SALEM NHP - FIRE ALARM/SPRINKLER INSP, TEST, MAINT
Solicitation number
140P4326Q0064
Issued by

About this file

This is Amendment 0001 to Request for Proposals (RFP) Number 140P4326Q0064 for fire alarm detection and suppression system inspections, maintenance, and repairs at Salem Maritime National Historical Park (including the replica ship Friendship of Salem) and Saugus Iron Works National Historic Site. The amendment, effective August 26, 2026, provides responses to eight questions received from potential offerors regarding system specifications, contractor responsibilities, wage determinations, and proposal submission requirements.

Key clarifications include: replacement fire alarm communication protocols now utilize Starlink cell radio at the Custom House and Narbonne House (monitored by NOREL) and AES Radio at St. Joseph Hall (monitored by American Alarm and Signal); contractors are responsible for connection testing and verification to existing central security alarm monitoring stations under base contract lines, with responsibility for establishing or modifying replacement reporting paths only if optional CLINs 00060-00065 are awarded; on-site fire watch supervision requires contractor staff presence during system testing, with minimal staffing needed if unexpected offline periods occur; contractors must furnish AES transceivers, antenna systems, and related equipment, with flexibility to substitute cellular radio if cost-effective; equivalent professional manufacturer training or third-party marine gaseous suppression system certifications are acceptable alternatives to factory-direct Kidde Marine certification; material markup percentages for unscheduled repairs should be entered in Attachment 2 Bid Schedule Row 58; contractors must propose a single baseline labor rate compliant with both Essex County (WD 2015-4067) and Middlesex/Suffolk Area (WD 2015-4065) wage determinations for on-call time and materials repair line items; there is no current incumbent; and device counts are available in the November 2025 fire alarm inspection and June 2026 sprinkler inspection reports provided as part of the amendment. The amendment also includes comprehensive fire alarm inspection reports from November 2025 documenting all tested devices, equipment specifications, and system inventories across eight Salem Maritime and one Saugus location.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: is not is required copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7.ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

PAGESOF

Contractor

The hour and date specified for receipt of Offers to sign this document and return

Jason Albright

See continuation page

NPS, NER - NE MABO

Boston National Historical Park Charlestown Navy Yard Building I-1 Boston MA 02129-4543

PNN

140P4326Q0064

09/09/2026

08/26/2026

1 177

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGES

NAME OF OFFEROR OR CONTRACTOR

SUPPLIES/SERVICES

(B)

UNIT

(D)

UNIT PRICE

(E)

AMOUNT

(F)

OPTIONAL FORM 336 (4-86)

Sponsored by GSA FAR (48 CFR) 53.110

ITEM NO.

(A)

QUANTITY

(C)

NSN 7540-01-152-8067

140P4326Q0064/0001

Fire alarm detection and suppression system inspections, maintenance, and repairs at Salem

Maritime NHP (including replica ship Friendship of Salem), and Saugus Iron Works NHS.

The purpose of this amendment is to provide a copy of the sign-in sheet from the organized site-visit, provide a response to questions received, provide prior fire alarm reports and sprinkler reports, and provide a photo of the ship panel.

Period of Performance: 10/01/2026 to

09/30/2027

Request for Proposal Number 140P4326Q0064 Fire Alarm/Sprinkler System Inspection, Testing, Maintenance, and Repair at Salem Maritime National Historical Park and Saugus Iron Works National Historic Site Amendment 0001

DESCRIPTION OF AMENDMENT/MODIFICATION

The following are a list of questions received for the Solicitation Number 140P4326Q0064, Fire Alarm/Sprinkler System Inspection, Testing, Maintenance, and Repair at Salem Maritime National Historical Park and Saugus Iron Works National Historic Site.

1) Salem Replacement Reporting Mechanism (SOW Section 1.2 & SOW Section 4.1) The Statement of Work notes that the municipal fire alarm master boxes in the two Salem locations were discontinued in June 2026, and that "the replacement reporting mechanism is not yet established". To ensure accurate pricing under the scheduled base line items

(CLIN 00010):

(a) What is the active replacement communication protocol or signal reporting mechanism currently utilized for the Salem buildings?

Answer: Starlink cell radio has replaced city fire box as primary communication in the Custom House (main panel that covers this building and 5 others) and Narbonne House and these locations are being monitored by NOREL. AES Radio has replaced city fire box (in conjunction with 2 phone lines) for St. Joseph Hall and is being monitored by American Alarm and Signal.

(b) Is the awardee responsible for establishing, installing, or programmatically modifying any replacement reporting path, or will the contractor's scope be limited strictly to connection testing and verification to the existing central security alarm monitoring station?

Answer: Base contract lines CLINs 00010, 11, 12, 20, 21, 22) for annual inspection and PMs include the latter (“connection testing and verification to the existing central security alarm monitoring station”). If and only if one or all of options in CLINs 00060, 61, 62, 63, 64 or 65 are awarded will the contractor be responsible for the former (“establishing, installing, or programmatically modifying any replacement reporting path) in the locations awarded.

2) On-Site Supervision & Fire Watch Requirements (SOW Section 1.2) The SOW states that the awardee is responsible for "supervision of buildings while fire alarms are disconnected, for all base and option lines". Given the historical landmark status and irreplaceable collections in these structures:

(a) Does this "supervision" require the contractor to provide dedicated, continuous on-site personnel to perform a physical, continuous Fire Watch in each building while systems are offline for testing? Answer: If the contractor staff is in the building and performing testing this requirement is met, If they need to leave briefly and the system is not functioning, they must coordinate the watch requirements themselves or with the COR.

(b) If a contractor-provided Fire Watch is mandatory, could the Government specify the minimum staffing and hourly surveillance coverage requirements expected during offline testing windows? Answer: In the rare and unexpected event this is required, one person would be sufficient, and watch details and payment would be coordinated with the COR. Contractor will make all reasonable efforts to avoid

National Historical Park and Saugus Iron Works National Historic Site Amendment 0001 situations where fire watch is required outside of business hours and is related to fixed price lines under this contract.

3) AES Radio Installation Options and Equipment Sourcing (CLINs 00060–00065 & SOW

Section 1.2) For the options to install code-compliant AES radio communications, please clarify the following technical parameters:

(a) Is the contractor required to furnish the AES transceivers, antenna systems, coaxial cabling, and power supplies, or is this equipment provided as Government-Furnished Property (GFP)? Answer: Contractor supplied.

(b) If Contractor-Furnished, does the Park have pre-approved manufacturer brands and specific model numbers compatible with the local municipal receiver network? Answer: If installed, awardee would take over monitoring after installation, so it must be compatible with their network.

(c) Given the strict historical preservation rules, are there specific exterior antenna placement limitations or non-destructive mounting methods that must be factored into our installation labor pricing. Answer: specific requirements in SOW to meet historic preservation rules must be followed, but bidders should assume this installation would be close proximity to the panels working within the standard kit antenna wire length of approximately 25’, and also placed in building interiors in the same or similar and adjacent spaces to where the panel is located. If signal is not strong enough to support functionality in such a location and longer wire runs and/or exterior antenna placement becomes required, NPS understands additional discussions and funds will be required.

NOTE: In reply to a question/suggestion posed at the walk-through on 9/3/26: For CLINs 00060–00065, bidders may substitute Cellular Radio for AES if they believe it can be done at a lower cost and improves or has the same likelihood of receiving sufficient signal when installed in such a location as described in 3)c) above. If bidders opt to do this, please include this cost in the proposal and note that pricing is for Cellular Radio. Alternately they can include both the aes and cellular radion price clearly marked for each CLIN, and NPS will calculate the total contract value using the higher number.

4) Kidde Marine FM-200 Specialized Training (SOW Section 1.4.5 & Factor 1) SOW

Section 1.4.5 states that the senior inspector "must document that they have been trained to service Kidde marine FM-200 systems". Will the Government accept equivalent professional manufacturer training or third-party specialized marine gaseous suppression system certifications (such as certified technicians on NFPA 2001 systems), or is a factory-direct certification issued exclusively by Kidde Marine mandatory to be deemed technically acceptable under Factor 1?

Answer: Other equivalent certifications and training will be accepted.

National Historical Park and Saugus Iron Works National Historic Site Amendment 0001

5) Time & Materials (T&M) Material Mark-up Proposal Structure (SOW Section 3.3.10.2)

SOW Section 3.3.10.2 (Material Costs) states that bidders will include with their proposal the percentage of material markup to be applied to supply and equipment purchases for unscheduled repairs. However, Attachment 2 (Bid Schedule) does not contain a dedicated field, formula cell, or CLIN for the entry of this percentage markup. Could the Government clarify where within the submission package or Excel sheet bidders should formally document their proposed material markup percentage?

Answer: Attachment 2 - Bid Schedule, Row 58 contains the cells for material mark-up percentages.

6) Location-Specific SCLS Wage Rate Applicability (DOL Wage Determinations) The solicitation incorporates two distinct DOL Wage Determinations: Essex County (WD 2015-4067) for Salem Maritime and Middlesex/Suffolk Area (WD 2015-4065) for Saugus Iron Works. For the on-call, unscheduled Time & Material repair line items (CLINs 00070–00072), should the contractor separate and propose distinct labor rates by location/county, or will one baseline wage determination govern the consolidated repair CLINs?

Answer: Repairs under these line items may be for either location. Therefore, there should be a single proposed labor rate that is in compliance with both wage determinations.

7) Is currently an incumbent? If so, who was the previous awardee, contract number, and value?

Answer: There is no current incumbent.

8) Could you provide a device count for fire alarm systems for all buildings?

Answer: Device counts can be found in the reports from annual inspections. Annual Inspections from November 2025 Fire Alarms, and June 2026 Sprinklers are provided as part of this amendment.

In reply to a question/suggestion posed at the walk-through on 9/3/26: Please also see photos of the Ship combined fire alarm and security alarm panel, as requested on the walk through 9/3/26.

160 DERBY ST - SHIP

160 DERBY ST

SHIP

SALEM, MA 01970

978-360-2080

Building Contact: JEREMY BUNAGIN Title: SITE CONTACT

Company: Norel Service Company, Inc.

Contact: Evan Olson Title: tester

Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards

Fire Alarm Systems

INSPECTION

CERTIFICATE

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Page of 2 8 Executive Summary

Norel Service Company, Inc. Download Date: 09/01/2026

Building: 160 DERBY ST - SHIPCompany: Norel Service Company, Inc.

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information

160 DERBY ST - SHIP

160 DERBY ST

SHIP

SALEM, MA 01970

United States of America

Contact: JEREMY BUNAGIN

Phone: 978-360-2080

Fax:

Mobile:

Email: Jeremy_Bunagin@nps.gov

Inspection Performed By Norel Service Company, Inc.

1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America

Inspector: Evan Olson

Phone: (781) 768-5500

Fax:

Mobile:

Email: wdwyer@norelservice.com

System Control Unit Manufacturer: burg system Inspection Date: 11/25/2025 IDC Style:

Model Number: Install Date: 11/20/2023 SLC Style:

Software Version: Version Date: 11/20/2023 NAC Style:

Location: 1st by staircase Disconnect Location: Disconnect Type:

Current Protection:

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 1 7.69% 1 100.00% 1 100.00% 0 0.00%

Initiating 12 92.31% 12 100.00% 12 100.00% 0 0.00%

Totals 13 100% 13 100.00% 13 100.00% 0 0.00%

Certification

Page of 3 8

Norel Service Company, Inc. Download Date: 09/01/2026

Contact: JEREMY BUNAGINInspector: Evan Olson

Signed: Nov 25, 2025

Page of 4 8 Notes & Recommendations

Norel Service Company, Inc. Download Date: 09/01/2026

NOTES & RECOMMENDATIONS

Generated by: BuildingReports.com

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note

11/25/25 Tested all FA Burglar Panel left normal Monitoring to be put back online by customer Cleaned out smokes

Page of 5 8 Inspection & Testing

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - burg systemBuilding: 160 DERBY ST - SHIP

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

PASSED

Control

Control Panel 1st by staircase Tested 12:00:41 PM 11/25/2025

Initiating

CO Detector tween decks Tested 11:55:44 AM 11/25/2025

CO Detector tween decks mizzen mast Tested 11:48:33 AM 11/25/2025

Heat Detector under tween decks by electrical panels Tested 11:56:12 AM 11/25/2025

Heat Detector under tween decks engine room Tested 11:56:55 AM 11/25/2025

Heat Detector under tween decks fore mast hold Tested 11:42:34 AM 11/25/2025

Smoke Detector tween decks by fire system storage Tested 11:58:19 AM 11/25/2025

Smoke Detector tween decks by stairs Tested 11:46:12 AM 11/25/2025

Smoke Detector tween decks for mest Tested 11:36:57 AM 11/25/2025

Smoke Detector under tween decks four peak Tested 11:40:25 AM 11/25/2025

Smoke Detector under tween decks hole number 2 Tested 11:45:08 AM 11/25/2025

Smoke Detector under tween decks laz Tested 11:53:45 AM 11/25/2025

Smoke Detector under tween decks tank compartment Tested 11:54:50 AM 11/25/2025

Page of 6 8 Service Summary

Norel Service Company, Inc. Download Date: 09/01/2026

SERVICE SUMMARY

Generated by: BuildingReports.com

The Service Summary section provides an overview of the services performed in this report.

Building: 160 DERBY ST - SHIP

Device Type Service Quantity

PASSED

CO Detector Tested 2

Control Panel Tested 1

Heat Detector Tested 3

Smoke Detector Tested 7

Total 13

Grand Total 13

Page of 7 8 Inventory & Warranty Report

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - burg systemBuilding: 160 DERBY ST - SHIP

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: 160 DERBY ST - SHIP

Device or Type Category % of Inventory Quantity

CO Detector Initiating 15.38% 2

Control Panel Control 7.69% 1

Heat Detector Initiating 23.08% 3

Smoke Detector Initiating 53.85% 7

Type Qty Model # Description Install Date

IN SERVICE - 2 YEARS TO 3 YEARS

burg system

Control Panel 1 11/20/2023

IN SERVICE - 5 YEARS TO 10 YEARS

Edwards

Heat Detector 1 282B-PL 11/20/2016

Heat Detector 2 604 11/20/2016

System Sensor

CO Detector 2 11/20/2016

Smoke Detector 7 2WB 11/20/2016

Page of 8 8 Zone Address Report

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - burg systemBuilding: 160 DERBY ST - SHIP

ZONE ADDRESS REPORT

Generated by: BuildingReports.com

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

ZONE/CIRCUIT:

Zone 1 Smoke Detector tween decks by fire system storage 85881417

Zone 1 Smoke Detector tween decks by stairs 85881441

Zone 1 Smoke Detector tween decks for mest 85881416

Zone 1 Heat Detector under tween decks by electrical panels 85881440

Zone 1 Heat Detector under tween decks engine room 85881427

Zone 1 Heat Detector under tween decks fore mast hold 85881425

Zone 1 Smoke Detector under tween decks four peak 85881443

Zone 1 Smoke Detector under tween decks hole number 2 85881444

Zone 1 Smoke Detector under tween decks laz 85881424

Zone 1 Smoke Detector under tween decks tank compartment 85881428

Zone 27 CO Detector tween decks 85881430

Zone 27 CO Detector tween decks mizzen mast 85881418

160 DERBY ST ST - JOSEPH'S HALL

160 DERBY ST

SALEM, MA 01970

978-360-2080

Building Contact: JEREMY BUNAGIN Title: SITE CONTACT

Company: Norel Service Company, Inc.

Contact: TYLER RUTINA Title: tester

Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards

Fire Alarm Systems

INSPECTION

CERTIFICATE

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for

Page of 2 15

Norel Service Company, Inc. Download Date: 09/01/2026

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information

160 DERBY ST ST - JOSEPH'S HALL

160 DERBY ST

SALEM, MA 01970

United States of America

Contact: JEREMY BUNAGIN

Phone: 978-360-2080

Fax:

Mobile:

Email: Jeremy_Bunagin@nps.gov

Inspection Performed By Norel Service Company, Inc.

1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America

Inspector: TYLER RUTINA

Phone: (781) 768-5500

Fax:

Mobile:

Email: wdwyer@norelservice.com

System Control Unit Manufacturer: Notifier Inspection Date: 11/25/2025 IDC Style:

Model Number: NFS 320 Install Date: 11/04/2024 SLC Style:

Software Version: Version Date: 11/04/2024 NAC Style:

Location: 1st Inside FACP Room Disconnect Location: 1st Inside FACP Room

Disconnect Type:

Current Protection:

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 5 10.87% 5 100.00% 5 100.00% 0 0.00%

Indicating 4 8.70% 4 100.00% 4 100.00% 0 0.00%

Initiating 37 80.43% 37 100.00% 37 100.00% 0 0.00%

Totals 46 100% 46 100.00% 46 100.00% 0 0.00%

Page of 3 15

Norel Service Company, Inc. Download Date: 09/01/2026

Building: 160 DERBY ST ST - JOSEPH'S HALL Contact: JEREMY BUNAGIN

Company: Norel Service Company, Inc.

Inspector: TYLER RUTINA

Signed: Nov 25, 2025

Page of 4 15

Norel Service Company, Inc. Download Date: 09/01/2026

NOTES & RECOMMENDATIONS

Generated by: BuildingReports.com

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note

11/25/2025 Completed testing of 100% of fire alarm devices and all audibles.

Cleaned out smoke detectors.

Panel normal upon departure.

Customer to notify central station.

Fire department notified.

Page of 5 15

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

PASSED

Control

Annunciator 1st By Front Entrance Tested 10:40:19 AM 11/25/2025

Battery 1st Inside FACP Tested 10:13:00 AM 11/25/2025

Battery 1st Inside FACP Tested 10:13:08 AM 11/25/2025

Control Panel 1st Inside FACP Room Tested 10:12:49 AM 11/25/2025

Disconnect 1st Inside FACP Room Tested 10:12:41 AM 11/25/2025

Indicating

Horn/Strobe Basement Inside All Areas Tested 10:47:59 AM 11/25/2025

Horn/Strobe 1st Inside All Areas Tested 10:47:56 AM 11/25/2025

Horn/Strobe 2nd Inside All Areas Tested 10:47:54 AM 11/25/2025

Horn/Strobe 3rd Inside All Areas Tested 10:47:52 AM 11/25/2025

Initiating

Duct Detector 1st Inside FACP Room RTU-1 Tested 10:13:22 AM 11/25/2025

Duct Detector 1st Inside FACP Room RTU-2 Tested 10:13:26 AM 11/25/2025

Duct Detector 1st Inside FACP Room RTU-3A Tested 10:44:50 AM 11/25/2025

Duct Detector 1st Inside FACP Room RTU-3B Tested 10:13:33 AM 11/25/2025

Duct Detector 1st Inside FACP Room RTU-4 Tested 10:13:35 AM 11/25/2025

Duct Detector 1st Inside FACP Room RTU-5 Tested 10:13:37 AM 11/25/2025

Duct Detector 1st Inside FACP Room RTU-6 Tested 10:13:38 AM 11/25/2025

Heat Detector Basement Inside Basement Electrical Room Tested 10:37:47 AM 11/25/2025

Page of 6 15

Norel Service Company, Inc. Download Date: 09/01/2026

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Masterbox 1st Inside Carpentry Shop Masterbox #141 Tested 10:12:44 AM 11/25/2025

Pull Station Basement By Rear Stairwell Tested 10:38:23 AM 11/25/2025

Pull Station 1st By Front Entrance Tested 10:40:26 AM 11/25/2025

Pull Station 1st By Side Exit Inside Hallway (Pelfry Court Exit)

Tested 10:14:51 AM 11/25/2025

Pull Station 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)

Tested 10:39:09 AM 11/25/2025

Pull Station 1st By Side Exit Inside Stairwell (Pelfry Court Exit)

Tested 10:15:36 AM 11/25/2025

Pull Station 1st Inside Side Stairwell By Exit (Derby Street Exit)

Tested 10:19:11 AM 11/25/2025

Pull Station 2nd By Side Exit To Front Stairwell Tested 10:17:47 AM 11/25/2025

Pull Station 3rd Inside Main Hallway Tested 10:23:33 AM 11/25/2025

Pull Station 3rd Inside Main Hallway By Front Stairwell Tested 10:25:31 AM 11/25/2025

Smoke Detector Basement Inside Basement By Elevator Machine Room

Tested 10:34:47 AM 11/25/2025

Smoke Detector Basement Inside Basement By Rear Stairwell Tested 10:34:17 AM 11/25/2025

Smoke Detector Basement Inside Basement Inside Rear Stairwell

Tested 10:33:49 AM 11/25/2025

Smoke Detector Basement Inside Basement Inside Stairwell Tested 10:36:56 AM 11/25/2025

Smoke Detector 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)

Tested 10:14:58 AM 11/25/2025

Smoke Detector 1st Inside Hallway By Side Exit (Pelfry Court Exit)

Tested 10:26:40 AM 11/25/2025

Smoke Detector 1st Inside Side Stairwell By Side Exit (Pelfry Court Exit)

Tested 10:15:44 AM 11/25/2025

Smoke Detector 1st Left Side Carpentry Shop Tested 10:13:55 AM 11/25/2025

Smoke Detector 1st Left Side Carpentry Shop Tested 10:40:06 AM 11/25/2025

Smoke Detector 1st Right Side Carpentry Shop Tested 10:30:16 AM 11/25/2025

Page of 7 15

Norel Service Company, Inc. Download Date: 09/01/2026

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit) Tested 10:20:46 AM 11/25/2025

Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit) Tested 10:22:17 AM 11/25/2025

Smoke Detector 2nd Inside Rear Stairwell Tested 10:23:16 AM 11/25/2025

Smoke Detector 2nd Inside Side Stairwell Hallway (Derby Street Exit)

Tested 10:20:29 AM 11/25/2025

Smoke Detector 3rd Inside Front Stairwell Tested 10:25:59 AM 11/25/2025

Smoke Detector 3rd Inside Main Hallway Tested 10:23:54 AM 11/25/2025

Smoke Detector 3rd Inside Main Hallway By Front Stairwell Tested 10:25:07 AM 11/25/2025

Smoke Detector 3rd Inside Main Hallway By Skylight Tested 10:24:30 AM 11/25/2025

Smoke Detector 3rd Inside Rear Stairwell Tested 10:23:05 AM 11/25/2025

Page of 8 15

Norel Service Company, Inc. Download Date: 09/01/2026

SERVICE SUMMARY

Generated by: BuildingReports.com

The Service Summary section provides an overview of the services performed in this report.

Building: 160 DERBY ST ST - JOSEPH'S HALL

Device Type Service Quantity

PASSED

Annunciator Tested 1

Battery, Sealed Lead Acid Tested 2

Control Panel Tested 1

Disconnect Tested 1

Duct Detector Tested 7

Heat Detector Tested 1

Horn/Strobe Tested 4

Masterbox Tested 1

Pull Station Tested 9

Smoke Detector, Photoelectric Tested 19

Total 46

Grand Total 46

Page of 9 15 Sound and Visual Testing

Norel Service Company, Inc. Download Date: 09/01/2026

SOUND AND VISUAL TESTING

Generated by: BuildingReports.com

The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.

Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.

Building: 160 DERBY ST ST - JOSEPH'S HALL

Audible/Visual Appliances Location Comment Ambient Alarm Synched ScanID

PASSED

Horn/Strobe

Basement Inside All Areas Passed ☐ 94111163

1st Inside All Areas Passed ☐ 94111193

2nd Inside All Areas Passed ☐ 94111195

3rd Inside All Areas Passed ☐ 94111203

Page of 10 15 Battery & Power Supply Testing

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL

BATTERY & POWER SUPPLY TESTING

Generated by: BuildingReports.com

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated

Ah Rated Volts

Pre Test

Post Test

Min Ah

Teste d Ah

MFG

Date

PASSED

Sealed Lead Acid 1st Inside FACP 18 12 11/04 /2024

Sealed Lead Acid 1st Inside FACP 18 12 11/04 /2024

Page of 11 15

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: 160 DERBY ST ST - JOSEPH'S HALL

Device or Type Category % of Inventory Quantity

Annunciator Control 2.17% 1

Battery Control 4.35% 2

Control Panel Control 2.17% 1

Disconnect Control 2.17% 1

Duct Detector Initiating 15.22% 7

Heat Detector Initiating 2.17% 1

Horn/Strobe Indicating 8.70% 4

Masterbox Initiating 2.17% 1

Pull Station Initiating 19.57% 9

Smoke Detector Initiating 41.30% 19

Type Qty Model # Description Install Date

IN SERVICE - 1 YEAR TO 2 YEARS

Gamewell

Masterbox 1 11/04/2024

Interstate

Battery 2 SLA1115 Sealed Lead Acid 11/04/2024

Notifer

Heat Detector 1 FSP-951 11/04/2024

Pull Station 9 NBG-12LX 11/04/2024

Page of 12 15

Norel Service Company, Inc. Download Date: 09/01/2026

Type Qty Model # Description Install Date

IN SERVICE - 1 YEAR TO 2 YEARS (continued)

Notifer (continued)

Smoke Detector 19 FSP-951 Photoelectric 11/04/2024

Notifier

Annunciator 1 11/04/2024

Control Panel 1 NFS 320 11/04/2024

System Sensor

Duct Detector 7 11/04/2024

Horn/Strobe 4 P2R 11/04/2024

(manufacturer not specified)

Disconnect 1 11/04/2024

Page of 13 15

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL

ZONE ADDRESS REPORT

Generated by: BuildingReports.com

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

ZONE/CIRCUIT:

L1D011 Smoke Detector 1st Left Side Carpentry Shop Photoelectric 94111172

L1D012 Smoke Detector 1st Right Side Carpentry Shop Photoelectric 94111174

L1D013 Smoke Detector 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)

Photoelectric 94111212

L1D018 Smoke Detector 1st Inside Side Stairwell By Side Exit (Pelfry Court Exit)

Photoelectric 94111158

L1D018 Smoke Detector 1st Left Side Carpentry Shop Photoelectric 94111164

L1D019 Smoke Detector 1st Inside Hallway By Side Exit (Pelfry Court Exit)

Photoelectric 94111166

L1D023 Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit)

Photoelectric 94111162

L1D023 Smoke Detector 2nd Inside Side Stairwell Hallway (Derby Street Exit)

Photoelectric 94111154

L1D027 Duct Detector 1st Inside FACP Room RTU-3A 94111196

L1D027 Duct Detector 1st Inside FACP Room RTU-3B 94111192

L1D028 Duct Detector 1st Inside FACP Room RTU-2 94111176

L1D029 Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit)

Photoelectric 94111188

L1D029 Smoke Detector 2nd Inside Rear Stairwell Photoelectric 94111182

L1D031 Smoke Detector 3rd Inside Main Hallway By Front Stairwell Photoelectric 94111187

L1D032 Smoke Detector 3rd Inside Main Hallway By Skylight Photoelectric 94111184

L1D033 Smoke Detector 3rd Inside Main Hallway Photoelectric 94111210

Page of 14 15

Norel Service Company, Inc. Download Date: 09/01/2026

Address Device Type Location Type ScanID

ZONE/CIRCUIT: (continued)

L1D034 Smoke Detector 3rd Inside Rear Stairwell Photoelectric 94111181

L1D036 Smoke Detector 3rd Inside Front Stairwell Photoelectric 94111183

L1D037 Duct Detector 1st Inside FACP Room RTU-5 94111215

L1D038 Duct Detector 1st Inside FACP Room RTU-6 94111214

L1D039 Duct Detector 1st Inside FACP Room RTU-4 94111213

L1D041 Smoke Detector Basement Inside Basement Inside Stairwell Photoelectric 94111217

L1D042 Heat Detector Basement Inside Basement Electrical Room 94111207

L1D043 Duct Detector 1st Inside FACP Room RTU-1 94111175

L1D044 Smoke Detector Basement Inside Basement By Rear Stairwell

Photoelectric 94111205

L1D045 Smoke Detector Basement Inside Basement By Elevator Machine Room

Photoelectric 94111206

L1D047 Smoke Detector Basement Inside Basement Inside Rear Stairwell

Photoelectric 94111204

L1M011 Pull Station 1st By Front Entrance 94111173

L1M013 Pull Station 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)

94111216

L1M013 Masterbox 1st Inside Carpentry Shop Masterbox #141 94111167

L1M013 Pull Station 1st Inside Side Stairwell By Exit (Derby Street Exit)

94111165

L1M014 Pull Station 1st By Side Exit Inside Stairwell (Pelfry Court Exit)

94111161

L1M015 Pull Station 1st By Side Exit Inside Hallway (Pelfry Court Exit)

94111201

L1M021 Pull Station 2nd By Side Exit To Front Stairwell 94111159

L1M031 Pull Station 3rd Inside Main Hallway By Front Stairwell 94111211

L1M032 Pull Station 3rd Inside Main Hallway 94111209

L1M049 Pull Station Basement By Rear Stairwell 94111208

ZONE/CIRCUIT: CIRCUIT #16

Page of 15 15

Norel Service Company, Inc. Download Date: 09/01/2026

Address Device Type Location Type ScanID

ZONE/CIRCUIT: CIRCUIT #16 (continued)

Disconnect 1st Inside FACP Room 39060097

174 DERBY ST HAWKES HSE

/GARDEN SHED

174 DERBY ST

GARDEN SHED

SALEM, MA 01970

978-360-2080

Building Contact: JEREMY BUNAGIN Title: SITE CONTACT

Company: Norel Service Company, Inc.

Contact: Evan Olson Title: tester

Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards

Fire Alarm Systems

INSPECTION

CERTIFICATE

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for

Page of 2 7

Norel Service Company, Inc. Download Date: 09/01/2026

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information

174 DERBY ST HAWKES HSE/GARDEN

SHED

174 DERBY ST

GARDEN SHED

SALEM, MA 01970

United States of America

Contact: JEREMY BUNAGIN

Phone: 978-360-2080

Fax:

Mobile:

Email: Jeremy_Bunagin@nps.gov

Inspection Performed By Norel Service Company, Inc.

1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America

Inspector: Evan Olson

Phone: (781) 768-5500

Fax:

Mobile:

Email: wdwyer@norelservice.com

System Control Unit Manufacturer: Bosch Inspection Date: 11/25/2025 IDC Style:

Model Number: l Install Date: 04/01/2024 SLC Style:

Software Version: Version Date: 12/31/1969 NAC Style:

Location: 1st burglar panel inside Hawkes house

Disconnect Location: Disconnect Type:

Current Protection:

Central Station Signal Verification Type: Mfg: AES Model #: 7788F

Test Time/Date: 11/25/25 10:12:57 AM Restore Time: Note:

Page of 3 7

Norel Service Company, Inc. Download Date: 09/01/2026

Building: 174 DERBY ST HAWKES HSE

/GARDEN SHED

Contact: JEREMY BUNAGIN

Company: Norel Service Company, Inc.

Inspector: Evan Olson

Signed: Nov 25, 2025

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 2 66.67% 2 100.00% 2 100.00% 0 0.00%

Initiating 1 33.33% 1 100.00% 1 100.00% 0 0.00%

Totals 3 100% 3 100.00% 3 100.00% 0 0.00%

Page of 4 7

Norel Service Company, Inc. Download Date: 09/01/2026

NOTES & RECOMMENDATIONS

Generated by: BuildingReports.com

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note

11/25/25 Tested 100% of FA devices Monitoring to be restored by customer

Page of 5 7

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 2 - Bosch lBuilding: 174 DERBY ST HAWKES HSE/GARDEN

SHED

Control Panel: 1Building: 174 DERBY ST HAWKES HSE/GARDEN

SHED

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

PASSED

Control

Communicator 1st inside hawkes house (instant alarm) Tested 10:12:57 AM 11/25/2025

Device Type Location Service Time Date

PASSED

Control

Control Panel 1st burglar panel inside Hawkes house Tested 10:12:54 AM 11/25/2025

Initiating

Heat Detector 1st inside garden shed (trips burg panel) Tested 10:04:10 AM 11/25/2025

Page of 6 7

Norel Service Company, Inc. Download Date: 09/01/2026

SERVICE SUMMARY

Generated by: BuildingReports.com

The Service Summary section provides an overview of the services performed in this report.

Building: 174 DERBY ST HAWKES HSE/GARDEN SHED

Device Type Service Quantity

PASSED

Communicator Tested 1

Control Panel Tested 1

Heat Detector Tested 1

Total 3

Grand Total 3

Page of 7 7

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 2 - Bosch lBuilding: 174 DERBY ST HAWKES HSE/GARDEN

SHED

Control Panel: 1Building: 174 DERBY ST HAWKES HSE/GARDEN

SHED

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: 174 DERBY ST HAWKES HSE/GARDEN SHED

Device or Type Category % of Inventory Quantity

Communicator Control 33.33% 1

Control Panel Control 33.33% 1

Heat Detector Initiating 33.33% 1

Type Qty Model # Description Install Date

IN SERVICE - 2 YEARS TO 3 YEARS

AES

Communicator 1 7788F 04/01/2024

Type Qty Model # Description Install Date

IN SERVICE - 2 YEARS TO 3 YEARS

Bosch

Control Panel 1 l 04/01/2024

Honeywell

Heat Detector 1 604 04/01/2024

176 DERBY ST

176 DERBY ST

CUSTOMS HSE, NARBONE HSE,DERBY & HAWKES HOUSE

SALEM, MA 01970

978-360-2080

Building Contact: JEREMY BUNAGIN Title: SITE CONTACT

Company: Norel Service Company, Inc.

Contact: Evan Olson Title: tester

Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards

Fire Alarm Systems

INSPECTION

CERTIFICATE

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for

Page of 2 23

Norel Service Company, Inc. Download Date: 09/01/2026

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information

176 DERBY ST

176 DERBY ST

CUSTOMS HSE, NARBONE HSE,DERBY

& HAWKES HOUSE

SALEM, MA 01970

United States of America

Contact: JEREMY BUNAGIN

Phone: 978-360-2080

Fax:

Mobile:

Email: Jeremy_Bunagin@nps.gov

Inspection Performed By Norel Service Company, Inc.

1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America

Inspector: Evan Olson

Phone: (781) 768-5500

Fax:

Mobile:

Email: wdwyer@norelservice.com

System Control Unit Manufacturer: Siemens Inspection Date: 11/25/2025 IDC Style:

Model Number: CP-35 Install Date: 11/20/2023 SLC Style:

Software Version: Version Date: 11/20/2023 NAC Style:

Location: Basement inside customs house

Disconnect Location: Basement inside customs house near FACP

Disconnect Type:

Current Protection:

Central Station Signal Verification Type: Digital Communicator Mfg: AES Model #: 7788F

Test Time/Date: 11/25/25 7:31:20 AM Restore Time: Note:

Page of 3 23

Norel Service Company, Inc. Download Date: 09/01/2026

Building: 176 DERBY ST Contact: JEREMY BUNAGIN

Company: Norel Service Company, Inc.

Inspector: Evan Olson

Signed: Nov 25, 2025

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 18 15.65% 18 100.00% 18 100.00% 0 0.00%

Indicating 4 3.48% 4 100.00% 4 100.00% 0 0.00%

Initiating 93 80.87% 93 100.00% 93 100.00% 0 0.00%

Totals 115 100% 115 100.00% 115 100.00% 0 0.00%

Page of 4 23

Norel Service Company, Inc. Download Date: 09/01/2026

NOTES & RECOMMENDATIONS

Generated by: BuildingReports.com

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note

11/25/25 Tested all FA devices with all AVs Panel left normal

Masterbox box back online by city of Salem

Page of 5 23

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 1 - Siemens CP-35Building: 176 DERBY ST

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

PASSED

Control

Battery Basement inside Communicator Customs house

Tested 7:37:01 AM 11/25/2025

Battery Basement inside customs house FACP Tested 7:29:41 AM 11/25/2025

Battery Basement inside customs house FACP Tested 7:29:50 AM 11/25/2025

Communicator Basement inside customs house Tested 7:31:20 AM 11/25/2025

Control Panel Basement inside customs house Tested 7:29:31 AM 11/25/2025

Disconnect Basement inside customs house near FACP Tested 7:30:47 AM 11/25/2025

Indicating

Horn All inside customs house Tested 7:29:26 AM 11/25/2025

Initiating

Heat Detector Basement inside customs house Inside storage behind kitchen

Tested 7:36:18 AM 11/25/2025

Heat Detector Basement inside customs house engine room

Tested 7:42:12 AM 11/25/2025

Heat Detector Basement inside customs house engine room

Tested 7:42:16 AM 11/25/2025

Heat Detector Basement inside customs house inside kitchen

Tested 7:34:58 AM 11/25/2025

Heat Detector Basement inside customs house near kitchen

Tested 7:42:05 AM 11/25/2025

Heat Detector Basement inside customs house near office Tested 7:42:08 AM 11/25/2025

Page of 6 23

Norel Service Company, Inc. Download Date: 09/01/2026

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Heat Detector Basement inside customs house near stairs Tested 7:41:58 AM 11/25/2025

Heat Detector 1st inside shed (reports to burglar panel) Tested 9:40:01 AM 11/25/2025

Masterbox Basement inside customs house #155 Tested 7:29:35 AM 11/25/2025

Pull Station Basement inside customs house near entrance

Tested 7:31:26 AM 11/25/2025

Pull Station 1st inside front room customs house Tested 9:39:37 AM 11/25/2025

Smoke Detector Basement inside front storage customs house

Tested 8:05:46 AM 11/25/2025

Smoke Detector Basement inside rear storage customs house Tested 8:05:42 AM 11/25/2025

Smoke Detector 1st inside front room customs house Tested 8:59:48 AM 11/25/2025

Smoke Detector 1st inside library customs house Tested 9:39:46 AM 11/25/2025

Smoke Detector 1st inside public storage customs house Tested 8:06:06 AM 11/25/2025

Smoke Detector 1st inside public storage customs house Tested 8:59:52 AM 11/25/2025

Smoke Detector 1st inside public storage customs house Tested 8:59:55 AM 11/25/2025

Smoke Detector 1st inside room customs house Tested 8:06:13 AM 11/25/2025

Smoke Detector 1st inside vault customs house Tested 8:59:45 AM 11/25/2025

Smoke Detector 2nd inside attic customs house Tested 8:11:44 AM 11/25/2025

Smoke Detector 2nd inside desk room customs house Tested 7:52:54 AM 11/25/2025

Smoke Detector 2nd inside eagle room customs house Tested 7:52:34 AM 11/25/2025

Smoke Detector 2nd inside fireplace customs house Tested 7:52:36 AM 11/25/2025

Smoke Detector 2nd inside front room customs house Tested 7:52:58 AM 11/25/2025

Smoke Detector 2nd inside public storage curatorial customs house

Tested 8:16:17 AM 11/25/2025

Smoke Detector 2nd inside special collection customs house Tested 8:17:19 AM 11/25/2025

Smoke Detector 2nd inside stairs near attic customs house Tested 8:14:55 AM 11/25/2025

Smoke Detector 3rd above Bally box customs house Tested 8:06:47 AM 11/25/2025

Page of 7 23

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 2 - Siemens SXL-EXBuilding: 176 DERBY ST

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Smoke Detector 3rd inside Bally box customs house Tested 8:14:12 AM 11/25/2025

Smoke Detector 3rd inside Bally box customs house Tested 8:15:15 AM 11/25/2025

Smoke Detector 3rd outside Bally box customs house Tested 8:06:44 AM 11/25/2025

Smoke Detector attic inside lighthouse customs house Tested 7:55:31 AM 11/25/2025

Device Type Location Service Time Date

PASSED

Control

Battery Basement inside FACP Narbonne Tested 8:58:40 AM 11/25/2025

Battery Basement inside FACP Narbonne Tested 8:58:46 AM 11/25/2025

Battery 1st inside FACP (Hawkes House) Tested 8:27:33 AM 11/25/2025

Battery 1st inside FACP (Hawkes House) Tested 8:27:37 AM 11/25/2025

Control Panel 1st inside Hawkes house in stair Tested 8:27:26 AM 11/25/2025

Indicating

Horn All inside Derby house Tested 9:25:40 AM 11/25/2025

Horn All inside Hawkes house Tested 8:27:29 AM 11/25/2025

Horn All inside west India goods Tested 9:43:58 AM 11/25/2025

Initiating

Heat Detector Basement right rear (Hawkes House) Tested 8:32:31 AM 11/25/2025

Heat Detector 3rd inside closet near restroom Derby House Tested 9:31:57 AM 11/25/2025

Heat Detector 3rd inside closet near souvenir Derby House Tested 9:33:29 AM 11/25/2025

Heat Detector 3rd inside closet near stairs Derby House Tested 9:34:01 AM 11/25/2025

Heat Detector 3rd inside rear stairwell left room (Hawkes House)

Tested 8:39:48 AM 11/25/2025

Heat Detector 3rd inside restroom (Hawkes House) Tested 8:39:55 AM 11/25/2025

Page of 8 23

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 3 - Siemens SXL-EXBuilding: 176 DERBY ST

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Heat Detector Attic above door (Hawkes House) Tested 8:42:26 AM 11/25/2025

Heat Detector Attic behind stairs (Hawkes House) Tested 8:41:53 AM 11/25/2025

Heat Detector Attic near right side (Hawkes House) Tested 8:41:39 AM 11/25/2025

Heat Detector Attic near roof (Hawkes House) Tested 8:42:35 AM 11/25/2025

Pull Station 1st near front entrance (Hawkes House) Tested 8:28:09 AM 11/25/2025

Pull Station 1st near rear entrance (Hawkes House) Tested 8:33:18 AM 11/25/2025

Pull Station 3rd inside front stairwell (Hawkes House) Tested 8:38:59 AM 11/25/2025

Pull Station 3rd inside rear stairwell (Hawkes House) Tested 8:39:45 AM 11/25/2025

Smoke Detector Basement left side (Hawkes House) Tested 8:32:38 AM 11/25/2025

Smoke Detector Basement rear (Hawkes House) Tested 8:32:34 AM 11/25/2025

Smoke Detector Basement right rear (Hawkes House) Tested 8:34:45 AM 11/25/2025

Smoke Detector 1st front copy machine (Hawkes House) Tested 8:47:17 AM 11/25/2025

Smoke Detector 1st front office (Hawkes House) Tested 8:47:14 AM 11/25/2025

Smoke Detector 1st front stairwell (Hawkes House) Tested 8:30:01 AM 11/25/2025

Smoke Detector 1st rear office space (Hawkes House) Tested 8:36:17 AM 11/25/2025

Smoke Detector 1st rear side room (Hawkes House) Tested 8:35:31 AM 11/25/2025

Smoke Detector 1st rear stairwell (Hawkes House) Tested 8:37:34 AM 11/25/2025

Smoke Detector 2nd inside front stairwell (Hawkes House) Tested 8:37:28 AM 11/25/2025

Smoke Detector 2nd inside rear stairwell (Hawkes House) Tested 8:36:47 AM 11/25/2025

Smoke Detector 3rd inside front stairwell (Hawkes House) Tested 8:38:21 AM 11/25/2025

Smoke Detector 3rd inside rear stairwell (Hawkes House) Tested 8:39:29 AM 11/25/2025

Smoke Detector 3rd near rear stairwell right room (Hawkes House)

Tested 8:39:20 AM 11/25/2025

Smoke Detector Attic above stairs (Hawkes House) Tested 8:40:49 AM 11/25/2025

Page of 9 23

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 4 - Siemens SXL-EXBuilding: 176 DERBY ST

Device Type Location Service Time Date

PASSED

Control

Battery Basement inside derby house FACP Tested 9:25:46 AM 11/25/2025

Battery Basement inside derby house FACP Tested 9:25:52 AM 11/25/2025

Control Panel Basement inside derby house Tested 9:25:36 AM 11/25/2025

Initiating

Pull Station 1st inside closet Derby house Tested 9:26:39 AM 11/25/2025

Smoke Detector Basement left side Derby house Tested 9:35:59 AM 11/25/2025

Smoke Detector Basement right side Derby house Tested 9:35:55 AM 11/25/2025

Smoke Detector 1st inside dining room Derby house Tested 9:32:41 AM 11/25/2025

Smoke Detector 1st inside display room Derby house Tested 9:26:57 AM 11/25/2025

Smoke Detector 1st inside fine dining room Derby house Tested 9:32:48 AM 11/25/2025

Smoke Detector 1st inside office Derby house Tested 9:32:34 AM 11/25/2025

Smoke Detector 2nd inside empty bedroom Derby house Tested 9:32:02 AM 11/25/2025

Smoke Detector 2nd inside green bedroom Derby house Tested 9:32:09 AM 11/25/2025

Smoke Detector 2nd inside guest bedroom Derby house Tested 9:32:05 AM 11/25/2025

Smoke Detector 2nd inside white bedroom Derby house Tested 9:32:12 AM 11/25/2025

Smoke Detector 2nd top of front stairwell Derby house Tested 9:28:43 AM 11/25/2025

Smoke Detector 3rd at top of stairs Derby house Tested 9:31:00 AM 11/25/2025

Smoke Detector 3rd inside paper room Derby house Tested 9:32:53 AM 11/25/2025

Smoke Detector 3rd inside restroom Derby house Tested 9:31:09 AM 11/25/2025

Smoke Detector 3rd inside souvenir room Derby house Tested 9:33:10 AM 11/25/2025

Smoke Detector 3rd inside spare room Derby house Tested 9:32:26 AM 11/25/2025

Smoke Detector 3rd inside wood room Derby house Tested 9:33:56 AM 11/25/2025

Page of 10 23

Norel Service Company, Inc. Download Date: 09/01/2026

Control Panel: 5 - Siemens SXL-EXBuilding: 176 DERBY ST

Device Type Location Service Time Date

PASSED

Control

Control Panel Basement inside Narbonne house Tested 8:58:20 AM 11/25/2025

Initiating

Heat Detector Basement inside Narbonne house Tested 8:58:55 AM 11/25/2025

Smoke Detector Basement above FACP Narbonne house Tested 8:58:07 AM 11/25/2025

Smoke Detector 1st above display table Narbonne house Tested 8:59:15 AM 11/25/2025

Smoke Detector 1st above stairs Narbonne house Tested 8:59:11 AM 11/25/2025

Smoke Detector 1st near entrance Narbonne Tested 8:55:09 AM 11/25/2025

Smoke Detector 1st near fireplace Narbonne house Tested 8:53:02 AM 11/25/2025

Smoke Detector 2nd above stairs Narbonne Tested 8:56:45 AM 11/25/2025

Device Type Location Service Time Date

PASSED

Control

Battery 1st inside FACP West India goods Tested 9:44:05 AM 11/25/2025

Battery 1st inside FACP West India goods Tested 9:44:08 AM 11/25/2025

Control Panel 1st inside West India goods Tested 9:43:54 AM 11/25/2025

Initiating

Heat Detector 1st inside west India goods near entrance Tested 9:44:40 AM 11/25/2025

Heat Detector 1st inside west India goods top of stairs Tested 9:50:36 AM 11/25/2025

Pull Station 1st inside hall West India goods Tested 9:46:05 AM 11/25/2025

Smoke Detector 1st…

This is the start of the file's text. The full file is on GovTribe.