THERMOSTAT
16 IN05
COM
WHT
BO00 21
COM
BLK
PANEL TERMINALS OUT
FAN START/STOP
WHT
BO01 23
COM
BLK
PANEL TERMINALS OUT
HEAT STAGE 1
BO02 25
COM
WHT
03 BO03
COM
BLK
UNIT HEATER
START/STOP
R
V-120 N.O.
WHT
BLK WHT/YEL
WHT/BLU
YEL
ORG
COM
LOAD
05 BO04
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
CHILLED
WATER VALVE
TF24-SR
WHT
RED
BLK
TF24-SR-V
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
CONDENSATE
OVERFLOW ALARM
24V COM
24 VAC
IN00 MICROSET II Thermostat
IN01
IN02
IN03
BO00 Supply Fan Start/Stop
BO01 Heat Stage 1
BO02 FOR FUTURE USE
BO03 Unit Heater Start/Stop
UNIVERSAL
INPUTS POINT DESCRIPTION
BINARY
OUTPUTS POINT DESCRIPTION
VLC-651R
CONFIG FCU_HEAT
AO00 Chilled Water Valve Control
ANALOG
OUTPUTS POINT DESCRIPTION
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
18+
18+
19-
19-
WHT
WHT
BLK
BLK
IN04
IN05
Discharge Air Temperature
FOR FUTURE USE
BO04 FOR FUTURE USE
Manufacturer Supplied Thermostat
FOR FUTURE USE
ER
G
K
O R
5T E I S
L D
P E
N E
N E
T R
0 5
I M
U N
Q P
E
MEANA
Y
M
GE
NT
Supply Fan Status
(POWER FROM FCU)
500 Ohm Resistor
06 AO00
02 24V GRD
01 24VAC
07 COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
DATE INITIALS REVISION TYPE
A 8/9/12 C2M
DEVICE TYPE, RESISTORS, CONDENSATE ALARM INPUT
AND MFR-SUPPLIED STAT MOUNTED AS-BUILT
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-3.4
CONFIG - FCU_HEAT
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
A
REV.
A
REV.
WHT
RED
BLK
WHT
24 VAC
2 COM
MS-2000-BT
ROOM TEMPERATURE
SENSOR
08 IN00
WHT
10 IN01
COM
BLK
V-H300
SUPPLY FAN
STATUS
WHT
11 IN02
COM
BLK
TS-2004-FB-10-AA
DISCH AIR TEMP.
13 IN03
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
14 IN04
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
WHT
BO00 21
COM
BLK
PANEL TERMINALS OUT
FAN START/STOP
WHT
BO01 23
COM
BLK
PANEL TERMINALS OUT
HEAT STAGE 1
WHT
BO02 25
COM
BLK
PANEL TERMINALS OUT
HEAT STAGE 2
(Existing on FCU-17 & -21
Only)
03 BO03
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
05 BO04
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
CHILLED WATER
VALVE
06 AO00
TF24-SR
24V COM
24VAC
WHT
RED
BLK
TF24-SR-V
CONDENSATE
OVERFLOW ALARM
24V COM
24 VAC
IN00 MICROSET II Thermostat
IN01
IN02
IN03
BO00 Supply Fan Start/Stop
BO01 Heat Stage 1
BO02 Heat Stage 2 (FCU-17 & -21 ONLY)
BO03
UNIVERSAL
INPUTS POINT DESCRIPTION
BINARY
OUTPUTS POINT DESCRIPTION
VLC-651R
CONFIG FCU_HEAT
AO00 Chilled Water Valve Control
ANALOG
OUTPUTS POINT DESCRIPTION
NOTE:
FROM PREVIOUS
MULTI-DROP
SHIELD
SHIELD
MULTI-DROP
TO NEXT
GROUND SHIELD ONLY
AT GLOBAL CONTROLLER.
TWIST AND TAPE
SO THERE IS NO
SHIELD EXPOSED
CABLE
CABLE
22-2 SH. ORG
22-2 SH. ORG
18+
18+
19-
19-
WHT
WHT
BLK
BLK
IN04
IN05
Discharge Air Temperature
FOR FUTURE USE
BO04 FOR FUTURE USE
FOR FUTURE USE
ER
G
K
O R
5T E I S
L D
P E
N E
N E
T R
0 5
I M
U N
Q P
E
MEANA
Y
M
GE
NT
Supply Fan Status
(POWER FROM FCU)
500 Ohm Resistor
07 COM
FOR FUTURE USE
FOR FUTURE USE
16 IN05
COM
UNUSED
BLK
WHT
SPARE TERMINALS
NOT BEING USED
DATE INITIALS REVISION TYPE
A 8/9/12 C2M
DEVICE TYPE, RESISTOR, CONDENSATE ALARM INPUT AND
ADDED STAGE 2 HEAT NOTE AS-BUILT
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-3.5
CONFIG - FCU
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
A
REV.
A
REV.
A
REV.
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.1
VAV SCHEDULE
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.2
DAMPER SCHEDULE
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.3
VALVE SCHEDULE
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.4
BILL OF MATERIALS
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.5
SEQUENCE OF OPERATIONS
(SHT 1 OF 3)
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.6
SEQUENCE OF OPERATIONS
(SHT 2 OF 3)
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
= VFD TERMINALS
PANEL TERMINAL
BLOCK
CONNECTIONS
CHILLER
TERMINALS
WIRED IN SERIES
W/AUTO SIDE OF
STARTER
= BOILER TERMINALS=
AHU/RTU/PACKAGE
UNIT TERMINALS
COOLING TOWER
TERMINALS
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
TC-A.7
SEQUENCE OF OPERATIONS
(SHT 3 OF 3)
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
SP
SP
SP
SP
SP SP
SP
SP
DATE INITIALS REVISION TYPE
A
B
C
D
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
FP-1.1
FLOOR PLAN - MAIN FLOOR
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
SP MS
- MICROSET
- CARBON
DIOXIDE
SENSOR
- FAN COIL UNIT
- VAV
- DUCTLESS
SPLIT SYSTEM
- REHEAT COIL
- UNIT VENTILATOR
- RANGE HOOD
- MCP/TCP
- UNDER SLAB
- SNS CABLE
- COMM CABLE
- 18/4 CABLING
- AHU
- RTU
- MAU
- BLOWER COIL
- UNIT HEATER
- RELIEF AIR FAN
STAINLESS PLATE
SENSOR
DUCT STATIC
PRESSURE SENSOR
PUMP
EXHAUST FAN
LOUVER
CO
RHC-##
DSS
- BOILER
- CHILLER
- COOLING TOWER
AHU
RTU
B
CT
CHL
MAU
- SUPPLY AIR FAN
- CONDENSING UNIT
- MOTORIZED DAMPERM
DP
DN
DN
SP
DATE INITIALS REVISION TYPE
A
B
C
D
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
FP-1.2
FLOOR PLAN - ATTIC
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
SP MS
- MICROSET
- CARBON
DIOXIDE
SENSOR
- FAN COIL UNIT
- VAV
- DUCTLESS
SPLIT SYSTEM
- REHEAT COIL
- UNIT VENTILATOR
- RANGE HOOD
- MCP/TCP
- UNDER SLAB
- SNS CABLE
- COMM CABLE
- 18/4 CABLING
- AHU
- RTU
- MAU
- BLOWER COIL
- UNIT HEATER
- RELIEF AIR FAN
STAINLESS PLATE
SENSOR
DUCT STATIC
PRESSURE SENSOR
PUMP
EXHAUST FAN
LOUVER
CO
RHC-##
DSS
- BOILER
- CHILLER
- COOLING TOWER
AHU
RTU
B
CT
CHL
MAU
- SUPPLY AIR FAN
- CONDENSING UNIT
SP
SP
SP
T
T
A
A
DATE INITIALS REVISION TYPE
A
9/2/10 AF REV. PER ENGINEER'S REQUEST
B
C
D
Mechanical
Contractor:
Consulting
Engineer:
Architect:
Page Number:
Job Number:Engineer:
Date:
Project:
Checked By:
CADD:
Page Title:
Project Mgr:
6/15/10
JIM LICHTEFELD AF
ASHEVILLE, NC
PROFESSIONAL MECH. CONTRACTORS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
NORFOLK, VA
PARSONS, BRINKERHOFF, QUADE, & DOUGLAS, INC.
MSB
MIKE BERGER
MAMMOTH CAVE, KENTUCKY
MAMMOTH CAVE NAT'L PARK - PHASE TWO
FP-1.3
FLOOR PLAN - BASEMENT
PHONE: (502) 636-2402
1501 S. Preston St.
Louisville, KY 40217
NOITAR
E
TNI
G
DLUB GNII
FAX: (502) 636-0105
ectservices.com
SINCE 1981
SP MS
- MICROSET
- CARBON
DIOXIDE
SENSOR
- FAN COIL UNIT
- VAV
- DUCTLESS
SPLIT SYSTEM
- REHEAT COIL
- UNIT VENTILATOR
- RANGE HOOD
- MCP/TCP
- UNDER SLAB
- SNS CABLE
- COMM CABLE
- 18/4 CABLING
- AHU
- RTU
- MAU
- BLOWER COIL
- UNIT HEATER
- RELIEF AIR FAN
STAINLESS PLATE
SENSOR
DUCT STATIC
PRESSURE SENSOR
PUMP
EXHAUST FAN
LOUVER
CO
RHC-##
DSS
- BOILER
- CHILLER
- COOLING TOWER
AHU
RTU
B
CT
CHL
MAU
- SUPPLY AIR FAN
- CONDENSING UNIT