Attachment_7_-_2023_Fire_Alarm_Tests_Combined_0001.pdf

PDF 7 MB Posted

Attached to
GLAC FIRE ALARM & SPRINKLER INSPECTIONS Federal contract opportunity
Solicitation number
140P1426Q0090
Issued by
Department of the Interior National Park Service Intermountain Region

About this file

This file is a collection of Fire Alarm Inspection and Testing Certificates documenting NFPA 72 compliance inspections conducted by Systems Northwest for multiple buildings at Glacier National Park between May 1-3, 2023. The inspections cover ten separate properties including dorms, apartments, administrative buildings, and specialized facilities, with testing performed by Luke Salewsky (License #FPL-IEL-LIC-001176) and accepted by Jon Murphy or Job Murphy representing Glacier National Park.

The certificates detail comprehensive testing results across fire control panels, initiating devices (smoke detectors, heat detectors, manual pull stations), power supplies (sealed lead-acid batteries), and water-based fire protection systems (waterflow switches, supervisory switches, and tamper switches). Most buildings achieved 100% pass rates on tested equipment; however, three buildings identified corrective actions requiring resolution: Building 41-55 Apartments had two failed supervisory low air switches and waterflow devices (marked as "missing on fire panel" and unresponsive); Archive Building #37 had one failed smoke detector in the vault requiring programming correction; and Building #217 Library had two batteries rated at 7Ah that tested significantly below capacity (2Ah and 3.9Ah), subsequently replaced during a follow-up inspection on the same date. The Headquarters Building had two skipped smoke detectors due to denied access. All inspections documented equipment specifications including manufacturer models (Silent Knight, Honeywell, FireLite, Simplex, Ademco, and Premium Power batteries), installation dates primarily from April-May 2021, and detailed load voltages and charger specifications for backup power systems.

View the file

Other files for this federal contract opportunity

Other files attached to GLAC FIRE ALARM & SPRINKLER INSPECTIONS, newest first.
File Type Posted
Attachment_6_-_Amendment_0001_Q_As_0001.docx DOCX document
Sol_140P1426Q0090_Amd_0001.pdf PDF
Attachment_8_-_2023_Fire_Sprinkler_Test_Reports_Combined_0001.pdf PDF
Attachment_2_-_Price_Schedule.xlsx XLSX spreadsheet
Attachment_4_-_Wage_Determination_-_Flathead_Co_.pdf PDF
Attachment_5_-_Wage_Determination_-_Glacier_Co_.pdf PDF
Attachment_3_-_2026_Fire_Alarm_and_Sprinkler_Inspections_Schedule.pdf PDF
Attachment_1_-_Scope_of_Work.docx DOCX document
Sol_140P1426Q0090.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Certificate Presented To

Glacier National Park

For

#69 Dorm 35

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Monday, May 01, 2023

Test Session :01 May 2023 10:35

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903 United States

Systems Northwest

Inspection Summary

Building Information

PROPERTY #69 Dorm 35 CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

13 13(100%) 13(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

1 1(100%) 1(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Monday, May 01, 2023

ACCEPTED BY 05/01/2023 TESTED BY 05/01/2023

Jon Murphy Luke Salewsky

Building Representative Technician

Fire Control Panel

Initiating Device

Power Supplies

Water-Based Fire Protection Systems

Page 2 of 6Systems Northwest

System Details

Control Units

DESCRIPTION FACPADDRESS / SCAN ADDRESS FACP

S/W VERSIONMANUFACTURER Silent Knight

LAST UPDATEMODEL 5808

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 04/25/2021

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.59 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 13.73

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.67 AMP HOURS 8

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 13.73

Page 3 of 6Systems Northwest

Testing Details

Fire Control Panel

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP FACP Manual 5/1/2023 11:02:17 AM

Manufacturer Silent Knight

Model 5808

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Waterflow M4 Riser WF Manual 5/1/2023 11:09:29 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S9 Living Area Manual 5/1/2023 11:10:00 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S8 Kitchen Manual 5/1/2023 11:10:17 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S7 Hall Manual 5/1/2023 11:10:41 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S5 Hall Manual 5/1/2023 11:11:26 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S10 Room A Manual 5/1/2023 11:11:31 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S3 Room D Manual 5/1/2023 11:11:33 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S11 Room B Manual 5/1/2023 11:12:04 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S4 Room C Manual 5/1/2023 11:12:08 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S2 Room E Manual 5/1/2023 11:12:28 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S1 FACP Manual 5/1/2023 11:12:30 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M2 Hall Manual 5/1/2023 11:15:39 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1 Hall Manual 5/1/2023 11:15:41 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Page 4 of 6Systems Northwest

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/1/2023 11:07:09 AM

Comment: 6 Ah

Manufacturer Centennial

Model CB1280

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 8

Battery Location FACP

Charger Voltage 13.73

Load Voltage 12.67

Nominal Voltage 12

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/1/2023 11:20:36 AM

Comment: 6.7 Ah

Manufacturer Centennial

Model CB1280

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 7

Battery Location FACP

Charger Voltage 13.73

Load Voltage 12.59

Nominal Voltage 12

Water-Based Fire Protection Systems

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Supervisory Low Air Switch M3 Riser Tamper Manual 5/1/2023 11:15:44 AM

Visual Inspection Passed (Manual)

Page 5 of 6Systems Northwest

Device/Equipment Details

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP FACP Silent Knight 5808 04/26/2021

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

S1 FACP 04/26/2021

S2 Room E 04/26/2021

S3 Room D 04/26/2021

S4 Room C 04/26/2021

S5 Hall 04/26/2021

S7 Hall 04/26/2021

S8 Kitchen 04/26/2021

S9 Living Area 04/26/2021

S10 Room A 04/26/2021

S11 Room B 04/26/2021

Manual Pull Station

M1 Hall 04/26/2021

M2 Hall 04/26/2021

Waterflow

M4 Riser WF 04/26/2021

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 Centennial CB1280 04/26/2021

Battery 2 FACP Battery 2 Centennial CB1280 04/26/2021

Water-Based Fire Protection Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Supervisory Low Air Switch

M3 Riser Tamper 04/26/2021

Page 6 of 6Systems Northwest

Glacier National Park

For

41-55 Apartments

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Tuesday, May 02, 2023

Test Session :02 May 2023 14:55

ACCEPTED BY TESTED BY

Job Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY 41-55 Apartments CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

15 15(100%) 15(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

3 3(100%) 1(33%) 2(67%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Tuesday, May 02, 2023

ACCEPTED BY 05/02/2023 TESTED BY 05/02/2023

Job Murphy Luke Salewsky

Building Representative Technician

Fire Control Panel

Initiating Device

Power Supplies

Page 2 of 7Systems Northwest

DESCRIPTION FACPADDRESS / SCAN ADDRESS FACP

S/W VERSIONMANUFACTURER Honeywell

LAST UPDATEMODEL GWF-7075

S/W LOCATIONSERIAL NUMBER

INSTALL DATE

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.81 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.56

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.82 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.56

Page 3 of 7Systems Northwest

Open Corrective Action & Solution Summary The following 2 corrective action(s) remain open following the system inspection, testing or maintenance activities

EQUIPMENT TYPE ADDRESS DESCRIPTION

Supervisory Low Air Switch 18 Riser Low Air

Created By: Luke Salewsky

Creation Date: 05/02/2023

Corrective Action: Device shows missing on fire panel. When testing it is in responsive.

Proposed Solution: Replace module.

Manufacturer:

Model:

Water Flow 19 Riser Water Flow

Created By: Luke Salewsky

Creation Date: 05/02/2023

Corrective Action: Device shows missing on fire panel. When testing it is in responsive.

Proposed Solution: Replace module

Manufacturer:

Model:

Page 4 of 7Systems Northwest

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP FACP Manual 5/2/2023 3:11:22 PM

Manufacturer Honeywell

Model GWF-7075

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General 8 FACP Manual 5/2/2023 3:01:05 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 10 Dorm 51 Manual 5/2/2023 3:02:38 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 3 Dorm 43 Living Manual 5/2/2023 3:04:26 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 4 Dorm 43 Bedroom Manual 5/2/2023 3:04:43 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 5 Dorm 45 Manual 5/2/2023 3:05:33 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 6 Dorm 47 Manual 5/2/2023 3:06:43 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 9 Dorm 49 Manual 5/2/2023 3:07:33 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 11 Dorm 53 Living Manual 5/2/2023 3:09:25 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 12 Dorm 53 Bedroom Manual 5/2/2023 3:09:34 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 14 Dorm 55 Living Manual 5/2/2023 3:10:19 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 13 Dorm 55 Bedroom Manual 5/2/2023 3:10:32 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 1 Dorm 41 Living Manual 5/2/2023 3:10:55 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 2 Dorm 41 Bedroom Manual 5/2/2023 3:11:04 PM

Visual Inspection Passed (Manual)

Page 5 of 7Systems Northwest

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General 7 Laundry Room Manual 5/2/2023 3:12:14 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station 15 Outside Manual 5/2/2023 3:16:58 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/2/2023 3:15:25 PM

Comment: 7.6 Ah

Manufacturer PowerSonic

Model PS-1270

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 7

Battery Location FACP

Charger Voltage 27.56

Load Voltage 12.82

Nominal Voltage 12

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/2/2023 3:16:26 PM

Comment: 6.8 Ah

Manufacturer PowerSonic

Model PS-1270

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 7

Battery Location FACP

Charger Voltage 27.56

Load Voltage 12.81

Nominal Voltage 12

Water-Based Fire Protection Systems

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Supervisory Tamper Switch 16 OS&Y Manual 5/2/2023 3:16:46 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Failed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Supervisory Low Air Switch 18 Riser Low Air Manual 5/2/2023 3:26:28 PM

Visual Inspection Failed (Manual)

Functional Inspection Failed

Water Flow 19 Riser Water Flow Manual 5/2/2023 3:27:13 PM

Visual Inspection Failed (Manual)

Functional Inspection Failed

Page 6 of 7Systems Northwest

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP FACP Honeywell GWF-7075

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

1 Dorm 41 Living

2 Dorm 41 Bedroom

3 Dorm 43 Living

4 Dorm 43 Bedroom

5 Dorm 45

6 Dorm 47

7 Laundry Room

8 FACP

9 Dorm 49

10 Dorm 51

11 Dorm 53 Living

12 Dorm 53 Bedroom

13 Dorm 55 Bedroom

14 Dorm 55 Living

Manual Pull Station

15 Outside

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 PowerSonic PS-1270

Battery 2 FACP Battery 2 PowerSonic PS-1270

Water-Based Fire Protection Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Supervisory Tamper Switch

16 OS&Y

Supervisory Low Air Switch

18 Riser Low Air

Water Flow

19 Riser Water Flow

Page 7 of 7Systems Northwest

Glacier National Park

For

99-113 Apartments

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Tuesday, May 02, 2023

Test Session :02 May 2023 15:32

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY 99-113 Apartments CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

15 15(100%) 15(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

4 4(100%) 4(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Tuesday, May 02, 2023

ACCEPTED BY 05/02/2023 TESTED BY 05/02/2023

Jon Murphy Luke Salewsky

Building Representative Technician

[Other]

Initiating Device

Power Supplies

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.65 AMP HOURS 8

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.55

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.87 AMP HOURS 8

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.55

[Other]

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

[Other] FACP FACP Manual 5/2/2023 3:48:33 PM

Manufacturer Honeywell

Model GWF-7075

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General 1 Dorm 99 Living Manual 5/2/2023 3:39:44 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 2 Dorm 99 Bedroom Manual 5/2/2023 3:39:47 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 3 Dorm 101 Living Manual 5/2/2023 3:40:47 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 4 Dorm 101 Bedroom Manual 5/2/2023 3:40:54 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 5 Dorm 103 Manual 5/2/2023 3:41:41 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 6 Dorm 105 Manual 5/2/2023 3:42:27 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 9 Dorm 107 Manual 5/2/2023 3:43:18 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 10 Dorm 109 Manual 5/2/2023 3:43:34 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 7 Laundry Room Manual 5/2/2023 3:44:53 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 11 Dorm 111 Living Manual 5/2/2023 3:46:02 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 13 Dorm 111 Bedroom Manual 5/2/2023 3:46:52 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 12 Dorm 113 Bedroom Manual 5/2/2023 3:47:47 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 14 Dorm 113 Living Manual 5/2/2023 3:47:50 PM

Visual Inspection Passed (Manual)

Manual Pull Station 15 Outside Manual 5/2/2023 3:48:11 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 8 FACP Manual 5/2/2023 3:48:30 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/2/2023 3:51:47 PM

Comment: 7.8 Ah

Manufacturer Premium Power

Model UB1280-ER

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 8

Battery Location FACP

Charger Voltage 27.55

Load Voltage 12.87

Nominal Voltage 12

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/2/2023 3:52:19 PM

Comment: 7.6 Ah

Manufacturer Premium Power

Model UB1280-ER

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 8

Battery Location FACP

Charger Voltage 27.55

Load Voltage 12.65

Nominal Voltage 12

Water-Based Fire Protection Systems

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Supervisory Tamper Switch 16 OS&Y Manual 5/2/2023 3:48:27 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Supervisory Low Air Switch 17 Riser Low Air Manual 5/2/2023 3:48:29 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Water Flow 18 Riser Water Flow Manual 5/2/2023 4:05:44 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Supervisory Tamper Switch 19 Riser Tamper Manual 5/2/2023 4:05:46 PM

Visual Inspection Passed (Manual)

[Other]

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

[Other]

FACP FACP Honeywell GWF-7075

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

1 Dorm 99 Living

2 Dorm 99 Bedroom

3 Dorm 101 Living

4 Dorm 101 Bedroom

5 Dorm 103

6 Dorm 105

7 Laundry Room

8 FACP

9 Dorm 107

10 Dorm 109

11 Dorm 111 Living

12 Dorm 113 Bedroom

13 Dorm 111 Bedroom

14 Dorm 113 Living

Manual Pull Station

15 Outside

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 Premium Power UB1280-ER

Battery 2 FACP Battery 2 Premium Power UB1280-ER

Water-Based Fire Protection Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Supervisory Tamper Switch

16 OS&Y

19 Riser Tamper

Supervisory Low Air Switch

17 Riser Low Air

Water Flow

18 Riser Water Flow

Glacier National Park

For

201 Paint Shop Building

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Tuesday, May 02, 2023

Test Session :02 May 2023 14:15

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY 201 Paint Shop Building CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

1 1(100%) 1(100%) 0(0%)

6 6(100%) 6(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Tuesday, May 02, 2023

ACCEPTED BY 05/02/2023 TESTED BY 05/02/2023

Jon Murphy Luke Salewsky

Building Representative Technician

Chemical Extinguishing Systems

Fire Control Panel

Initiating Device

Power Supplies

DESCRIPTION FACPADDRESS / SCAN ADDRESS FACP

S/W VERSIONMANUFACTURER FireLite

LAST UPDATEMODEL MS-9200UDLS

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 04/25/2021

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE

LOAD VOLTAGE 12.66 AMP HOURS

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION CHARGER VOLTAGE 27.35

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE

LOAD VOLTAGE 12.78 AMP HOURS

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION CHARGER VOLTAGE 27.35

Chemical Extinguishing Systems

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fuel Shut-off Operated Correctly

L1M08 Gas Shutoff Manual 5/2/2023 2:30:07 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Fire Control Panel

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP FACP Manual 5/2/2023 2:23:20 PM

Manufacturer FireLite

Model MS-9200UDLS

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Manual Pull Station L1M01 Riser Room Manual 5/2/2023 2:23:17 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Valve Tamper Switch L1M06 Riser Room Tamper Manual 5/2/2023 2:23:23 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station L1M02 East Exit Manual 5/2/2023 2:23:25 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station L1M03 West Exit Manual 5/2/2023 2:23:27 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station L1M04 Office Area Manual 5/2/2023 2:23:29 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General L1D01 Riser Room Manual 5/2/2023 2:23:31 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/2/2023 2:37:34 PM

Comment: 7.2 Ah

Manufacturer Premium Power

Model UB1280-ER

Visual Inspection Passed (Manual)

Functional Inspection Passed

Charger Voltage 27.35

Load Voltage 12.78

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/2/2023 2:39:58 PM

Comment: 6.8 Ah

Manufacturer Premium Power

Model UB1280-ER

Visual Inspection Passed (Manual)

Functional Inspection Passed

Charger Voltage 27.35

Load Voltage 12.66

Water-Based Fire Protection Systems

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Water Flow L1M05 Riser WF Manual 5/2/2023 2:23:19 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Supervisory Low Air Switch L1M07 Riser Low Air Manual 5/2/2023 2:23:33 PM

Visual Inspection Passed (Manual)

Chemical Extinguishing Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fuel Shut-off Operated Correctly

L1M08 Gas Shutoff 04/26/2021

Fire Control Panel

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP FACP FireLite MS-9200UDLS 04/26/2021

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

L1D01 Riser Room 04/26/2021

Manual Pull Station

L1M01 Riser Room 04/26/2021

L1M02 East Exit 04/26/2021

L1M03 West Exit 04/26/2021

L1M04 Office Area 04/26/2021

Valve Tamper Switch

L1M06 Riser Room Tamper 04/26/2021

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 Premium Power UB1280-ER 04/26/2021

Battery 2 FACP Battery 2 Premium Power UB1280-ER 04/26/2021

Water-Based Fire Protection Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Water Flow

L1M05 Riser WF 04/26/2021

Supervisory Low Air Switch

L1M07 Riser Low Air 04/26/2021

Glacier National Park

For

Apgar Transit Building #1584

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Monday, May 01, 2023

Test Session :01 May 2023 13:17

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY Apgar Transit Building #1584 CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

32 32(100%) 32(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

3 3(100%) 3(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Monday, May 01, 2023

ACCEPTED BY 05/01/2023 TESTED BY 05/01/2023

Jon Murphy Luke Salewsky

Building Representative Technician

Fire Control Panel

Initiating Device

Power Supplies

Page 2 of 8Systems Northwest

DESCRIPTION FACPADDRESS / SCAN ADDRESS FACP

S/W VERSIONMANUFACTURER Simplex

LAST UPDATEMODEL 4010

S/W LOCATIONSERIAL NUMBER

INSTALL DATE

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 13.19 AMP HOURS 14

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.49

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 13.25 AMP HOURS 14

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.49

Page 3 of 8Systems Northwest

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP FACP Manual 5/1/2023 1:18:38 PM

Manufacturer Simplex

Model 4010

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - Duct M1-11 EC1 Boiler Room Manual 5/1/2023 1:18:55 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - Duct M1-12 EC2 Boiler Room Manual 5/1/2023 1:18:56 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-5 FACP Manual 5/1/2023 1:19:38 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-6 Transit Management Manual 5/1/2023 1:27:35 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-10 Work Room Manual 5/1/2023 1:27:37 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-8 Break Room Manual 5/1/2023 1:27:39 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-7 Break Room Manual 5/1/2023 1:27:40 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-13 Mechanical Room Manual 5/1/2023 1:27:44 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-3 South Lobby Exit Manual 5/1/2023 1:27:45 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-1 North Lobby Manual 5/1/2023 1:27:47 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-15 Men's Vestibule Manual 5/1/2023 1:27:48 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-30 Mechanical Room by Men's Restroom Manual 5/1/2023 1:27:50 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-14 Janitor Room Manual 5/1/2023 1:27:52 PM

Visual Inspection Passed (Manual)

Page 4 of 8Systems Northwest

Heat Detector M1-28 Men's Restroom Manual 5/1/2023 1:27:53 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-32 Men's Restroom Manual 5/1/2023 1:27:59 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-17 Family Restroom Manual 5/1/2023 1:28:01 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-20 Women's Restroom Manual 5/1/2023 1:28:02 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-25 Women's Restroom Manual 5/1/2023 1:28:03 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-24 Women's Restroom Manual 5/1/2023 1:28:05 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-23 Attic Access Manual 5/1/2023 1:28:08 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-26 Women's Restroom Manual 5/1/2023 1:28:09 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-27 Women's Restroom Manual 5/1/2023 1:28:11 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-22 East Storage Manual 5/1/2023 1:28:13 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-19 Plumbing Room Manual 5/1/2023 1:28:14 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-21 Women's Restroom Manual 5/1/2023 1:28:17 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-18 Family Restroom Manual 5/1/2023 1:28:21 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-16 Men's Vestibule Manual 5/1/2023 1:28:23 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector M1-29 Men's Restroom Manual 5/1/2023 1:28:26 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Pull Station M1-31 Mechanical Room Men's Restroom Manual 5/1/2023 1:28:28 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-4 Counting Room Manual 5/1/2023 1:28:31 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General M1-9 West Side Storage Manual 5/1/2023 1:28:33 PM

Visual Inspection Passed (Manual)

Page 5 of 8Systems Northwest

Beam M1-2 Lobby Manual 5/1/2023 1:28:35 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/1/2023 1:38:43 PM

Comment: 14 Ah

Manufacturer Duracell

Model Dura12-14F2

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 14

Battery Location FACP

Charger Voltage 27.49

Load Voltage 13.19

Nominal Voltage 12

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/1/2023 1:39:36 PM

Comment: 13 Ah

Manufacturer Duracell

Model Dura12-14F2

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 14

Battery Location FACP

Charger Voltage 27.49

Load Voltage 13.25

Nominal Voltage 12

Water-Based Fire Protection Systems

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Supervisory Low Air Switch M1-38 Low Air Manual 5/1/2023 1:19:28 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Water Flow M1-37 Water Flow Manual 5/1/2023 1:19:31 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Supervisory Tamper Switch M1-36 Back Flow Tamper Manual 5/1/2023 1:19:33 PM

Visual Inspection Passed (Manual)

Page 6 of 8Systems Northwest

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP FACP Simplex 4010

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Manual Pull Station

M1-1 North Lobby

M1-3 South Lobby Exit

M1-7 Break Room

M1-16 Men's Vestibule

M1-18 Family Restroom

M1-21 Women's Restroom

M1-31 Mechanical Room Men's Restroom

Beam

M1-2 Lobby

Smoke Detector - General

M1-4 Counting Room

M1-5 FACP

M1-6 Transit Management

M1-8 Break Room

M1-9 West Side Storage

M1-10 Work Room

M1-13 Mechanical Room

M1-15 Men's Vestibule

M1-19 Plumbing Room

M1-22 East Storage

M1-23 Attic Access

M1-30 Mechanical Room by Men's Restroom

Smoke Detector - Duct

M1-11 EC1 Boiler Room

M1-12 EC2 Boiler Room

Heat Detector

M1-14 Janitor Room

M1-17 Family Restroom

M1-20 Women's Restroom

M1-24 Women's Restroom

M1-25 Women's Restroom

M1-26 Women's Restroom

M1-27 Women's Restroom

M1-28 Men's Restroom

M1-29 Men's Restroom

M1-32 Men's Restroom

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 Duracell Dura12-14F2

Battery 2 FACP Battery 2 Duracell Dura12-14F2

Page 7 of 8Systems Northwest

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Supervisory Tamper Switch

M1-36 Back Flow Tamper

Water Flow

M1-37 Water Flow

Supervisory Low Air Switch

M1-38 Low Air

Page 8 of 8Systems Northwest

Glacier National Park

For

Archive Building #37 (Museum Office)

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Tuesday, May 02, 2023

Test Session :02 May 2023 09:23

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY Archive Building #37 (Museum Office)

CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

6 6(100%) 5(83%) 1(17%)

2 2(100%) 2(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Tuesday, May 02, 2023

ACCEPTED BY 05/02/2023 TESTED BY 05/02/2023

Jon Murphy Luke Salewsky

Building Representative Technician

Fire Control Panel

Initiating Device

DESCRIPTION FACPADDRESS / SCAN ADDRESS FACP

S/W VERSIONMANUFACTURER Ademco

LAST UPDATEMODEL Vista-33FB

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 04/25/2021

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.94 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Above FACP CHARGER VOLTAGE 13.64

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.88 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Above FACP CHARGER VOLTAGE 13.64

The following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities

EQUIPMENT TYPE ADDRESS DESCRIPTION

Smoke Detector - General 1-6 Vault

Created By: Luke Salewsky

Creation Date: 05/02/2023

Corrective Action: Device is not programmed correctly to report as smoke detector. Device will not Annunciate locally as well.

Proposed Solution:

Manufacturer:

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP FACP Manual 5/2/2023 9:26:52 AM

Manufacturer Ademco

Model Vista-33FB

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Manual Pull Station 1-2 Office Manual 5/2/2023 9:26:55 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General 1-1 FACP Office Smoke Manual 5/2/2023 9:32:13 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Valve Tamper Switch 1-5 Riser Tamper Manual 5/2/2023 9:33:11 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Waterflow 1-3 Water Flow Manual 5/2/2023 9:33:14 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Supervisory - High/Low Air Pressure Switch

1-4 Riser Low Air Manual 5/2/2023 9:33:15 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Failed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General 1-6 Vault Manual 5/2/2023 9:30:30 AM

Functional Inspection Failed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/2/2023 9:35:17 AM

Comment: 6.4 Ah

Manufacturer PowerSonic

Model PS-1270

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 7

Battery Location Above FACP

Charger Voltage 13.64

Load Voltage 12.88

Nominal Voltage 12

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/2/2023 9:36:26 AM

Comment: 5.0 Ah

Manufacturer PowerSonic

Model PS-1270

Visual Inspection Passed (Manual)

Amp Hours 7

Battery Location Above FACP

Charger Voltage 13.64

Load Voltage 12.94

Nominal Voltage 12

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP FACP Ademco Vista-33FB 04/26/2021

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

1-1 FACP Office Smoke 04/26/2021

1-6 Vault 04/26/2021

Manual Pull Station

1-2 Office 04/26/2021

Waterflow

1-3 Water Flow 04/26/2021

Supervisory - High/Low Air Pressure Switch

1-4 Riser Low Air 04/26/2021

Valve Tamper Switch

1-5 Riser Tamper 04/26/2021

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 PowerSonic PS-1270 04/26/2021

Battery 2 FACP Battery 2 PowerSonic PS-1270 04/26/2021

Glacier National Park

For

B#215 Community Building

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Tuesday, May 02, 2023

Test Session :02 May 2023 16:22

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY B#215 Community Building CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

18 16(89%) 16(89%) 0(0%)

2 2(100%) 2(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Tuesday, May 02, 2023

ACCEPTED BY 05/02/2023 TESTED BY 05/02/2023

Jon Murphy Luke Salewsky

Building Representative Technician

Fire Control Panel

Initiating Device

DESCRIPTIONADDRESS / SCAN ADDRESS FACP

S/W VERSIONMANUFACTURER Honeywell

LAST UPDATEMODEL GWF-7075

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 05/01/2023

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION

ADDRESS / SCAN ADDRESS FACP Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.9 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION CHARGER VOLTAGE 27.52

TYPE Battery - Sealed Lead-acid DESCRIPTION

ADDRESS / SCAN ADDRESS FACP Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.96 AMP HOURS 7

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION CHARGER VOLTAGE 27.52

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Control Panel FACP Manual 5/2/2023 4:33:03 PM

Manufacturer Honeywell

Model GWF-7075

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General S001 Above FACP Manual 5/2/2023 4:34:40 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S008 Meeting Hall Manual 5/2/2023 4:34:46 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S009 Meeting Hall East Manual 5/2/2023 4:34:57 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M018 Meeting Hall Manual 5/2/2023 4:35:52 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S011 Storage Room Manual 5/2/2023 4:36:02 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S012 Corridor Manual 5/2/2023 4:36:11 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S004 Stage Manual 5/2/2023 4:36:49 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S002 in I/T Room Manual 5/2/2023 4:36:59 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S010 Day Room Manual 5/2/2023 4:37:37 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M019 Day Room Manual 5/2/2023 4:38:01 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S006 Fouer Manual 5/2/2023 4:38:17 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M016 Fouer Manual 5/2/2023 4:38:32 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Restorable Spot

S007 Warming Kitchen Manual 5/2/2023 4:38:41 PM

Visual Inspection Passed (Manual)

Pull Station M017 Warming Kitchen Manual 5/2/2023 4:38:49 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General S003 In Storage Room Manual 5/2/2023 4:39:52 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Restorable Spot

S005 Under Stage Manual 5/2/2023 4:52:40 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Skipped

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General S013 Basement Entry Manual 5/2/2023 4:30:00 PM

Comment: No access

Smoke Detector - General S014 Basement Main Manual 5/2/2023 4:30:00 PM

Comment: No access

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid FACP Battery 2 Manual 5/2/2023 4:56:45 PM

Comment: 7 Ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 7

Charger Voltage 27.52

Load Voltage 12.9

Nominal Voltage 12

Battery - Sealed Lead-acid FACP Battery 1 Manual 5/2/2023 4:57:47 PM

Comment: 7.4 Ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 7

Charger Voltage 27.52

Load Voltage 12.96

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Control Panel

FACP Honeywell GWF-7075 05/02/2023

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

S001 Above FACP 05/02/2023

S002 in I/T Room 05/02/2023

S003 In Storage Room 05/02/2023

S004 Stage 05/02/2023

S006 Fouer 05/02/2023

S008 Meeting Hall 05/02/2023

S009 Meeting Hall East 05/02/2023

S010 Day Room 05/02/2023

S011 Storage Room 05/02/2023

S012 Corridor 05/02/2023

S013 Basement Entry 05/02/2023

S014 Basement Main 05/02/2023

Heat Detector - Restorable Spot

S005 Under Stage 05/02/2023

S007 Warming Kitchen 05/02/2023

Pull Station

M016 Fouer 05/02/2023

M017 Warming Kitchen 05/02/2023

M018 Meeting Hall 05/02/2023

M019 Day Room 05/02/2023

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

FACP Battery 1 03/02/2020

FACP Battery 2 03/02/2020

Glacier National Park

For

Building # 686

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Wednesday, May 03, 2023

Test Session :03 May 2023 09:22

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY Building # 686 CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTRY United States EMAIL lukes@snwmt.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

1 1(100%) 1(100%) 0(0%)

17 17(100%) 17(100%) 0(0%)

2 2(100%) 2(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Wednesday, May 03, 2023

ACCEPTED BY 05/03/2023 TESTED BY 05/03/2023

Jon Murphy Luke Salewsky

Building Representative Technician

Fire Control Panel

Initiating Device

DESCRIPTION PANELADDRESS / SCAN ADDRESS N0

S/W VERSION V1MANUFACTURER FireLite

LAST UPDATEMODEL NFW-50X

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 04/29/2021

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 1

ADDRESS / SCAN ADDRESS Battery 1 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.78 AMP HOURS 8

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.49

TYPE Battery - Sealed Lead-acid DESCRIPTION FACP Battery 2

ADDRESS / SCAN ADDRESS Battery 2 NOMINAL VOLTAGE 12

LOAD VOLTAGE 12.16 AMP HOURS 8

STANDBY HOURS ALARM MINUTES

BATTERY LOCATION Battery - Nickel-cadmium CHARGER VOLTAGE 27.49

The following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities

EQUIPMENT TYPE ADDRESS DESCRIPTION

N/A General General

N/A

Created By: Luke Salewsky

Creation Date: 05/03/2023

Corrective Action: Control valve is not monitored

Proposed Solution: Install monitor module to monitor control valve

Manufacturer:

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Panel N000 N000 PANEL Manual 5/3/2023 9:23:34 AM

Manufacturer FireLite

Model NFW-50X

Visual Inspection Passed (Manual)

Functional Inspection Passed

Software Version V1

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Manual Fire Box N000 L1M008 MECHANICAL ROOM Manual 5/3/2023 9:23:23 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D001 PANEL SMOKE Manual 5/3/2023 9:23:28 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D005 UNIT 59A LIVING ROOM Manual 5/3/2023 9:47:07 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D006 UNIT 59A BEDROOM Manual 5/3/2023 9:47:23 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D004 UNIT 59B LIVING ROOM Manual 5/3/2023 9:48:18 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D007 UNIT 59B BEDROOM Manual 5/3/2023 9:48:34 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D009 UNIT 59C LIVING ROOM Manual 5/3/2023 9:49:28 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D010 UNIT 59D LIVING ROOM Manual 5/3/2023 9:50:05 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D014 UNIT 59E LIVING ROOM Manual 5/3/2023 9:50:34 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D013 UNIT 59E BEDROOM Manual 5/3/2023 9:51:25 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D011 UNIT 59F LIVING ROOM Manual 5/3/2023 9:52:08 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N000 L1D012 UNIT 59F BEDROOM Manual 5/3/2023 9:52:26 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N000 L1M003 LAUNDRY ROOM Manual 5/3/2023 9:53:29 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Restorable Spot

N000 L1D002 LAUNDRY HEAT Manual 5/3/2023 9:53:30 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Supervisory N000 L1M017 LOW PRESSURE Manual 5/3/2023 9:55:00 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Mechanical, Electrosonic, or Pressure Waterflow Device

N000 L1M016 SPRINKLER WATERFLOW Manual 5/3/2023 9:55:02 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Valve Tamper Switch N000 L1M015 SHUTOFF VALVE TAMPER Manual 5/3/2023 9:55:20 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Battery 1 FACP Battery 1 Manual 5/3/2023 9:28:58 AM

Comment: 5 Ah

Manufacturer Premium Power

Model UB1280-ER

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 8

Battery Location FACP

Charger Voltage 27.49

Load Voltage 12.78

Nominal Voltage 12

Battery - Sealed Lead-acid Battery 2 FACP Battery 2 Manual 5/3/2023 9:31:20 AM

Comment: 5.4 Ah

Manufacturer Premium Power

Model UB1280-ER

Visual Inspection Passed (Manual)

Functional Inspection Passed

Amp Hours 8

Battery Location FACP

Charger Voltage 27.49

Load Voltage 12.16

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Panel

N000 N000 PANEL FireLite NFW-50X 04/30/2021

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

N000 L1D001 PANEL SMOKE 04/30/2021

N000 L1D004 UNIT 59B LIVING ROOM 04/30/2021

N000 L1D005 UNIT 59A LIVING ROOM 04/30/2021

N000 L1D006 UNIT 59A BEDROOM 04/30/2021

N000 L1D007 UNIT 59B BEDROOM 04/30/2021

N000 L1D009 UNIT 59C LIVING ROOM 04/30/2021

N000 L1D010 UNIT 59D LIVING ROOM 04/30/2021

N000 L1D011 UNIT 59F LIVING ROOM 04/30/2021

N000 L1D012 UNIT 59F BEDROOM 04/30/2021

N000 L1D013 UNIT 59E BEDROOM 04/30/2021

N000 L1D014 UNIT 59E LIVING ROOM 04/30/2021

Heat Detector - Restorable Spot

N000 L1D002 LAUNDRY HEAT 04/30/2021

Manual Fire Box

N000 L1M003 LAUNDRY ROOM 04/30/2021

N000 L1M008 MECHANICAL ROOM 04/30/2021

Valve Tamper Switch

N000 L1M015 SHUTOFF VALVE TAMPER 04/30/2021

Mechanical, Electrosonic, or Pressure Waterflow Device

N000 L1M016 SPRINKLER WATERFLOW 04/30/2021

Supervisory

N000 L1M017 LOW PRESSURE 04/30/2021

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid

Battery 1 FACP Battery 1 Premium Power UB1280-ER

Battery 2 FACP Battery 2 Premium Power UB1280-ER

Glacier National Park

For

Building #217 Library/Facilities Management Office

128 W Glacier

West Glacier, Montana 59936

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Monday, May 01, 2023

Test Session :01 May 2023 08:51

ACCEPTED BY TESTED BY

Jon Murphy

Glacier National Park

128 W Glacier West Glacier, Montana 59936 United States

Luke Salewsky

Systems Northwest

PO Box 5390, Kalispell, MT,US 59903

PROPERTY Building #217 Library/Facilities Management Office

CONTACT

ADDRESS 128 W Glacier PHONE

CITY/STATE/ZIP West Glacier, Montana 59936 MOBILE

COUNTRY United States EMAIL

Inspector Information

COMPANY Systems Northwest CONTACT Luke Salewsky

ADDRESS

PO Box 5390, Kalispell, MT,US 59903

LICENSE NUMBER FPL-IEL-LIC-001176

PHONE +1 406-309-4518

COUNTR…