Sol_140P4326Q0064_Amd_0001.pdf
PDF 15 MB Posted
- Solicitation number
- 140P4326Q0064
About this file
This is Amendment 0001 to Request for Proposals (RFP) Number 140P4326Q0064 for fire alarm detection and suppression system inspections, maintenance, and repairs at Salem Maritime National Historical Park (including the replica ship Friendship of Salem) and Saugus Iron Works National Historic Site. The amendment, effective August 26, 2026, provides responses to eight questions received from potential offerors regarding system specifications, contractor responsibilities, wage determinations, and proposal submission requirements.
Key clarifications include: replacement fire alarm communication protocols now utilize Starlink cell radio at the Custom House and Narbonne House (monitored by NOREL) and AES Radio at St. Joseph Hall (monitored by American Alarm and Signal); contractors are responsible for connection testing and verification to existing central security alarm monitoring stations under base contract lines, with responsibility for establishing or modifying replacement reporting paths only if optional CLINs 00060-00065 are awarded; on-site fire watch supervision requires contractor staff presence during system testing, with minimal staffing needed if unexpected offline periods occur; contractors must furnish AES transceivers, antenna systems, and related equipment, with flexibility to substitute cellular radio if cost-effective; equivalent professional manufacturer training or third-party marine gaseous suppression system certifications are acceptable alternatives to factory-direct Kidde Marine certification; material markup percentages for unscheduled repairs should be entered in Attachment 2 Bid Schedule Row 58; contractors must propose a single baseline labor rate compliant with both Essex County (WD 2015-4067) and Middlesex/Suffolk Area (WD 2015-4065) wage determinations for on-call time and materials repair line items; there is no current incumbent; and device counts are available in the November 2025 fire alarm inspection and June 2026 sprinkler inspection reports provided as part of the amendment. The amendment also includes comprehensive fire alarm inspection reports from November 2025 documenting all tested devices, equipment specifications, and system inventories across eight Salem Maritime and one Saugus location.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: is not is required copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7.ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
PAGESOF
Contractor
The hour and date specified for receipt of Offers to sign this document and return
Jason Albright
See continuation page
NPS, NER - NE MABO
Boston National Historical Park Charlestown Navy Yard Building I-1 Boston MA 02129-4543
PNN
140P4326Q0064
09/09/2026
08/26/2026
1 177
CONTINUATION SHEET
REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGES
NAME OF OFFEROR OR CONTRACTOR
SUPPLIES/SERVICES
(B)
UNIT
(D)
UNIT PRICE
(E)
AMOUNT
(F)
OPTIONAL FORM 336 (4-86)
Sponsored by GSA FAR (48 CFR) 53.110
ITEM NO.
(A)
QUANTITY
(C)
NSN 7540-01-152-8067
140P4326Q0064/0001
Fire alarm detection and suppression system inspections, maintenance, and repairs at Salem
Maritime NHP (including replica ship Friendship of Salem), and Saugus Iron Works NHS.
The purpose of this amendment is to provide a copy of the sign-in sheet from the organized site-visit, provide a response to questions received, provide prior fire alarm reports and sprinkler reports, and provide a photo of the ship panel.
Period of Performance: 10/01/2026 to
09/30/2027
Request for Proposal Number 140P4326Q0064 Fire Alarm/Sprinkler System Inspection, Testing, Maintenance, and Repair at Salem Maritime National Historical Park and Saugus Iron Works National Historic Site Amendment 0001
DESCRIPTION OF AMENDMENT/MODIFICATION
The following are a list of questions received for the Solicitation Number 140P4326Q0064, Fire Alarm/Sprinkler System Inspection, Testing, Maintenance, and Repair at Salem Maritime National Historical Park and Saugus Iron Works National Historic Site.
1) Salem Replacement Reporting Mechanism (SOW Section 1.2 & SOW Section 4.1) The Statement of Work notes that the municipal fire alarm master boxes in the two Salem locations were discontinued in June 2026, and that "the replacement reporting mechanism is not yet established". To ensure accurate pricing under the scheduled base line items
(CLIN 00010):
(a) What is the active replacement communication protocol or signal reporting mechanism currently utilized for the Salem buildings?
Answer: Starlink cell radio has replaced city fire box as primary communication in the Custom House (main panel that covers this building and 5 others) and Narbonne House and these locations are being monitored by NOREL. AES Radio has replaced city fire box (in conjunction with 2 phone lines) for St. Joseph Hall and is being monitored by American Alarm and Signal.
(b) Is the awardee responsible for establishing, installing, or programmatically modifying any replacement reporting path, or will the contractor's scope be limited strictly to connection testing and verification to the existing central security alarm monitoring station?
Answer: Base contract lines CLINs 00010, 11, 12, 20, 21, 22) for annual inspection and PMs include the latter (“connection testing and verification to the existing central security alarm monitoring station”). If and only if one or all of options in CLINs 00060, 61, 62, 63, 64 or 65 are awarded will the contractor be responsible for the former (“establishing, installing, or programmatically modifying any replacement reporting path) in the locations awarded.
2) On-Site Supervision & Fire Watch Requirements (SOW Section 1.2) The SOW states that the awardee is responsible for "supervision of buildings while fire alarms are disconnected, for all base and option lines". Given the historical landmark status and irreplaceable collections in these structures:
(a) Does this "supervision" require the contractor to provide dedicated, continuous on-site personnel to perform a physical, continuous Fire Watch in each building while systems are offline for testing? Answer: If the contractor staff is in the building and performing testing this requirement is met, If they need to leave briefly and the system is not functioning, they must coordinate the watch requirements themselves or with the COR.
(b) If a contractor-provided Fire Watch is mandatory, could the Government specify the minimum staffing and hourly surveillance coverage requirements expected during offline testing windows? Answer: In the rare and unexpected event this is required, one person would be sufficient, and watch details and payment would be coordinated with the COR. Contractor will make all reasonable efforts to avoid
National Historical Park and Saugus Iron Works National Historic Site Amendment 0001 situations where fire watch is required outside of business hours and is related to fixed price lines under this contract.
3) AES Radio Installation Options and Equipment Sourcing (CLINs 00060–00065 & SOW
Section 1.2) For the options to install code-compliant AES radio communications, please clarify the following technical parameters:
(a) Is the contractor required to furnish the AES transceivers, antenna systems, coaxial cabling, and power supplies, or is this equipment provided as Government-Furnished Property (GFP)? Answer: Contractor supplied.
(b) If Contractor-Furnished, does the Park have pre-approved manufacturer brands and specific model numbers compatible with the local municipal receiver network? Answer: If installed, awardee would take over monitoring after installation, so it must be compatible with their network.
(c) Given the strict historical preservation rules, are there specific exterior antenna placement limitations or non-destructive mounting methods that must be factored into our installation labor pricing. Answer: specific requirements in SOW to meet historic preservation rules must be followed, but bidders should assume this installation would be close proximity to the panels working within the standard kit antenna wire length of approximately 25’, and also placed in building interiors in the same or similar and adjacent spaces to where the panel is located. If signal is not strong enough to support functionality in such a location and longer wire runs and/or exterior antenna placement becomes required, NPS understands additional discussions and funds will be required.
NOTE: In reply to a question/suggestion posed at the walk-through on 9/3/26: For CLINs 00060–00065, bidders may substitute Cellular Radio for AES if they believe it can be done at a lower cost and improves or has the same likelihood of receiving sufficient signal when installed in such a location as described in 3)c) above. If bidders opt to do this, please include this cost in the proposal and note that pricing is for Cellular Radio. Alternately they can include both the aes and cellular radion price clearly marked for each CLIN, and NPS will calculate the total contract value using the higher number.
4) Kidde Marine FM-200 Specialized Training (SOW Section 1.4.5 & Factor 1) SOW
Section 1.4.5 states that the senior inspector "must document that they have been trained to service Kidde marine FM-200 systems". Will the Government accept equivalent professional manufacturer training or third-party specialized marine gaseous suppression system certifications (such as certified technicians on NFPA 2001 systems), or is a factory-direct certification issued exclusively by Kidde Marine mandatory to be deemed technically acceptable under Factor 1?
Answer: Other equivalent certifications and training will be accepted.
National Historical Park and Saugus Iron Works National Historic Site Amendment 0001
5) Time & Materials (T&M) Material Mark-up Proposal Structure (SOW Section 3.3.10.2)
SOW Section 3.3.10.2 (Material Costs) states that bidders will include with their proposal the percentage of material markup to be applied to supply and equipment purchases for unscheduled repairs. However, Attachment 2 (Bid Schedule) does not contain a dedicated field, formula cell, or CLIN for the entry of this percentage markup. Could the Government clarify where within the submission package or Excel sheet bidders should formally document their proposed material markup percentage?
Answer: Attachment 2 - Bid Schedule, Row 58 contains the cells for material mark-up percentages.
6) Location-Specific SCLS Wage Rate Applicability (DOL Wage Determinations) The solicitation incorporates two distinct DOL Wage Determinations: Essex County (WD 2015-4067) for Salem Maritime and Middlesex/Suffolk Area (WD 2015-4065) for Saugus Iron Works. For the on-call, unscheduled Time & Material repair line items (CLINs 00070–00072), should the contractor separate and propose distinct labor rates by location/county, or will one baseline wage determination govern the consolidated repair CLINs?
Answer: Repairs under these line items may be for either location. Therefore, there should be a single proposed labor rate that is in compliance with both wage determinations.
7) Is currently an incumbent? If so, who was the previous awardee, contract number, and value?
Answer: There is no current incumbent.
8) Could you provide a device count for fire alarm systems for all buildings?
Answer: Device counts can be found in the reports from annual inspections. Annual Inspections from November 2025 Fire Alarms, and June 2026 Sprinklers are provided as part of this amendment.
In reply to a question/suggestion posed at the walk-through on 9/3/26: Please also see photos of the Ship combined fire alarm and security alarm panel, as requested on the walk through 9/3/26.
160 DERBY ST - SHIP
160 DERBY ST
SHIP
SALEM, MA 01970
978-360-2080
Building Contact: JEREMY BUNAGIN Title: SITE CONTACT
Company: Norel Service Company, Inc.
Contact: Evan Olson Title: tester
Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards
Fire Alarm Systems
INSPECTION
CERTIFICATE
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 8 Executive Summary
Norel Service Company, Inc. Download Date: 09/01/2026
Building: 160 DERBY ST - SHIPCompany: Norel Service Company, Inc.
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
160 DERBY ST - SHIP
160 DERBY ST
SHIP
SALEM, MA 01970
United States of America
Contact: JEREMY BUNAGIN
Phone: 978-360-2080
Fax:
Mobile:
Email: Jeremy_Bunagin@nps.gov
Inspection Performed By Norel Service Company, Inc.
1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America
Inspector: Evan Olson
Phone: (781) 768-5500
Fax:
Mobile:
Email: wdwyer@norelservice.com
System Control Unit Manufacturer: burg system Inspection Date: 11/25/2025 IDC Style:
Model Number: Install Date: 11/20/2023 SLC Style:
Software Version: Version Date: 11/20/2023 NAC Style:
Location: 1st by staircase Disconnect Location: Disconnect Type:
Current Protection:
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 1 7.69% 1 100.00% 1 100.00% 0 0.00%
Initiating 12 92.31% 12 100.00% 12 100.00% 0 0.00%
Totals 13 100% 13 100.00% 13 100.00% 0 0.00%
Certification
Page of 3 8
Norel Service Company, Inc. Download Date: 09/01/2026
Contact: JEREMY BUNAGINInspector: Evan Olson
Signed: Nov 25, 2025
Page of 4 8 Notes & Recommendations
Norel Service Company, Inc. Download Date: 09/01/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note
11/25/25 Tested all FA Burglar Panel left normal Monitoring to be put back online by customer Cleaned out smokes
Page of 5 8 Inspection & Testing
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - burg systemBuilding: 160 DERBY ST - SHIP
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Control Panel 1st by staircase Tested 12:00:41 PM 11/25/2025
Initiating
CO Detector tween decks Tested 11:55:44 AM 11/25/2025
CO Detector tween decks mizzen mast Tested 11:48:33 AM 11/25/2025
Heat Detector under tween decks by electrical panels Tested 11:56:12 AM 11/25/2025
Heat Detector under tween decks engine room Tested 11:56:55 AM 11/25/2025
Heat Detector under tween decks fore mast hold Tested 11:42:34 AM 11/25/2025
Smoke Detector tween decks by fire system storage Tested 11:58:19 AM 11/25/2025
Smoke Detector tween decks by stairs Tested 11:46:12 AM 11/25/2025
Smoke Detector tween decks for mest Tested 11:36:57 AM 11/25/2025
Smoke Detector under tween decks four peak Tested 11:40:25 AM 11/25/2025
Smoke Detector under tween decks hole number 2 Tested 11:45:08 AM 11/25/2025
Smoke Detector under tween decks laz Tested 11:53:45 AM 11/25/2025
Smoke Detector under tween decks tank compartment Tested 11:54:50 AM 11/25/2025
Page of 6 8 Service Summary
Norel Service Company, Inc. Download Date: 09/01/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: 160 DERBY ST - SHIP
Device Type Service Quantity
PASSED
CO Detector Tested 2
Control Panel Tested 1
Heat Detector Tested 3
Smoke Detector Tested 7
Total 13
Grand Total 13
Page of 7 8 Inventory & Warranty Report
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - burg systemBuilding: 160 DERBY ST - SHIP
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: 160 DERBY ST - SHIP
Device or Type Category % of Inventory Quantity
CO Detector Initiating 15.38% 2
Control Panel Control 7.69% 1
Heat Detector Initiating 23.08% 3
Smoke Detector Initiating 53.85% 7
Type Qty Model # Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS
burg system
Control Panel 1 11/20/2023
IN SERVICE - 5 YEARS TO 10 YEARS
Edwards
Heat Detector 1 282B-PL 11/20/2016
Heat Detector 2 604 11/20/2016
System Sensor
CO Detector 2 11/20/2016
Smoke Detector 7 2WB 11/20/2016
Page of 8 8 Zone Address Report
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - burg systemBuilding: 160 DERBY ST - SHIP
ZONE ADDRESS REPORT
Generated by: BuildingReports.com
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
ZONE/CIRCUIT:
Zone 1 Smoke Detector tween decks by fire system storage 85881417
Zone 1 Smoke Detector tween decks by stairs 85881441
Zone 1 Smoke Detector tween decks for mest 85881416
Zone 1 Heat Detector under tween decks by electrical panels 85881440
Zone 1 Heat Detector under tween decks engine room 85881427
Zone 1 Heat Detector under tween decks fore mast hold 85881425
Zone 1 Smoke Detector under tween decks four peak 85881443
Zone 1 Smoke Detector under tween decks hole number 2 85881444
Zone 1 Smoke Detector under tween decks laz 85881424
Zone 1 Smoke Detector under tween decks tank compartment 85881428
Zone 27 CO Detector tween decks 85881430
Zone 27 CO Detector tween decks mizzen mast 85881418
160 DERBY ST ST - JOSEPH'S HALL
160 DERBY ST
SALEM, MA 01970
978-360-2080
Building Contact: JEREMY BUNAGIN Title: SITE CONTACT
Company: Norel Service Company, Inc.
Contact: TYLER RUTINA Title: tester
Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards
Fire Alarm Systems
INSPECTION
CERTIFICATE
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for
Page of 2 15
Norel Service Company, Inc. Download Date: 09/01/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
160 DERBY ST ST - JOSEPH'S HALL
160 DERBY ST
SALEM, MA 01970
United States of America
Contact: JEREMY BUNAGIN
Phone: 978-360-2080
Fax:
Mobile:
Email: Jeremy_Bunagin@nps.gov
Inspection Performed By Norel Service Company, Inc.
1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America
Inspector: TYLER RUTINA
Phone: (781) 768-5500
Fax:
Mobile:
Email: wdwyer@norelservice.com
System Control Unit Manufacturer: Notifier Inspection Date: 11/25/2025 IDC Style:
Model Number: NFS 320 Install Date: 11/04/2024 SLC Style:
Software Version: Version Date: 11/04/2024 NAC Style:
Location: 1st Inside FACP Room Disconnect Location: 1st Inside FACP Room
Disconnect Type:
Current Protection:
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 5 10.87% 5 100.00% 5 100.00% 0 0.00%
Indicating 4 8.70% 4 100.00% 4 100.00% 0 0.00%
Initiating 37 80.43% 37 100.00% 37 100.00% 0 0.00%
Totals 46 100% 46 100.00% 46 100.00% 0 0.00%
Page of 3 15
Norel Service Company, Inc. Download Date: 09/01/2026
Building: 160 DERBY ST ST - JOSEPH'S HALL Contact: JEREMY BUNAGIN
Company: Norel Service Company, Inc.
Inspector: TYLER RUTINA
Signed: Nov 25, 2025
Page of 4 15
Norel Service Company, Inc. Download Date: 09/01/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note
11/25/2025 Completed testing of 100% of fire alarm devices and all audibles.
Cleaned out smoke detectors.
Panel normal upon departure.
Customer to notify central station.
Fire department notified.
Page of 5 15
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Annunciator 1st By Front Entrance Tested 10:40:19 AM 11/25/2025
Battery 1st Inside FACP Tested 10:13:00 AM 11/25/2025
Battery 1st Inside FACP Tested 10:13:08 AM 11/25/2025
Control Panel 1st Inside FACP Room Tested 10:12:49 AM 11/25/2025
Disconnect 1st Inside FACP Room Tested 10:12:41 AM 11/25/2025
Indicating
Horn/Strobe Basement Inside All Areas Tested 10:47:59 AM 11/25/2025
Horn/Strobe 1st Inside All Areas Tested 10:47:56 AM 11/25/2025
Horn/Strobe 2nd Inside All Areas Tested 10:47:54 AM 11/25/2025
Horn/Strobe 3rd Inside All Areas Tested 10:47:52 AM 11/25/2025
Initiating
Duct Detector 1st Inside FACP Room RTU-1 Tested 10:13:22 AM 11/25/2025
Duct Detector 1st Inside FACP Room RTU-2 Tested 10:13:26 AM 11/25/2025
Duct Detector 1st Inside FACP Room RTU-3A Tested 10:44:50 AM 11/25/2025
Duct Detector 1st Inside FACP Room RTU-3B Tested 10:13:33 AM 11/25/2025
Duct Detector 1st Inside FACP Room RTU-4 Tested 10:13:35 AM 11/25/2025
Duct Detector 1st Inside FACP Room RTU-5 Tested 10:13:37 AM 11/25/2025
Duct Detector 1st Inside FACP Room RTU-6 Tested 10:13:38 AM 11/25/2025
Heat Detector Basement Inside Basement Electrical Room Tested 10:37:47 AM 11/25/2025
Page of 6 15
Norel Service Company, Inc. Download Date: 09/01/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Masterbox 1st Inside Carpentry Shop Masterbox #141 Tested 10:12:44 AM 11/25/2025
Pull Station Basement By Rear Stairwell Tested 10:38:23 AM 11/25/2025
Pull Station 1st By Front Entrance Tested 10:40:26 AM 11/25/2025
Pull Station 1st By Side Exit Inside Hallway (Pelfry Court Exit)
Tested 10:14:51 AM 11/25/2025
Pull Station 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)
Tested 10:39:09 AM 11/25/2025
Pull Station 1st By Side Exit Inside Stairwell (Pelfry Court Exit)
Tested 10:15:36 AM 11/25/2025
Pull Station 1st Inside Side Stairwell By Exit (Derby Street Exit)
Tested 10:19:11 AM 11/25/2025
Pull Station 2nd By Side Exit To Front Stairwell Tested 10:17:47 AM 11/25/2025
Pull Station 3rd Inside Main Hallway Tested 10:23:33 AM 11/25/2025
Pull Station 3rd Inside Main Hallway By Front Stairwell Tested 10:25:31 AM 11/25/2025
Smoke Detector Basement Inside Basement By Elevator Machine Room
Tested 10:34:47 AM 11/25/2025
Smoke Detector Basement Inside Basement By Rear Stairwell Tested 10:34:17 AM 11/25/2025
Smoke Detector Basement Inside Basement Inside Rear Stairwell
Tested 10:33:49 AM 11/25/2025
Smoke Detector Basement Inside Basement Inside Stairwell Tested 10:36:56 AM 11/25/2025
Smoke Detector 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)
Tested 10:14:58 AM 11/25/2025
Smoke Detector 1st Inside Hallway By Side Exit (Pelfry Court Exit)
Tested 10:26:40 AM 11/25/2025
Smoke Detector 1st Inside Side Stairwell By Side Exit (Pelfry Court Exit)
Tested 10:15:44 AM 11/25/2025
Smoke Detector 1st Left Side Carpentry Shop Tested 10:13:55 AM 11/25/2025
Smoke Detector 1st Left Side Carpentry Shop Tested 10:40:06 AM 11/25/2025
Smoke Detector 1st Right Side Carpentry Shop Tested 10:30:16 AM 11/25/2025
Page of 7 15
Norel Service Company, Inc. Download Date: 09/01/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit) Tested 10:20:46 AM 11/25/2025
Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit) Tested 10:22:17 AM 11/25/2025
Smoke Detector 2nd Inside Rear Stairwell Tested 10:23:16 AM 11/25/2025
Smoke Detector 2nd Inside Side Stairwell Hallway (Derby Street Exit)
Tested 10:20:29 AM 11/25/2025
Smoke Detector 3rd Inside Front Stairwell Tested 10:25:59 AM 11/25/2025
Smoke Detector 3rd Inside Main Hallway Tested 10:23:54 AM 11/25/2025
Smoke Detector 3rd Inside Main Hallway By Front Stairwell Tested 10:25:07 AM 11/25/2025
Smoke Detector 3rd Inside Main Hallway By Skylight Tested 10:24:30 AM 11/25/2025
Smoke Detector 3rd Inside Rear Stairwell Tested 10:23:05 AM 11/25/2025
Page of 8 15
Norel Service Company, Inc. Download Date: 09/01/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: 160 DERBY ST ST - JOSEPH'S HALL
Device Type Service Quantity
PASSED
Annunciator Tested 1
Battery, Sealed Lead Acid Tested 2
Control Panel Tested 1
Disconnect Tested 1
Duct Detector Tested 7
Heat Detector Tested 1
Horn/Strobe Tested 4
Masterbox Tested 1
Pull Station Tested 9
Smoke Detector, Photoelectric Tested 19
Total 46
Grand Total 46
Page of 9 15 Sound and Visual Testing
Norel Service Company, Inc. Download Date: 09/01/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.
Building: 160 DERBY ST ST - JOSEPH'S HALL
Audible/Visual Appliances Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
Basement Inside All Areas Passed ☐ 94111163
1st Inside All Areas Passed ☐ 94111193
2nd Inside All Areas Passed ☐ 94111195
3rd Inside All Areas Passed ☐ 94111203
Page of 10 15 Battery & Power Supply Testing
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated
Ah Rated Volts
Pre Test
Post Test
Min Ah
Teste d Ah
MFG
Date
PASSED
Sealed Lead Acid 1st Inside FACP 18 12 11/04 /2024
Sealed Lead Acid 1st Inside FACP 18 12 11/04 /2024
Page of 11 15
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: 160 DERBY ST ST - JOSEPH'S HALL
Device or Type Category % of Inventory Quantity
Annunciator Control 2.17% 1
Battery Control 4.35% 2
Control Panel Control 2.17% 1
Disconnect Control 2.17% 1
Duct Detector Initiating 15.22% 7
Heat Detector Initiating 2.17% 1
Horn/Strobe Indicating 8.70% 4
Masterbox Initiating 2.17% 1
Pull Station Initiating 19.57% 9
Smoke Detector Initiating 41.30% 19
Type Qty Model # Description Install Date
IN SERVICE - 1 YEAR TO 2 YEARS
Gamewell
Masterbox 1 11/04/2024
Interstate
Battery 2 SLA1115 Sealed Lead Acid 11/04/2024
Notifer
Heat Detector 1 FSP-951 11/04/2024
Pull Station 9 NBG-12LX 11/04/2024
Page of 12 15
Norel Service Company, Inc. Download Date: 09/01/2026
Type Qty Model # Description Install Date
IN SERVICE - 1 YEAR TO 2 YEARS (continued)
Notifer (continued)
Smoke Detector 19 FSP-951 Photoelectric 11/04/2024
Notifier
Annunciator 1 11/04/2024
Control Panel 1 NFS 320 11/04/2024
System Sensor
Duct Detector 7 11/04/2024
Horn/Strobe 4 P2R 11/04/2024
(manufacturer not specified)
Disconnect 1 11/04/2024
Page of 13 15
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - Notifier NFS 320Building: 160 DERBY ST ST - JOSEPH'S HALL
ZONE ADDRESS REPORT
Generated by: BuildingReports.com
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
ZONE/CIRCUIT:
L1D011 Smoke Detector 1st Left Side Carpentry Shop Photoelectric 94111172
L1D012 Smoke Detector 1st Right Side Carpentry Shop Photoelectric 94111174
L1D013 Smoke Detector 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)
Photoelectric 94111212
L1D018 Smoke Detector 1st Inside Side Stairwell By Side Exit (Pelfry Court Exit)
Photoelectric 94111158
L1D018 Smoke Detector 1st Left Side Carpentry Shop Photoelectric 94111164
L1D019 Smoke Detector 1st Inside Hallway By Side Exit (Pelfry Court Exit)
Photoelectric 94111166
L1D023 Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit)
Photoelectric 94111162
L1D023 Smoke Detector 2nd Inside Side Stairwell Hallway (Derby Street Exit)
Photoelectric 94111154
L1D027 Duct Detector 1st Inside FACP Room RTU-3A 94111196
L1D027 Duct Detector 1st Inside FACP Room RTU-3B 94111192
L1D028 Duct Detector 1st Inside FACP Room RTU-2 94111176
L1D029 Smoke Detector 2nd Inside Front Stairwell (Derby Street Exit)
Photoelectric 94111188
L1D029 Smoke Detector 2nd Inside Rear Stairwell Photoelectric 94111182
L1D031 Smoke Detector 3rd Inside Main Hallway By Front Stairwell Photoelectric 94111187
L1D032 Smoke Detector 3rd Inside Main Hallway By Skylight Photoelectric 94111184
L1D033 Smoke Detector 3rd Inside Main Hallway Photoelectric 94111210
Page of 14 15
Norel Service Company, Inc. Download Date: 09/01/2026
Address Device Type Location Type ScanID
ZONE/CIRCUIT: (continued)
L1D034 Smoke Detector 3rd Inside Rear Stairwell Photoelectric 94111181
L1D036 Smoke Detector 3rd Inside Front Stairwell Photoelectric 94111183
L1D037 Duct Detector 1st Inside FACP Room RTU-5 94111215
L1D038 Duct Detector 1st Inside FACP Room RTU-6 94111214
L1D039 Duct Detector 1st Inside FACP Room RTU-4 94111213
L1D041 Smoke Detector Basement Inside Basement Inside Stairwell Photoelectric 94111217
L1D042 Heat Detector Basement Inside Basement Electrical Room 94111207
L1D043 Duct Detector 1st Inside FACP Room RTU-1 94111175
L1D044 Smoke Detector Basement Inside Basement By Rear Stairwell
Photoelectric 94111205
L1D045 Smoke Detector Basement Inside Basement By Elevator Machine Room
Photoelectric 94111206
L1D047 Smoke Detector Basement Inside Basement Inside Rear Stairwell
Photoelectric 94111204
L1M011 Pull Station 1st By Front Entrance 94111173
L1M013 Pull Station 1st By Side Exit Inside Side Stairwell (Pelfry Court Exit)
94111216
L1M013 Masterbox 1st Inside Carpentry Shop Masterbox #141 94111167
L1M013 Pull Station 1st Inside Side Stairwell By Exit (Derby Street Exit)
94111165
L1M014 Pull Station 1st By Side Exit Inside Stairwell (Pelfry Court Exit)
94111161
L1M015 Pull Station 1st By Side Exit Inside Hallway (Pelfry Court Exit)
94111201
L1M021 Pull Station 2nd By Side Exit To Front Stairwell 94111159
L1M031 Pull Station 3rd Inside Main Hallway By Front Stairwell 94111211
L1M032 Pull Station 3rd Inside Main Hallway 94111209
L1M049 Pull Station Basement By Rear Stairwell 94111208
ZONE/CIRCUIT: CIRCUIT #16
Page of 15 15
Norel Service Company, Inc. Download Date: 09/01/2026
Address Device Type Location Type ScanID
ZONE/CIRCUIT: CIRCUIT #16 (continued)
Disconnect 1st Inside FACP Room 39060097
174 DERBY ST HAWKES HSE
/GARDEN SHED
174 DERBY ST
GARDEN SHED
SALEM, MA 01970
978-360-2080
Building Contact: JEREMY BUNAGIN Title: SITE CONTACT
Company: Norel Service Company, Inc.
Contact: Evan Olson Title: tester
Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards
Fire Alarm Systems
INSPECTION
CERTIFICATE
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for
Page of 2 7
Norel Service Company, Inc. Download Date: 09/01/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
174 DERBY ST HAWKES HSE/GARDEN
SHED
174 DERBY ST
GARDEN SHED
SALEM, MA 01970
United States of America
Contact: JEREMY BUNAGIN
Phone: 978-360-2080
Fax:
Mobile:
Email: Jeremy_Bunagin@nps.gov
Inspection Performed By Norel Service Company, Inc.
1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America
Inspector: Evan Olson
Phone: (781) 768-5500
Fax:
Mobile:
Email: wdwyer@norelservice.com
System Control Unit Manufacturer: Bosch Inspection Date: 11/25/2025 IDC Style:
Model Number: l Install Date: 04/01/2024 SLC Style:
Software Version: Version Date: 12/31/1969 NAC Style:
Location: 1st burglar panel inside Hawkes house
Disconnect Location: Disconnect Type:
Current Protection:
Central Station Signal Verification Type: Mfg: AES Model #: 7788F
Test Time/Date: 11/25/25 10:12:57 AM Restore Time: Note:
Page of 3 7
Norel Service Company, Inc. Download Date: 09/01/2026
Building: 174 DERBY ST HAWKES HSE
/GARDEN SHED
Contact: JEREMY BUNAGIN
Company: Norel Service Company, Inc.
Inspector: Evan Olson
Signed: Nov 25, 2025
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 2 66.67% 2 100.00% 2 100.00% 0 0.00%
Initiating 1 33.33% 1 100.00% 1 100.00% 0 0.00%
Totals 3 100% 3 100.00% 3 100.00% 0 0.00%
Page of 4 7
Norel Service Company, Inc. Download Date: 09/01/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note
11/25/25 Tested 100% of FA devices Monitoring to be restored by customer
Page of 5 7
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 2 - Bosch lBuilding: 174 DERBY ST HAWKES HSE/GARDEN
SHED
Control Panel: 1Building: 174 DERBY ST HAWKES HSE/GARDEN
SHED
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Communicator 1st inside hawkes house (instant alarm) Tested 10:12:57 AM 11/25/2025
Device Type Location Service Time Date
PASSED
Control
Control Panel 1st burglar panel inside Hawkes house Tested 10:12:54 AM 11/25/2025
Initiating
Heat Detector 1st inside garden shed (trips burg panel) Tested 10:04:10 AM 11/25/2025
Page of 6 7
Norel Service Company, Inc. Download Date: 09/01/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: 174 DERBY ST HAWKES HSE/GARDEN SHED
Device Type Service Quantity
PASSED
Communicator Tested 1
Control Panel Tested 1
Heat Detector Tested 1
Total 3
Grand Total 3
Page of 7 7
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 2 - Bosch lBuilding: 174 DERBY ST HAWKES HSE/GARDEN
SHED
Control Panel: 1Building: 174 DERBY ST HAWKES HSE/GARDEN
SHED
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: 174 DERBY ST HAWKES HSE/GARDEN SHED
Device or Type Category % of Inventory Quantity
Communicator Control 33.33% 1
Control Panel Control 33.33% 1
Heat Detector Initiating 33.33% 1
Type Qty Model # Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS
AES
Communicator 1 7788F 04/01/2024
Type Qty Model # Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS
Bosch
Control Panel 1 l 04/01/2024
Honeywell
Heat Detector 1 604 04/01/2024
176 DERBY ST
176 DERBY ST
CUSTOMS HSE, NARBONE HSE,DERBY & HAWKES HOUSE
SALEM, MA 01970
978-360-2080
Building Contact: JEREMY BUNAGIN Title: SITE CONTACT
Company: Norel Service Company, Inc.
Contact: Evan Olson Title: tester
Inspection Date: Nov 25, 2025 Tested to NFPA 72 Standards
Fire Alarm Systems
INSPECTION
CERTIFICATE
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for
Page of 2 23
Norel Service Company, Inc. Download Date: 09/01/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
176 DERBY ST
176 DERBY ST
CUSTOMS HSE, NARBONE HSE,DERBY
& HAWKES HOUSE
SALEM, MA 01970
United States of America
Contact: JEREMY BUNAGIN
Phone: 978-360-2080
Fax:
Mobile:
Email: Jeremy_Bunagin@nps.gov
Inspection Performed By Norel Service Company, Inc.
1 Monarch Drive Suite 201 Littleton, MA 01460 United States of America
Inspector: Evan Olson
Phone: (781) 768-5500
Fax:
Mobile:
Email: wdwyer@norelservice.com
System Control Unit Manufacturer: Siemens Inspection Date: 11/25/2025 IDC Style:
Model Number: CP-35 Install Date: 11/20/2023 SLC Style:
Software Version: Version Date: 11/20/2023 NAC Style:
Location: Basement inside customs house
Disconnect Location: Basement inside customs house near FACP
Disconnect Type:
Current Protection:
Central Station Signal Verification Type: Digital Communicator Mfg: AES Model #: 7788F
Test Time/Date: 11/25/25 7:31:20 AM Restore Time: Note:
Page of 3 23
Norel Service Company, Inc. Download Date: 09/01/2026
Building: 176 DERBY ST Contact: JEREMY BUNAGIN
Company: Norel Service Company, Inc.
Inspector: Evan Olson
Signed: Nov 25, 2025
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 18 15.65% 18 100.00% 18 100.00% 0 0.00%
Indicating 4 3.48% 4 100.00% 4 100.00% 0 0.00%
Initiating 93 80.87% 93 100.00% 93 100.00% 0 0.00%
Totals 115 100% 115 100.00% 115 100.00% 0 0.00%
Page of 4 23
Norel Service Company, Inc. Download Date: 09/01/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note
11/25/25 Tested all FA devices with all AVs Panel left normal
Masterbox box back online by city of Salem
Page of 5 23
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 1 - Siemens CP-35Building: 176 DERBY ST
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery Basement inside Communicator Customs house
Tested 7:37:01 AM 11/25/2025
Battery Basement inside customs house FACP Tested 7:29:41 AM 11/25/2025
Battery Basement inside customs house FACP Tested 7:29:50 AM 11/25/2025
Communicator Basement inside customs house Tested 7:31:20 AM 11/25/2025
Control Panel Basement inside customs house Tested 7:29:31 AM 11/25/2025
Disconnect Basement inside customs house near FACP Tested 7:30:47 AM 11/25/2025
Indicating
Horn All inside customs house Tested 7:29:26 AM 11/25/2025
Initiating
Heat Detector Basement inside customs house Inside storage behind kitchen
Tested 7:36:18 AM 11/25/2025
Heat Detector Basement inside customs house engine room
Tested 7:42:12 AM 11/25/2025
Heat Detector Basement inside customs house engine room
Tested 7:42:16 AM 11/25/2025
Heat Detector Basement inside customs house inside kitchen
Tested 7:34:58 AM 11/25/2025
Heat Detector Basement inside customs house near kitchen
Tested 7:42:05 AM 11/25/2025
Heat Detector Basement inside customs house near office Tested 7:42:08 AM 11/25/2025
Page of 6 23
Norel Service Company, Inc. Download Date: 09/01/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Heat Detector Basement inside customs house near stairs Tested 7:41:58 AM 11/25/2025
Heat Detector 1st inside shed (reports to burglar panel) Tested 9:40:01 AM 11/25/2025
Masterbox Basement inside customs house #155 Tested 7:29:35 AM 11/25/2025
Pull Station Basement inside customs house near entrance
Tested 7:31:26 AM 11/25/2025
Pull Station 1st inside front room customs house Tested 9:39:37 AM 11/25/2025
Smoke Detector Basement inside front storage customs house
Tested 8:05:46 AM 11/25/2025
Smoke Detector Basement inside rear storage customs house Tested 8:05:42 AM 11/25/2025
Smoke Detector 1st inside front room customs house Tested 8:59:48 AM 11/25/2025
Smoke Detector 1st inside library customs house Tested 9:39:46 AM 11/25/2025
Smoke Detector 1st inside public storage customs house Tested 8:06:06 AM 11/25/2025
Smoke Detector 1st inside public storage customs house Tested 8:59:52 AM 11/25/2025
Smoke Detector 1st inside public storage customs house Tested 8:59:55 AM 11/25/2025
Smoke Detector 1st inside room customs house Tested 8:06:13 AM 11/25/2025
Smoke Detector 1st inside vault customs house Tested 8:59:45 AM 11/25/2025
Smoke Detector 2nd inside attic customs house Tested 8:11:44 AM 11/25/2025
Smoke Detector 2nd inside desk room customs house Tested 7:52:54 AM 11/25/2025
Smoke Detector 2nd inside eagle room customs house Tested 7:52:34 AM 11/25/2025
Smoke Detector 2nd inside fireplace customs house Tested 7:52:36 AM 11/25/2025
Smoke Detector 2nd inside front room customs house Tested 7:52:58 AM 11/25/2025
Smoke Detector 2nd inside public storage curatorial customs house
Tested 8:16:17 AM 11/25/2025
Smoke Detector 2nd inside special collection customs house Tested 8:17:19 AM 11/25/2025
Smoke Detector 2nd inside stairs near attic customs house Tested 8:14:55 AM 11/25/2025
Smoke Detector 3rd above Bally box customs house Tested 8:06:47 AM 11/25/2025
Page of 7 23
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 2 - Siemens SXL-EXBuilding: 176 DERBY ST
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 3rd inside Bally box customs house Tested 8:14:12 AM 11/25/2025
Smoke Detector 3rd inside Bally box customs house Tested 8:15:15 AM 11/25/2025
Smoke Detector 3rd outside Bally box customs house Tested 8:06:44 AM 11/25/2025
Smoke Detector attic inside lighthouse customs house Tested 7:55:31 AM 11/25/2025
Device Type Location Service Time Date
PASSED
Control
Battery Basement inside FACP Narbonne Tested 8:58:40 AM 11/25/2025
Battery Basement inside FACP Narbonne Tested 8:58:46 AM 11/25/2025
Battery 1st inside FACP (Hawkes House) Tested 8:27:33 AM 11/25/2025
Battery 1st inside FACP (Hawkes House) Tested 8:27:37 AM 11/25/2025
Control Panel 1st inside Hawkes house in stair Tested 8:27:26 AM 11/25/2025
Indicating
Horn All inside Derby house Tested 9:25:40 AM 11/25/2025
Horn All inside Hawkes house Tested 8:27:29 AM 11/25/2025
Horn All inside west India goods Tested 9:43:58 AM 11/25/2025
Initiating
Heat Detector Basement right rear (Hawkes House) Tested 8:32:31 AM 11/25/2025
Heat Detector 3rd inside closet near restroom Derby House Tested 9:31:57 AM 11/25/2025
Heat Detector 3rd inside closet near souvenir Derby House Tested 9:33:29 AM 11/25/2025
Heat Detector 3rd inside closet near stairs Derby House Tested 9:34:01 AM 11/25/2025
Heat Detector 3rd inside rear stairwell left room (Hawkes House)
Tested 8:39:48 AM 11/25/2025
Heat Detector 3rd inside restroom (Hawkes House) Tested 8:39:55 AM 11/25/2025
Page of 8 23
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 3 - Siemens SXL-EXBuilding: 176 DERBY ST
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Heat Detector Attic above door (Hawkes House) Tested 8:42:26 AM 11/25/2025
Heat Detector Attic behind stairs (Hawkes House) Tested 8:41:53 AM 11/25/2025
Heat Detector Attic near right side (Hawkes House) Tested 8:41:39 AM 11/25/2025
Heat Detector Attic near roof (Hawkes House) Tested 8:42:35 AM 11/25/2025
Pull Station 1st near front entrance (Hawkes House) Tested 8:28:09 AM 11/25/2025
Pull Station 1st near rear entrance (Hawkes House) Tested 8:33:18 AM 11/25/2025
Pull Station 3rd inside front stairwell (Hawkes House) Tested 8:38:59 AM 11/25/2025
Pull Station 3rd inside rear stairwell (Hawkes House) Tested 8:39:45 AM 11/25/2025
Smoke Detector Basement left side (Hawkes House) Tested 8:32:38 AM 11/25/2025
Smoke Detector Basement rear (Hawkes House) Tested 8:32:34 AM 11/25/2025
Smoke Detector Basement right rear (Hawkes House) Tested 8:34:45 AM 11/25/2025
Smoke Detector 1st front copy machine (Hawkes House) Tested 8:47:17 AM 11/25/2025
Smoke Detector 1st front office (Hawkes House) Tested 8:47:14 AM 11/25/2025
Smoke Detector 1st front stairwell (Hawkes House) Tested 8:30:01 AM 11/25/2025
Smoke Detector 1st rear office space (Hawkes House) Tested 8:36:17 AM 11/25/2025
Smoke Detector 1st rear side room (Hawkes House) Tested 8:35:31 AM 11/25/2025
Smoke Detector 1st rear stairwell (Hawkes House) Tested 8:37:34 AM 11/25/2025
Smoke Detector 2nd inside front stairwell (Hawkes House) Tested 8:37:28 AM 11/25/2025
Smoke Detector 2nd inside rear stairwell (Hawkes House) Tested 8:36:47 AM 11/25/2025
Smoke Detector 3rd inside front stairwell (Hawkes House) Tested 8:38:21 AM 11/25/2025
Smoke Detector 3rd inside rear stairwell (Hawkes House) Tested 8:39:29 AM 11/25/2025
Smoke Detector 3rd near rear stairwell right room (Hawkes House)
Tested 8:39:20 AM 11/25/2025
Smoke Detector Attic above stairs (Hawkes House) Tested 8:40:49 AM 11/25/2025
Page of 9 23
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 4 - Siemens SXL-EXBuilding: 176 DERBY ST
Device Type Location Service Time Date
PASSED
Control
Battery Basement inside derby house FACP Tested 9:25:46 AM 11/25/2025
Battery Basement inside derby house FACP Tested 9:25:52 AM 11/25/2025
Control Panel Basement inside derby house Tested 9:25:36 AM 11/25/2025
Initiating
Pull Station 1st inside closet Derby house Tested 9:26:39 AM 11/25/2025
Smoke Detector Basement left side Derby house Tested 9:35:59 AM 11/25/2025
Smoke Detector Basement right side Derby house Tested 9:35:55 AM 11/25/2025
Smoke Detector 1st inside dining room Derby house Tested 9:32:41 AM 11/25/2025
Smoke Detector 1st inside display room Derby house Tested 9:26:57 AM 11/25/2025
Smoke Detector 1st inside fine dining room Derby house Tested 9:32:48 AM 11/25/2025
Smoke Detector 1st inside office Derby house Tested 9:32:34 AM 11/25/2025
Smoke Detector 2nd inside empty bedroom Derby house Tested 9:32:02 AM 11/25/2025
Smoke Detector 2nd inside green bedroom Derby house Tested 9:32:09 AM 11/25/2025
Smoke Detector 2nd inside guest bedroom Derby house Tested 9:32:05 AM 11/25/2025
Smoke Detector 2nd inside white bedroom Derby house Tested 9:32:12 AM 11/25/2025
Smoke Detector 2nd top of front stairwell Derby house Tested 9:28:43 AM 11/25/2025
Smoke Detector 3rd at top of stairs Derby house Tested 9:31:00 AM 11/25/2025
Smoke Detector 3rd inside paper room Derby house Tested 9:32:53 AM 11/25/2025
Smoke Detector 3rd inside restroom Derby house Tested 9:31:09 AM 11/25/2025
Smoke Detector 3rd inside souvenir room Derby house Tested 9:33:10 AM 11/25/2025
Smoke Detector 3rd inside spare room Derby house Tested 9:32:26 AM 11/25/2025
Smoke Detector 3rd inside wood room Derby house Tested 9:33:56 AM 11/25/2025
Page of 10 23
Norel Service Company, Inc. Download Date: 09/01/2026
Control Panel: 5 - Siemens SXL-EXBuilding: 176 DERBY ST
Device Type Location Service Time Date
PASSED
Control
Control Panel Basement inside Narbonne house Tested 8:58:20 AM 11/25/2025
Initiating
Heat Detector Basement inside Narbonne house Tested 8:58:55 AM 11/25/2025
Smoke Detector Basement above FACP Narbonne house Tested 8:58:07 AM 11/25/2025
Smoke Detector 1st above display table Narbonne house Tested 8:59:15 AM 11/25/2025
Smoke Detector 1st above stairs Narbonne house Tested 8:59:11 AM 11/25/2025
Smoke Detector 1st near entrance Narbonne Tested 8:55:09 AM 11/25/2025
Smoke Detector 1st near fireplace Narbonne house Tested 8:53:02 AM 11/25/2025
Smoke Detector 2nd above stairs Narbonne Tested 8:56:45 AM 11/25/2025
Device Type Location Service Time Date
PASSED
Control
Battery 1st inside FACP West India goods Tested 9:44:05 AM 11/25/2025
Battery 1st inside FACP West India goods Tested 9:44:08 AM 11/25/2025
Control Panel 1st inside West India goods Tested 9:43:54 AM 11/25/2025
Initiating
Heat Detector 1st inside west India goods near entrance Tested 9:44:40 AM 11/25/2025
Heat Detector 1st inside west India goods top of stairs Tested 9:50:36 AM 11/25/2025
Pull Station 1st inside hall West India goods Tested 9:46:05 AM 11/25/2025
Smoke Detector 1st…