B08_Attachment_8_Q_A_Amd_001_0001.docx

DOCX document 23 KB Posted

Attached to
CERC A3 Single Phase Electrical Panel Upgrade
Solicitation number
140G0125Q0052
Issued by

About this file

This is a Questions & Answers document (Amendment 001) for solicitation 140G0125Q0052 that provides clarification on the dimensions and specifications of the switchboard equipment for the CERC A3 Single Phase Electrical Panel Upgrade project. The document specifies that the new switchgear area will be 17' wide x 8' tall and details the current configuration, which includes one 1200-amp main disconnect, ten 200-amp switches, two 100-amp switches, one 200-amp disconnect, one 600-amp disconnect, and one 400-amp disconnect.

The related contract opportunity is a small business set-aside solicitation from the US Geological Survey for electrical upgrades at the Columbia Environmental Research Center in Columbia, MO. The work involves replacing an existing building main single-phase 1200-amp disconnect with a new 600-volt 1200-amp distribution panel. The project is valued between $100,000 and $250,000, with RFQ release expected on 2/6/2025 and quotes due 2/28/2025. A site visit is strongly encouraged, and vendors must be registered in SAM.gov to be considered for award.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140G0125Q0052 Questions & Answers Amendment 001

1. Can you confirm the dimensions of the switchboard and how many/ what size the switches are?

a. The area that will be free for the new switchgear is 17' wide x 8' tall.

b. Currently, there is -

i. 1 -1200 amp main disconnect

ii. 10 - 200 amp switches

iii. 2 - 100 amp switches

iv. 1 - 200 amp disconnect

v. 1 - 600 amp disconnect

vi. 1 -400 amp disconnect