This submittal list outlines product and service requirements for replacing and upgrading the HVAC systems at the Natchez Visitor Center. Key specifications include demolition and removal of existing HVAC equipment, installation of new condensing boilers, water chillers, air handling units, ductwork, piping, controls, and commissioning. The solicitation seeks proposals to perform the HVAC replacement and upgrade work for the Natchez National Historical Park, with submissions due by May 18, 2021. Relevant experience, licenses, and manufacturer approvals are required. Submittals include plans, shop drawings, product data, samples, test reports, warranties and closeout documentation.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUBMITTAL LIST
Park Acronym/Project Management Information System (PMIS) Number: 311660
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S O
R
L A
B O
R A
T O
Y
T E
S T
S
R E
P O
R T
S
C
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A N
D
IN
S
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
P
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
01 32 16 Construction Schedule
1.3.B Schedule of Values X
1.3.C Construction Baseline Schedule X
1.3.D CPM Reports X
1.3.E Contruction Schedule Updates X
1.3.F Construction Schedule Revisions and Time Impact Analysis X
01 32 33 Photographic Documentation X
1.2.A Construction Images X
1.2.B Closeout X
01 35 23 Safety Requirements
1.2.A Accident Prevention Plan X
01 35 91 Historic Preservation Treatment Procedures
1.3.A Historic Preservation Treatment Plan X
1.3.B Alternitive Methods and Materials X
1.3.C Photographs and Videotape X
01 40 00 Quality Requirements
1.4.A Quality Control Plan X
1.4.B Qualification Data X
1.4C Contractor's Quality Control Daily Reports X
1.4D Test Reports X
1.4E Accessibility Inspection Reports X
1.4F Off-site Inspection Reports X
ACTION
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 1 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.4.H Permits, Licenses, and Certificates X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 2 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
01 57 19.11 Indoor Air Quality Management
1.4.A Indoor Air Quality Management Plan X
1.4.B Product Data X
1.4.C Inspection and Test Reports X
01 57 23 Temporary Storm Water Pollution Prevention
1.3.A Pollution Prevention Plan (UPPP) X
1.3.B Inspection Schedule X
01 67 00 Product Requirements
1.3.A Sustainable Design Closeout Documentation X
01 73 29 Cutting and Patching
1.2.A Cutting & Patching Plan X
01 73 40 Execution
1.2.A Landfill Reciepts X
1.2.B Quantity Surveys X
01 74 19 Construction Waste Management & Disposal
1.4.A Construction Waste Management & Disposal Plan X
1.4.B Recycling and Processing Facility Records X
1.4.C Qualification Data X
1.4.D Statement of Refrigerant Recovery X
1.4.E Closeout Submittals X X
01 78 23 Operation and Maintenance Data
1.2.A Manual X
01 79 00 Demonstration & Training
1.3.A Instruction Program X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 3 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.3.B Demonstration & Training Videos X
01 81 13 Sustainable Design Requirements
1.3 Federal Sustainability Documentation Preliminary Submittals X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 4 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
01 91 14 Total Building Commissioning
1.6.A Two-week look-ahead schedule X
1.6.B Certificates of Readiness X
1.6.C Contractor's Commissioning Representative Qualifications X
1.6.D Commissioning Plan X
1.6.E Pre-functional Checklists X
1.6.F Owner's Project Requirements X
1.6.G Functional Performance Test Forms X
1.6.H List of test instrumentation X X X
1.6.I Deficiency Report and Resolution Record X
1.6.J Closeout Documentation X
05 12 00 Structural Steel
1.05A Product Data: X
1.05B Shop Drawings: Show fabrication of structural-steel components. X
1.06A Qualification Data: For qualified Installer and Fabricator. X
1.06B Welding certificates. X
1.06C
Material (Mill) test reports for structural steel, including chemical and physical properties. X
1.06D Product Test Reports: X
1.06E Source quality-control reports. X
1.06F Survey of existing conditions. X
05 50 00 Metal Fabrications
1.04A
Shop Drawings: Show fabrication and installation details for
Metal Fabrications. X
05 53 13 Bar Gratings
1.03A Product Data: X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 5 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.03B Shop Drawings: X
1.04A Certificates: X
06 10 00 Rough Carpentry
1.03B
Product Data: Provide technical data on wood preservative materials and application instructions . X
07 62 00 Sheet Metal Flashing and Trim
1.04B
Fabricator and Installer Qualifications: Company specializing in sheet metal work with 5 years of documented experience. X
1.03B
Shop Drawings: Indicate material profile, jointing pattern, jointing details, fastening methods, flashings, terminations, and installation details. X
07 72 00 Roof Accessories
1.04B
Product Data: Manufacturer's data sheets on each product to be used.
1.04C Warranty Documentation X
07 92 00 Joint Sealants
1.05D
Preinstallation Field Adhesion Test Plan: Submit at least two weeks prior to start of installation. X
1.05F
Field Quality Control Plan: Submit at least two weeks prior to start of installation. X
1.04C
Preconstruction Laboratory Test Reports: Submit at least four weeks prior to start of installation. X
1.04F Preinstallation Field Adhesion Test Reports: X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 6 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04G
Field Quality Control Log: Submit filled out log for each length or instance of sealant installed, within 10 days after completion of inspections/tests; include bagged test samples and photographic records, if any. X
1.05B
Installer Qualifications: Company specializing in performing the work of this section and with at least three years of documented experience . X
1.05A
Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience. X
1.04B
Product Data for Sealants: Submit manufacturer's technical data sheets for each product to be used, that includes the following. X
08 31 00 Access Doors and Panels
1.03B
Product Data: Provide sizes, types, finishes, hardware, scheduled locations, and details of adjoining work. X
09 21 16 Gypsum Board Assemblies
1.04A
Installer Qualifications: Company specializing in performing gypsum board installation and finishing , with minimum five years of experience . X
1.03B
Product Data: Provide data on metal framing, gypsum board, accessories, and joint finishing system . X
1.03C
Product Data: Provide manufacturer's data on partition head to structure connectors, showing compliance with requirements. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 7 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.03D
Test Reports: For stud framing products that do not comply with
ASTM C1513 or ASTM E1233/E1233M, provide independent laboratory reports showing maximum stud heights at required spacings and deflections. X
09 51 00 Acoustical Ceilings
1.05A
Suspension System Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience. X
1.04D
Maintenance Materials: Furnish the following for NPS/OWNER's use in maintenance of project. X
1.05B
Acoustical Unit Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience. X
1.04B
Product Data: Provide data on suspension system components and acoustical units . X
09 91 13 Exterior Painting
1.04B
Applicator Qualifications: Company specializing in performing the type of work specified with minimum three years experience . X
1.04A
Manufacturer Qualifications: Company specializing in manufacturing the products specified, with minimum three years documented experience. X
1.03B
Product Data: Provide complete list of products to be used, with the following information for each: X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 8 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.03C
Samples: Submit two painted samples, illustrating selected colors and textures for each color and system selected with specified coats cascaded . Submit on tempered hardboard , [8
1/2 x 11] inch in size. X
09 91 23 Interior Painting
1.04B
Product Data: Provide complete list of products to be used, with the following information for each: X
1.05A
Manufacturer Qualifications: Company specializing in manufacturing the products specified, with minimum three years documented experience. X
06 10 00 Rough Carpentry
1.03B
Product Data: Provide technical data on wood preservative materials and application instructions . X
07 62 00 Sheet Metal Flashing and Trim
1.04B
Fabricator and Installer Qualifications: Company specializing in sheet metal work with 5 years of documented experience. X
1.03B
Shop Drawings: Indicate material profile, jointing pattern, jointing details, fastening methods, flashings, terminations, and installation details. X
07 72 00 Roof Accessories
1.04B
Product Data: Manufacturer's data sheets on each product to be used. X
07 92 00 Joint Sealants
1.04D
Preinstallation Field Adhesion Test Plan: Submit at least two weeks prior to start of installation. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 9 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04E
Field Quality Control Plan: Submit at least two weeks prior to start of installation. X
1.04G
Field Quality Control Log: Submit filled out log for each length or instance of sealant installed, within 10 days after completion of inspections/tests; include bagged test samples and photographic records, if any. X
1.05F
Field Quality Control Log Form: Show same data fields as on
Preinstallation Field Adhesion Test Log, with known information filled out and lines for multiple tests per sealant/substrate combinations; include visual inspection and specified field testing;
allow for possibility that more tests than minimum specified may be necessary. X
1.05G
Record the type of failure that occurred, other information required by test method, and the information required on the Field
Quality Control Log. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 10 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.05B
Installer Qualifications: Company specializing in performing the work of this section and with at least three years of documented experience . X
1.05A
Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience. X
1.04B
Product Data for Sealants: Submit manufacturer's technical data sheets for each product to be used, that includes the following. X
Color Cards for Selection: Where sealant color is not specified, submit manufacturer's color cards showing standard colors available for selection. X
08 31 00 Access Doors and Panels X
1.04A Manufacturer Qualifications X
1.04B Installer Qualifications
09 21 16 Gypsum Board Assemblies
1.04A
Installer Qualifications: Company specializing in performing gypsum board installation and finishing , with minimum five years of experience . X
1.03B
Product Data: Provide data on metal framing, gypsum board, accessories, and joint finishing system . X
1.03C
Product Data: Provide manufacturer's data on partition head to structure connectors, showing compliance with requirements. X
09 51 00 Acoustical Ceilings
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 11 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.05A
Suspension System Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience. X
1.05B
Acoustical Unit Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience. X
1.04B
Product Data: Provide data on suspension system components and acoustical units . X
1.04C Samples X
09 91 13 Exterior Painting
Manufacturer's installation instructions. X
1.04A
Applicator Qualifications: Company specializing in performing the type of work specified with minimum three years experience . X
1.04B
Manufacturer Qualifications: Company specializing in manufacturing the products specified, with minimum three years documented experience. X
1.03B
Product Data: Provide complete list of products to be used, with the following information for each: X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 12 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.03C
Samples: Submit two painted samples, illustrating selected colors and textures for each color and system selected with specified coats cascaded . Submit on tempered hardboard , [8
1/2 x 11] inch in size. X
23 00 10 Common Work Results for Mechanical
1.08E
LICENSING: Submit current Mechanical Contractor and Welder licenses specific to the state in which the work is to be performed for each onsite supervisor that will have responsible charge over the work. Submit a minimum of (2) licenses to ensure that at least one licensed supervisor will be onsite at all times during the installation. X
1.09C
Installer Qualifications: Unless specifically noted otherwise in the specifications or drawings, a company specializing in performing work of the type specified and with at least three years of documented experience and approved by manufacturer . X
1.08D
ELECTRICAL COORDINATION STATEMENT: Submit a written statement confirming coordination of voltage and power connection requirements for all Mechanical equipment and controls requiring an electrical connection. Statement shall bear the names and signatures of the Mechanical and Electrical subcontractors. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 13 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.08C
SHOP DRAWINGS: Submit Mechanical shop drawings for review by the NPS/OWNER and the Contracting Officer of Record prior to beginning work. Background information shall be CAD or other computer-drawn versions of the floor plans or reflected ceiling plans of the Contract Drawings. Drawing from the Contract
Documents shall not be copied for use as backgrounds, and hand drawings or sketch "markups" of the Contract Drawings shall not be accepted. X
23 05 23 General Duty Valves for HVAC Piping
1.04B
Product Data: Provide data on valves including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections.
23 05 29 Hangers and Supports for HVAC Piping and Equipment
1.03B
Product Data: Provide manufacturer's standard catalog pages and data sheets for channel (strut) framing systems, non-penetrating rooftop supports, post-installed concrete and masonry anchors, thermal insulated pipe supports, all refrigerant piping supports, and cold galvanizing compound . X
23 05 53
Identification for HVAC Piping and Equipment and
Equipment
1.04B
Product Data: Provide manufacturers catalog literature for each product required. X
23 05 93 Testing, Adjusting, and Balancing for HVAC
1.04C
Field Logs: Submit at least twice a week to the Commissioning
Authority . X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 14 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04D
Control System Coordination Reports: Communicate in writing to the controls installer all setpoint and parameter changes made or problems and discrepancies identified during TAB that affect, or could affect, the control system setup and operation. X
3.01C TAB Agency Qualifications: X
3.01D
TAB Supervisor and Technician Qualifications: Certified by same organization as TAB agency. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 15 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04B
TAB Plan: Submit a written plan indicating the testing, adjusting, and balancing standard to be followed and the specific approach for each system and component. X
23 07 13 Duct Insulation
1.05B
Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations. X
23 07 19 HVAC Piping Insulation
1.04B
Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations. X
23 09 23 Direct Digital Control System for HVAC
1.06D
Installer Qualifications: Company specializing in performing work of the type specified and with minimum [five] years of documented experience and approved by manufacturer . X
1.05B
Product Data: Provide data for each system component and software module. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 16 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.05C Shop Drawings: X
23 11 23 Facility Natural Gas Piping
1.04B
Product Data: Provide data on pipe materials, pipe fittings, valves, and accessories. Provide manufacturers catalog information. Indicate valve data and ratings. X
23 21 13 Hydronic Piping
1.05B
Welders Certificate: Include welders certification of compliance with ASME BPVC-IX . X
1.05C Product Data: X
23 21 14 Hydronic Specialties
1.04C
Certificates: Inspection certificates for pressure vessels from authority having jurisdiction . X
1.04B
Product Data: Provide product data for manufactured products and assemblies required for this project. Include component sizes, rough-in requirements, service sizes, and finishes. Include product description and model . X
23 21 23 Hydronic Pumps
1.04B
Product Data: Provide certified pump curves showing performance characteristics with pump and system operating point plotted. Include NPSH curve when applicable. Include electrical characteristics and connection requirements. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 17 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
23 23 00 Refrigerant Piping
1.05F Submit welders certification of compliance with ASME X
2.01C Welders Certification: In accordance with ASME X
1.06A
Installer Qualifications: Company specializing in performing the type of work specified in this section, with minimum 5 years of documented experience. X
1.05B
Product Data: Provide general assembly of specialties, including manufacturers catalogue information. Provide manufacturers catalog data including load capacity. X
1.05G Installer's Qualification Statement. X
1.05C
Shop Drawings: Indicate schematic layout of system, including equipment, critical dimensions, piping, exterior piping protective cover systems, and sizes. X
23 31 00 HVAC Duct and Casings
1.04B Product Data: Provide data for duct materials . X
1.04C
Shop Drawings: Indicate duct fittings, particulars such as gauges, sizes, welds, and configuration prior to start of work for medium pressure class and higher systems. X
23 33 00 Air Duct Accessories
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 18 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04B
Product Data: Provide for shop fabricated assemblies including volume control dampers . Include electrical characteristics and connection requirements. X
23 34 16 Centrifulal HVAC Fans
1.04C
Manufacturer's Instructions: Include complete installation instructions. X
1.04B
Product Data: Provide data on centrifugal fans and accessories including fan curves with specified operating point clearly plotted, power, RPM, sound power levels for both fan inlet and outlet at rated capacity, and electrical characteristics and connection requirements. X
23 37 00 Air Outlets and Inlets
1.04B
Product Data: Provide data for equipment required for this project. Review outlets and inlets as to size, finish, and type of mounting prior to submission. Submit schedule of outlets and inlets showing type, size, location, application, and noise level. X
23 52 16 Condensing Boilers
1.04E
Manufacturer's Field Reports: Burner manifold gas pressure, percent carbon monoxide (CO), percent oxygen (O), percent excess air, flue gas temperature at outlet, ambient temperature, net stack temperature, percent stack loss, percent combustion efficiency, and heat output. X
1.04B
Product Data: Provide data indicating general assembly, components, controls, safety controls, and wiring diagrams with electrical characteristics and connection requirements, and service connections. X
23 64 23 Scroll Water Chillers
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 19 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04C
Manufacturer's Certificate: Certify that components furnished but not produced by manufacturer meet or exceed manufacturer's requirements. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 20 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04E
Manufacturer's Instructions: Submit manufacturer's complete installation instructions. X
1.04B
Product Data: Provide rated capacities, weights, specialties and accessories, electrical requirements and wiring diagrams. X
23 73 13 Modular Air Handling Units
1.03A Product Data X
23 74 33 Dedicated Outdoor Air Units
1.03B
Product Data: Provide data with dimensions, duct and service connections, accessories, controls, electrical nameplate data, and wiring diagrams. X
23 81 29 Variable Refrigerant Flow HVAC Systems
1.06C
Installer Qualifications: Trained and approved by manufacturer of equipment. X
1.06D
Product Data: Submit manufacturer's standard data sheets showing the following for each item of equipment, marked to correlate to equipment item markings indicated in Contract
Documents: X
1.06E
Shop Drawings: Installation drawings custom-made for this project; include as-designed HVAC layouts, locations of equipment items, refrigerant piping sizes and locations, condensate piping sizes and locations, remote sensing devices, control components, electrical connections, control wiring connections, and ASHRAE 15 compliance calculations. Include at a minimum: X
26 05 19 Low-Voltabe Electrical Power Conductors and Cables
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 21 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for conductors and cables, including detailed information on materials, construction, ratings, listings, and available sizes, configurations, and stranding. X
26 05 26 Grounding and Bonding for Electrical Systems
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for grounding and bonding system components . X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 22 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
26 05 29 Hangers and Supports for Electrical Systems
1.03B
Product Data: Provide manufacturer's standard catalog pages and data sheets for channel (strut) framing systems, non-penetrating rooftop supports, and post-installed concrete and masonry anchors . X
26 05 33.13 Conduit for Electrical Systems
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for conduits and fittings . X
23 05 33.16 Boxes for Electrical Systems
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for cabinets and enclosures, boxes for hazardous (classified) locations, floor boxes, and underground boxes/enclosures . X
26 05 53 Identification for Electrical Systems
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for each product . X
26 05 83 Wiring Connections
1.04A
Product Data: Provide wiring device manufacturer’s catalog information showing dimensions, configurations, and construction. X
26 22 00 Low-Voltage Transformers
1.04B
Product Data: Include voltage, kVA, impedance, tap configurations, insulation system class and rated temperature rise, efficiency, sound level, enclosure ratings, outline and support point dimensions, weight, required clearances, service condition requirements, and installed features. X
26 24 16 Panelboards
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 23 of 24
Project Title:
REPLACE / UPGRADE HVAC SYSTEMS – NATCHEZ
VISITOR CENTER
SUBMITTAL REQUIREMENTS
(Indicate with X)
INFORMATIONAL
S P
E C
IF
IC
A T
IO
N
S E
C T
IO
N
P A
R A
G R
A P
H N
U M
B E
R
DESCRIPTION
C E
R T
IF
IC
A T
IO
N
S
B O
R A
T O
S T
S
R E
P O
R T
S
L C
U L A
T
IO
N
S O R
P L A
N
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
O T
H E
R
S A
M P
L E
S
S H
A W
IN
G
S
M A
N U
F A
C T
U R
E R
D A
T A
A
T R
U C
T
IO
N S
ACTION
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for panelboards, enclosures, overcurrent protective devices, and other installed components and accessories. X
26 27 26 Wiring Devices
1.04B
Product Data: Provide manufacturer's catalog information showing dimensions, colors, and configurations. X
26 28 16.16 Enclosed Switches
1.04B
Product Data: Provide manufacturer's standard catalog pages and data sheets for enclosed switches and other installed components and accessories. X
Submittal List with Review Estimate Template | National Park Service (NPS) - Denver Service Center (DSC) page 24 of 24