This document is an Addendum (Addendum 2) to a federal solicitation for the Yosemite National Park (YOSE) Tuolumne Meadows Water Distribution System Rehabilitation project (Solicitation Number 140P2025R0062). The project involves comprehensive water infrastructure upgrades, including water line rehabilitation, water tank construction, tree removal, and staging area preparations. Key technical details include installing a new water tank, replacing water distribution lines, addressing tree removal requirements, and establishing specific construction guidelines for sensitive park environments.
The addendum provides detailed responses to 28 contractor questions covering critical project aspects such as water line configurations, fire service lines, staging area management, tree removal protocols, and contractor logistics. Notable requirements include tree removal outside breeding seasons, specific ground stabilization practices, restoration of staging areas, and unique site-specific constraints like preserving the Great Sierra Wagon Road visitor access. The project allows contractor RV camping in a designated area with specific bear safety requirements, and provides clarification on concrete batching, electrical installations, and spoil disposal locations. The project is managed by the Department of the Interior National Park Service and aims to rehabilitate a water system that currently provides an average of 34,000 gallons of potable water daily to park visitor areas and NPS facilities.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
YOSE 228647 Rehabilitate Tuolumne Meadows Water Distribution System, 140P2025R0062 Addendum 2: NPS Responses to Contractor Questions 8/19/2025
Note: Grayed sections represents questions addressed in previous addendum.
| Area/Location |
| Contractor Question |
| NPS Response |
| 1 |
| Tuolumne Wastewater Treatment Plan |
| Is the fire service line separate from the domestic water line, particularly in reference to the fire hydrant and associated shut-off valve? |
| The domestic water line and fire service line utilizes the same water system. |
| 2 |
| All Staging Areas |
| Will the contractor be required to place ballast or other ground stabilization material in the designated staging area? |
| Best Management Practices such as silt fences, rice wattles, and other ground stabilizing material are required to be placed in locations per the Contractor SWPPP that is submitted into SMARTS and approved by the State Regional Water Quality Control Board. |
| 3 |
| All Staging Areas |
| Clarify the contractor’s responsibility for restoration of the staging areas, including any required repairs to existing surfaces such as parking lots or paved areas used during construction |
| Contractor is required to restore staging areas, including repairs to the existing asphalt caused by contractor equipment. |
| 4 |
| Tuolumne Water Line |
| Perma-pipes Polytherm product is listed in the specifications. Can you help to clarify where the Polytherm product is required? |
| The Polytherm product is an anti-corrosion coating outside of the carrier pipe that is hung under the Tuolumne River Bridge. Sheet 20S100 20S501 (pdf pg 62 and 63) |
| 5 |
| Proposed Water Tank |
| Are their safety/security features that need to be included with construction of the proposed water tank? |
| Yes. As a supplement to WELDED STEEL TANK Specification 33 16 13.13: |
1. Provide metal signage at tank top access hatch (roof level) and tank manway (ground level) that says “Danger Confined Space” pursuant to 29 CFR 1910.146(c)(2).
2. Provide a self-closing gate with a lockable latch that slides/swings away from the ladder and will not swing/drop onto the operators head. Pursuant to 29 CFR 1910.29(b)(13)(i).
| 6 |
| Tuolumne Water Tank |
| Is the contractor responsible for the removal and disposal of tree stumps within the designated work area? |
| Yes contractor is responsible for the removal and disposal of tree stumps. |
| 7 |
| Tuolumne Water Tank |
| Will tree roots located within the line of disturbance be removed entirely, or is partial removal acceptable depending on proximity to new construction? |
| Full removal of tree roots is necessary. |
| 8 |
| Tuolumne Water Tank |
| Is there a defined line of disturbance associated with the project/new water tank construction? |
| Sheet 10C100 (Sheet 60 of 73) shows the new tank location. The elevation of the new tank is lower than the existing ground topography and will require the Contractor to make a 2:1 daylight to match the existing grade. This daylight line is noted on Sheet 10C100 and is the defined line of disturbance. |
| 9 |
| Tuolumne Water Tank |
| Is the contractor responsible for identifying and marking trees designated for removal? |
| Contractor is responsible for marking and confirming with YOSE prior to tree demolition in accordance with Tree Removal and Protection Spec, 32 00 00. |
| 10 |
| Tuolumne Water Tank |
| Is the contractor responsible for the removal of trees within the footprint of the new water tank installation? |
| Yes, the Contractor is required to remove existing trees within the construction footprint of the new water tank installation. Per Tree Removal and Protection Spec, 32 00 00, contractor shall submit a tree removal and tree protection plan for approval by the Contracting Officer's Representative. Identify equipment and foot traffic routes, material stockpile locations, planned tree removals, and planned tree protection measures in the plan. |
NPS has provided a Tree Demolition Exhibit with Addendum 1 showing approximate tree location, diameter, and species.
| 11 |
| Tree Removal and Protection Spec, 32 00 00 |
| When can tree trimming, clearing, and felling activities occur? |
| Per Tree Removal and Protection Spec, 32 00 00, all tree trimming, clearing, and felling activities required by this Project shall be performed outside the dates of April 1st thru September 15th for the protection of breeding bats and birds.” |
HOWEVER, such activities mentioned above may occur during the breeding season (May 1 – July 31) if a Terrestrial Wildlife survey is performed by YOSE NPS. As noted in PEPC 99252:
If project work involves vegetation modification and occurs during the breeding season (May 1 - July 31), please reach out to terrestrial wildlife (heather_mackey@nps.gov) to arrange a survey for nesting migratory birds before removal or trimming, to fulfil requirements of the Migratory Bird Treaty Act of 1918. Once surveyed the project has 1 week to perform project work, if work is not completed within 1 week, trees must be resurveyed. If an active nest is discovered, project work may not occur within a 100-foot radius buffer of the nest until nestlings fledge.
| 12 |
| Ranger Station Stables |
| What portion of the identified staging area will be available for contractor use? |
| The Revised Staging Areas document has been uploaded along with this Addendum. This document clarifies this area. |
| 13 |
| Piping Line along Great Sierra Wagon Rd |
| Will the Great Sierra Wagon Road be closed to visitors during construction? |
| The Great Wagon Sierra Road will detour visitor pedestrian to a temporary route adjacent to the Great Wagon Sierra Road to allow for Contractor full access along this corridor. Contractor to coordinate with YOSE for a period between September and October for this section of pipe. Sht 24-26, Sta 83+50 to 108+00. |
| 14 |
| All Staging Areas |
| Is the contractor required to limit staging activities to specific areas at any given time, or will full use of all designated staging zones be permitted throughout the project duration? |
| The Revised Staging Areas document has been uploaded along with this Addendum. This document clarifies the staging activities. |
| 15 |
| Spec Vol 2, 00 01 01 iv |
| Volume 2 Specs Table of Contents, 00 01 01 – iv, identifies “reference documents” for the Tuolumne River Bridge. We did not see these among the documents provided. Please let us know where we can find these. |
| The 2022 Bridge Inspection Report has been uploaded along with this Addendum. |
| 16 |
| Plan Sheet 68, Detail 3312-795 |
| Detail 3312-795 for backflow preventers on Plan Sheet 68 shows an “INSULATED FIBERGLASS ENCLOSURE WITH ELECTRIC HEATER”. Note 5 of the detail says to “INSTALL 100 VOLT PLUG GFCI RECEPTACLE”. Other than the electric plan sheets in the project plan set for the Tank Site, we do not find any plans for where electrical service is to be used for connection to the various backflow preventer locations to energize an electric heater or a new GFCI receptacle. Are the backflow preventer enclosures intended to have electric heaters and GFCI receptacles? Please clarify the project intent relative to these two issues. |
| The 100V plug and GFCI receptacle are erroneously added to Detail 3312-795 for backflow prevention. Backflow preventer assemblies are not intended to have electric heaters and GFCI receptacles. Offeror to remove the 100V plug and GFCI receptacle when submitting their bid. Offeror to include insulated fiberglass enclosure for each backflow preventer. |
| 17 |
| Plan Sheet 67, Detail 3311-072 |
| Detail 3311-072 on Plan Sheet 67 shows 1.5” and 2” Water Meter sizes. Yet the service piping sizes shown on the plans for the various water services are only 1” and 2”. There are no 1.5” service lines shown. We expect that the intent was to provide the same size Water Meter on the run of pipe associated with that meter, meaning a 2” meter on 2” service lines and a 1” meter on 1” service lines. Please confirm this is a correct interpretation. |
| Visitor Center Restroom meter on Sheet 17 calls for a 1.5” meter. Include appropriate reducer fittings to connect to service line in bid. |
Aside from the notation above, utilize a 1” meter on a 1” service line and a 2” meter on a 2” service line in bid.
| 18 |
| Plan Sheet 39 |
| On Plan Sheet 39 ENLARGED PLAN RANGER STATION EAST, there is a ‘random’ Backflow Preventer Symbol’ that is not associated with a pipe service line. We believe this is an inadvertent symbol not meant to be used in this area, but please confirm. If it is intended to be used, please provide a revised piping layout to show where and how this BFP is incorporated into the project. |
| The ’random’ Backflow Prevention Symbol is a drafting error. No backflow prevention assembly is intended for this area. |
| 19 |
| Specification 31 23 16 EXCAVATION |
| Specification 31 23 16 EXCAVATION, paragraph 3.07A says to “Dispose of excavated materials, which are unsuitable or not needed for fill or backfill, in designated spoil disposal areas.” Please identify the designated location or locations of allowable spoil disposal areas. |
| Boulders and rock may be disposed of by the Contractor to the May Lake Quarry. |
Excess cut material may be temporary stored as described in the Revised Staging Area document.
Trunks, slash, and roots shall be removed out of the park Contractor.
| 20 |
| Asphalt Patching |
| Please confirm if there is any asphalt patch work, as none is shown in the plans. |
| Contractor is required to perform asphalt patch work wherever the installed water line requires open trench cuts into the existing asphalt per Detail 3123-115B (Sht 64) and Detail 3212-215 (Sht 65). |
Examples of water line requiring open trench cuts into existing asphalt are listed below (but are not limited to these examples alone):
Sht 17 apprx Sta 13+40 to 16+40 Sht 24 apprx Sta 80+50 to 80+75 Sht 26 apprx Sta 108+35 to 108+65 Sht 28 apprx Sta 126+00 to 128+00 Sht 29 apprx Sta 129+75 to 130+00 Sht 29 apprx Sta 136+20 to 136+40 Sht 33 apprx Sta 212+50 to 212+90 Sht 37 Sta 111+30 to 112+90
Do note that a previous Tioga Road pavement project installed casing pipe allowing this project to avoid cutting into Tioga Road asphalt pavement when crossing Tioga Road.
| 21 |
| Electrical Question |
| Is the installation of any new electrical panels included in this project? |
| This project does not include installation of new electrical panels. |
| 22 |
| Water Tank |
| Will an aeration system be required for the welded steel tank? |
No aeration system is required.
| 23 |
| Contractor Logistics |
| Is there any requirement for river flow diversion? |
There is no requirement for river flow diversion.
| 24 |
| Contractor Logistics |
| Will it be necessary to establish a self-batching plant for concrete? |
| Contractor has discretion as to the use of a concrete batch plant for this project. Please note the attached Revised Staging Area document states that the Upper Dog Lake Parking Lot and Concessionaire Stables Parking Lot staging area (which is in the vicinity of the TM Water Treatment Plant) is a permissible location for a concrete batch plant. |
| 25 |
| Contractor Price Schedule |
| Are trees are required to be removed as part of this project and if so, what CLIN should it be assigned too? |
| Contractor is responsible to remove all trees required to successfully complete the project. We anticipate tree removal at the Visitor Center (Sta 10+00 to xx+XX), Trunks, slash, and roots shall be removed out of the park. Tree removal occurring along the water alignment shall be part of CLIN 0001 Water Distribution Pipeline. Tree removal occurring in the footprint of the Water Treatment Plant and new water storage tank shall be as part of CLIN 004 Water Tank Demolition. |
Contractor is responsible for the confirm the full tree removal count. However there is a density of trees at the following location:
Sta 10+50 to 13+00 (Road Camp) Sta 17+00 to 18+60 (along Visitor Center Exit) Sta 219+50 to 227+50 (Sht 33 to 35) Sta 152+75 (New Water Tank)
| 27 |
| Contract Price Schedule |
| Please clarify the process flow for removing and replacing the existing antenna tower located adjacent to the existing water storage tank. |
| Process flow as follows: |
1. Others will remove the top section of the existing tower before Contractor mobilization.
2. Contractor to remove the concrete tower base (apprx 4 cubic yards).
3. Others to project a new tower including the new foundation, tower assembly, and electrical run after the Contractor completion.
Removal of existing concrete tower base shall be part of Water Tank Demolition, CLIN 004.
| 28 |
| Contractor Ability to RV Camp |
| Is there ability for the Contractor to be housed in Tuolumne Meadows? |
| Yes! The Contractor may use their portion of the Tuolumne Meadows Concessionaire Stable Parking Lot staging area for dry RV camping (please see the Revised Staging Areas document for location). The Contractor shall submit an RV Camping Plan which will be reviewed and approved by Yosemite. There will not be any traditional power, sewer, or water hookups. |
The Mobil Gas Station in Lee Vining and the Upper Pines Campground in Yosemite Valley are the nearest RV dump stations (The Tuolumne Meadows dump station will be closed for the duration of this project). Food must be stored in completely hard sided RVs or stored in the metal Bear Saver bins that are provided on site.
Yosemite anticipates the RV count to not exceed 10 RVs.