Lead Based Paint Testing Summary Bldg 101.pdf

PDF 105 KB Posted

Attached to
Building 101 HVAC Tower Renovation Federal contract opportunity
Solicitation number
1333ND24RNB190036
Issued by
Department of Commerce National Institute of Standards and Technology

About this file

This is a lead-based paint XRF testing summary report for Building 101 at NIST Gaithersburg, documenting 105 test locations throughout the facility. The report details testing results from various building components including walls, doors, mechanical equipment, structural elements, and fixtures across multiple rooms and areas including mechanical rooms, offices, restrooms, corridors, and exterior locations.

Of the 105 tests conducted, five locations tested positive for lead-based paint: a concrete support column in mechanical room A050 (1.5 mg/cm²), an orange metal air handler in room A049 (5.7 mg/cm²), a ceramic wall in restroom E002 (1.3 mg/cm²), a metal door in the library E011 (1.3 mg/cm²), and an orange metal elevator door frame in mechanical room A150 (1.3 mg/cm²). The report notes the condition of each tested component as either "Intact" or "Damaged" and provides specific location details including room numbers, wall orientations, and component descriptions. This testing appears to be supporting documentation for the planned HVAC tower renovation project.

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Lead Based Paint Testing Summary NIST Gaithersberg Building 101

Test # Room ID Color Substrate Component Test Loc. XRF Result Classification Comments

1 A031 Baseboard 0.5 GymBlue Metal South wall Negative

Condition: Damaged

2 A025 Door 0 GymBlue Metal East wall Negative

Condition: Damaged

3 A025 Locker Door 0 GymTan Metal Other Negative

Condition: Damaged

4 A050 Air Handler Exterior 0.1 Mech RoomWhite Metal Other Negative

Condition: Damaged

5 A050 Support Column 1.5 Mech RoomOrange Concrete Other Positive

Condition: Damaged

6 A050 CMU 0.1 Mech RoomTan Concrete North wall Negative

Condition: Intact

7 A050 Air Handler Duct 0.2 Mech RoomWhite Metal Other Negative

Condition: Damaged

8 E004 Fire Suppression System 0.1 Mech RoomRed Metal Other Negative

Condition: Intact

9 E004 Wall 0.3 Mech RoomTan Concrete South wall Negative

Condition: Intact

10 E004 Air Handler Duct 0.1 Mech RoomWhite Metal Other Negative

Condition: Damaged

11 A050 Handrail 0.1 Mech RoomBeige Metal Other Negative

Condition: Damaged

12 A049 Equip. Platform Frame 0.6 Mech RoomWhite Metal Other Negative

Condition: Damaged

13 A049 Air Handler 5.7 Mech RoomOrange Metal Other Positive

Condition: Intact

14 A049 Framing 0.2 Mech RoomBlue Metal West wall Negative

Condition: Damaged

15 E001 Wall 0 Mech RoomWhite Drywall West wall Negative

Condition: Intact

16 E002 Wall 1.3 RestroomWhite Ceramic South wall Positive

Condition: Intact

17 E001 Ceiling 0.1 LobbyWhite Fiberboard Ceiling Negative

Condition: Intact

18 E011 Wall 0.1 LibraryWhite Plaster East wall Negative

Condition: Intact

19 E011 Door 1.3 LibraryGray Metal North wall Positive

Condition: Intact

20 A041 Chair Rail 0 Office AreaWhite Wood West wall Negative

Condition: Intact

21 CO A 0 Wall 0.1 CorridorWhite Concrete North wall Negative

Condition: Intact

22 A026 Wall 0.1 OfficeWhite Metal West wall Negative

Condition: Intact

23 CO B B Ladder 0.1 CorridorWhite Metal Other Negative

Condition: Intact

24 C028 Wall 0.1 OfficeWhite Drywall East wall Negative

Condition: Intact

25 C030 Baseboard 0.4 Corridor o/s C030Gray Metal East wall Negative

Condition: Intact

26 C032 Door Frame 0.6 Corridor o/s C028Tan Metal East wall Negative

Condition: Intact

27 C005 Wall 0.1 Locker RoomTan Brick West wall Negative

Condition: Intact

28 D001 Equip. Platform 0.6 Mech RoomGray Metal Other Negative

Condition: Intact

29 D001 Equip Frame 0.3 Mech RoomWhite Metal Other Negative

Condition: Damaged

30 D001 Duct Work 0.1 Mech RoomWhite Metal Other Negative

Condition: Damaged

31 D001 Air Handling Unit 0.1 Mech RoomWhite Metal Other Negative

Condition: Damaged

32 D001 Wall 0.2 Mech RoomBrown Concrete East wall Negative

Condition: Intact

33 D001 Door 0.7 Mech RoomGray Metal West wall Negative

Condition: Damaged

34 CO B A Wall 0.2 Corridor o/s of B33Tan Concrete East wall Negative

Condition: Intact

35 B100 Wall 0.4 LobbyTan Brick South wall Negative

Condition: Intact

36 Corridor Wall 0.2 O/S B101Lacquer Wood West wall Negative

Condition: Intact

37 B107 Wall 0.2 Meeting RoomWhite Plaster South wall Negative

Condition: Intact

38 B109 Door Frame 0.5 ClosetTan Metal North wall Negative

Condition: Intact

39 D100 Baseboard 0.2 OfficeTan Metal North wall Negative

Condition: Intact

40 D200 Door 0 AuditoriumLacquer Wood North wall Negative

Condition: Intact

41 D108 Wall 0 BackstageTan Concrete North wall Negative

42 D108 Stair tread cap 0.4 BackstageTan Metal Other Negative

Condition: Damaged

43 D100 Stage Floor 0.4 AuditoriumLacquer Wood Floor Negative

Condition: Intact

44 Green Wall 0.2 AuditoriumLacquer Wood East wall Negative

Condition: Intact

45 C100 Heat Register 0.1 Meeting RoomTan Metal South wall Negative

Condition: Intact

46 C100 Wall 0.1 Meeting RoomTan Concrete East wall Negative

Condition: Intact

47 C102 Toilet 0 RestroomWhite Ceramic Other Negative

Condition: Intact

48 C115 Wall 0 Kitchen AreaTan Brick East wall Negative

Condition: Intact

49 C115 Door 0 Kitchen AreaOrange Metal East wall Negative

Condition: Intact

50 CO A 1 Wall 0.1 Across from ElevatorTan Metal North wall Negative

Condition: Intact

51 A150 Column 0.3 Mech Room.Brown Concrete Other Negative

Condition: Damaged

52 A150 Air Handling Unit 0.1 Mech Room.White Metal Other Negative

Condition: Damaged

53 A150 Conduit 0.3 Mech Room.White Metal Other Negative

Condition: Damaged

54 A150 Wall 0.3 Mech Room.Beige Concrete North wall Negative

Condition: Damaged

55 A150 Elevator Door Frame 1.3 Mech Room.Orange Metal North wall Positive

Condition: Intact

56 E104 Wall 0.1 Conf. RoomWhite Concrete North wall Negative

Condition: Intact

57 E107 Heat Register 0.2 MuseumWhite Metal West wall Negative

Condition: Intact

58 E114 Underside of Spiral Stair 0.1 LibraryWhite Concrete Other Negative

Condition: Intact

59 E114 Wall 0.2 LibraryTan Metal West wall Negative

Condition: Intact

60 E114 Wall 0.1 StairsWhite Drywall East wall Negative

Condition: Intact

61 ST E 1 Stair Stringer 0.6 StairsGreen Metal Other Negative

Condition: Intact

62 ST E 1 Stair Riser 0.6 StairsGreen Metal Other Negative

Condition: Intact

51 A150 Column 0.3 Mech51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 MechBrown Concrete Other Negative51 A150 Column 0.3 Mech51 A150 Column 0.3 Mech51 A150 Column 0.3 Mech Room.

Condition: Damaged

52 A150 Air52 A150 Air52 A150 AirWhite Metal Other Negative52 A150 Air52 A150 AirWhite Metal Other Negative52 A150 Air52 A150 AirWhite Metal Other Negative52 A150 Air Handling Unit 0.1 MechWhite Metal Other NegativeUnit 0.1 MechUnit 0.1 MechWhite Metal Other NegativeUnit 0.1 MechUnit 0.1 MechWhite Metal Other NegativeUnit 0.1 MechUnit 0.1 MechUnit 0.1 Mech Room.

Condition: Damaged

53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 MechWhite Metal Other Negative53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 Mech53 A150 Conduit 0.3 Mech Room.

Condition: Damaged

54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 MechBeige Concrete North54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mechwall Negative54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mechwall Negative54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mechwall Negative54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mech54 A150 Wall 0.3 Mech Room.

Condition: Damaged

55 A150 Elevator55 A150 Elevator55 A150 ElevatorOrange Metal North55 A150 Elevator55 A150 ElevatorOrange Metal North55 A150 Elevator55 A150 ElevatorOrange Metal North55 A150 Elevator Door Frame 1.3 MechFrame 1.3 MechOrange Metal NorthFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 MechFrame 1.3 Mech Room.

63 ST E 1 Hand Rail 0.1 StairsLacquer Wood Other Negative

Condition: Intact

64 ST E 1 Underside of Stair 0.4 StairsGreen Metal Other Negative

Condition: Intact

65 CO A 2 Wall 0.1 CorridorTan Metal North wall Negative

Condition: Intact

66 A212 Ceiling 0 RestroomWhite Plaster Ceiling Negative

Condition: Intact

67 A312 Door 0.2 RestroomGray Metal North wall Negative

Condition: Intact

68 A320 Door Frame 0.5 Copy RoomTan Metal North wall Negative

Condition: Intact

69 CO A 4 Stairwell Door 0.4 CorridorOrange Metal South wall Negative

Condition: Intact

70 A413 Wall 0.1 OfficeTan Metal East wall Negative

Condition: Intact

71 ST 5 5 Pipe 0.2 Stairwell Fire Suppression

Red Metal Other Negative

Condition: Intact

72 ST 5 5 Stair Stringer 0.2 StairwellWhite Metal Other Negative

Condition: Intact

73 A600 Baseboard 0.2 OfficeTan Metal West wall Negative

Condition: Intact

74 A622 Cabinet 0.2 Copy RoomLacquer Wood East wall Negative

Condition: Intact

75 CO A 7 Wall 0.4 CorridorGray Plaster South wall Negative

Condition: Intact

76 A716 Ceiling 0.3 KitchenWhite Drywall Ceiling Negative

Condition: Intact

77 CO A 9 Wall 0.1 CorridorTan Metal East wall Negative

Condition: Intact

78 A912 Wall 1.3 RestroomWhite Ceramic West wall Positive

Condition: Intact

79 A808 Wall 0 ClosetTan Concrete North wall Negative

Condition: Intact

80 A811 Door 1.3 OfficeTan Metal South wall Negative

Condition: Intact

81 CO A 10 Door 0.4 CorridorTan Metal North wall Negative

Condition: Intact

82 A1011 Ceiling tile 0.3 OfficeWhite Fiber Board Ceiling Negative

Condition: Intact

83 A1016 Ceiling 0 Copy RoomWhite Drywall Ceiling Negative

84 A1112 Door 0.1 RestroomLacquer Wood North wall Negative

Condition: Intact

85 A1117 Wall 0.1 OfficeWhite Drywall West wall Negative

Condition: Intact

86 A1122 Baseboard 0.3 Copy RoomWhite Metal East wall Negative

Condition: Intact

87 S Exterior Guardrail 0.2 Dock AreaYellow Metal Other Negative

Condition: Damaged

88 S Exterior Handrail 0.4 Dock AreaBlack Metal Other Negative

Condition: Intact

89 S Exterior Garage Door Frame 0.2 Dock AreaBlue Metal South wall Negative

Condition: Intact

90 S Exterior Double Doors 0.1 Dock AreaBlue Metal South wall Negative

Condition: Intact

91 S Exterior Column Guard 0.2 Dock AreaBlue Metal Other Negative

Condition: Damaged

92 S Exterior Column 0.4 Health Unit EntranceWhite Concrete Other Negative

Condition: Damaged

93 S Exterior Fire Pipe 0.1 LibraryRed Metal South wall Negative

Condition: Intact

94 N Exterior Walkway Column 0.3 Center WalkwayWhite Concrete Other Negative

Condition: Intact

95 ST 5 12 Wall 0.4Tan Concrete West wall Negative

Condition: Damaged

96 ST 5 12 Ceiling 0.1Tan Concrete Ceiling Negative

Condition: Damaged

97 ST 5 12 Door 0.2Black Metal North wall Negative

Condition: Intact

98 ST 5 12 Door Frame 0.3Black Metal North wall Negative

Condition: Intact

99 1200 Floor 0.2Gray Concrete Floor Negative

Condition: Damaged

100 1200 Ducting 0.1White Metal Other Negative

Condition: Damaged

101 1200 1? Wall 0.1Brown Concrete East wall Negative

Condition: Intact

102 1301 Door 0.3Green Metal East wall Negative

Condition: Intact

103 1301 Door Frame 0.5Green Metal East wall Negative

Condition: Intact

104 1301 Air Handling Unit 9.7 Orange underneathWhite Metal Other Positive

Condition: Damaged

105 1301 Wall Header 0.1White Concrete West wall Negative

File details come from the government source that posted it. Updated .