This is a Suspect Material Inventory Summary for NIST MD – 225 Technology building, prepared by Ayuda and printed on September 22, 2026. The document catalogues asbestos-containing materials (ACM), presumed asbestos-containing materials (PACM), and non-asbestos (ND) materials identified across 31 locations throughout the facility's attic mechanical spaces and stairwells.
The inventory spans multiple room types—primarily attic mechanical areas (MR-A03 through MR-M29, MR-C, MR-D, MR-E, MR-G, MR-J, MR-W) and two stairwell locations (ST-1-4 and ST-4-4)—with materials documented by SACM_ID codes and quantified in square feet (SF), linear feet (LF), or each (EA) units. Commonly identified ACM materials include black and gray pliable caulks associated with metal panel wall seams (CK03, CK04, CK06), dark brown pliable sealant on ribbed ducting (DS08), off-white soft firestop material (FSM03), duct pin mastic under fiberglass insulated ducting (MA05—frequently quantified at 2,200–3,000 SF per room), thin tar-impregnated coatings over fiberglass (MS01), and gray mud over fiberglass insulated large flanges (PF06). PACM materials documented include miscellaneous gaskets at pipe flanges and connections (GM01), grey mudded pipe fittings (PF03), and fire door insulation (FD01). Non-asbestos materials are also recorded, such as gray pliable sealant associated with duct seams (DS01) and white pliable sealant associated with newer fiberglass insulation (PS07). This comprehensive inventory provides the baseline material descriptions, locations, ACM determinations, and quantities necessary for asbestos abatement planning and regulatory compliance at the NIST facility.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1333ND26QNB190579 A004 SF30 Amendment 2026 09 23.pdf | ||
| 1333ND26QNB190579 A003 SF30 Amendment 2026 09 17.pdf | ||
| 1333ND26QNB190579 A002 SF30 Amendment 2026 09 16.pdf | ||
| 1333ND26QNB190579 A001 SF30 Amendment 2026 09 15.pdf | ||
| NB193000-26-02027 Sample Gnatt Chart.xlsx | XLSX spreadsheet | |
| 1333ND26QFB190579 Combined Synopsis Solicitation Notice (12) 2026 09 14.pdf | ||
| NB193000-26-02027 B225 Duct Cleaning Drawing Package.pdf | ||
| NB193000-26-02027 QASP 2026 09 01.pdf | ||
| 1333ND26QNB190579 SF1449 Solicitation 2026 09 14.pdf | ||
| 1333ND26QNB190579 PPQ_Template.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUSPECT MATERIAL INVENTORY SUMMARY
NIST MD - 225 Technology
Room_ID
MR-A03
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
84 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
240 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
26 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
4 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
On HV-1
- Other ACM
26 EA
DS10 Black, silicon like sealant associated with duct connections
Used at ACU-1 concrete foundation
- Other ND
84 EA
FSM03 Off-white, soft firestop material - Other ACM
20 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
19 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2200 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-1 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
28 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
14 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
8 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
144 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
1 EA
Printed 9/22/2026 11:13:21 AM
Room_ID
MR-A08
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
196 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
256 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
28 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
2 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
46 EA
FSM03 Off-white, soft firestop material - Other ACM
20 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
14 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
1800 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-3 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
34 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
6 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
70 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
1 EA
Printed 9/22/2026 11:13:21 AM
Room_ID
MR-A13
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
150 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
212 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
32 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
2 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
46 EA
FSM03 Off-white, soft firestop material - Other ACM
8 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
18 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2200 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-5, and return E-5 and E-7 units
- Other ACM
132 LF
PF03 Grey mudded pipe fittings - Other PACM
20 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
35 LF
PF05 Mudded fittings associated with roof drains - Other PACM
1 EA
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
6 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
20 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
65 EA
Printed 9/22/2026 11:13:22 AM
Room_ID
MR-A19
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
170 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams
Limited silicon replacement
- Other ACM
160 LF
DS01 Gray, pliable sealant associated with duct seams
Include metal seam patch on S side of ACU-7
- Other ND
34 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
1 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
33 EA
FSM03 Off-white, soft firestop material - Other ACM
19 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
12 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
1200 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside return E-7 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
34 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
12 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
24 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
70 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
3 EA
TI01 Thin, gray mud over fiberglass tank insulation - Other ACM
36 SF
Printed 9/22/2026 11:13:22 AM
Room_ID
MR-A24
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
170 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
200 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
16 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
3 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
18 EA
DS13 Red, pliable duct sealant - Other ND
6 EA
FSM03 Off-white, soft firestop material - Other ACM
18 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
10 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
1000 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-9 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
40 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
70 LF
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
10 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
80 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
4 EA
Printed 9/22/2026 11:13:23 AM
Room_ID
MR-A29
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
140 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
290 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
4 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
30 EA
FSM03 Off-white, soft firestop material - Other ACM
20 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
6 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
1600 SF
PF03 Grey mudded pipe fittings - Other PACM
40 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
26 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
4 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
12 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
90 EA
Room_ID
MR-C
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
11 104 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
66 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
132 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
162 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams
Under silicon and replacement caulking
- Other ACM
108 LF
CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams
Ducting and ACU unit
- Other ACM
90 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
6 EA
DS10 Black, silicon like sealant associated with duct connections - Other ND
2 EA
DS13 Red, pliable duct sealant - Other ND
1 EA
FSM01 Red, pliable fire stop material in wall penetrations - Other ND
3 EA
FSM03 Off-white, soft firestop material
Under cloth cover
- Other ACM
2 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
24 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
200 SF
PF03 Grey mudded pipe fittings - Other PACM
50 EA
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
26 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
12 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
34 EA
TI01 Thin, gray mud over fiberglass tank insulation
At tank ends
- Other ACM
18 SF
Room_ID
MR-D03
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS08 Dark brown, pliable sealant associated with ribbed ducting
Some connections are painted
- Other ACM
22 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
50 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
5 EA
Room_ID
MR-D08
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
6 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting
Some connections are painted
- Other ACM
20 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
70 SF
DS13 Red, pliable duct sealant - Other ND
8 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
5 EA
Printed 9/22/2026 11:13:24 AM
Room_ID
MR-D13
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
6 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
6 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
60 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
5 EA
Room_ID
MR-D19
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
27 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
70 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
4 EA
Printed 9/22/2026 11:13:25 AM
Room_ID
MR-D24
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
6 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
20 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
7 EA
Room_ID
MR-D29
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams
NW corner of unit E-11
- Other ACM
5 LF
DS11 White pliable sealant associated with duct wrap repair - Other ND
60 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
8 EA
Printed 9/22/2026 11:13:26 AM
Room_ID
MR-E
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
20 104 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
220 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
440 SF
DS01 Gray, pliable sealant associated with duct seams - Other ND
6 LF
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
13 EA
DS13 Red, pliable duct sealant - Other ND
8 EA
FSM01 Red, pliable fire stop material in wall penetrations - Other ND
2 EA
FSM03 Off-white, soft firestop material - Other ACM
5 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
12 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
820 SF
OT01 Black, hard tar-like fire retardant on back of metal wall panels
Stored on floor
- Other ACM
100 SF
PF03 Grey mudded pipe fittings - Other PACM
40 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
16 LF
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
32 EA
Printed 9/22/2026 11:13:26 AM
Room_ID
MR-G03
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 29 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
18 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
8 EA
DS12 Dark gray pliable sealant associated with duct seams - Other ND
30 EA
DS13 Red, pliable duct sealant - Other ND
54 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
3000 SF
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
13 EA
Room_ID
MR-G08
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 29 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
19 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting
On ribbed ducting crossing center of grid
- Other ACM
3 EA
DS12 Dark gray pliable sealant associated with duct seams - Other ND
7 EA
DS13 Red, pliable duct sealant - Other ND
60 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
3000 SF
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
18 EA
Printed 9/22/2026 11:13:27 AM
Room_ID
MR-G13
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 29 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
18 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
6 EA
DS13 Red, pliable duct sealant - Other ND
36 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
3000 SF
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
27 EA
Room_ID
MR-G19
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 29 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
19 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
3 EA
DS12 Dark gray pliable sealant associated with duct seams - Other ND
12 EA
DS13 Red, pliable duct sealant - Other ND
65 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
3000 SF
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
18 EA
Printed 9/22/2026 11:13:28 AM
Room_ID
MR-G24
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 29 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
10 LF
DS02 White, thin, pliable duct sealant associated with silver wrap fiberglass duct insulation
- Other ND
120 SF
DS07 Dark olive green, pliable sealant associated with duct seams - Other ND
2 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
16 EA
DS12 Dark gray pliable sealant associated with duct seams - Other ND
8 EA
DS13 Red, pliable duct sealant - Other ND
80 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
3000 SF
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
18 EA
Printed 9/22/2026 11:13:29 AM
Room_ID
MR-G29
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 29 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
28 LF
DS07 Dark olive green, pliable sealant associated with duct seams - Other ND
2 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
9 EA
DS12 Dark gray pliable sealant associated with duct seams - Other ND
6 EA
DS13 Red, pliable duct sealant - Other ND
120 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
3000 SF
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
On flanges only
- Other ND
36 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
9 EA
Room_ID
MR-J03
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
57 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
60 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
13 EA
Printed 9/22/2026 11:13:29 AM
Room_ID
MR-J08
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS01 Gray, pliable sealant associated with duct seams - Other ND
8 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
6 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
50 SF
DS13 Red, pliable duct sealant - Other ND
8 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
13 EA
Room_ID
MR-J13
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS08 Dark brown, pliable sealant associated with ribbed ducting
Some connections are painted
- Other ACM
9 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
85 SF
DS13 Red, pliable duct sealant - Other ND
7 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
12 EA
Printed 9/22/2026 11:13:30 AM
Room_ID
MR-J19
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS04 Tan, brittle sealant on round ducting associated with heating ducting - Other ACM
5 EA
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
25 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
60 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
4 EA
Room_ID
MR-J24
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS08 Dark brown, pliable sealant associated with ribbed ducting
Some connections are painted
- Other ACM
24 EA
DS11 White pliable sealant associated with duct wrap repair - Other ND
60 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
20 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
4 EA
Printed 9/22/2026 11:13:31 AM
Room_ID
MR-J29
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 13 13
SACM_ID Material Description Location(s) ACM Determination
QTY
DS11 White pliable sealant associated with duct wrap repair - Other ND
60 SF
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2500 SF
PF03 Grey mudded pipe fittings - Other PACM
140 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
25 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
5 EA
Printed 9/22/2026 11:13:31 AM
Room_ID
MR-M03
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
168 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
232 LF
CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams
Limited material associated with VU-1 ducting
- Other ACM
6 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
26 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
4 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
23 EA
FSM03 Off-white, soft firestop material - Other ACM
19 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
11 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2200 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-2 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
23 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
6 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
6 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
130 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
1 EA
Printed 9/22/2026 11:13:32 AM
Room_ID
MR-M08
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 11
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
112 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams
Assumed under limited silicon caulking patch
- Other ACM
216 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
33 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
2 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
32 EA
FSM03 Off-white, soft firestop material - Other ACM
22 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
10 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2200 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-4 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
44 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
6 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
10 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
130 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
3 EA
TI02 Gray mud over fiberglass insulated tank ends - Other PACM
100 SF
Room_ID
MR-M13
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
112 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams
Assumed under silicon caulking patch
- Other ACM
154 LF
CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams
Patch on N side near NW corner
- Other ACM
6 LF
DS01 Gray, pliable sealant associated with duct seams - Other ND
26 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
1 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
38 EA
FSM03 Off-white, soft firestop material - Other ACM
20 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
8 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2200 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-6 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
32 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
12 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
50 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
1 EA
Room_ID
MR-M19
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
60 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
1 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
14 EA
FSM03 Off-white, soft firestop material - Other ACM
10 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
15 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2400 SF
PF03 Grey mudded pipe fittings - Other PACM
24 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF05 Mudded fittings associated with roof drains - Other PACM
1 EA
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
12 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation
Primarily associated with large flanges at W end
- Other ND
16 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
20 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
1 EA
TI01 Thin, gray mud over fiberglass tank insulation - Other ACM
12 SF
Printed 9/22/2026 11:13:33 AM
Room_ID
MR-M24
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
112 LF
CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM
252 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
2 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
22 EA
FSM03 Off-white, soft firestop material - Other ACM
16 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
8 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
1800 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-8 and return E-8 units
- Other ACM
88 LF
PF03 Grey mudded pipe fittings - Other PACM
36 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
4 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND
6 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
80 EA
Printed 9/22/2026 11:13:33 AM
Room_ID
MR-M29
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
56 23 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
168 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
336 SF
CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND
60 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
1 EA
DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams
- Other ACM
14 EA
FSM03 Off-white, soft firestop material - Other ACM
10 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
15 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
2400 SF
MS01 Thin, tar impregnated coating over fiberglass
Inside supply S-12 unit
- Other ACM
44 LF
PF03 Grey mudded pipe fittings - Other PACM
24 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
80 LF
PF05 Mudded fittings associated with roof drains - Other PACM
1 EA
PF06 Gray mud over fiberglass insulated large flanges - Other ACM
12 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation
Primarily associated with large flanges at W end
- Other ND
16 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
20 EA
PS08 White, pliable sealant associated with access hatches in ducting - Other ND
1 EA
TI01 Thin, gray mud over fiberglass tank insulation - Other ACM
12 SF
Printed 9/22/2026 11:13:34 AM
Room_ID
MR-W
Description
Attic Mechanical
North/South Wall Length
East/West Wall Length Height
12 104 13
SACM_ID Material Description Location(s) ACM Determination
QTY
CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM
120 SF
CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM
240 SF
DS01 Gray, pliable sealant associated with duct seams - Other ND
9 LF
DS07 Dark olive green, pliable sealant associated with duct seams - Other ND
13 LF
DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM
4 EA
FD01 Fire door insulation - Other PACM
1 EA
FSM03 Off-white, soft firestop material - Other ACM
1 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
22 EA
MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM
500 SF
PF03 Grey mudded pipe fittings - Other PACM
34 EA
PF04 Large, mudded fittings associated with ribbed ducting - Other ACM
6 LF
PF06 Gray mud over fiberglass insulated large flanges
Includes one large "T" flange at center
- Other ACM
6 EA
PS06 Off-white sealant associated with cloth wrapped fiberglass insulation
Includes large flanges at N end
- Other ND
18 EA
PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units
- Other ND
16 EA
Printed 9/22/2026 11:13:34 AM
Room_ID
ST-1-4
Description
Stairwell East, 4th Level
North/South Wall Length
East/West Wall Length Height
9 22 22
SACM_ID Material Description Location(s) ACM Determination
QTY
CK01 White, brittle caulk associated with stair rail and wall joints - Other ACM
36 LF
FD01 Fire door insulation - Other PACM
1 EA
Room_ID
ST-4-4
Description
Stairwell West, 4th Level (top landing only)
North/South Wall Length
East/West Wall Length Height
9 8 14
SACM_ID Material Description Location(s) ACM Determination
QTY
FD01 Fire door insulation - Other PACM
1 EA
GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM
2 EA
Printed 9/22/2026 11:13:35 AM