This document is a Questions and Answers (Q&A) addendum for the Lolo National Forest T-150 Building Reconstruction project (solicitation #1240LU25R0018), scheduled for bid on 08/08/2025 at 11:00 am. The document provides clarifications on various technical aspects of the project, including lighting fixtures, fencing, building materials, and optional construction elements. Key details include: no liquidated damages will be applied, the project requires bonding but not Builder's Risk insurance, and it is a small business set-aside. The project involves reconstructing a building with optional elements such as fitness and restroom areas, and specific technical clarifications were made about lighting fixtures, downspout colors, and material specifications. Notable substitutions were approved for Drexel Metals roofing, Arcadia products, and C.H.I. coiling doors. The project will follow the Buy American Act requirements under FAR Clause 52.225-11, and no local building permits are required as the U.S. Forest Service will conduct their own inspections.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lolo National Forest T-150 Building Reconstruction, 1240LU25R0018
08/08/2025 11:00 am
Additional submitted questions:
1. Is there any liquidated damages? No liquidated damages in this contract.
2. A403/ detail 1 grid 9 shows mop sink, grid 8 shows drinking fountain. Are these part of Option 2? If option 2 is not accepted, where do they go? Fitness and Restroom Areas shall be installed only if “Option Item 2 – Fitness and Restroom Areas” is selected. All infrastructure for option 2 is base bid. The mop sink and drinking fountain fixtures are associated with Option 2. Note: Option item numbering will be clarified in a future amendment.
3. A701 finish schedule calls out full size FRP. A403/ details 2-13 calls for 5’ FRP. Which is correct? Full size FRP is not required. See interior elevations on sheet A403 for layout and dimensions of FRP panels.
4. C101 calls for fence to remain / reuse. Correct
5. C106A calls for new fence and gates. Correct
6. C106 calls for new fence and Asphalt Correct
7. C108 has new fence details Correct
8. A011 Protect existing / Remove and relocate Correct see civil drawings
9. A101 / 1 Is new fence part of Option 1 or is it base bid? See dash line, and Civil drawings - Base bid
10. US Forestry T150 #1240LU25R0018, will this project need local building permits or will Forestry perform their on inspections? No local building permits required.
11. I am a local (Butte MT) manufacturer representative for several commercial building product lines. One of these is Drexel Metals a division of Carlisle Construction Materials. Drexel is a premier manufacturer of metal roofing and wall panels. I have had several qualified contractors reach out to me about this project expressing interest in using Drexel. I would like to formally request Drexel be added as an approved equal per addendum. Confirmed acceptable. The proposed metal roof panel product substitution will be added as a note into the applicable specifications section and then included in a future amendment.
12. Is there a Builders Risk required for Forestry T150 #1240LU25R0018? Builders Risk is not a requirement, bonding is required.
13. What the series of RLM Lighting is specified on fixtures E1E and E3 by TMS Lighting?
This is on E004. See responses below, 18 and 19.
14. Also, can you please verify if this project needs to meet BAA requirements? FAR Clause 52.225-11 Buy American Act-Construction Materials under Trade Agreements (NOV 2023) is included in this solicitation and impending contract.
15. I am looking at the ICT portion of this bid and have an RFI:
The legend and specs include security cameras, but I don't see any on the plans on the exchange. Is there another set of plans that includes cameras?
There are no cameras in this scope, just the infrastructure shown for future installation. Spec section 28 2300 is removed.
Installation of camera pathways shall be considered under option 1.
Bid items 27/28 will be added to SOI in a future amendment.
16. Who is responsible for the ACM panel in detail 4 of sheet A510? Is there an ACM panel spec that I am missing? ACM Panel not required - 1/8" alum plate with bend ends acceptable for infill panels. Color to match storefront.
17. Detail 1 on Sheet A510 shows SF3. I noticed that the jambs are drawn continuously.
I believe those jambs should not continue on past the head of each storefront bay.
We will provide pricing for three separate storefront openings per, with detail 4.
Correct, sections of storefront are not continuous at elevations see updated transition detail at jambs. These will be shown in a future the amendment.
Please see below regarding the lighting fixtures specified on this project:
18. Type E1E – Specified as TMS Lighting 0-19W-30K-120-W/M-XX. Fixture schedule description is 16” diameter RLM light ceiling mount at soffit but mounting is specified as surface wall mount. The attached specification sheet indicates that this is a wall mount fixture. I must confirm whether the mounting is ceiling mount rather than wall mount as that would require a custom mounting. If the attached spec sheet is the correct series, the catalog number should be prefaced with “4W.”
E1E fixtures are to be wall mounted, see elevations and plan drawings. Please use a wall type fixture for mounting (no custom mounting required). Updated cut sheet https://tmslighting.com/farm-light.html#wdetails for bidding 10W-O-15LED-30K-
120-WM-XX-
19. Types E3/E3E – Specified as TMS Lighting 0-16-19LED-C01-30K-120-XX. Fixture schedule description is 16” diameter RLM light surface mount at soffit. The attached specification sheet indicates that this is a ceiling pendant mount fixture. I must confirm whether the mounting is ceiling surface mount at the soffit or ceiling pendant mount as a ceiling mount would require a custom mounting. It is entirely possible that the specified 1” stem mount is interpreted as surface mount. If that is the case, no further clarification is need other than prefacing the catalog number with “NAU” per the attached spec sheet. Please see drawings for additional https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Ftmslighting.com%2Ffarm-light.html%23wdetails&data=05%7C02%7Ctanner.grimstad%40usda.gov%7Cb01429c826ab45ebaf8b08ddd0693963%7Ced5b36e701ee4ebc867ee03cfa0d4697%7C1%7C0%7C638895872719461777%7CUnknown%7CTWFpbGZsb3d8eyJFbXB0eU1hcGkiOnRydWUsIlYiOiIwLjAuMDAwMCIsIlAiOiJXaW4zMiIsIkFOIjoiTWFpbCIsIldUIjoyfQ%3D%3D%7C0%7C%7C%7C&sdata=0sI2NFmg7mR5lq3U2EhgG8n%2Bf%2FulFhbKr%2FpxLwkjyT0%3D&reserved=0 references of the required mounting. These fixtures in those locations are intended with stem mount at soffit.
20. Types H1/H1E – Specified as Lithonia XIB-L24-30000LM-AVCL-MVOLT-GZ10-40K- 90CRI-UPL. The XIB high bay is a wet location high bay which seems unusual for mezzanine mounting. I would like to confirm whether this fixture really needs to be wet location listed. The exits mounted in the same area are not wet location, so that is another reason for my question. Wet location type is not required. Please use fixture IBE Non-Wet location High Bay.
21. Bid Option #2 vs. Bid Option #3 – Section 01 2300 lists Option Item No. 2 as Fitness and Restroom Areas (Rooms 104 – 108. Option Item No. 3 is Interior Fence Partitions. Note #8 on Sheet E103 states “shaded area is to be bid as Option Item
3. For Base Bid, simply continue the pattern of Type F1 luminaires from Storage Area 103 throughout this area.” From this description, I believe this is Option 2 rather than Option 3. Please clarify this for bidding purposes. Restrooms are option 2 so electrical notes are correct in designation of #2. The revised option numbering will be shown in a future amendment.
22. I'm reaching out to see if you know the color for the downspout adapter? Final finish colors are selected once physical samples of options are provided during submittal process. Design intent is to attempt to closely match the downspout and roof material color – METAL SALES - Old Zinc Grey (W29) is the reference. Note...but until final roofing color is selected a final color can not be selected to match.
23. Specification Section 105123 Lockers is included in the specifications. No lockers appear to be indicated in the plans. Is this specification required for the project?
No lockers in the project.
24. Specification Section 113013 Residential Appliances is included in the specifications. Sheet A110 indicates that these are to be provided and installed by Owner. Is the specification strictly for reference? Correct, this specification is only for reference.
25. Specification Section 133419 Metal Building Systems is included in the specifications. This appears to be a structural steel building and specification for all components of the building are included elsewhere. Should this Specification 133419 be deleted? Yes, division 13 should be deleted. In the near future a drawing amendment will be issued showing the updated option numbers on drawings and specifications.
26. Sheet A003; Ceiling Assemblies C1; States ‘(SSD) See Structural Drawings for sizes and spacing.’ Assembly also indicates 600S162-54 @ 16” OC. Structural plans do not contain these elements. Should we follow the 600S152-54 @ 16” OC? Yes, the 16” O.C. is a MINIMUM requirement.
27. Sheet A120; Reflected Ceiling Plan; Level 1 RCP; Lower right hand side: Calls for “Caged Ceiling 12’ AFF. See Structural Drawings (SSD).” Structural plans do indicate any of these elements. Please clarify for bidding purposes. Correct, this is not a structural condition. The intent is to use the same wire cage partition manufacturers system for the ceiling as the walls. Verify with cage partition manufacturer the shown span and area. Utilize their approved system for caging the ceiling secure.
28. Can you confirm this is a small business set-aside project? Yes
29. Can we get a copy of the site visit sign in sheet? This sign-in sheet was posted
8/4/25 on the solicitation link on SAM.gov.
30. Can you provide the existing building plans as .pdf files? SEE EXISTING T150
INSPECTION REPORT.
31. Can you clarify the Option Item numbering? There seems to be various plan sheets showing different numberings. For instance, Sheet A110 shows the Fitness / Restroom area as Option 3. Sheet A120 shows the ceiling clouds as Option 6.
Revised option numbering will be addressed in a future amendment.
32. Civil plans do not call for repair of existing lawn areas north of the building. Is this to be part of our scope? Is this area irrigated? Any sod removed for trenching will need to be replaced as well as irrigation lines and sprinkler heads prior to substantial completion. Any sod that is damaged for construction and is not included in the trench limits will need to be replaced prior to substantial completion.
33. 1/A101 calls out “landscaping gravel” north and east of the building, and “landscaping area” west of the building. Is all of this meant to be landscaping gravel as shown in 2/C107? Yes
34. Demolition note 1 on C101 calls out exploratory excavation for a potential water line. Are we to include only the exploratory excavation in our pricing? Or are we to assume there is a water line and include pricing for removing it? SEE DEMOLITION
NOTE 1 ON C101 FOR CLARIFICATION.
35. C102 has a 1”=30’ scale. Should this be 1” = 20’? Yes, the overall view on sheet C102 is at a 1”=20’ scale, the scale bar in the upper right hand corner of the page is incorrect.
36. Can you confirm if abatement is part of our scope? Specification 024100, 1.01A notes “excluding of hazardous materials”. Abatement is the responsibility of the contractor.
37. Can you clarify what work is being covered under specification 133419? It looks like the structure steel and framing are all under Division 5 specs. Division 13 is being removed in a future amendment.
38. There is a specification for lockers (105123), but I haven’t located any on the plans. Can you clarify where these occur? No lockers in project, locker specifications will be removed in future amended drawings.
39. Can you clarify the height of the Option 4 caged partition? Will be option 3 in future amended drawings, but height = 12’-0”
40. A601 includes a Type W wire cage door. I don’t see this occurring on the plan or in the schedule. Does this exist? CLARIFICATION: TYPE W DOOR NOT
REQUIRED. NO DOORS IN DOOR SCHEDULE ARE TYPE W.
41. A120 refers to structural plans for the caged ceiling. Can you clarify where this is on structural plans? CLARIFICATION, this is not a structural condition. The intent is to use the same wire cage partition manufacturers system for the ceiling as the walls. Verify with cage partition manufacturer the shown span and area. Utilize their approved system for caging the ceiling secure.
42. Can you provide a size for door 102? THIS SIZE WILL DEPEND ON MFR
CAPABILITIES. OUR REQUESTED SIZE IS 6’-0” W X 7’-0” H. PLEASE PLAN FOR
CAGED PARTITION TO ALLOW SLIDING DOOR TO MOVE FREELY PAST T150
COLUMN @ INTERSECTION OF GRIDS 10 & D.
43. The Accessories Legend on A403 show Baby Changing Stations but it is not called out in the spec. Are these owner furnished or do you have a basis of design? No changing stations required see sheet A403.
44. There are Shower Benches shown on the plans but it is not included in the spec. Is this included in the Shower Enclosure or do you have a basis of design? No accessories spec, these are built-ins.
45. Are the Shower Grab Bars included in the Shower Enclosure Bid or should these be included in the Toilet Accessories Bid? Grab bars required for showers.
46. I am not seeing Lockers on the plans. Can you please advise? No lockers required, locker specifications will be removed in future amended drawings.
47. I've noticed on the exterior elevations that there are two different shaded areas stating "insulated wall panels" (specifically elevation #1 & #4) , which contradicts the materials legend. May I please get clarification on this? The elevations had shading turned on and that made it hard to tell what the material was in shadow.
The shading was turned off and a revised sheet A201 will be issued in future amended drawings.
Please all see attachments for additional clarifications:
1. Arcadia substitution request (approved). Will be included in the future amended specifications.
2. Drexel substitution request (approved). Will be included in the future amended specifications.
3. C.H.I. coiling door substitution request (approved). Will be included in the future amended specifications.
4. Light fixture clarification (farm light). Attachment included below.
5. E3 cut sheet. Attachment included below.
6. Piedmont Brochure WITH CHIPS. Attachment included below.
FORTETM PENDANT
QUANTITY:
TYPE:
PROJECT:
APPLICATION • PENDANT MOUNT
• INDOOR OR OUTDOOR RATED
APPLICATION • PENDANT MOUNT
• INDOOR OR OUTDOOR RATED
PN: FOR
FINISHES • AVAILABLE IN SEVERAL TMS SPECIALTY, AND
POWDER COATED FINISHES
• CUSTOM RAL FINISHES AVAILABLE
FINISHES • AVAILABLE IN SEVERAL TMS SPECIALTY, AND
POWDER COATED FINISHES
• CUSTOM RAL FINISHES AVAILABLE
DIMMING • 0 - 10V STANDARD DIMMINGDIMMING • 0 - 10V STANDARD DIMMING
WEIGHT • 4.6 LBS MAXIMUM WEIGHT • 4.6 LBS MAXIMUM
ILLUMINATION • DIRECT
• LED 90CRI
• 995 - 1,887 LUMENS
ILLUMINATION • DIRECT
• LED 90CRI
• 995 - 1,887 LUMENS
ELECTRICAL • 120V, 277V AND 347V
• 10kA SURGE SUPRESSION STANDARD
ELECTRICAL • 120V, 277V AND 347V
• 10kA SURGE SUPRESSION STANDARD DIFFUSERS • CLEAR OR FROSTED, TEMPERED GLASS GLOBEDIFFUSERS • CLEAR OR FROSTED, TEMPERED GLASS GLOBE
MOUNTING • 120” (305CM) BLACK OR WHITE DROP CORD
W/ AIRCRAFT CABLE (OPTIONAL)
• 1“ TO 60” (2.5CM TO 152CM) STEM MOUNT
MOUNTING • 120” (305CM) BLACK OR WHITE DROP CORD
W/ AIRCRAFT CABLE (OPTIONAL)
• 1“ TO 60” (2.5CM TO 152CM) STEM MOUNT
CONSTRUCTION • ALUMINUM, BRUSHED COPPER OR STEELCONSTRUCTION • ALUMINUM, BRUSHED COPPER OR STEEL
DIMENSION • 12”, 14” 16“ (31CM, 36CM, 41CM)DIMENSION • 12”, 14” 16“ (31CM, 36CM, 41CM)
DIRECT
100W
100IN
15W
1342 1108
15LED
17W
17LED
19W
19LED
FORTETM PENDANT
QUANTITY:
TYPE:
PROJECT:
FOR
120V
VOLTAGE
277V
347V
100IN
100W 100W15W
995 1109
15LED 100IN
15W
1144 1109
15LED
17W
17LED
19W
19LEDILLUMINATION1
LED (W)
LUMENS
3.
CRD C01 C06 C12 C18 C24 C36 C48 C60
MOUNTING
4.
12”DIA. (31CM)
14”DIA. (36CM)
16”DIA. (41CM)
DIAMETER
2.
1 8765 12 1311109432
OUTDOOR
O
APPLICATION
1.
INDOOR
I
NOTE: SOME OPTIONS MAY NOT BE COMPATIBLE WITH OTHERS. ALL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. CONTACT TMS LIGHTING FOR UPDATED SPECIFICATIONS.
NONE
12” (31CM) WIRED GUARD
W12
14” (36CM) WIRED GUARD
W14
16” (41CM) WIRED GUARD
W1613.
LED DIMMING (0 - 10V, CURRENT - SINKING)
DIML
NONE
DIMMING
10.
FROSTED
GLOBE
G2
CLEAR, ELONGATED
GLOBE WITH CAST GUARD
G11
NONE
GLOBE/
LENS
9.
CLEAR, ELONGATED
GLOBE
G1
CEILING SLOPE ADAPTER
FOR STEM MOUNT (30°)
BL
AIRCRAFT CABLE
FOR DROP CORDS
ACC
NONE
MOUNTING5
ACCESSORIES
WIRE GUARD
12.
INTEGRAL
EM
NONE
REMOTE
EMR
REMOTE COLD PACK
EMCR
INTEGRAL COLD PACK
EMC
EMERGENCY4
11.
2. GLOBES AND EMERGENCY ARE NOT AVAILABLE WITH THE 17W LED PAR 38 LAMPS
4. 10W AT 90 MINUTES. EMERGENCY OPTION IS ONLY AVAILABLE IN 120 - 277V SYSTEMS
3. A CLEAR COAT IS APPLIED TO COPPER. PATINA WILL FORM OVER TIME
5. MAY REQUIRE TO COMPLY WITH LOCAL SEISMIC/EARTHQUAKE CODE
1. 12” IS ONLY AVAILABLE FOR 100IN AND 15LED
120”(305CM)
DROP CORD
1”(2.5CM)
STEM MOUNT
6”(15CM)
STEM MOUNT
12”(31CM)
STEM MOUNT
18”(46CM)
STEM MOUNT
24”(61CM)
STEM MOUNT
36”(91CM)
STEM MOUNT
48”(122CM)
STEM MOUNT
60”(152CM)
STEM MOUNT
35K
40K
NONE
LED CCT
6.
30K
BLACK DROP CORD
BC
NONE
CORD
5.
WHITE DROP CORD
WC
FINISH3
8.
ADDITIONAL AND PREMIUM FINISHES
AVAILABLE. SEE FINISHES CHART MATTE
WHITE
F04
GLOSS
WHITE
F05
MATTE
BLACK
F15
GLOSS
BLACK
F16
PEWTER
F09
SILVER
METALLIC
F31
SATIN
ALUMINUM
F18
DROP CORD MOUNT STEM MOUNT
FOR - 12”
3.4LB
FOR - 16”
4.6LB
FOR - 14”
4LB
6.25” (15.8CM)
ø12”DIA (30CM) ø14”DIA (35CM) ø16”DIA (40.8CM)
7.18” (18CM) 8” (20CM)
3”(8CM)
REMOTE DRIVER ENCLOSURE REMOTE DRIVER ENCLOSURE
3”(8CM) 3”(8CM)
H
DIADIA
ADJUSTABLE DROP CORD
120”(305CM) MAX.
INCLUDED
H
AIRCRAFT CABLE
120”(305CM)
H
DIA
STEM MOUNT
60”(152CM) MAX.
SPECIFY LENGTH
REMOTE DRIVER ENCLOSURE
DROP CORD MOUNT
W/AIRCRAFT CABLE
POWER CORD
NOTE: THIS FIXTURE CAN BE CUSTOMIZE. DIMENSION, LAMP TYPES, ENCLOSURE, AND COLOR CAN BE MODIFIED TO SUIT YOUR LIGHTING AND ARCHITECTURAL REQUIREMENTS. CONTACT YOUR LOCAL REPRESENTATIVE FOR MORE DETAILS: https://tmslighting.com/sales-agents.html
CUSTOM
PN
FOR
100INC
15LED
FORTETM PENDANT
LUMINAIRE LUMENS 995
TOTAL LUMINAIRE EFFICIENCY 58%
LUMINAIRE EFFICACY RATING 10
TOTAL LUMINAIRE WATTS 100
LUMINAIRE LUMENS 1887
TOTAL LUMINAIRE EFFICIENCY NA
LUMINAIRE EFFICACY RATING 87
TOTAL LUMINAIRE WATTS 22
WATTAGELUMENSSIZE (DIA) ILLUMINATION
100INC
IES INDOOR REPORT
PHOTOMETRIC FILENAME : FOR 16 19LED.IES
POLAR GRAPH
IES INDOOR REPORT
PHOTOMETRIC FILENAME : FOR 12 100IN.IES
POLAR GRAPH
DIRECT
100INC 100
15LED
15LED
19LED
19LED
MAXIMUM CANDELA = 309.726 LOCATED AT HORIZONTAL ANGLE = 90, VERTICAL ANGLE = 5
# 1 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (90 - 270)
# 2 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (0 - 180)
MAXIMUM CANDELA = 51353.46 LOCATED AT HORIZONTAL ANGLE = 0, VERTICAL ANGLE = 0
# 1 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (90 - 270)
# 2 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (0 - 180)
80 1300
DISPLAYED FINISHES DIFFER BETWEEN SCREENS AS WELL AS PRINTERS AND MAY NOT ACCURATELY DEPICT COLOR.
FINISHES ARE SUBJECT TO AVAILABLILITY AND MAY NOT BE APPLICABLE TO ALL FIXTURES OR FOR QUICKSHIP.
NOTE: ALL FINISHES NOT MARKED WITH NOTATION (1) ARE APPLIED TO THE EXTERIOR ONLY. THE INTERIOR WILL BE F05 GLOSS WHITE.
MATTE FINISHES AVAILABLE. CONSULT FACTORY.
F04
MATTE
WHITE
FINISHES
F09
PEWTER
F05
GLOSS
WHITE
F15
MATTE
BLACK
F16
GLOSS
BLACK
F311
SILVER
METALLIC
F41
ELECTRIC
PURPLE
F18
SATIN
ALUMINUM
F40
BUBBLE
PINK
F10
FIRE
RED
F08
MIDNIGHT
BLUE
F45
COPPER
METALLIC
F39
AQUA
BLUE
F13
FOREST
GREEN
F38
MEADOW
GREEN
F06
CLAY
BROWN
F14
SUNSHINE
YELLOW
F11
CITRUS
ORANGE
F281
DARK
CHAMPAGNE
F221
HARVEST
GOLD
F331
PYRITE
BRONZE
F261
MELTED
COPPER
F07
ZEUS
BROWN
F21
ARCH
BRONZE
F321
BRONZE
METALLIC
F251
MELTED
GOLD
F241
MELTED
PLATINUM
RAL
CUSTOM
(RAL #)
F441
FAUX
COPPER
F431
FAUX
GOLD
F421
FAUX
CHROME
PREMIUM FINISHES
PREMIUM MATERIALS
BR1 2
BRUSHED
ALUMINUM
AN1 2
ANODIZED
SS1 2
STAINLESS
STEEL
CO1 2
SOLID
COPPER
2: MATERIALS ARE CONSISTENT (INTERIOR & EXTERIOR). STEMS AND CANOPIES WILL BE F16 GLOSS BLACK.
1: FINISHES IS APPLIED TO THE INTERIOR AND EXTERIOR OF THE FIXTURE.
FARM LIGHTTM WALL
QUANTITY:
TYPE:
PROJECT:
APPLICATION • WALL MOUNT
• INDOOR OR OUTDOOR RATED
APPLICATION • WALL MOUNT
• INDOOR OR OUTDOOR RATED
PN: 10W
FINISHES • AVAILABLE ANODIZED, BRUSHED, AND IN SEVERAL TMS
POWDER COATED FINISHES
• CUSTOM RAL FINISHES AVAILABLE
FINISHES • AVAILABLE ANODIZED, BRUSHED, AND IN SEVERAL TMS
POWDER COATED FINISHES
• CUSTOM RAL FINISHES AVAILABLE
DIMMING • 0 - 10V STANDARD DIMMINGDIMMING • 0 - 10V STANDARD DIMMING
WEIGHT • 2.5 LBS MAXIMUMWEIGHT • 2.5 LBS MAXIMUM
ELECTRICAL • 120V, 277V AND 347V
• 10kA SURGE SUPRESSION STANDARD
ELECTRICAL • 120V, 277V AND 347V
• 10kA SURGE SUPRESSION STANDARD
DIFFUSERS • HIGH EFFICIENCY ACRYLICDIFFUSERS • HIGH EFFICIENCY ACRYLIC
MOUNTING • WALL, MOUNTED TO A 4”(10CM) J-BOXMOUNTING • WALL, MOUNTED TO A 4”(10CM) J-BOX
CONSTRUCTION • ALUMINUMCONSTRUCTION • ALUMINUM
DIRECT
DIMENSION • 12”DIA (30CM)DIMENSION • 12”DIA (30CM)
DRIVER • WALL MOUNT (INTEGRAL)
• REMOTE MOUNT (INDOOR OR OUTDOOR)
DRIVER • WALL MOUNT (INTEGRAL)
• REMOTE MOUNT (INDOOR OR OUTDOOR)
ILLUMINATION • DIRECT
• LED 90CRI
• INCANDESCENT MEDIUM BASE SOCKET
• 753 - 1602 LUMENS
ILLUMINATION • DIRECT
• LED 90CRI
• INCANDESCENT MEDIUM BASE SOCKET
• 753 - 1602 LUMENS
https://tmslighting.com/farm-light.html https://tmslighting.com/farm-light.html https://tmslighting.com/home.html
EMERGENCY2
QUANTITY:
TYPE:
PROJECT:
10W
NOTE: SOME OPTIONS MAY NOT BE COMPATIBLE WITH OTHERS. ALL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. CONTACT TMS LIGHTING FOR UPDATED SPECIFICATIONS.
INDOOR
I
OUTDOOR
O
APPLICATION
1.
FINISH1
6.
----8.
NONE INTEGRAL
EM
INTEGRAL
COLD PACK
EMC
REMOTE
EMR
REMOTE
COLD PACK
EMCR
NONE
DIMMING
7.
LED DIMMING (0 - 10V, CURRENT - SINKING)
DIML
120V
VOLTAGE
4.
277V
347V
150W
150IN
ILLUMINATION
LED (W)
2.
15W
2240LUMENS 1090
15LED
NONE
WALL MOUNT
(INTEGRAL)
WM
REMOTE INDOOR MOUNT
(NEMA 1)
N1
REMOTE OUTDOOR MOUNT
(NEMA 4)
N4
DRIVER
5.
1 8 9765432
WIRE
GUARD
----9.
NONE
W12
12”
WIRE GUARD
1. WALL PLATE OR DRIVER ENCLOSURE, CONDUIT, AND TOP CAP ARE ALWAYS IN “F18-SATIN ALUMINUM” FINISH. SEE FINISH CHART FOR REFLECTOR.
2. 10W AT 90 MINUTES. EMERGENCY OPTION IS ONLY AVAILABLE IN 120 - 277V SYSTEMS
4000K
40K
3000K
30K
NONE
LED CCT
3.
3500K
35K
BRUSHED
ALUMINUM
BR
ANODIZED
AN
FAUX
GOLD
F43
FAUX
COPPER
F44
COPPER
METALLIC
F45
CUSTOM
(SPECIFY RAL)
RAL
BUBBLE
PINK
F40
ELECTRIC
PURPLE
F41
FAUX
CHROME
F42
MELTED
GOLD
F25
MELTED
COPPER
F26
PYRITE
BRONZE
F33
DARK
CAMPAGNE
F28
BRONZE
METALLIC
F32
AQUA
BLUE
F39
MEADOW
GREEN
F38
ARCH.
BRONZE
F21
HARVEST
GOLD
F22
MELTED
PLATINUM
F24
CLAY
BROWN
F06
ZEUS
BROWN
F07
CITRUS
ORANGE
F11
MIDNIGHT
BLUE
F08
FIRE
RED
F10
SUNSHINE
YELLOW
F14
FOREST
GREEN
F13
MATTE
WHITE
F04
GLOSS
WHITE
F05
PEWTER
F09
MATTE
BLACK
F15
GLOSS
BLACK
F16
SATIN
ALUMINUM
F18
SILVER
METALLIC
F31 https://tmslighting.com/farm-light.html
10W
5.75”(15CM)
7.5”(19CM)
12”
(30.5CM)
3.36”
(8.5CM)
19.9(50.5CM)
INTEGRAL LED DRIVER
PROFILE
NOTE: THIS FIXTURE CAN BE CUSTOMIZE. DIMENSION, LAMP TYPES, ENCLOSURE, AND COLOR CAN BE MODIFIED TO SUIT YOUR LIGHTING AND ARCHITECTURAL REQUIREMENTS. CONTACT YOUR LOCAL REPRESENTATIVE FOR MORE DETAILS: https://tmslighting.com/sales-agents.html
CUSTOM
PN
10W
FARM LIGHTTM WALL
LUMINAIRE LUMENS 1090
TOTAL LUMINAIRE EFFICIENCY NA
LUMINAIRE EFFICACY RATING 64
TOTAL LUMINAIRE WATTS 17
LUMINAIRE LUMENS 2240
TOTAL LUMINAIRE EFFICIENCY 84%
LUMINAIRE EFFICACY RATING 15
TOTAL LUMINAIRE WATTS 150
WATTAGELUMENSILLUMINATION
15LED
150IN
MAXIMUM CANDELA = 1078.77 LOCATED AT HORIZONTAL ANGLE = 0, VERTICAL ANGLE = 0
# 1 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (90 - 270)
# 2 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (0 - 180)
# 3 - HORIZONTAL CONE THROUGH VERTICAL ANGLE (90)
MAXIMUM CANDELA = 613.755 LOCATED AT HORIZONTAL ANGLE = 45, VERTICAL ANGLE = 5
# 1 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (90 - 270)
# 2 - VERTICAL PLANE THROUGH HORIZONTAL ANGLES (0 - 180)
IES INDOOR REPORT
PHOTOMETRIC FILENAME : 10W 150IN.IES
POLAR GRAPH
IES INDOOR REPORT
PHOTOMETRIC FILENAME : 10W 15LED F05.IES
POLAR GRAPH
DIRECT
AN1 2
ANODIZED
F04
MATTE
WHITE
FINISHES
F09
PEWTER
F05
GLOSS
WHITE
F15
MATTE
BLACK
F16
GLOSS
BLACK
F311
SILVER
METALLIC
F41
ELECTRIC
PURPLE
F18
SATIN
ALUMINUM
F40
BUBBLE
PINK
F10
FIRE
RED
F08
MIDNIGHT
BLUE
F45
COPPER
METALLIC
F39
AQUA
BLUE
F13
FOREST
GREEN
F38
MEADOW
GREEN
F06
CLAY
BROWN
F14
SUNSHINE
YELLOW
F11
CITRUS
ORANGE
F281
DARK
CHAMPAGNE
F221
HARVEST
GOLD
F331
PYRITE
BRONZE
F261
MELTED
COPPER
F07
ZEUS
BROWN
F21
ARCH
BRONZE
F321
BRONZE
METALLIC
F251
MELTED
GOLD
F241
MELTED
PLATINUM
F441
FAUX
COPPER
F431
FAUX
GOLD
F421
FAUX
CHROME
RAL
CUSTOM
(RAL #)
PREMIUM FINISHES
PREMIUM MATERIALS
BR1 2
BRUSHED
ALUMINUM
DISPLAYED FINISHES DIFFER BETWEEN SCREENS AS WELL AS PRINTERS AND MAY NOT ACCURATELY DEPICT COLOR.
FINISHES ARE SUBJECT TO AVAILABLILITY AND MAY NOT BE APPLICABLE TO ALL FIXTURES OR FOR QUICKSHIP.
NOTE: ALL FINISHES NOT MARKED WITH NOTATION (1) ARE APPLIED TO THE EXTERIOR ONLY. THE INTERIOR WILL BE F05 GLOSS WHITE.
MATTE FINISHES AVAILABLE. CONSULT FACTORY.
2: MATERIALS ARE CONSISTENT (INTERIOR & EXTERIOR). STEMS AND CANOPIES WILL BE F16 GLOSS BLACK.
1: FINISHES IS APPLIED TO THE INTERIOR AND EXTERIOR OF THE FIXTURE.
FARM LIGHTTM WALL
Lolo National Forest
| NAME: |
| TYPE: |
| QUANTITY: |
| APPLICATION: [ ] |
| DIAMETER: [ ] |
| ILLUMINATION: [ ] |
| MOUNTING: [ ] |
| CORD: [ ] |
| LEDCCT: [ ] |
| VOLTAGE: [ ] |
| FINISH: [ ] |
| GLOBE/LENS: [ ] |
| DIMMING: [ ] |
| EMERGENCY: [ ] |
| MOUNTING ACCESSORIES: [ ] |
| WIREGUARD: [ ] |
File details come from the government source that posted it. Updated .