Asbestos Inventory Summary w Photos.pdf
PDF 1 MB Posted
- Attached to
- Building 101 HVAC Tower Renovation Federal contract opportunity
- Solicitation number
- 1333ND24RNB190036
About this file
This is an asbestos inventory summary report with photographs for NIST MD - Administration building, documenting various asbestos-containing materials (ACM), presumed ACM (PACM), and non-detect (ND) materials.
The inventory details eight distinct materials found across rooms A150A, A150B, and A150C, including: gray pliable caulk (800 LF total, non-friable Category II), duct insulation (60 SF total, friable), brown pin mastic (5,100 SF total, non-friable Category II), gray latex duct sealant (300 SF total, non-friable Category II), cloth HVAC vibration collars (10 EA total, friable), light gray mudded pipe fittings (140 EA total, friable), electrical insulators in switch cabinets (2 EA total, non-friable Category II), and fire doors (1 EA total, non-friable Category II). Each material is documented with photographs and specific location details. The report is dated February 20, 2025, and appears to be supporting documentation for a HVAC tower renovation project at NIST's Building 101.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Friability
ASBESTOS INVENTORY SUMMARY
GROUPED BY MATERIAL AND SORTED BY LOCATION
NIST MD - Administration
Asbestos Determination ACM
CK04 Gray, pliable caulk associated with ACU base and seams on unit Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
Same material as CK14. Sample CK04-05 is associated with CK14. See CK14 for additional details
- Other 300 NF IILFA150A
- Other 200 NF IILFA150B
- Other 300 NF IILFA150C
800 LFTOTAL QUANTITY
DI01 Duct insulation associated with vertical ducts in mezzanine mechanical room Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
Labeled as ACM. Insulated portion located around duct hatch doors
- Other 20 FSFA150A
- Other 20 FSFA150B
- Other 20 FSFA150C
60 SFTOTAL QUANTITY
Legend: F=Friable, NF I = Category I Non-Friable, NFII = Category II Non-Friable. N=North, E=East, W=West, S=South, SF=Square Feet, LF=Linear Feet, EA=Each
Printed 2/20/2025 5:02:07 PM
MA09 Brown pin mastic associated with duct fiberglass insulation (on bare duct under insulation) Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
Only observed at exposed bare ducting
- Other 1800 NF IISFA150A
- Other 1500 NF IISFA150B
- Other 1800 NF IISFA150C
5100 SFTOTAL QUANTITY
Legend: F=Friable, NF I = Category I Non-Friable, NFII = Category II Non-Friable. N=North, E=East, W=West, S=South, SF=Square Feet, LF=Linear Feet, EA=Each
Asbestos Determination ND
DS04 Gray, latex like duct sealant Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
- Other 100 NF IISFA150A
Assumed inside corners and seams of ACU A6- Other 100 NF IISFA150B
Assumed inside corners and seams of ACU units- Other 100 NF IISFA150C
300 SFTOTAL QUANTITY
FSM02 Light red (pink hue) firestop material Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
- Other 2 NF IIEAA150A
- Other 1 NF IIEAA150C
3 EATOTAL QUANTITY
Legend: F=Friable, NF I = Category I Non-Friable, NFII = Category II Non-Friable. N=North, E=East, W=West, S=South, SF=Square Feet, LF=Linear Feet, EA=Each
HVC01 Cloth HVAC vibration collars
Location Quantity FriabilityRoom ID Comments
- Other 5 FEAA150A
- Other 5 FEAA150C
10 EATOTAL QUANTITY
PF01 Light gray mudded pipe fittings Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
Based on NIST policy all fittings presumed ACM. Mud may only be present at edges of fittings (see photo)
- Other 20 FEAA150A
- Other 20 FEAA150B
- Other 100 FEAA150C
140 EATOTAL QUANTITY
Legend: F=Friable, NF I = Category I Non-Friable, NFII = Category II Non-Friable. N=North, E=East, W=West, S=South, SF=Square Feet, LF=Linear Feet, EA=Each
Asbestos Determination PACM
EI01 Electrical insulators (cement board, phenolic panels, etc.)
Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
Assumed inside electrical switch cabinets
1 switchboard- Other 1 NF IIEAA150A
1 switchboard- Other 1 NF IIEAA150C
2 EATOTAL QUANTITY
FD01 Fire doors Material DescriptionSACM ID
Location Quantity FriabilityRoom ID Comments
Doors with potential fire rating insulation inside the doors
- Other 1 NF IIEAA150A
1 EATOTAL QUANTITY
Legend: F=Friable, NF I = Category I Non-Friable, NFII = Category II Non-Friable. N=North, E=East, W=West, S=South, SF=Square Feet, LF=Linear Feet, EA=Each
GM01 Miscellaneous gasket materials associated with larger pipe connections
Location Quantity FriabilityRoom ID Comments
Placeholder for all assumed gasket materials
- Other 30 NF IEAA150A
- Other 20 NF IEAA150C
50 EATOTAL QUANTITY
Legend: F=Friable, NF I = Category I Non-Friable, NFII = Category II Non-Friable. N=North, E=East, W=West, S=South, SF=Square Feet, LF=Linear Feet, EA=Each
File details come from the government source that posted it. Updated .