13611 OSPM Fire Alarm System Upgrade Plans.pdf
PDF 4 MB Posted
- Attached to
- OSPM Fire Alarm System Upgrade
- Solicitation number
- S-29100-00013611
- Issued by
- Marion County, Oregon
About this file
This file comprises architectural and engineering design plans for the Oregon State Penitentiary Minimum Fire Alarm Upgrade project prepared by Landis Consulting and dated April 7, 2025. The project is managed by the Oregon Department of Corrections, Facilities Services, with Pete Belisle serving as the Construction Project Manager. The scope involves the complete replacement of the existing fire alarm system with a new addressable fire alarm system and two-way communication dial-out capability across five buildings at the penitentiary: the Transportation Building, Main Housing Building, Classroom Building, Recreation Building, and Physical Plant Building. The new Fire Alarm Control Panel will be located in the Transportation Building and will monitor all five buildings with occupant notification coverage, sprinkler monitoring of the Main Housing Building, installation of a new two-way communication call station that dials to off-site central station monitoring, and a smoke evacuation system in the Main Housing Building. The design complies with the 2022 Oregon Structural Specialty Code, 2021 Oregon Electrical Specialty Code, 2022 Oregon Fire Code, and 2022 NFPA 72 Code. The project documentation includes comprehensive demolition and proposed site plans, fire alarm riser diagrams, sprinkler coverage plans, electrical details, and panel schedules across 18 detailed drawing sheets totaling approximately 20,205 square feet for the Main Housing Building, 8,224 square feet for the Transportation Building, 3,368 square feet for the Classroom Building, 2,425 square feet for the Recreation Building, and 1,348 square feet for the Physical Plant Building.
The design calls for significant system infrastructure including multiple Signaling Line Circuits (SLC), Notification Appliance Circuits (NAC), and P-Link wiring throughout the facility, with new conduit installation estimated at approximately 3/4 inches diameter connecting buildings via underground trenching coordinated with the owner. The project requires removal of existing fire alarm devices and monitoring modules from multiple locations, replacement of smoke detectors with wireguards throughout the Main Housing Building, and installation of new junction boxes, relay modules, surge arresters, and line isolation modules. The existing 120-volt branch circuits will be reused and extended to new equipment where applicable, with some new 20-ampere circuits required for additional NAC power supplies. Notably, the design includes provisions for addressing existing smoke evacuation fans in the Main Housing Building that do not function, requiring contractor testing and diagnostics of branch circuit continuity, motor insulation, and control circuits to identify and correct the source of failure. The contract documents specify that contractors may modify proposed conduit routes for constructability while maintaining the design intent to minimize concrete wall penetrations, and contractors must as-built the actual conduit routes installed.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E0.0
COVER SHEET
SHEET INDEX
E0.0 - COVER SHEET
E0.1 - ABBREVIATIONS & SYMBOL LEGEND
E0.2 - FIRE ALARM RISER DIAGRAM
E0.3 - SPRINKLER COVERAGE PLAN
E0.4 - ELECTRICAL DETAILS
E1.1 - DEMOLITION SITE PLAN
E1.2 - TRANSPORTATION BUILDING DEMOLITION PLAN
E1.3 - MAIN HOUSING BUILDING DEMOLITION PLAN - NORTH & SOUTH
E1.4 - MAIN HOUSING BUILDING DEMOLITION PLAN - EAST & WEST
E1.5 - CLASSROOM BUILDING DEMOLITION PLAN
E1.6 - RECREATION BUILDING DEMOLITION PLAN
E2.1 - PROPOSED SITE PLAN
E2.2 - TRANSPORTATION BUILDING FIRE ALARM PLAN
E2.3 - MAIN HOUSING BUILDING FIRE ALARM PLAN - NORTH & SOUTH
E2.4 - MAIN HOUSING BUILDING FIRE ALARM PLAN - EAST & WEST
E2.4.1 - MAIN HOUSING BUILDING TUNNEL FIRE ALARM PLAN
E2.5 - CLASSROOM BUILDING FIRE ALARM PLAN
E2.6 - RECREATION BUILDING FIRE ALARM PLAN
E2.7 - PHYSICAL PLANT FIRE ALARM PLAN
E2.8 - PANEL SCHEDULES
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE
ELECTRICAL
LANDIS CONSUILTING
6446 FAIRWAY AVE SE UNIT 220,
SALEM, OREGON 97306
(503) 584-1576
PRINCIPAL/EOR: BEN PERRY
Ben_Perry@Landisconsulting.com
PROJECT MANAGER: DEVON LUTE
Devon_Lute@Landisconsulting.com
DESIGNER: JORDAN LUTE
Jordan_Lute@Landisconsulting.com
AREA OF PROJECT
VICINITY MAP1
OWNER
PETE BELISLE
CONSTRUCTION PROJECT MANAGER 2
DEPARTMENT OF CORRECTIONS,
FACILITIES SERVICES
3601 STATE STREET
SALEM, OREGON 97301
PROJECT CONTACTS PROJECT DESCRIPTION
REPLACEMENT OF EXISTING FIRE ALARM SYSTEM WITH NEW
ADDRESSABLE FIRE ALARM SYSTEM AND TWO-WAY
COMMUNICATION DIAL OUT. FIRE ALARM CONTROL PANEL SHALL BE
LOCATED IN THE TRANSPORTATION BUILDING AND WILL MONITOR
ALL FIVE BUILDINGS.
SYSTEM DESCRIPTION
- GENERAL OCCUPANT NOTIFICATION COVERAGE.
- SPRINKLER MONITORING OF MAIN HOUSING BUILDING.
- INSTALLATION OF NEW TWO-WAY COMMUNICATION
CALL STATION. CALL STATION DIALS OFF SITE TO A CENTRAL
STATION MONITORING.
- SMOKE EVACUATION SYSTEM IN MAIN HOUSING BUILDING.
DESIGN SHALL COMPLY WITH THE FOLLOWING CODES:
2022 OREGON STRUCTURAL SPECIALTY CODE
2021 OREGON ELECTRICAL SPECIALTY CODE
2022 OREGON FIRE CODE
2022 NFPA 72
CODE INFORMATION
TRANSPORTATION BUILDING:
MAIN HOUSING BUILDING:
CLASSROOM BUILDING:
RECREATION BUILDING:
PHYSICAL PLANT BUILDING:
OCCUPANCY GROUP
TRANSPORTATION BUILDING:
MAIN HOUSING BUILDING:
CLASSROOM BUILDING:
RECREATION BUILDING:
PHYSICAL PLANT BUILDING:
SPRINKLER COVERAGE
TRANSPORTATION BUILDING:
MAIN HOUSING BUILDING:
CLASSROOM BUILDING:
RECREATION BUILDING:
PHYSICAL PLANT BUILDING:
AREA MAP2
STATE ST
H
AW
TH
O
R N
E
AV
E N
E
IN
TE
R
ST
AT
E
I-5
G
EE
R D
R
AI
R
PO
R
T R
D S
E
TH
S T
SE
STATE ST
PA
RK
A
VE
N E
AREA OF PROJECT
8,224 SQ. FT.
20,205 SQ.FT.
3,368 SQ.FT.
2,425 SQ.FT.
1,348 SQ.FT.
TYPE B
TYPE I-3
TYPE B
TYPE I-3
TYPE I-3
PARTIAL COVERAGE
PARTIAL COVERAGE
FULL COVERAGE
FULL COVERAGE
NONE
FINISHED CEILING
FINISHED FLOOR
M
AX
M
IN
M
IN
6" (M
IN
MANUAL PULL STATION
HORN/STROBE
1. LOCATE ALL FIRE ALARM DEVICES PER NFPA 72
REQUIREMENTS.
NOTES:
M
AX
M
AX
FIRE ALARM CONTROL PANEL
DUAL PATH COMMUNICATOR
" M
AX
FIRE ALARM ANNUNCIATOR
NAC BOOSTER POWER SUPPLY
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E0.1
ABBREVIATIONS &
SYMBOL LEGEND
Electrical Abbreviations & Symbol Legend Abbreviations
A AMPERE
AC ALTERNATING CURRENT, AIR CONDITIONING UNIT
AHJ AUTHORITY HAVING JURISDICTION
AIC AVAILABLE INTERRUPTING CAPACITY
AF AMPERE FRAME / AMPERE FUSED
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ARMS ARC FLASH REDUCTION MAINTENANCE SYSTEM
AT AMPERE TRIP
AV AUDIO / VIDEO
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BFG BELOW FINISHED GRADE
BLDG BUILDING
C CONDUIT
CAT CATEGORY
CB CIRCUIT BREAKER
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CFOI CONTRACTOR FURNISHED, OWNER INSTALLED
CKT CIRCUIT
CPT CONTROL POWER TRANSFORMER
CR CONTROL RELAY
CU COPPER
dB DECIBAL
DC DIRECT CURRENT
DIM DIMENSION
DIV DIVISION
DTL DETAIL
DWG DRAWING
EL ELEVATION
EMT ELECTRICAL METALLIC TUBING
EOLR END OF LINE RESISTOR
FACP FIRE ALARM CONTROL PANEL
FF FINISH FLOOR
FLA FULL LOAD AMPERES
FT FOOT, FEET
FBO FURNISHED BY OTHERS
G, GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HH HAND HOLE
HP HORSEPOWER
ID IDENTIFICATION
IDC INITIATING DEVICE CIRCUIT
IDF INTERMEDIATE DISTRIBUTION FRAME
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
IG ISOLATED GROUND
IT INFORMATION TECHNOLOGY
JB JUNCTION BOX
KAIC THOUSAND AMPS INTERRUPTING CURRENT
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LAN LOCAL AREA NETWORK
LED LIGHT EMITTING DIODE
LS LIMIT SWITCH
LSI ELECTRONIC TRIP UNIT ADJUSTABLE LONG TIME DELAY,
SHORT TIME DELAY, INSTANTANEOUS TRIP
LSIG ELECTRONIC TRIP UNIT WITH ADJUSTABLE LONG TIME DELAY,
SHORT TIME DELAY, INSTANTANEOUS TRIP, AND GROUND
FAULT
LV LOW VOLTAGE
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MDF MAIN DISTRIBUTION FRAME
MHz MEGAHERTZ
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
N NEUTRAL
NAC NOTIFICATION APPLIANCE CIRCUIT
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
Ø PHASE
PB PULL BOX, PANIC BUTTON, PUSH BUTTON
PE PHOTO EYE
PNL PANEL
POE POWER OVER ETHERNET
PTZ PAN, TILT, ZOOM
RF RADIO FREQUENCY
RFI REQUEST FOR INFORMATION
SPD SURGE PROTECTION DEVICE
STD STANDARD
SW SWITCH
T/M THERMAL MAGNETIC CIRCUIT BREAKER
TBD TO BE DETERMINED
TV TELEVISION / MONITOR OUTLET
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
UH UNIT HEATER
UG UNDERGROUND
UL UNDERWRITERS LABORATORIES
UPS UNINTERRUPTIBLE POWER SUPPLY
UON UNLESS OTHERWISE NOTED
USB UNIVERSAL SERIAL BUS
V VOLTS, VOLTAGE
VA VOLT-AMPERE
VFD VARIABLE FREQUENCY DRIVE
W WATT, WIRE
WAN WIDE AREA NETWORK
WAP WIRELESS ACCESS POINT
WI-FI WIRELESS FIDELITY
W/ WITH
W/O WITHOUT
XFMR TRANSFORMER
Y WYE
1P ONE POLE
2P TWO POLE
3P THREE POLE
4P FOUR POLE
Drawing Symbol Variables
3 THREE WAY SWITCH.
4 FOUR WAY SWITCH.
#J QUANTITY OF JACKS AND HORIZONTAL CABLES.
J = CAT6, JA = CAT6A, JE = CAT5E
+XX MOUNTING UNITS EXPRESSED IN INCHES TO CENTERLINE ABOVE
FINISHED FLOOR OR GRADE.
C MOUNTED HORIZONTALLY AT 4" ABOVE COUNTERTOP.
CL CLOCK.
DR DUAL RELAY.
E RED EMERGENCY SWITCH.
EL ELEVATOR RECALL.
ETR EXISTING DEVICE SHALL REMAIN.
G GLASS BREAK SENSOR.
K KEYED SWITCH.
LF LOW FREQUENCY.
LV LOW VOLTAGE SWITCH.
M MOTOR RATED TOGGLE SWITCH.
NEX REPLACE EXISTING WIRING DEVICE AND FACEPLATE WITH NEW. BACK BOX
AND CONDUIT SHALL REMAIN.
O INTEGRAL OCCUPANCY SENSOR.
P ADA PHONE, VERIFY HEIGHT WITH ARCHITECT / OWNER.
REX REMOVE EXISTING DEVICE / EQUIPMENT.
TK MOUNTED IN TOE KICK OF CASEWORK.
TV MOUNTED ADJACENT TO TV AT 60" AFF, UON.
V VANDAL RESISTANT.
WG WIREGUARD.
WP WEATHERPROOF.
Raceways
CONDUIT AND/OR CONDUCTORS INSTALLED ABOVE GRADE,
CONCEALED IN WALL OR CEILING SPACE.
CONDUIT TURNED DOWN.
CONDUIT AND/OR CONDUCTORS INSTALLED BELOW GRADE, BELOW
SLAB.
CONDUIT TURNED UP.
CONDUIT STUBBED AND CAPPED.
CONDUIT DIRECT CONNECTION TO EQUIPMENT.
FLEXIBLE CONNECTION TO EQUIPMENT.
CONDUIT / WIRING CONTINUATION.
HOMERUN TO PANELBOARD.
CABLE TRAY. SIZE AND TYPE AS INDICATED ON DRAWINGS.
Miscellaneous
JUNCTION BOX (ROUND, SQUARE).
THERMOSTAT.
RELAY.
CORD REEL.
MOTOR / EXHAUST FAN.
CEILING FAN.
UTILITY POLE.
WEATHERHEAD.
GROUND ROD.
GROUND ROD WITH TEST WELL.
SURFACE RACEWAY / WIREMOLD.
JJ
T
R
FIRE RATED BACKBOARD.
GROUND BUS BAR.
Annotation
CONDUIT & CONDUCTOR CALLOUT. REFER TO CONDUIT &
CONDUCTOR SCHEDULE.
KEYED NOTE CALLOUT. REFER TO CORRESPONDING SHEET
KEYNOTES.XX
(E) INDICATES EXISTING EQUIPMENT TO REMAIN.
(D) INDICATES EXISTING EQUIPMENT TO BE DEMOLISHED.
(N) INDICATES NEW EQUIPMENT.
KEYED NOTE CALLOUT. REFER TO CORRESPONDING SHEET
KEYNOTES.
KEYED NOTE CALLOUT. REFER TO CORRESPONDING SHEET
KEYNOTES.
MECHANICAL EQUIPMENT CALLOUT. REFER TO MECHANICAL
EQUIPMENT CONNECTION SCHEDULE.
X
EX.XX
DETAIL CALLOUT. REFER TO DETAIL AND SHEET AS INDICATED ON
CALLOUT.
FIXTURE MOUNTING CALLOUT. HEIGHT ABOVE FINISHED FLOOR
(A.F.F.)
XXXXX EQUIPMENT CALLOUT. REFER TO NEMA CONNECTION SCHEDULE.
X
EX.XX
SECTION CALLOUT. REFER TO DETAIL AND SHEET AS INDICATED ON
CALLOUT.
ELEVATION CALLOUT. REFER TO DETAIL AND SHEET AS INDICATED
ON CALLOUT.
EX.XX
(RR)/(RD) INDICATES EXISTING EQUIPMENT OR DEVICE TO BE REMOVED AND
REINSTALLED.
XX'-XX"
PXXX
XX
XX-XX
XX
Power Distribution
DUPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.
QUADPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.
GFCI QUADPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.
SIDE HATCHED RECEPTACLE, TO BE WIRED TO SWITCHED CIRCUIT.
NEMA SPECIAL RECEPTACLE, MOUNTED AT 18" AFF, UON. NEMA
CONFIGURATION AS INDICATED.
RECEPTACLE MOUNTED ON CEILING.
CENTER HATCHED RECEPTACLE TO BE WIRED TO EMERGENCY
CIRCUIT.
TAMPER RESISTANT DUPLEX RECEPTACLE, MOUNTED AT 18" AFF,
UON.
GFCI DUPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.
PANELBOARD SURFACE MOUNT.
PANELBOARD FLUSH MOUNT.
MAIN DISTRIBUTION PANEL.
DISCONNECT SWITCH.
FUSED DISCONNECT SWITCH.
ENCLOSED CIRCUIT BREAKER.
COMBINATION STARTER.
FLOORBOX COMBINATION POWER & DATA.
FLOORBOX POWER.
POKETHRU COMBINATION POWER & DATA.
POKETHRU POWER.
POWER POLE.
SIMPLEX RECEPTACLE, MOUNTED AT 18" AFF, UON.
UTILITY CT METER.
TAMPER RESISTANT QUADPLEX RECEPTACLE, MOUNTED AT 18" AFF,
UON.
RECEPTACLE MOUNTED IN-COUNTER.
UTILITY TRANSFORMER.
F
TS
FS
PS
MM
RI
RO
FIRE ALARM AUDIO/VISUAL - WALL MOUNTED. CANDELA RATING AS
SHOWN ON DRAWING.
FIRE ALARM VISUAL - WALL MOUNTED. CANDELA RATING AS SHOWN
ON DRAWING.
FIRE ALARM AUDIO/VISUAL - CEILING MOUNTED. CANDELA RATING
AS SHOWN ON DRAWING.
FIRE ALARM VISUAL - CEILING MOUNTED. CANDELA RATING AS
SHOWN ON DRAWING.
FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED.
FIRE ALARM SMOKE DETECTOR - WALL MOUNTED.
FIRE ALARM HEAT DETECTOR - CEILING MOUNTED.
FIRE ALARM HEAT DETECTOR - WALL MOUNTED.
FIRE ALARM DUCT SMOKE DETECTOR.
FIRE ALARM DUCT SMOKE DETECTOR WITH REMOTE TEST STATION.
FIRE ALARM MANUAL PULL STATION - WALL MOUNTED.
FIRE ALARM MANUAL TAMPER SWITCH.
FIRE ALARM MANUAL FLOW SWITCH.
FIRE ALARM MANUAL PRESSURE SWITCH.
FIRE ALARM MONITOR MODULE.
FIRE ALARM RELAY INPUT.
FIRE ALARM RELAY OUTPUT.
Fire Alarm
PIV
SA
FIRE ALARM POST INDICATOR VALVE.
FIRE ALARM SURGE ARRESTOR.
FAA FIRE ALARM ANNUNCIATOR.
FIRE ALARM MAGNETIC DOOR HOLD.
FIRE ALARM BELL.FB
IM FIRE ALARM ISOLATION MODULE.
TS
FIRE ALARM BEAM SMOKE DETECTOR.
S
S
H
H
S
S
S
SCALE:
DEVICE MOUNTING HEIGHTS1 1/2" = 1'-0"
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E0.2
FIRE ALARM RISER
DIAGRAM
(N) FIRE ALARM
CONTROL PANEL(N) FIRE ALARM
ANNUNCIATOR
SLC LOOP WIRING
P-LINK WIRING
WIRING LEGEND
NAC WIRING(N) DUAL PATH
COMMUNICATOR
TRANSPORTATION BUILDING
N0-1-1 N0-1-2 N0-1-3 N0-1-4 N0-1-5 N0-1-6 N0-1-7 N0-1-8 N0-1-9 N0-1-10 N0-1-11
EOLR
EOLR
EOLR
N0-2-1 N0-2-2 N0-2-3 N0-2-4 N0-2-5 N0-2-6 N0-2-7 N0-2-8 N0-2-9
N0-3-1 N0-3-2 N0-3-3 N0-3-4 N0-3-5 N0-3-6 N0-3-7
(N) NAC BOOSTER
POWER SUPPLY N1
SA SA
(N) FIRE ALARM
ANNUNCIATOR
(N) FIRE ALARM
ANNUNCIATOR
SA SA
MAIN HOUSING
CLASSROOM BUILDING
SA SA
RECREATION BUILDING
PHYSICAL PLANT BUILDING
N1-3-1
N1-4-1
N1-5-3
N2-1-1
N2-3-1
F S IM F MM MM MM S S S S
S0.01 S0.02 S0.03 S0.04 S0.05 S0.06 S0.07 S0.08 S0.09 S0.10 S0.11
N3-1-1
N3-2-1
N2-1-2
N3-1-2 N3-1-3 N3-1-4 N3-1-5 N3-1-6 N3-1-7 N3-1-8 N3-1-9
N3-2-2 N3-2-3 N3-2-4 N3-2-5 N3-2-6 N3-2-7 N3-2-8
N4-1-1
N4-2-1
N4-3-1 N4-3-2 N4-3-3 N4-3-4
N4-1-2 N4-1-3 N4-1-4 N4-1-5
N4-2-2 N4-2-3 N4-2-4 N4-2-5 N4-2-6
EOLR
EOLR
EOLR
EOLR
EOLR
N1-2-1
N1-1-1 N1-1-2 N1-1-3 N1-1-4 N1-1-5 N1-1-6 N1-1-7 N1-1-8 N1-1-9 N1-1-10 N1-1-11 N1-1-12 N1-1-13 N1-1-14
N1-2-2 N1-2-3 N1-2-4 N1-2-5 N1-2-6 N1-2-7 N1-2-8 N1-2-9
N1-3-2 N1-3-3 N1-3-4 N1-3-5 N1-3-6 N1-3-7 N1-3-8 N1-3-9
N1-4-2 N1-4-3 N1-4-4 N1-4-5 N1-4-6 N1-4-7
N1-5-4
N2-1-3 N2-1-4
N2-3-2 N2-3-3
N2-2-3 N2-2-4 N2-2-5
F S F F S S S
S4.01 S4.02 S4.03 S4.04 S4.05 S4.06 S4.07 S4.08 S4.09 S4.10 S4.11 S S S S S
S4.12 S
S4.13 S
S4.14
MM
S4.15
MM
S4.16
IM
S4.17
IM HF H H
S4.18 S4.19 S4.20 S4.21 S4.22 S4.23 S4.24 S4.25 S4.26 S4.27 H H H H H
IMS MM FSS
S3.01 S3.02 S3.03 S3.04 S3.05 S3.06 S3.07 S3.08 S3.09 S F
F S S
S1.01 S1.02 S1.03 S1.04 S1.05 S1.06 S1.07 S1.08 S1.09
S SS S S S
S1.10 S1.11 S
S1.12 F
S1.13 S S
S1.14 S1.15 S S
S1.16
MM
S1.17
MM
S1.18 H
S1.19 F
S1.20 H
S1.21 S
S1.22 H
S1.23 S
S1.24 S1.25 S S
S1.28 S
S1.27 S1.26 S S
S1.30 S
S1.29 S
S1.33 S
S1.32 S1.31 S S
S1.35 S
S1.34 S
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
S S
S2.01 S2.02 S2.03 S2.04 S2.05 S2.06 S2.07 S2.08
S SS SSS S
S2.09 S2.10 S2.11 S2.12 S2.13
S S SS S
S2.14 S2.15 S2.16 S2.17 S2.18
S S SS S
S2.19 S2.20 S2.21 S2.22 S2.23
S S SS S
S2.24 S2.25 S2.26 S S
S
S2.28 S2.27 S
S2.29
RO
S2.30
SS
S2.31S2.32 F
S2.33 S
S2.36 S
S2.35 S2.34 S S
S2.41 S S
S2.40 S2.39 S2.38 S2.37 S S S
S2.46 S S
S2.45 S2.44 S2.43 S2.42 S S S
S2.51 S S
S2.50 S2.49 S2.48 S2.47 S S S
S2.52 S
S
S2.53 S2.54 S2.55 S S
S2.56 S
S2.61
SS
S2.57 S2.58 S2.59 S2.60 S S S
S2.62
RO
S2.63 S
S2.64 F
S2.65 S
S2.68
SS
S2.66 S2.67 S S
S2.69 S2.70 S2.71 S2.72 S2.73
S S SS
S2.74 S S
S2.75 S2.76 S2.77
SS
S2.78 S
S2.83 S S
S2.82 S2.81 S2.80 S2.79
S S SS
S2.88 S2.87 S2.86 S2.85 S2.84
S S SS
S2.89
SS
S2.93 S2.92 S2.91 S2.90 S S S
S2.94
SS
S2.98 S2.97 S2.96 S2.95 S S S
S2.99
SS
S2.102 S2.101 S2.100 S S
S2.103
RO
S2.104 S
S2.105 S
S2.107 S
S2.106 F
N0-1 N0-2 N0-3
SLC
N1-1 N1-2 N1-3
SLC
EXP.
N1-4 N1-5 N1-6
(N) NAC BOOSTER
POWER SUPPLY N2
N2-1 N2-2 N2-3
SLC
EXP.
N2-4 N2-5 N2-6
(N) NAC BOOSTER
POWER SUPPLY N3
N3-1 N3-2 N3-3
SLC
EXP.
N3-4 N3-5 N3-6
(N) NAC BOOSTER
POWER SUPPLY N4
N4-1 N4-2 N4-3
SLC
EXP.
N4-4 N4-5 N4-6
120V
120V
120V
120V
120V
120V
N1-5-1 N1-5-2
N0-4 N0-4-1 N0-4-2
N1-6-1 N1-6-2 N1-6-3 N1-6-4
(FRONT ENTRY ACCESS
CONTROL OVERRIDE)
N0-5 N0-6
SA
SA
SA
SA
F S0.12
RO
S0.13
EOLR
EOLR
S3.10
SMM
(E) PANEL IN
OFFICE 107 FS FB
(E) FLOW SWITCH
ON RISER
(E) PANEL A
CKT. #5 FS FB
(E) FLOW SWITCH
ON RISER
(E) PANEL E
CKT. #10 FS FB
(E) FLOW SWITCH
ON RISER
Main Housing Building
E1.3,E1.4
Classroom Building E1.5
Recreation Building E1.6
Physical Plant Building
Transportation Building E1.2
Carport (No Scope)
FB
FB
FB
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E0.3
SPRINKLER
COVERAGE PLAN
20'10'5'0'
SCALE:
SPRINKLER COVERAGE PLAN1 1" = 20'
EXISTING FIRE RISER
EXISTING FIRE RISER
EXISTING FIRE RISER
- SPRINKLER COVERAGE
SPRINKLER COVERAGE LEGEND
GENERAL SHEET NOTES
1. THE FIRE SPRINKLER SYSTEM IN THE MAIN HOUSING
UNIT IS FED FROM THE TRANSPORTATION BUILDING
FIRE SPRINKLER RISER.
FIRE SPRINKLER WATER FLOW BELL
FIRE SPRINKLER WATER FLOW BELL
FIRE SPRINKLER WATER FLOW BELL
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E0.4
ELECTRICAL DETAILS
8" MIN.
MOUNTING DETAIL SHALL BE UTILIZED FOR
ALL NON-CAST IRON ENCLOSURES OR
BOXES WITH EXTERNAL MOUNTING FEET.
PROVIDE SIMILAR MOUNTING FOR
ENCLOSURES WITH INTERNAL MOUNTING
HOLES.
ENCLOSURE WALL
MOUNTING DETAIL
201DETAIL NO.NTSSCALE:
NON-CONCRETE
ENCASED DUCTBANK
DETAIL
402DETAIL NO.NTSSCALE:
FINISHED GRADE
UNDISTRIBUTED EARTH
INSTALL CONDUITS
PER SCHEDULE, TYP.
NOTES:
1.TYPICAL EXCEPT AS SPECIFIED.
2. MAINTAIN A MINIMUM OF 12" SEPARATION BETWEEN POWER CONDUITS AND
CONTROL, TELECOMMUNICATION AND INSTRUMENTATION.
3. BACKFILL SHALL BE AS SPECIFIED IN SECTION 02226/312300.
3" M
IN
S
EP
AR
AT
IO
N , T
YP
3" MIN SEPARATION, TYP.
" M
IN
6" COVER OF SCREENED GRANULAR
BACKFILL SHALL SURROUND CONDUITS.
BACKFILL SHALL CONTAIN ONLY SOIL AND
ROCKS THAT WILL PASS THROUGH A
3/4" SIEVE. AND NO MORE THAN 15% OF
THE MATERIAL PASSES THROUGH A
NO. 200 MESH SIEVE.
3" M
IN
. B
ED
D
IN
G
SU
B
BA
SE
O F
SU
R
FA
C
E
NATIVE BACKFILL, FREE OF ROCKS AND
DEBRIS LARGER THAN 4" DIAMETER
TRENCH WARNING TAPE
(16130.T01/260533.T01)
COMPACTED EARTH
PROVIDE 6" MINIMUM OF 3/4" MINUS
GRAVEL BASE PER SECTION 02226/312300.
WALL MOUNTED CEILING OR WALL MOUNTED
TRAPEZE MOUNTED
CONDUIT STRAP
GALVANIZED ANCHORS
GALVANIZED STRUT CHANNEL
GALVANIZED ANCHORS
M
AX
3" (TYP.)
1" (T
YP
36" MAX.
BETWEEN HANGERS
GALVANIZED STRUT CHANNEL
6" M
IN
5" M
IN
9" M
IN
1" MIN.
1" (TYP.)
GALVANIZED HARDWARE
GALVANIZED STRUT CHANNEL
SEISMIC BRACING
PRODUCTS
INSTALL THREADED RODS
USED FOR CONDUIT HANGERS
WITH JAMB NUTS AND FLAT
PLATE FITTINGS (TYP).
CEILING
CONDUIT
MOUNTING
202DETAIL NO.NTSSCALE:
GRC ELBOW WITH PVC
WRAP CONDUIT
TRANSITION
403DETAIL NO.NTSSCALE:
2" M
AX
PVC-40 GRC CONDUIT WRAPPED IN PVC TAPE
FINISHED GRADE
CONDUIT TYPE, AS SPECIFIED.
FEMALE ADAPTER (FEMALE
THREADS FOR GRC, SOCKET
END FOR PVC.)
CONCRETE
GRC COUPLING
E1.3,E1.4
Classroom Building E1.5
Recreation Building E1.6
Physical Plant Building (No Demolition)
Transportation Building E1.2
Carport (No Scope)
J
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E1.1
DEMOLITION SITE
PLAN
SHEET KEY NOTES
30'15'0'
SCALE:
DEMOLITION SITE PLAN1 1" = 30'
1. REMOVE ALL FIRE ALARM WIRING BETWEEN FACP IN
TRANSPORTATION BUILDING AND THE MAIN
HOUSING BUILDING THROUGH EXISTING CONDUT(S).
THE CONDUIT ORIGINATES ON THE
TRANSPORTATION BUILDING AND CONNECTS TO
THE MAIN HOUSING BUILDING TUNNEL.
LOBBY
ENTRANCE
BREAKROOM
102A
RESTROOM
102B
DATA
STORAGE
ROOM
SHAKEDOWN
JANITOR
OFFICE
MULTIPURPOSE
107A
RESTROOM
OFFICE
OFFICE
STORAGE
LOUNGE
LIBRARY
BARBER
111A
STORAGE
RESTROOM
ELEC.
CLASSROOM
CARDIO
ROOM
OFFICE
118A
STORAGE
STORAGE
REC ROOM
100A
CORRIDOR A
100B
CORRIDOR B
100C
CORRIDOR C
LOBBY
ENTRANCE
BREAKROOM
102A
RESTROOM
102B
DATA
STORAGE
ROOM
SHAKEDOWN
JANITOR
OFFICE
MULTIPURPOSE
107A
RESTROOM
OFFICE
OFFICE
STORAGE
LOUNGE
LIBRARY
BARBER
111A
STORAGE
RESTROOM
ELEC.
CLASSROOM
CARDIO
ROOM
OFFICE
118A
STORAGE
STORAGE
REC ROOM
100A
CORRIDOR A
100B
CORRIDOR B
100C
CORRIDOR C
FFAA
S
S
MM
MM MM
FB
FB
S
S
RO
(E) PANEL A1
(D) FIRE ALARM CONTROL PANEL
(E) FIRE ALARM JUNCTION BOX
(E) PANEL M
(E) PANEL E
(E) PANEL A
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E1.2
TRANSPORTATION
BUILDING
DEMOLITION PLAN
GENERAL SHEET NOTES
SHEET KEY NOTES
SCALE:
TRANSPORTATION BUILDING
DEMOLITION PLAN1 1/8" = 1'-0"
1. ALL FIRE ALARM DEVICES SHOWN AS DASHED
SHALL BE REMOVED COMPLETELY. REMOVE WIRING
COMPLETELY BACK TO SOURCE.
2. ANY DEVICE BEING REMOVED AND NOT REPLACED
WITH A NEW DEVICE IN THE SAME LOCATION/BOX
SHALL BE PROVIDED WITH A BLANK COVERPLATE.
1. EXISTING FIRE ALARM CONTROL PANEL SHALL BE
REPLACED WITH NEW IN SAME LOCATION.
CONTRACTOR SHALL MAINTAIN EXISTING 120V
BRANCH CIRCUIT AND EXTEND TO NEW FIRE ALARM
CONTROL PANEL.
2. REMOVE MONITORING MODULE FOR FIRE
SPRINKLER RISER MONITORING.
3. PROVIDE BLANK COVERPLATE. PAINT TO MATCH
EXISTING WALL.
4. REMOVE EXISTING DOOR HOLD OPEN POWER
SUPPLY TRANSFORMER. WIRE EXISTING DOOR
HOLD OPENS TO NEW NAC CIRCUIT ON NEW FIRE
ALARM CONTROL PANEL.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
E
C
W1 S.R.
W2 S.R.
W3 S.R.
W24 S.R.
W23 S.R.
W22 S.R.
E32 S.R.
E1 S.R.
N24
DINING
VISITATION
N1 A & O
N2 A & O
N3 A & O
N4 A & O
N20
TELEPHONE
ROOM
N21
STORAGE
N10
STORAGE
N9
COUNSEL
N8
OFFICE
N27
NURSE'S
STATION
N26
ITS
L13
L22
DRYING
N7
STORAGE
N34
OFFICE
N35
N22
STORAGE
N33
EXAM
N28
EXAM
N6
BOILER
N29
N30
N31
N5
K5
OFFICE K4
K2
DRY
STORAGE
L2
STORAGE
L24
LAUNDRY
K1
KITCHEN
K3
FREEZER
K6
WALK-IN
COOLER
L14
N36
CONTROL
L20
L1
LOBBY
100C
CORRIDOR C
N6
BOILER
100N
CORRIDOR N
100B
CORRIDOR B
100A
CORRIDOR A
100K
CORRIDOR K
K7
DISHWASHING
100D
CORRIDOR D 003
STORAGE
STORAGE
STORAGE
STORAGE
K8
N24
DINING
VISITATION
N1 A & O
N2 A & O
N3 A & O
N4 A & O
N20
TELEPHONE
ROOM
N21
STORAGE
N10
STORAGE
N9
COUNSEL
N8
OFFICE
N27
NURSE'S
STATION
N26
ITS
L13
L22
DRYING
N7
STORAGE
N34
OFFICE
N35
N22
STORAGE
N33
EXAM
N28
EXAM
N6
BOILER
N29
N30
N31
N5
K5
OFFICE K4
K2
DRY
STORAGE
L2
STORAGE
L24
LAUNDRY
K1
KITCHEN
K3
FREEZER
K6
WALK-IN
COOLER
L14
N36
CONTROL
L20
L1
LOBBY
100C
CORRIDOR C
N6
BOILER
100N
CORRIDOR N
100B
CORRIDOR B
100A
CORRIDOR A
100K
CORRIDOR K
K7
DISHWASHING
100D
CORRIDOR D 003
STORAGE
STORAGE
STORAG
STORAGE
K8
S
S
S
S
S
S
S
S
S
S
S
S S
FB
FB
FB
FB
MMMM
FB
S S
S
F
S
FAA
D C
S2 S.R.
S3 S.R.
S4 S.R.
S5 S.R.
S6 S.R.
S7 S.R.
S8 S.R.
S9 S.R.
S10 S.R.
S11 S.R.
S12 S.R.
S23 S.R.
S22 S.R.
S21 S.R.
S20 S.R.
S19 S.R.
S18 S.R.
S17 S.R.
S16 S.R.
S15 S.R.
S14 S.R.
S13 S.R.
S24 S.R.
W1 S.R.
L22
DRYING
L2
STORAGE
L3
STORAGE
L7
JANITOR
L24
LAUNDRY
N36
L1
LOBBY
L19
CONFERENCE
100S
CORRIDOR S
100D
CORRIDOR D
100F
CORRIDOR F
STORAGE
STORAGE
STORAGE
STORAGE
STORAGE
L8
S1
RESTROOM
S2 S.R.
S3 S.R.
S4 S.R.
S5 S.R.
S6 S.R.
S7 S.R.
S8 S.R.
S9 S.R.
S10 S.R.
S11 S.R.
S12 S.R.
S23 S.R.
S22 S.R.
S21 S.R.
S20 S.R.
S19 S.R.
S18 S.R.
S17 S.R.
S16 S.R.
S15 S.R.
S14 S.R.
S13 S.R.
S24 S.R.
L22
DRYING
L2
STORAGE
L3
STORAGE
L7
JANITOR
L24
LAUNDRY
N36
L1
LOBBY
L19
CONFERENCE
100S
CORRIDOR S
100D
CORRIDOR D
100F
CORRIDOR F
STORAGE
STORAGE
STORAGE
STORAGE
STORAGE
L8
S1
RESTROOM
S
S
FB
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
FB
S
S
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E1.3
MAIN HOUSING
BUILDING
DEMOLITION PLAN -
NORTH & SOUTH
SCALE:
MAIN HOUSING BUILDING
DEMOLITION PLAN - NORTH1 1/8" = 1'-0"
MATCHLINEMATCHLINE
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
SCALE:
MAIN HOUSING BUILDING
DEMOLITION PLAN - SOUTH2 1/8" = 1'-0"
MATCHLINEMATCHLINE
M
AT
C H
LI
N
E
M
AT
C H
LI
N
E
1. SMOKE EVACUATION DAMPER CONTROL.
2. MONITORING MODULE SERVE KITCHEN HOODS IN
KITCHEN K1.
(D) FIRE ALARM JUNCTION BOX
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
M
AT
C H
LI
N
E
M
AT
C H
LI
N
E
GENERAL SHEET NOTES
SHEET KEY NOTES
1. ALL FIRE ALARM DEVICES SHOWN AS DASHED
SHALL BE REMOVED COMPLETELY. REMOVE WIRING
COMPLETELY BACK TO SOURCE.
2. ANY DEVICE BEING REMOVED AND NOT REPLACED
WITH A NEW DEVICE IN THE SAME LOCATION/BOX
SHALL BE PROVIDED WITH A BLANK COVERPLATE.
3. ALL SMOKE DETECTORS ON THIS SHEET HAVE
WIREGUARDS. CONTRACTOR SHALL REMOVE AND
REPLACE ALL WIREGUARDS.
(E) POWER PANEL
F E
W1 S.R.
W2 S.R.
W3 S.R.
W4 S.R.
W5 S.R.
W6 S.R.
W7 S.R.
W8 S.R.
W9 S.R.
W10 S.R.
W11 S.R.
W12 S.R.
W24 S.R.
W23 S.R.
W22 S.R.
W21 S.R.
W20 S.R.
W19 S.R.
W18 S.R.
W17 S.R.
W16 S.R.
W15 S.R.
W14 S.R.
W13 S.R.
N35
LOBBY
100W
CORRIDOR W
STORAGE
STORAGE
W25 S.R.
W1 S.R.
W2 S.R.
W3 S.R.
W4 S.R.
W5 S.R.
W6 S.R.
W7 S.R.
W8 S.R.
W9 S.R.
W10 S.R.
W11 S.R.
W12 S.R.
W24 S.R.
W23 S.R.
W22 S.R.
W21 S.R.
W20 S.R.
W19 S.R.
W18 S.R.
W17 S.R.
W16 S.R.
W15 S.R.
W14 S.R.
W13 S.R.
100W
CORRIDOR W
STORAGE
STORAGE
W25 S.R.
S S S S S S S S S S
S S S S S S S S S S
S S
S S
S S S S S S
FB
S
B A
E32 S.R.
E31 S.R.
E30 S.R.
E29 S.R.
E28 S.R.
E27 S.R.
E26 S.R.
E25 S.R.
E24 S.R.
E23 S.R.
E22 S.R.
E21 S.R.
E20 S.R.
E19 S.R.
E18 S.R.
E17 S.R.
E1 S.R.
E2 S.R.
E3 S.R.
E4 S.R.
E5 S.R.
E6 S.R.
E7 S.R.
E8 S.R.
E9 S.R.
E10 S.R.
E11 S.R.
E12 S.R.
E13 S.R.
E14 S.R.
E15 S.R.
E16 S.R.
100E
CORRIDOR E
STORAGE
STORAGE
STORAGE
K8
E32 S.R.
E31 S.R.
E30 S.R.
E29 S.R.
E28 S.R.
E27 S.R.
E26 S.R.
E25 S.R.
E24 S.R.
E23 S.R.
E22 S.R.
E21 S.R.
E20 S.R.
E19 S.R.
E18 S.R.
E17 S.R.
E1 S.R.
E2 S.R.
E3 S.R.
E4 S.R.
E5 S.R.
E6 S.R.
E7 S.R.
E8 S.R.
E9 S.R.
E10 S.R.
E11 S.R.
E12 S.R.
E13 S.R.
E14 S.R.
E15 S.R.
E16 S.R.
100E
CORRIDOR E
S S S S S S S S S S S S S S S S
S S S S S S S S S S S S S S S S
S S S S S S S S
FB FB
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E1.4
MAIN HOUSING
BUILDING
DEMOLITION PLAN -
EAST & WEST
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
SCALE:
MAIN HOUSING BUILDING
DEMOLITION PLAN - WEST1 1/8" = 1'-0"
SCALE:
MAIN HOUSING BUILDING
DEMOLITION PLAN - EAST2 1/8" = 1'-0"
MATCHLINE
MATCHLINE
MATCHLINE
MATCHLINE
1. SMOKE EVACUATION DAMPER CONTROL.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
GENERAL SHEET NOTES
SHEET KEY NOTES
1. ALL FIRE ALARM DEVICES SHOWN AS DASHED
SHALL BE REMOVED COMPLETELY. REMOVE WIRING
COMPLETELY BACK TO SOURCE.
2. ANY DEVICE BEING REMOVED AND NOT REPLACED
WITH A NEW DEVICE IN THE SAME LOCATION/BOX
SHALL BE PROVIDED WITH A BLANK COVERPLATE.
3. ALL SMOKE DETECTORS ON THIS SHEET HAVE
WIREGUARDS. CONTRACTOR SHALL REMOVE AND
REPLACE ALL WIREGUARDS.
ENTRANCE102
KITCHENETTE
102A
UTILITY
RESTROOM
RESTROOM
CLASSROOM
CLASSROOM
OFFICE
COPIER
OFFICE
OFFICE
OFFICE
100A
CORRIDOR A
100B
CORRIDOR B
ENTRANCE102
KITCHENETTE
102A
UTILITY
RESTROOM
RESTROOM
CLASSROOM
CLASSROOM
OFFICE
COPIER
OFFICE
OFFICE
OFFICE
100A
CORRIDOR A
100B
CORRIDOR B
F
S S
S
S
F
MM
RO
S
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E1.5
CLASSROOM
BUILDING
DEMOLITION PLAN
SCALE:
CLASSROOM BUILDING
DEMOLITION PLAN1 3/16" = 1'-0"
(E) POWER PANELS
1. REMOVE NAC POWER SUPPLY. MAINTAIN EXISTING
120V BRANCH CIRCUIT.
2. REMOVE MONITORING MODULE FOR FIRE
SPRINKLER MONITORING.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
GENERAL SHEET NOTES
SHEET KEY NOTES
1. ALL FIRE ALARM DEVICES SHOWN AS DASHED
SHALL BE REMOVED COMPLETELY. REMOVE WIRING
COMPLETELY BACK TO SOURCE.
2. ANY DEVICE BEING REMOVED AND NOT REPLACED
WITH A NEW DEVICE IN THE SAME LOCATION/BOX
SHALL BE PROVIDED WITH A BLANK COVERPLATE.
UTILITY
BREAK ROOM
REC ROOM
REC ROOM
PROGRAMS
BARBER 104
OFFICE
ELEC.
SHOWERS
RESTROOM
C100
CORRIDOR
UTILITY
BREAK ROOM
REC ROOM
REC ROOM
PROGRAMS
BARBER 104
OFFICE
ELEC.
SHOWERS
RESTROOM
C100
CORRIDOR
MM
S
FB
MM
SS
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E1.6
RECREATION
BUILDING
DEMOLITION PLAN
SCALE:
RECREATION BUILDING
DEMOLITION PLAN1 3/16" = 1'-0"
1. REMOVE MONITORING MODULE FOR FIRE
SPRINKLER RISER MONITORING.
(E) POWER PANELS
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
GENERAL SHEET NOTES
SHEET KEY NOTES
1. ALL FIRE ALARM DEVICES SHOWN AS DASHED
SHALL BE REMOVED COMPLETELY. REMOVE WIRING
COMPLETELY BACK TO SOURCE.
2. ANY DEVICE BEING REMOVED AND NOT REPLACED
WITH A NEW DEVICE IN THE SAME LOCATION/BOX
SHALL BE PROVIDED WITH A BLANK COVERPLATE.
E2.3,E2.4
Classroom Building E2.5
Recreation Building E2.6
Physical Plant Building E2.7
Transportation Building E2.2
Carport (No Scope)
J
J
J
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.1
PROPOSED SITE PLAN
SHEET KEY NOTES
30'15'0'
SCALE:
PROPOSED SITE PLAN1 1" = 30'
1. EXISTING SMOKE EVACUATION FANS DO NOT TURN
ON. CONTRACTOR SHALL PROVIDE TESTING TO
IDENTIFY SOURCE OF PROBLEM AND CORRECT.
PERFORM THE FOLLOWING TESTS: BRANCH CIRCUIT
CONDUCTOR CONTINUITY AND INSULATION
TESTING; MOTOR INSULATION TESTING; TESTING
ALL CONTROL CIRCUITS WITHIN THE FAN MOTOR
STARTER. IDENTIFY THE SOURCE OF THE PROBLEM
AND PROPOSED SOLUTION TO THE ENGINEER AND
OWNER.
2. NEW 3/4" CONDUIT FOR SLC AND P-LINK WIRING.
CONDUIT SHALL ORIGINATE IN MAIN HOUSING
TELEPHONE ROOM AND TERMINATE IN CLASSROOM
BUILDING IN UTILITY ROOM 102A.
3. NEW 3/4" CONDUIT FOR SLC AND P-LINK WIRING.
CONDUIT SHALL ORIGINATE IN MAIN HOUSING
TELEPHONE ROOM AND TERMINATE IN RECREATION
BUILDING IN ELECTRICAL ROOM 107.
4. NEW 3/4" CONDUIT FOR SLC AND P-LINK WIRING.
CONDUIT SHALL ORIGINATE IN THE RECREATION
BUILDING AND TERMINATE IN THE PHYSICAL PLANT.
COORDINATE EXACT LOCATION OF TRENCHING
WITH OWNER PRIOR TO INSTALLATION. ALL
TRENCHING SHALL BE PROVIDED BY THE
CONTRACTOR.
5. EXISTING FIRE ALARM CONDUIT BETWEEN
TRANSPORTATION BUILDING AND MAIN HOUSING
UNIT TUNNEL. UTILIZE EXISTING CONDUIT FOR NEW
FIRE ALARM P-LINK WIRING BETWEEN THE NEW
FACP IN THE TRANSPORTATION BUILDING AND THE
NEW FIRE ALARM EQUIPMENT IN THE MAIN HOUSING
TELEPHONE ROOM.
6. NEW P-LINK WIRING ABOVE ACCESSIBLE CEILINGS.
7. NEW P-LINK WIRING INSTALLED IN TUNNEL TO NEW
FIRE ALARM EQUIPMENT IN TELEPHONE ROOM IN
MAIN HOUSING UNIT.
ELECTRICAL ROOM 115(N) FIRE ALARM CONTROL PANEL
(E) FIRE ALARM JUNCTION BOX
TELEPHONE ROOM N20 WITH
NEW FIRE ALARM EQUIPMENT
UTILITY ROOM 102A
ELECTRICAL ROOM 107
1 TUNNEL
LOBBY
ENTRANCE
BREAKROOM
102A
RESTROOM
102B
DATA
STORAGE
ROOM
SHAKEDOWN
JANITOR
OFFICE
MULTIPURPOSE
107A
RESTROOM
OFFICE
OFFICE
STORAGE
LOUNGE
LIBRARY
BARBER
111A
STORAGE
RESTROOM
ELEC.
CLASSROOM
CARDIO
ROOM
OFFICE
118A
STORAGE
STORAGE
REC ROOM
100A
CORRIDOR A
100B
CORRIDOR B
100C
CORRIDOR C
LOBBY
ENTRANCE
BREAKROOM
102A
RESTROOM
102B
DATA
STORAGE
ROOM
SHAKEDOWN
JANITOR
OFFICE
MULTIPURPOSE
107A
RESTROOM
OFFICE
OFFICE
STORAGE
LOUNGE
LIBRARY
BARBER
111A
STORAGE
RESTROOM
ELEC.
CLASSROOM
CARDIO
ROOM
OFFICE
118A
STORAGE
STORAGE
REC ROOM
100A
CORRIDOR A
100B
CORRIDOR B
100C
CORRIDOR C
FAA
FF
SA SA
IM
MM
MM
F
S
S
S
S
S
N0-1
N0-1-1
N0-1-2
N0-1-3
N0-1-4
N0-1-5
N0-1-6
N0-1-7
N0-1-8
N0-1-9
N0-1-10
N0-1-11
EOLR
N0-2 N0-3
N0-2-1
N0-2-2
N0-2-3
N0-2-4
N0-2-5
N0-2-6
N0-2-7
N0-2-8
N0-2-9
EOLR
N0-3-1
N0-3-2
N0-3-3
N0-3-4
N0-3-5
N0-3-6
N0-3-7
EOLR
FB
S0.01
S0.02 S0.03
S0.04
S0.05 S0.06
S0.12 S0.08
S0.09
S0.10
S0.11
J
RO
N0-4-1
N0-4-2
EOLR
S0.13
MM S0.07
(E) PANEL A1
(E) PANEL E
(N) FIRE ALARM CONTROL PANEL31
(E) PANEL A
(E) PANEL M
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.2
TRANSPORTATION
BUILDING FIRE
ALARM PLAN
GENERAL SHEET NOTES
SHEET KEY NOTES
SCALE:
ELECTRICAL PROPOSED
TRANSPORTATION BUILDING PLAN1 1/8" = 1'-0"
1. NEW FIRE ALARM CONTROL PANEL. REUSE EXISTING
120V BRANCH CIRCUIT PANEL E, CIRCUIT #8.
2. MOUNT NEW FIRE ALARM ANNUNCIATOR RECESSED
IN NEW WOOD SLAT WALL.
3. NEW DUAL PATH COMMUNICATOR (STACKED ABOVE
FACP). WIRE TO PANEL E, CIRCUIT #8.
4. NEW MONITORING MODULE FOR FIRE SPRINKLER
MONITORING OF TWO TAMPER SWITCHES AND ONE
FLOW SWITCH.
5. SURGE ARRESTERS FOR INCOMING FIRE ALARM
CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC
CIRCUIT.
6. PROVIDE 1/2" CONDUIT TO NEW DEVICE.
7. PROVIDE NEW RELAY FOR EXISTING FRONT ENTRY
GATE OVERRIDE.
8. PROVIDE 120V CIRCUIT FOR NEW FIRE BELL ON
PANEL B.
9. PROVIDE COVER GUARD ON PULL STATION.
10. PROVIDE WIREGUARD.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
1. THE MAJORITY OF NEW NOTIFICATION DEVICES ON
THIS SHEET SHALL BE INSTALLED IN THE SAME
LOCATION AS THE DEVICES WHICH WERE REMOVED
AS SHOWN ON THE DEMOLITION DRAWINGS.
2. NEW NOTIFICATION DEVICES SHOWN ON THIS
SHEET WHICH ARE NOT INSTALLED IN THE SAME
LOCATION AS REMOVED DEVICES SHALL BE
PROVIDED WITH A NEW BOX AND CONDUIT.
3. NAC WIRING SHALL BE PERMITTED TO BE INSTALLED
FREE AIR ABOVE THE ACCESSIBLE CEILINGS IN THIS
BUILDING.
(E) FIRE ALARM JUNCTION BOX
(E) PANEL B
E
C
W1 S.R.
W2 S.R.
W3 S.R.
W24 S.R.
W23 S.R.
W22 S.R.
E32 S.R.
E1 S.R.
N24
DINING
VISITATION
N1 A & O
N2 A & O
N3 A & O
N4 A & O
N20
TELEPHONE
ROOM
N21
STORAGE
N10
STORAGE
N9
COUNSEL
N8
OFFICE
N27
NURSE'S
STATION
N26
ITS
L13
L22
DRYING
N7
STORAGE
N34
OFFICE
N35
N22
STORAGE
N33
EXAM
N28
EXAM
N6
BOILER
N29
N30
N31
N5
K5
OFFICE K4
K2
DRY
STORAGE
L2
STORAGE
L24
LAUNDRY
K1
KITCHEN
K3
FREEZER
K6
WALK-IN
COOLER
L14
N36
CONTROL
L20
L1
LOBBY
100C
CORRIDOR C
N6
BOILER
100N
CORRIDOR N
100B
CORRIDOR B
100A
CORRIDOR A
100K
CORRIDOR K
K7
DISHWASHING
100D
CORRIDOR D 003
STORAGE
STORAGE
STORAGE
STORAGE
K8
S
S
S
S
S
S
S
S
H
H
S
S S
S
S
MMMM
S
S
15 15
F
F
15 15
SASA
S
S
S
S
S
S
FAA
F
H
S
N1-1
N1-1-1
N1-1-2
N1-1-3
N1-1-4
N1-1-5
N1-1-6
N1-1-7
N1-1-8 N1-1-9
N1-1-10
N1-1-11
N1-1-12 EOLR
N1-1-14 N1-2
N1-2-1
N1-2-2
N1-2-3
N1-2-4
N1-2-5N1-2-6
N1-2-7
N1-2-8
N1-2-9
EOLR
N1-3
N1-3-1
N1-3-2
N1-3-3
N1-3-4
N1-3-6 N1-3-7 N1-3-8
EOLR
N1-3-9
N1-4
N1-4-1
N1-4-2
N1-4-3
N1-4-4 N1-4-5
N1-4-6
N1-4-7
EOLR
N1-5-4
N1-1-13
S1.01 S1.02
S1.03
S1.04
S1.05
S1.06
S1.07
S1.08
S1.09
S1.10
S1.11
S1.12
S1.13
S1.14
S1.15
S1.16 S1.17 S1.18
S1.19
S1.20
S1.21
S1.22 S1.23 S1.24
S1.25
S1.26S1.27
S1.28
S1.29
S1.30
N1-6-1N1-6-2
N1-6-4
EOLR
D C
S2 S.R.
S3 S.R.
S4 S.R.
S5 S.R.
S6 S.R.
S7 S.R.
S8 S.R.
S9 S.R.
S10 S.R.
S11 S.R.
S12 S.R.
S23 S.R.
S22 S.R.
S21 S.R.
S20 S.R.
S19 S.R.
S18 S.R.
S17 S.R.
S16 S.R.
S15 S.R.
S14 S.R.
S13 S.R.
S24 S.R.
W1 L22
DRYING
L3
STORAGE
L7
JANITOR
L24
LAUNDRY
L19
CONFERENCE
100S
CORRIDOR S
100F
CORRIDOR F
STORAGE
STORAGE
L8
S1
RESTROOM
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
F
RO
N2-2
N1-5-2
N1-5-1
N2-2-1
N2-2-2
EOLR
N2-2-3
S
S
N1-3-5
N1-5
N1-5-4
EOLR
N1-5-3
S1.29
S1.31 S1.32
S1.33
S1.34
S1.35
S2.35 S2.34
S2.37 S2.38
S2.39 S2.40
S2.42 S2.43
S2.44 S2.45
S2.47 S2.48
S2.49 S2.50
S2.52 S2.53
S2.54 S2.55
S2.57 S2.58
S2.59 S2.60
S2.61 S2.65
S2.64
S2.62 S2.63
S2.56
S2.51
S2.46
S2.41
S2.36
N1-6-3
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.3
MAIN HOUSING
BUILDING FIRE
ALARM PLAN -
NORTH & SOUTH
GENERAL SHEET NOTES
SHEET KEY NOTES
SCALE:
MAIN HOUSING BUILDING
FIRE ALARM PLAN - NORTH1 1/8" = 1'-0"
MATCHLINEMATCHLINE
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
(E) POWER PANELS
1. TWO (2) NEW NAC POWER SUPPLIES. WIRE NAC
BOOSTER POWER SUPPLIES TO PANEL A1, CIRCUIT
#13 IN CONTROL ROOM N36.
2. SURGE ARRESTERS FOR INCOMING FIRE ALARM
CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC
CIRCUIT.
3. MONITORING MODULE FOR HOOD ANSUL SYSTEMS.
4. RELAY OUTPUT MODULE SHALL CONTROL THE
SMOKE EXHAUST FAN.
5. ALL SMOKE DETECTORS SHOWN WITHIN THIS AREA
SHALL BE REPLACED IN THE SAME LOCATION.
6. PROVIDE 1/2" CONDUIT.
7. NEW INITIATING DEVICE WHICH IS NOT
REPLACEMENT.
8. SMOKE DETECTORS IN THIS HATCHED AREA SHALL
BE PART OF THE AUTOMATIC SMOKE CONTROL
SYSTEM. THE SMOKE DETECTORS SHALL START THE
SMOKE EXHAUST FAN LOCATED ON THE ROOF OF
THIS CELL BLOCK.
9. ROUTE HOMERUN DOWN TO TUNNEL BELOW AND
THEN TO NAC PANEL IN ROOM N20.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
SCALE:
MAIN HOUSING BUILDING
FIRE ALARM PLAN - SOUTH2 1/8" = 1'-0"
MATCHLINEMATCHLINE
M
AT
C H
LI
N
E
M
AT
C H
LI
N
E
1. CIRCUIT LINES SHOWN ON THIS PLAN REPRESENT
PROPOSED CONDUIT ROUTE FOR BIDDING
PURPOSES. THE DESIGN INTENT IS TO MINIMIZE
CONCRETE WALL PENETRATIONS AND CONDUIT
LENGTH. CONTRACTOR MAY MODIFY THE CONDUIT
ROUTES SHOWN ON THIS PLAN FOR
CONSTRUCTABILITY AND EFFICIENCY. CONTRACTOR
MAY COMBINE NAC CIRCUIT HOMERUNS FOR
EFFICIENCY. CONTRACTOR SHALL AS-BUILT THE
ACTUAL CONDUIT ROUTES.
2. CONTRACTOR SHALL BE PERMITTED TO COMBINE
FIRE ALARM CIRCUIT HOME RUNS IN COMMON
CONDUITS IN THE NORTH CELL BLOCK CORRIDOR.
MAXIMUM CONDUIT SIZE SHALL BE 0.75".
3. CONDUIT HOMERUNS SHALL BE INSTALLED ON
CORRIDOR CEILINGS (NORTH CELL BLOCK) OR
SHALL TURN DOWN INTO THE TUNNELS. CONDUIT
HOMERUNS SHALL NOT BE PERMITTED TO BE
INSTALLED THROUGH CELLS AS THEY CREATE A
LIGATURE HAZARD.
4. ALL NEW FIRE ALARM SMOKE DETECTORS, HEAT
DETECTORS, AND NOTIFICATION DEVICES ON THIS
SHEET SHALL BE PROVIDED WITH WIRE GUARDS.
ALL PULL STATIONS WILL BE PROVIDED WITH COVER
GUARDS.
5. WHERE SMOKE DETECTORS ARE REPLACED, THE
EXISTING CONDUIT SHALL BE RE-USED. THE WIRING
SHALL BE REPLACED WITH NEW. THE AREAS WHERE
SMOKE DETECTORS ARE RE-USED IS GENERALLY IN
THE CELLS, CELL BLOCK CORRIDOR SKYLIGHTS,
CAFETERIA, KITCHEN, AND OTHER SMALLER AREAS
SHOWN ON THE DRAWINGS.
6. ALL NEW SMOKE DETECTORS WHICH ARE NOT
REPLACEMENT OF EXISTING SMOKE DETECTORS
SHALL BE PROVIDED WITH NEW BOX AND CONDUIT.
7. ALL NEW SURFACE WALL MOUNTED NOTIFICATION
DEVICES SHALL BE PROVIDED WITH A FINISHED
BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO
COVER THE 4-SQUARE BACK BOX.
8. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION
DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM
WIRING SHALL BE EXPOSED.
SKYLIGHT (TYP)
7 7
(E) POWER PANEL
F E
W1 S.R.
W2 S.R.
W3 S.R.
W4 S.R.
W5 S.R.
W6 S.R.
W7 S.R.
W8 S.R.
W9 S.R.
W10 S.R.
W11 S.R.
W12 S.R.
W24 S.R.
W23 S.R.
W22 S.R.
W21 S.R.
W20 S.R.
W19 S.R.
W18 S.R.
W17 S.R.
W16 S.R.
W15 S.R.
W14 S.R.
W13 S.R.
N34
OFFICE
N35
LOBBY
100W
CORRIDOR W
STORAGE
STORAGE
W25 S.R.
S S S S S S S S S S
S S S S S S S S S S
S S
S S
S S S S S S 1515 1515
F
S
RO
N2-1-1N2-1-2N2-1-3
N2-1-4
EOLR
S2.01
S2.02
S2.04
S2.05
S2.06
S2.07
S2.09
S2.10
S2.11
S2.12
S2.14
S2.15
S2.16
S2.17
S2.19
S2.20
S2.21
S2.22
S2.24
S2.25
S2.27
S2.28
S2.31
S2.33
S2.03S2.08S2.13S2.18S2.23S2.26
S2.30 S2.39
S2.32
N2-1
B A
E32 S.R.
E31 S.R.
E30 S.R.
E29 S.R.
E28 S.R.
E27 S.R.
E26 S.R.
E25 S.R.
E24 S.R.
E23 S.R.
E22 S.R.
E21 S.R.
E20 S.R.
E19 S.R.
E18 S.R.
E17 S.R.
E1 S.R.
E2 S.R.
E3 S.R.
E4 S.R.
E5 S.R.
E6 S.R.
E7 S.R.
E8 S.R.
E9 S.R.
E10 S.R.
E11 S.R.
E12 S.R.
E13 S.R.
E14 S.R.
E15 S.R.
E16 S.R.
100E
CORRIDOR E
STORAGE
STORAGE
STORAGE
K8
S S S S S S S S S S S S S S S S
S S S S S S S S S S S S S S S S
S S S S S S S S15
F
RO
N2-3
N2-3-1
N2-3-2
EOLR
N2-3-3
S2.66
S2.67
S2.69
S2.70
S2.72
S2.71
S2.73
S2.75
S2.77
S2.76
S2.79
S2.80
S2.82
S2.81
S2.84
S2.85
S2.87
S2.86
S2.88
S2.90
S2.92
S2.91
S2.93
S2.95
S2.97
S2.96
S2.98
S2.100
S2.102
S2.101
S2.107
S2.105
S2.106 S2.104
S2.103S2.99S2.94S2.89S2.83S2.78S2.74S2.68
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.4
MAIN HOUSING
BUILDING FIRE
ALARM PLAN - EAST
& WEST
GENERAL SHEET NOTES
SHEET KEY NOTES
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
M
AT
C H
LI
N
E M
AT
C
H
LI
N E
SCALE:
MAIN HOUSING BUILDING
FIRE ALARM PLAN - WEST1 1/8" = 1'-0"
SCALE:
MAIN HOUSING BUILDING
FIRE ALARM PLAN - EAST2 1/8" = 1'-0"
MATCHLINE
MATCHLINE
MATCHLINE
MATCHLINE
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
1. RELAY OUTPUT MODULE SHALL CONTROL THE
SMOKE EXHAUST FAN.
2. PROVIDE 1/2" CONDUIT.
3. SMOKE DETECTORS IN THIS HATCHED AREA SHALL
BE PART OF THE AUTOMATIC SMOKE CONTROL
SYSTEM. THE SMOKE DETECTORS SHALL START THE
SMOKE EXHAUST FAN LOCATED ON THE ROOF OF
THIS CELL BLOCK.
4. ROUTE HOMERUN DOWN TO TUNNEL BELOW AND
THEN TO NAC PANEL IN ROOM N20.
1. CIRCUIT LINES SHOWN ON THIS PLAN REPRESENT
PROPOSED CONDUIT ROUTE FOR BIDDING
PURPOSES. THE DESIGN INTENT IS TO MINIMIZE
CONCRETE WALL PENETRATIONS AND CONDUIT
LENGTH. CONTRACTOR MAY MODIFY THE CONDUIT
ROUTES SHOWN ON THIS PLAN FOR
CONSTRUCTABILITY AND EFFICIENCY. CONTRACTOR
MAY COMBINE NAC CIRCUIT HOMERUNS FOR
EFFICIENCY. CONTRACTOR SHALL AS-BUILT THE
ACTUAL CONDUIT ROUTES.
2. CONTRACTOR SHALL BE PERMITTED TO COMBINE
FIRE ALARM CIRCUIT HOME RUNS IN COMMON
CONDUITS IN THE NORTH CELL BLOCK CORRIDOR.
MAXIMUM CONDUIT SIZE SHALL BE 0.75".
3. CONDUIT HOMERUNS SHALL BE INSTALLED ON
CORRIDOR CEILINGS (NORTH CELL BLOCK) OR
SHALL TURN DOWN INTO THE TUNNELS. CONDUIT
HOMERUNS SHALL NOT BE PERMITTED TO BE
INSTALLED THROUGH CELLS AS THEY CREATE A
LIGATURE HAZARD.
4. ALL NEW FIRE ALARM SMOKE DETECTORS, HEAT
DETECTORS, AND NOTIFICATION DEVICES ON THIS
SHEET SHALL BE PROVIDED WITH WIRE GUARDS.
ALL PULL STATIONS WILL BE PROVIDED WITH COVER
GUARDS.
5. WHERE SMOKE DETECTORS ARE REPLACED, THE
EXISTING CONDUIT SHALL BE RE-USED. THE WIRING
SHALL BE REPLACED WITH NEW. THE AREAS WHERE
SMOKE DETECTORS ARE RE-USED IS GENERALLY IN
THE CELLS, CELL BLOCK CORRIDOR SKYLIGHTS,
CAFETERIA, KITCHEN, AND OTHER SMALLER AREAS
SHOWN ON THE DRAWINGS.
6. ALL NEW SMOKE DETECTORS WHICH ARE NOT
REPLACEMENT OF EXISTING SMOKE DETECTORS
SHALL BE PROVIDED WITH NEW BOX AND CONDUIT.
7. ALL NEW SURFACE WALL MOUNTED NOTIFICATION
DEVICES SHALL BE PROVIDED WITH A FINISHED
BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO
COVER THE 4-SQUARE BACK BOX.
8. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION
DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM
WIRING SHALL BE EXPOSED.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.4.1
MAIN HOUSING
BUILDING TUNNEL
FIRE ALARM PLAN
GENERAL SHEET NOTES
SCALE:
MAIN HOUSING BUILDING
FIRE ALARM PLAN - TUNNEL1 1/16" = 1'-0"
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
1. ALL FIRE ALARM CIRCUITS SHOWN ON THIS SHEET
SHALL BE IN FREE AIR IN THE TUNNEL, STRAPPED
TO EXISTING CABLE TRAY AND STRUT HANGERS.
UP TO ROOM N20
CIRCUIT N2-1, N2-2, N2-3
CIRCUIT N2-1
CIRCUIT N2-2
CIRCUIT N2-3
UP TO ROOM S2
UP TO ROOM W24
UP TO ROOM E32
TO RECREATION BUILDING
TO CLASSROOM BUILDING
PLINK
PLINK
TO TRANSPORTATION BUILDING
PLINK
ENTRANCE102
KITCHENETTE
102A
UTILITY
RESTROOM
RESTROOM
CLASSROOM
CLASSROOM
OFFICE
COPIER
OFFICE
OFFICE
OFFICE
100A
CORRIDOR A
100B
CORRIDOR B
ENTRANCE102
KITCHENETTE
102A
UTILITY
RESTROOM
RESTROOM
CLASSROOM
CLASSROOM
OFFICE
COPIER
OFFICE
OFFICE
OFFICE
100A
CORRIDOR A
100B
CORRIDOR B
110,WP
F
S S
S
S
F
30 30
MM
SA
SA
IM
S
FB
FAA
N3-1 N3-1-1
N3-1-2
N3-1-3
N3-1-4
N3-1-5
N3-1-6
N3-1-7
N3-1-8
N3-1-9
EOLR
N3-2-1 N3-2-2
N3-2-3 N3-2-4
N3-2-5N3-2-6
N3-2-7
EOLR
N3-2-8
N3-2
S3.01 S3.02
S3.03
S3.10 S3.05
S3.06
S3.07
S3.08
S3.09
TS
MM S3.04
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.5
CLASSROOM
BUILDING FIRE
ALARM PLAN
GENERAL SHEET NOTES
SHEET KEY NOTES
SCALE:
CLASSROOM BUILDING
FIRE ALARM PLAN1 3/16" = 1'-0"
(E) POWER PANELS
1. NEW NAC POWER SUPPLY N3. RE-USE EXISTING
120V BRANCH CIRCUIT FROM EXISTING PANEL IN
OFFICE 107.
2. NEW MONITORING MODULE FOR FIRE SPRINKLER
MONITORING. TAMPER SWITCH AND FLOW SWITCH.
3. SURGE ARRESTERS FOR INCOMING FIRE ALARM
CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC
CIRCUIT.
4. PROVIDE 120V CIRCUIT FOR NEW FIRE BELL FROM
EXISTING PANEL IN OFFICE 107. CONTRACTOR
SHALL AS-BUILT THE CIRCUIT NUMBER ON THE
DRAWINGS.
5. PROVIDE NEW TAMPER SWITCH IN OS&Y VALVE.
VALVE PROVIDED BY OWNER.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
1. ALL FIRE ALARM WIRING WITHIN THE CLASSROOM
SHALL BE INSTALLED IN FREE AIR ABOVE THE
ACCESSIBLE CEILING IN THIS BUILDING.
2. ALL NEW SURFACE WALL MOUNTED NOTIFICATION
DEVICES SHALL BE PROVIDED WITH A FINISHED
BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO
COVER THE 4-SQUARE BACK BOX.
UTILITY
BREAK ROOM
REC ROOM
REC ROOM
PROGRAMS
BARBER 104
OFFICE
ELEC.
SHOWERS
RESTROOM
C100
CORRIDOR
UTILITY
BREAK ROOM
REC ROOM
REC ROOM
PROGRAMS
BARBER 104
OFFICE
ELEC.
SHOWERS
RESTROOM
C100
CORRIDOR
UTILITY
BREAK ROOM
REC ROOM
REC ROOM
PROGRAMS
BARBER 104
OFFICE
ELEC.
SHOWERS
RESTROOM
C100
CORRIDOR
MM
S
MM
S
S S
S
S S
SS
S
F
F
F
15 110,WP
SASAIM
S
FB
N4-1-1
N4-1-2
N4-1-3
N4-1-4
N4-1-5
EOLR
N4-1 N4-2
N4-2-1
N4-2-2
N4-2-3
N4-2-4
N4-2-5
EOLR
N4-2-6
S4.01
S4.02
S4.03 S4.04
S4.05
S4.06
S4.07
S4.08
S4.09
S4.104.11
S4.12
S4.13 S4.14
S4.15S4.16S4.17
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.6
RECREATION
BUILDING FIRE
ALARM PLAN
SCALE:
RECREATION BUILDING
FIRE ALARM PLAN1 3/16" = 1'-0"
1. NEW NAC POWER SUPPLY N4. PROVIDE NEW 120V,
20A CIRCUIT. WIRE TO PANEL A, CIRCUIT #3. ASSUME
NEW 20A SINGLE POLE CIRCUIT BREAKER IS
REQUIRED.
2. NEW MONITORING MODULE FOR FIRE SPRINKLER
MONITORING OF TAMPER AND FLOW SWITCH.
3. SURGE ARRESTERS FOR INCOMING FIRE ALARM
CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC
CIRCUIT.
4. WIRE NEW FIRE ALARM BELL TO PANEL A, CIRCUIT
#5.
(E) SUB PANEL A1
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
TO PHYSICAL
PLANT BUILDING
(N) 12 X 12 X 6 NEMA 3R FIRE ALARM
JUNCTION BOX
(E) PANEL A
GENERAL SHEET NOTES
SHEET KEY NOTES
1. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION
DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM
WIRING SHALL BE EXPOSED.
2. ALL NEW SURFACE WALL MOUNTED NOTIFICATION
DEVICES SHALL BE PROVIDED WITH A FINISHED
BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO
COVER THE 4-SQUARE BACK BOX
3. ALL NEW FIRE ALARM SMOKE DETECTORS, HEAT
DETECTORS, AND NOTIFICATION DEVICES ON THIS
SHEET SHALL BE PROVIDED WITH WIRE GUARDS.
ALL PULL STATIONS WILL BE PROVIDED WITH COVER
GUARDS.
102A
STORAGE
MAINTENANCE
STORAGE
STORAGE
RESTROOM
STORAGE
C100
CORRIDOR
102A
STORAGE
MAINTENANCE
STORAGE
STORAGE
RESTROOM
STORAGE
C100
CORRIDOR
H
F
S
H H
H
H
H
H
SAIM
N4-3
N4-3-1
N4-3-2
N4-3-3
N4-3-4
EOLR
S4.18
S4.19
S4.20S4.21
S4.22
S4.23S4.24
S4.25
S4.26
S4.27
Drawing No.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.7
PHYSICAL PLANT
FIRE ALARM PLAN
GENERAL SHEET NOTES
SHEET KEY NOTES
SCALE:
PHYSICAL PLANT
FIRE ALARM PLAN1 3/16" = 1'-0"
1. SURGE ARRESTERS FOR INCOMING FIRE ALARM
CIRCUIT WIRING. LINE ISOLATION MODULE FOR SLC
CIRCUIT.
KEYPLANNORTH
OREGON STATE PENITENTIARY MINIMUM
FIRE ALARM UPGRADE DESIGN
NORTH
WEST EAST
SO
U
TH
TO RECREATION
BUILDING
(N) 12 X 12 X 6 NEMA 3R FIRE ALARM
JUNCTION BOX
1. ALL FIRE ALARM WIRING FOR NEW NOTIFICATION
DEVICES SHALL BE IN CONDUIT. NO FIRE ALARM
WIRING SHALL BE EXPOSED.
2. ALL NEW SURFACE WALL MOUNTED NOTIFICATION
DEVICES SHALL BE PROVIDED WITH A FINISHED
BOX/SKIRT ACCESSORY BY THE MANUFACTURER TO
COVER THE 4-SQUARE BACK BOX.
S
T A
T E
ST
SA
LE
M
O R
R ev
04/07/2025
6804Proj. No.
Date
D es cr ip ti o n
Checked
Drawn
Design
BP
JL
DL
O R
EG
O
N S
TA
TE
P
EN
IT
EN
TI
AR
Y M
IN
IM
U M
FI
R
E
AL
AR
M
U
PG
R
AD
E
Sa le m -5
-1 w w w .l an d is co n su lt in g .c o m
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
E2.8
PANEL SCHEDULES
| Sheets and Views |
| E0.0 Cover Sheet |
| E0.1 Abbreviations & Symbol Legend |
| E0.2 Fire Alarm Riser Diagram |
| E0.3 Sprinkler Coverage Plan |
| E0.4 Electrical Details |
| E1.1 Demolition Site Plan |
| E1.2 Transportation Building Demolition Plan |
| E1.3 Main Housing Building Demolition Plan - North & South |
| E1.4 Main Housing Building Demolition Plan - East & West |
| E1.5 Classroom Building Demolition Plan |
| E1.6 Recreation Building Demolition Plan |
| E2.1 Proposed Site Plan |
| E2.2 Transportation Building Fire Alarm Plan |
| E2.3 Main Housing Building Fire Alarm Plan - North & South |
| E2.4 Main Housing Building Fire Alarm Plan - East & West |
| E2.4.1 Main Housing Building Tunnel Fire Alarm Plan |
| E2.5 Classroom Building Fire Alarm Plan |
| E2.6 Recreation Building Fire Alarm Plan |
| E2.7 Physical Plant Fire Alarm Plan |
| E2.8 Panel Schedules |
| Ben Perry | |
| 2025-04-04T15:58:12-0700 | |
| DIGITALLY SIGNED | |
| Benjamin Earl Perry | |
| I attest to the accuracy and integrity of this document |