RFI Official Responses - 3.pdf
PDF 105 KB Posted
- Solicitation number
- 127EAW21R0040
About this file
This document contains responses to a Request for Information (RFI) related to solicitation 127EAW21R0040 for the Sourgrass Water System Rehabilitation Project. The Forest Service responded to one RFI, clarifying that SikaTop Seal 107 coating will be spray applied to the tank interior at a minimum thickness of 40 mils in two coats. Specifications were revised accordingly. The solicitation is for a project with an estimated value between $250,000 and $500,000 and has a total small business set aside. All RFIs must be submitted by July 1, 2021 and an organized pre-proposal site visit will be held.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sourgrass Water System Rehabilitation Project Specifications.pdf | ||
| A00003.pdf | ||
| RFI Official Responses - 2.pdf | ||
| A00002 - RFIs.pdf | ||
| RFI Official Responses - 1.pdf | ||
| A00001 - Site Visit Notes.pdf | ||
| 4. Fire Plan.pdf | ||
| 127EAW21R0040.pdf | ||
| 6. RFI Form.docx | DOCX document | |
| 5. Davis-Bacon Act WD # CA20210018.pdf | ||
| 3. Sourgrass Specifications.pdf | ||
| 1. Statement of Work.pdf | ||
| 2. Sourgrass Drawings - Plans.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOR OFFICIAL USE ONLY
REQUEST FOR INFORMATION (RFI) OFFICIAL RESPONSES
127EAW21R0040 - Sourgrass Water System Rehabilitation Project
RFI responses will be responded to as necessary in amendment format which will be posted to the solicitation via beta.SAM.gov
Telephone requests for information will not be accepted or returned.
RFI #1 – I know the RFI deadline is passed but I just discovered a possible typo in the technical specification, Page 07160-56 which substantially conflicts with SikaTop Seal-107 manufacturer data. The specification indicates "400 sq. ft/gal. = 40 mils" and the manufacturer data indicates "40 ft.2/gal. = 40 mils".
USFS Response – SikaTop Seal 107© will be spray applied to the tank interior floor and walls.
Application thickness will be a minimum of 40 mils per coat with a minimum of two (2) coats.
Theoretical thickness on smooth substrate: 40 sq. ft/gal. = 40 mils. See attached revised project specs.