B225 ASBESTOS_MATERIAL INVENTORY REPORT.pdf

PDF 410 KB Posted

Attached to
B225 Duct Cleaning Services Federal contract opportunity
Solicitation number
1333ND26QNB190579
Issued by
Department of Commerce National Institute of Standards and Technology

About this file

This is a Suspect Material Inventory Summary for NIST MD – 225 Technology building, prepared by Ayuda and printed on September 22, 2026. The document catalogues asbestos-containing materials (ACM), presumed asbestos-containing materials (PACM), and non-asbestos (ND) materials identified across 31 locations throughout the facility's attic mechanical spaces and stairwells.

The inventory spans multiple room types—primarily attic mechanical areas (MR-A03 through MR-M29, MR-C, MR-D, MR-E, MR-G, MR-J, MR-W) and two stairwell locations (ST-1-4 and ST-4-4)—with materials documented by SACM_ID codes and quantified in square feet (SF), linear feet (LF), or each (EA) units. Commonly identified ACM materials include black and gray pliable caulks associated with metal panel wall seams (CK03, CK04, CK06), dark brown pliable sealant on ribbed ducting (DS08), off-white soft firestop material (FSM03), duct pin mastic under fiberglass insulated ducting (MA05—frequently quantified at 2,200–3,000 SF per room), thin tar-impregnated coatings over fiberglass (MS01), and gray mud over fiberglass insulated large flanges (PF06). PACM materials documented include miscellaneous gaskets at pipe flanges and connections (GM01), grey mudded pipe fittings (PF03), and fire door insulation (FD01). Non-asbestos materials are also recorded, such as gray pliable sealant associated with duct seams (DS01) and white pliable sealant associated with newer fiberglass insulation (PS07). This comprehensive inventory provides the baseline material descriptions, locations, ACM determinations, and quantities necessary for asbestos abatement planning and regulatory compliance at the NIST facility.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUSPECT MATERIAL INVENTORY SUMMARY

NIST MD - 225 Technology

Room_ID

MR-A03

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

84 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

240 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

26 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

4 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

On HV-1

- Other ACM

26 EA

DS10 Black, silicon like sealant associated with duct connections

Used at ACU-1 concrete foundation

- Other ND

84 EA

FSM03 Off-white, soft firestop material - Other ACM

20 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

19 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2200 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-1 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

28 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

14 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

8 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

144 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

1 EA

Printed 9/22/2026 11:13:21 AM

Room_ID

MR-A08

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

196 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

256 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

28 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

2 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

46 EA

FSM03 Off-white, soft firestop material - Other ACM

20 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

14 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

1800 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-3 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

34 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

6 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

70 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

1 EA

Printed 9/22/2026 11:13:21 AM

Room_ID

MR-A13

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

150 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

212 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

32 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

2 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

46 EA

FSM03 Off-white, soft firestop material - Other ACM

8 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

18 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2200 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-5, and return E-5 and E-7 units

- Other ACM

132 LF

PF03 Grey mudded pipe fittings - Other PACM

20 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

35 LF

PF05 Mudded fittings associated with roof drains - Other PACM

1 EA

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

6 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

20 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

65 EA

Printed 9/22/2026 11:13:22 AM

Room_ID

MR-A19

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

170 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams

Limited silicon replacement

- Other ACM

160 LF

DS01 Gray, pliable sealant associated with duct seams

Include metal seam patch on S side of ACU-7

- Other ND

34 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

1 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

33 EA

FSM03 Off-white, soft firestop material - Other ACM

19 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

12 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

1200 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside return E-7 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

34 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

12 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

24 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

70 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

3 EA

TI01 Thin, gray mud over fiberglass tank insulation - Other ACM

36 SF

Printed 9/22/2026 11:13:22 AM

Room_ID

MR-A24

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

170 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

200 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

16 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

3 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

18 EA

DS13 Red, pliable duct sealant - Other ND

6 EA

FSM03 Off-white, soft firestop material - Other ACM

18 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

10 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

1000 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-9 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

40 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

70 LF

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

10 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

80 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

4 EA

Printed 9/22/2026 11:13:23 AM

Room_ID

MR-A29

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

140 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

290 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

4 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

30 EA

FSM03 Off-white, soft firestop material - Other ACM

20 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

6 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

1600 SF

PF03 Grey mudded pipe fittings - Other PACM

40 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

26 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

4 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

12 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

90 EA

Room_ID

MR-C

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

11 104 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

66 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

132 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

162 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams

Under silicon and replacement caulking

- Other ACM

108 LF

CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams

Ducting and ACU unit

- Other ACM

90 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

6 EA

DS10 Black, silicon like sealant associated with duct connections - Other ND

2 EA

DS13 Red, pliable duct sealant - Other ND

1 EA

FSM01 Red, pliable fire stop material in wall penetrations - Other ND

3 EA

FSM03 Off-white, soft firestop material

Under cloth cover

- Other ACM

2 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

24 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

200 SF

PF03 Grey mudded pipe fittings - Other PACM

50 EA

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

26 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

12 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

34 EA

TI01 Thin, gray mud over fiberglass tank insulation

At tank ends

- Other ACM

18 SF

Room_ID

MR-D03

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS08 Dark brown, pliable sealant associated with ribbed ducting

Some connections are painted

- Other ACM

22 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

50 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

5 EA

Room_ID

MR-D08

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

6 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting

Some connections are painted

- Other ACM

20 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

70 SF

DS13 Red, pliable duct sealant - Other ND

8 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

5 EA

Printed 9/22/2026 11:13:24 AM

Room_ID

MR-D13

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

6 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

6 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

60 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

5 EA

Room_ID

MR-D19

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

27 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

70 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

4 EA

Printed 9/22/2026 11:13:25 AM

Room_ID

MR-D24

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

6 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

20 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

7 EA

Room_ID

MR-D29

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams

NW corner of unit E-11

- Other ACM

5 LF

DS11 White pliable sealant associated with duct wrap repair - Other ND

60 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

8 EA

Printed 9/22/2026 11:13:26 AM

Room_ID

MR-E

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

20 104 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

220 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

440 SF

DS01 Gray, pliable sealant associated with duct seams - Other ND

6 LF

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

13 EA

DS13 Red, pliable duct sealant - Other ND

8 EA

FSM01 Red, pliable fire stop material in wall penetrations - Other ND

2 EA

FSM03 Off-white, soft firestop material - Other ACM

5 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

12 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

820 SF

OT01 Black, hard tar-like fire retardant on back of metal wall panels

Stored on floor

- Other ACM

100 SF

PF03 Grey mudded pipe fittings - Other PACM

40 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

16 LF

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

32 EA

Printed 9/22/2026 11:13:26 AM

Room_ID

MR-G03

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 29 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

18 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

8 EA

DS12 Dark gray pliable sealant associated with duct seams - Other ND

30 EA

DS13 Red, pliable duct sealant - Other ND

54 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

3000 SF

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

13 EA

Room_ID

MR-G08

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 29 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

19 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting

On ribbed ducting crossing center of grid

- Other ACM

3 EA

DS12 Dark gray pliable sealant associated with duct seams - Other ND

7 EA

DS13 Red, pliable duct sealant - Other ND

60 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

3000 SF

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

18 EA

Printed 9/22/2026 11:13:27 AM

Room_ID

MR-G13

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 29 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

18 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

6 EA

DS13 Red, pliable duct sealant - Other ND

36 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

3000 SF

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

27 EA

Room_ID

MR-G19

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 29 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

19 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

3 EA

DS12 Dark gray pliable sealant associated with duct seams - Other ND

12 EA

DS13 Red, pliable duct sealant - Other ND

65 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

3000 SF

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

18 EA

Printed 9/22/2026 11:13:28 AM

Room_ID

MR-G24

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 29 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

10 LF

DS02 White, thin, pliable duct sealant associated with silver wrap fiberglass duct insulation

- Other ND

120 SF

DS07 Dark olive green, pliable sealant associated with duct seams - Other ND

2 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

16 EA

DS12 Dark gray pliable sealant associated with duct seams - Other ND

8 EA

DS13 Red, pliable duct sealant - Other ND

80 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

3000 SF

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

18 EA

Printed 9/22/2026 11:13:29 AM

Room_ID

MR-G29

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 29 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

28 LF

DS07 Dark olive green, pliable sealant associated with duct seams - Other ND

2 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

9 EA

DS12 Dark gray pliable sealant associated with duct seams - Other ND

6 EA

DS13 Red, pliable duct sealant - Other ND

120 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

3000 SF

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

On flanges only

- Other ND

36 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

9 EA

Room_ID

MR-J03

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

57 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

60 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

13 EA

Printed 9/22/2026 11:13:29 AM

Room_ID

MR-J08

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS01 Gray, pliable sealant associated with duct seams - Other ND

8 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

6 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

50 SF

DS13 Red, pliable duct sealant - Other ND

8 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

13 EA

Room_ID

MR-J13

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS08 Dark brown, pliable sealant associated with ribbed ducting

Some connections are painted

- Other ACM

9 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

85 SF

DS13 Red, pliable duct sealant - Other ND

7 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

12 EA

Printed 9/22/2026 11:13:30 AM

Room_ID

MR-J19

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS04 Tan, brittle sealant on round ducting associated with heating ducting - Other ACM

5 EA

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

25 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

60 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

4 EA

Room_ID

MR-J24

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS08 Dark brown, pliable sealant associated with ribbed ducting

Some connections are painted

- Other ACM

24 EA

DS11 White pliable sealant associated with duct wrap repair - Other ND

60 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

20 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

4 EA

Printed 9/22/2026 11:13:31 AM

Room_ID

MR-J29

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 13 13

SACM_ID Material Description Location(s) ACM Determination

QTY

DS11 White pliable sealant associated with duct wrap repair - Other ND

60 SF

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2500 SF

PF03 Grey mudded pipe fittings - Other PACM

140 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

25 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

5 EA

Printed 9/22/2026 11:13:31 AM

Room_ID

MR-M03

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

168 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

232 LF

CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams

Limited material associated with VU-1 ducting

- Other ACM

6 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

26 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

4 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

23 EA

FSM03 Off-white, soft firestop material - Other ACM

19 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

11 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2200 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-2 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

23 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

6 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

6 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

130 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

1 EA

Printed 9/22/2026 11:13:32 AM

Room_ID

MR-M08

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 11

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

112 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams

Assumed under limited silicon caulking patch

- Other ACM

216 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

33 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

2 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

32 EA

FSM03 Off-white, soft firestop material - Other ACM

22 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

10 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2200 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-4 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

44 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

6 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

10 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

130 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

3 EA

TI02 Gray mud over fiberglass insulated tank ends - Other PACM

100 SF

Room_ID

MR-M13

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

112 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams

Assumed under silicon caulking patch

- Other ACM

154 LF

CK07 Off-white, brittle caulk associated with duct and ACU metal wall seams

Patch on N side near NW corner

- Other ACM

6 LF

DS01 Gray, pliable sealant associated with duct seams - Other ND

26 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

1 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

38 EA

FSM03 Off-white, soft firestop material - Other ACM

20 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

8 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2200 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-6 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

32 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

12 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

50 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

1 EA

Room_ID

MR-M19

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

60 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

1 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

14 EA

FSM03 Off-white, soft firestop material - Other ACM

10 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

15 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2400 SF

PF03 Grey mudded pipe fittings - Other PACM

24 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF05 Mudded fittings associated with roof drains - Other PACM

1 EA

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

12 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation

Primarily associated with large flanges at W end

- Other ND

16 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

20 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

1 EA

TI01 Thin, gray mud over fiberglass tank insulation - Other ACM

12 SF

Printed 9/22/2026 11:13:33 AM

Room_ID

MR-M24

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

112 LF

CK06 Gray, pliable caulk associated with ACU metal wall seams - Other ACM

252 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

2 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

22 EA

FSM03 Off-white, soft firestop material - Other ACM

16 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

8 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

1800 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-8 and return E-8 units

- Other ACM

88 LF

PF03 Grey mudded pipe fittings - Other PACM

36 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

4 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation - Other ND

6 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

80 EA

Printed 9/22/2026 11:13:33 AM

Room_ID

MR-M29

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

56 23 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

168 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

336 SF

CK05 Brown, pliable caulk associated with ACU and concrete pad floor seams - Other ND

60 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

1 EA

DS09 Brown (painted tan), pliable sealant associated with ribbed ducting seams

- Other ACM

14 EA

FSM03 Off-white, soft firestop material - Other ACM

10 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

15 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

2400 SF

MS01 Thin, tar impregnated coating over fiberglass

Inside supply S-12 unit

- Other ACM

44 LF

PF03 Grey mudded pipe fittings - Other PACM

24 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

80 LF

PF05 Mudded fittings associated with roof drains - Other PACM

1 EA

PF06 Gray mud over fiberglass insulated large flanges - Other ACM

12 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation

Primarily associated with large flanges at W end

- Other ND

16 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

20 EA

PS08 White, pliable sealant associated with access hatches in ducting - Other ND

1 EA

TI01 Thin, gray mud over fiberglass tank insulation - Other ACM

12 SF

Printed 9/22/2026 11:13:34 AM

Room_ID

MR-W

Description

Attic Mechanical

North/South Wall Length

East/West Wall Length Height

12 104 13

SACM_ID Material Description Location(s) ACM Determination

QTY

CK03 Black, pliable caulk associated with lower metal panel wall seams - Other ACM

120 SF

CK04 Gray, pliable caulk associated with upper metal panel wall seams - Other ACM

240 SF

DS01 Gray, pliable sealant associated with duct seams - Other ND

9 LF

DS07 Dark olive green, pliable sealant associated with duct seams - Other ND

13 LF

DS08 Dark brown, pliable sealant associated with ribbed ducting - Other ACM

4 EA

FD01 Fire door insulation - Other PACM

1 EA

FSM03 Off-white, soft firestop material - Other ACM

1 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

22 EA

MA05 Duct pin mastic under fiberglass insulated ducting - Other ACM

500 SF

PF03 Grey mudded pipe fittings - Other PACM

34 EA

PF04 Large, mudded fittings associated with ribbed ducting - Other ACM

6 LF

PF06 Gray mud over fiberglass insulated large flanges

Includes one large "T" flange at center

- Other ACM

6 EA

PS06 Off-white sealant associated with cloth wrapped fiberglass insulation

Includes large flanges at N end

- Other ND

18 EA

PS07 White, pliable sealant associated with newer fiberglass insulation on ACU units

- Other ND

16 EA

Printed 9/22/2026 11:13:34 AM

Room_ID

ST-1-4

Description

Stairwell East, 4th Level

North/South Wall Length

East/West Wall Length Height

9 22 22

SACM_ID Material Description Location(s) ACM Determination

QTY

CK01 White, brittle caulk associated with stair rail and wall joints - Other ACM

36 LF

FD01 Fire door insulation - Other PACM

1 EA

Room_ID

ST-4-4

Description

Stairwell West, 4th Level (top landing only)

North/South Wall Length

East/West Wall Length Height

9 8 14

SACM_ID Material Description Location(s) ACM Determination

QTY

FD01 Fire door insulation - Other PACM

1 EA

GM01 Miscellaneous gaskets associated with pipe flanges and connections - Other PACM

2 EA

Printed 9/22/2026 11:13:35 AM

File details come from the government source that posted it. Updated .