Warner Creek Correctional Facility Boiler Replacement
Solicitation number
S-29100-00013414
Issued by
Lake County, Oregon

About this file

This is Addendum 1 for the Oregon Department of Corrections' solicitation S-29100-00013414 for the Warner Creek Correctional Facility (WCCF) Boiler Replacement project. The addendum formally modifies the original Invitation to Bid (ITB) and includes a substitution request for a heat exchanger, specifically approving a Hexonic heat exchanger in place of the originally specified Alpha Laval model. The substitution request was submitted by Pac West Sales Inc. on 6/3/25 and was approved by Jesse Swanson on 6/11/25. The technical documentation provided includes detailed calculation sheets and technical specifications for the Hexonic AJFB-015-P150-29 heat exchanger, which is designed for water-to-water heat exchange with specific performance parameters.

The heat exchanger specifications indicate a heat load of 537,421.8 BTU/h, with water inlet temperatures of 165°F and 55°F, and outlet temperatures of 100°F and 162.70°F. The unit is designed with a heat transfer area of 50.3 ft², can handle maximum pressures up to 150 psi, and is constructed with stainless steel 2" external thread connections. The design meets ASME BPVC Section VIII, Division 1 standards, with plates made of 0.5 mm 316L material and NBR HT gaskets. The addendum requires bidders to sign and return the document by the bid closing date, with failure to do so potentially resulting in bid rejection.

View the file

Other files

File Type Posted
252301_WCCF-Boiler Replacement BID Set 2-24-25.pdf PDF
13414 SPECS.pdf PDF
1314 Plan Holders List~1.pdf PDF
13414 Bid Tab.pdf PDF
13414 ITB GTC SC.pdf PDF
7007 NOIA.pdf PDF
13414 ADDENDA 2.pdf PDF
25-022-PSC Bid Tab - filled.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Oregon

Department of Corrections Purchasing Section

3723 Fairview Industrial Dr SE Salem, OR 97302

(971)707-0238 Ryan.N.Kirtley@doc.oregon.gov

06/16/2025

ADDENDUM 1

For S-29100-00013414

WCCF Boiler Replacement

Below you will find Revisions, clarifications, deletions and/or additions to the bid specifications.

This addendum modifies the related Invitation to Bid only to the extent specifically indicated herein. All other areas not specifically mentioned or affected by this addendum shall remain in full force and effect.

This addendum shall be added to and become part of the original Invitation to Bid.

1. Revision; Substitution request approved, see attached.

This addendum represents a material change to the ITB and is required to be signed and returned by the Bid Closing Date and Time. Failure to do so may result in bid rejection.

Company Name: __________________________________________________________

Authorized Signature: ______________________________________________________

Date:_______________________________________

SUBSTITUTION REQUEST

TO: Ryan Kirtley

PROJECT: Warner Creek Correctional

SPECIFIED ITEM: Alpha Laval

Section 23 57 00 Page 1 Paragraph 2.1 Description: Water-to Water Heat Exchangers

PROPOSED SUBSTITUTION: Hexonic

Attached data includes product description, specifications, drawings, photographs, performance and test data adequate for evaluation of the request; applicable portions of the data are clearly identified.

Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its proper installation.

The undersigned certifies that the following paragraphs, unless modified by attachments, are correct:

1. The proposed substitution does not affect dimensions shown on Drawings.

2. The undersigned will pay for changes to the building design, including engineering design.

3. The proposed substitution will have no adverse affect on other trades, the construction schedule, or specified warranty requirements.

4. Maintenance and service parts will be locally available for the proposed substitution.

The undersigned further states that the function, appearance, and quality of the proposed substitution are equivalent or superior to the specified item.

Submitted by: Thomas Szklarz

Signature: ______________________

Firm: Pac West Sales Inc

Address: 11112 47th Avenue West

Mukilteo, WA 98275

Date: 6/3/25

Telephone: 425-493-9680_____

For use by the A/E

Approved Approved as noted

Not Approved Received too late

By: ______________________

Date: ______________________ Remarks: ______________________ jesse.swanson Text Box X jesse.swanson Text Box Jesse Swanson jesse.swanson Text Box 6/11/2025

HEAT EXCHANGERS CALCULATION SHEET

Project US.25.06.000025 Warner Creek Correctional Calculation US2506000041.001 New selection 1 Prepared 2025-06-03 Prepared by Alex Matrunich HEX type AJFB-015-P150-29 Catalog Number Total no. of units 1 No. of units in series/parallel 1 / 1

PROJECT DATA SHEET

INPUT DATA Side 1 Side 2 UNITS Heat load 537421,8 BTU/h

LMTD 14,4 °F

Min oversizing 0,00 % Fluid Water Water Inlet temperature 165,00 55,00 °F Outlet temperature 100,00 162,70 °F Mass flow 138,24 83,40 lb/min Inlet volume flow 16,99 10,00 USGal/min Outlet volume flow 16,70 10,24 USGal/min Max pressure drop 3,6 3,6 psi HEAT EXCHANGER Side 1 Side 2 UNITS Heat transfer area 50,3 ft² Fouling factor 0,00001468 ft²h°F/BTU OHTC clean 751,8 BTU/ft²h°F OHTC fouling 743,6 BTU/ft²h°F Oversize 1,1 % Calc. press. drop 1,7 0,7 psi Connections velocity 1,58 0,95 ft/s Internal velocity 0,51 0,30 ft/s Internal Reynolds No. 1490 703 Heat transfer coefficient 1381,8 877,9 BTU/ft²h°F

NTU 4,6 7,6

PHYSICAL PROPERTIES Side 1 Side 2 UNITS Fluid Water Water Ref. temperature 132,5 108,9 °F Density 61,44 61,79 lb/ft³ Heat capacity 1,00 1,00 BTU/lb°F Thermal conductivity 0,375 0,366 BTU/fth°F Dynamic viscosity 0,4964 0,6218 cP Prandtl No. 3,16 4,20

CAIRO

HEXONIC Inc., 34-18 Northern Blvd, FL 1, Long Island City, NY 11101, + 1 (347) 667-9045, + 1 (347) 849-1580, info.us@hexonic.com www.hexonic.com ver. 1.0.1.0, build 060525 Page 1 of 3 http://www.hexonic.com

HEAT EXCHANGERS TECHNICAL DATA SHEET

Project US.25.06.000025 Warner Creek Correctional Calculation US2506000041.001 New selection 1 Prepared 2025-06-03 Prepared by Alex Matrunich HEX type AJFB-015-P150-29 Catalog Number

CAIRO

HEXONIC Inc., 34-18 Northern Blvd, FL 1, Long Island City, NY 11101, + 1 (347) 667-9045, + 1 (347) 849-1580, info.us@hexonic.com www.hexonic.com ver. 1.0.1.0, build 060525 Page 2 of 3 http://www.hexonic.com

WORKING CONDITIONS

Max pressure 150 psi

Test pressure 195 psi

Max temperature 250 °F

Min temperature -4 °F

Fluid group 2

CONNECTION TYPES

4 x External thread 2" Stainless steel

CONNECTIONS LOCATION

Counter-current flow

K1 - side 1 inlet

K2 - side 2 outlet

K3 - side 2 inlet

K4 - side 1 outlet

DESIGN DATA

Side 1 flow arrangement 14 x 1 + 0 x 0

Side 2 flow arrangement 14 x 1 + 0 x 0

Total number of plates 29

Max no. of plates 51

Expansion capacity 76 %

Channel mixing H

Fluid volume 3,1 USGal

Weight 319,0 / 325,7 lb

Frame STD 150 psi Carbon steel

Frame colour RAL 2004

Plates 0,5 mm 250 psi 316L

Gaskets NBR HT

Design code ASME BPVC Sec.VIII, Div. 1, Ed. 2023

Inspection code ASME BPVC Sec.VIII, Div. 1, Ed. 2023, UM

DIMENSIONS

L 15,7 inch

L1 5,3 inch

Assembly Measurement 3,3 inch

CAIRO

HEXONIC Inc., 34-18 Northern Blvd, FL 1, Long Island City, NY 11101, + 1 (347) 667-9045, + 1 (347) 849-1580, info.us@hexonic.com www.hexonic.com ver. 1.0.1.0, build 060525 Page 3 of 3 http://www.hexonic.com

13414 ADDENDA 1
06/16/2025
ADDENDUM 1
Heat exchanger Sub request-1
Heat exchnager substitute.pdf
20250603_US2506000041_AJFB-015-29H_ Warner Creek Correctional (002).pdf