B09_Attachment_15_Valve_Schedule_Damper_Schedule_0003.pdf

PDF 504 KB Posted

Attached to
EROS Removal and replacement of chilled and conden
Solicitation number
140G0126Q0288
Issued by

About this file

This document consists of HVAC equipment schedules and specifications for the Eros Data Center in Sioux Falls, South Dakota, prepared by Honeywell, Inc. The file contains detailed valve and damper schedules with technical specifications for air handling units (AHUs) and related HVAC components.

The valve schedule specifies control valves, heating coils, cooling coils, and heat recovery units across eleven AHUs, with detailed data including valve models (primarily V5013F1061 and V5013B1003), flow rates in GPM ranging from 40 to 144, line sizes from 2" to 3", pressure drops, and operator specifications (MP953C1075 model actuators operating at 8-12 PSI with direct acting control). Connection types include screwed, flanged, flared, and soldered configurations. The damper schedule covers mixing box dampers, exhaust air dampers, and cooling tower dampers across multiple units and systems, specifying damper types (D640, D641, D642, D643, D643LS), mounting configurations (vertical and horizontal blade options), duct dimensions, and MP918B1006 operator units operating at 3-13 PSI. The document was prepared as-built documentation dated May 9, 2016, with systems engineered by Honeywell and installed by Gil Haugan Construction under the supervision of Rick Krause. All schedules include clearance requirements, connection details, and reference drawings with specific installation notes indicating that sequencing is controlled through software rather than manual positioners.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNIT KEY QTY. SERVING

HRC-2 1 AHU 2 HEAT RECOVERY

HC-2 1 AHU 2 HEATING COIL

CC-2 1 AHU 2 COOLING COIL

HRC-5 1 AHU 5 HEAT RECOVERY

HC-5 1 AHU 5 HEATING COIL

CC-5 1 AHU 5 COOLING COIL

HRC-8 1 AHU 8 HEAT RECOVERY

HC-8 1 AHU 8 HEATING COIL

CC-8 1 AHU 8 COOLING COIL

HRC-9 1 AHU 9 HEAT RECOVERY

HC-9 1 AHU 9 HEATING COIL

CC-9 1 AHU 9 COOLING COIL

HRC-1C 1 AHU 10 HEAT RECOVER'

HC-10 1 AHU 10 HEATING COIL

CC-10 1 AHU 10 COOLING COIL

HRC-11 1 AHU 11 HEAT RECOVER'

HC-11 1 AHU 11 HEATING COIL

ARCHITECT: SPrTZNAGEL

ENGINEER: SPrTZNAGEL

GPM

CONTRACTOR: GIL HAUGAN CONSTRUCTION

SYSTEMS ENGINEER: =�OUl,GUA

INSTALLATION SUPERVISOR: RICK KRAUSE

MBH LINE

# SIZE

INLET SIZE

2 1/'Z' z'

2 1/'Z' z'

:!' 2 1/'Z'

:!' z'

:!' 2 1/'Z'

:!' 2 1/'Z'

2 1/'Z' 2 1/'Z'

2 1/'Z' z'

:!' 2 1/'Z'

2 1/'Z' z'

2 1/'Z' z'

2 1/'Z' z'

:!' z'

:!' z'

:!' 2 1/'Z' z' z'

2 1/'Z' z'

VALVE SCHEDULE

VALVE DATA OPERATOR DATA

CV PD

PATTERN CONNECTION

POSITION VALVE OPERATOR SIZE RANGE ACTION

2-WAY l-WAY SC FLG FLR SD ANG o.s. # o.s. #

40 2.9 X X V5013F1061 MP953C1075 6" 8-12# DA

40 4.1 X X V5013F1061 MP953C1075 6" 8-12# DA

63 3.4 X X V501381003 MP953C1075 6" 8-12# DA

40 4.4 X X V5013F1061 MP953C1075 6" 8-12# DA

63 2.5 X X V501381003 MP953C1075 6" 8-12# DA

63 4.4 X X V501381003 MP953C1075 6" 8-12# DA

63 1.2 X X V501381003 MP953C1075 6" 8-12# DA

40 4.4 X X V5013F1061 MP953C1075 6" 8-12# DA

63 3.9 --x X V501381003 MP953C1075 6" 8-12# DA

40 1.2 X X V5013F1061 MP953C1075 6" 8-12# DA

40 1.8 X X V5013F1061 MP953C1075 6" 8-12# DA

40 3.9 IX X V5013F1061 MP953C1075 6" 8-12# DA

40 4.8 X X V5013F1061 MP953C1075 6" 8-12# DA

40 8.1 X X V5013F1061 MP953C1075 6" 8-12# DA

63 5.2 _;x.,, X V501381003 MP953C1075 6" 8-12# DA

40 1.2 X X V5013F1061 MP953C1075 6" 8-12# DA

40 1.8 X X V5013F1061 MP953C1075 6" 8-12# DA

X X MP953C1075

X X MP953C1075

X ;

X

MP953C1075

I

MP953C1075

X MP953C1075

X X I

I

X

X X X X

IX

IX X

1:!' s· DA

X X

SEE SEE

DETAIL ORDER DWG REMARKS -�

NO AS

A

A

A

A

A

A

A

A NO POSmONERS PROVIDED

A BECAUSE SEQUENCING

DONE THROUGH SOFTWARE

A

A

A

A

A

A

A

A

C

B 3/4" NPT

DETAIL "A" DETAIL "D"

SUPPLY- -RETURN SUPPLY -� _ RETURN

DETAIL "B"

-RETURN

-SUPPLY

DETAIL "C"

CLEARANCE

VALVE DISTANCE*

VP525

VP526 11/2"

VP527

VP531

VP512A

33/8" VP5138

VP517A

VP513A

4" VP522AB

' 3-45 DEG SAE Fl.ARE

FITTINGS NO T BY

HONEYWELL

DETAIL "E"

3-'45 DEG SJ,E flARE

FITTINGS NOT OY

HONE'IWEI.I.

� -RETURN

1------- -SUPPLY

DETAIL "F''

VALVE

V5011, V5013

MP953C-F

(5" OPERATOR)

V5011, V5013

MP953C-F

(8" OPERATOR)

V5011, V5013

MP953C-F

(13" OPERATOR)

J-45 DEG SAE Fl.ARE

/ FITTINGS NO T OY

HONEYWELL

DISTANCE*

43/8"

53/8"

71 1/16"

* DISTANCE - FROM TOP OF OPERATOR

TO NEAREST OBSTRUCTION

LEGEND

SC -SCREWED

FLG -FLANGED

FLR -FLARED

SD -SOLDERED

ANG-ANGLED

AS BUIL TS

Honeywell, Inc.

5/09/'16 1607 "C" AVE SIOUX FALLS, SD 57104

Cl NOW ONLY I VALVE S/25/ ECW'l--------------------t - EROS DATA CENTER

A CHANGE FCI TD PNEU S/24/95 ECV SIOUX FALLS, SOUTH DAKOTA

DATE ,U,PD

j;;

r=-w••

A\\N B� JP

I

DA TE

I D l'O, BY:

SHEET 500F N���;: 958-24 Q 09-5 Q

R�.

HRC-1 1 AHU 1 HEAT RECOVERY 1 1/2"

HC-1 1 AHU 1 HEATING COIL 2"

CC-1 1 AHU 1 COOLING COIL 1 1/2"

AHU 3 HEAT RECOVERY 2"HRC-3

HC-3

CC-3

HRC-4

HC-4

CC-4

HRC-6

HC-6

CC-6

AHU 3 HEATING COIL

AHU 3 COOLING COIL

AHU 4 HEAT RECOVERY

AHU 4 HEATING COIL

AHU 4 COOLING COIL

AHU 6 HEAT RECOVERY

AHU 6 HEATING COIL

AHU 8 COOLING COIL

2"

2 1/2"

2"

2"

3"

1 1/4"

1 1/2"

1 1/2"

MP953C1075

MP953C1075

MP953C1075

673730-001

HONEYWELL

MP953C1075

MP953C1075

MP9531075

AHU 3 STEM IACCUATOR 1/2"ST INJ 3

ST INJ 4 1/2"

ST INJ 5 1/2"

AHU 4 STEAM ACCUATOR

AHU 5 STREAM ACCUATOR

hEAT EXCHANGER CONDENSATEHEAT eXCH 6" MP953E-1400-1

HONEYWELL

DAMPER SCHEDULE

DAMPER OPERATOR DATA

UNIT /SERVING FUNCTION DUCT SIZE DIMENSIONS MOUNTING REMARKS TYPE ClTY. EDGING FIG. AREA NORMAL FACTORY D.S. NUMBER QTY, PAC SPRING WIDTH HEIGHT A B (FT2) POSITION n�TI<"R # INTERN"' EXTERNAi RANGE

AHU-2 MIXING BOX -- -- -- -- -- -- MP918B1006 1 >< 3-13#

AHU-5 MIXING BOX -- - -- -- -- -- MP918B1006 1 >< 3-13#

AHU-8 MIXING BOX -- - -- -- -- -- MP918B1006 1 >< 3-13#

r B m

A w

AHU-9 MIXING BOX -- - --

-- -- -- MP918B1006 1 >< 3-13#

AHU-10 MIXING BOX -- -- -- -- -- -- MP918B1006 1 >< 3-13#

AHU-10 EXHAUST AIR 96" 36" D643A 1 96" 36" YES 4 24.0 N.C. MP918B1006 1 >< 3-13#

NO P OSITI ONER PROVIDED FIG. I-PARALLEL FIG. 2-PARALLEL

TYPES D640 8. D642 TYPES D640 8. D642

AHU-11 MIXING BOX MP918B1006 1 >< 3-13#

BECAUSE SEQUENCIING (VERTICAL BLADES) (HORIZONTAL BLADES)

-- -- -- -- -- -- D ONE THROUGH S OFTWARE

AHU-11 EXHAUST AIR 24" 66" D643A 1 24" 66" YES 4 11.0 N.C. MP918B1006 1 >< 3-13# MINIMUM SIZE EITHER DIMENSION - 8 IN.

CT-1 INLET 84" 78" ALUM. 1 84" 78" YES 4 45.5 N.C. MP918B1006 2 >< 3-13#

CT-1 OUTLET 84" 66" ALUM. 1 84" 66" YES 4 38.5 N.C. MP918B1006 2 >< 3-13#

�B--j Tfl.·ml

CT-2 INLET 84" 78" ALUM. 1 84" 78" YES 4 45.5 N.C. MP918B1006 2 >< 3-13#

CT-2 OUTLET 84" 66" ALUM. 1 84" 66" YES 4 38.5 N.C. MP918B1006 2 >< 3-13#

l-

CT-3 INLET 84" 78" ALUM. 1 84" 78" YES 4 45.5 N.C. MP918B1006 2 >< 3-13#

84" 66" 84" 66" 3-13#

FIG, 3-□PPOSED FIG. 4-□PP□SED

CT-3 OUTLET ALUM. 1 YES 4 38.5 N.C. MP918B1006 2 >< TYPES D641 & D643 TYPES D641 8. D643

(VERTICAL BLADES) <HORIZONTAL BLADES)

MGS-BLDG. 36" 2 2" D643LS 1 36" 2 2" -- 4 5.5 N.C. MP918B1006 1 ">< MINIMUM SIZE EITHER DIMENSION - 8 IN, 3-13# 2 POSITI ON

MECH. R O OM EF-2 72" 12" D643LS 1 72" 12"

-- 4 6.0 N.C. MP918B1006 1 >< 3-13# 2 POSITI ON PLEASE FURNISH CORRECT DUCT SIZES FOR AUTOMATIC DAMPERS FOR THE ABOVE JOB AND RETURN ONE COPY TO THE

ATTENTION OF THE \,/RITER AS SOON AS POSSIBLE. INDICATE EXACT DUCT DR OPENING SIZE. DAMPERS \,/ILL BE BUILT SMALLER TO ALLOW FOR CLEARANCE. INDICATE HORIZONTAL OR VERTICAL BLADE MOUNTING FOR MULTISECTI□N DAMPERS

BY FIGURE NUMBER.

DAMPERS ARE BUILT IN EVEN 2 IN. INCREMENTS. IF A DUCT HAS ODD DIMENSIONS, WE WILL FURNISH NEXT SMALLER EVEN SIZE. FILLER SECTIONS MUST BE FIELD FABRICATED. \,/HEN CORRECT DUCT SIZES HAVE BEEN RECEIVED, 1,/E \,/ILL ORDER THE DAMPERS FROM OUR FACTORY AND \,/ILL PROVIDE YOU WITH A DAMPER INFORMATION FORM GIVING THE EXACT SIZES OF DAMPERS WE \,/ILL SUPPLY AND AN INSTALLATION PLANNING GUIDE TO ASSIST YOUR INSTALLER.

REPLY•

THE DAMPERS WILL BE REQUIRED ON DA

SHIPPING AD.DRESS,

SIZES APPROVED BY•

REH/IRKS,

Honeywell, Inc.

C P.O. BOX 916, VALLEY FORGE, PA 19482

ARCHITECT: B AS BUILT 5/8/96

ENGINEER: A PER FIELD REVIEW EROS DATA CENTER

SIOUX FALLS, SOUTH DAKOTA

CONTRACTOR: REVISIONS DATE APPD.

SYSTEMS ENGINEER: SUPERSEDES !DRAWN BY: JP I DATE I DRAWING 958-24009-51 1BINSTALLATION SUPERVISOR: SUPERSEDED BY I APPROVED BY: I SHEET OF I NUMBER

AHU-1 MIXING BOX MP918B1006

AHU-3 MIXING BOX MP918B1006

AHU-4 MIXING BOX MP918B1006

AHU-6 MIXING BOX MP918B1006

CT-4 INLET 84" 78" ALUM 1 86" 60" YES N.C.

CT-4 OUTLET 84" 66" ALUM 1 86" 60" YES N.C.

File details come from the government source that posted it. Updated .