Lead Based Paint Testing Summary Bldg 101.pdf
PDF 105 KB Posted
- Attached to
- Building 101 HVAC Tower Renovation Federal contract opportunity
- Solicitation number
- 1333ND24RNB190036
About this file
This is a lead-based paint XRF testing summary report for Building 101 at NIST Gaithersburg, documenting 105 test locations throughout the facility. The report details testing results from various building components including walls, doors, mechanical equipment, structural elements, and fixtures across multiple rooms and areas including mechanical rooms, offices, restrooms, corridors, and exterior locations.
Of the 105 tests conducted, five locations tested positive for lead-based paint: a concrete support column in mechanical room A050 (1.5 mg/cm²), an orange metal air handler in room A049 (5.7 mg/cm²), a ceramic wall in restroom E002 (1.3 mg/cm²), a metal door in the library E011 (1.3 mg/cm²), and an orange metal elevator door frame in mechanical room A150 (1.3 mg/cm²). The report notes the condition of each tested component as either "Intact" or "Damaged" and provides specific location details including room numbers, wall orientations, and component descriptions. This testing appears to be supporting documentation for the planned HVAC tower renovation project.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lead Based Paint Testing Summary NIST Gaithersberg Building 101
Test # Room ID Color Substrate Component Test Loc. XRF Result Classification Comments
1 A031 Baseboard 0.5 GymBlue Metal South wall Negative
Condition: Damaged
2 A025 Door 0 GymBlue Metal East wall Negative
Condition: Damaged
3 A025 Locker Door 0 GymTan Metal Other Negative
Condition: Damaged
4 A050 Air Handler Exterior 0.1 Mech RoomWhite Metal Other Negative
Condition: Damaged
5 A050 Support Column 1.5 Mech RoomOrange Concrete Other Positive
Condition: Damaged
6 A050 CMU 0.1 Mech RoomTan Concrete North wall Negative
Condition: Intact
7 A050 Air Handler Duct 0.2 Mech RoomWhite Metal Other Negative
Condition: Damaged
8 E004 Fire Suppression System 0.1 Mech RoomRed Metal Other Negative
Condition: Intact
9 E004 Wall 0.3 Mech RoomTan Concrete South wall Negative
Condition: Intact
10 E004 Air Handler Duct 0.1 Mech RoomWhite Metal Other Negative
Condition: Damaged
11 A050 Handrail 0.1 Mech RoomBeige Metal Other Negative
Condition: Damaged
12 A049 Equip. Platform Frame 0.6 Mech RoomWhite Metal Other Negative
Condition: Damaged
13 A049 Air Handler 5.7 Mech RoomOrange Metal Other Positive
Condition: Intact
14 A049 Framing 0.2 Mech RoomBlue Metal West wall Negative
Condition: Damaged
15 E001 Wall 0 Mech RoomWhite Drywall West wall Negative
Condition: Intact
16 E002 Wall 1.3 RestroomWhite Ceramic South wall Positive
Condition: Intact
17 E001 Ceiling 0.1 LobbyWhite Fiberboard Ceiling Negative
Condition: Intact
18 E011 Wall 0.1 LibraryWhite Plaster East wall Negative
Condition: Intact
19 E011 Door 1.3 LibraryGray Metal North wall Positive
Condition: Intact
20 A041 Chair Rail 0 Office AreaWhite Wood West wall Negative
Condition: Intact
21 CO A 0 Wall 0.1 CorridorWhite Concrete North wall Negative
Condition: Intact
22 A026 Wall 0.1 OfficeWhite Metal West wall Negative
Condition: Intact
23 CO B B Ladder 0.1 CorridorWhite Metal Other Negative
Condition: Intact
24 C028 Wall 0.1 OfficeWhite Drywall East wall Negative
Condition: Intact
25 C030 Baseboard 0.4 Corridor o/s C030Gray Metal East wall Negative
Condition: Intact
26 C032 Door Frame 0.6 Corridor o/s C028Tan Metal East wall Negative
Condition: Intact
27 C005 Wall 0.1 Locker RoomTan Brick West wall Negative
Condition: Intact
28 D001 Equip. Platform 0.6 Mech RoomGray Metal Other Negative
Condition: Intact
29 D001 Equip Frame 0.3 Mech RoomWhite Metal Other Negative
Condition: Damaged
30 D001 Duct Work 0.1 Mech RoomWhite Metal Other Negative
Condition: Damaged
31 D001 Air Handling Unit 0.1 Mech RoomWhite Metal Other Negative
Condition: Damaged
32 D001 Wall 0.2 Mech RoomBrown Concrete East wall Negative
Condition: Intact
33 D001 Door 0.7 Mech RoomGray Metal West wall Negative
Condition: Damaged
34 CO B A Wall 0.2 Corridor o/s of B33Tan Concrete East wall Negative
Condition: Intact
35 B100 Wall 0.4 LobbyTan Brick South wall Negative
Condition: Intact
36 Corridor Wall 0.2 O/S B101Lacquer Wood West wall Negative
Condition: Intact
37 B107 Wall 0.2 Meeting RoomWhite Plaster South wall Negative
Condition: Intact
38 B109 Door Frame 0.5 ClosetTan Metal North wall Negative
Condition: Intact
39 D100 Baseboard 0.2 OfficeTan Metal North wall Negative
Condition: Intact
40 D200 Door 0 AuditoriumLacquer Wood North wall Negative
Condition: Intact
41 D108 Wall 0 BackstageTan Concrete North wall Negative
42 D108 Stair tread cap 0.4 BackstageTan Metal Other Negative
Condition: Damaged
43 D100 Stage Floor 0.4 AuditoriumLacquer Wood Floor Negative
Condition: Intact
44 Green Wall 0.2 AuditoriumLacquer Wood East wall Negative
Condition: Intact
45 C100 Heat Register 0.1 Meeting RoomTan Metal South wall Negative
Condition: Intact
46 C100 Wall 0.1 Meeting RoomTan Concrete East wall Negative
Condition: Intact
47 C102 Toilet 0 RestroomWhite Ceramic Other Negative
Condition: Intact
48 C115 Wall 0 Kitchen AreaTan Brick East wall Negative
Condition: Intact
49 C115 Door 0 Kitchen AreaOrange Metal East wall Negative
Condition: Intact
50 CO A 1 Wall 0.1 Across from ElevatorTan Metal North wall Negative
Condition: Intact
51 A150 Column 0.3 Mech Room.Brown Concrete Other Negative
Condition: Damaged
52 A150 Air Handling Unit 0.1 Mech Room.White Metal Other Negative
Condition: Damaged
53 A150 Conduit 0.3 Mech Room.White Metal Other Negative
Condition: Damaged
54 A150 Wall 0.3 Mech Room.Beige Concrete North wall Negative
Condition: Damaged
55 A150 Elevator Door Frame 1.3 Mech Room.Orange Metal North wall Positive
Condition: Intact
56 E104 Wall 0.1 Conf. RoomWhite Concrete North wall Negative
Condition: Intact
57 E107 Heat Register 0.2 MuseumWhite Metal West wall Negative
Condition: Intact
58 E114 Underside of Spiral Stair 0.1 LibraryWhite Concrete Other Negative
Condition: Intact
59 E114 Wall 0.2 LibraryTan Metal West wall Negative
Condition: Intact
60 E114 Wall 0.1 StairsWhite Drywall East wall Negative
Condition: Intact
61 ST E 1 Stair Stringer 0.6 StairsGreen Metal Other Negative
Condition: Intact
62 ST E 1 Stair Riser 0.6 StairsGreen Metal Other Negative
Condition: Intact
51 A150 Column 0.3 Mech51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 Mech51 A150 Column 0.3 Mech Room.
Condition: Damaged
52 A150 Air52 A150 Air52 A150 AirWhite Metal Other Negative52 A150 Air52 A150 AirWhite Metal Other Negative52 A150 Air52 A150 AirWhite Metal Other Negative52 A150 Air Handling Unit 0.1 MechWhite Metal Other NegativeUnit 0.1 MechUnit 0.1 MechWhite Metal Other NegativeUnit 0.1 MechUnit 0.1 MechWhite Metal Other NegativeUnit 0.1 MechUnit 0.1 MechUnit 0.1 Mech Room.
Condition: Damaged
53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 Mech Room.
Condition: Damaged
54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mechwall Negative54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mechwall Negative54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mechwall Negative54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mech Room.
Condition: Damaged
55 A150 Elevator55 A150 Elevator55 A150 ElevatorOrange Metal North55 A150 Elevator55 A150 ElevatorOrange Metal North55 A150 Elevator55 A150 ElevatorOrange Metal North55 A150 Elevator Door Frame 1.3 MechFrame 1.3 MechOrange Metal NorthFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 Mech Room.
63 ST E 1 Hand Rail 0.1 StairsLacquer Wood Other Negative
Condition: Intact
64 ST E 1 Underside of Stair 0.4 StairsGreen Metal Other Negative
Condition: Intact
65 CO A 2 Wall 0.1 CorridorTan Metal North wall Negative
Condition: Intact
66 A212 Ceiling 0 RestroomWhite Plaster Ceiling Negative
Condition: Intact
67 A312 Door 0.2 RestroomGray Metal North wall Negative
Condition: Intact
68 A320 Door Frame 0.5 Copy RoomTan Metal North wall Negative
Condition: Intact
69 CO A 4 Stairwell Door 0.4 CorridorOrange Metal South wall Negative
Condition: Intact
70 A413 Wall 0.1 OfficeTan Metal East wall Negative
Condition: Intact
71 ST 5 5 Pipe 0.2 Stairwell Fire Suppression
Red Metal Other Negative
Condition: Intact
72 ST 5 5 Stair Stringer 0.2 StairwellWhite Metal Other Negative
Condition: Intact
73 A600 Baseboard 0.2 OfficeTan Metal West wall Negative
Condition: Intact
74 A622 Cabinet 0.2 Copy RoomLacquer Wood East wall Negative
Condition: Intact
75 CO A 7 Wall 0.4 CorridorGray Plaster South wall Negative
Condition: Intact
76 A716 Ceiling 0.3 KitchenWhite Drywall Ceiling Negative
Condition: Intact
77 CO A 9 Wall 0.1 CorridorTan Metal East wall Negative
Condition: Intact
78 A912 Wall 1.3 RestroomWhite Ceramic West wall Positive
Condition: Intact
79 A808 Wall 0 ClosetTan Concrete North wall Negative
Condition: Intact
80 A811 Door 1.3 OfficeTan Metal South wall Negative
Condition: Intact
81 CO A 10 Door 0.4 CorridorTan Metal North wall Negative
Condition: Intact
82 A1011 Ceiling tile 0.3 OfficeWhite Fiber Board Ceiling Negative
Condition: Intact
83 A1016 Ceiling 0 Copy RoomWhite Drywall Ceiling Negative
84 A1112 Door 0.1 RestroomLacquer Wood North wall Negative
Condition: Intact
85 A1117 Wall 0.1 OfficeWhite Drywall West wall Negative
Condition: Intact
86 A1122 Baseboard 0.3 Copy RoomWhite Metal East wall Negative
Condition: Intact
87 S Exterior Guardrail 0.2 Dock AreaYellow Metal Other Negative
Condition: Damaged
88 S Exterior Handrail 0.4 Dock AreaBlack Metal Other Negative
Condition: Intact
89 S Exterior Garage Door Frame 0.2 Dock AreaBlue Metal South wall Negative
Condition: Intact
90 S Exterior Double Doors 0.1 Dock AreaBlue Metal South wall Negative
Condition: Intact
91 S Exterior Column Guard 0.2 Dock AreaBlue Metal Other Negative
Condition: Damaged
92 S Exterior Column 0.4 Health Unit EntranceWhite Concrete Other Negative
Condition: Damaged
93 S Exterior Fire Pipe 0.1 LibraryRed Metal South wall Negative
Condition: Intact
94 N Exterior Walkway Column 0.3 Center WalkwayWhite Concrete Other Negative
Condition: Intact
95 ST 5 12 Wall 0.4Tan Concrete West wall Negative
Condition: Damaged
96 ST 5 12 Ceiling 0.1Tan Concrete Ceiling Negative
Condition: Damaged
97 ST 5 12 Door 0.2Black Metal North wall Negative
Condition: Intact
98 ST 5 12 Door Frame 0.3Black Metal North wall Negative
Condition: Intact
99 1200 Floor 0.2Gray Concrete Floor Negative
Condition: Damaged
100 1200 Ducting 0.1White Metal Other Negative
Condition: Damaged
101 1200 1? Wall 0.1Brown Concrete East wall Negative
Condition: Intact
102 1301 Door 0.3Green Metal East wall Negative
Condition: Intact
103 1301 Door Frame 0.5Green Metal East wall Negative
Condition: Intact
104 1301 Air Handling Unit 9.7 Orange underneathWhite Metal Other Positive
Condition: Damaged
105 1301 Wall Header 0.1White Concrete West wall Negative