13611 OSPM Fire Alarm System Upgrade Plans.pdf

PDF 4 MB Posted

Attached to
OSPM Fire Alarm System Upgrade
Solicitation number
S-29100-00013611
Issued by
Marion County, Oregon

About this file

This file comprises architectural and engineering design plans for the Oregon State Penitentiary Minimum Fire Alarm Upgrade project prepared by Landis Consulting and dated April 7, 2025. The project is managed by the Oregon Department of Corrections, Facilities Services, with Pete Belisle serving as the Construction Project Manager. The scope involves the complete replacement of the existing fire alarm system with a new addressable fire alarm system and two-way communication dial-out capability across five buildings at the penitentiary: the Transportation Building, Main Housing Building, Classroom Building, Recreation Building, and Physical Plant Building. The new Fire Alarm Control Panel will be located in the Transportation Building and will monitor all five buildings with occupant notification coverage, sprinkler monitoring of the Main Housing Building, installation of a new two-way communication call station that dials to off-site central station monitoring, and a smoke evacuation system in the Main Housing Building. The design complies with the 2022 Oregon Structural Specialty Code, 2021 Oregon Electrical Specialty Code, 2022 Oregon Fire Code, and 2022 NFPA 72 Code. The project documentation includes comprehensive demolition and proposed site plans, fire alarm riser diagrams, sprinkler coverage plans, electrical details, and panel schedules across 18 detailed drawing sheets totaling approximately 20,205 square feet for the Main Housing Building, 8,224 square feet for the Transportation Building, 3,368 square feet for the Classroom Building, 2,425 square feet for the Recreation Building, and 1,348 square feet for the Physical Plant Building.

The design calls for significant system infrastructure including multiple Signaling Line Circuits (SLC), Notification Appliance Circuits (NAC), and P-Link wiring throughout the facility, with new conduit installation estimated at approximately 3/4 inches diameter connecting buildings via underground trenching coordinated with the owner. The project requires removal of existing fire alarm devices and monitoring modules from multiple locations, replacement of smoke detectors with wireguards throughout the Main Housing Building, and installation of new junction boxes, relay modules, surge arresters, and line isolation modules. The existing 120-volt branch circuits will be reused and extended to new equipment where applicable, with some new 20-ampere circuits required for additional NAC power supplies. Notably, the design includes provisions for addressing existing smoke evacuation fans in the Main Housing Building that do not function, requiring contractor testing and diagnostics of branch circuit continuity, motor insulation, and control circuits to identify and correct the source of failure. The contract documents specify that contractors may modify proposed conduit routes for constructability while maintaining the design intent to minimize concrete wall penetrations, and contractors must as-built the actual conduit routes installed.

View the file

Other files

File Type Posted
13611 ADDENDA 1.pdf PDF
OSPM Fire Alarm Addendum 1 Plans.pdf PDF
13611 OSPM Fire Alarm System Upgrade SOW.pdf PDF
13611 Plan holder list.pdf PDF
7005 Contract_Executed.pdf PDF
724022-Bid Register with Rank~1.pdf PDF
13611 Bid Tab.pdf PDF
13611 ITB_GTC_SGC_SPECS~1.pdf PDF
7005 NOITA.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E0.0

COVER SHEET

SHEET INDEX

E0.0 - COVER SHEET

E0.1 - ABBREVIATIONS & SYMBOL LEGEND

E0.2 - FIRE ALARM RISER DIAGRAM

E0.3 - SPRINKLER COVERAGE PLAN

E0.4 - ELECTRICAL DETAILS

E1.1 - DEMOLITION SITE PLAN

E1.2 - TRANSPORTATION BUILDING DEMOLITION PLAN

E1.3 - MAIN HOUSING BUILDING DEMOLITION PLAN - NORTH & SOUTH

E1.4 - MAIN HOUSING BUILDING DEMOLITION PLAN - EAST & WEST

E1.5 - CLASSROOM BUILDING DEMOLITION PLAN

E1.6 - RECREATION BUILDING DEMOLITION PLAN

E2.1 - PROPOSED SITE PLAN

E2.2 - TRANSPORTATION BUILDING FIRE ALARM PLAN

E2.3 - MAIN HOUSING BUILDING FIRE ALARM PLAN - NORTH & SOUTH

E2.4 - MAIN HOUSING BUILDING FIRE ALARM PLAN - EAST & WEST

E2.4.1 - MAIN HOUSING BUILDING TUNNEL FIRE ALARM PLAN

E2.5 - CLASSROOM BUILDING FIRE ALARM PLAN

E2.6 - RECREATION BUILDING FIRE ALARM PLAN

E2.7 - PHYSICAL PLANT FIRE ALARM PLAN

E2.8 - PANEL SCHEDULES

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE

ELECTRICAL

LANDIS CONSUILTING

6446 FAIRWAY AVE SE UNIT 220,

SALEM, OREGON 97306

(503) 584-1576

PRINCIPAL/EOR: BEN PERRY

Ben_Perry@Landisconsulting.com

PROJECT MANAGER: DEVON LUTE

Devon_Lute@Landisconsulting.com

DESIGNER: JORDAN LUTE

Jordan_Lute@Landisconsulting.com

AREA OF PROJECT

VICINITY MAP1

OWNER

PETE BELISLE

CONSTRUCTION PROJECT MANAGER 2

DEPARTMENT OF CORRECTIONS,

FACILITIES SERVICES

3601 STATE STREET

SALEM, OREGON 97301

PROJECT CONTACTS PROJECT DESCRIPTION

REPLACEMENT OF EXISTING FIRE ALARM SYSTEM WITH NEW

ADDRESSABLE FIRE ALARM SYSTEM AND TWO-WAY

COMMUNICATION DIAL OUT. FIRE ALARM CONTROL PANEL SHALL BE

LOCATED IN THE TRANSPORTATION BUILDING AND WILL MONITOR

ALL FIVE BUILDINGS.

SYSTEM DESCRIPTION

- GENERAL OCCUPANT NOTIFICATION COVERAGE.

- SPRINKLER MONITORING OF MAIN HOUSING BUILDING.

- INSTALLATION OF NEW TWO-WAY COMMUNICATION

CALL STATION. CALL STATION DIALS OFF SITE TO A CENTRAL

STATION MONITORING.

- SMOKE EVACUATION SYSTEM IN MAIN HOUSING BUILDING.

DESIGN SHALL COMPLY WITH THE FOLLOWING CODES:

2022 OREGON STRUCTURAL SPECIALTY CODE

2021 OREGON ELECTRICAL SPECIALTY CODE

2022 OREGON FIRE CODE

2022 NFPA 72

CODE INFORMATION

TRANSPORTATION BUILDING:

MAIN HOUSING BUILDING:

CLASSROOM BUILDING:

RECREATION BUILDING:

PHYSICAL PLANT BUILDING:

OCCUPANCY GROUP

TRANSPORTATION BUILDING:

MAIN HOUSING BUILDING:

CLASSROOM BUILDING:

RECREATION BUILDING:

PHYSICAL PLANT BUILDING:

SPRINKLER COVERAGE

TRANSPORTATION BUILDING:

MAIN HOUSING BUILDING:

CLASSROOM BUILDING:

RECREATION BUILDING:

PHYSICAL PLANT BUILDING:

AREA MAP2

STATE ST

H

AW

TH

O

R N

E

AV

E N

E

IN

TE

R

ST

AT

E

I-5

G

EE

R D

R

AI

R

PO

R

T R

D S

E

TH

S T

SE

STATE ST

PA

RK

A

VE

N E

AREA OF PROJECT

8,224 SQ. FT.

20,205 SQ.FT.

3,368 SQ.FT.

2,425 SQ.FT.

1,348 SQ.FT.

TYPE B

TYPE I-3

TYPE B

TYPE I-3

TYPE I-3

PARTIAL COVERAGE

PARTIAL COVERAGE

FULL COVERAGE

FULL COVERAGE

NONE

FINISHED CEILING

FINISHED FLOOR

M

AX

M

IN

M

IN

6" (M

IN

MANUAL PULL STATION

HORN/STROBE

1. LOCATE ALL FIRE ALARM DEVICES PER NFPA 72

REQUIREMENTS.

NOTES:

M

AX

M

AX

FIRE ALARM CONTROL PANEL

DUAL PATH COMMUNICATOR

" M

AX

FIRE ALARM ANNUNCIATOR

NAC BOOSTER POWER SUPPLY

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E0.1

ABBREVIATIONS &

SYMBOL LEGEND

Electrical Abbreviations & Symbol Legend Abbreviations

A AMPERE

AC ALTERNATING CURRENT, AIR CONDITIONING UNIT

AHJ AUTHORITY HAVING JURISDICTION

AIC AVAILABLE INTERRUPTING CAPACITY

AF AMPERE FRAME / AMPERE FUSED

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ARMS ARC FLASH REDUCTION MAINTENANCE SYSTEM

AT AMPERE TRIP

AV AUDIO / VIDEO

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BFG BELOW FINISHED GRADE

BLDG BUILDING

C CONDUIT

CAT CATEGORY

CB CIRCUIT BREAKER

CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

CFOI CONTRACTOR FURNISHED, OWNER INSTALLED

CKT CIRCUIT

CPT CONTROL POWER TRANSFORMER

CR CONTROL RELAY

CU COPPER

dB DECIBAL

DC DIRECT CURRENT

DIM DIMENSION

DIV DIVISION

DTL DETAIL

DWG DRAWING

EL ELEVATION

EMT ELECTRICAL METALLIC TUBING

EOLR END OF LINE RESISTOR

FACP FIRE ALARM CONTROL PANEL

FF FINISH FLOOR

FLA FULL LOAD AMPERES

FT FOOT, FEET

FBO FURNISHED BY OTHERS

G, GND GROUND

GFCI GROUND FAULT CIRCUIT INTERRUPTER

HH HAND HOLE

HP HORSEPOWER

ID IDENTIFICATION

IDC INITIATING DEVICE CIRCUIT

IDF INTERMEDIATE DISTRIBUTION FRAME

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS

IG ISOLATED GROUND

IT INFORMATION TECHNOLOGY

JB JUNCTION BOX

KAIC THOUSAND AMPS INTERRUPTING CURRENT

KCMIL THOUSAND CIRCULAR MILS

KVA KILOVOLT-AMPERE

KW KILOWATT

LAN LOCAL AREA NETWORK

LED LIGHT EMITTING DIODE

LS LIMIT SWITCH

LSI ELECTRONIC TRIP UNIT ADJUSTABLE LONG TIME DELAY,

SHORT TIME DELAY, INSTANTANEOUS TRIP

LSIG ELECTRONIC TRIP UNIT WITH ADJUSTABLE LONG TIME DELAY,

SHORT TIME DELAY, INSTANTANEOUS TRIP, AND GROUND

FAULT

LV LOW VOLTAGE

MCA MINIMUM CIRCUIT AMPACITY

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MDF MAIN DISTRIBUTION FRAME

MHz MEGAHERTZ

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

N NEUTRAL

NAC NOTIFICATION APPLIANCE CIRCUIT

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

Ø PHASE

PB PULL BOX, PANIC BUTTON, PUSH BUTTON

PE PHOTO EYE

PNL PANEL

POE POWER OVER ETHERNET

PTZ PAN, TILT, ZOOM

RF RADIO FREQUENCY

RFI REQUEST FOR INFORMATION

SPD SURGE PROTECTION DEVICE

STD STANDARD

SW SWITCH

T/M THERMAL MAGNETIC CIRCUIT BREAKER

TBD TO BE DETERMINED

TV TELEVISION / MONITOR OUTLET

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

UH UNIT HEATER

UG UNDERGROUND

UL UNDERWRITERS LABORATORIES

UPS UNINTERRUPTIBLE POWER SUPPLY

UON UNLESS OTHERWISE NOTED

USB UNIVERSAL SERIAL BUS

V VOLTS, VOLTAGE

VA VOLT-AMPERE

VFD VARIABLE FREQUENCY DRIVE

W WATT, WIRE

WAN WIDE AREA NETWORK

WAP WIRELESS ACCESS POINT

WI-FI WIRELESS FIDELITY

W/ WITH

W/O WITHOUT

XFMR TRANSFORMER

Y WYE

1P ONE POLE

2P TWO POLE

3P THREE POLE

4P FOUR POLE

Drawing Symbol Variables

3 THREE WAY SWITCH.

4 FOUR WAY SWITCH.

#J QUANTITY OF JACKS AND HORIZONTAL CABLES.

J = CAT6, JA = CAT6A, JE = CAT5E

+XX MOUNTING UNITS EXPRESSED IN INCHES TO CENTERLINE ABOVE

FINISHED FLOOR OR GRADE.

C MOUNTED HORIZONTALLY AT 4" ABOVE COUNTERTOP.

CL CLOCK.

DR DUAL RELAY.

E RED EMERGENCY SWITCH.

EL ELEVATOR RECALL.

ETR EXISTING DEVICE SHALL REMAIN.

G GLASS BREAK SENSOR.

K KEYED SWITCH.

LF LOW FREQUENCY.

LV LOW VOLTAGE SWITCH.

M MOTOR RATED TOGGLE SWITCH.

NEX REPLACE EXISTING WIRING DEVICE AND FACEPLATE WITH NEW. BACK BOX

AND CONDUIT SHALL REMAIN.

O INTEGRAL OCCUPANCY SENSOR.

P ADA PHONE, VERIFY HEIGHT WITH ARCHITECT / OWNER.

REX REMOVE EXISTING DEVICE / EQUIPMENT.

TK MOUNTED IN TOE KICK OF CASEWORK.

TV MOUNTED ADJACENT TO TV AT 60" AFF, UON.

V VANDAL RESISTANT.

WG WIREGUARD.

WP WEATHERPROOF.

Raceways

CONDUIT AND/OR CONDUCTORS INSTALLED ABOVE GRADE,

CONCEALED IN WALL OR CEILING SPACE.

CONDUIT TURNED DOWN.

CONDUIT AND/OR CONDUCTORS INSTALLED BELOW GRADE, BELOW

SLAB.

CONDUIT TURNED UP.

CONDUIT STUBBED AND CAPPED.

CONDUIT DIRECT CONNECTION TO EQUIPMENT.

FLEXIBLE CONNECTION TO EQUIPMENT.

CONDUIT / WIRING CONTINUATION.

HOMERUN TO PANELBOARD.

CABLE TRAY. SIZE AND TYPE AS INDICATED ON DRAWINGS.

Miscellaneous

JUNCTION BOX (ROUND, SQUARE).

THERMOSTAT.

RELAY.

CORD REEL.

MOTOR / EXHAUST FAN.

CEILING FAN.

UTILITY POLE.

WEATHERHEAD.

GROUND ROD.

GROUND ROD WITH TEST WELL.

SURFACE RACEWAY / WIREMOLD.

JJ

T

R

FIRE RATED BACKBOARD.

GROUND BUS BAR.

Annotation

CONDUIT & CONDUCTOR CALLOUT. REFER TO CONDUIT &

CONDUCTOR SCHEDULE.

KEYED NOTE CALLOUT. REFER TO CORRESPONDING SHEET

KEYNOTES.XX

(E) INDICATES EXISTING EQUIPMENT TO REMAIN.

(D) INDICATES EXISTING EQUIPMENT TO BE DEMOLISHED.

(N) INDICATES NEW EQUIPMENT.

KEYED NOTE CALLOUT. REFER TO CORRESPONDING SHEET

KEYNOTES.

KEYED NOTE CALLOUT. REFER TO CORRESPONDING SHEET

KEYNOTES.

MECHANICAL EQUIPMENT CALLOUT. REFER TO MECHANICAL

EQUIPMENT CONNECTION SCHEDULE.

X

EX.XX

DETAIL CALLOUT. REFER TO DETAIL AND SHEET AS INDICATED ON

CALLOUT.

FIXTURE MOUNTING CALLOUT. HEIGHT ABOVE FINISHED FLOOR

(A.F.F.)

XXXXX EQUIPMENT CALLOUT. REFER TO NEMA CONNECTION SCHEDULE.

X

EX.XX

SECTION CALLOUT. REFER TO DETAIL AND SHEET AS INDICATED ON

CALLOUT.

ELEVATION CALLOUT. REFER TO DETAIL AND SHEET AS INDICATED

ON CALLOUT.

EX.XX

(RR)/(RD) INDICATES EXISTING EQUIPMENT OR DEVICE TO BE REMOVED AND

REINSTALLED.

XX'-XX"

PXXX

XX

XX-XX

XX

Power Distribution

DUPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.

QUADPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.

GFCI QUADPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.

SIDE HATCHED RECEPTACLE, TO BE WIRED TO SWITCHED CIRCUIT.

NEMA SPECIAL RECEPTACLE, MOUNTED AT 18" AFF, UON. NEMA

CONFIGURATION AS INDICATED.

RECEPTACLE MOUNTED ON CEILING.

CENTER HATCHED RECEPTACLE TO BE WIRED TO EMERGENCY

CIRCUIT.

TAMPER RESISTANT DUPLEX RECEPTACLE, MOUNTED AT 18" AFF,

UON.

GFCI DUPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.

PANELBOARD SURFACE MOUNT.

PANELBOARD FLUSH MOUNT.

MAIN DISTRIBUTION PANEL.

DISCONNECT SWITCH.

FUSED DISCONNECT SWITCH.

ENCLOSED CIRCUIT BREAKER.

COMBINATION STARTER.

FLOORBOX COMBINATION POWER & DATA.

FLOORBOX POWER.

POKETHRU COMBINATION POWER & DATA.

POKETHRU POWER.

POWER POLE.

SIMPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.

UTILITY CT METER.

TAMPER RESISTANT QUADPLEX RECEPTACLE, MOUNTED AT 18" AFF,

UON.

RECEPTACLE MOUNTED IN-COUNTER.

UTILITY TRANSFORMER.

F

TS

FS

PS

MM

RI

RO

FIRE ALARM AUDIO/VISUAL - WALL MOUNTED. CANDELA RATING AS

SHOWN ON DRAWING.

FIRE ALARM VISUAL - WALL MOUNTED. CANDELA RATING AS SHOWN

ON DRAWING.

FIRE ALARM AUDIO/VISUAL - CEILING MOUNTED. CANDELA RATING

AS SHOWN ON DRAWING.

FIRE ALARM VISUAL - CEILING MOUNTED. CANDELA RATING AS

SHOWN ON DRAWING.

FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED.

FIRE ALARM SMOKE DETECTOR - WALL MOUNTED.

FIRE ALARM HEAT DETECTOR - CEILING MOUNTED.

FIRE ALARM HEAT DETECTOR - WALL MOUNTED.

FIRE ALARM DUCT SMOKE DETECTOR.

FIRE ALARM DUCT SMOKE DETECTOR WITH REMOTE TEST STATION.

FIRE ALARM MANUAL PULL STATION - WALL MOUNTED.

FIRE ALARM MANUAL TAMPER SWITCH.

FIRE ALARM MANUAL FLOW SWITCH.

FIRE ALARM MANUAL PRESSURE SWITCH.

FIRE ALARM MONITOR MODULE.

FIRE ALARM RELAY INPUT.

FIRE ALARM RELAY OUTPUT.

Fire Alarm

PIV

SA

FIRE ALARM POST INDICATOR VALVE.

FIRE ALARM SURGE ARRESTOR.

FAA FIRE ALARM ANNUNCIATOR.

FIRE ALARM MAGNETIC DOOR HOLD.

FIRE ALARM BELL.FB

IM FIRE ALARM ISOLATION MODULE.

TS

FIRE ALARM BEAM SMOKE DETECTOR.

S

S

H

H

S

S

S

SCALE:

DEVICE MOUNTING HEIGHTS1 1/2" = 1'-0"

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E0.2

FIRE ALARM RISER

DIAGRAM

(N) FIRE ALARM

CONTROL PANEL(N) FIRE ALARM

ANNUNCIATOR

SLC LOOP WIRING

P-LINK WIRING

WIRING LEGEND

NAC WIRING(N) DUAL PATH

COMMUNICATOR

TRANSPORTATION BUILDING

N0-1-1 N0-1-2 N0-1-3 N0-1-4 N0-1-5 N0-1-6 N0-1-7 N0-1-8 N0-1-9 N0-1-10 N0-1-11

EOLR

EOLR

EOLR

N0-2-1 N0-2-2 N0-2-3 N0-2-4 N0-2-5 N0-2-6 N0-2-7 N0-2-8 N0-2-9

N0-3-1 N0-3-2 N0-3-3 N0-3-4 N0-3-5 N0-3-6 N0-3-7

(N) NAC BOOSTER

POWER SUPPLY N1

SA SA

(N) FIRE ALARM

ANNUNCIATOR

(N) FIRE ALARM

ANNUNCIATOR

SA SA

MAIN HOUSING

CLASSROOM BUILDING

SA SA

RECREATION BUILDING

PHYSICAL PLANT BUILDING

N1-3-1

N1-4-1

N1-5-3

N2-1-1

N2-3-1

F S IM F MM MM MM S S S S

S0.01 S0.02 S0.03 S0.04 S0.05 S0.06 S0.07 S0.08 S0.09 S0.10 S0.11

N3-1-1

N3-2-1

N2-1-2

N3-1-2 N3-1-3 N3-1-4 N3-1-5 N3-1-6 N3-1-7 N3-1-8 N3-1-9

N3-2-2 N3-2-3 N3-2-4 N3-2-5 N3-2-6 N3-2-7 N3-2-8

N4-1-1

N4-2-1

N4-3-1 N4-3-2 N4-3-3 N4-3-4

N4-1-2 N4-1-3 N4-1-4 N4-1-5

N4-2-2 N4-2-3 N4-2-4 N4-2-5 N4-2-6

EOLR

EOLR

EOLR

EOLR

EOLR

N1-2-1

N1-1-1 N1-1-2 N1-1-3 N1-1-4 N1-1-5 N1-1-6 N1-1-7 N1-1-8 N1-1-9 N1-1-10 N1-1-11 N1-1-12 N1-1-13 N1-1-14

N1-2-2 N1-2-3 N1-2-4 N1-2-5 N1-2-6 N1-2-7 N1-2-8 N1-2-9

N1-3-2 N1-3-3 N1-3-4 N1-3-5 N1-3-6 N1-3-7 N1-3-8 N1-3-9

N1-4-2 N1-4-3 N1-4-4 N1-4-5 N1-4-6 N1-4-7

N1-5-4

N2-1-3 N2-1-4

N2-3-2 N2-3-3

N2-2-3 N2-2-4 N2-2-5

F S F F S S S

S4.01 S4.02 S4.03 S4.04 S4.05 S4.06 S4.07 S4.08 S4.09 S4.10 S4.11 S S S S S

S4.12 S

S4.13 S

S4.14

MM

S4.15

MM

S4.16

IM

S4.17

IM HF H H

S4.18 S4.19 S4.20 S4.21 S4.22 S4.23 S4.24 S4.25 S4.26 S4.27 H H H H H

IMS MM FSS

S3.01 S3.02 S3.03 S3.04 S3.05 S3.06 S3.07 S3.08 S3.09 S F

F S S

S1.01 S1.02 S1.03 S1.04 S1.05 S1.06 S1.07 S1.08 S1.09

S SS S S S

S1.10 S1.11 S

S1.12 F

S1.13 S S

S1.14 S1.15 S S

S1.16

MM

S1.17

MM

S1.18 H

S1.19 F

S1.20 H

S1.21 S

S1.22 H

S1.23 S

S1.24 S1.25 S S

S1.28 S

S1.27 S1.26 S S

S1.30 S

S1.29 S

S1.33 S

S1.32 S1.31 S S

S1.35 S

S1.34 S

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

S S

S2.01 S2.02 S2.03 S2.04 S2.05 S2.06 S2.07 S2.08

S SS SSS S

S2.09 S2.10 S2.11 S2.12 S2.13

S S SS S

S2.14 S2.15 S2.16 S2.17 S2.18

S S SS S

S2.19 S2.20 S2.21 S2.22 S2.23

S S SS S

S2.24 S2.25 S2.26 S S

S

S2.28 S2.27 S

S2.29

RO

S2.30

SS

S2.31S2.32 F

S2.33 S

S2.36 S

S2.35 S2.34 S S

S2.41 S S

S2.40 S2.39 S2.38 S2.37 S S S

S2.46 S S

S2.45 S2.44 S2.43 S2.42 S S S

S2.51 S S

S2.50 S2.49 S2.48 S2.47 S S S

S2.52 S

S

S2.53 S2.54 S2.55 S S

S2.56 S

S2.61

SS

S2.57 S2.58 S2.59 S2.60 S S S

S2.62

RO

S2.63 S

S2.64 F

S2.65 S

S2.68

SS

S2.66 S2.67 S S

S2.69 S2.70 S2.71 S2.72 S2.73

S S SS

S2.74 S S

S2.75 S2.76 S2.77

SS

S2.78 S

S2.83 S S

S2.82 S2.81 S2.80 S2.79

S S SS

S2.88 S2.87 S2.86 S2.85 S2.84

S S SS

S2.89

SS

S2.93 S2.92 S2.91 S2.90 S S S

S2.94

SS

S2.98 S2.97 S2.96 S2.95 S S S

S2.99

SS

S2.102 S2.101 S2.100 S S

S2.103

RO

S2.104 S

S2.105 S

S2.107 S

S2.106 F

N0-1 N0-2 N0-3

SLC

N1-1 N1-2 N1-3

SLC

EXP.

N1-4 N1-5 N1-6

(N) NAC BOOSTER

POWER SUPPLY N2

N2-1 N2-2 N2-3

SLC

EXP.

N2-4 N2-5 N2-6

(N) NAC BOOSTER

POWER SUPPLY N3

N3-1 N3-2 N3-3

SLC

EXP.

N3-4 N3-5 N3-6

(N) NAC BOOSTER

POWER SUPPLY N4

N4-1 N4-2 N4-3

SLC

EXP.

N4-4 N4-5 N4-6

120V

120V

120V

120V

120V

120V

N1-5-1 N1-5-2

N0-4 N0-4-1 N0-4-2

N1-6-1 N1-6-2 N1-6-3 N1-6-4

(FRONT ENTRY ACCESS

CONTROL OVERRIDE)

N0-5 N0-6

SA

SA

SA

SA

F S0.12

RO

S0.13

EOLR

EOLR

S3.10

SMM

(E) PANEL IN

OFFICE 107 FS FB

(E) FLOW SWITCH

ON RISER

(E) PANEL A

CKT. #5 FS FB

(E) FLOW SWITCH

ON RISER

(E) PANEL E

CKT. #10 FS FB

(E) FLOW SWITCH

ON RISER

Main Housing Building

E1.3,E1.4

Classroom Building E1.5

Recreation Building E1.6

Physical Plant Building

Transportation Building E1.2

Carport (No Scope)

FB

FB

FB

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E0.3

SPRINKLER

COVERAGE PLAN

20'10'5'0'

SCALE:

SPRINKLER COVERAGE PLAN1 1" = 20'

EXISTING FIRE RISER

EXISTING FIRE RISER

EXISTING FIRE RISER

- SPRINKLER COVERAGE

SPRINKLER COVERAGE LEGEND

GENERAL SHEET NOTES

1. THE FIRE SPRINKLER SYSTEM IN THE MAIN HOUSING

UNIT IS FED FROM THE TRANSPORTATION BUILDING

FIRE SPRINKLER RISER.

FIRE SPRINKLER WATER FLOW BELL

FIRE SPRINKLER WATER FLOW BELL

FIRE SPRINKLER WATER FLOW BELL

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E0.4

ELECTRICAL DETAILS

8" MIN.

MOUNTING DETAIL SHALL BE UTILIZED FOR

ALL NON-CAST IRON ENCLOSURES OR

BOXES WITH EXTERNAL MOUNTING FEET.

PROVIDE SIMILAR MOUNTING FOR

ENCLOSURES WITH INTERNAL MOUNTING

HOLES.

ENCLOSURE WALL

MOUNTING DETAIL

201DETAIL NO.NTSSCALE:

NON-CONCRETE

ENCASED DUCTBANK

DETAIL

402DETAIL NO.NTSSCALE:

FINISHED GRADE

UNDISTRIBUTED EARTH

INSTALL CONDUITS

PER SCHEDULE, TYP.

NOTES:

1.TYPICAL EXCEPT AS SPECIFIED.

2. MAINTAIN A MINIMUM OF 12" SEPARATION BETWEEN POWER CONDUITS AND

CONTROL, TELECOMMUNICATION AND INSTRUMENTATION.

3. BACKFILL SHALL BE AS SPECIFIED IN SECTION 02226/312300.

3" M

IN

S

EP

AR

AT

IO

N , T

YP

3" MIN SEPARATION, TYP.

" M

IN

6" COVER OF SCREENED GRANULAR

BACKFILL SHALL SURROUND CONDUITS.

BACKFILL SHALL CONTAIN ONLY SOIL AND

ROCKS THAT WILL PASS THROUGH A

3/4" SIEVE. AND NO MORE THAN 15% OF

THE MATERIAL PASSES THROUGH A

NO. 200 MESH SIEVE.

3" M

IN

. B

ED

D

IN

G

SU

B

BA

SE

O F

SU

R

FA

C

E

NATIVE BACKFILL, FREE OF ROCKS AND

DEBRIS LARGER THAN 4" DIAMETER

TRENCH WARNING TAPE

(16130.T01/260533.T01)

COMPACTED EARTH

PROVIDE 6" MINIMUM OF 3/4" MINUS

GRAVEL BASE PER SECTION 02226/312300.

WALL MOUNTED CEILING OR WALL MOUNTED

TRAPEZE MOUNTED

CONDUIT STRAP

GALVANIZED ANCHORS

GALVANIZED STRUT CHANNEL

GALVANIZED ANCHORS

M

AX

3" (TYP.)

1" (T

YP

36" MAX.

BETWEEN HANGERS

GALVANIZED STRUT CHANNEL

6" M

IN

5" M

IN

9" M

IN

1" MIN.

1" (TYP.)

GALVANIZED HARDWARE

GALVANIZED STRUT CHANNEL

SEISMIC BRACING

PRODUCTS

INSTALL THREADED RODS

USED FOR CONDUIT HANGERS

WITH JAMB NUTS AND FLAT

PLATE FITTINGS (TYP).

CEILING

CONDUIT

MOUNTING

202DETAIL NO.NTSSCALE:

GRC ELBOW WITH PVC

WRAP CONDUIT

TRANSITION

403DETAIL NO.NTSSCALE:

2" M

AX

PVC-40 GRC CONDUIT WRAPPED IN PVC TAPE

FINISHED GRADE

CONDUIT TYPE, AS SPECIFIED.

FEMALE ADAPTER (FEMALE

THREADS FOR GRC, SOCKET

END FOR PVC.)

CONCRETE

GRC COUPLING

E1.3,E1.4

Classroom Building E1.5

Recreation Building E1.6

Physical Plant Building (No Demolition)

Transportation Building E1.2

Carport (No Scope)

J

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E1.1

DEMOLITION SITE

PLAN

SHEET KEY NOTES

30'15'0'

SCALE:

DEMOLITION SITE PLAN1 1" = 30'

1. REMOVE ALL FIRE ALARM WIRING BETWEEN FACP IN

TRANSPORTATION BUILDING AND THE MAIN

HOUSING BUILDING THROUGH EXISTING CONDUT(S).

THE CONDUIT ORIGINATES ON THE

TRANSPORTATION BUILDING AND CONNECTS TO

THE MAIN HOUSING BUILDING TUNNEL.

LOBBY

ENTRANCE

BREAKROOM

102A

RESTROOM

102B

DATA

STORAGE

ROOM

SHAKEDOWN

JANITOR

OFFICE

MULTIPURPOSE

107A

RESTROOM

OFFICE

OFFICE

STORAGE

LOUNGE

LIBRARY

BARBER

111A

STORAGE

RESTROOM

ELEC.

CLASSROOM

CARDIO

ROOM

OFFICE

118A

STORAGE

STORAGE

REC ROOM

100A

CORRIDOR A

100B

CORRIDOR B

100C

CORRIDOR C

LOBBY

ENTRANCE

BREAKROOM

102A

RESTROOM

102B

DATA

STORAGE

ROOM

SHAKEDOWN

JANITOR

OFFICE

MULTIPURPOSE

107A

RESTROOM

OFFICE

OFFICE

STORAGE

LOUNGE

LIBRARY

BARBER

111A

STORAGE

RESTROOM

ELEC.

CLASSROOM

CARDIO

ROOM

OFFICE

118A

STORAGE

STORAGE

REC ROOM

100A

CORRIDOR A

100B

CORRIDOR B

100C

CORRIDOR C

FFAA

S

S

MM

MM MM

FB

FB

S

S

RO

(E) PANEL A1

(D) FIRE ALARM CONTROL PANEL

(E) FIRE ALARM JUNCTION BOX

(E) PANEL M

(E) PANEL E

(E) PANEL A

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E1.2

TRANSPORTATION

BUILDING

DEMOLITION PLAN

GENERAL SHEET NOTES

SHEET KEY NOTES

SCALE:

TRANSPORTATION BUILDING

DEMOLITION PLAN1 1/8" = 1'-0"

1. ALL FIRE ALARM DEVICES SHOWN AS DASHED

SHALL BE REMOVED COMPLETELY. REMOVE WIRING

COMPLETELY BACK TO SOURCE.

2. ANY DEVICE BEING REMOVED AND NOT REPLACED

WITH A NEW DEVICE IN THE SAME LOCATION/BOX

SHALL BE PROVIDED WITH A BLANK COVERPLATE.

1. EXISTING FIRE ALARM CONTROL PANEL SHALL BE

REPLACED WITH NEW IN SAME LOCATION.

CONTRACTOR SHALL MAINTAIN EXISTING 120V

BRANCH CIRCUIT AND EXTEND TO NEW FIRE ALARM

CONTROL PANEL.

2. REMOVE MONITORING MODULE FOR FIRE

SPRINKLER RISER MONITORING.

3. PROVIDE BLANK COVERPLATE. PAINT TO MATCH

EXISTING WALL.

4. REMOVE EXISTING DOOR HOLD OPEN POWER

SUPPLY TRANSFORMER. WIRE EXISTING DOOR

HOLD OPENS TO NEW NAC CIRCUIT ON NEW FIRE

ALARM CONTROL PANEL.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

E

C

W1 S.R.

W2 S.R.

W3 S.R.

W24 S.R.

W23 S.R.

W22 S.R.

E32 S.R.

E1 S.R.

N24

DINING

VISITATION

N1 A & O

N2 A & O

N3 A & O

N4 A & O

N20

TELEPHONE

ROOM

N21

STORAGE

N10

STORAGE

N9

COUNSEL

N8

OFFICE

N27

NURSE'S

STATION

N26

ITS

L13

L22

DRYING

N7

STORAGE

N34

OFFICE

N35

N22

STORAGE

N33

EXAM

N28

EXAM

N6

BOILER

N29

N30

N31

N5

K5

OFFICE K4

K2

DRY

STORAGE

L2

STORAGE

L24

LAUNDRY

K1

KITCHEN

K3

FREEZER

K6

WALK-IN

COOLER

L14

N36

CONTROL

L20

L1

LOBBY

100C

CORRIDOR C

N6

BOILER

100N

CORRIDOR N

100B

CORRIDOR B

100A

CORRIDOR A

100K

CORRIDOR K

K7

DISHWASHING

100D

CORRIDOR D 003

STORAGE

STORAGE

STORAGE

STORAGE

K8

N24

DINING

VISITATION

N1 A & O

N2 A & O

N3 A & O

N4 A & O

N20

TELEPHONE

ROOM

N21

STORAGE

N10

STORAGE

N9

COUNSEL

N8

OFFICE

N27

NURSE'S

STATION

N26

ITS

L13

L22

DRYING

N7

STORAGE

N34

OFFICE

N35

N22

STORAGE

N33

EXAM

N28

EXAM

N6

BOILER

N29

N30

N31

N5

K5

OFFICE K4

K2

DRY

STORAGE

L2

STORAGE

L24

LAUNDRY

K1

KITCHEN

K3

FREEZER

K6

WALK-IN

COOLER

L14

N36

CONTROL

L20

L1

LOBBY

100C

CORRIDOR C

N6

BOILER

100N

CORRIDOR N

100B

CORRIDOR B

100A

CORRIDOR A

100K

CORRIDOR K

K7

DISHWASHING

100D

CORRIDOR D 003

STORAGE

STORAGE

STORAG

STORAGE

K8

S

S

S

S

S

S

S

S

S

S

S

S S

FB

FB

FB

FB

MMMM

FB

S S

S

F

S

FAA

D C

S2 S.R.

S3 S.R.

S4 S.R.

S5 S.R.

S6 S.R.

S7 S.R.

S8 S.R.

S9 S.R.

S10 S.R.

S11 S.R.

S12 S.R.

S23 S.R.

S22 S.R.

S21 S.R.

S20 S.R.

S19 S.R.

S18 S.R.

S17 S.R.

S16 S.R.

S15 S.R.

S14 S.R.

S13 S.R.

S24 S.R.

W1 S.R.

L22

DRYING

L2

STORAGE

L3

STORAGE

L7

JANITOR

L24

LAUNDRY

N36

L1

LOBBY

L19

CONFERENCE

100S

CORRIDOR S

100D

CORRIDOR D

100F

CORRIDOR F

STORAGE

STORAGE

STORAGE

STORAGE

STORAGE

L8

S1

RESTROOM

S2 S.R.

S3 S.R.

S4 S.R.

S5 S.R.

S6 S.R.

S7 S.R.

S8 S.R.

S9 S.R.

S10 S.R.

S11 S.R.

S12 S.R.

S23 S.R.

S22 S.R.

S21 S.R.

S20 S.R.

S19 S.R.

S18 S.R.

S17 S.R.

S16 S.R.

S15 S.R.

S14 S.R.

S13 S.R.

S24 S.R.

L22

DRYING

L2

STORAGE

L3

STORAGE

L7

JANITOR

L24

LAUNDRY

N36

L1

LOBBY

L19

CONFERENCE

100S

CORRIDOR S

100D

CORRIDOR D

100F

CORRIDOR F

STORAGE

STORAGE

STORAGE

STORAGE

STORAGE

L8

S1

RESTROOM

S

S

FB

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

FB

S

S

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E1.3

MAIN HOUSING

BUILDING

DEMOLITION PLAN -

NORTH & SOUTH

SCALE:

MAIN HOUSING BUILDING

DEMOLITION PLAN - NORTH1 1/8" = 1'-0"

MATCHLINEMATCHLINE

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

SCALE:

MAIN HOUSING BUILDING

DEMOLITION PLAN - SOUTH2 1/8" = 1'-0"

MATCHLINEMATCHLINE

M

AT

C H

LI

N

E

M

AT

C H

LI

N

E

1. SMOKE EVACUATION DAMPER CONTROL.

2. MONITORING MODULE SERVE KITCHEN HOODS IN

KITCHEN K1.

(D) FIRE ALARM JUNCTION BOX

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

M

AT

C H

LI

N

E

M

AT

C H

LI

N

E

GENERAL SHEET NOTES

SHEET KEY NOTES

1. ALL FIRE ALARM DEVICES SHOWN AS DASHED

SHALL BE REMOVED COMPLETELY. REMOVE WIRING

COMPLETELY BACK TO SOURCE.

2. ANY DEVICE BEING REMOVED AND NOT REPLACED

WITH A NEW DEVICE IN THE SAME LOCATION/BOX

SHALL BE PROVIDED WITH A BLANK COVERPLATE.

3. ALL SMOKE DETECTORS ON THIS SHEET HAVE

WIREGUARDS. CONTRACTOR SHALL REMOVE AND

REPLACE ALL WIREGUARDS.

(E) POWER PANEL

F E

W1 S.R.

W2 S.R.

W3 S.R.

W4 S.R.

W5 S.R.

W6 S.R.

W7 S.R.

W8 S.R.

W9 S.R.

W10 S.R.

W11 S.R.

W12 S.R.

W24 S.R.

W23 S.R.

W22 S.R.

W21 S.R.

W20 S.R.

W19 S.R.

W18 S.R.

W17 S.R.

W16 S.R.

W15 S.R.

W14 S.R.

W13 S.R.

N35

LOBBY

100W

CORRIDOR W

STORAGE

STORAGE

W25 S.R.

W1 S.R.

W2 S.R.

W3 S.R.

W4 S.R.

W5 S.R.

W6 S.R.

W7 S.R.

W8 S.R.

W9 S.R.

W10 S.R.

W11 S.R.

W12 S.R.

W24 S.R.

W23 S.R.

W22 S.R.

W21 S.R.

W20 S.R.

W19 S.R.

W18 S.R.

W17 S.R.

W16 S.R.

W15 S.R.

W14 S.R.

W13 S.R.

100W

CORRIDOR W

STORAGE

STORAGE

W25 S.R.

S S S S S S S S S S

S S S S S S S S S S

S S

S S

S S S S S S

FB

S

B A

E32 S.R.

E31 S.R.

E30 S.R.

E29 S.R.

E28 S.R.

E27 S.R.

E26 S.R.

E25 S.R.

E24 S.R.

E23 S.R.

E22 S.R.

E21 S.R.

E20 S.R.

E19 S.R.

E18 S.R.

E17 S.R.

E1 S.R.

E2 S.R.

E3 S.R.

E4 S.R.

E5 S.R.

E6 S.R.

E7 S.R.

E8 S.R.

E9 S.R.

E10 S.R.

E11 S.R.

E12 S.R.

E13 S.R.

E14 S.R.

E15 S.R.

E16 S.R.

100E

CORRIDOR E

STORAGE

STORAGE

STORAGE

K8

E32 S.R.

E31 S.R.

E30 S.R.

E29 S.R.

E28 S.R.

E27 S.R.

E26 S.R.

E25 S.R.

E24 S.R.

E23 S.R.

E22 S.R.

E21 S.R.

E20 S.R.

E19 S.R.

E18 S.R.

E17 S.R.

E1 S.R.

E2 S.R.

E3 S.R.

E4 S.R.

E5 S.R.

E6 S.R.

E7 S.R.

E8 S.R.

E9 S.R.

E10 S.R.

E11 S.R.

E12 S.R.

E13 S.R.

E14 S.R.

E15 S.R.

E16 S.R.

100E

CORRIDOR E

S S S S S S S S S S S S S S S S

S S S S S S S S S S S S S S S S

S S S S S S S S

FB FB

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E1.4

MAIN HOUSING

BUILDING

DEMOLITION PLAN -

EAST & WEST

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

SCALE:

MAIN HOUSING BUILDING

DEMOLITION PLAN - WEST1 1/8" = 1'-0"

SCALE:

MAIN HOUSING BUILDING

DEMOLITION PLAN - EAST2 1/8" = 1'-0"

MATCHLINE

MATCHLINE

MATCHLINE

MATCHLINE

1. SMOKE EVACUATION DAMPER CONTROL.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

GENERAL SHEET NOTES

SHEET KEY NOTES

1. ALL FIRE ALARM DEVICES SHOWN AS DASHED

SHALL BE REMOVED COMPLETELY. REMOVE WIRING

COMPLETELY BACK TO SOURCE.

2. ANY DEVICE BEING REMOVED AND NOT REPLACED

WITH A NEW DEVICE IN THE SAME LOCATION/BOX

SHALL BE PROVIDED WITH A BLANK COVERPLATE.

3. ALL SMOKE DETECTORS ON THIS SHEET HAVE

WIREGUARDS. CONTRACTOR SHALL REMOVE AND

REPLACE ALL WIREGUARDS.

ENTRANCE102

KITCHENETTE

102A

UTILITY

RESTROOM

RESTROOM

CLASSROOM

CLASSROOM

OFFICE

COPIER

OFFICE

OFFICE

OFFICE

100A

CORRIDOR A

100B

CORRIDOR B

ENTRANCE102

KITCHENETTE

102A

UTILITY

RESTROOM

RESTROOM

CLASSROOM

CLASSROOM

OFFICE

COPIER

OFFICE

OFFICE

OFFICE

100A

CORRIDOR A

100B

CORRIDOR B

F

S S

S

S

F

MM

RO

S

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E1.5

CLASSROOM

BUILDING

DEMOLITION PLAN

SCALE:

CLASSROOM BUILDING

DEMOLITION PLAN1 3/16" = 1'-0"

(E) POWER PANELS

1. REMOVE NAC POWER SUPPLY. MAINTAIN EXISTING

120V BRANCH CIRCUIT.

2. REMOVE MONITORING MODULE FOR FIRE

SPRINKLER MONITORING.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

GENERAL SHEET NOTES

SHEET KEY NOTES

1. ALL FIRE ALARM DEVICES SHOWN AS DASHED

SHALL BE REMOVED COMPLETELY. REMOVE WIRING

COMPLETELY BACK TO SOURCE.

2. ANY DEVICE BEING REMOVED AND NOT REPLACED

WITH A NEW DEVICE IN THE SAME LOCATION/BOX

SHALL BE PROVIDED WITH A BLANK COVERPLATE.

UTILITY

BREAK ROOM

REC ROOM

REC ROOM

PROGRAMS

BARBER 104

OFFICE

ELEC.

SHOWERS

RESTROOM

C100

CORRIDOR

UTILITY

BREAK ROOM

REC ROOM

REC ROOM

PROGRAMS

BARBER 104

OFFICE

ELEC.

SHOWERS

RESTROOM

C100

CORRIDOR

MM

S

FB

MM

SS

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E1.6

RECREATION

BUILDING

DEMOLITION PLAN

SCALE:

RECREATION BUILDING

DEMOLITION PLAN1 3/16" = 1'-0"

1. REMOVE MONITORING MODULE FOR FIRE

SPRINKLER RISER MONITORING.

(E) POWER PANELS

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

GENERAL SHEET NOTES

SHEET KEY NOTES

1. ALL FIRE ALARM DEVICES SHOWN AS DASHED

SHALL BE REMOVED COMPLETELY. REMOVE WIRING

COMPLETELY BACK TO SOURCE.

2. ANY DEVICE BEING REMOVED AND NOT REPLACED

WITH A NEW DEVICE IN THE SAME LOCATION/BOX

SHALL BE PROVIDED WITH A BLANK COVERPLATE.

E2.3,E2.4

Classroom Building E2.5

Recreation Building E2.6

Physical Plant Building E2.7

Transportation Building E2.2

Carport (No Scope)

J

J

J

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.1

PROPOSED SITE PLAN

SHEET KEY NOTES

30'15'0'

SCALE:

PROPOSED SITE PLAN1 1" = 30'

1. EXISTING SMOKE EVACUATION FANS DO NOT TURN

ON. CONTRACTOR SHALL PROVIDE TESTING TO

IDENTIFY SOURCE OF PROBLEM AND CORRECT.

PERFORM THE FOLLOWING TESTS: BRANCH CIRCUIT

CONDUCTOR CONTINUITY AND INSULATION

TESTING; MOTOR INSULATION TESTING; TESTING

ALL CONTROL CIRCUITS WITHIN THE FAN MOTOR

STARTER. IDENTIFY THE SOURCE OF THE PROBLEM

AND PROPOSED SOLUTION TO THE ENGINEER AND

OWNER.

2. NEW 3/4" CONDUIT FOR SLC AND P-LINK WIRING.

CONDUIT SHALL ORIGINATE IN MAIN HOUSING

TELEPHONE ROOM AND TERMINATE IN CLASSROOM

BUILDING IN UTILITY ROOM 102A.

3. NEW 3/4" CONDUIT FOR SLC AND P-LINK WIRING.

CONDUIT SHALL ORIGINATE IN MAIN HOUSING

TELEPHONE ROOM AND TERMINATE IN RECREATION

BUILDING IN ELECTRICAL ROOM 107.

4. NEW 3/4" CONDUIT FOR SLC AND P-LINK WIRING.

CONDUIT SHALL ORIGINATE IN THE RECREATION

BUILDING AND TERMINATE IN THE PHYSICAL PLANT.

COORDINATE EXACT LOCATION OF TRENCHING

WITH OWNER PRIOR TO INSTALLATION. ALL

TRENCHING SHALL BE PROVIDED BY THE

CONTRACTOR.

5. EXISTING FIRE ALARM CONDUIT BETWEEN

TRANSPORTATION BUILDING AND MAIN HOUSING

UNIT TUNNEL. UTILIZE EXISTING CONDUIT FOR NEW

FIRE ALARM P-LINK WIRING BETWEEN THE NEW

FACP IN THE TRANSPORTATION BUILDING AND THE

NEW FIRE ALARM EQUIPMENT IN THE MAIN HOUSING

TELEPHONE ROOM.

6. NEW P-LINK WIRING ABOVE ACCESSIBLE CEILINGS.

7. NEW P-LINK WIRING INSTALLED IN TUNNEL TO NEW

FIRE ALARM EQUIPMENT IN TELEPHONE ROOM IN

MAIN HOUSING UNIT.

ELECTRICAL ROOM 115(N) FIRE ALARM CONTROL PANEL

(E) FIRE ALARM JUNCTION BOX

TELEPHONE ROOM N20 WITH

NEW FIRE ALARM EQUIPMENT

UTILITY ROOM 102A

ELECTRICAL ROOM 107

1 TUNNEL

LOBBY

ENTRANCE

BREAKROOM

102A

RESTROOM

102B

DATA

STORAGE

ROOM

SHAKEDOWN

JANITOR

OFFICE

MULTIPURPOSE

107A

RESTROOM

OFFICE

OFFICE

STORAGE

LOUNGE

LIBRARY

BARBER

111A

STORAGE

RESTROOM

ELEC.

CLASSROOM

CARDIO

ROOM

OFFICE

118A

STORAGE

STORAGE

REC ROOM

100A

CORRIDOR A

100B

CORRIDOR B

100C

CORRIDOR C

LOBBY

ENTRANCE

BREAKROOM

102A

RESTROOM

102B

DATA

STORAGE

ROOM

SHAKEDOWN

JANITOR

OFFICE

MULTIPURPOSE

107A

RESTROOM

OFFICE

OFFICE

STORAGE

LOUNGE

LIBRARY

BARBER

111A

STORAGE

RESTROOM

ELEC.

CLASSROOM

CARDIO

ROOM

OFFICE

118A

STORAGE

STORAGE

REC ROOM

100A

CORRIDOR A

100B

CORRIDOR B

100C

CORRIDOR C

FAA

FF

SA SA

IM

MM

MM

F

S

S

S

S

S

N0-1

N0-1-1

N0-1-2

N0-1-3

N0-1-4

N0-1-5

N0-1-6

N0-1-7

N0-1-8

N0-1-9

N0-1-10

N0-1-11

EOLR

N0-2 N0-3

N0-2-1

N0-2-2

N0-2-3

N0-2-4

N0-2-5

N0-2-6

N0-2-7

N0-2-8

N0-2-9

EOLR

N0-3-1

N0-3-2

N0-3-3

N0-3-4

N0-3-5

N0-3-6

N0-3-7

EOLR

FB

S0.01

S0.02 S0.03

S0.04

S0.05 S0.06

S0.12 S0.08

S0.09

S0.10

S0.11

J

RO

N0-4-1

N0-4-2

EOLR

S0.13

MM S0.07

(E) PANEL A1

(E) PANEL E

(N) FIRE ALARM CONTROL PANEL31

(E) PANEL A

(E) PANEL M

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.2

TRANSPORTATION

BUILDING FIRE

ALARM PLAN

GENERAL SHEET NOTES

SHEET KEY NOTES

SCALE:

ELECTRICAL PROPOSED

TRANSPORTATION BUILDING PLAN1 1/8" = 1'-0"

1. NEW FIRE ALARM CONTROL PANEL. REUSE EXISTING

120V BRANCH CIRCUIT PANEL E, CIRCUIT #8.

2. MOUNT NEW FIRE ALARM ANNUNCIATOR RECESSED

IN NEW WOOD SLAT WALL.

3. NEW DUAL PATH COMMUNICATOR (STACKED ABOVE

FACP). WIRE TO PANEL E, CIRCUIT #8.

4. NEW MONITORING MODULE FOR FIRE SPRINKLER

MONITORING OF TWO TAMPER SWITCHES AND ONE

FLOW SWITCH.

5. SURGE ARRESTERS FOR INCOMING FIRE ALARM

CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC

CIRCUIT.

6. PROVIDE 1/2" CONDUIT TO NEW DEVICE.

7. PROVIDE NEW RELAY FOR EXISTING FRONT ENTRY

GATE OVERRIDE.

8. PROVIDE 120V CIRCUIT FOR NEW FIRE BELL ON

PANEL B.

9. PROVIDE COVER GUARD ON PULL STATION.

10. PROVIDE WIREGUARD.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

1. THE MAJORITY OF NEW NOTIFICATION DEVICES ON

THIS SHEET SHALL BE INSTALLED IN THE SAME

LOCATION AS THE DEVICES WHICH WERE REMOVED

AS SHOWN ON THE DEMOLITION DRAWINGS.

2. NEW NOTIFICATION DEVICES SHOWN ON THIS

SHEET WHICH ARE NOT INSTALLED IN THE SAME

LOCATION AS REMOVED DEVICES SHALL BE

PROVIDED WITH A NEW BOX AND CONDUIT.

3. NAC WIRING SHALL BE PERMITTED TO BE INSTALLED

FREE AIR ABOVE THE ACCESSIBLE CEILINGS IN THIS

BUILDING.

(E) FIRE ALARM JUNCTION BOX

(E) PANEL B

E

C

W1 S.R.

W2 S.R.

W3 S.R.

W24 S.R.

W23 S.R.

W22 S.R.

E32 S.R.

E1 S.R.

N24

DINING

VISITATION

N1 A & O

N2 A & O

N3 A & O

N4 A & O

N20

TELEPHONE

ROOM

N21

STORAGE

N10

STORAGE

N9

COUNSEL

N8

OFFICE

N27

NURSE'S

STATION

N26

ITS

L13

L22

DRYING

N7

STORAGE

N34

OFFICE

N35

N22

STORAGE

N33

EXAM

N28

EXAM

N6

BOILER

N29

N30

N31

N5

K5

OFFICE K4

K2

DRY

STORAGE

L2

STORAGE

L24

LAUNDRY

K1

KITCHEN

K3

FREEZER

K6

WALK-IN

COOLER

L14

N36

CONTROL

L20

L1

LOBBY

100C

CORRIDOR C

N6

BOILER

100N

CORRIDOR N

100B

CORRIDOR B

100A

CORRIDOR A

100K

CORRIDOR K

K7

DISHWASHING

100D

CORRIDOR D 003

STORAGE

STORAGE

STORAGE

STORAGE

K8

S

S

S

S

S

S

S

S

H

H

S

S S

S

S

MMMM

S

S

15 15

F

F

15 15

SASA

S

S

S

S

S

S

FAA

F

H

S

N1-1

N1-1-1

N1-1-2

N1-1-3

N1-1-4

N1-1-5

N1-1-6

N1-1-7

N1-1-8 N1-1-9

N1-1-10

N1-1-11

N1-1-12 EOLR

N1-1-14 N1-2

N1-2-1

N1-2-2

N1-2-3

N1-2-4

N1-2-5N1-2-6

N1-2-7

N1-2-8

N1-2-9

EOLR

N1-3

N1-3-1

N1-3-2

N1-3-3

N1-3-4

N1-3-6 N1-3-7 N1-3-8

EOLR

N1-3-9

N1-4

N1-4-1

N1-4-2

N1-4-3

N1-4-4 N1-4-5

N1-4-6

N1-4-7

EOLR

N1-5-4

N1-1-13

S1.01 S1.02

S1.03

S1.04

S1.05

S1.06

S1.07

S1.08

S1.09

S1.10

S1.11

S1.12

S1.13

S1.14

S1.15

S1.16 S1.17 S1.18

S1.19

S1.20

S1.21

S1.22 S1.23 S1.24

S1.25

S1.26S1.27

S1.28

S1.29

S1.30

N1-6-1N1-6-2

N1-6-4

EOLR

D C

S2 S.R.

S3 S.R.

S4 S.R.

S5 S.R.

S6 S.R.

S7 S.R.

S8 S.R.

S9 S.R.

S10 S.R.

S11 S.R.

S12 S.R.

S23 S.R.

S22 S.R.

S21 S.R.

S20 S.R.

S19 S.R.

S18 S.R.

S17 S.R.

S16 S.R.

S15 S.R.

S14 S.R.

S13 S.R.

S24 S.R.

W1 L22

DRYING

L3

STORAGE

L7

JANITOR

L24

LAUNDRY

L19

CONFERENCE

100S

CORRIDOR S

100F

CORRIDOR F

STORAGE

STORAGE

L8

S1

RESTROOM

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

F

RO

N2-2

N1-5-2

N1-5-1

N2-2-1

N2-2-2

EOLR

N2-2-3

S

S

N1-3-5

N1-5

N1-5-4

EOLR

N1-5-3

S1.29

S1.31 S1.32

S1.33

S1.34

S1.35

S2.35 S2.34

S2.37 S2.38

S2.39 S2.40

S2.42 S2.43

S2.44 S2.45

S2.47 S2.48

S2.49 S2.50

S2.52 S2.53

S2.54 S2.55

S2.57 S2.58

S2.59 S2.60

S2.61 S2.65

S2.64

S2.62 S2.63

S2.56

S2.51

S2.46

S2.41

S2.36

N1-6-3

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.3

MAIN HOUSING

BUILDING FIRE

ALARM PLAN -

NORTH & SOUTH

GENERAL SHEET NOTES

SHEET KEY NOTES

SCALE:

MAIN HOUSING BUILDING

FIRE ALARM PLAN - NORTH1 1/8" = 1'-0"

MATCHLINEMATCHLINE

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

(E) POWER PANELS

1. TWO (2) NEW NAC POWER SUPPLIES. WIRE NAC

BOOSTER POWER SUPPLIES TO PANEL A1, CIRCUIT

#13 IN CONTROL ROOM N36.

2. SURGE ARRESTERS FOR INCOMING FIRE ALARM

CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC

CIRCUIT.

3. MONITORING MODULE FOR HOOD ANSUL SYSTEMS.

4. RELAY OUTPUT MODULE SHALL CONTROL THE

SMOKE EXHAUST FAN.

5. ALL SMOKE DETECTORS SHOWN WITHIN THIS AREA

SHALL BE REPLACED IN THE SAME LOCATION.

6. PROVIDE 1/2" CONDUIT.

7. NEW INITIATING DEVICE WHICH IS NOT

REPLACEMENT.

8. SMOKE DETECTORS IN THIS HATCHED AREA SHALL

BE PART OF THE AUTOMATIC SMOKE CONTROL

SYSTEM. THE SMOKE DETECTORS SHALL START THE

SMOKE EXHAUST FAN LOCATED ON THE ROOF OF

THIS CELL BLOCK.

9. ROUTE HOMERUN DOWN TO TUNNEL BELOW AND

THEN TO NAC PANEL IN ROOM N20.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

SCALE:

MAIN HOUSING BUILDING

FIRE ALARM PLAN - SOUTH2 1/8" = 1'-0"

MATCHLINEMATCHLINE

M

AT

C H

LI

N

E

M

AT

C H

LI

N

E

1. CIRCUIT LINES SHOWN ON THIS PLAN REPRESENT

PROPOSED CONDUIT ROUTE FOR BIDDING

PURPOSES. THE DESIGN INTENT IS TO MINIMIZE

CONCRETE WALL PENETRATIONS AND CONDUIT

LENGTH. CONTRACTOR MAY MODIFY THE CONDUIT

ROUTES SHOWN ON THIS PLAN FOR

CONSTRUCTABILITY AND EFFICIENCY. CONTRACTOR

MAY COMBINE NAC CIRCUIT HOMERUNS FOR

EFFICIENCY. CONTRACTOR SHALL AS-BUILT THE

ACTUAL CONDUIT ROUTES.

2. CONTRACTOR SHALL BE PERMITTED TO COMBINE

FIRE ALARM CIRCUIT HOME RUNS IN COMMON

CONDUITS IN THE NORTH CELL BLOCK CORRIDOR.

MAXIMUM CONDUIT SIZE SHALL BE 0.75".

3. CONDUIT HOMERUNS SHALL BE INSTALLED ON

CORRIDOR CEILINGS (NORTH CELL BLOCK) OR

SHALL TURN DOWN INTO THE TUNNELS. CONDUIT

HOMERUNS SHALL NOT BE PERMITTED TO BE

INSTALLED THROUGH CELLS AS THEY CREATE A

LIGATURE HAZARD.

4. ALL NEW FIRE ALARM SMOKE DETECTORS, HEAT

DETECTORS, AND NOTIFICATION DEVICES ON THIS

SHEET SHALL BE PROVIDED WITH WIRE GUARDS.

ALL PULL STATIONS WILL BE PROVIDED WITH COVER

GUARDS.

5. WHERE SMOKE DETECTORS ARE REPLACED, THE

EXISTING CONDUIT SHALL BE RE-USED. THE WIRING

SHALL BE REPLACED WITH NEW. THE AREAS WHERE

SMOKE DETECTORS ARE RE-USED IS GENERALLY IN

THE CELLS, CELL BLOCK CORRIDOR SKYLIGHTS,

CAFETERIA, KITCHEN, AND OTHER SMALLER AREAS

SHOWN ON THE DRAWINGS.

6. ALL NEW SMOKE DETECTORS WHICH ARE NOT

REPLACEMENT OF EXISTING SMOKE DETECTORS

SHALL BE PROVIDED WITH NEW BOX AND CONDUIT.

7. ALL NEW SURFACE WALL MOUNTED NOTIFICATION

DEVICES SHALL BE PROVIDED WITH A FINISHED

BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO

COVER THE 4-SQUARE BACK BOX.

8. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION

DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM

WIRING SHALL BE EXPOSED.

SKYLIGHT (TYP)

7 7

(E) POWER PANEL

F E

W1 S.R.

W2 S.R.

W3 S.R.

W4 S.R.

W5 S.R.

W6 S.R.

W7 S.R.

W8 S.R.

W9 S.R.

W10 S.R.

W11 S.R.

W12 S.R.

W24 S.R.

W23 S.R.

W22 S.R.

W21 S.R.

W20 S.R.

W19 S.R.

W18 S.R.

W17 S.R.

W16 S.R.

W15 S.R.

W14 S.R.

W13 S.R.

N34

OFFICE

N35

LOBBY

100W

CORRIDOR W

STORAGE

STORAGE

W25 S.R.

S S S S S S S S S S

S S S S S S S S S S

S S

S S

S S S S S S 1515 1515

F

S

RO

N2-1-1N2-1-2N2-1-3

N2-1-4

EOLR

S2.01

S2.02

S2.04

S2.05

S2.06

S2.07

S2.09

S2.10

S2.11

S2.12

S2.14

S2.15

S2.16

S2.17

S2.19

S2.20

S2.21

S2.22

S2.24

S2.25

S2.27

S2.28

S2.31

S2.33

S2.03S2.08S2.13S2.18S2.23S2.26

S2.30 S2.39

S2.32

N2-1

B A

E32 S.R.

E31 S.R.

E30 S.R.

E29 S.R.

E28 S.R.

E27 S.R.

E26 S.R.

E25 S.R.

E24 S.R.

E23 S.R.

E22 S.R.

E21 S.R.

E20 S.R.

E19 S.R.

E18 S.R.

E17 S.R.

E1 S.R.

E2 S.R.

E3 S.R.

E4 S.R.

E5 S.R.

E6 S.R.

E7 S.R.

E8 S.R.

E9 S.R.

E10 S.R.

E11 S.R.

E12 S.R.

E13 S.R.

E14 S.R.

E15 S.R.

E16 S.R.

100E

CORRIDOR E

STORAGE

STORAGE

STORAGE

K8

S S S S S S S S S S S S S S S S

S S S S S S S S S S S S S S S S

S S S S S S S S15

F

RO

N2-3

N2-3-1

N2-3-2

EOLR

N2-3-3

S2.66

S2.67

S2.69

S2.70

S2.72

S2.71

S2.73

S2.75

S2.77

S2.76

S2.79

S2.80

S2.82

S2.81

S2.84

S2.85

S2.87

S2.86

S2.88

S2.90

S2.92

S2.91

S2.93

S2.95

S2.97

S2.96

S2.98

S2.100

S2.102

S2.101

S2.107

S2.105

S2.106 S2.104

S2.103S2.99S2.94S2.89S2.83S2.78S2.74S2.68

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.4

MAIN HOUSING

BUILDING FIRE

ALARM PLAN - EAST

& WEST

GENERAL SHEET NOTES

SHEET KEY NOTES

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

M

AT

C H

LI

N

E M

AT

C

H

LI

N E

SCALE:

MAIN HOUSING BUILDING

FIRE ALARM PLAN - WEST1 1/8" = 1'-0"

SCALE:

MAIN HOUSING BUILDING

FIRE ALARM PLAN - EAST2 1/8" = 1'-0"

MATCHLINE

MATCHLINE

MATCHLINE

MATCHLINE

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

1. RELAY OUTPUT MODULE SHALL CONTROL THE

SMOKE EXHAUST FAN.

2. PROVIDE 1/2" CONDUIT.

3. SMOKE DETECTORS IN THIS HATCHED AREA SHALL

BE PART OF THE AUTOMATIC SMOKE CONTROL

SYSTEM. THE SMOKE DETECTORS SHALL START THE

SMOKE EXHAUST FAN LOCATED ON THE ROOF OF

THIS CELL BLOCK.

4. ROUTE HOMERUN DOWN TO TUNNEL BELOW AND

THEN TO NAC PANEL IN ROOM N20.

1. CIRCUIT LINES SHOWN ON THIS PLAN REPRESENT

PROPOSED CONDUIT ROUTE FOR BIDDING

PURPOSES. THE DESIGN INTENT IS TO MINIMIZE

CONCRETE WALL PENETRATIONS AND CONDUIT

LENGTH. CONTRACTOR MAY MODIFY THE CONDUIT

ROUTES SHOWN ON THIS PLAN FOR

CONSTRUCTABILITY AND EFFICIENCY. CONTRACTOR

MAY COMBINE NAC CIRCUIT HOMERUNS FOR

EFFICIENCY. CONTRACTOR SHALL AS-BUILT THE

ACTUAL CONDUIT ROUTES.

2. CONTRACTOR SHALL BE PERMITTED TO COMBINE

FIRE ALARM CIRCUIT HOME RUNS IN COMMON

CONDUITS IN THE NORTH CELL BLOCK CORRIDOR.

MAXIMUM CONDUIT SIZE SHALL BE 0.75".

3. CONDUIT HOMERUNS SHALL BE INSTALLED ON

CORRIDOR CEILINGS (NORTH CELL BLOCK) OR

SHALL TURN DOWN INTO THE TUNNELS. CONDUIT

HOMERUNS SHALL NOT BE PERMITTED TO BE

INSTALLED THROUGH CELLS AS THEY CREATE A

LIGATURE HAZARD.

4. ALL NEW FIRE ALARM SMOKE DETECTORS, HEAT

DETECTORS, AND NOTIFICATION DEVICES ON THIS

SHEET SHALL BE PROVIDED WITH WIRE GUARDS.

ALL PULL STATIONS WILL BE PROVIDED WITH COVER

GUARDS.

5. WHERE SMOKE DETECTORS ARE REPLACED, THE

EXISTING CONDUIT SHALL BE RE-USED. THE WIRING

SHALL BE REPLACED WITH NEW. THE AREAS WHERE

SMOKE DETECTORS ARE RE-USED IS GENERALLY IN

THE CELLS, CELL BLOCK CORRIDOR SKYLIGHTS,

CAFETERIA, KITCHEN, AND OTHER SMALLER AREAS

SHOWN ON THE DRAWINGS.

6. ALL NEW SMOKE DETECTORS WHICH ARE NOT

REPLACEMENT OF EXISTING SMOKE DETECTORS

SHALL BE PROVIDED WITH NEW BOX AND CONDUIT.

7. ALL NEW SURFACE WALL MOUNTED NOTIFICATION

DEVICES SHALL BE PROVIDED WITH A FINISHED

BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO

COVER THE 4-SQUARE BACK BOX.

8. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION

DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM

WIRING SHALL BE EXPOSED.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.4.1

MAIN HOUSING

BUILDING TUNNEL

FIRE ALARM PLAN

GENERAL SHEET NOTES

SCALE:

MAIN HOUSING BUILDING

FIRE ALARM PLAN - TUNNEL1 1/16" = 1'-0"

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

1. ALL FIRE ALARM CIRCUITS SHOWN ON THIS SHEET

SHALL BE IN FREE AIR IN THE TUNNEL, STRAPPED

TO EXISTING CABLE TRAY AND STRUT HANGERS.

UP TO ROOM N20

CIRCUIT N2-1, N2-2, N2-3

CIRCUIT N2-1

CIRCUIT N2-2

CIRCUIT N2-3

UP TO ROOM S2

UP TO ROOM W24

UP TO ROOM E32

TO RECREATION BUILDING

TO CLASSROOM BUILDING

PLINK

PLINK

TO TRANSPORTATION BUILDING

PLINK

ENTRANCE102

KITCHENETTE

102A

UTILITY

RESTROOM

RESTROOM

CLASSROOM

CLASSROOM

OFFICE

COPIER

OFFICE

OFFICE

OFFICE

100A

CORRIDOR A

100B

CORRIDOR B

ENTRANCE102

KITCHENETTE

102A

UTILITY

RESTROOM

RESTROOM

CLASSROOM

CLASSROOM

OFFICE

COPIER

OFFICE

OFFICE

OFFICE

100A

CORRIDOR A

100B

CORRIDOR B

110,WP

F

S S

S

S

F

30 30

MM

SA

SA

IM

S

FB

FAA

N3-1 N3-1-1

N3-1-2

N3-1-3

N3-1-4

N3-1-5

N3-1-6

N3-1-7

N3-1-8

N3-1-9

EOLR

N3-2-1 N3-2-2

N3-2-3 N3-2-4

N3-2-5N3-2-6

N3-2-7

EOLR

N3-2-8

N3-2

S3.01 S3.02

S3.03

S3.10 S3.05

S3.06

S3.07

S3.08

S3.09

TS

MM S3.04

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.5

CLASSROOM

BUILDING FIRE

ALARM PLAN

GENERAL SHEET NOTES

SHEET KEY NOTES

SCALE:

CLASSROOM BUILDING

FIRE ALARM PLAN1 3/16" = 1'-0"

(E) POWER PANELS

1. NEW NAC POWER SUPPLY N3. RE-USE EXISTING

120V BRANCH CIRCUIT FROM EXISTING PANEL IN

OFFICE 107.

2. NEW MONITORING MODULE FOR FIRE SPRINKLER

MONITORING. TAMPER SWITCH AND FLOW SWITCH.

3. SURGE ARRESTERS FOR INCOMING FIRE ALARM

CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC

CIRCUIT.

4. PROVIDE 120V CIRCUIT FOR NEW FIRE BELL FROM

EXISTING PANEL IN OFFICE 107. CONTRACTOR

SHALL AS-BUILT THE CIRCUIT NUMBER ON THE

DRAWINGS.

5. PROVIDE NEW TAMPER SWITCH IN OS&Y VALVE.

VALVE PROVIDED BY OWNER.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

1. ALL FIRE ALARM WIRING WITHIN THE CLASSROOM

SHALL BE INSTALLED IN FREE AIR ABOVE THE

ACCESSIBLE CEILING IN THIS BUILDING.

2. ALL NEW SURFACE WALL MOUNTED NOTIFICATION

DEVICES SHALL BE PROVIDED WITH A FINISHED

BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO

COVER THE 4-SQUARE BACK BOX.

UTILITY

BREAK ROOM

REC ROOM

REC ROOM

PROGRAMS

BARBER 104

OFFICE

ELEC.

SHOWERS

RESTROOM

C100

CORRIDOR

UTILITY

BREAK ROOM

REC ROOM

REC ROOM

PROGRAMS

BARBER 104

OFFICE

ELEC.

SHOWERS

RESTROOM

C100

CORRIDOR

UTILITY

BREAK ROOM

REC ROOM

REC ROOM

PROGRAMS

BARBER 104

OFFICE

ELEC.

SHOWERS

RESTROOM

C100

CORRIDOR

MM

S

MM

S

S S

S

S S

SS

S

F

F

F

15 110,WP

SASAIM

S

FB

N4-1-1

N4-1-2

N4-1-3

N4-1-4

N4-1-5

EOLR

N4-1 N4-2

N4-2-1

N4-2-2

N4-2-3

N4-2-4

N4-2-5

EOLR

N4-2-6

S4.01

S4.02

S4.03 S4.04

S4.05

S4.06

S4.07

S4.08

S4.09

S4.104.11

S4.12

S4.13 S4.14

S4.15S4.16S4.17

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.6

RECREATION

BUILDING FIRE

ALARM PLAN

SCALE:

RECREATION BUILDING

FIRE ALARM PLAN1 3/16" = 1'-0"

1. NEW NAC POWER SUPPLY N4. PROVIDE NEW 120V,

20A CIRCUIT. WIRE TO PANEL A, CIRCUIT #3. ASSUME

NEW 20A SINGLE POLE CIRCUIT BREAKER IS

REQUIRED.

2. NEW MONITORING MODULE FOR FIRE SPRINKLER

MONITORING OF TAMPER AND FLOW SWITCH.

3. SURGE ARRESTERS FOR INCOMING FIRE ALARM

CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC

CIRCUIT.

4. WIRE NEW FIRE ALARM BELL TO PANEL A, CIRCUIT

#5.

(E) SUB PANEL A1

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

TO PHYSICAL

PLANT BUILDING

(N) 12 X 12 X 6 NEMA 3R FIRE ALARM

JUNCTION BOX

(E) PANEL A

GENERAL SHEET NOTES

SHEET KEY NOTES

1. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION

DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM

WIRING SHALL BE EXPOSED.

2. ALL NEW SURFACE WALL MOUNTED NOTIFICATION

DEVICES SHALL BE PROVIDED WITH A FINISHED

BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO

COVER THE 4-SQUARE BACK BOX

3. ALL NEW FIRE ALARM SMOKE DETECTORS, HEAT

DETECTORS, AND NOTIFICATION DEVICES ON THIS

SHEET SHALL BE PROVIDED WITH WIRE GUARDS.

ALL PULL STATIONS WILL BE PROVIDED WITH COVER

GUARDS.

102A

STORAGE

MAINTENANCE

STORAGE

STORAGE

RESTROOM

STORAGE

C100

CORRIDOR

102A

STORAGE

MAINTENANCE

STORAGE

STORAGE

RESTROOM

STORAGE

C100

CORRIDOR

H

F

S

H H

H

H

H

H

SAIM

N4-3

N4-3-1

N4-3-2

N4-3-3

N4-3-4

EOLR

S4.18

S4.19

S4.20S4.21

S4.22

S4.23S4.24

S4.25

S4.26

S4.27

Drawing No.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.7

PHYSICAL PLANT

FIRE ALARM PLAN

GENERAL SHEET NOTES

SHEET KEY NOTES

SCALE:

PHYSICAL PLANT

FIRE ALARM PLAN1 3/16" = 1'-0"

1. SURGE ARRESTERS FOR INCOMING FIRE ALARM

CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC

CIRCUIT.

KEYPLANNORTH

OREGON STATE PENITENTIARY MINIMUM

FIRE ALARM UPGRADE DESIGN

NORTH

WEST EAST

SO

U

TH

TO RECREATION

BUILDING

(N) 12 X 12 X 6 NEMA 3R FIRE ALARM

JUNCTION BOX

1. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION

DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM

WIRING SHALL BE EXPOSED.

2. ALL NEW SURFACE WALL MOUNTED NOTIFICATION

DEVICES SHALL BE PROVIDED WITH A FINISHED

BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO

COVER THE 4-SQUARE BACK BOX.

S

T A

T E

ST

SA

LE

M

O R

R ev

04/07/2025

6804Proj. No.

Date

D es cr ip ti o n

Checked

Drawn

Design

BP

JL

DL

O R

EG

O

N S

TA

TE

P

EN

IT

EN

TI

AR

Y M

IN

IM

U M

FI

R

E

AL

AR

M

U

PG

R

AD

E

Sa le m -5

-1 w w w .l an d is co n su lt in g .c o m

PDERETSI

GER LA

NOI

SSEFOR

OREGON

86683

NIG

N

E R

EE

8 , 2

M A Y

PERRY

B

EN

JAMI N

E.

EXPIRES: 12-31-2026

Digitally Signed

E2.8

PANEL SCHEDULES

Sheets and Views
E0.0 Cover Sheet
E0.1 Abbreviations & Symbol Legend
E0.2 Fire Alarm Riser Diagram
E0.3 Sprinkler Coverage Plan
E0.4 Electrical Details
E1.1 Demolition Site Plan
E1.2 Transportation Building Demolition Plan
E1.3 Main Housing Building Demolition Plan - North & South
E1.4 Main Housing Building Demolition Plan - East & West
E1.5 Classroom Building Demolition Plan
E1.6 Recreation Building Demolition Plan
E2.1 Proposed Site Plan
E2.2 Transportation Building Fire Alarm Plan
E2.3 Main Housing Building Fire Alarm Plan - North & South
E2.4 Main Housing Building Fire Alarm Plan - East & West
E2.4.1 Main Housing Building Tunnel Fire Alarm Plan
E2.5 Classroom Building Fire Alarm Plan
E2.6 Recreation Building Fire Alarm Plan
E2.7 Physical Plant Fire Alarm Plan
E2.8 Panel Schedules